This is a Standard Form 30 Amendment to a federal solicitation (RFQ) for RTAA Chiller replacement services at the Martinsburg VA Medical Center.
The solicitation number is 36C24526Q0549, issued by the Department of Veterans Affairs VISN 5 Contract Satellite Office in Baltimore, Maryland, and administered by Martinsburg VA Medical Center in Martinsburg, West Virginia. This modification (0001) extends the RFQ due date to June 19, 2026, at 9:00 AM EDT and adjusts the estimated period of performance to June 30, 2026 through June 29, 2027. The contract involves the removal and replacement of an existing Trane RTAA Chiller with a new Trane RTAA Chiller or equivalent. The principal NAICS code is 238220 (Plumbing, Heating, and Air-Conditioning Contractors), and the product/service code is J041 (Maintenance, Repair, and Rebuilding of Equipment—Refrigeration, Air Conditioning, and Air Circulating Equipment). The price/cost schedule shows one line item for 1 EA with blank unit price and amount fields to be completed by offerors.
The amendment includes vendor questions and answers addressing nine key clarifications: (1) the existing 400A disconnect must be replaced; (2) barrel heater and heat trace circuits must connect to the first-floor emergency panel; (3) Johnson Controls contact information for BAS coordination; (4) all existing isolation valves must be replaced with butterfly valves, all chilled water piping must be replaced back to existing isolation valves, and an additional field-installed flow switch is required; (5) redundant heat trace should have one cable operational and one installed as a spare; (6) BACnet card requirements per specifications; (7) heat trace wattage depends on chiller brand selection; (8) sequence of operation documentation is required for commissioning; and (9) heat trace installation must include an actual thermostat rather than plug-in setup.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24526Q0549 0001_1.docx | DOCX document | |
| S02-36C24526Q0549-RTAA Chiller Replacement-Martinsburg VAMC.pdf | ||
| Martinsburg VA Map Site Map.pdf | ||
| 36C24526Q0549_1.docx | DOCX document | |
| RTAA-SVX01A-EN.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE 7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO. 1. CONTRACT ID CODE
FACILITY CODE CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30 PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print) (Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
1 5
613-26-2-601-0214
None
19ACQ
Department of Veterans Affairs
VISN 5 Contract Satellite office
510 Butler Avenue, Building 306 A
Baltimore MD 21201
Trever Turcotte
Trever.Turcotte@va.gov
19ACQ
Department of Veterans Affairs
Martinsburg, VA Medical Center
510 Butler Avenue, Building 500
Martinsburg WV 25405
To all Offerors/Bidders
36C24526Q0549
X
X X
** HOUR & DATE for Receipt of Offers is EXTENDED to: 06-19-2026 9:00 AM EDT
See CONTINUATION Page
X 1
Modification 0001 of Solicitation 36C24526Q0549 RTAA Chiller Replacement-Martinsburg VA Medical Center is to extend
Solicitation due date, adjust estimated period of performance, and to answer questions submitted by Vendors.
RFQ due date is now 06/19/2026 at 9:00 am EDT (See RFQ for submittal details)
Estimated Period of Performance: 06/30/2026, to 06/29/2027
See Vendor Questions and Answers (Pg. 3)
Trever Turcotte
Contracting Officer
VA-VHA-RPOE-2023-0077
CONTINUATION PAGE
A.1 PRICE/COST SCHEDULE
ITEM INFORMATION
ITEM
NUMBER
DESCRIPTION OF
SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
1.00 EA __________________ __________________
Remove and Replace Existing Trane RTAA Chiller with a New Trane RTAA Chiller or Equivalent Contract Period: Base POP Begin: 06-30-2026 POP End: 06-29-2027 PRINCIPAL NAICS CODE: 238220 - Plumbing, Heating, and Air- Conditioning Contractors PRODUCT/SERVICE CODE: J041 - Maintenance, Repair, and Rebuilding of Equipment - Refrigeration, Air Conditioning, and Air Circulating Equipment
GRAND TOTAL __________________
A.2 VENDOR QUESTIONS AND ANSWERS
Solicitation 36C24526Q0549- RTAA Chiller Replacement-Martinsburg VA Medical Center
Questions & Answers.
1. The existing 400A disconnect appears to be in poor condition and may not be suitable for reuse. Can the Contractor install a NEMA 3R junction box for splicing and terminate directly to the new chiller, since the new chiller includes an integral service disconnect? Or does the Government want the existing disconnect replaced as part of this project? Please clarify.
• The Government would like the existing disconnect replaced under this requirement.
2. Please confirm whether the new barrel heater dedicated circuit and the new heat trace circuits are required to be fed from the emergency panel located on the first floor, or if an alternate power source is acceptable. Please advise on the intended power source for these circuits.
• Both circuits need to be run to an emergency panel in case the medical center loses power and needs to go to generator power. The emergency panel located on the first floor will be used.
3. During the site visit, it was mentioned that Johnson Controls is the preferred BAS contractor for this facility. Can the Government please provide the contact information for the Johnson Controls account representative or facility point of contact so that we may coordinate and obtain any necessary pricing related to the
BAS scope of work?
• JCI Contact Information: Seamus Corcoran
Account Executive
Johnson Controls
(443) 497-1803
4. The specifications indicate that the Contractor shall install new chilled water piping, including fittings, valves, supports, and a new flow switch.
Please clarify the following:
• Is the Contractor required to replace the existing isolation valves associated with the chiller installation, or may the existing valves remain in service if found to be operational? Contractor will be required to replace the existing isolation valves associated with the chiller installation.
• Does the Government intend for all chilled water piping to be replaced back to the existing isolation valves, or only the piping necessary to connect the new chiller? The chilled water pipping needs to be replaced back to the existing isolation valves.
• If valve replacement is required, does the Government prefer butterfly valves or gate valves? Replaced with Butterfly Valve
• The specified chiller is provided with an integral factory-installed flow switch. Please confirm whether an additional field-installed flow switch is required. Additional flow switch will need to be installed in the chiller piping.
5. The specifications require the installation of a new heat trace system with a redundant wire per pipe. Please clarify the Government's intent regarding the redundant heat trace requirement. Specifically, does this requirement mean that two heat trace cables are to be installed on each pipe, with one cable connected and operational and the second cable installed as a spare for future use in the event of failure? Alternatively, should both heat trace cables be connected and operational as part of a redundant heat tracing system? Please provide additional guidance on the intended configuration.
• The Government would like to have one cable connected and operational and the second cable to be installed as a spare for future use in the event of a failure
6. Is a BACnet card needed?
7. Heat Trace-What Wattage per foot is required?
• That will depend on what brand of Chiller will be used
8. Commissioning – will a sequence of operation be provided for commissioning agent, or will factory start up sheets satisfy?
• Sequence of Operation.
9. Can you tell us how you would like us to install the heat trace? Are you ok with the plug-in setup you have now moving forward or would you like an actual thermostat?
• Actual Thermostat.