Drawings _WV VAMC HUNTINGTON BRONCHOSCOPY ROOM EXPAND_COMBINED SET .pdf
PDF 23 MB Posted
- Solicitation number
- 36C24524B0019
About this file
This document is a set of drawings for the Construct Expansion of Pain and Bronchoscopy Room Project 581-23-111 at the VA Medical Center in Huntington, West Virginia. The related federal contract opportunity is Solicitation Number 36C24524B0019, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 5. The project involves constructing an expansion to the existing bronchoscopy room. The drawings provide detailed design specifications and layouts for the construction work. Key details include the project location, project number, and drawing titles covering various aspects of the construction, such as architectural, electrical, and mechanical plans. This document serves as part of the solicitation package to support the competitive bidding process for this federal contract opportunity.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24524B0019 0002.docx | DOCX document | |
| SPECS COMBINED.pdf | ||
| Huntington Bronchoscopy Revised_S2 Response.pdf | ||
| Site Visit IFB Bronch and Pain Room.pdf | ||
| 36C24524B0019 0001.docx | DOCX document | |
| WD P07 current.pdf | ||
| 36C24524B0019_1.docx | DOCX document | |
| VHA ICRA signed .pdf | ||
| Spec Combined 5 10 24 100CD _01 Revised.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Location
Issue Date
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
VAMC HUNTINGTON
Project Director
Revisions: Date:
VA FORM
08 -
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Stewart C. Cluck 717.850.2515
CONSTRUCTION
DOCUMENTS
600 North Hartley Street, Suite 152 York, PA 17404
1S
HOMCO Renaissance and
GPI-Renaissance JV 7510 Langport Ct.
Hanover, MD 21076
410-340-8284
5001 LOUISE DRIVE,
MECHANICSBURG PA 17055
T 717-691-1340
1 - REVIEW COMMENTS 05/10/2024
GI-000
COVER SHEET
JEGSCC03/20/2024
581-23-111EXPAND PAIN AND
BRONCHOSCOPY
PROCEDURE ROOM
VA MEDICAL CENTER HUNTINGTON WV
BUILDING 1S
HUNTINGTON, WEST VIRGINIA 25704
EXPAND PAIN AND BRONCHOSCOPY PROCEDURE ROOM
A/E CONTRACT NUMBER VA-36C 24519 D0021
CONTRACT NUMBER VA-36C 24519 D0021
PROJECT 581-23-111
VA WEST VIRGINIA HEALTH CARE SYSTEM
1540 SPRING VALLEY DRIVE, HUNTINGTON
WEST VIRGINIA
SECTION CALLOUT
EXTERIOR ELEVATION CALLOUT
INTERIOR ELEVATION CALLOUT
XX
ROOM NAME
ROOM NUMBER
DOOR TAG
REVISION DELTA
ELEVATION DESIGNATION
WALL / PARTITION TAG
COLUMN GRID DESIGNATION
LEVEL NAME
DATUM
SCALE
NAME
LEVEL
VIEW TITLE
WINDOW TAG
CENTERLINE
CLDETAIL CALLOUT
VIEW NUMBER
SHEET NUMBER
ROOM TAG
SYMBOL LEGEND
VIEW TITLE
SCALE: x/x" = x' - x"
A101
ROOM NAME
P###
A000
# VIEW NUMBER
SHEET NUMBER
A000
1 VIEW NUMBER
SHEET NUMBER
A000
1 VIEW NUMBER
SHEET NUMBER
ROUGH DIMENSION
FINISH DIMENSION
A101
XXXXXX
X' - X"
DEMOLITION KEYNOTE
D#
W#
AB ANCHOR BOLT(S), AUGER BORING
ACI AMERICAN CONCRETE INSTITUTE
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AJC ASPHALTIC CONCRETE
ALT ALTERNATE / ALTERNATING
APPROX APPROXIMATE(LY)
ARCH ARCHITECT(URAL)
ASSOC ASSOCIATED / ASSOCIATION
ASTM AMERICAN SOCIETY OF TESTING MATERIALS
ATC AUTOMATIC TEMPERATURE CONTROL
AWP ACOUSTICAL WALL PANEL
BC BOTTOM OF CURB
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
BKT BRACKET
BLDG BUILDING
BLVD BOULEVARD
BM BENCH MARK
BOB BOTTOM OF BEAM
BOF BOTTOM OF FOOTING
BOJ BOTTOM OF JOIST
BOS BOTTOM OF STEEL
BOTT BOTTOM
BRG BEARING
BSMT BASEMENT
BUR BUILT-UP ROOF
CART CARTWAY
CCT CUBICLE CURTAIN TRACK
CF CUBIC (FOOT) FEET
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CI CAST IRON
CIP CAST IRON PIPE
CJ CONTRACTION / CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEARANCE / CLEAR
CM CORRUGATED METAL
CMP CORRUGATED METAL PIPE ARCH
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEANOUT
COB CENTER OF BEAM
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONST CONSTRUCTION
CONT CONTINUOUS
CORRG CORRUGATED
CPP CORRUGATED PLASTIC PIPE
CPT CARPET
CR CLASSROOM
CUH CABINET UNIT HEATER
DBL DOUBLE
DH DRILL HOLE
DIAG DIAGONAL
DIFF DIFFUSER
DIM DIMENSION
DP DAMPROOF(ING)
DS DOWN SPOUT
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ENGR ENGINEER(ING)
EOF EDGE OF FLOOR
EOS EDGE OF SLAB
EQUIP EQUIPMENT
EST ESTIMATE
EW EACH WAY
EX EXISTING
FBD FIBER BOARD
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFE FINISHED FLOOR ELEVATION
FIN FINISH(ED)
FIX FIXTURE
FM FACTORY MANUAL
FP FULL PENETRATION WELD
FPR FIRE PROOF(ING)
FTG FOOTING
FURN FURNITURE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GFI GROUND FAULT INTERRUPTER
GLBLK GLAZED BLOCK
GPM GALLONS PER MINUTE
GYM GYMNASIUM
GWB GYPSUM WALLBOARD
H/ V HEATING AND VENTILATING
HB HOSE BIB
HC HEATING CONTRACTOR
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
HVAC HEATING/ VENTILATING/ AIR CONDITIONING
HW HOT WATER
HYD HYDRANT
IBC INTERNATIONAL BUILDING CODE
INCL INCLUDE/ INCLUSIVE
INSUL INSULATE/ INSULATION
JAN JANITOR
KSI KIPS PER SQUARE INCH
LAB LABORATORY
LAV LAVATORY
LB(S) POUND(S)
LDY LAUNDRY
LF LINEAL FEET
LH LEFT HAND
LHR LEFT HAND REVERSE
LIB LIBRARY
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MAS MASONRY
MAX MAXIMUM
MB MAILBOX
MC MECHANICAL CONTRACTOR
MECH MECHANIC(AL)
MED MEDICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MFD MANUFACTURED
MFR MANUFACTURE(R)
MIN MINIMUM
MISC MISCELLANEOUS
MM MILLIMETER
MO MASONRY OPENING
MTD MOUNTED
MTG MOUNTING
NA NOT APPLICABLE
NEC NATIONAL ELECTRIC CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
OC ON CENTER(S)
OPNG OPENING(S)
OPP OPPOSITE
PC PLUMBING CONTRACTOR
PCF POUNDS PER CUBIC FOOT
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLWD PLYWOOD
POLYISO POLYISOCYANURATE
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PTL PRESSURE TREATED LUMBER
PTD PAINTED
RA RETURN AIR
RC REINFORCED CONCRETE
RD ROOF DRAIN
REBAR REINFORCING BAR
REG REGISTER
REINF REINFORCED/REINFORCING
RH RIGHT HAND
RHR RIGHT HAND REVERSE
RL RAIN LEADER
RO ROUGH OPENING
RWC RAIN WATER CONDUCTOR
SA SUPPLY AIR
SECT SECTION(AL)
SJ SAW JOINT
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SP SOUNDPROOF
SPAND SPANDREL
SPECS SPECIFICATIONS
SPR SPRINKLER(ED)
SQ SQUARE
SF SQUARE FOOT/FEET
SI SQUARE INCH(ES)
SS STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STER STERILIZER
STOR STORAGE
STRUCT STRUCTURAL
SV SHEET VINYL
SW STORMWATER
T&B TOP AND BOTTOM
T&G TONGUE & GROOVE
TC TOP OF CURB
TEL TELEPHONE
TEMP TEMPERED
TG TOP OF GRATE
TH THICK/THICKNESS
THRU THROUGH
TOB TOP OF BEAM
TOF TOP OF FOOTING
TOJ TOP OF JOIST
TOS TOP OF STEEL
TW TOP OF WALL
TYP TYPICAL
UC UNDERCUT (DOORS)
UCC UNIFORM CONSTRUCTION CODE
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VOL VOLUME
VT VINYL TREAD
VWC VINYL WALL COVERING
WC WATER CLOSET
WCO WALL CLEAN OUT
WDW WINDOW
WGL WIRE GLASS
WM WOOD MOLDING
WP WEATHERPROOF
WP WORK POINT
WSL WATER SURFACE ELEVATION
WT WEIGHT
WWF WELDED WIRE FABRIC
ABBREVIATIONS
BRONCHOSCOPY
ROOM - BUILDING
1S - 3RD FLOOR -
ROOM 3B-147
C O
U R
A G
E D
R
IV
E
COURAGE DRIVE
HONOR HI ROAD
HERSHEL "WOODY" WILLIAMS
VA MEDICAL CENTER
Location
Issue Date
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
VAMC HUNTINGTON
Project Director
Revisions: Date:
VA FORM
08 -
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Stewart C. Cluck 717.850.2515
CONSTRUCTION
DOCUMENTS
600 North Hartley Street, Suite 152 York, PA 17404
1S
HOMCO Renaissance and
GPI-Renaissance JV 7510 Langport Ct.
Hanover, MD 21076
410-340-8284
5001 LOUISE DRIVE,
MECHANICSBURG PA 17055
T 717-691-1340
1 - REVIEW COMMENTS 05/10/2024
GI-001
GENERAL INFORMATION
JEGSCC03/20/2024
581-23-111EXPAND PAIN AND
BRONCHOSCOPY
PROCEDURE ROOM
PN
N
LOCATION MAP/IMAGE
SHEET LIST
SHEET NAME
GENERAL
GI-000 COVER SHEET
GI-001 GENERAL INFORMATION
ARCHITECTURAL
A-001 ICRA PLAN
A-101 DEMO / NEW WORK PLANS
A-501 DETAILS
STRUCTURAL
S-001 OVERHEAD EQUIPMENT SUPPORT
MECHANICAL
M-001 MECHANICAL LEGEND, NOTES, & ABBREVIATIONS
M-101 THIRD FLOOR MECHANICAL DEMOLITION & NEW WORK PLANS
M-201 MECHANICAL DETAILS AND SCHEDULES
PLUMBING
FA/PL-001 PLUMBING LEGEND, NOTES, SCHEDULES & ABBREVIATIONS
PL-101 THIRD FLOOR PLUMBING DEMOLITION & NEW WORK PLANS
PL-201 PLUMBING DETAILS
ELECTRICAL
E-001 ELECTRICAL SYMBOLS & ABBREVIATIONS
E-002 ELECTRICAL DEMOLITION AND NEW WORK NOTES
E-101 POWER AND LIGHTING NEW WORK PLANS
E-601 ELECTRICAL PANEL SCHEDULES
ED-101 POWER AND LIGHTING DEMOLITION PLANS
PN
N
LOCATION
BRONCHOSCOPY
ROOM
3B-147
3B-149 3B-165
3B-168
3B-169
3B-172
3B-146
AREA OF WORK
EXISTING GROUND FLOOR PLANEXISTING THIRD FLOOR PLAN
AREA OF WORK
WASTE PATH
WASTE PATH
Location
Issue Date
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
VAMC HUNTINGTON
Project Director
Revisions: Date:
VA FORM
08 -
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Stewart C. Cluck 717.850.2515
CONSTRUCTION
DOCUMENTS
600 North Hartley Street, Suite 152 York, PA 17404
1S
HOMCO Renaissance and
GPI-Renaissance JV 7510 Langport Ct.
Hanover, MD 21076
410-340-8284
5001 LOUISE DRIVE,
MECHANICSBURG PA 17055
T 717-691-1340
1 - REVIEW COMMENTS 05/10/2024
A-001
ICRA PLAN
JEGSCC03/20/2024
581-23-111EXPAND PAIN AND
BRONCHOSCOPY
PROCEDURE ROOM
SCALE: 1/8" = 1'-0"A-001
ICRA PLAN2
A-001
ENVIRONMENTAL WASTE PATH PLAN1
1 - DOORS TO BRONCHOSCOPY ROOM BEYOND
DOUBLE DOORS / SERVICE ELEVATORS ON RIGHT
2 - SERVICE ELEVATORS 3 - EXIT OUT OF ELEVATORS ON GROUND FLOOR,
MAKE A RIGHT
4 - LOOKING TO RIGHT AT AMBULANCE BAY 5 - LOOKING OUT AMBULANCE BAY AT DUMPSTER LOCATION 6 - DUMPSTER LOCATION
THIRD FLOOR LEVEL THIRD FLOOR LEVEL GROUND FLOOR LEVEL GROUND FLOOR LEVEL GROUND FLOOR LEVEL
BRONCHOSCOPY
ROOM
3B-147
3B-149 3B-165
3B-169
3B-172
3B-146
E1
A
O R
T A
B L E
D1
C-ARM *
C-ARM
MONITOR *
A-101
CORNER GUARDS
P1
P1
P1
P1
P1
P1
P2
P1
P1
5' - 0"
* EQUIPMENT PROVIDED BY VA
EPOXY FLOORING
PARTITION TYPES
EXISTING WALL
P1
5/8" GYPSUM BOARD WITH LEAD-LINED
(1/32" LEAD SHEET)
3 5/8" METAL STUD
P2
HYGIENIC VINYL
WALL COVERING
HYGIENIC VINYL WALL COVERING
5/8" TYPE 'X' GYPSUM BOARD
5/8" GYPSUM BOARD WITH LEAD-LINED
(1/32" LEAD SHEET)
BRONCHOSCOPY
ROOM
3B-147
3B-146
3B-149 3B-165
3B-169
3B-172
E1
A
7' - 11 3/4"A.F.F.
2' - 4"
C E
IL
IN
G T
R A
C K
ALIGN
ACCESS HATCH
( 16" X 16" MIN )
ACCESS HATCH
( 16" X 16" MIN )
D6
REFER TO MEP DRAWINGS FOR DEMOLITION
OF ALL MEP EQUIPMENT
D5
E1
A
D4
D3
D3
D1
D2
3B-147 3B-169
3B-165
3B-172
3B-146
3B-149
3B-148
REMOVE EXISTING VCT TILE, RUBBER BASE AND ALL ASSOCIATED COMPONENTS. PATCH
AND REPAIR ADJACENT SURFACES AND PREPARE FOR NEW WORK
REMOVE EXISTING VINYL SHEET FLOORING AND ALL ASSOCIATED COMPONENTS. PATCH
AND REPAIR ADJACENT SURFACES AND PREPARE FOR NEW WORK
REMOVE EXISTING DOOR AND FRAME. PATCH AND REPAIR ADJACENT SURFACES AND
PREPARE FOR NEW WORK.
REMOVE EXISTING ACT CEILING SYSTEM AND ALL ASSOCIATED HARDWARE.
PATCH AND PREPARE ADJACENT SURFACES FOR NEW WORK.
REMOVE EXISTING HARD CEILING SYSTEM AND ALL ASSOCIATED HARDWARE.
PATCH AND PREPARE ADJACENT SURFACES FOR NEW WORK.
REMOVE EXISTING WALL AND ALL ASSOCIATED COMPONENTS. CAP OFF PLUMBING
CONNECTIONS AND PREPARE ADJACENT SURFACES FOR NEW WORK.
D1
D2
D3
D4
D5
D6
HM-1
FINISH FLOOR
2"
2"
FN
FINISH FLOOR
6"6"
PANEL 1 PANEL 2
LITE PANEL
SUPPORT - TYP
KEYNOTE LEGEND
STAINLESS STEEL COUNTERTOP WITH INTEGRAL 4"
BACKSPLASH
STAINLESS STEEL DROP IN SINK
Location
Issue Date
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
VAMC HUNTINGTON
Project Director
Revisions: Date:
VA FORM
08 -
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Stewart C. Cluck 717.850.2515
CONSTRUCTION
DOCUMENTS
600 North Hartley Street, Suite 152 York, PA 17404
1S
HOMCO Renaissance and
GPI-Renaissance JV 7510 Langport Ct.
Hanover, MD 21076
410-340-8284
5001 LOUISE DRIVE,
MECHANICSBURG PA 17055
T 717-691-1340
1 - REVIEW COMMENTS 05/10/2024
A-101
DEMO / NEW WORK PLANS
JEGSCC03/20/2024
581-23-111EXPAND PAIN AND
BRONCHOSCOPY
PROCEDURE ROOM
DEMOLITION KEY NOTES
SCALE: 1/4" = 1'-0"A-101
PLAN - SHOWING EQUIPMENT2
FLOOR FINISH LEGEND
SCALE: 1/4" = 1'-0"A-101
REFLECTED CEILING PLAN3
SCALE: 1/4" = 1'-0"A-101
PLAN - DEMOLITION1
DOOR AND FRAME SCHEDULE
NUMBER
PANEL
THICKNESS
PANEL
FIRE RATING
FRAME HARDWARE
REMARKSWIDTH HEIGHT TYPE MATERIAL GLAZING TYPE MATERIAL SET
GROUND FLOOR
D1 5' - 4" 7' - 0" 1 3/4" WD X-RAY SHIELDED
WINDOW FRAME w/
X-RAY LEAD GLASS
1/2 HR -
SMOKE ONLY
HM1 HM 001 LEAD-LINED DOOR SYSTEM: PANEL 1: 46" PANEL 2:
18"
DOOR FRAME TYPES DOOR PANEL TYPES
ROOM FINISH SCHEDULE
ROOM FLOOR BASE
CEILING
FINISH
WALLS
REMARKSNUMBER NAME FINISH FINISH
NORTH EAST SOUTH WEST
FINISH FINISH FINISH FINISH
GROUND FLOOR
3B-147 BRONCHOSCOPY ROOM EPOXY
COATING
EPOXY WRAP
UP
GYP PNT /
LEAD-LINED
PNT /
LEAD-LINED
PNT /
LEAD-LINED
PNT /
LEAD-LINED
PROVIDE CORNER GUARDS
WHERE INDICATED ON PLANS
SCALE: 1/2" = 1'-0"A-101
CASEWORK ELEVATION4
FN
NOTE: ENSURE NEW LEAD-LINED SHEETS ARE
IN CONTACT WITH EXISTING WALLS AND NO GAPS
ARE PRESENT. REFER TO SPECS FOR ADDITIONAL
INFORMATION
NOTE: FURR OUT EXISTING WALLS AS REQUIRED TO
ENSURE LEAD-LINE BY BOARD AND GYPSUM BOARD
FACES ALIGN
X-RAY SHIELDED FRAMES w/ X-RAY LEAD GLASS AND DOOR PANEL
X-RAY SHIELDED DOOR (CONTINUOUS LEAD SHEET CENTER WITHIN DOOR PANEL)
NOTE: ALL EXISTING EQUIPMENT WITHIN ROOMS TO BE RE-LOCATED FOR CONSTRUCTION.
COORDINATE WITH VA STAFF IN CHARGE.
Set #001 - WD PAIR
DOORS:
6 HINGES A8111 FBB168 4.5" X 4.5" US26D ST
1 DUSTPROOF STRIKE L04021 3911 626 TR
2 FLUSH BOLT L04081/L04251 3917-12 626 TR
1 DEADBOLT E06091 48H-7R 626 BE
1 PULL PLATE 1018 3 ½ X 15 (INSIDE ROOM) 630 TR
1 PUSH PLATE 1820 3 ½ X 15 (OUTSIDE ROOM) 630 TR
1 CLOSER CO2011/CO2021 HD8016 AF80P 689 BE
2 MOP PLATE J103 KM050 4" X 1" LDW B4E-HEAVY-KP CSK 630 TR
2 ARMOR PLATE J102 KA050 34" X 2" LDW B4E-HEAVY-KP CSK 630 TR
2 WALL BUMPER L02251 1270CV 626 TR
2 DOOR SILENCERS L03011 1229A GREY TR
OPTION LIST
Code Description
1/4-20 SSMS/EA STAINLESS MACHINE SCREWS/EXPANSION ANC.
54 CONCEALED WIRES (4)
B4E-HEAVY-KP BEVELED 4 EDGES - KICK PLATES
C QUICK CONNECT WIRING OPTION
C QUICK CONNECT WIRING SYSTEM
CSK COUNTER SINKING OF KICK AND MOP PLATES
EPT PREP EPT PREP (FULL MORTISE)
FL FIRE EXIT HARDWARE
LAR LENGTH AS REQUIRED
LDW LESS DOOR WIDTH
MLR MOTORIZED LATCH RETRACTION
RQE REQUEST TO EXIT
VIB DOUBLE VISUAL INDICTOR OPTION
WTS WEATHERIZED TOUCHBAR MONITORING SWITCH
MANUFACTURER LIST
CODE NAME
BE BEST ACCESS SYSTEMS
BY BY RELATED SECTION
DM DORMA DOOR CONTROLS
NA NATIONAL GUARD
PR BEST PRECISION EXIT DEVICES
RC RCI
ST BEST HINGES AND SLIDING
TR TRIMCO
DOOR HARDWARE
DOOR
ASSEMBLY
TRANSITION STRIP
EPOXY FLOORING
SYSTEM (RES-IV)
EXISTING FLOOR
INTERIORINTERIOR
DOOR ASSEMBLY
HOLLOW METAL FRAME
INTERIORINTERIOR
REFER TO WALL TYPE P1
EXISTING WALL
DOOR ASSEMBLY
HOLLOW METAL FRAME
INTERIORINTERIOR
REFER TO WALL TYPE P1
EXISTING WALL
SHIM W/ BACKER ROD +
SEALANT (BOTH SIDES)
INTERIORINTERIOR
REFER TO WALL TYPE P1
EXISTING WALL
5/8" TYPE 'X' GYPSUM BOARD
METAL CHANNEL GYPSUM
BOARD SUSPENSION SYSTEM
Location
Issue Date
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
VAMC HUNTINGTON
Project Director
Revisions: Date:
VA FORM
08 -
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Stewart C. Cluck 717.850.2515
CONSTRUCTION
DOCUMENTS
600 North Hartley Street, Suite 152 York, PA 17404
1S
HOMCO Renaissance and
GPI-Renaissance JV 7510 Langport Ct.
Hanover, MD 21076
410-340-8284
5001 LOUISE DRIVE,
MECHANICSBURG PA 17055
T 717-691-1340
1 - REVIEW COMMENTS 05/10/2024
A-501
DETAILS
JEGSCC03/20/2024
581-23-111EXPAND PAIN AND
BRONCHOSCOPY
PROCEDURE ROOM
SCALE: 3" = 1'-0"A-501
DOOR DETAIL - SILL3
SCALE: 3" = 1'-0"A-501
DOOR DETAIL - JAMB2
SCALE: 3" = 1'-0"A-501
DOOR DETAIL - HEAD1
SCALE: 3" = 1'-0"A-501
CEILING DETAIL4
DUCTWORK SYMBOLS
SUPPLY DIFFUSER 1-WAY BLOW
SUPPLY DUCT (SECTION)
RETURN, EXHAUST, OR TRANSFER
DUCT (SECTION)
EXHAUST DUCT (SECTION)
DRAWING SYMBOLS
DETAIL DESIGNATION OR ENLARGED PLAN
X
X HVAC DRAWING NUMBER WHERE DETAIL IS SHOWN
X
XX
SECTION DESIGNATION
HVAC DRAWING NUMBER WHERE SECTION IS SHOWN
HVAC DRAWING NUMBER WHERE TAKEN FROM
X
X
EQUIPMENT TAG
TAG NUMBER
POINT OF NEW CONNECTION
POINT OF DISCONNECTION
X-X
T
S
THERMOSTAT
TEMPERATURE SENSOR
XXX
GRILLE/REGISTER/DIFFUSER
GRILLE/REGISTER/DIFFUSER TAG
GRILLE/REGISTER/DIFFUSER NUMBER
BALANCING CFM
AIR FLOW DIRECTION
UNIT HEATER UH
X
DUCTWORK SYMBOLS
DOUBLE LINE SINGLE LINE
DUCT WIDTH x DEPTH
ACOUSTICAL DUCT LINING
AD ACCESS DOOR
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFR ABOVE FINISHED ROOF
AHU AIR HANDLING UNIT
AP ACCESS PANEL
ARCH ARCHITECTURE
ATC AUTOMATIC TEMPURATURE CONTROL
ATM ATMOSPHERE
AUX AUXILIARY
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
BC BACKWARD CURVE
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BI BACKWARD INCLINED
BOD BOTTOM OF DUCT
BOJ BOTTOM OF JOIST
BOS BOTTOM OF STEEL
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
CC COOLING COIL
CCW COUNTER CLOCKWISE
CFM CUBIC FEET PER MINUTE
C&I CONTROLS AND INSTRUMENTATION
CLG CEILING
CMU CONCRETE MASONARY UNIT
COND CONDENSATE
CONN CONNECTION
CONT CONTINUATION
CORR CORRIDOR
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CU FT CUBIC FEET
CVS CONTROL VALVE STATION
CVT CONVERTER
CW CLOCKWISE
D DIFFUSER OR REGISTER
dB DECIBEL, RE 10 WATT
DBT DRY BULB TEMPURATURE (°F)
DDC DIRECT DIGITAL CONTROL
DEG DEGREE FAHRENHEIT (°F)
DIA DIAMETER
DIM DIMENSION
DN DOWN
DP DEW POINT TEMPURATURE (°F)
DX DIRECT EXPANSION
DWG DRAWING
E EXHAUST
EA EXHAUST AIR
EAT ENTERING AIR TEMPURATURE (°F)
EC ELECTRICAL CONTRACTOR
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEV ELEVATION
EMS ENERGY MANAGEMENT SYSTEM
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPURATURE (°F)
EUH ELECTRIC UNIT HEATER
F FILTER
FA FACE AREA
FC FORWARD CURVE
FLR FLOOR
FP FIRE PROTECTION
FPM FEET PER MINUTE
FRP FIBERGLASS REINFORCED POLYMER
FT FEET
FVEL FACE VELOCITY
GA GAUGE OR GAGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GUH GAS UNIT HEATER
HC HEATING COIL
HG MERCURY
HP HORSEPOWER
HR HOUR
ID INSIDE DIAMETER
IN INCH
KW KIOWATTS
KWH KILOWATT HOUR
L LOUVER
LAT LEAVING AIR TEMPURATURE (°F)
LBS POUNDS
LF LINEAR FEET
LWT LEAVING WATER TEMPURATURE (°F)
M MOTOR OPERATED
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MMBH 1,000,000 BTUH
NA NOT APPLICABLE
NC NOISE CRITERIA, dB RE 20 uPa
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPS NOMINAL PIPE SIZE
NPT NOMINAL PIPE THREAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTSIDE AIR DAMPER
OD OUTSIDE DIAMETER
OZ OUNCE
PTAC PACKAGE TERMINAL AIR CONDITIONER
PC PLUMBING CONTRACTOR
PD PRESSURE DROP
PDI PRESSURE DIFFERENTIAL INDICATOR
PH PHASE
PPM PART PER MILLION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA PSI, ABSOLUTE
PSIATM PSI, ATMOSPHERE
PSIG PSI, GAUGE
QTY QUANTITY
R REGISTER
RA RETURN AIR
RC ROOM CRITERIA, dB RE 20 uPa
RF RETURN/RELIEF AIR FAN
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
S SMOKE DETECTOR
SA SUPPLY AIR
SAF SUPPLY AIR FAN
SCFM CFM, STANDARD CONDITIONS
SEER SEASONAL ENERGY EFFICIENY RATIO
SENS SENSIBLE
SF SQUARE FEET
SP STATIC PRESSURE (IN.WG.)
SPEC SPECIFICATION
SPS STATIC PRESSURE SENSOR
SQ SQUARE
STD STANDARD
T THERMOSTAT
TA TRANSFER AIR
TD TEMPURATURE DIFFERENCE (°F)
TEMP TEMPURATURE
TG TRANSFER GRILL
TOD TOP OF DUCT
TOP TOP OF PIPE
TOS TOP OF STEEL
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TYP TYPICAL
UC UNDERCUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
UV UNIT VENTILATOR
V VALVE
VA VOLT-AMPERE
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VFV VAV, WITH FAN VOL VOLUME
VVT VARIABLE VOLUME VARIBLE TEMPURATURE
W WATT
WB WET BULB TEMPURATURE (°F)
WMS WIRE MESH SCREEN
W/ WITH
MECHANICAL ABBREVIATIONS PIPING SYMBOLS
GENERAL
(NAME) E EXISTING PIPE
ROUND DUCT
INCLINED RISE, IN DIRECTION
OF AIR FLOWR
R
D D
INCLINED DROP, IN
DIRECTION OF AIR FLOW
FLEXIBLE DUCT CONNECTION
ELBOW WITH TURNING VANES
STANDARD RADIUS ELBOW
DAMPER IN WALL
OR FLOORX
SUPPLY REGISTER, DIFFUSER,
OR GRILLE (WALL TYPE)
RETURN GRILLE/REGISTER
RUNOUT TO ROUND SUPPLY
DIFFUSER
RUNOUT TO SQUARE SUPPLY
DIFFUSER
BOD
BOD
BACKDRAFT DAMPER
MOTOR OPERATED DAMPER
M M
MANUAL VOLUME DAMPER
VD
VD
S
S
SMOKE DETECTOR FURNISHED
AND WIRED BY THE E.C.,
INSTALLED BY THE M.C
X
F
S
FS
FIRE
SMOKE
FIRE/SMOKE
DIRECTION OF FLOW
AIR CONDITIONING & REFRIGERATION
RL
RS
REFRIGERANT LIQUID
REFRIGERANT SUCTION
1. CODES AND STANDARDS LISTED IN SPECIFICATIONS AND DRAWINGS ARE MINIMUM STANDARDS. WHERE REQUIREMENTS ON THE DRAWINGS OR SPECIFICATIONS EXCEED THE MINIMUM CODE REQUIREMENTS, THE DRAWINGS OR SPECIFICATIONS SHALL GOVERN.
2. THE POWER RATING OF MOTORS AND OTHER MECHANICAL EQUIPMENT AND THE ELECTRICAL CHARACTERISTICS OF ELECTRICAL SYSTEMS SERVING THEM HAVE BEEN ESTABLISHED AS MINIMUMS WHICH ALLOW THAT EQUIPMENT TO FUNCTION PROPERLY TO PRODUCE THE REQUIRED CAPACITIES. POWER RATINGS INCLUDE REASONABLE SAFETY FACTORS TO ACCOMMODATE COMMON DIFFERENCES BETWEEN DESIGN PARAMETERS AND FIELD CONSTRUCTION PRACTICES. EQUIPMENT WITH POWER RATINGS LESS THAN THOSE INDICATED ON THE DRAWINGS SHALL NOT BE PERMITTED.
3. REASONABLE EFFORTS HAVE BEEN MADE TO COORDINATE ELECTRICAL REQUIREMENTS OF MECHANICAL EQUIPMENT WITH THE ELECTRICAL SYSTEMS SERVING THAT EQUIPMENT. DIFFERENCES AMONG MANUFACTURERS OF MECHANICAL EQUIPMENT MAKE IT IMPOSSIBLE TO PRODUCE A SINGLE ELECTRICAL DESIGN WHICH WILL SATISFY THE VARYING ELECTRICAL REQUIREMENTS OF THE THOSE MANUFACTURERS. CONSEQUENTLY, THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL REQUIREMENTS OF THE MECHANICAL EQUIPMENT ACTUALLY FURNISHED ON THIS PROJECT WITH THE EQUIPMENT ACTUALLY FURNISHED ON THIS PROJECT AND PROVIDE ELECTRICAL SYSTEMS REQUIRED BY THAT EQUIPMENT. THIS COORDINATION EFFORT SHALL BE COMPLETED PRIOR TO THE INSTALLATION OF EITHER THE MECHANICAL EQUIPMENT OR THE ELECTRICAL SYSTEMS SERVING THAT EQUIPMENT. ELECTRICAL SYSTEM REVISIONS REQUIRED TO COORDINATE WITH THE MECHANICAL EQUIPMENT ACTUALLY FURNISHED SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
4. DRAWINGS INDICATE GENERAL LOCATIONS OF FIXTURES, APPARATUS, EQUIPMENT, PIPING, AND DUCTWORK. CHANGES ON LOCATION SHALL BE MADE TO ACCOMMODATE EXISTING OR NEW BUILDING CONDITIONS AND COORDINATION WITH OTHER TRADES, INCLUDING HVAC, PLUMBING, ELECTRICAL, FIRE PROTECTION, STRUCTURAL, AND ARCHITECTURAL, SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER.
5. PROVIDE ACCESS TO EQUIPMENT AND PORTIONS OF BUILDING SYSTEMS REQUIRING SERVICE.
6. DO NOT INSTALL DUCTWORK, PIPING, OR EQUIPMENT IN ELECTRICAL ROOMS, ELEVATOR ROOMS, OR ELEVATOR SHAFTS, UNLESS EXPLICITLY INDICATED ON THE
DRAWINGS. PIPING, DUCTWORK, AND EQUIPMENT (SWITCHGEAR, SWITCHBOARDS, PANELS, MOTOR CONTROL CENTERS, VARIABLE FREQUENCY DRIVES, TRANSFORMERS, OR STARTERS) SHALL NOT BE INSTALLED DIRECTLY ABOVE OR 42" IN FRONT OF ELECTRICAL EQUIPMENT FROM THE FLOOR TO THE STRUCTURE
ABOVE.
7. FOR RENOVATION PROJECTS WHERE THE BUILDING IS OCCUPIED, SCHEDULE WORK SO EXISTING SYSTEMS WILL BE INTERRUPTED FOR A MINIMUM AMOUNT OF TIME. OBTAIN APPROVAL FROM THE OWNER AND ARCHITECT AT LEAST 14 DAYS PRIOR TO INTERRUPTION OR CONNECTION. NO ALLOWANCE WILL BE MADE FOR
LACK OF KNOWLEDGE OF EXISTING CONDITIONS.
8. UNLESS INDICATED OTHERWISE, EQUIPMENT AND MATERIALS SHALL BE NEW AND OF THE CUSTOMARY STANDARD AND QUALITY FURNISHED BY THE DESIGNATED
MANUFACTURER FOR THAT CATALOG NUMBER.
9. FOR EXISTING SYSTEMS, REMOVE EXPOSED PIPING AND DUCTWORK RENDERED USELESS DUE TO CHANGES. PLUG OUTLETS IN PIPING. CAP AND SEAL OPENINGS
IN DUCTWORK AND SEAL AIRTIGHT.
10. AIR SYSTEMS SHALL OPERATE WITHOUT AERODYNAMIC NOISE GENERATED FROM FAULTY INSTALLATION OF DUCTWORK, DIFFUSERS, OR ANY PORTION OF THE AIR
DISTRIBUTION SYSTEM.
11. SUPPORT PIPING INDEPENDENTLY OF EQUIPMENT. HANGER RODS SHALL BE SUSPENDED FROM THE STRUCTURE. DO NOT SUSPEND FROM OTHER PIPING, CONDUIT, EQUIPMENT, OR DUCTWORK.
12. ALL WORK REFERENCED UNDER DIVISION 23 SHALL BE DONE BY THE MECHANICAL CONTRACTOR.
13. ALL EXISTING DUCTWORK, PIPING, EQUIPMENT, SYSTEMS, AND ASSOCIATED APPURTENANCES TO BE DEMOLISHED, NOT CONCEALED WITHIN AN INACCESSIBLE
CHASE OR WALL, SHALL BE REMOVED IN THEIR ENTIRETY. ANY OF THESE ITEMS ABANDONED AS A RESULT OF ALL NEW WORK SHALL BE CAPPED APPROPRIATELY AND LABELED INDICATING THE ITEMS' PREVIOUS SERVICE AND DESTINATION/ORIGINATION. THE GOVERNMENT, ARCHITECT, OR ENGINEER SHALL BE NOTIFIED OF
ANY ABANDONED ITEMS.
GENERAL MECHANICAL NOTES:
1. INSTALL PIPING TO ALLOW ACCESS FOR VALVES, AIR VENTS, AND EQUIPMENT REQUIRING ACCESSIBILITY, AND TO PROVIDE MAXIMUM
HEADROOM.
2. PROVIDE OFFSETS TO MAINTAIN CEILING HEIGHT AND TO COORDINATE WITH OTHER TRADES.
3. INSTALL VALVES IN HORIZONTAL PIPING WITH VALVE STEMS AT OR ABOVE THE PIPE CENTERLINE.
4. ARRANGE PIPING FOR VENTING OF AIR AND DRAINAGE OF ENTIRE SYSTEM.
5. REPLACE EXISTING MECHANICAL PIPE HANGERS AND PIPE FLOOR SUPPORTS WITH NEW TO SERVE EXISTING MECHANICAL PIPING TO REMAIN
IN ORDER TO ACCOMMODATE THE INSTALLATION OF ALL NEW EQUIPMENT, SYSTEMS, AND DEVICES. MECHANICAL CONTRACTOR SHALL VERIFY
EXACT LOCATIONS AND SIZES IN THE FIELD.
6. WHEREVER NEW PIPING IS JOINED TO EXISTING PIPING, THE MECHANICAL CONTRACTOR SHALL PROPERLY SEAL THESE CONNECTIONS WATERTIGHT AND INSULATE THESE LOCATIONS WITH NEW INSULATION AS INDICATED IN THE SPECIFICATION.
7. FOR COPPER AND STEEL PIPING GROOVED OR MECHANICALLY FORMED T-TYPE FITTINGS ARE NOT ACCEPTABLE.
1. CHANGES IN SHAPE OR DIMENSION SHALL BE MADE WITH MAXIMUM TRANSITION OF 1 TO 7.
2. SEPARATE GALVANIZED SHEET METAL FROM ALUMINUM OR COPPER PER THE SPECIFICATIONS.
3. PROVIDE SUPPLEMENTAL STIFFENING AND SUPPORTS TO DUCTS AND APPARATUS CASINGS TO PREVENT DRUMMING, SAGGING AND TO PROVIDE A
STRUCTURALLY SOUND ASSEMBLY.
4. PROVIDE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES.
5. PROVIDE DUCTWORK AND TRANSITIONS TO CONNECT DUCTWORK TO NEW OR EXISTING EQUIPMENT, DUCTWORK, AND COILS.
6. INSTALL FLEXIBLE PERMANENT DUCTWORK IN A FULLY EXTENDED CONDITION WITHOUT SAGS AND KINKS.
7. MECHANICAL CONTRACTOR SHALL INSTALL DUCT MOUNTED SMOKE DETECTORS IN ACCESSIBLE LOCATIONS. DETECTORS SHALL BE FURNISHED AND WIRED
BY THE ELECTRICAL CONTRACTOR. REFER TO ELECTRICAL DRAWINGS FOR EXACT QUANTITY AND LOCATIONS.
8. INDICATED DIMENSIONS DENOTE FREE AND CLEAR INSIDE DIMENSIONS.
9. REPLACE EXISTING DUCT HANGERS WITH NEW TO SERVE EXISTING DUCTWORK TO REMAIN IN ORDER TO ACCOMMODATE THE INSTALLATION OF ALL NEW
EQUIPMENT, SYSTEMS, AND DEVICES. MECHANICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS AND SIZES IN THE FIELD.
10. WHEREVER NEW DUCTWORK IS JOINED TO EXISTING DUCTWORK, THE MECHANICAL CONTRACTOR SHALL PROPERLY SEAL THESE CONNECTIONS AIRTIGHT
AND INSULATE THESE LOCATIONS WITH NEW INSULATION AS INDICATED IN THE SPECIFICATION.
GENERAL PIPING NOTES:
GENERAL DUCTWORK NOTES:
1. TRANSFORMERS OR FILTERS FOR OPERATION OF AUTOMATIC TEMPERATURE CONTROLS FROM BUILDING POWER CIRCUITS SHALL BE PROVIDED UNDER
DIVISION 23.
2. LOW VOLTAGE WIRING (LOWER THAN 110 VOLTS) FOR INTERLOCKED DEVICES, ATC CONTROLLERS, TERMINAL CONTROL UNITS, FLOW MEASURING DEVICES, AND OTHER POWER CONSUMING CONTROL DEVICES SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. ALL LOW VOLTAGE WIRING SHALL BE
INSTALLED IN A CONDUIT AND SHALL BE PLENUM RATED.
3. WIRING 110 VOLTS AND HIGHER FOR INTERLOCKED DEVICES, ATC CONTROLLERS, TERMINAL CONTROL UNITS, FLOW MEASURING DEVICES, AND OTHER POWER CONSUMING CONTROL DEVICES SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR WITH DIVISION 26 REQUIREMENTS. COORDINATE WITH
THE ELECTRICAL CONTRACTOR.
4. BRANCH CIRCUIT WIRING AND CONDUIT FURNISHED FOR CONTROL EQUIPMENT POWER SHALL BE SEPARATE FROM OTHER POWER WIRING. EACH CIRCUIT SHALL EXTEND TO A 120V BRANCH CIRCUIT PANEL, AND IDENTIFIED 120V, 20 AMPERE, SINGLE POLE BRANCH CIRCUIT BREAKER FURNISHED IN THE PANEL TO SERVE THE CIRCUIT. NO MORE THAN 2 ATC CONTROLLER INSTALLATIONS SHALL OPERATE FROM A SINGLE 120V BRANCH CIRCUIT, UNLESS INDICATED
OTHERWISE.
5. WHERE SYSTEMS ARE SERVED BY EMERGENCY POWER, CONTROLS FOR OPERATION OF THOSE SYSTEMS SHALL ALSO BE SERVED BY EMERGENCY POWER.
6. WHERE DAMPERS PREVENT AIRFLOW THROUGH AN AIR HANDLING UNIT OR FAN, THOSE DAMPERS SHALL BE PROVEN OPEN PRIOR TO STARTING THE UNIT OR
FAN. PROOF SHALL BE BY MECHANICAL SAFETY LIMIT SWITCH ACTIVATED BY THE DAMPER BLADE. FOR SERVICE WITH VARIABLE FREQUENCY DRIVES THE SWITCH SHALL BE WIRED IN THE AUTOMATIC AND HAND/TEST POSITIONS AND IN THE BYPASS POSITION FOR VARIABLE FREQUENCY DRIVES WITH BYPASS.
7. ALL AIR PIPING OR TUBING SHALL BE PLENUM RATED. MECHANICAL CONTRACTOR SHALL FURNISH ALL AIR PIPING AND TUBING REQUIRED FOR AUTOMATIC
CONTROLS SYSTEMS.
8. PROVIDE SUPPLEMENTAL STIFFENING AND SUPPORTS TO DUCTS AND APPARATUS CASINGS TO PREVENT DRUMMING, SAGGING AND TO PROVIDE A
STRUCTURALLY SOUND ASSEMBLY.
GENERAL AUTOMATIC TEMPERATURE CONTROL NOTES:
VAV BOX
PTAC UNIT
PT
X
VAV
X
LIMITS OF DEMOLITION
Location
Issue Date
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
VAMC HUNTINGTON
Project Director
Revisions: Date:
VA FORM 08 -
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Stewart C. Cluck 717.850.2515
CONSTRUCTION
DOCUMENTS
600 North Hartley Street, Suite 152 York, PA 17404
1S
HOMCO Renaissance and GPI-Renaissance JV
7510 Langport Ct.
Hanover, MD 21076 410-340-8284
5001 LOUISE DRIVE,
MECHANICSBURG PA 17055
T 717-691-1340
M-001
MECHANICAL LEGEND, NOTES, &
ABBREVIATIONS
AMRDLA03/20/2024
581-23-111EXPAND PAIN AND
BRONCHOSCOPY
PROCEDURE ROOM
PLAN REVIEW COMMENTS 05/10/2024
05/10/202405/10/2024
1 - REVIEW COMMENTS
E1
A
Room
3B-149
Room
3B-165
Room
3B-169
Room
3B-172
Room
3B-146
Room
3B-168 12"x8"
"x
12"x12"
T
"x
E1
A
BRONCHOSCOPY
ROOM
3B-147
E-1
630 CFM
12"x12"
EXISTING 12X12
DUCT BACK TO
AC-08
"x
(E X
IS
T
IN
G
(EXISTING)12"x12"
S -1
C F
M
S-1
250 CFM
(EXISTING)
16"x8"
10"ø 10"ø
CAP OPEN
END
Location
Issue Date
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
VAMC HUNTINGTON
Project Director
Revisions: Date:
VA FORM 08 -
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Stewart C. Cluck 717.850.2515
CONSTRUCTION
DOCUMENTS
600 North Hartley Street, Suite 152 York, PA 17404
1S
HOMCO Renaissance and GPI-Renaissance JV
7510 Langport Ct.
Hanover, MD 21076 410-340-8284
5001 LOUISE DRIVE,
MECHANICSBURG PA 17055
T 717-691-1340
M-101
THIRD FLOOR MECHANICAL
DEMOLITION & NEW WORK PLANS
AMRDLA03/20/2024
581-23-111EXPAND PAIN AND
BRONCHOSCOPY
PROCEDURE ROOM
1/4" = 1'-0"M-101
1 THIRD FLOOR MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"M-101
2 THIRD FLOOR MECHANICAL HVAC PLAN
GENERAL NOTES:
1. ADJUST SUPPLY AIR AT ADD-15 ON AC-08 LOCATED IN MECHANICAL ROOM 3B-126.
KEYED NOTES:
RELOCATE EXISTING NEGATIVE PRESURE INDICATOR TO LOCATION OUTSIDE NEW ROOM ENTRY.1
PLAN REVIEW COMMENTS 05/10/2024
05/10/2024
USE METAL NOSING ON INITIAL
LEADING EDGE NOSING MAY BE
FORMED OF DUCT OR CHANNEL
OR ZEE ATTACHED BY SCREWS,
RIVETS OR WELDS
LINED DUCT
CONNECTION (NO
EXPOSED LINER EDGES)
C
C
C B
DIMENSIONS
6"3"
A B
VELOCITY
0-6000 FPM 4" 16"
C E
A
B
B E
A
E
AIR FLOW
LAPPED & BUTTED CORNER
ALTERNATIVE FOLDED CORNER
LINER
WASHER
INTEGRAL OR
PRESSED ON HEAD1" THICK DUCT
LINER OR AS
SPECIFIED
WELDED PINS ONLY
ALL TRANSVERSE EDGES TO
BE COATED WITH ADHESIVE
LINER ADHERED TO THE
DUCT WITH A 100% AREA
COVERAGE OF ADHESIVE.
NOTES:
1. THE VELOCITY RATED SIDE OF
THE LINER MUST FACE THE AIR
FLOW.
2. MAXIMUM SPACING FOR
FASTENERS. ACTUAL INTERVALS
ARE APPROXIMATE.
DUCT DIMENSION
UP TO 457 (18")
482(189")- 1524(60")
1549(61")- 2438(96")
OVER 2438(96")
HANGER
TYPE
A
B
C
D
ROD DIA.
25.4(1") STRAP
7.94(5/16")
9.53(3/8")
12.7(1/2")
ANGLE SIZE
36.1x36.1x3.18(1-1/2"x1-1/2"x1/8")
36.1x36.1x3.18(1-1/2"x1-1/2"x3/16")
50.8x50.8x8.35(2"x2"x1/4")
SPACING MAX
24.38(8'-0")
12.19(4'-0")
24.38(8'-0")
24.38(8'-0")
MAX. SIDE
SHEET METAL SCREW,
RIVET OR BOLT TO BOTH
SIDES OF DUCT NUT AND WASHER AT END
OF SCREW
BRACING ANGLES,
SEE NOTES.
HANGER ROD
SECURE THE
STRUCTURE ABOVE AS
RECOMMENDED
25.4(1")x16 GA. GALV.
IRON STRAP OR ALUM.
MAX. SIDE
TYPE A TYPE B,C,D
24.8(8FT.) MAX. HANGER SPACING, ALSO
PROVIDE 3 HANGERS AT EACH TAKE OFF
OR BRANCH.
24.8(8FT.) MAX. HANGER SPACING
NOTES:
1. FOR SEVERAL DUCTS ON ONE HANGER, TYPE B,C OR D MAY BE USED. SIZE OF
HANGER SHALL BE SELECTED ON SUM OF DUCT WIDTHS EQUAL TO MAX. WIDTH OF
DUCT SCHEDULE.
2. DO NOT ATTACH HANGERS TO ROOF DECK OR BOTTOM.
SECURE THE
STRUCTURE ABOVE AS
RECOMMENDED
MAIN SUPPLY, RETURN, OR EXHAUST DUCT(LO OR
MEDIUM PRESSURE)
DISTANCE (1/4)x
DUCT WIDTH;
101.6(4") MINIMUM
VOLUME DAMPER (TYP.)
RECTANGULAR
BRANCH TAKE-OFF
DUCT
45° ENTRY FITTING
CONCEAL
DUCT TAKE-
OFF FITTING
BELLMOUTH DUCT TAKE-
OFF FITTING
VOLUME DAMPER (TYPICAL)
ROUND BRANCH TAKE OFF DUCT (TYPICAL)
NOTES:
1. SPIN-IN DUCT TAKE OFF FITTINGS MAY BE USED IN LIEU OF CONICAL OR BELLMOUTH FITTING ONLY
WHERE MAIN DUCT DIMENSIONS ARE NOT SUFFICIENT TO ALLOW THE USE OF A CONICAL OR
BELLMOUTH.
2. SEAL ALL TAKE-OFF AND OTHER FITTINGS AIR TIGHT AS PER SPECIFICATION.
3. FABRICATE BRANCH DUCT TAKE-OFF FITTING PER LATEST EDITION OF DUCT CONSTRUCTION
MANUAL, AS INDICATED ON PLANS, OR AS DESCRIBED IN SPECIFICATIONS.
4. APPLIES TO SUPPLY AND EXHAUST RUNOUTS TO GRILLES, REGISTERS, AND DIFFUSERS.
IF A DIMENSION IS GREATER
THAN 2'-0", SUPPORT ELBOW
FROM STRUCTURE ABOVE
MAX. LENGTH OF
FLEX DUCT 5'-0"
NON-KINKED
SUPPLY DUCT
ROUND OR
RECTANGULAR
MAIN OR BRANCH
DUCT
DRAW BAND BUCKLEY TYPE ATMD
FITTING (OR EQUAL)
PROVIDE A TYPICAL DUCT TAKEOFF WHERE
FLEX EXCEEDS 5'-0" (MAX. LENGTH)
CEILING TYPE VARIES.
REFER TO
ARCHITECTURAL PLANS
FOR CEILING TYPE.
FLEX DUCTNON- RESTRICTIVE 90
ELBOW "THERMAFLEX"
FLEX-FLOW OR EQUAL.
INSTALL AT ALL ROUND
NECK DIFFUSERS
DRAW BAND ON
DIFFUSER NECK
ROUND NECK
OR NECK
ADAPTOR
SUPPLY AIR DIFFUSER WITH ROUND NECK &
O.B.D. MOUNTING DETAIL VARIES. REFER TO
ARCH. FOR CEILING TYPE AND DIFFUSER
MANUFACTURER FOR MOUNTING REQUIREMENTS
NOTES:
1. INSULATED FLEXIBLE DUCT - SHALL BE PRESTRETCHED BEFORE INSTALL.
2. DIAMETER TO BE EQUAL TO DIFFUSER INLET SIZE UNLESS OTHERWISE NOTED.
TAG MAXIMUM
AIRFLOW
(CFM)
MAX. NECK
VELOCITY
(FPM)
NOMINAL
MODULE
SIZE (IN.)
MAX. STATIC
PRESSURE (IN.)
MAX. NOISE
CRITERIA (NC)
PATTERN MATERIAL REMARKS
S-1 275 24X24 0.037 16 4-WAY ALUMINUM 1,2,3
BASIS OF DESIGN
TITUS TMS-AA
DIFFUSERS, REGISTERS AND GRILLES SCHEDULE
REMARKS:
*NR = NO REQUIREMENT
1. TEMPERATURE SETPOINT SHALL BE 68°F
2. RELATIVE HUMIDITY SHALL BE 20-60%
3. COLOR AND FINISH BY ARCHITECT
630 24X24 0.02 - EGG CRATE ALUMINUM 1,2,3TITUS 45F200
R-1
DUCT SIZE DUCT
ANCHOR BOLT
ANGLE
DIAGONAL
BOTH SIDES
LONGITUDINAL ANGLE
CUT WASHER
BOLTS WITH
HORIZONTAL ANGLE
(TYPICAL)
VERTICAL ANGLE
(TYPICAL)
ANGLE CLIP
SEISMIC RESTRAINTS
PROVIDE THE WORK IN COMPLIANCE WITH THE MOST STRINGENT SEISMIC REQUIREMENTS FOR THE APPLICABLE CODES AS SPECIFIED IN SPECIFICATIONS HEREIN. PROVIDE SEISMIC RESTRAINTS FOR MATERIALS AND EQUIPMENT OF THIS DIVISION, INCLUDING (BUT NOT LIMITED TO) THE ITEMS LISTED BELOW. THE ATTACHMENTS SHALL RESIST FORCE APPLIED TO THE CENTER OF GRAVITY OF THE COMPONENTS. CRITERIA SHALL BE THE OPERATING WEIGHT OF THE ITEM AS INDICATED IN SPECIFICATIONS HEREIN FOR HORIZONTAL FORCES AND VERTICAL FORCES. DESIGN FOR THE HORIZONTAL FORCES TO BE APPLIED IN ANY DIRECTION.
WALL MOUNTED OR SUSPENDED COMPONENTS SHALL, IN ADDITION, RESIST A DOWNWARD FORCE TO THE OPERATING WEIGHT. PROVIDE BRACING AND ANCHORAGE OF PIPING AND CONDUIT HANGERS AND TRAPEZES
IN ACCORDANCE WITH THE GUIDELINES PER SPECIFICATIONS HEREIN.
CAREFULLY REVIEW THE SPACE AVAILABLE TO INSURE THAT THE RESTRAINT SYSTEMS INDICATED WILL NOT
IMPAIR THE REQUIRED EQUIPMENT CLEARANCE, WORKING SPACE OR ACCESS.
SUBMIT DETAILS AND ASSOCIATED CALCULATIONS OF THE SEISMIC ANCHORAGE PER SPECIFICATIONS
HEREIN.
ALL PIPES SHALL BE SUPPORTED AND BRACED PER SEISMIC RESTRAINTS OF MECHANICAL AND PLUMBING SYSTEMS INDICATED IN SPECIFICATIONS HEREIN. ONCE THE EXACT LOCATION OF ALL PIPES HAS BEEN ESTABLISHED, THE STRUCTURAL ENGINEER MUST CHECK THE ADEQUACY OF THE SUPPORTING STRUCTURE.
ALL EXTERIOR AIR HANDLING UNITS, DUCTWORK, AND PIPING SHALL BE PROVIDED WITH SEISMIC RESTRAINT
IN ACCORDANCE WITH SPECIFICATIONS HEREIN.
SEISMIC NOTE:
THESE DETAILS ARE PROVIDED TO INDICATE THE INTENT AND BASIC REQUIREMENTS
FOR SEISMIC RESTRAINT OF THE PIPING, DUCTWORK AND CONDUIT SYSTEMS WITHIN
AND OUTSIDE THE BUILDING. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
OBTAIN THE SERVICES OF A SEISMIC ENGINEER AND TO PROVIDE SEISMIC
RESTRAINTS IN ACCORDANCE WITH THE CRITERIA INDICATED IN THE SPECIFICATIONS.
Location
Issue Date
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
VAMC HUNTINGTON
Project Director
Revisions: Date:
VA FORM 08 -
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Stewart C. Cluck 717.850.2515
CONSTRUCTION
DOCUMENTS
600 North Hartley Street, Suite 152 York, PA 17404
1S
HOMCO Renaissance and GPI-Renaissance JV
7510 Langport Ct.
Hanover, MD 21076 410-340-8284
5001 LOUISE DRIVE,
MECHANICSBURG PA 17055
T 717-691-1340
M-201
MECHANICAL DETAILS AND
SCHEDULES
AMRDLA03/20/2024
581-23-111EXPAND PAIN AND
BRONCHOSCOPY
PROCEDURE ROOM
NOT TO SCALEM-201
1 ACOUSTICAL LINING DETAIL
NOT TO SCALEM-201
2 DUCT HANGERS DETAIL
NOT TO SCALEM-201
3 BRANCH TAKE-OFF DETAIL
NOT TO SCALEM-201
4 SUPPLY AIR DIFFUSER DETAIL (SIDE TAP)
NOT TO SCALEM-201
5 SEISMIC BRACING FOR RECTANGULAR DUCTS
PLAN REVIEW COMMENTS 05/10/2024
PLUMBING FIXTURE SCHEDULE
FIXTURE SANITARY VENT
REMARKS
MARK COLD WATER HOT WATER
NOTES:
1. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL STOPS ON SUPPLY LINES TO ALL FIXTURES.
2. PLUMBING CONTRACTOR TO FURNISH AND INSTALL ACCESS DOORS FOR ALL VALVES AS REQUIRED.
3. ALL EXPOSED PIPING UNDER ADA ACCESSIBLE COUNTERTOP SINKS AND LAVATORIES SHALL BE INSULATED AND PROTECTED WITH PREFABRICATED
MOLDED COVERS AS MANUFACTURED BY TRUEBRO CO, OR EQUAL.
4. PLUMBING CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR INTERIOR ELEVATIONS AND MOUNTING HEIGHTS FOR PLUMBING
FIXTURES.
5. PROVIDE WATTS SERIES LFUSG-B THERMOSTATIC MIXING VALVE (SET TO 80°F - 95°F) FOR ALL LAVATORIES AND HAND WASHING SINKS.
6. PROVIDE LAMANIAR FLOW DEVICE WITH A FLOW CONTROL RESTRICTOR AND VANDAL RESISTANT HOUSING. AERATORS ARE PROHIBITED.
7. PROVIDE FOOT PEDAL AS MANUFACTUERED BY CHICAGO FAUCETS MODEL 625-SLOABCP. PROVIDE SUPPLY LINE CONNECTION FROM FOOT PEDAL TO
FAUCET.
S-1 COUNTERTOP SINK
MANUFACTURER MODEL
1/2" 1/2" 1 1/2"1 1/2" LUSTERTONE, SINGLE BOWL SINK, 18 GAUGE, TYPE 304 STAINLESS STEEL, SATIN FINISH, CENTER
DRAIN, GOOSENECK, THREE HOLE DRILLING CONFIGURATION, PROVIDE CUTOUT TEMPLATE.
MANUAL FAUCET, 0.5 GPM. PROVIDE DRAIN WITH TAILPIECE AND WASTE TEE FITTING AND P-TRAP
PROFLO OR EQUAL. PROVIDE WATER SUPPLY AND STOPS PROFLO OR EQUAL.
ELKAY LR2219
FIXTURE
MANUFACTURER MODEL
CHICAGO
FAUCETS
786-TWE72ABCP
FAUCET CONNECTIONS
FLOW RATE
0.5 GPM
DRAWING SYMBOLS
DETAIL DESIGNATION OR ENLARGED PLAN
PLUMBING DRAWING NUMBER WHERE DETAIL IS SHOWN
POINT OF NEW CONNECTION
POINT OF DISCONNECTION
LEGEND
DIRECTION OF FLOW
BALL
"P" TRAP
PIPING SYMBOLS
PIPING SPECIALTIES & FITTINGS
CAPPED OUTLET
CHANGE IN ELEVATION OF PIPE
PIPE RISE OR ELBOW TURNED UP
PIPE DROP OR ELBOW TURNED DOWN
KEYED DEMOLITION NOTE
KEYED DRAWING NOTE
SAN SANITARY PIPING BELOW FLOOR
SANITARY PIPING ABOVE FLOOR
VENT PIPING
POTABLE COLD WATER PIPING
POTABLE HOT WATER PIPING
POTABLE HOT WATER RETURN PIPING
CLEANOUT / WALL CLEANOUT
CO
FCO
FLOOR CLEANOUT
AC ALTERNATING CURRENT
AD ACCESS DOOR
ARCH ARCHITECTURE
BF BELOW FLOOR
BFF BELOW FINISHED FLOOR
CI CAST IRON
CLG CEILING
CO CLEAN OUT
CONN CONNECTION
CONT CONTINUATION
CONTR CONTRACTOR
CW COLD WATER
DIA DIAMETER
DIM DIMENSION
DN DOWN
EXIST EXISTING
FLR FLOOR
GC GENERAL CONTRACTOR
GEN GENERAL
HW HOT WATER
HWR HOT WATER RETURN
ID INSIDE DIAMETER
IN INCH
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NA NOT APPLICABLE
NTS NOT TO SCALE
PC PLUMBING CONTRACTOR
PLB PLUMBING
QTY QUANTITY
SAN SANITARY
SPEC SPECIFICATION
STD STANDARD
TYP TYPICAL
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
V VENT
W WASTE
PLUMBING ABBREVIATIONS
A. GENERAL PLUMBING NOTES
1. ALL SYSTEMS ARE SHOWN SCHEMATICALLY. THE DRAWINGS AS PREPARED ARE
DIAGRAMMATIC BUT SHALL BE FOLLOWED AS CLOSELY AS CONSTRUCTION OF
THE PROJECT AND THE WORK OF ALL TRADES WILL PERMIT.
FIXTURE/EQUIPMENT LOCATIONS ARE APPROXIMATE. CHECK AND VERIFY ALL
CONDITIONS AT THE SITE WITHIN THE CONTRACT LIMITS.
2. CODES AND STANDARDS LISTED IN THE SPECIFICATION AND DRAWINGS ARE A
MINIMUM STANDARD. WHERE REQUIREMENTS ON THE DRAWINGS AND
SPECIFICATION EXCEED THE MINIMUM CODE REQUIREMENTS, THE DRAWINGS
OR SPECIFICATIONS SHALL GOVERN.
3. IT IS INTENDED THAT THE DRAWINGS AND SPECIFICATIONS SHALL PROVIDE A
WORKING INSTALLATION COMPLETE IN DETAIL AND ALL ITEMS FOR A COMPLETE
INSTALLATION SHALL BE PROVIDED WHETHER OR NOT SPECIFIED OR SHOWN
ON THE DRAWINGS.
4. PROVIDE ALL LABOR AND MATERIALS NEEDED FOR A COMPLETE AND
PROPERLY OPERATIONAL PLUMBING SYSTEM. THE OMISSION OF EXPRESSED
REFERENCE IN THE DRAWINGS OR SPECIFICATIONS TO ANY LABOR OR
MATERIAL NECESSARY FOR THE PROPER EXECUTION OF THE WORK IN
ACCORDANCE WITH PRESENT GOOD PRACTICE OF THE TRADE SHALL NOT
RELIEVE THIS CONTRACTOR FROM PROVIDING, AT NO COST, SUCH ADDITIONAL
LABOR AND MATERIALS UNDER THIS CONTRACT.
5. ALL EQUIPMENT AND MATERIALS INCORPORATED IN THIS WORK SHALL BE NEW
UNLESS OTHERWISE NOTED AND SHALL BE OF THE CUSTOMARY STANDARD
AND QUALITY FURNISHED BY THE DESIGNATED MANUFACTURER FOR THAT
CATALOG NUMBER. THE CATALOG NUMBER PRODUCTS SHALL BE BY
MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH
PRODUCTS.
6. DRAWINGS INDICATE GENERAL LOCATION OF FIXTURES, EQUIPMENT, AND
PIPING. CHANGES OF LOCATION SHALL BE MADE TO ACCOMMODATE EXISTING
OR NEW BUILDING CONDITIONS AND COORDINATION WITH OTHER TRADES,
INCLUDING HVAC, PLUMBING, ELECTRICAL, FIRE PROTECTION, STRUCTURAL,
AND ARCHITECTURAL CHANGES SHALL BE MADE WITHOUT ADDITIONAL COST
TO OWNER.
7. ALL WORK REFERENCED ON THE DRAWINGS SHALL BE DONE BY THE PLUMBING
CONTRACTOR UNLESS OTHERWISE NOTED.
8. BEFORE STARTING WORK THE CONTRACTOR IS RESPONSIBLE TO MAKE A
THOROUGH EXAMINATION OF THOSE PORTIONS OF THE STRUCTURE IN WHICH
THE WORK IS TO BE PREFORMED. THE CONTRACTOR IS RESPONSIBLE FOR
CHECKING, FIELD VERIFYING AND CONFIRMING ALL CONDITIONS AND
DIMENSIONS INCLUDING BUT NOT LIMITED TO EXISTING COLD WATER, HOT
WATER, HOT WATER RECIRCULATING, DRAIN, WASTE, VENT AND GAS PIPING
AND LOCATIONS, SIZES AND INVERTS AS APPLICABLE ON THE PROJECT SITE
AND FOR COORDINATION OF HIS WORK WITH THAT OF OTHER TRADES WITH
THE LEAST POSSIBLE INTERFERENCE.
9. ALL CONTRACTORS SHALL EXAMINE THE SITE AND REVIEW THE DRAWINGS AND
SPECIFICATIONS PRIOR TO SUBMITTING A PROPOSAL.
10. CONTRACTOR SHALL VERIFY DEPTH, SIZE, LOCATION OF ALL EXISTING UTILITIES
IN FIELD PRIOR TO STARTING WORK.
11. WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND OWNER.
12. VALVES AND FITTINGS SHALL CONFORM TO THE REDUCTION OF LEAD IN
DRINKING WATER ACT AND ALL REVISIONS THEREOF.
13. CONTRACTOR SHALL PROTECT THE PIPING FROM STRESS AND STRAIN.
CONTRACTOR SHALL PROTECT THE IN-SLAB PIPING FROM CORROSION, STRESS
AND STRAIN TO CONFORM.
14. ALL FACTORY APPLIED COATINGS AND FINISHES SHALL BE PROVIDED WITHOUT
RUST, SCRATCHES, OR DENTS.
B. COORDINATION REQUIREMENTS
1. COORDINATE EXACT LOCATIONS AND CLEARANCES WITH THE SUPPLIER AND
ALL TRADES PRIOR TO INSTALLATION. DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS.
2. COORDINATE LOCATION AND INSTALLATION OF ALL PLUMBING WORK WITH
OTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES. MODIFICATIONS
DUE TO FIELD CONDITIONS SHALL BE COMPLETELY RESOLVED BY CONTRACTOR
IN ACCORDANCE WITH RECOMMENDATIONS OF THE CONSTRUCTION MANAGER.
3. COORDINATE FINAL LOCATIONS OF PLUMBING FIXTURES AND EQUIPMENT WITH
ARCHITECTURAL PLANS. REFER TO THE ARCHITECTURAL DRAWINGS FOR ALL
EXACT DIMENSIONS AND CONFIRM ALL DIMENSIONS IN THE FIELD.
4. REPORT TO THE ARCHITECT/ENGINEER ANY AND ALL CONDITIONS WHICH MAY
INTERFERE WITH OR OTHERWISE AFFECT OR PREVENT THE PROPER
EXECUTION AND COMPLETION OF THE WORK. DO NOT START THE WORK UNTIL
SUCH CONDITIONS HAVE BEEN EXAMINED AND A COURSE OF ACTION MUTUALLY
AGREED UPON. COORDINATE LOCATION AND INSTALLATION OF PLUMBING
WORK WITH OTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES.
MODIFICATIONS DUE TO FIELD CONDITIONS SHALL BE MADE AS REQUIRED.
GENERAL PLUMBING NOTES
SAN
X X
X
1. CONSTRUCTION MATERIALS AND EQUIPMENT REMOVED SHALL BECOME
THE PROPERTY OF THE OWNER. UNWANTED CONSTRUCTION MATERIALS
AND EQUIPMENT SHALL BE LEGALLY DISPOSED OF, OFF THE SITE UNLESS
NOTED OTHERWISE.
2. CONTRACTOR SHALL NOT CONSIDER THE DEMOLITION DRAWINGS AND
NOTES TO BE ALL-INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY
TO INSPECT AND ASSESS EACH AREA AND TO FULFILL THE INTENT OF THE
WORK INDICATED BY THE CONTRACT DOCUMENTS.
3. CHECK AND VERIFY ALL CONDITIONS AT THE SITE WITHIN THE CONTRACT
LIMITS.
4. REFER TO NEW WORK DRAWINGS FOR ADDITIONAL INFORMATION
AFFECTING DEMOLITION WORK BEFORE BEGINNING WORK.
5. CONTRACTOR SHALL DISCONNECT, REMOVE AND/OR RELOCATE EXISTING
EQUIPMENT AS SHOWN OR AS MAY BECOME NECESSARY TO ACCOMPLISH
DESIRED RESULTS. NO ADDITIONAL CLAIMS SHALL BE MADE FOR
DEMOLITION WORK NOT SPECIFICALLY INDICATED OR SPECIFIED UNLESS,
IN THE ARCHITECT'S/ENGINEER'S OPINION, IT IS BEYOND THE SCOPE OF
WORK.
6. CONNECTING WORK, NEW WORK, OR EXTENSION OF EXISTING WORK
SHALL CORRESPOND IN ALL RESPECTS WITH THAT TO WHICH IT
CONNECTS, UNLESS OTHERWISE INDICATED OR SPECIFIED. EXISTING
WORK SHALL BE CUT, DRILLED, ALTERED OR TEMPORARILY REMOVED AND
REPLACED AS NECESSARY FOR THE PERFORMANCE OF THE CONTRACT.
7. PATCH ALL OPENINGS IN BUILDING CONSTRUCTION WHERE PIPING, ETC. IS
REMOVED. PATCHING SHALL BE THE SAME MATERIALS AS THE
SURROUNDING CONSTRUCTION. FINISH TO MATCH EXISTING TO THE
EXTENT POSSIBLE.
8. WHERE PIPING TO REMAIN IS SUPPORTED FROM EQUIPMENT AND/OR
PIPING BEING REMOVED, EXTEND EXISTING HANGERS OR PROVIDE NEW
HANGERS AND SUPPORTS AS REQUIRED TO RESUPPORT ITEMS FROM
THE BUILDING STRUCTURES.
9. CONTRACTOR SHALL PROVIDE AND MAINTAIN SAFETY AND DUST
BARRIERS AS REQUIRED BY HEALTH AND SAFETY REGULATIONS.
10. NO STRUCTURAL MEMBER SHALL BE CUT OR ALTERED WITHOUT
AUTHORIZATION OF THE ARCHITECT/ENGINEER.
11. COORDINATE WORK WITH THE WORK OF ALL OTHER TRADES.
12. CONTRACTOR IS RESPONSIBLE TO RESTORE DAMAGED OR DEFACED
WORK REMAINING IN PLACE TO THE EXTENT OF THE ORIGINAL CONTRACT
DOCUMENTS.
13. ITEMS NOTED TO BE REMOVED SHALL BE REMOVED IN THEIR ENTIRETY
INCLUDING, BUT NOT LIMITED TO; PIPING, CONTROLS, VALVES, AND
HANGERS. PIPING SHALL BE REMOVED BACK TO THE MAINS AND CAPPED
UNLESS OTHERWISE NOTED.
14. DEBRIS AND DEMOLISHED MATERIALS SHALL BE CLEARED FROM THE SITE
AT FREQUENT INTERVALS. DO NOT ALLOW DEBRIS TO ACCUMULATE TO
THE EXTENT THAT IT WILL INTERFERE WITH WORK OR PASSAGE OF THE
WORKMEN.
15. THE OWNER ACCEPTS NO RESPONSIBILITY FOR LOSS OR DAMAGE TO
MATERIALS OR STRUCTURES ON SITE, OR FOR THE SALVAGE VALUE OF
WHICH THE CONTRACTOR MAY HAVE REFLECTED IN HIS BID.
16. THE CONTRACTOR SHALL GIVE ADVANCE NOTICE TO THE OWNER WHEN
WORK IS TO BE PERFORMED WHICH COULD INTERRUPT SERVICES TO
OTHER AREAS. THE OWNER'S POLICY AND PROCEDURE SHALL BE
STRICTLY ADHERED TO.
17. BEFORE STARTING WORK ALL CONTRACTORS SHALL MAKE A THOROUGH
EXAMINATION OF THOSE PORTIONS OF THE STRUCTURE IN WHICH THE
WORK IS TO BE PERFORMED. CHECK ALL THE WORK ADJOINING OR AT
UNDERLYING LOCATIONS. REPORT TO THE PROFESSIONAL ANY AND ALL
CONDITIONS WHICH MAY INTERFERE WITH OR OTHERWISE EFFECT OR
PREVENT THE PROPER EXECUTION AND COMPLETION OF THE WORK. DO
NOT START THE WORK UNTIL SUCH CONDITIONS HAVE BEEN EXAMINED
AND A COURSE OF ACTION MUTUALLY AGREED UPON.
18. TAKE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO EXISTING
INTERIOR FINISHES WHEN INSTALLING NEW PLUMBING WORK. ANY
DAMAGE TO ADJACENT AREAS SHALL BE REPAIRED AND REFINISHED BY
THE PLUMBING CONTRACTOR TO MATCH EXISTING.
19. ALL CHANGES CANNOT BE DETAILED COMPLETELY ON THE DRAWINGS.
SOME REMOVALS AND RELOCATION OF EXISTING PLUMBING WORK WILL
BE NECESSARY FOR SATISFACTORY PERFORMANCE OF THIS AND OTHER
TRADES. TAKE INTO CONSIDERATION IN PROPOSAL ALL REQUIRED
CHANGES.
20. ALL WORK REQUIRING SHUT DOWN OF EXISTING SYSTEMS SHALL BE
APPROVED BY THE OWNER. SUBMIT SCHEDULE OR REQUIRED OUTAGES
TO THE OWNER FOR APPROVAL. PERFORM WORK IN A MANNER TO
MINIMIZE SHUT DOWN TIME.
21. ALL REMOVAL POINTS ARE TO BE FIELD VERIFIED MAKE ALL ADJUSTMENT
AS NECESSARY PER ACTUAL FIELD CONDITIONS.
22. THE DEMOLITION DRAWING IS PROVIDED AS A GENERAL GUIDE TO THE
REMOVAL OF MATERIALS NEEDED TO FULLY COMPLETE THIS PROJECT.
GENERAL PLUMBING DEMOLITION NOTES
C. PLUMBING INSTALLATION REQUIREMENTS
1. INSTALL ALL EQUIPMENT, FIXTURES AND MATERIAL IN STRICT ACCORDANCE
WITH RESPECTIVE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS
AND RECOMMENDATIONS. WHERE THERE IS A CONFLICT BETWEEN THE
MANUFACTURER AND THE CODE, THE CODE SHALL APPLY UNLESS THE
MANUFACTURER IS MORE RESTRICTIVE. MAINTAIN CLEARANCES FOR
CLEARANCE ACCESS TO MAINTAIN AND SERVICE EQUIPMENT, VALVES AND
CONTROL. ALL DIMENSIONS SHALL BE TAKEN FROM CERTIFIED
MANUFACTURER'S DIMENSION INSTALLATION SHEETS AND ROUGH-IN
DIMENSIONS.
2. ALL INSTALLATION AND WORK SHALL BE PERFORMED IN A NEAT, WORKMANLIKE
MANNER SO AS NOT TO DAMAGE ANY SURFACES, EQUIPMENT, OR MATERIALS.
3. ALL EQUIPMENT AND PIPING SHALL BE SUPPORTED INDEPENDENTLY OF
EQUIPMENT IN AN APPROVED MANNER FROM THE BUILDING STRUCTURE AND
INCLUDES HANGERS AND RESTRAINTS IN ACCORDANCE WITH ALL APPLICABLE
CODES AND SEISMIC RESTRAINT REQUIREMENTS. DO NOT SUSPEND FROM
OTHER PIPING, EQUIPMENT OR DUCTWORK.
4. PROVIDE PIPE ESCUTCHEONS AT ALL EXPOSED PENETRATIONS OF FLOOR,
WALLS, AND CEILINGS.
5. INSTALL SUFFICIENT UNIONS IN PIPING SYSTEMS TO ALLOW SERVICE OF ANY
CONNECTED EQUIPMENT WITHOUT BREAKING FITTINGS OR CUTTING PIPING
CONNECTIONS.
6. THE MANUFACTURER'S AND MODEL NUMBERS LISTED ON THE SCHEDULES AND
DETAILS ARE THE BASIS OF DESIGN FOR THIS PROJECT AND SHALL SET THE
MINIMUM STANDARD FOR QUALITY, CAPACITY, PERFORMANCE AND FEATURES,
AND IS NOT INTENDED TO PRECLUDE OTHER EQUAL MANUFACTURER'S
SUBMISSION FOR REVIEW.
7. ALL DIMENSIONS AND PIPE SIZES ARE IN INCHES UNLESS OTHERWISE NOTED.
8. RUN-OUTS TO EQUIPMENT AND FIXTURES SHALL BE SIZED AS INDICATED AND
INCREASED OR REDUCED AT POINT OF FINAL CONNECTION TO EQUIPMENT.
9. ALL SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH APPLICABLE CODES OR
REGULATIONS AND PROPERLY TESTED IN ACCORDANCE WITH THE SAME.
10. ANY CUTTING OR PATCHING NECESSARY TO PERMIT THE INSTALLATION OF ANY
WORK UNDER THIS CONTRACT SHALL BE THE RESPONSIBILITY OF THE
PLUMBING CONTRACTOR.
11. THE PLUMBING CONTRACTOR SHALL PROVIDE DOMESTIC WATER SHUTOFF
VALVES AT ALL TAKE OFF BRANCHES, MAINS AND AT EACH FIXTURE/EQUIPMENT
AND OUTLETS REQUIRING WATER INCLUDING SHUTOFF VALVES AT POINT OF
NEW CONNECTIONS.
12. ALL PIPING SHALL BE LOCATED AS SHOWN ON THE DRAWINGS, CONNECTING TO
ALL PLUMBING FIXTURES AND OTHER EQUIPMENT REQUIRING WATER,
SANITARY AND GAS, AND WITH OUTLETS ADJACENT TO THE EQUIPMENT
FURNISHED UNDER OTHER CONTRACTS REQUIRING CONNECTIONS.
13. ALL PIPING SHALL BE CONCEALED IN WALLS, PARTITIONS, CHASES, FURRED
SPACES OR IN HUNG CEILINGS/ABOVE CEILINGS, EXCEPT IN MECHANICAL
EQUIPMENT ROOMS AND ELSEWHERE UNLESS OTHERWISE NOTED.
14. INSTALL PIPING TO CONSERVE BUILDING SPACE AND NOT INTERFERE WITH USE
OF SPACE. ROUTE PIPING IN ORDERLY MANNER AND MAINTAIN GRADIENT.
GROUP WHENEVER PRACTICAL AT COMMON ELEVATIONS.
15. INSTALL PIPING TO ALLOW FOR EXPANSION AND CONTRACTION WITHOUT
STRESSING PIPE, JOINTS, OR CONNECTED EQUIPMENT. PROVIDE CLEARANCE
FOR INSTALLATION OF INSULATION AND ACCESS TO VALVES AND FITTINGS.
16. ALL COPPER TUBING SHALL BE CUT WITH SQUARE ENDS, AND ALL BURRS AND
FINS REMOVED. TUBING SHALL BE CAREFULLY HANDLED AND PROTECTED TO
AVOID DAMAGE. ANY PIPE CUT, DENTED OR OTHERWISE DAMAGED MUST BE
REPLACED WITH NEW PIPE BY THE CONTRACTOR.
17. THREADED-TO-SOLDERED…
This is the start of the file's text. The full file is on GovTribe.