This is an Amendment to a Previous Combined Solicitation for fire protection systems inspection, testing, and maintenance services at the VA New Jersey Healthcare System's Lyons Campus in Lyons, New Jersey. The solicitation (36C24226Q0339) is issued as a Request for Quote (RFQ) for commercial products and services under FAR subpart 12.202 and is set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBCs). The contracting office is the Department of Veterans Affairs Network Contracting Office 2 at the James J. Peters VA Medical Center in Bronx, New York. The response deadline has been extended to April 1, 2026 at 12:00 p.m. Eastern Time, with a 99-day archive period following the response date. The NAICS code is 238220 (Fire Sprinkler System Installation), and the Product Service Code is H142.

The required services include quarterly, semi-annual, and annual inspections, testing, and maintenance of fire protection systems, including portable fire extinguishers, fire alarm system components, kitchen hood suppression systems, fire sprinkler systems, fire pumps, and backflow preventers. The base period runs from April 13, 2026 through April 12, 2027. This amendment specifically addresses Questions and Answers regarding sprinkler replacement specifications, clarifying that the facility requires a mix of sprinkler head types (55% pendent-style, 20% upright-style, 20% sidewall-style, and 5% dry-pendent and dry-horizontal styles), all quick-response, chrome, 155F, 5.6K rating, Factory Mutual approved, and UL listed per the VA Fire Protection Design Manual. Contractors should reference FAR 52.212-1 regarding line item 0014 for parts and materials pricing. Point of contact is Contract Specialist Yasmin Moses at Yasmin.Moses@va.gov.

View the file

Other files for this federal contract opportunity

Other files attached to H142--Amendment Three| Lyons Fire Protections Systems ITM/Repair|Answer Solicitation Questions, newest first.
File Type Posted
36C24226Q0339 0002.docx DOCX document
36C24226Q0339 0001_1.docx DOCX document
Wage SAM.gov.pdf PDF
852.219-75.docx DOCX document
36C24226Q0339_1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

SUBJECT*
Lyons Fire Protections Systems ITM/Repair

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
10468-3904
SOLICITATION NUMBER*
36C24226Q0339
RESPONSE DATE/TIME/ZONE
04-01-2026 12:00pm EASTERN TIME, NEW YORK, USA
ARCHIVE
99 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
SDVOSBC
PRODUCT SERVICE CODE*
H142
NAICS CODE*
238220
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 2 James J. Peters VA Medical Center 130 West Kingsbridge Road Bronx NY 10468-3904

POINT OF CONTACT*

Contract Specialist Yasmin Moses Yasmin.Moses@va.gov

PLACE OF PERFORMANCE

ADDRESS
Department of Veterans Affairs

VA New Jersey Healthcare System

Lyons Campus

151 Knollcroft Road

Lyons New Jersey

POSTAL CODE
07939
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

Lyons Fire Protections Systems

Solicitation Questions and Reponses

Question 1- For the 500-unit sprinkler replacement task, would the Government consider accepting pricing for the replacement of standard temperature, K5.6/K8.0 quick-response or standard-response sprinklers within the firm fixed-price. And any requirement for specialty sprinklers (e.g., Attic, Dry-Pendent, or Institutional sprinklers) that exceed that standard unit cost threshold be addressed via CLIN X014 (Parts and Materials) or via a separate 'Over-and-Above' provision?

Response- The facility has a variety of sprinkler heads that function in different areas. The standard styles are:

· 55% facility coverage- Pendent-style, QR, Chrome, 155F, 5.6K

· 20% facility coverage- Upright-style, QR, Chrome or brass, 155F, 5.6K

· 20% facility coverage- Sidewall-style, QR, Chrome, 155F, 5.6K

· 2.5% facility coverage- Dry-pendent, QR, Deep escutcheon, Chrome, 155F, 5.6K, 24in.

· 2.5% facility coverage- Dry-horizontal, QR, Deep escutcheon, Chrome, 155F, 5.6K, 24in.

All sprinkler heads selected for installation shall comply with the requirements of the VA Fire Protection Design Manual (latest edition) and shall, unless otherwise stated:

· Replace any standard response sprinkler head with an in-kind quick response

· Shall not be recessed or concealed

· Shall be Factory Mutual (FM) approved

· Shall be Underwriters Laboratories (UL) listed Regarding line item 0014- Please refer to FAR 52.212-1 Note- The response date is hereby extended from 3/31/2026 at 3:00pm to 4/01/2026 at 12:00pm EST.