This document is a set of drawings for the Construct Expansion of Pain and Bronchoscopy Room Project 581-23-111 at the VA Medical Center in Huntington, West Virginia. The related federal contract opportunity is Solicitation Number 36C24524B0019, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 5. The project involves constructing an expansion to the existing bronchoscopy room. The drawings provide detailed design specifications and layouts for the construction work. Key details include the project location, project number, and drawing titles covering various aspects of the construction, such as architectural, electrical, and mechanical plans. This document serves as part of the solicitation package to support the competitive bidding process for this federal contract opportunity.

View the file

Other files

File Type Posted
36C24524B0019 0002.docx DOCX document
SPECS COMBINED.pdf PDF
Huntington Bronchoscopy Revised_S2 Response.pdf PDF
Site Visit IFB Bronch and Pain Room.pdf PDF
36C24524B0019 0001.docx DOCX document
WD P07 current.pdf PDF
36C24524B0019_1.docx DOCX document
VHA ICRA signed .pdf PDF
Spec Combined 5 10 24 100CD _01 Revised.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Location

Issue Date

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

VAMC HUNTINGTON

Project Director

Revisions: Date:

VA FORM

08 -

A

F ile

P a th

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Stewart C. Cluck 717.850.2515

CONSTRUCTION

DOCUMENTS

600 North Hartley Street, Suite 152 York, PA 17404

1S

HOMCO Renaissance and

GPI-Renaissance JV 7510 Langport Ct.

Hanover, MD 21076

410-340-8284

5001 LOUISE DRIVE,

MECHANICSBURG PA 17055

T 717-691-1340

1 - REVIEW COMMENTS 05/10/2024

GI-000

COVER SHEET

JEGSCC03/20/2024

581-23-111EXPAND PAIN AND

BRONCHOSCOPY

PROCEDURE ROOM

VA MEDICAL CENTER HUNTINGTON WV

BUILDING 1S

HUNTINGTON, WEST VIRGINIA 25704

EXPAND PAIN AND BRONCHOSCOPY PROCEDURE ROOM

A/E CONTRACT NUMBER VA-36C 24519 D0021

CONTRACT NUMBER VA-36C 24519 D0021

PROJECT 581-23-111

VA WEST VIRGINIA HEALTH CARE SYSTEM

1540 SPRING VALLEY DRIVE, HUNTINGTON

WEST VIRGINIA

SECTION CALLOUT

EXTERIOR ELEVATION CALLOUT

INTERIOR ELEVATION CALLOUT

XX

ROOM NAME

ROOM NUMBER

DOOR TAG

REVISION DELTA

ELEVATION DESIGNATION

WALL / PARTITION TAG

COLUMN GRID DESIGNATION

LEVEL NAME

DATUM

SCALE

NAME

LEVEL

VIEW TITLE

WINDOW TAG

CENTERLINE

CLDETAIL CALLOUT

VIEW NUMBER

SHEET NUMBER

ROOM TAG

SYMBOL LEGEND

VIEW TITLE

SCALE: x/x" = x' - x"

A101

ROOM NAME

P###

A000

# VIEW NUMBER

SHEET NUMBER

A000

1 VIEW NUMBER

SHEET NUMBER

A000

1 VIEW NUMBER

SHEET NUMBER

ROUGH DIMENSION

FINISH DIMENSION

A101

XXXXXX

X' - X"

DEMOLITION KEYNOTE

D#

W#

AB ANCHOR BOLT(S), AUGER BORING

ACI AMERICAN CONCRETE INSTITUTE

ACT ACOUSTICAL CEILING TILE

ADA AMERICANS WITH DISABILITIES ACT

ADDL ADDITIONAL

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION

AJC ASPHALTIC CONCRETE

ALT ALTERNATE / ALTERNATING

APPROX APPROXIMATE(LY)

ARCH ARCHITECT(URAL)

ASSOC ASSOCIATED / ASSOCIATION

ASTM AMERICAN SOCIETY OF TESTING MATERIALS

ATC AUTOMATIC TEMPERATURE CONTROL

AWP ACOUSTICAL WALL PANEL

BC BOTTOM OF CURB

BFF BELOW FINISHED FLOOR

BFG BELOW FINISHED GRADE

BKT BRACKET

BLDG BUILDING

BLVD BOULEVARD

BM BENCH MARK

BOB BOTTOM OF BEAM

BOF BOTTOM OF FOOTING

BOJ BOTTOM OF JOIST

BOS BOTTOM OF STEEL

BOTT BOTTOM

BRG BEARING

BSMT BASEMENT

BUR BUILT-UP ROOF

CART CARTWAY

CCT CUBICLE CURTAIN TRACK

CF CUBIC (FOOT) FEET

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CI CAST IRON

CIP CAST IRON PIPE

CJ CONTRACTION / CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLR CLEARANCE / CLEAR

CM CORRUGATED METAL

CMP CORRUGATED METAL PIPE ARCH

CMU CONCRETE MASONRY UNIT

CNTR COUNTER

CO CLEANOUT

COB CENTER OF BEAM

COL COLUMN

CONC CONCRETE

CONF CONFERENCE

CONST CONSTRUCTION

CONT CONTINUOUS

CORRG CORRUGATED

CPP CORRUGATED PLASTIC PIPE

CPT CARPET

CR CLASSROOM

CUH CABINET UNIT HEATER

DBL DOUBLE

DH DRILL HOLE

DIAG DIAGONAL

DIFF DIFFUSER

DIM DIMENSION

DP DAMPROOF(ING)

DS DOWN SPOUT

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EF EACH FACE

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

ENGR ENGINEER(ING)

EOF EDGE OF FLOOR

EOS EDGE OF SLAB

EQUIP EQUIPMENT

EST ESTIMATE

EW EACH WAY

EX EXISTING

FBD FIBER BOARD

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FFE FINISHED FLOOR ELEVATION

FIN FINISH(ED)

FIX FIXTURE

FM FACTORY MANUAL

FP FULL PENETRATION WELD

FPR FIRE PROOF(ING)

FTG FOOTING

FURN FURNITURE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GFI GROUND FAULT INTERRUPTER

GLBLK GLAZED BLOCK

GPM GALLONS PER MINUTE

GYM GYMNASIUM

GWB GYPSUM WALLBOARD

H/ V HEATING AND VENTILATING

HB HOSE BIB

HC HEATING CONTRACTOR

HM HOLLOW METAL

HORIZ HORIZONTAL

HT HEIGHT

HVAC HEATING/ VENTILATING/ AIR CONDITIONING

HW HOT WATER

HYD HYDRANT

IBC INTERNATIONAL BUILDING CODE

INCL INCLUDE/ INCLUSIVE

INSUL INSULATE/ INSULATION

JAN JANITOR

KSI KIPS PER SQUARE INCH

LAB LABORATORY

LAV LAVATORY

LB(S) POUND(S)

LDY LAUNDRY

LF LINEAL FEET

LH LEFT HAND

LHR LEFT HAND REVERSE

LIB LIBRARY

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

MAS MASONRY

MAX MAXIMUM

MB MAILBOX

MC MECHANICAL CONTRACTOR

MECH MECHANIC(AL)

MED MEDICAL

MEP MECHANICAL, ELECTRICAL, PLUMBING

MFD MANUFACTURED

MFR MANUFACTURE(R)

MIN MINIMUM

MISC MISCELLANEOUS

MM MILLIMETER

MO MASONRY OPENING

MTD MOUNTED

MTG MOUNTING

NA NOT APPLICABLE

NEC NATIONAL ELECTRIC CODE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NTS NOT TO SCALE

OC ON CENTER(S)

OPNG OPENING(S)

OPP OPPOSITE

PC PLUMBING CONTRACTOR

PCF POUNDS PER CUBIC FOOT

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PLWD PLYWOOD

POLYISO POLYISOCYANURATE

PREFAB PREFABRICATED

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PTL PRESSURE TREATED LUMBER

PTD PAINTED

RA RETURN AIR

RC REINFORCED CONCRETE

RD ROOF DRAIN

REBAR REINFORCING BAR

REG REGISTER

REINF REINFORCED/REINFORCING

RH RIGHT HAND

RHR RIGHT HAND REVERSE

RL RAIN LEADER

RO ROUGH OPENING

RWC RAIN WATER CONDUCTOR

SA SUPPLY AIR

SECT SECTION(AL)

SJ SAW JOINT

SLV SHORT LEG VERTICAL

SOG SLAB ON GRADE

SP SOUNDPROOF

SPAND SPANDREL

SPECS SPECIFICATIONS

SPR SPRINKLER(ED)

SQ SQUARE

SF SQUARE FOOT/FEET

SI SQUARE INCH(ES)

SS STAINLESS STEEL

STC SOUND TRANSMISSION CLASS

STD STANDARD

STER STERILIZER

STOR STORAGE

STRUCT STRUCTURAL

SV SHEET VINYL

SW STORMWATER

T&B TOP AND BOTTOM

T&G TONGUE & GROOVE

TC TOP OF CURB

TEL TELEPHONE

TEMP TEMPERED

TG TOP OF GRATE

TH THICK/THICKNESS

THRU THROUGH

TOB TOP OF BEAM

TOF TOP OF FOOTING

TOJ TOP OF JOIST

TOS TOP OF STEEL

TW TOP OF WALL

TYP TYPICAL

UC UNDERCUT (DOORS)

UCC UNIFORM CONSTRUCTION CODE

UG UNDERGROUND

UNO UNLESS NOTED OTHERWISE

VB VINYL BASE

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VOL VOLUME

VT VINYL TREAD

VWC VINYL WALL COVERING

WC WATER CLOSET

WCO WALL CLEAN OUT

WDW WINDOW

WGL WIRE GLASS

WM WOOD MOLDING

WP WEATHERPROOF

WP WORK POINT

WSL WATER SURFACE ELEVATION

WT WEIGHT

WWF WELDED WIRE FABRIC

ABBREVIATIONS

BRONCHOSCOPY

ROOM - BUILDING

1S - 3RD FLOOR -

ROOM 3B-147

C O

U R

A G

E D

R

IV

E

COURAGE DRIVE

HONOR HI ROAD

HERSHEL "WOODY" WILLIAMS

VA MEDICAL CENTER

Location

Issue Date

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

VAMC HUNTINGTON

Project Director

Revisions: Date:

VA FORM

08 -

A

F ile

P a th

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Stewart C. Cluck 717.850.2515

CONSTRUCTION

DOCUMENTS

600 North Hartley Street, Suite 152 York, PA 17404

1S

HOMCO Renaissance and

GPI-Renaissance JV 7510 Langport Ct.

Hanover, MD 21076

410-340-8284

5001 LOUISE DRIVE,

MECHANICSBURG PA 17055

T 717-691-1340

1 - REVIEW COMMENTS 05/10/2024

GI-001

GENERAL INFORMATION

JEGSCC03/20/2024

581-23-111EXPAND PAIN AND

BRONCHOSCOPY

PROCEDURE ROOM

PN

N

LOCATION MAP/IMAGE

SHEET LIST

SHEET NAME

GENERAL

GI-000 COVER SHEET

GI-001 GENERAL INFORMATION

ARCHITECTURAL

A-001 ICRA PLAN

A-101 DEMO / NEW WORK PLANS

A-501 DETAILS

STRUCTURAL

S-001 OVERHEAD EQUIPMENT SUPPORT

MECHANICAL

M-001 MECHANICAL LEGEND, NOTES, & ABBREVIATIONS

M-101 THIRD FLOOR MECHANICAL DEMOLITION & NEW WORK PLANS

M-201 MECHANICAL DETAILS AND SCHEDULES

PLUMBING

FA/PL-001 PLUMBING LEGEND, NOTES, SCHEDULES & ABBREVIATIONS

PL-101 THIRD FLOOR PLUMBING DEMOLITION & NEW WORK PLANS

PL-201 PLUMBING DETAILS

ELECTRICAL

E-001 ELECTRICAL SYMBOLS & ABBREVIATIONS

E-002 ELECTRICAL DEMOLITION AND NEW WORK NOTES

E-101 POWER AND LIGHTING NEW WORK PLANS

E-601 ELECTRICAL PANEL SCHEDULES

ED-101 POWER AND LIGHTING DEMOLITION PLANS

PN

N

LOCATION

BRONCHOSCOPY

ROOM

3B-147

3B-149 3B-165

3B-168

3B-169

3B-172

3B-146

AREA OF WORK

EXISTING GROUND FLOOR PLANEXISTING THIRD FLOOR PLAN

AREA OF WORK

WASTE PATH

WASTE PATH

Location

Issue Date

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

VAMC HUNTINGTON

Project Director

Revisions: Date:

VA FORM

08 -

A

F ile

P a th

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Stewart C. Cluck 717.850.2515

CONSTRUCTION

DOCUMENTS

600 North Hartley Street, Suite 152 York, PA 17404

1S

HOMCO Renaissance and

GPI-Renaissance JV 7510 Langport Ct.

Hanover, MD 21076

410-340-8284

5001 LOUISE DRIVE,

MECHANICSBURG PA 17055

T 717-691-1340

1 - REVIEW COMMENTS 05/10/2024

A-001

ICRA PLAN

JEGSCC03/20/2024

581-23-111EXPAND PAIN AND

BRONCHOSCOPY

PROCEDURE ROOM

SCALE: 1/8" = 1'-0"A-001

ICRA PLAN2

A-001

ENVIRONMENTAL WASTE PATH PLAN1

1 - DOORS TO BRONCHOSCOPY ROOM BEYOND

DOUBLE DOORS / SERVICE ELEVATORS ON RIGHT

2 - SERVICE ELEVATORS 3 - EXIT OUT OF ELEVATORS ON GROUND FLOOR,

MAKE A RIGHT

4 - LOOKING TO RIGHT AT AMBULANCE BAY 5 - LOOKING OUT AMBULANCE BAY AT DUMPSTER LOCATION 6 - DUMPSTER LOCATION

THIRD FLOOR LEVEL THIRD FLOOR LEVEL GROUND FLOOR LEVEL GROUND FLOOR LEVEL GROUND FLOOR LEVEL

BRONCHOSCOPY

ROOM

3B-147

3B-149 3B-165

3B-169

3B-172

3B-146

E1

A

O R

T A

B L E

D1

C-ARM *

C-ARM

MONITOR *

A-101

CORNER GUARDS

P1

P1

P1

P1

P1

P1

P2

P1

P1

5' - 0"

* EQUIPMENT PROVIDED BY VA

EPOXY FLOORING

PARTITION TYPES

EXISTING WALL

P1

5/8" GYPSUM BOARD WITH LEAD-LINED

(1/32" LEAD SHEET)

3 5/8" METAL STUD

P2

HYGIENIC VINYL

WALL COVERING

HYGIENIC VINYL WALL COVERING

5/8" TYPE 'X' GYPSUM BOARD

5/8" GYPSUM BOARD WITH LEAD-LINED

(1/32" LEAD SHEET)

BRONCHOSCOPY

ROOM

3B-147

3B-146

3B-149 3B-165

3B-169

3B-172

E1

A

7' - 11 3/4"A.F.F.

2' - 4"

C E

IL

IN

G T

R A

C K

ALIGN

ACCESS HATCH

( 16" X 16" MIN )

ACCESS HATCH

( 16" X 16" MIN )

D6

REFER TO MEP DRAWINGS FOR DEMOLITION

OF ALL MEP EQUIPMENT

D5

E1

A

D4

D3

D3

D1

D2

3B-147 3B-169

3B-165

3B-172

3B-146

3B-149

3B-148

REMOVE EXISTING VCT TILE, RUBBER BASE AND ALL ASSOCIATED COMPONENTS. PATCH

AND REPAIR ADJACENT SURFACES AND PREPARE FOR NEW WORK

REMOVE EXISTING VINYL SHEET FLOORING AND ALL ASSOCIATED COMPONENTS. PATCH

AND REPAIR ADJACENT SURFACES AND PREPARE FOR NEW WORK

REMOVE EXISTING DOOR AND FRAME. PATCH AND REPAIR ADJACENT SURFACES AND

PREPARE FOR NEW WORK.

REMOVE EXISTING ACT CEILING SYSTEM AND ALL ASSOCIATED HARDWARE.

PATCH AND PREPARE ADJACENT SURFACES FOR NEW WORK.

REMOVE EXISTING HARD CEILING SYSTEM AND ALL ASSOCIATED HARDWARE.

PATCH AND PREPARE ADJACENT SURFACES FOR NEW WORK.

REMOVE EXISTING WALL AND ALL ASSOCIATED COMPONENTS. CAP OFF PLUMBING

CONNECTIONS AND PREPARE ADJACENT SURFACES FOR NEW WORK.

D1

D2

D3

D4

D5

D6

HM-1

FINISH FLOOR

2"

2"

FN

FINISH FLOOR

6"6"

PANEL 1 PANEL 2

LITE PANEL

SUPPORT - TYP

KEYNOTE LEGEND

STAINLESS STEEL COUNTERTOP WITH INTEGRAL 4"

BACKSPLASH

STAINLESS STEEL DROP IN SINK

Location

Issue Date

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

VAMC HUNTINGTON

Project Director

Revisions: Date:

VA FORM

08 -

A

F ile

P a th

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Stewart C. Cluck 717.850.2515

CONSTRUCTION

DOCUMENTS

600 North Hartley Street, Suite 152 York, PA 17404

1S

HOMCO Renaissance and

GPI-Renaissance JV 7510 Langport Ct.

Hanover, MD 21076

410-340-8284

5001 LOUISE DRIVE,

MECHANICSBURG PA 17055

T 717-691-1340

1 - REVIEW COMMENTS 05/10/2024

A-101

DEMO / NEW WORK PLANS

JEGSCC03/20/2024

581-23-111EXPAND PAIN AND

BRONCHOSCOPY

PROCEDURE ROOM

DEMOLITION KEY NOTES

SCALE: 1/4" = 1'-0"A-101

PLAN - SHOWING EQUIPMENT2

FLOOR FINISH LEGEND

SCALE: 1/4" = 1'-0"A-101

REFLECTED CEILING PLAN3

SCALE: 1/4" = 1'-0"A-101

PLAN - DEMOLITION1

DOOR AND FRAME SCHEDULE

NUMBER

PANEL

THICKNESS

PANEL

FIRE RATING

FRAME HARDWARE

REMARKSWIDTH HEIGHT TYPE MATERIAL GLAZING TYPE MATERIAL SET

GROUND FLOOR

D1 5' - 4" 7' - 0" 1 3/4" WD X-RAY SHIELDED

WINDOW FRAME w/

X-RAY LEAD GLASS

1/2 HR -

SMOKE ONLY

HM1 HM 001 LEAD-LINED DOOR SYSTEM: PANEL 1: 46" PANEL 2:

18"

DOOR FRAME TYPES DOOR PANEL TYPES

ROOM FINISH SCHEDULE

ROOM FLOOR BASE

CEILING

FINISH

WALLS

REMARKSNUMBER NAME FINISH FINISH

NORTH EAST SOUTH WEST

FINISH FINISH FINISH FINISH

GROUND FLOOR

3B-147 BRONCHOSCOPY ROOM EPOXY

COATING

EPOXY WRAP

UP

GYP PNT /

LEAD-LINED

PNT /

LEAD-LINED

PNT /

LEAD-LINED

PNT /

LEAD-LINED

PROVIDE CORNER GUARDS

WHERE INDICATED ON PLANS

SCALE: 1/2" = 1'-0"A-101

CASEWORK ELEVATION4

FN

NOTE: ENSURE NEW LEAD-LINED SHEETS ARE

IN CONTACT WITH EXISTING WALLS AND NO GAPS

ARE PRESENT. REFER TO SPECS FOR ADDITIONAL

INFORMATION

NOTE: FURR OUT EXISTING WALLS AS REQUIRED TO

ENSURE LEAD-LINE BY BOARD AND GYPSUM BOARD

FACES ALIGN

X-RAY SHIELDED FRAMES w/ X-RAY LEAD GLASS AND DOOR PANEL

X-RAY SHIELDED DOOR (CONTINUOUS LEAD SHEET CENTER WITHIN DOOR PANEL)

NOTE: ALL EXISTING EQUIPMENT WITHIN ROOMS TO BE RE-LOCATED FOR CONSTRUCTION.

COORDINATE WITH VA STAFF IN CHARGE.

Set #001 - WD PAIR

DOORS:

6 HINGES A8111 FBB168 4.5" X 4.5" US26D ST

1 DUSTPROOF STRIKE L04021 3911 626 TR

2 FLUSH BOLT L04081/L04251 3917-12 626 TR

1 DEADBOLT E06091 48H-7R 626 BE

1 PULL PLATE 1018 3 ½ X 15 (INSIDE ROOM) 630 TR

1 PUSH PLATE 1820 3 ½ X 15 (OUTSIDE ROOM) 630 TR

1 CLOSER CO2011/CO2021 HD8016 AF80P 689 BE

2 MOP PLATE J103 KM050 4" X 1" LDW B4E-HEAVY-KP CSK 630 TR

2 ARMOR PLATE J102 KA050 34" X 2" LDW B4E-HEAVY-KP CSK 630 TR

2 WALL BUMPER L02251 1270CV 626 TR

2 DOOR SILENCERS L03011 1229A GREY TR

OPTION LIST

Code Description

1/4-20 SSMS/EA STAINLESS MACHINE SCREWS/EXPANSION ANC.

54 CONCEALED WIRES (4)

B4E-HEAVY-KP BEVELED 4 EDGES - KICK PLATES

C QUICK CONNECT WIRING OPTION

C QUICK CONNECT WIRING SYSTEM

CSK COUNTER SINKING OF KICK AND MOP PLATES

EPT PREP EPT PREP (FULL MORTISE)

FL FIRE EXIT HARDWARE

LAR LENGTH AS REQUIRED

LDW LESS DOOR WIDTH

MLR MOTORIZED LATCH RETRACTION

RQE REQUEST TO EXIT

VIB DOUBLE VISUAL INDICTOR OPTION

WTS WEATHERIZED TOUCHBAR MONITORING SWITCH

MANUFACTURER LIST

CODE NAME

BE BEST ACCESS SYSTEMS

BY BY RELATED SECTION

DM DORMA DOOR CONTROLS

NA NATIONAL GUARD

PR BEST PRECISION EXIT DEVICES

RC RCI

ST BEST HINGES AND SLIDING

TR TRIMCO

DOOR HARDWARE

DOOR

ASSEMBLY

TRANSITION STRIP

EPOXY FLOORING

SYSTEM (RES-IV)

EXISTING FLOOR

INTERIORINTERIOR

DOOR ASSEMBLY

HOLLOW METAL FRAME

INTERIORINTERIOR

REFER TO WALL TYPE P1

EXISTING WALL

DOOR ASSEMBLY

HOLLOW METAL FRAME

INTERIORINTERIOR

REFER TO WALL TYPE P1

EXISTING WALL

SHIM W/ BACKER ROD +

SEALANT (BOTH SIDES)

INTERIORINTERIOR

REFER TO WALL TYPE P1

EXISTING WALL

5/8" TYPE 'X' GYPSUM BOARD

METAL CHANNEL GYPSUM

BOARD SUSPENSION SYSTEM

Location

Issue Date

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

VAMC HUNTINGTON

Project Director

Revisions: Date:

VA FORM

08 -

A

F ile

P a th

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Stewart C. Cluck 717.850.2515

CONSTRUCTION

DOCUMENTS

600 North Hartley Street, Suite 152 York, PA 17404

1S

HOMCO Renaissance and

GPI-Renaissance JV 7510 Langport Ct.

Hanover, MD 21076

410-340-8284

5001 LOUISE DRIVE,

MECHANICSBURG PA 17055

T 717-691-1340

1 - REVIEW COMMENTS 05/10/2024

A-501

DETAILS

JEGSCC03/20/2024

581-23-111EXPAND PAIN AND

BRONCHOSCOPY

PROCEDURE ROOM

SCALE: 3" = 1'-0"A-501

DOOR DETAIL - SILL3

SCALE: 3" = 1'-0"A-501

DOOR DETAIL - JAMB2

SCALE: 3" = 1'-0"A-501

DOOR DETAIL - HEAD1

SCALE: 3" = 1'-0"A-501

CEILING DETAIL4

DUCTWORK SYMBOLS

SUPPLY DIFFUSER 1-WAY BLOW

SUPPLY DUCT (SECTION)

RETURN, EXHAUST, OR TRANSFER

DUCT (SECTION)

EXHAUST DUCT (SECTION)

DRAWING SYMBOLS

DETAIL DESIGNATION OR ENLARGED PLAN

X

X HVAC DRAWING NUMBER WHERE DETAIL IS SHOWN

X

XX

SECTION DESIGNATION

HVAC DRAWING NUMBER WHERE SECTION IS SHOWN

HVAC DRAWING NUMBER WHERE TAKEN FROM

X

X

EQUIPMENT TAG

TAG NUMBER

POINT OF NEW CONNECTION

POINT OF DISCONNECTION

X-X

T

S

THERMOSTAT

TEMPERATURE SENSOR

XXX

GRILLE/REGISTER/DIFFUSER

GRILLE/REGISTER/DIFFUSER TAG

GRILLE/REGISTER/DIFFUSER NUMBER

BALANCING CFM

AIR FLOW DIRECTION

UNIT HEATER UH

X

DUCTWORK SYMBOLS

DOUBLE LINE SINGLE LINE

DUCT WIDTH x DEPTH

ACOUSTICAL DUCT LINING

AD ACCESS DOOR

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFR ABOVE FINISHED ROOF

AHU AIR HANDLING UNIT

AP ACCESS PANEL

ARCH ARCHITECTURE

ATC AUTOMATIC TEMPURATURE CONTROL

ATM ATMOSPHERE

AUX AUXILIARY

AVG AVERAGE

AWG AMERICAN WIRE GAUGE

BC BACKWARD CURVE

BDD BACKDRAFT DAMPER

BHP BRAKE HORSEPOWER

BI BACKWARD INCLINED

BOD BOTTOM OF DUCT

BOJ BOTTOM OF JOIST

BOS BOTTOM OF STEEL

BTU BRITISH THERMAL UNIT

BTUH BTU PER HOUR

CC COOLING COIL

CCW COUNTER CLOCKWISE

CFM CUBIC FEET PER MINUTE

C&I CONTROLS AND INSTRUMENTATION

CLG CEILING

CMU CONCRETE MASONARY UNIT

COND CONDENSATE

CONN CONNECTION

CONT CONTINUATION

CORR CORRIDOR

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONTROL VALVE

CU FT CUBIC FEET

CVS CONTROL VALVE STATION

CVT CONVERTER

CW CLOCKWISE

D DIFFUSER OR REGISTER

dB DECIBEL, RE 10 WATT

DBT DRY BULB TEMPURATURE (°F)

DDC DIRECT DIGITAL CONTROL

DEG DEGREE FAHRENHEIT (°F)

DIA DIAMETER

DIM DIMENSION

DN DOWN

DP DEW POINT TEMPURATURE (°F)

DX DIRECT EXPANSION

DWG DRAWING

E EXHAUST

EA EXHAUST AIR

EAT ENTERING AIR TEMPURATURE (°F)

EC ELECTRICAL CONTRACTOR

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

ELEV ELEVATION

EMS ENERGY MANAGEMENT SYSTEM

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPURATURE (°F)

EUH ELECTRIC UNIT HEATER

F FILTER

FA FACE AREA

FC FORWARD CURVE

FLR FLOOR

FP FIRE PROTECTION

FPM FEET PER MINUTE

FRP FIBERGLASS REINFORCED POLYMER

FT FEET

FVEL FACE VELOCITY

GA GAUGE OR GAGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GUH GAS UNIT HEATER

HC HEATING COIL

HG MERCURY

HP HORSEPOWER

HR HOUR

ID INSIDE DIAMETER

IN INCH

KW KIOWATTS

KWH KILOWATT HOUR

L LOUVER

LAT LEAVING AIR TEMPURATURE (°F)

LBS POUNDS

LF LINEAR FEET

LWT LEAVING WATER TEMPURATURE (°F)

M MOTOR OPERATED

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MC MECHANICAL CONTRACTOR

MCC MOTOR CONTROL CENTER

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MMBH 1,000,000 BTUH

NA NOT APPLICABLE

NC NOISE CRITERIA, dB RE 20 uPa

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NPS NOMINAL PIPE SIZE

NPT NOMINAL PIPE THREAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OAD OUTSIDE AIR DAMPER

OD OUTSIDE DIAMETER

OZ OUNCE

PTAC PACKAGE TERMINAL AIR CONDITIONER

PC PLUMBING CONTRACTOR

PD PRESSURE DROP

PDI PRESSURE DIFFERENTIAL INDICATOR

PH PHASE

PPM PART PER MILLION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA PSI, ABSOLUTE

PSIATM PSI, ATMOSPHERE

PSIG PSI, GAUGE

QTY QUANTITY

R REGISTER

RA RETURN AIR

RC ROOM CRITERIA, dB RE 20 uPa

RF RETURN/RELIEF AIR FAN

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RPM REVOLUTIONS PER MINUTE

RTU ROOF TOP UNIT

S SMOKE DETECTOR

SA SUPPLY AIR

SAF SUPPLY AIR FAN

SCFM CFM, STANDARD CONDITIONS

SEER SEASONAL ENERGY EFFICIENY RATIO

SENS SENSIBLE

SF SQUARE FEET

SP STATIC PRESSURE (IN.WG.)

SPEC SPECIFICATION

SPS STATIC PRESSURE SENSOR

SQ SQUARE

STD STANDARD

T THERMOSTAT

TA TRANSFER AIR

TD TEMPURATURE DIFFERENCE (°F)

TEMP TEMPURATURE

TG TRANSFER GRILL

TOD TOP OF DUCT

TOP TOP OF PIPE

TOS TOP OF STEEL

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TYP TYPICAL

UC UNDERCUT

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

UV UNIT VENTILATOR

V VALVE

VA VOLT-AMPERE

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VFV VAV, WITH FAN VOL VOLUME

VVT VARIABLE VOLUME VARIBLE TEMPURATURE

W WATT

WB WET BULB TEMPURATURE (°F)

WMS WIRE MESH SCREEN

W/ WITH

MECHANICAL ABBREVIATIONS PIPING SYMBOLS

GENERAL

(NAME) E EXISTING PIPE

ROUND DUCT

INCLINED RISE, IN DIRECTION

OF AIR FLOWR

R

D D

INCLINED DROP, IN

DIRECTION OF AIR FLOW

FLEXIBLE DUCT CONNECTION

ELBOW WITH TURNING VANES

STANDARD RADIUS ELBOW

DAMPER IN WALL

OR FLOORX

SUPPLY REGISTER, DIFFUSER,

OR GRILLE (WALL TYPE)

RETURN GRILLE/REGISTER

RUNOUT TO ROUND SUPPLY

DIFFUSER

RUNOUT TO SQUARE SUPPLY

DIFFUSER

BOD

BOD

BACKDRAFT DAMPER

MOTOR OPERATED DAMPER

M M

MANUAL VOLUME DAMPER

VD

VD

S

S

SMOKE DETECTOR FURNISHED

AND WIRED BY THE E.C.,

INSTALLED BY THE M.C

X

F

S

FS

FIRE

SMOKE

FIRE/SMOKE

DIRECTION OF FLOW

AIR CONDITIONING & REFRIGERATION

RL

RS

REFRIGERANT LIQUID

REFRIGERANT SUCTION

1. CODES AND STANDARDS LISTED IN SPECIFICATIONS AND DRAWINGS ARE MINIMUM STANDARDS. WHERE REQUIREMENTS ON THE DRAWINGS OR SPECIFICATIONS EXCEED THE MINIMUM CODE REQUIREMENTS, THE DRAWINGS OR SPECIFICATIONS SHALL GOVERN.

2. THE POWER RATING OF MOTORS AND OTHER MECHANICAL EQUIPMENT AND THE ELECTRICAL CHARACTERISTICS OF ELECTRICAL SYSTEMS SERVING THEM HAVE BEEN ESTABLISHED AS MINIMUMS WHICH ALLOW THAT EQUIPMENT TO FUNCTION PROPERLY TO PRODUCE THE REQUIRED CAPACITIES. POWER RATINGS INCLUDE REASONABLE SAFETY FACTORS TO ACCOMMODATE COMMON DIFFERENCES BETWEEN DESIGN PARAMETERS AND FIELD CONSTRUCTION PRACTICES. EQUIPMENT WITH POWER RATINGS LESS THAN THOSE INDICATED ON THE DRAWINGS SHALL NOT BE PERMITTED.

3. REASONABLE EFFORTS HAVE BEEN MADE TO COORDINATE ELECTRICAL REQUIREMENTS OF MECHANICAL EQUIPMENT WITH THE ELECTRICAL SYSTEMS SERVING THAT EQUIPMENT. DIFFERENCES AMONG MANUFACTURERS OF MECHANICAL EQUIPMENT MAKE IT IMPOSSIBLE TO PRODUCE A SINGLE ELECTRICAL DESIGN WHICH WILL SATISFY THE VARYING ELECTRICAL REQUIREMENTS OF THE THOSE MANUFACTURERS. CONSEQUENTLY, THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL REQUIREMENTS OF THE MECHANICAL EQUIPMENT ACTUALLY FURNISHED ON THIS PROJECT WITH THE EQUIPMENT ACTUALLY FURNISHED ON THIS PROJECT AND PROVIDE ELECTRICAL SYSTEMS REQUIRED BY THAT EQUIPMENT. THIS COORDINATION EFFORT SHALL BE COMPLETED PRIOR TO THE INSTALLATION OF EITHER THE MECHANICAL EQUIPMENT OR THE ELECTRICAL SYSTEMS SERVING THAT EQUIPMENT. ELECTRICAL SYSTEM REVISIONS REQUIRED TO COORDINATE WITH THE MECHANICAL EQUIPMENT ACTUALLY FURNISHED SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

4. DRAWINGS INDICATE GENERAL LOCATIONS OF FIXTURES, APPARATUS, EQUIPMENT, PIPING, AND DUCTWORK. CHANGES ON LOCATION SHALL BE MADE TO ACCOMMODATE EXISTING OR NEW BUILDING CONDITIONS AND COORDINATION WITH OTHER TRADES, INCLUDING HVAC, PLUMBING, ELECTRICAL, FIRE PROTECTION, STRUCTURAL, AND ARCHITECTURAL, SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER.

5. PROVIDE ACCESS TO EQUIPMENT AND PORTIONS OF BUILDING SYSTEMS REQUIRING SERVICE.

6. DO NOT INSTALL DUCTWORK, PIPING, OR EQUIPMENT IN ELECTRICAL ROOMS, ELEVATOR ROOMS, OR ELEVATOR SHAFTS, UNLESS EXPLICITLY INDICATED ON THE

DRAWINGS. PIPING, DUCTWORK, AND EQUIPMENT (SWITCHGEAR, SWITCHBOARDS, PANELS, MOTOR CONTROL CENTERS, VARIABLE FREQUENCY DRIVES, TRANSFORMERS, OR STARTERS) SHALL NOT BE INSTALLED DIRECTLY ABOVE OR 42" IN FRONT OF ELECTRICAL EQUIPMENT FROM THE FLOOR TO THE STRUCTURE

ABOVE.

7. FOR RENOVATION PROJECTS WHERE THE BUILDING IS OCCUPIED, SCHEDULE WORK SO EXISTING SYSTEMS WILL BE INTERRUPTED FOR A MINIMUM AMOUNT OF TIME. OBTAIN APPROVAL FROM THE OWNER AND ARCHITECT AT LEAST 14 DAYS PRIOR TO INTERRUPTION OR CONNECTION. NO ALLOWANCE WILL BE MADE FOR

LACK OF KNOWLEDGE OF EXISTING CONDITIONS.

8. UNLESS INDICATED OTHERWISE, EQUIPMENT AND MATERIALS SHALL BE NEW AND OF THE CUSTOMARY STANDARD AND QUALITY FURNISHED BY THE DESIGNATED

MANUFACTURER FOR THAT CATALOG NUMBER.

9. FOR EXISTING SYSTEMS, REMOVE EXPOSED PIPING AND DUCTWORK RENDERED USELESS DUE TO CHANGES. PLUG OUTLETS IN PIPING. CAP AND SEAL OPENINGS

IN DUCTWORK AND SEAL AIRTIGHT.

10. AIR SYSTEMS SHALL OPERATE WITHOUT AERODYNAMIC NOISE GENERATED FROM FAULTY INSTALLATION OF DUCTWORK, DIFFUSERS, OR ANY PORTION OF THE AIR

DISTRIBUTION SYSTEM.

11. SUPPORT PIPING INDEPENDENTLY OF EQUIPMENT. HANGER RODS SHALL BE SUSPENDED FROM THE STRUCTURE. DO NOT SUSPEND FROM OTHER PIPING, CONDUIT, EQUIPMENT, OR DUCTWORK.

12. ALL WORK REFERENCED UNDER DIVISION 23 SHALL BE DONE BY THE MECHANICAL CONTRACTOR.

13. ALL EXISTING DUCTWORK, PIPING, EQUIPMENT, SYSTEMS, AND ASSOCIATED APPURTENANCES TO BE DEMOLISHED, NOT CONCEALED WITHIN AN INACCESSIBLE

CHASE OR WALL, SHALL BE REMOVED IN THEIR ENTIRETY. ANY OF THESE ITEMS ABANDONED AS A RESULT OF ALL NEW WORK SHALL BE CAPPED APPROPRIATELY AND LABELED INDICATING THE ITEMS' PREVIOUS SERVICE AND DESTINATION/ORIGINATION. THE GOVERNMENT, ARCHITECT, OR ENGINEER SHALL BE NOTIFIED OF

ANY ABANDONED ITEMS.

GENERAL MECHANICAL NOTES:

1. INSTALL PIPING TO ALLOW ACCESS FOR VALVES, AIR VENTS, AND EQUIPMENT REQUIRING ACCESSIBILITY, AND TO PROVIDE MAXIMUM

HEADROOM.

2. PROVIDE OFFSETS TO MAINTAIN CEILING HEIGHT AND TO COORDINATE WITH OTHER TRADES.

3. INSTALL VALVES IN HORIZONTAL PIPING WITH VALVE STEMS AT OR ABOVE THE PIPE CENTERLINE.

4. ARRANGE PIPING FOR VENTING OF AIR AND DRAINAGE OF ENTIRE SYSTEM.

5. REPLACE EXISTING MECHANICAL PIPE HANGERS AND PIPE FLOOR SUPPORTS WITH NEW TO SERVE EXISTING MECHANICAL PIPING TO REMAIN

IN ORDER TO ACCOMMODATE THE INSTALLATION OF ALL NEW EQUIPMENT, SYSTEMS, AND DEVICES. MECHANICAL CONTRACTOR SHALL VERIFY

EXACT LOCATIONS AND SIZES IN THE FIELD.

6. WHEREVER NEW PIPING IS JOINED TO EXISTING PIPING, THE MECHANICAL CONTRACTOR SHALL PROPERLY SEAL THESE CONNECTIONS WATERTIGHT AND INSULATE THESE LOCATIONS WITH NEW INSULATION AS INDICATED IN THE SPECIFICATION.

7. FOR COPPER AND STEEL PIPING GROOVED OR MECHANICALLY FORMED T-TYPE FITTINGS ARE NOT ACCEPTABLE.

1. CHANGES IN SHAPE OR DIMENSION SHALL BE MADE WITH MAXIMUM TRANSITION OF 1 TO 7.

2. SEPARATE GALVANIZED SHEET METAL FROM ALUMINUM OR COPPER PER THE SPECIFICATIONS.

3. PROVIDE SUPPLEMENTAL STIFFENING AND SUPPORTS TO DUCTS AND APPARATUS CASINGS TO PREVENT DRUMMING, SAGGING AND TO PROVIDE A

STRUCTURALLY SOUND ASSEMBLY.

4. PROVIDE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES.

5. PROVIDE DUCTWORK AND TRANSITIONS TO CONNECT DUCTWORK TO NEW OR EXISTING EQUIPMENT, DUCTWORK, AND COILS.

6. INSTALL FLEXIBLE PERMANENT DUCTWORK IN A FULLY EXTENDED CONDITION WITHOUT SAGS AND KINKS.

7. MECHANICAL CONTRACTOR SHALL INSTALL DUCT MOUNTED SMOKE DETECTORS IN ACCESSIBLE LOCATIONS. DETECTORS SHALL BE FURNISHED AND WIRED

BY THE ELECTRICAL CONTRACTOR. REFER TO ELECTRICAL DRAWINGS FOR EXACT QUANTITY AND LOCATIONS.

8. INDICATED DIMENSIONS DENOTE FREE AND CLEAR INSIDE DIMENSIONS.

9. REPLACE EXISTING DUCT HANGERS WITH NEW TO SERVE EXISTING DUCTWORK TO REMAIN IN ORDER TO ACCOMMODATE THE INSTALLATION OF ALL NEW

EQUIPMENT, SYSTEMS, AND DEVICES. MECHANICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS AND SIZES IN THE FIELD.

10. WHEREVER NEW DUCTWORK IS JOINED TO EXISTING DUCTWORK, THE MECHANICAL CONTRACTOR SHALL PROPERLY SEAL THESE CONNECTIONS AIRTIGHT

AND INSULATE THESE LOCATIONS WITH NEW INSULATION AS INDICATED IN THE SPECIFICATION.

GENERAL PIPING NOTES:

GENERAL DUCTWORK NOTES:

1. TRANSFORMERS OR FILTERS FOR OPERATION OF AUTOMATIC TEMPERATURE CONTROLS FROM BUILDING POWER CIRCUITS SHALL BE PROVIDED UNDER

DIVISION 23.

2. LOW VOLTAGE WIRING (LOWER THAN 110 VOLTS) FOR INTERLOCKED DEVICES, ATC CONTROLLERS, TERMINAL CONTROL UNITS, FLOW MEASURING DEVICES, AND OTHER POWER CONSUMING CONTROL DEVICES SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. ALL LOW VOLTAGE WIRING SHALL BE

INSTALLED IN A CONDUIT AND SHALL BE PLENUM RATED.

3. WIRING 110 VOLTS AND HIGHER FOR INTERLOCKED DEVICES, ATC CONTROLLERS, TERMINAL CONTROL UNITS, FLOW MEASURING DEVICES, AND OTHER POWER CONSUMING CONTROL DEVICES SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR WITH DIVISION 26 REQUIREMENTS. COORDINATE WITH

THE ELECTRICAL CONTRACTOR.

4. BRANCH CIRCUIT WIRING AND CONDUIT FURNISHED FOR CONTROL EQUIPMENT POWER SHALL BE SEPARATE FROM OTHER POWER WIRING. EACH CIRCUIT SHALL EXTEND TO A 120V BRANCH CIRCUIT PANEL, AND IDENTIFIED 120V, 20 AMPERE, SINGLE POLE BRANCH CIRCUIT BREAKER FURNISHED IN THE PANEL TO SERVE THE CIRCUIT. NO MORE THAN 2 ATC CONTROLLER INSTALLATIONS SHALL OPERATE FROM A SINGLE 120V BRANCH CIRCUIT, UNLESS INDICATED

OTHERWISE.

5. WHERE SYSTEMS ARE SERVED BY EMERGENCY POWER, CONTROLS FOR OPERATION OF THOSE SYSTEMS SHALL ALSO BE SERVED BY EMERGENCY POWER.

6. WHERE DAMPERS PREVENT AIRFLOW THROUGH AN AIR HANDLING UNIT OR FAN, THOSE DAMPERS SHALL BE PROVEN OPEN PRIOR TO STARTING THE UNIT OR

FAN. PROOF SHALL BE BY MECHANICAL SAFETY LIMIT SWITCH ACTIVATED BY THE DAMPER BLADE. FOR SERVICE WITH VARIABLE FREQUENCY DRIVES THE SWITCH SHALL BE WIRED IN THE AUTOMATIC AND HAND/TEST POSITIONS AND IN THE BYPASS POSITION FOR VARIABLE FREQUENCY DRIVES WITH BYPASS.

7. ALL AIR PIPING OR TUBING SHALL BE PLENUM RATED. MECHANICAL CONTRACTOR SHALL FURNISH ALL AIR PIPING AND TUBING REQUIRED FOR AUTOMATIC

CONTROLS SYSTEMS.

8. PROVIDE SUPPLEMENTAL STIFFENING AND SUPPORTS TO DUCTS AND APPARATUS CASINGS TO PREVENT DRUMMING, SAGGING AND TO PROVIDE A

STRUCTURALLY SOUND ASSEMBLY.

GENERAL AUTOMATIC TEMPERATURE CONTROL NOTES:

VAV BOX

PTAC UNIT

PT

X

VAV

X

LIMITS OF DEMOLITION

Location

Issue Date

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

VAMC HUNTINGTON

Project Director

Revisions: Date:

VA FORM 08 -

A

F ile

P a th

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Stewart C. Cluck 717.850.2515

CONSTRUCTION

DOCUMENTS

600 North Hartley Street, Suite 152 York, PA 17404

1S

HOMCO Renaissance and GPI-Renaissance JV

7510 Langport Ct.

Hanover, MD 21076 410-340-8284

5001 LOUISE DRIVE,

MECHANICSBURG PA 17055

T 717-691-1340

M-001

MECHANICAL LEGEND, NOTES, &

ABBREVIATIONS

AMRDLA03/20/2024

581-23-111EXPAND PAIN AND

BRONCHOSCOPY

PROCEDURE ROOM

PLAN REVIEW COMMENTS 05/10/2024

05/10/202405/10/2024

1 - REVIEW COMMENTS

E1

A

Room

3B-149

Room

3B-165

Room

3B-169

Room

3B-172

Room

3B-146

Room

3B-168 12"x8"

"x

12"x12"

T

"x

E1

A

BRONCHOSCOPY

ROOM

3B-147

E-1

630 CFM

12"x12"

EXISTING 12X12

DUCT BACK TO

AC-08

"x

(E X

IS

T

IN

G

(EXISTING)12"x12"

S -1

C F

M

S-1

250 CFM

(EXISTING)

16"x8"

10"ø 10"ø

CAP OPEN

END

Location

Issue Date

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

VAMC HUNTINGTON

Project Director

Revisions: Date:

VA FORM 08 -

A

F ile

P a th

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Stewart C. Cluck 717.850.2515

CONSTRUCTION

DOCUMENTS

600 North Hartley Street, Suite 152 York, PA 17404

1S

HOMCO Renaissance and GPI-Renaissance JV

7510 Langport Ct.

Hanover, MD 21076 410-340-8284

5001 LOUISE DRIVE,

MECHANICSBURG PA 17055

T 717-691-1340

M-101

THIRD FLOOR MECHANICAL

DEMOLITION & NEW WORK PLANS

AMRDLA03/20/2024

581-23-111EXPAND PAIN AND

BRONCHOSCOPY

PROCEDURE ROOM

1/4" = 1'-0"M-101

1 THIRD FLOOR MECHANICAL DEMOLITION PLAN

1/4" = 1'-0"M-101

2 THIRD FLOOR MECHANICAL HVAC PLAN

GENERAL NOTES:

1. ADJUST SUPPLY AIR AT ADD-15 ON AC-08 LOCATED IN MECHANICAL ROOM 3B-126.

KEYED NOTES:

RELOCATE EXISTING NEGATIVE PRESURE INDICATOR TO LOCATION OUTSIDE NEW ROOM ENTRY.1

PLAN REVIEW COMMENTS 05/10/2024

05/10/2024

USE METAL NOSING ON INITIAL

LEADING EDGE NOSING MAY BE

FORMED OF DUCT OR CHANNEL

OR ZEE ATTACHED BY SCREWS,

RIVETS OR WELDS

LINED DUCT

CONNECTION (NO

EXPOSED LINER EDGES)

C

C

C B

DIMENSIONS

6"3"

A B

VELOCITY

0-6000 FPM 4" 16"

C E

A

B

B E

A

E

AIR FLOW

LAPPED & BUTTED CORNER

ALTERNATIVE FOLDED CORNER

LINER

WASHER

INTEGRAL OR

PRESSED ON HEAD1" THICK DUCT

LINER OR AS

SPECIFIED

WELDED PINS ONLY

ALL TRANSVERSE EDGES TO

BE COATED WITH ADHESIVE

LINER ADHERED TO THE

DUCT WITH A 100% AREA

COVERAGE OF ADHESIVE.

NOTES:

1. THE VELOCITY RATED SIDE OF

THE LINER MUST FACE THE AIR

FLOW.

2. MAXIMUM SPACING FOR

FASTENERS. ACTUAL INTERVALS

ARE APPROXIMATE.

DUCT DIMENSION

UP TO 457 (18")

482(189")- 1524(60")

1549(61")- 2438(96")

OVER 2438(96")

HANGER

TYPE

A

B

C

D

ROD DIA.

25.4(1") STRAP

7.94(5/16")

9.53(3/8")

12.7(1/2")

ANGLE SIZE

36.1x36.1x3.18(1-1/2"x1-1/2"x1/8")

36.1x36.1x3.18(1-1/2"x1-1/2"x3/16")

50.8x50.8x8.35(2"x2"x1/4")

SPACING MAX

24.38(8'-0")

12.19(4'-0")

24.38(8'-0")

24.38(8'-0")

MAX. SIDE

SHEET METAL SCREW,

RIVET OR BOLT TO BOTH

SIDES OF DUCT NUT AND WASHER AT END

OF SCREW

BRACING ANGLES,

SEE NOTES.

HANGER ROD

SECURE THE

STRUCTURE ABOVE AS

RECOMMENDED

25.4(1")x16 GA. GALV.

IRON STRAP OR ALUM.

MAX. SIDE

TYPE A TYPE B,C,D

24.8(8FT.) MAX. HANGER SPACING, ALSO

PROVIDE 3 HANGERS AT EACH TAKE OFF

OR BRANCH.

24.8(8FT.) MAX. HANGER SPACING

NOTES:

1. FOR SEVERAL DUCTS ON ONE HANGER, TYPE B,C OR D MAY BE USED. SIZE OF

HANGER SHALL BE SELECTED ON SUM OF DUCT WIDTHS EQUAL TO MAX. WIDTH OF

DUCT SCHEDULE.

2. DO NOT ATTACH HANGERS TO ROOF DECK OR BOTTOM.

SECURE THE

STRUCTURE ABOVE AS

RECOMMENDED

MAIN SUPPLY, RETURN, OR EXHAUST DUCT(LO OR

MEDIUM PRESSURE)

DISTANCE (1/4)x

DUCT WIDTH;

101.6(4") MINIMUM

VOLUME DAMPER (TYP.)

RECTANGULAR

BRANCH TAKE-OFF

DUCT

45° ENTRY FITTING

CONCEAL

DUCT TAKE-

OFF FITTING

BELLMOUTH DUCT TAKE-

OFF FITTING

VOLUME DAMPER (TYPICAL)

ROUND BRANCH TAKE OFF DUCT (TYPICAL)

NOTES:

1. SPIN-IN DUCT TAKE OFF FITTINGS MAY BE USED IN LIEU OF CONICAL OR BELLMOUTH FITTING ONLY

WHERE MAIN DUCT DIMENSIONS ARE NOT SUFFICIENT TO ALLOW THE USE OF A CONICAL OR

BELLMOUTH.

2. SEAL ALL TAKE-OFF AND OTHER FITTINGS AIR TIGHT AS PER SPECIFICATION.

3. FABRICATE BRANCH DUCT TAKE-OFF FITTING PER LATEST EDITION OF DUCT CONSTRUCTION

MANUAL, AS INDICATED ON PLANS, OR AS DESCRIBED IN SPECIFICATIONS.

4. APPLIES TO SUPPLY AND EXHAUST RUNOUTS TO GRILLES, REGISTERS, AND DIFFUSERS.

IF A DIMENSION IS GREATER

THAN 2'-0", SUPPORT ELBOW

FROM STRUCTURE ABOVE

MAX. LENGTH OF

FLEX DUCT 5'-0"

NON-KINKED

SUPPLY DUCT

ROUND OR

RECTANGULAR

MAIN OR BRANCH

DUCT

DRAW BAND BUCKLEY TYPE ATMD

FITTING (OR EQUAL)

PROVIDE A TYPICAL DUCT TAKEOFF WHERE

FLEX EXCEEDS 5'-0" (MAX. LENGTH)

CEILING TYPE VARIES.

REFER TO

ARCHITECTURAL PLANS

FOR CEILING TYPE.

FLEX DUCTNON- RESTRICTIVE 90

ELBOW "THERMAFLEX"

FLEX-FLOW OR EQUAL.

INSTALL AT ALL ROUND

NECK DIFFUSERS

DRAW BAND ON

DIFFUSER NECK

ROUND NECK

OR NECK

ADAPTOR

SUPPLY AIR DIFFUSER WITH ROUND NECK &

O.B.D. MOUNTING DETAIL VARIES. REFER TO

ARCH. FOR CEILING TYPE AND DIFFUSER

MANUFACTURER FOR MOUNTING REQUIREMENTS

NOTES:

1. INSULATED FLEXIBLE DUCT - SHALL BE PRESTRETCHED BEFORE INSTALL.

2. DIAMETER TO BE EQUAL TO DIFFUSER INLET SIZE UNLESS OTHERWISE NOTED.

TAG MAXIMUM

AIRFLOW

(CFM)

MAX. NECK

VELOCITY

(FPM)

NOMINAL

MODULE

SIZE (IN.)

MAX. STATIC

PRESSURE (IN.)

MAX. NOISE

CRITERIA (NC)

PATTERN MATERIAL REMARKS

S-1 275 24X24 0.037 16 4-WAY ALUMINUM 1,2,3

BASIS OF DESIGN

TITUS TMS-AA

DIFFUSERS, REGISTERS AND GRILLES SCHEDULE

REMARKS:

*NR = NO REQUIREMENT

1. TEMPERATURE SETPOINT SHALL BE 68°F

2. RELATIVE HUMIDITY SHALL BE 20-60%

3. COLOR AND FINISH BY ARCHITECT

630 24X24 0.02 - EGG CRATE ALUMINUM 1,2,3TITUS 45F200

R-1

DUCT SIZE DUCT

ANCHOR BOLT

ANGLE

DIAGONAL

BOTH SIDES

LONGITUDINAL ANGLE

CUT WASHER

BOLTS WITH

HORIZONTAL ANGLE

(TYPICAL)

VERTICAL ANGLE

(TYPICAL)

ANGLE CLIP

SEISMIC RESTRAINTS

PROVIDE THE WORK IN COMPLIANCE WITH THE MOST STRINGENT SEISMIC REQUIREMENTS FOR THE APPLICABLE CODES AS SPECIFIED IN SPECIFICATIONS HEREIN. PROVIDE SEISMIC RESTRAINTS FOR MATERIALS AND EQUIPMENT OF THIS DIVISION, INCLUDING (BUT NOT LIMITED TO) THE ITEMS LISTED BELOW. THE ATTACHMENTS SHALL RESIST FORCE APPLIED TO THE CENTER OF GRAVITY OF THE COMPONENTS. CRITERIA SHALL BE THE OPERATING WEIGHT OF THE ITEM AS INDICATED IN SPECIFICATIONS HEREIN FOR HORIZONTAL FORCES AND VERTICAL FORCES. DESIGN FOR THE HORIZONTAL FORCES TO BE APPLIED IN ANY DIRECTION.

WALL MOUNTED OR SUSPENDED COMPONENTS SHALL, IN ADDITION, RESIST A DOWNWARD FORCE TO THE OPERATING WEIGHT. PROVIDE BRACING AND ANCHORAGE OF PIPING AND CONDUIT HANGERS AND TRAPEZES

IN ACCORDANCE WITH THE GUIDELINES PER SPECIFICATIONS HEREIN.

CAREFULLY REVIEW THE SPACE AVAILABLE TO INSURE THAT THE RESTRAINT SYSTEMS INDICATED WILL NOT

IMPAIR THE REQUIRED EQUIPMENT CLEARANCE, WORKING SPACE OR ACCESS.

SUBMIT DETAILS AND ASSOCIATED CALCULATIONS OF THE SEISMIC ANCHORAGE PER SPECIFICATIONS

HEREIN.

ALL PIPES SHALL BE SUPPORTED AND BRACED PER SEISMIC RESTRAINTS OF MECHANICAL AND PLUMBING SYSTEMS INDICATED IN SPECIFICATIONS HEREIN. ONCE THE EXACT LOCATION OF ALL PIPES HAS BEEN ESTABLISHED, THE STRUCTURAL ENGINEER MUST CHECK THE ADEQUACY OF THE SUPPORTING STRUCTURE.

ALL EXTERIOR AIR HANDLING UNITS, DUCTWORK, AND PIPING SHALL BE PROVIDED WITH SEISMIC RESTRAINT

IN ACCORDANCE WITH SPECIFICATIONS HEREIN.

SEISMIC NOTE:

THESE DETAILS ARE PROVIDED TO INDICATE THE INTENT AND BASIC REQUIREMENTS

FOR SEISMIC RESTRAINT OF THE PIPING, DUCTWORK AND CONDUIT SYSTEMS WITHIN

AND OUTSIDE THE BUILDING. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO

OBTAIN THE SERVICES OF A SEISMIC ENGINEER AND TO PROVIDE SEISMIC

RESTRAINTS IN ACCORDANCE WITH THE CRITERIA INDICATED IN THE SPECIFICATIONS.

Location

Issue Date

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

VAMC HUNTINGTON

Project Director

Revisions: Date:

VA FORM 08 -

A

F ile

P a th

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Stewart C. Cluck 717.850.2515

CONSTRUCTION

DOCUMENTS

600 North Hartley Street, Suite 152 York, PA 17404

1S

HOMCO Renaissance and GPI-Renaissance JV

7510 Langport Ct.

Hanover, MD 21076 410-340-8284

5001 LOUISE DRIVE,

MECHANICSBURG PA 17055

T 717-691-1340

M-201

MECHANICAL DETAILS AND

SCHEDULES

AMRDLA03/20/2024

581-23-111EXPAND PAIN AND

BRONCHOSCOPY

PROCEDURE ROOM

NOT TO SCALEM-201

1 ACOUSTICAL LINING DETAIL

NOT TO SCALEM-201

2 DUCT HANGERS DETAIL

NOT TO SCALEM-201

3 BRANCH TAKE-OFF DETAIL

NOT TO SCALEM-201

4 SUPPLY AIR DIFFUSER DETAIL (SIDE TAP)

NOT TO SCALEM-201

5 SEISMIC BRACING FOR RECTANGULAR DUCTS

PLAN REVIEW COMMENTS 05/10/2024

PLUMBING FIXTURE SCHEDULE

FIXTURE SANITARY VENT

REMARKS

MARK COLD WATER HOT WATER

NOTES:

1. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL STOPS ON SUPPLY LINES TO ALL FIXTURES.

2. PLUMBING CONTRACTOR TO FURNISH AND INSTALL ACCESS DOORS FOR ALL VALVES AS REQUIRED.

3. ALL EXPOSED PIPING UNDER ADA ACCESSIBLE COUNTERTOP SINKS AND LAVATORIES SHALL BE INSULATED AND PROTECTED WITH PREFABRICATED

MOLDED COVERS AS MANUFACTURED BY TRUEBRO CO, OR EQUAL.

4. PLUMBING CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR INTERIOR ELEVATIONS AND MOUNTING HEIGHTS FOR PLUMBING

FIXTURES.

5. PROVIDE WATTS SERIES LFUSG-B THERMOSTATIC MIXING VALVE (SET TO 80°F - 95°F) FOR ALL LAVATORIES AND HAND WASHING SINKS.

6. PROVIDE LAMANIAR FLOW DEVICE WITH A FLOW CONTROL RESTRICTOR AND VANDAL RESISTANT HOUSING. AERATORS ARE PROHIBITED.

7. PROVIDE FOOT PEDAL AS MANUFACTUERED BY CHICAGO FAUCETS MODEL 625-SLOABCP. PROVIDE SUPPLY LINE CONNECTION FROM FOOT PEDAL TO

FAUCET.

S-1 COUNTERTOP SINK

MANUFACTURER MODEL

1/2" 1/2" 1 1/2"1 1/2" LUSTERTONE, SINGLE BOWL SINK, 18 GAUGE, TYPE 304 STAINLESS STEEL, SATIN FINISH, CENTER

DRAIN, GOOSENECK, THREE HOLE DRILLING CONFIGURATION, PROVIDE CUTOUT TEMPLATE.

MANUAL FAUCET, 0.5 GPM. PROVIDE DRAIN WITH TAILPIECE AND WASTE TEE FITTING AND P-TRAP

PROFLO OR EQUAL. PROVIDE WATER SUPPLY AND STOPS PROFLO OR EQUAL.

ELKAY LR2219

FIXTURE

MANUFACTURER MODEL

CHICAGO

FAUCETS

786-TWE72ABCP

FAUCET CONNECTIONS

FLOW RATE

0.5 GPM

DRAWING SYMBOLS

DETAIL DESIGNATION OR ENLARGED PLAN

PLUMBING DRAWING NUMBER WHERE DETAIL IS SHOWN

POINT OF NEW CONNECTION

POINT OF DISCONNECTION

LEGEND

DIRECTION OF FLOW

BALL

"P" TRAP

PIPING SYMBOLS

PIPING SPECIALTIES & FITTINGS

CAPPED OUTLET

CHANGE IN ELEVATION OF PIPE

PIPE RISE OR ELBOW TURNED UP

PIPE DROP OR ELBOW TURNED DOWN

KEYED DEMOLITION NOTE

KEYED DRAWING NOTE

SAN SANITARY PIPING BELOW FLOOR

SANITARY PIPING ABOVE FLOOR

VENT PIPING

POTABLE COLD WATER PIPING

POTABLE HOT WATER PIPING

POTABLE HOT WATER RETURN PIPING

CLEANOUT / WALL CLEANOUT

CO

FCO

FLOOR CLEANOUT

AC ALTERNATING CURRENT

AD ACCESS DOOR

ARCH ARCHITECTURE

BF BELOW FLOOR

BFF BELOW FINISHED FLOOR

CI CAST IRON

CLG CEILING

CO CLEAN OUT

CONN CONNECTION

CONT CONTINUATION

CONTR CONTRACTOR

CW COLD WATER

DIA DIAMETER

DIM DIMENSION

DN DOWN

EXIST EXISTING

FLR FLOOR

GC GENERAL CONTRACTOR

GEN GENERAL

HW HOT WATER

HWR HOT WATER RETURN

ID INSIDE DIAMETER

IN INCH

MAX MAXIMUM

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

NA NOT APPLICABLE

NTS NOT TO SCALE

PC PLUMBING CONTRACTOR

PLB PLUMBING

QTY QUANTITY

SAN SANITARY

SPEC SPECIFICATION

STD STANDARD

TYP TYPICAL

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

V VENT

W WASTE

PLUMBING ABBREVIATIONS

A. GENERAL PLUMBING NOTES

1. ALL SYSTEMS ARE SHOWN SCHEMATICALLY. THE DRAWINGS AS PREPARED ARE

DIAGRAMMATIC BUT SHALL BE FOLLOWED AS CLOSELY AS CONSTRUCTION OF

THE PROJECT AND THE WORK OF ALL TRADES WILL PERMIT.

FIXTURE/EQUIPMENT LOCATIONS ARE APPROXIMATE. CHECK AND VERIFY ALL

CONDITIONS AT THE SITE WITHIN THE CONTRACT LIMITS.

2. CODES AND STANDARDS LISTED IN THE SPECIFICATION AND DRAWINGS ARE A

MINIMUM STANDARD. WHERE REQUIREMENTS ON THE DRAWINGS AND

SPECIFICATION EXCEED THE MINIMUM CODE REQUIREMENTS, THE DRAWINGS

OR SPECIFICATIONS SHALL GOVERN.

3. IT IS INTENDED THAT THE DRAWINGS AND SPECIFICATIONS SHALL PROVIDE A

WORKING INSTALLATION COMPLETE IN DETAIL AND ALL ITEMS FOR A COMPLETE

INSTALLATION SHALL BE PROVIDED WHETHER OR NOT SPECIFIED OR SHOWN

ON THE DRAWINGS.

4. PROVIDE ALL LABOR AND MATERIALS NEEDED FOR A COMPLETE AND

PROPERLY OPERATIONAL PLUMBING SYSTEM. THE OMISSION OF EXPRESSED

REFERENCE IN THE DRAWINGS OR SPECIFICATIONS TO ANY LABOR OR

MATERIAL NECESSARY FOR THE PROPER EXECUTION OF THE WORK IN

ACCORDANCE WITH PRESENT GOOD PRACTICE OF THE TRADE SHALL NOT

RELIEVE THIS CONTRACTOR FROM PROVIDING, AT NO COST, SUCH ADDITIONAL

LABOR AND MATERIALS UNDER THIS CONTRACT.

5. ALL EQUIPMENT AND MATERIALS INCORPORATED IN THIS WORK SHALL BE NEW

UNLESS OTHERWISE NOTED AND SHALL BE OF THE CUSTOMARY STANDARD

AND QUALITY FURNISHED BY THE DESIGNATED MANUFACTURER FOR THAT

CATALOG NUMBER. THE CATALOG NUMBER PRODUCTS SHALL BE BY

MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH

PRODUCTS.

6. DRAWINGS INDICATE GENERAL LOCATION OF FIXTURES, EQUIPMENT, AND

PIPING. CHANGES OF LOCATION SHALL BE MADE TO ACCOMMODATE EXISTING

OR NEW BUILDING CONDITIONS AND COORDINATION WITH OTHER TRADES,

INCLUDING HVAC, PLUMBING, ELECTRICAL, FIRE PROTECTION, STRUCTURAL,

AND ARCHITECTURAL CHANGES SHALL BE MADE WITHOUT ADDITIONAL COST

TO OWNER.

7. ALL WORK REFERENCED ON THE DRAWINGS SHALL BE DONE BY THE PLUMBING

CONTRACTOR UNLESS OTHERWISE NOTED.

8. BEFORE STARTING WORK THE CONTRACTOR IS RESPONSIBLE TO MAKE A

THOROUGH EXAMINATION OF THOSE PORTIONS OF THE STRUCTURE IN WHICH

THE WORK IS TO BE PREFORMED. THE CONTRACTOR IS RESPONSIBLE FOR

CHECKING, FIELD VERIFYING AND CONFIRMING ALL CONDITIONS AND

DIMENSIONS INCLUDING BUT NOT LIMITED TO EXISTING COLD WATER, HOT

WATER, HOT WATER RECIRCULATING, DRAIN, WASTE, VENT AND GAS PIPING

AND LOCATIONS, SIZES AND INVERTS AS APPLICABLE ON THE PROJECT SITE

AND FOR COORDINATION OF HIS WORK WITH THAT OF OTHER TRADES WITH

THE LEAST POSSIBLE INTERFERENCE.

9. ALL CONTRACTORS SHALL EXAMINE THE SITE AND REVIEW THE DRAWINGS AND

SPECIFICATIONS PRIOR TO SUBMITTING A PROPOSAL.

10. CONTRACTOR SHALL VERIFY DEPTH, SIZE, LOCATION OF ALL EXISTING UTILITIES

IN FIELD PRIOR TO STARTING WORK.

11. WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND OWNER.

12. VALVES AND FITTINGS SHALL CONFORM TO THE REDUCTION OF LEAD IN

DRINKING WATER ACT AND ALL REVISIONS THEREOF.

13. CONTRACTOR SHALL PROTECT THE PIPING FROM STRESS AND STRAIN.

CONTRACTOR SHALL PROTECT THE IN-SLAB PIPING FROM CORROSION, STRESS

AND STRAIN TO CONFORM.

14. ALL FACTORY APPLIED COATINGS AND FINISHES SHALL BE PROVIDED WITHOUT

RUST, SCRATCHES, OR DENTS.

B. COORDINATION REQUIREMENTS

1. COORDINATE EXACT LOCATIONS AND CLEARANCES WITH THE SUPPLIER AND

ALL TRADES PRIOR TO INSTALLATION. DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS.

2. COORDINATE LOCATION AND INSTALLATION OF ALL PLUMBING WORK WITH

OTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES. MODIFICATIONS

DUE TO FIELD CONDITIONS SHALL BE COMPLETELY RESOLVED BY CONTRACTOR

IN ACCORDANCE WITH RECOMMENDATIONS OF THE CONSTRUCTION MANAGER.

3. COORDINATE FINAL LOCATIONS OF PLUMBING FIXTURES AND EQUIPMENT WITH

ARCHITECTURAL PLANS. REFER TO THE ARCHITECTURAL DRAWINGS FOR ALL

EXACT DIMENSIONS AND CONFIRM ALL DIMENSIONS IN THE FIELD.

4. REPORT TO THE ARCHITECT/ENGINEER ANY AND ALL CONDITIONS WHICH MAY

INTERFERE WITH OR OTHERWISE AFFECT OR PREVENT THE PROPER

EXECUTION AND COMPLETION OF THE WORK. DO NOT START THE WORK UNTIL

SUCH CONDITIONS HAVE BEEN EXAMINED AND A COURSE OF ACTION MUTUALLY

AGREED UPON. COORDINATE LOCATION AND INSTALLATION OF PLUMBING

WORK WITH OTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES.

MODIFICATIONS DUE TO FIELD CONDITIONS SHALL BE MADE AS REQUIRED.

GENERAL PLUMBING NOTES

SAN

X X

X

1. CONSTRUCTION MATERIALS AND EQUIPMENT REMOVED SHALL BECOME

THE PROPERTY OF THE OWNER. UNWANTED CONSTRUCTION MATERIALS

AND EQUIPMENT SHALL BE LEGALLY DISPOSED OF, OFF THE SITE UNLESS

NOTED OTHERWISE.

2. CONTRACTOR SHALL NOT CONSIDER THE DEMOLITION DRAWINGS AND

NOTES TO BE ALL-INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY

TO INSPECT AND ASSESS EACH AREA AND TO FULFILL THE INTENT OF THE

WORK INDICATED BY THE CONTRACT DOCUMENTS.

3. CHECK AND VERIFY ALL CONDITIONS AT THE SITE WITHIN THE CONTRACT

LIMITS.

4. REFER TO NEW WORK DRAWINGS FOR ADDITIONAL INFORMATION

AFFECTING DEMOLITION WORK BEFORE BEGINNING WORK.

5. CONTRACTOR SHALL DISCONNECT, REMOVE AND/OR RELOCATE EXISTING

EQUIPMENT AS SHOWN OR AS MAY BECOME NECESSARY TO ACCOMPLISH

DESIRED RESULTS. NO ADDITIONAL CLAIMS SHALL BE MADE FOR

DEMOLITION WORK NOT SPECIFICALLY INDICATED OR SPECIFIED UNLESS,

IN THE ARCHITECT'S/ENGINEER'S OPINION, IT IS BEYOND THE SCOPE OF

WORK.

6. CONNECTING WORK, NEW WORK, OR EXTENSION OF EXISTING WORK

SHALL CORRESPOND IN ALL RESPECTS WITH THAT TO WHICH IT

CONNECTS, UNLESS OTHERWISE INDICATED OR SPECIFIED. EXISTING

WORK SHALL BE CUT, DRILLED, ALTERED OR TEMPORARILY REMOVED AND

REPLACED AS NECESSARY FOR THE PERFORMANCE OF THE CONTRACT.

7. PATCH ALL OPENINGS IN BUILDING CONSTRUCTION WHERE PIPING, ETC. IS

REMOVED. PATCHING SHALL BE THE SAME MATERIALS AS THE

SURROUNDING CONSTRUCTION. FINISH TO MATCH EXISTING TO THE

EXTENT POSSIBLE.

8. WHERE PIPING TO REMAIN IS SUPPORTED FROM EQUIPMENT AND/OR

PIPING BEING REMOVED, EXTEND EXISTING HANGERS OR PROVIDE NEW

HANGERS AND SUPPORTS AS REQUIRED TO RESUPPORT ITEMS FROM

THE BUILDING STRUCTURES.

9. CONTRACTOR SHALL PROVIDE AND MAINTAIN SAFETY AND DUST

BARRIERS AS REQUIRED BY HEALTH AND SAFETY REGULATIONS.

10. NO STRUCTURAL MEMBER SHALL BE CUT OR ALTERED WITHOUT

AUTHORIZATION OF THE ARCHITECT/ENGINEER.

11. COORDINATE WORK WITH THE WORK OF ALL OTHER TRADES.

12. CONTRACTOR IS RESPONSIBLE TO RESTORE DAMAGED OR DEFACED

WORK REMAINING IN PLACE TO THE EXTENT OF THE ORIGINAL CONTRACT

DOCUMENTS.

13. ITEMS NOTED TO BE REMOVED SHALL BE REMOVED IN THEIR ENTIRETY

INCLUDING, BUT NOT LIMITED TO; PIPING, CONTROLS, VALVES, AND

HANGERS. PIPING SHALL BE REMOVED BACK TO THE MAINS AND CAPPED

UNLESS OTHERWISE NOTED.

14. DEBRIS AND DEMOLISHED MATERIALS SHALL BE CLEARED FROM THE SITE

AT FREQUENT INTERVALS. DO NOT ALLOW DEBRIS TO ACCUMULATE TO

THE EXTENT THAT IT WILL INTERFERE WITH WORK OR PASSAGE OF THE

WORKMEN.

15. THE OWNER ACCEPTS NO RESPONSIBILITY FOR LOSS OR DAMAGE TO

MATERIALS OR STRUCTURES ON SITE, OR FOR THE SALVAGE VALUE OF

WHICH THE CONTRACTOR MAY HAVE REFLECTED IN HIS BID.

16. THE CONTRACTOR SHALL GIVE ADVANCE NOTICE TO THE OWNER WHEN

WORK IS TO BE PERFORMED WHICH COULD INTERRUPT SERVICES TO

OTHER AREAS. THE OWNER'S POLICY AND PROCEDURE SHALL BE

STRICTLY ADHERED TO.

17. BEFORE STARTING WORK ALL CONTRACTORS SHALL MAKE A THOROUGH

EXAMINATION OF THOSE PORTIONS OF THE STRUCTURE IN WHICH THE

WORK IS TO BE PERFORMED. CHECK ALL THE WORK ADJOINING OR AT

UNDERLYING LOCATIONS. REPORT TO THE PROFESSIONAL ANY AND ALL

CONDITIONS WHICH MAY INTERFERE WITH OR OTHERWISE EFFECT OR

PREVENT THE PROPER EXECUTION AND COMPLETION OF THE WORK. DO

NOT START THE WORK UNTIL SUCH CONDITIONS HAVE BEEN EXAMINED

AND A COURSE OF ACTION MUTUALLY AGREED UPON.

18. TAKE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO EXISTING

INTERIOR FINISHES WHEN INSTALLING NEW PLUMBING WORK. ANY

DAMAGE TO ADJACENT AREAS SHALL BE REPAIRED AND REFINISHED BY

THE PLUMBING CONTRACTOR TO MATCH EXISTING.

19. ALL CHANGES CANNOT BE DETAILED COMPLETELY ON THE DRAWINGS.

SOME REMOVALS AND RELOCATION OF EXISTING PLUMBING WORK WILL

BE NECESSARY FOR SATISFACTORY PERFORMANCE OF THIS AND OTHER

TRADES. TAKE INTO CONSIDERATION IN PROPOSAL ALL REQUIRED

CHANGES.

20. ALL WORK REQUIRING SHUT DOWN OF EXISTING SYSTEMS SHALL BE

APPROVED BY THE OWNER. SUBMIT SCHEDULE OR REQUIRED OUTAGES

TO THE OWNER FOR APPROVAL. PERFORM WORK IN A MANNER TO

MINIMIZE SHUT DOWN TIME.

21. ALL REMOVAL POINTS ARE TO BE FIELD VERIFIED MAKE ALL ADJUSTMENT

AS NECESSARY PER ACTUAL FIELD CONDITIONS.

22. THE DEMOLITION DRAWING IS PROVIDED AS A GENERAL GUIDE TO THE

REMOVAL OF MATERIALS NEEDED TO FULLY COMPLETE THIS PROJECT.

GENERAL PLUMBING DEMOLITION NOTES

C. PLUMBING INSTALLATION REQUIREMENTS

1. INSTALL ALL EQUIPMENT, FIXTURES AND MATERIAL IN STRICT ACCORDANCE

WITH RESPECTIVE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS

AND RECOMMENDATIONS. WHERE THERE IS A CONFLICT BETWEEN THE

MANUFACTURER AND THE CODE, THE CODE SHALL APPLY UNLESS THE

MANUFACTURER IS MORE RESTRICTIVE. MAINTAIN CLEARANCES FOR

CLEARANCE ACCESS TO MAINTAIN AND SERVICE EQUIPMENT, VALVES AND

CONTROL. ALL DIMENSIONS SHALL BE TAKEN FROM CERTIFIED

MANUFACTURER'S DIMENSION INSTALLATION SHEETS AND ROUGH-IN

DIMENSIONS.

2. ALL INSTALLATION AND WORK SHALL BE PERFORMED IN A NEAT, WORKMANLIKE

MANNER SO AS NOT TO DAMAGE ANY SURFACES, EQUIPMENT, OR MATERIALS.

3. ALL EQUIPMENT AND PIPING SHALL BE SUPPORTED INDEPENDENTLY OF

EQUIPMENT IN AN APPROVED MANNER FROM THE BUILDING STRUCTURE AND

INCLUDES HANGERS AND RESTRAINTS IN ACCORDANCE WITH ALL APPLICABLE

CODES AND SEISMIC RESTRAINT REQUIREMENTS. DO NOT SUSPEND FROM

OTHER PIPING, EQUIPMENT OR DUCTWORK.

4. PROVIDE PIPE ESCUTCHEONS AT ALL EXPOSED PENETRATIONS OF FLOOR,

WALLS, AND CEILINGS.

5. INSTALL SUFFICIENT UNIONS IN PIPING SYSTEMS TO ALLOW SERVICE OF ANY

CONNECTED EQUIPMENT WITHOUT BREAKING FITTINGS OR CUTTING PIPING

CONNECTIONS.

6. THE MANUFACTURER'S AND MODEL NUMBERS LISTED ON THE SCHEDULES AND

DETAILS ARE THE BASIS OF DESIGN FOR THIS PROJECT AND SHALL SET THE

MINIMUM STANDARD FOR QUALITY, CAPACITY, PERFORMANCE AND FEATURES,

AND IS NOT INTENDED TO PRECLUDE OTHER EQUAL MANUFACTURER'S

SUBMISSION FOR REVIEW.

7. ALL DIMENSIONS AND PIPE SIZES ARE IN INCHES UNLESS OTHERWISE NOTED.

8. RUN-OUTS TO EQUIPMENT AND FIXTURES SHALL BE SIZED AS INDICATED AND

INCREASED OR REDUCED AT POINT OF FINAL CONNECTION TO EQUIPMENT.

9. ALL SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH APPLICABLE CODES OR

REGULATIONS AND PROPERLY TESTED IN ACCORDANCE WITH THE SAME.

10. ANY CUTTING OR PATCHING NECESSARY TO PERMIT THE INSTALLATION OF ANY

WORK UNDER THIS CONTRACT SHALL BE THE RESPONSIBILITY OF THE

PLUMBING CONTRACTOR.

11. THE PLUMBING CONTRACTOR SHALL PROVIDE DOMESTIC WATER SHUTOFF

VALVES AT ALL TAKE OFF BRANCHES, MAINS AND AT EACH FIXTURE/EQUIPMENT

AND OUTLETS REQUIRING WATER INCLUDING SHUTOFF VALVES AT POINT OF

NEW CONNECTIONS.

12. ALL PIPING SHALL BE LOCATED AS SHOWN ON THE DRAWINGS, CONNECTING TO

ALL PLUMBING FIXTURES AND OTHER EQUIPMENT REQUIRING WATER,

SANITARY AND GAS, AND WITH OUTLETS ADJACENT TO THE EQUIPMENT

FURNISHED UNDER OTHER CONTRACTS REQUIRING CONNECTIONS.

13. ALL PIPING SHALL BE CONCEALED IN WALLS, PARTITIONS, CHASES, FURRED

SPACES OR IN HUNG CEILINGS/ABOVE CEILINGS, EXCEPT IN MECHANICAL

EQUIPMENT ROOMS AND ELSEWHERE UNLESS OTHERWISE NOTED.

14. INSTALL PIPING TO CONSERVE BUILDING SPACE AND NOT INTERFERE WITH USE

OF SPACE. ROUTE PIPING IN ORDERLY MANNER AND MAINTAIN GRADIENT.

GROUP WHENEVER PRACTICAL AT COMMON ELEVATIONS.

15. INSTALL PIPING TO ALLOW FOR EXPANSION AND CONTRACTION WITHOUT

STRESSING PIPE, JOINTS, OR CONNECTED EQUIPMENT. PROVIDE CLEARANCE

FOR INSTALLATION OF INSULATION AND ACCESS TO VALVES AND FITTINGS.

16. ALL COPPER TUBING SHALL BE CUT WITH SQUARE ENDS, AND ALL BURRS AND

FINS REMOVED. TUBING SHALL BE CAREFULLY HANDLED AND PROTECTED TO

AVOID DAMAGE. ANY PIPE CUT, DENTED OR OTHERWISE DAMAGED MUST BE

REPLACED WITH NEW PIPE BY THE CONTRACTOR.

17. THREADED-TO-SOLDERED…