This is an amendment to a combined solicitation for fire protection systems inspection, testing, and maintenance services at the Department of Veterans Affairs New Jersey Healthcare System at Lyons Campus in Lyons, New Jersey. The solicitation number is 36C24226Q0339, with a response deadline of March 31, 2026 at 3:00 PM Eastern Time. The requirement covers quarterly, semi-annual, and annual inspections and testing for portable fire extinguishers, fire hydrants, fire pumps, sprinkler systems, backflow preventers, water flow switches, tamper switches, and kitchen hood suppression systems across four contract periods: a base period from April 13, 2026 through April 12, 2027, followed by four one-year option periods extending through April 12, 2031. This solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBs) under NAICS code 238220 with a small business size standard of $19.0 million, and uses Product Service Code H142.

The line items include annual inspections and testing of 349 fire extinguishers, 40 fire hydrants, 2 fire pumps, 10 backflow preventers, quarterly main drain testing, semi-annual inspections of 25 wet and dry sprinkler systems, 1 anti-freeze sprinkler system, 197 tamper switches, and 124 waterflow switches, along with semi-annual testing of kitchen hood suppression systems from four manufacturers (Ansul, Kidde, Buckeye, and Denlar), replacement of up to 500 expired sprinkler heads per year, and labor rates for repairs and materials. The amendment clarifies that line items for five-year full flow hydrant testing (previously items 1015, 2015, 3015, and 4015) have been removed from the pricing schedule as such testing is only required once within a five-year inspection cycle per NFPA 291. Additionally, the amendment increases the technical capability statement limit from 10 pages to 20 pages maximum to allow offerors adequate space to demonstrate compliance with all requirements including inspection reports, written plans, and NICET certifications without constraint.

View the file

Other files for this federal contract opportunity

Other files attached to H142--Amendment Three| Lyons Fire Protections Systems ITM/Repair|Answer Solicitation Questions, newest first.
File Type Posted
36C24226Q0339 0003.docx DOCX document
36C24226Q0339 0001_1.docx DOCX document
852.219-75.docx DOCX document
Wage SAM.gov.pdf PDF
36C24226Q0339_1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

SUBJECT*
Lyons Fire Protections Systems ITM/Repair

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
10468-3904
SOLICITATION NUMBER*
36C24226Q0339
RESPONSE DATE/TIME/ZONE
03-31-2026 3:00pm EASTERN TIME, NEW YORK, USA
ARCHIVE
99 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
SDVOSBC
PRODUCT SERVICE CODE*
H142
NAICS CODE*
238220
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 2 James J. Peters VA Medical Center 130 West Kingsbridge Road Bronx NY 10468-3904

POINT OF CONTACT*

Contract Specialist Yasmin Moses Yasmin.Moses@va.gov

PLACE OF PERFORMANCE

ADDRESS
Department of Veterans Affairs

VA New Jersey Healthcare System

Lyons Campus

151 Knollcroft Road

Lyons New Jersey

POSTAL CODE
07939
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

Lyons Fire Protections Systems

Solicitation Questions and Reponses

Question 1 - The Price/Cost Schedule currently includes Line Item X015 in each contract year. However, the described task for this line item is to perform a five (5)‑year full flow test of the fire hydrants, which based on NFPA 291 is only required to be performed once within the five‑year inspection cycle.

Response- Line items 1015, 2015, 3015, and 4015 have been removed from the Price/Cost Schedule. Please see revised schedule below.

All interested companies shall provide quotations for the following:

Supplies/Services

Line Item
Description
Quantity
Unit of Measure
Unit Price
Total Price

BASE PERIOD- April 13, 2026 – April 12, 2027

0001
Annual ITM on Fire Extinguishers
349
YR
0002
Annual Inspection on Fire Hydrants
40
EA
0003
Annual Flow Test on Fire Pumps
2
EA
0004
Annual Inspections on Sprinkler Backflow Preventers
10
EA
0005
Annual Recycling and Replacement of Extinguishers
50
EA
0006
Quarterly Main Drain Testing at all Backflow Preventer Locations
1
YR
0007
Semi-Annual Inspection of 25 Wet and Dry Sprinkler Systems
2
JB
0008
Semi-Annual Inspection of 1 Anti-Freeze Sprinkler System
2
JB
0009
Semi-Annual Testing of Kitchen Hood Suppression Systems
1
YR

NSP

Price SLINs Below

0009AA
Semi-Annual Testing of Ansul Kitchen Hood Suppression Systems

(Current Quantity 4, Quantity may change during the life of the contract)

2
JB
0009AB
Semi-Annual Testing of Kidde Kitchen Hood Suppression Systems (Current Quantity 7- Quantity may change during the life of the contract)
2
JB
0009AC
Semi-Annual Testing of Buckeye system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
0009AD
Semi-Annual Testing of Denlar system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
0010
Semi-Annual Inspection of 197 Tamer Switches
2
JB
0011
Semi-Annual Inspection of 124 Waterflow Switches
2
JB
0012
Replace Expired Sprinkler Heads (not to exceed quantity listed)
500
EA
0013
Labor Rate for Repairs (see SOW, section F5)
1
HR
0014
Provide Parts/Material
1
LT

Refer to FAR 52.212-1

0015
Fire Hydrants, Five Year Full Flow Testing IAW NFPA 291
40
EA

OPTION 1 - April 13, 2027 – April 12, 2028

1001
Annual ITM on Fire Extinguishers
349
YR
1002
Annual Inspection on Fire Hydrants
40
EA
1003
Annual Flow Test on Fire Pumps
2
EA
1004
Annual Inspections on Sprinkler Backflow Preventers
10
EA
1005
Annual Recycling and Replacement of Extinguishers
50
EA
1006
Quarterly Main Drain Testing at all Backflow Preventer Locations
1
YR
1007
Semi-Annual Inspection of 25 Wet and Dry Sprinkler Systems
2
JB
1008
Semi-Annual Inspection of 1 Anti-Freeze Sprinkler System
2
JB
1009
Semi-Annual Testing of Kitchen Hood Suppression Systems
1
YR

NSP

Price SLINs Below

1009AA
Semi-Annual Testing of Ansul Kitchen Hood Suppression Systems

(Current Quantity 4, Quantity may change during the life of the contract)

2
JB
1009AB
Semi-Annual Testing of Kidde Kitchen Hood Suppression Systems (Current Quantity 7- Quantity may change during the life of the contract)
2
JB
1009AC
Semi-Annual Testing of Buckeye system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
1009AD
Semi-Annual Testing of Denlar system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
1010
Semi-Annual Inspection of 197 Tamer Switches
2
JB
1011
Semi-Annual Inspection of 124 Waterflow Switches
2
JB
1012
Replace Expired Sprinkler Heads (not to exceed quantity listed)
500
EA
1013
Labor Rate for Repairs (see SOW, section F5)
1
HR
1014
Provide Parts/Material
1
LT

Refer to FAR 52.212-1

OPTION 2- April 13, 2028 – April 12, 2029

2001
Annual ITM on Fire Extinguishers
349
YR
2002
Annual Inspection on Fire Hydrants
40
EA
2003
Annual Flow Test on Fire Pumps
2
EA
2004
Annual Inspections on Sprinkler Backflow Preventers
10
EA
2005
Annual Recycling and Replacement of Extinguishers
50
EA
2006
Quarterly Main Drain Testing at all Backflow Preventer Locations
1
YR
2007
Semi-Annual Inspection of 25 Wet and Dry Sprinkler Systems
2
JB
2008
Semi-Annual Inspection of 1 Anti-Freeze Sprinkler System
2
JB
2009
Semi-Annual Testing of Kitchen Hood Suppression Systems
1
YR

NSP

Price SLINs Below

2009AA
Semi-Annual Testing of Ansul Kitchen Hood Suppression Systems

(Current Quantity 4, Quantity may change during the life of the contract)

2
JB
2009AB
Semi-Annual Testing of Kidde Kitchen Hood Suppression Systems (Current Quantity 7- Quantity may change during the life of the contract)
2
JB
2009AC
Semi-Annual Testing of Buckeye system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
2009AD
Semi-Annual Testing of Denlar system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
2010
Semi-Annual Inspection of 197 Tamer Switches
2
JB
2011
Semi-Annual Inspection of 124 Waterflow Switches
2
JB
2012
Replace Expired Sprinkler Heads (not to exceed quantity listed)
500
EA
2013
Service Labor Rate for Repairs (see SOW, section F5)
1
HR
2014
Provide Parts/Material
1
LT

Refer to FAR 52.212-1

OPTION 3- April 13, 2029 – April 12, 2030

3001
Annual ITM on Fire Extinguishers
349
YR
3002
Annual Inspection on Fire Hydrants
40
EA
3003
Annual Flow Test on Fire Pumps
2
EA
3004
Annual Inspections on Sprinkler Backflow Preventers
10
EA
3005
Annual Recycling and Replacement of Extinguishers
50
EA
3006
Quarterly Main Drain Testing at all Backflow Preventer Locations
1
YR
3007
Semi-Annual Inspection of 25 Wet and Dry Sprinkler Systems
2
JB
3008
Semi-Annual Inspection of 1 Anti-Freeze Sprinkler System
2
JB
3009
Semi-Annual Testing of Kitchen Hood Suppression Systems
1
YR

NSP

Price SLINs Below

3009AA
Semi-Annual Testing of Ansul Kitchen Hood Suppression Systems

(Current Quantity 4, Quantity may change during the life of the contract)

2
JB
3009AB
Semi-Annual Testing of Kidde Kitchen Hood Suppression Systems (Current Quantity 7- Quantity may change during the life of the contract)
2
JB
3009AC
Semi-Annual Testing of Buckeye system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
3009AD
Semi-Annual Testing of Denlar system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
3010
Semi-Annual Inspection of 197 Tamer Switches
2
JB
3011
Semi-Annual Inspection of 124 Waterflow Switches
2
JB
3012
Replace Expired Sprinkler Heads (not to exceed quantity listed)
500
EA
3013
Labor Rate for Repairs (see SOW, section F5)
1
HR
3014
Provide Parts/Material
1
LT

Refer to FAR 52.212-1

OPTION 4 - April 13, 2030 – April 12, 2031

4001
Annual ITM on Fire Extinguishers
349
YR
4002
Annual Inspection on Fire Hydrants
40
EA
4003
Annual Flow Test on Fire Pumps
2
EA
4004
Annual Inspections on Sprinkler Backflow Preventers
10
EA
4005
Annual Recycling and Replacement of Extinguishers
50
EA
4006
Quarterly Main Drain Testing at all Backflow Preventer Locations
1
YR
4007
Semi-Annual Inspection of 25 Wet and Dry Sprinkler Systems
2
JB
4008
Semi-Annual Inspection of 1 Anti-Freeze Sprinkler System
2
JB
4009
Semi-Annual Testing of Kitchen Hood Suppression Systems
1
YR

NSP

Price SLINs Below

4009AA
Semi-Annual Testing of Ansul Kitchen Hood Suppression Systems

(Current Quantity 4, Quantity may change during the life of the contract)

2
JB
4009AB
Semi-Annual Testing of Kidde Kitchen Hood Suppression Systems (Current Quantity 7- Quantity may change during the life of the contract)
2
JB
4009AC
Semi-Annual Testing of Buckeye system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
4009AD
Semi-Annual Testing of Denlar system Kitchen Hood Suppression Systems (Current Quantity 1- Quantity may change during the life of the contract)
2
JB
4010
Semi-Annual Inspection of 197 Tamer Switches
2
JB
4011
Semi-Annual Inspection of 124 Waterflow Switches
2
JB
4012
Replace Expired Sprinkler Heads (not to exceed quantity listed)
500
EA
4013
Labor Rate for Repairs (see SOW, section F5)
1
HR
4014
Provide Parts/Material
1
LT

Refer to FAR 52.212-1

Question 2- The solicitation instructions request submission of sample quarterly, semi-annual, and annual inspection reports as part of the Technical Capability Statement, which is limited to 10 pages. However, the requested inspection reports, in their complete and representative form, could reasonably total dozens of pages and would significantly reduce space available for other required elements, including the Written Plan and NICET certifications with evidence of experience. To ensure full compliance with all submission requirements while maintaining clarity and document quality, we respectfully request clarification on the following…

Response- A technical capability statement that clearly and concisely describes how the offeror will provide the required services without parroting back each section of the statement of work. This should be a maximum 20-page technical capability statement demonstrating the Vendor’s technical capability to meet all the requirements of the statement of work.

*= Required Field
Amendment to a Previous Combined Solicitation

Page 1 of

Amendment to a Previous Combined Solicitation

File details come from the government source that posted it. Updated .