About this file
This document contains a combined solicitation and synopsis for air balancing services at the Wilkes-Barre VA Medical Center. The Department of Veterans Affairs Network Contracting Office is seeking quotes for air balancing services at the Wilkes-Barre VA Medical Center located in Wilkes-Barre, Pennsylvania. Interested vendors should provide firm fixed price quotes for air balancing services in accordance with the attached statement of work and price schedule by February 1, 2021. The anticipated period of performance will begin on February 15, 2021 following contract award. The associated NAICS code is 238220 for plumbing, heating, and air conditioning contractors, with a small business size standard of $16.5 million. The wage determination number 2015-42391 Rev 12 dated May 11, 2020 applies.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24421Q0221 0002_1.docx | DOCX document | |
| Attachment 005--Regular Locations.pdf | ||
| Attachment 006--Location Diagrams.pdf | ||
| Attachment 004--COVID Locations.pdf | ||
| 36C24421Q0221 0001_1.docx | DOCX document | |
| Attachment 2.pdf | ||
| 36C24421Q0221_1.docx | DOCX document | |
| Attachment 1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Room # Area Description Calibration Interval
Pressure Relationship to Adjacent Areas
Minimum Pressure (Inches Water Colum)
Air Changes per Hour
(ACH)
AB‐21 ED Fast Track1 Temp Airborne Isolation Rm Quarterly Negative 0.01 12 AB‐23 ED Fast Track2 Temp Airborne Isolation Rm Quarterly Negative 0.01 12 AB‐25 ED Triage1 Temp Airborne Isolation Rm Quarterly Negative 0.01 12 AB‐27 ED Triage2 Temp Airborne Isolation Rm Quarterly Negative 0.01 12 A4‐20A &ante ICU Temp Airborne Isolation Rm Quarterly Negative 0.01 12 A4‐21A &ante ICU Temp Airborne Isolation Rm Quarterly Negative 0.01 12 A4‐22 ICU Temp Airborne Isolation Rm Quarterly Negative 0.01 12 A4‐23 ICU Temp Airborne Isolation Rm Quarterly Negative 0.01 12 A4‐24 ICU Temp Airborne Isolation Rm Quarterly Negative 0.01 12 A4‐25 ICU Temp Airborne Isolation Rm Quarterly Negative 0.01 12 A4‐26 ICU Temp Airborne Isolation Rm Quarterly Negative 0.01 12
Calibration of Pressure Monitors and Validate Air Flows ‐ Attachment 3 Temp COVID Rooms