This solicitation seeks air balancing services at the Wilkes-Barre VA Medical Center. Interested vendors must provide quotations for air balancing services with a period of performance beginning on February 15, 2021 following contract award. Quotes are due by February 1, 2021 and must be submitted to the contracting specialist. The solicitation incorporates Service Contract Act Wage Determination Number 2015-42391 Rev 12 dated 05-11-2020. Vendors must be registered in the System for Award Management to receive an award. The North American Industry Classification System code is 238220 and there is no set aside.

View the file

Other files

File Type Posted
36C24421Q0221 0002_1.docx DOCX document
Attachment 006--Location Diagrams.pdf PDF
Attachment 004--COVID Locations.pdf PDF
Attachment 003--COVID Locations.pdf PDF
36C24421Q0221 0001_1.docx DOCX document
Attachment 2.pdf PDF
36C24421Q0221_1.docx DOCX document
Attachment 1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Room # Area Description Calibration Interval

Pressure Relationship to Adjacent Areas

Ideal Pressure (Inches Water Colum)

Minimum Pressure (Inches Water Colum)

Air Changes per Hour

(ACH)

Notes ASHRAE 170 (2013edt)

A4‐50 Operating room Quarterly Positive ‐ 0.01 15 7.4.1 A4‐54 Operating room Quarterly Positive ‐ 0.01 15 7.4.1 A4‐55 Operating room Quarterly Positive ‐ 0.01 15 7.4.1 A4‐56 Operating room Quarterly Positive ‐ 0.01 15 7.4.1 N4‐114 Sterile Processing Service Quarterly Positive 0.01 0.005 4 VHA DIR 1116(2) N4‐112 Sterile Processing Service Quarterly Positive 0.01 0.005 4 VHA DIR 1761(1) N4‐113 Sterile Processing Service Quarterly Positive 0.01 0.005 4 VHA DIR 1116(2) N4‐111 Sterile Processing Service Quarterly Positive 0.01 0.005 4 VHA DIR 1116(2) N4‐107 Sterile Processing Service Quarterly Positive 0.01 0.005 4 VHA DIR 1116(2) N4‐104 Sterile Processing Service Quarterly Positive 0.01 0.005 4 VHA DIR 1116(2) N4‐102 Sterile Processing Service Quarterly Positive 0.01 0.005 4 VHA DIR 1116(2) N4‐101 Sterile Processing Service Quarterly Positive 0.01 0.005 10 VHA DIR 1116(2) N4‐94 Sterile Processing Service Quarterly Negative 0.01 0.005 6 VHA DIR 1116(2) N4‐97 Sterile Processing Service Quarterly Negative 0.01 0.005 6 VHA DIR 1116(2) N4‐106 Sterile Processing Service Quarterly Negative 0.01 0.005 6 VHA DIR 1116(2) N4‐98 Sterile Processing Service Quarterly Negative 0.01 0.005 10 VHA DIR 1116(2) N4‐103 Sterile Processing Service Quarterly Negative 0.01 0.005 10 VHA DIR 1116(2) N4‐100 Sterile Processing Service Quarterly Negative 0.01 0.005 10 VHA DIR 1116(2) N4‐95 Sterile Processing Service Quarterly Negative 0.01 0.005 10 VHA DIR 1116(2) N4‐92 Sterile Processing Service Quarterly Negative 0.01 0.005 10 VHA DIR 1116(2) N4‐93 Sterile Processing Service Quarterly Negative 0.01 0.005 10 VHA DIR 1116(2) N4‐89 Recovery Room Quarterly Positive ‐ 0.005 6 A4‐21A Intensive Care Isolation Rm Quarterly Negative ‐ 0.01 12 7.2.1 Note a.

A4‐21 Intensive Care Isolation Ante Rm Quarterly Negative 0.01 0.005 10 7.2.1 Note a.

A4‐20A Intensive Care Isolation Rm Quarterly Negative ‐ 0.01 12 7.2.1 Note a.

A4‐20 Intensive Care Isolation Ante Rm Quarterly Negative 0.01 0.005 10 7.2.1 Note a.

A4‐16 Intensive Care Isolation Rm Quarterly Negative ‐ 0.01 12 7.2.1 Note a.

A4‐16A Intensive Care Isolation Ante Rm Quarterly Negative 0.01 0.005 10 7.2.1 Note a.

A4‐17 Intensive Care Isolation Ante Rm Quarterly Negative 0.01 0.005 10 7.2.1 Note a.

A4‐31 Intensive Care Isolation Rm Quarterly Negative ‐ 0.01 12 7.2.1 Note a.

C4‐44 4E In‐Patient Airborne Isolation Rm Quarterly Negative ‐ 0.01 12 7.2.1 NOTE a.

C4‐44B 4E In‐Patient Airborne Isolation Ante Rm Quarterly Negative 0.01 0.005 10 7.2.1 NOTE a.

C4‐44D 4E In‐Patient Airborne Isolation Rm Quarterly Negative ‐ 0.01 12 7.2.1 NOTE a.

C4‐44C 4E In‐Patient Airborne Isolation Ante Rm Quarterly Negative 0.01 0.005 10 7.2.1 NOTE a.

4‐105 Hemo‐Dialysis (Airborne Isolation Rm) Quarterly Negative ‐ 0.01 12 7.2.1 Note a.

Calibration of Pressure Monitors and Air Balancing ‐ Attachment 1

Relationship to Adjacent Areas

Ideal Pressure (Inches Water Colum)

Minimum Pressure (Inches Water Colum)

Air Changes per Hour

(ACH)

Notes ASHRAE 170 (2013edt)

4‐104 Hemo‐Dialysis (Sterile Supply) Semi annual Positive ‐ 0.005 4 VHA DIR 1761(1) 4‐120 Hemo‐Dialysis (Soiled Utility Rm) Semi annual Negative ‐ 0.005 10 4‐109 Hemo‐Dialysis (Soiled Equipment Rm) Semi annual Negative ‐ 0.005 10 4‐111 Hemo‐Dialysis (Clean Utility Rm) Semi annual Positive ‐ 0.005 4 4‐102 Hemo‐Dialysis (HAC) Semi annual Negative ‐ 0.005 4 A4‐48 Cardiac Cath. Area (Sterile Supply) Semi annual Positive ‐ 0.005 4 4‐132 Cardiac Cath. Area (Cath Recovery Rm) Semi annual ‐ ‐ ‐ 6 4‐136 Clean Utility Cardiac Cath. Area Semi annual Positive ‐ 0.005 4 4‐138 Cardiac Cath. Area (Soiled Utility ) Semi annual Negative ‐ 0.005 4 4‐148 Cardiac Cath. Area (Sterile Supply) Semi annual Positive ‐ 0.005 4 VHA DIR 1761(1) 4‐146 Cardiac Cath. Area (Procedure Rm /RME) Semi annual Positive 0.01 20 7.5.2 4‐144 Cardiac Cath. Area (Sterile Supply) Semi annual Positive ‐ 0.005 4 VHA DIR 1761(1) Bronchoscopy room 3rd Floor Respiratory Therapy Semi annual Negative 0.01 12 Pulmonary Function lab 3rd Floor Respiratory Therapy Semi annual Negative 0.005 12 Airborne Isolation Room Emergency Department (new room) Semi annual Negative 0.01 12 A2‐15 Women's Health (Procedure Room) Semi annual Positive 0.01 0.005 TBD CB‐89A Pharmacy Clean room ‐ Ante Semi annual * CB‐89B Pharmacy Clean room ‐ IV Prep Semi annual * CB‐89C Pharmacy Clean room ‐ Chemo Semi annual * CB‐89S Pharmacy Clean room ‐ Haz Drug Storage Rm Semi annual * AOPC 138 Isolation Room Semi annual Negative 0.01 12 AOPC 144 Isolation Room Semi annual Negative 0.01 12 AOPC 243 Sound Both Semi annual Neutral 12 AOPC 245 Dental Exam Room Semi annual Negative 0.01 12 AOPC 246 Dental Exam Room Semi annual Negative 0.01 12 AOPC 278 Dental Exam Room Semi annual Negative 0.01 12 SOPC 139 Isolation Room Semi annual Negative 0.01 12 SOPC 142 Isolation Room Semi annual Negative 0.01 12

Service to be coordinated to test rooms prior to cleanroom certification.

Pressure monitors to be calibrated semi annually.

Pressure Relationship to Adjacent Areas based on previous certification.

Relationship to Adjacent Areas

Ideal Pressure (Inches Water Colum)

Minimum Pressure (Inches Water Colum)

Air Changes per Hour

(ACH)

Notes ASHRAE 170 (2013edt)

A4‐65 Operating room support area (large clean core) Annual Relative via diagram 0.01 0.005 ‐ Diagram (a) of area Basement (CG‐90,91,84) Pharmacy area Annual Positive 0.01 0.005 4 Diagram (b) of area C9‐58 Ward9 (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) C5‐32 5 East Surgical Clinic (RME) Annual Positive 0.01 4 VHA DIR 1116(2) C5‐51D 5 East Surgical Clinic (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) C5‐48A 6 East Surgical Clinic (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) A4‐31 ICU (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) A4‐31 ICU (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1116(2) A4‐06 Near ICU (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) C4‐61 GI Procedure Room Annual Negative 0.01 10 170_Table 7.1 C4‐65 GI Procedure Room Annual Negative 0.01 10 170_Table 7.1 C4‐63 GI Scope Room (RME storage) Annual Positive 0.01 4 VHA DIR 1116(2) C4‐64 GI Sterile Supplies (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1116(2) C4‐70S 4 West SPU (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) N4‐76 O2 / NO manifold Rm Annual Negative 0.01 8 170_Table 7.1 C4‐51D 4 East (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) C4‐51E 4 East (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) CLC 4‐135 Oncology (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) N3‐82 Lab (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) C3‐49 Eye Clinic (Procedure Rm) Annual Positive 0.01 10 170_Table 7.1 C3‐52 Echo lab (Procedure Rm) Annual Positive 0.01 10 170_Table 7.1 A3‐15 Eye Clinic (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) A3‐11 Eye Clinic (RME) Annual Positive 0.01 4 VHA DIR 1116(2) C3‐53 Podiatry (RME) Annual Positive 0.01 4 VHA DIR 1116(2) C3‐54 Podiatry (RME) Annual Positive 0.01 5 VHA DIR 1116(2) C3‐71 Specialty Clinic (RME) Annual Positive 0.01 4 VHA DIR 1116(2) CLC 3‐150 CLC (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) A2‐18 Primary Care Clinic (RME & Sterile Supply) Annual Positive 0.01 4 VHA DIR 1116(2) A2‐56 CT Room (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1116(2) CLC 2‐150 CLC (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1116(2) NM‐209 (2d Floor) Radiology (Isotope Room) Annual Negative 0.01 0.005 6 170_Table 7.1 NM‐221 (2d Floor) Radiology (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) N1‐131 Dental (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1116(2) N1‐139 Dental (RME) Annual Positive 0.01 4 VHA DIR 1116(2) A1‐02 Primary Care Clinic (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1116(2) C1‐46 MHC (Sterile Supply) Annual Positive 0.01 4 VHA DIR 1761(1) Decon Shower Room Emergency Department Entrance Annual Negative 0.01 0.01 12 170_Table 7.1 AG‐40D Emergency Department Annual Positive 0.01 4 VHA DIR 1116(2) CB‐64 (near loading dock) Logistic main (Sterile Supply) or new room Annual Positive 0.01 4 VHA DIR 1116(2)

NOTE: Green annotates RME storage requirement based on VHA directive NOTE: Blue annotates Logistics storage requirement based on VHA directive

7.2.1 NOTE a. ‐ ASHRAE Standard 170 edition 2013 or current edition