This is a 100% Construction Documents package for the Samuel S. Stratton Department of Veterans Affairs Medical Center in Albany, NY, detailing facade repairs, roof repairs, and interior abatement work for Project No. 528A8-21-812.
The project scope encompasses facade repairs to the A-Wing, B-Wing chapel area, and core entrance roof repairs, with a total construction duration of 30 weeks (210 days). Work is phased into six phases: Phase 1 addresses A-Wing parapet repairs (weeks 8-11); Phase 2 covers A-Wing roof work (weeks 12-15); Phase 3 and 4 include A-Wing facade cleaning and repairs (weeks 16-18 and 19-22); Phase 5 addresses core entrance area roof repairs (week 23-24); and Phase 6 encompasses B-Wing 11th floor chapel area work including asbestos abatement and mold remediation (weeks 25-29). The documents include detailed elevation drawings, repair procedures, material specifications, and construction details. Key repair work includes replacing cracked or spalled masonry, repointing open masonry joints, replacing stone units and brick, removing and replacing mortar and sealants, roof membrane repairs, window replacement, and facade cleaning. The B-Wing chapel area requires comprehensive asbestos abatement of floor tiles, mastic, and caulking, as well as mold remediation with EPA-approved disinfectants. All asbestos work must be performed by NYSDOL-certified handlers and supervisors. The construction documents include keyed notes, general notes, schedules, typical details, and infection control precautions for the occupied medical facility.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE LOCATION
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
BUILDING 1
(AREA OF
WORK)
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
SITE SAFETY & PROPOSED STAGING PLAN1
SAFETY NOTES:
LEGEND:
GENERAL NOTES:
REFERENCE RADIO FREQUENCY EXPOSURE MAPS (NTS):
0 . - . "' C m • C
ID
L ii C
_c u Q_
- 2 0 <{ 0 -
• n C st-m I 10 go
"' st- 0 N
£ I C • N 0 "' I
TI
C a ic:111 f C 0 70
�w N �o ii "' z 3'
0 JJ "'
-2 0 c 0 I 0 g (.() Ct:::•- I
• f-- C 0 -
0 - I
<I) (I) g
N rC:::
• (IJ
C (I) 0 .£:
£ <I)
0 (IJ
C -
LL
m C to C a "0 �, 0 "' L
• 0•
/£ - <I) u (I) Q_
"1i
... ,,lJ <I) C 0 -
0..
C 0 0
.D
£ / 0 C
00 I £
ID wC LL 0
I
<I) L - Q_
(I) g O' -
Q) • C cJ o 0 u
£ ' 'LL
0 s m
:0 § � -
£ -- 0 L
(I) (I) ro� <l'. 0 <I)
-2 (IJ
• LL
C 0 -u
(IJ
£ 0 L
C 0..
C / ID u
0 => �
Q_ .o / C <I) 0 Q)
E
_c N n -w
"'�8~ - N g n- -
C Q 0 0
I £ 0) 0 0 "" C 0
:c'" "' � <I) ·a 0 •co -C: I I Revisions, 0 >-
VA FORM 08-6231
Date
CONSULTANTS:
TIPONS
AIIOCIATII, ,.c. I STRUCTURAL ENQINEERS
70 South Franklin Street Wilkes-Barre, PA 18701 570 I 824-6340 info@edpons.com edpons.com
2 3
A Adelaide
.....- " ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
REGISTRATION EXPIRES: 08/31/2026
4 5 6
Coping Level (231.312' ±)
12th FL.
(228.333' ±)
11th FL.
(216.416' ±)
1 oth FL.
(203.583' ±)
9th FL.
(192.583' ±)
8th FL.
(181.583' ±)
7th FL.
(170.583' ±)
6th FL.
(159.583' ±)
5th FL.
(148.583' ±)
4th FL.
(137.125' ±)
3rd FL .
(124.520' ±)
2nd FL.
(111.916' ±)
1 st FL .
(100.000' ±)
BASEMENT
(88.089' ±)
SUB BASEMENT
(75.083' ±)
ARCHITECT /ENGINEERS:
Drawilg Trtle
A-WING
I
;-l::'m I
N-
I
I
I = I
I
I
I
-1
;J:: r-- I
N
;J::r--
I N
I
<D I n
GRADE
I
I I
11 '---------'I I ;
II
I :
a
8 9
ASBESTOS AWARENESS KEYNOTES
H H H J I / / J I / / J I
Ill 111 111
1r//lr//ll
STONE PANEL ADHESIVE IS PRESUMED ASBESTOS CONTAINING MATERIAL (PACM). DURING THE COURSE OF THE WORK. THE ADJACENT MORTAR & SEALANT REMOVAL AT THE LIMESTONE BANDS SHALL NOT DISTURB THE UNDERLYING PANEL ADHESIVE. NO DISTURBANCE OF STONE PANELS IS SCHEDULE, BUT IF ANY DISTURBANCE OCCURS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK, VACATE THE WORK AREA
AND CONTACT THE ENVIRONMENT AL CONSUL TANT.
l''---------'11 ' ' I
Ill I I ri 7 /ri 7 7n1111 I I I I
""'" / ,, ,- / /111 11
0 GRADE
a L ______ � _____ _J
WING C WING D
ELEVATION A-3
SCALE, 1/s"-1'-o"
CORE
WING B WING A
GENERAL NOTES:
1. REFERENCE SHEETS AS-102 FOR KEYED NOTES FOR COORDINATING ARCHITECTURAL SCOPE
ON ELEVATION A-3 ..
1100% CONSTRUCTION DOCUMENT�
Project Trtle
VA STRATTON
Project NIJTlber s28A8-21-a12 11 Off ice of
UNAUTHORIZED ALTERATION OR ADDmON TO A PLAN BEARING A LICENSED PROFESSIONAL ENGINEER'S SEAL IS A VIOLATION OF SECTION 7209, SUB-DMSION 2 OF THE N.Y. STATE EDUCATION LAW. ELEVATIONS A-3 ASBESTOS AWARENESS FACADE A WING REPAIRS L ilgNumb r Construction and Facilities Management FELLENZER Ill
FE PROJECT NO:
17· 103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940
1 845-343-1481; fx 855-320-8735
ENGINEERING LLP www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735
Approved, Ergileering Manager
DEPT OF VETERANS AFFAIRS
NElWORK CONTRACTING OFRCE 2
2875 UNION ROAD, SUITE 3500
CHEEKTOWAGA NY 14227
� I Location Ir Drawilg NIJTlber _ ALBANY, NY IDate I !Checked
I Drawn H A - 1 0 0
JF AEHA Dwg. 3 of 26
8 9
� Department of � Veterans Affairs
A
I . 3
I C
I
I
F
10/25/24
AutoCAD SHX Text 8/28/24
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
B-WING 11TH FLR CHAPEL ABATEMENT PLAN1
1. ALL ASBESTOS CONTAINING MATERIALS (ACM) AND PRESUMED ASBESTOS CONTAINING MATERIALS (PACM) SHALL BE REMOVED AND DISPOSED OF IN ACCORDANCE WITH THE SPECIFICATION AND APPLICABLE REGULATIONS. PERSONNEL HOLDING CURRENT NEW YORK STATE DEPARTMENT OF LABOR (NYSDOL) ASBESTOS HANDLER'S CERTIFICATES SHALL PERFORM THE WORK. ADDITIONALLY, THE CONTRACTOR MUST EMPLOY NYSDOL CERTIFIED SUPERVISORS TO BE ON THE WORK SITE FOR ALL ABATEMENT ACTIVITIES. THE CONTRACTOR MUST BE CURRENTLY LICENSED BY THE NYSDOL. ALL CERTIFICATES AND LICENSES ARE TO BE READILY AVAILABLE FOR VERIFICATION BY THE VETERANS AFFAIRS MEDICAL CENTER (VAMC).
2. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND DISPOSAL OF ALL ASBESTOS-CONTAINING MATERIALS AND ASBESTOS-CONTAMINATED MATERIALS WITHIN THE SPECIFIED AREAS. ALL ASBESTOS ABATEMENT WORK SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OF ANY OTHER WORK UNLESS NOTED OTHERWISE
3. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES OF ASBESTOS-CONTAINING
MATERIALS.
4. CONTRACTOR IS RESPONSIBLE FOR PRECLEANING ANY EXISTING ASBESTOS CONTAMINATION, DUST AND
DEBRIS WITHIN THE REMOVAL AREAS.
5. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF BUILDING FINISHES. THE CONTRACTOR SHALL REPAIR ANY AND ALL DAMAGES CAUSED BY ABATEMENT ACTIVITIES OR HIS PERSONNEL.
6. CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES AND FOR COORDINATING ALL PORTIONS OF THE SCOPE OF WORK UNDER THIS CONTRACT.
7. THE WORK WILL BE PHASED TO ACCOMMODATE THE VAMC FACILITY REQUIREMENTS. WORK MAY HAVE TO BE
PERFORMED OFF-HOURS, WEEKENDS AND AT NIGHT AT NO ADDITIONAL COST TO THE VAMC.
8. THE PROJECT SHALL BE FILED AS A LARGE PROJECT WITH THE NYSDOL AND USEPA.
ASBESTOS ABATEMENT KEYNOTES QTY
GENERAL ASBESTOS ABATEMENT NOTES
AA1 REMOVE ANCHORING DEVICES AND REMOVE / DECONTAMINATE PEWS AND OTHER ITEMS
ANCHORED THROUGH ASBESTOS CONTAINING FLOOR TILE OF ALL ACM. STORE CHURCH
PEWS, KNEELERS, PULPIT, ALTAR AND ALL SIMILAR FIXED FURNISHINGS IN LOCATION
DETERMINED BY VA.
TYP. FOR 150 SQ. FT.
AA2
AA3 NOT USED
AA4 PRIOR TO ANY WINDOW REPLACEMENT WORK COMMENCING, REMOVE EXISTING STAINED
GLASS PANELS AND STORE FOR RE-INSTALLATION. REMOVE & DISPOSE OF EXTERIOR
PERIMETER PACM CAULKING AND EXISTING WINDOW SYSTEMS WITH PACM GLAZING
COMPOUND.
TYP. FOR 2,050 SQ. FT.
TYP. FOR 120 LIN FT.
CAULK & 180 LIN. FT.
GLAZING COMPOUND
AA1
AA1
AA1
AA1
AA1
REMOVE AND DISPOSE OF FLOOR TILE & MASTIC ON CONCRETE FLOOR.
AA2
AA2
AA4
AA4
AA4 AA4 AA4 AA4 AA4
AA4 AA4 AA4 AA4 AA4
B-WING 11TH FLR CHAPEL SOUTH ELEVATION ABATEMENT3
B-WING 11TH FLR CHAPEL NORTH ELEVATION ABATEMENT2
*USE PROFESSIONAL JUDGMENT TO DETERMINE PRUDENT LEVELS OF
PERSONAL PROTECTIVE EQUIPMENT AND CONTAINMENT FOR EACH
SITUATION, PARTICULARLY AS THE REMEDIATION SITE SIZE
INCREASES AND THE POTENTIAL FOR EXPOSURE AND HEALTH
EFFECTS RISES. ASSESS THE NEED FOR INCREASED PERSONAL
PROTECTIVE EQUIPMENT, IF, DURING THE REMEDIATION, MORE
EXTENSIVE CONTAMINATION IS ENCOUNTERED THAN WAS EXPECTED.
THESE GUIDELINES ARE FOR DAMAGE CAUSED BY CLEAN WATER. IF
YOU KNOW OR SUSPECT THAT THE WATER SOURCE IS CONTAMINATED
WITH SEWAGE, OR CHEMICAL OR BIOLOGICAL POLLUTANTS, THEN THE
OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA)
REQUIRES PPE AND CONTAINMENT. AN EXPERIENCED PROFESSIONAL
SHOULD BE CONSULTED IF YOU AND/OR YOUR REMEDIATORS DO NOT
HAVE EXPERTISE IN REMEDIATING CONTAMINATED WATER
SITUATIONS.
CLEANUP METHODS
METHOD 1: WET VACUUM (IN THE CASE OF POROUS MATERIALS, SOME
MOLD SPORES/FRAGMENTS WILL REMAIN IN THE MATERIAL BUT WILL
NOT GROW IF THE MATERIAL IS COMPLETELY DRIED). STEAM
CLEANING MAY BE AN
ALTERNATIVE FOR CARPETS AND SOME UPHOLSTERED FURNITURE.
METHOD 2: DAMP-WIPE SURFACES WITH PLAIN WATER OR WITH
WATER AND DETERGENT SOLUTION (EXCEPT WOOD--USE WOOD
FLOOR CLEANER); SCRUB AS NEEDED.
METHOD 3: HIGH-EFFICIENCY PARTICULATE AIR (HEPA) VACUUM AFTER
THE MATERIAL HAS BEEN THOROUGHLY DRIED. DISPOSE OF THE
CONTENTS OF THE HEPA VACUUM IN WELL-SEALED PLASTIC BAGS.
METHOD 4: DISCARD - REMOVE WATER-DAMAGED MATERIALS AND
SEAL IN PLASTIC BAGS WHILE INSIDE OF CONTAINMENT, IF PRESENT.
DISPOSE OF AS NORMAL WASTE. HEPA VACUUM AREA AFTER IT IS
DRIED.
PERSONAL PROTECTIVE EQUIPMENT (PPE)
MINIMUM: GLOVES, N-95 RESPIRATOR, GOGGLES/EYE PROTECTION
LIMITED: GLOVES, N-95 RESPIRATOR OR HALF-FACE RESPIRATOR WITH
HEPA FILTER, DISPOSABLE OVERALLS, GOGGLES/EYE PROTECTION
FULL: GLOVES, DISPOSABLE FULL BODY CLOTHING, HEAD GEAR, FOOT
COVERINGS, FULL-FACE RESPIRATOR WITH HEPA FILTER
CONTAINMENT
LIMITED: USE POLYETHYLENE SHEETING CEILING TO FLOOR AROUND
AFFECTED AREA WITH A SLIT ENTRY AND
COVERING FLAP; MAINTAIN AREA UNDER NEGATIVE PRESSURE WITH
HEPA FILTERED FAN UNIT. BLOCK SUPPLY AND RETURN AIR VENTS
WITHIN CONTAINMENT AREA.
FULL: USE TWO LAYERS OF FIRE-RETARDANT POLYETHYLENE
SHEETING WITH ONE AIRLOCK CHAMBER. MAINTAIN AREA UNDER
NEGATIVE PRESSURE WITH HEPA FILTERED FAN EXHAUSTED OUTSIDE
OF BUILDING. BLOCK SUPPLY AND RETURN AIR VENTS WITHIN
CONTAINMENT AREA.
TABLE DEVELOPED FROM LITERATURE AND REMEDIATION
DOCUMENTS INCLUDING BIOAEROSOLS: ASSESSMENT ANDCONTROL
(AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL
HYGIENISTS, 1999) AND IICRC S500,
STANDARD AND REFERENCE GUIDE FOR PROFESSIONAL WATER
DAMAGE RESTORATION (INSTITUTE OF INSPECTION, CLEANING AND
RESTORATION, 1999); SEE RESOURCES LIST FOR MORE INFORMATION.)
GENERAL MOLD REMEDIATION NOTES & GUIDELINES
REMOVE AND DISPOSE OF MOLD ON WALLS.
MOLD REMEDIATION KEYNOTES QTY
400 sq. ft.
CHAPEL
1. ESTABLISH CONTAINMENT OF THE CHAPEL AFTER ASBESTOS ABATEMENT IS COMPLETE.
2. INSTALL AIRLOCK TO ENTRANCE OF CONTAINMENT STRUCTURE AND UTILIZE AN AIR EXCHANGE UNIT
(NEGATIVE PRESSURE), EXHAUSTING TO THE EXTERIOR OF THE BUILDING PRIOR TO MOLD ABATEMENT.
3. REMOVAL OF WALLPAPER TO EXPOSE MOLD AFFECTED AREAS.
4. ALL AREAS WITHIN THE CHAPEL WILL HAVE A THOROUGH CLEANING WITH AN EPA APPROVED ANTI-MICROBIAL
DISINFECTANT THROUGHOUT CONTAINMENT AREA LIMITED TO: WALLS
MOLD WORK NOTES:
M1
M1
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
AA2
M1
M1
AA2
M1
REGISTRATION EXPIRES: 08/31/2026
ALTAR
10/25/24
AutoCAD SHX Text
SW4
AutoCAD SHX Text C1101b
AutoCAD SHX Text B1102
AutoCAD SHX Text B1101
AutoCAD SHX Text
ALTER
AutoCAD SHX Text
CHAPEL 9'-9" C.H. (B1103)
AutoCAD SHX Text 11th FL.
AutoCAD SHX Text (216.416' ±)
AutoCAD SHX Text 12th FL.
AutoCAD SHX Text (228.333' ±)
AutoCAD SHX Text Coping Level
AutoCAD SHX Text (231.312' ±)
AutoCAD SHX Text 11th FL.
AutoCAD SHX Text (216.416' ±)
AutoCAD SHX Text 12th FL.
AutoCAD SHX Text (228.333' ±)
AutoCAD SHX Text Coping Level
AutoCAD SHX Text (231.312' ±)
AutoCAD SHX Text
ALBANY, NY
AutoCAD SHX Text 528A8-21-812
AutoCAD SHX Text 8/28/24
AutoCAD SHX Text UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN BEARING A LICENSED PROFESSIONAL ENGINEER'S SEAL IS A VIOLATION OF SECTION 7209, SUB-DIVISION 2 OF THE N.Y. STATE EDUCATION LAW.
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Engineering Manager
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
AutoCAD SHX Text
VA STRATTON FACADE A WING REPAIRS
AutoCAD SHX Text
JF
AutoCAD SHX Text
AEHA
AutoCAD SHX Text
AutoCAD SHX Text DEPT OF VETERANS AFFAIRS NETWORK CONTRACTING OFFICE 2 2875 UNION ROAD, SUITE 3500 CHEEKTOWAGA, NY 14227
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
B-WING PARTIAL 11TH ASBESTOS ABATEMENT PLAN, ELEVATIONS AND MOLD REMEDIATION
AutoCAD SHX Text
HA-101
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
12 2
12 2
ELEVATION B-11 ELEVATION B-102
SECTION AT PARAPET WALL ABOVE CHAPEL3 SECTION AT BRICK INFILL4 FLASHING DETAIL5
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701
570 | 824-6340 info@edpons.com edpons.com
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
%%UWING C
AutoCAD SHX Text %%uCORE
AutoCAD SHX Text
%%UWING B
AutoCAD SHX Text
%%UWING D
AutoCAD SHX Text
%%UWING A
AutoCAD SHX Text
%%UWING C
AutoCAD SHX Text %%uCORE
AutoCAD SHX Text
%%UWING B
AutoCAD SHX Text
%%UWING D
AutoCAD SHX Text
%%UWING A
AutoCAD SHX Text 11th FL.
AutoCAD SHX Text (216.416' ±)
AutoCAD SHX Text 10th FL.
AutoCAD SHX Text (203.583' ±)
AutoCAD SHX Text 12'-10"
AutoCAD SHX Text 12th FL.
AutoCAD SHX Text (228.333' ±)
AutoCAD SHX Text 11'-11"
AutoCAD SHX Text Coping Level
AutoCAD SHX Text (231.312' ±)
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text (E)S15x42.9
AutoCAD SHX Text (E)S12x31.8
AutoCAD SHX Text (E)W14x30
AutoCAD SHX Text
COL C
AutoCAD SHX Text L
AutoCAD SHX Text
COL C
AutoCAD SHX Text L
AutoCAD SHX Text
COL C
AutoCAD SHX Text L
AutoCAD SHX Text (E)S15x42.9
AutoCAD SHX Text (E)S12x31.8
AutoCAD SHX Text (E)W14x30
AutoCAD SHX Text
COL C
AutoCAD SHX Text L
AutoCAD SHX Text
COL C
AutoCAD SHX Text L
AutoCAD SHX Text
COL C
AutoCAD SHX Text L
AutoCAD SHX Text
COL C
AutoCAD SHX Text L
AutoCAD SHX Text
COL C
AutoCAD SHX Text L
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text KEY NOTES: 1. INSTALL 3/8"X1'-10" BOTTOM PLATE CONT. INSTALL 3/8"X1'-10" BOTTOM PLATE CONT. 2. REINSTALL STONE TO MATCH EXISTING. REINSTALL STONE TO MATCH EXISTING. 3. INSTALL NEW BRICK OVER WINDOW TO MATCH INSTALL NEW BRICK OVER WINDOW TO MATCH EXISTING. 4. SEE DRAWING AS-301 FOR ADDITIONAL SEE DRAWING AS-301 FOR ADDITIONAL INFORMATION NOT SHOWN HERE
AutoCAD SHX Text 27'-8"
AutoCAD SHX Text 27'-8"
AutoCAD SHX Text
SCALE: 1/8"=1'-0"
AutoCAD SHX Text
SCALE: 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 21'-8"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
T/COPING
AutoCAD SHX Text
FIN. 12TH FL.
AutoCAD SHX Text 1'-10"±
AutoCAD SHX Text
%%URECONSTRUCTION
AutoCAD SHX Text
%%UREMOVALS
AutoCAD SHX Text
SCALE: 1"=1'-0"
AutoCAD SHX Text
EXIST. BUILT-UP ROOFING OVER CONC. DECK
AutoCAD SHX Text REMOVE EXIST. STONE, ANY ANY STONE THAT IS CRACKED DURING REMOVAL SHALL BE REPLACED AT NO ADDITIONAL COST TO THE VA.
AutoCAD SHX Text
REMOVE EXIST. PLATE
AutoCAD SHX Text
REMOVE (3)-COURSES OF BLOCK OVER BEAM
AutoCAD SHX Text
T/COPING
AutoCAD SHX Text
FIN. 12TH FL.
AutoCAD SHX Text 1'-4 1/2"±
AutoCAD SHX Text 1'-10"±
AutoCAD SHX Text
EXIST. BUILT-UP ROOFING OVER CONC. DECK
AutoCAD SHX Text
INSTALL 3/8"X1'-10" BOTTOM PLATE CONT.
AutoCAD SHX Text
BRICK TIES
AutoCAD SHX Text
INSTALL (3) COURSES OF BRICK
AutoCAD SHX Text
NEW COPPER FLASHING
AutoCAD SHX Text
REMOVE BRICK ON INTERIOR IN SECTIONS AS REQ'D TO INSTALL NEW PLATE
AutoCAD SHX Text
REINSTALL STONE
AutoCAD SHX Text
CLEAN EXIST. SPANDREL SUPPORT. CLEAR WEEP HOLE LOCATIONS FROM OBSTRUCTION
AutoCAD SHX Text
INSTALL BRICK AND REPAIR ALL INTERIOR FINISHES AFTER BRICK INSTALLATION
AutoCAD SHX Text 8 1/4"±
AutoCAD SHX Text
T/COPING
AutoCAD SHX Text
FIN. 12TH FL.
AutoCAD SHX Text 1'-10"±
AutoCAD SHX Text
%%URECONSTRUCTION
AutoCAD SHX Text
%%UREMOVALS
AutoCAD SHX Text
SCALE: 1"=1'-0"
AutoCAD SHX Text
EXIST. BUILT-UP ROOFING OVER CONC. DECK
AutoCAD SHX Text
REMOVE EXIST. PLATE
AutoCAD SHX Text
REMOVE (3)-COURSES OF BLOCK OVER BEAM
AutoCAD SHX Text
T/COPING
AutoCAD SHX Text
FIN. 12TH FL.
AutoCAD SHX Text 1'-4 1/2"±
AutoCAD SHX Text 1'-10"±
AutoCAD SHX Text
INSTALL 3/8"X1'-10" BOTTOM PLATE CONT.
AutoCAD SHX Text
BRICK TIES
AutoCAD SHX Text
INSTALL (3) COURSES OF BRICK
AutoCAD SHX Text
SEE PLAN FOR BEAM SIZE
AutoCAD SHX Text
REMOVE BRICK ON INTERIOR IN SECTIONS AS REQ'D TO INSTALL NEW PLATE
AutoCAD SHX Text
REINSTALL STONE
AutoCAD SHX Text
CLEAN EXIST. SPANDREL SUPPORT. CLEAR WEEP HOLE LOCATIONS FROM OBSTRUCTION
AutoCAD SHX Text
INSTALL BRICK AND REPAIR ALL INTERIOR FINISHES AFTER BRICK INSTALLATION
AutoCAD SHX Text 8 1/4"±
AutoCAD SHX Text
INSTALL (3) COURSES OF BRICK
AutoCAD SHX Text
14"X1 " H.D. GALV. 12" H.D. GALV. BRICK TIE @ 16" O.C.
AutoCAD SHX Text L2"x2"x " CONT. 316" CONT. H.D. GALV. .
AutoCAD SHX Text
SEE PLAN FOR BEAM SIZE
AutoCAD SHX Text
SEE PLAN FOR BEAM SIZE
AutoCAD SHX Text
SEE PLAN FOR BEAM SIZE
AutoCAD SHX Text 316 3@12
AutoCAD SHX Text 316 3@12
AutoCAD SHX Text
8" @ 2END
AutoCAD SHX Text 316 3@12
AutoCAD SHX Text
8" @ 2END
AutoCAD SHX Text REMOVE EXIST. STONE, ANY ANY STONE THAT IS CRACKED DURING REMOVAL SHALL BE REPLACED AT NO ADDITIONAL COST TO THE VA.
AutoCAD SHX Text
NEW COPPER FLASHING
AutoCAD SHX Text
SEE DETAIL 5
AutoCAD SHX Text
SEE DETAIL 5
AutoCAD SHX Text
REMOVE EXIST. FLASHING
AutoCAD SHX Text
EXISTING BRICK VENEER
AutoCAD SHX Text
COPPER FLASHING
AutoCAD SHX Text
LEAD WEDGE
AutoCAD SHX Text
SEALANT
AutoCAD SHX Text
1" MIN.
AutoCAD SHX Text
SAWCUT EXIST MORTAR JOINT TO INSTALL REGLET
AutoCAD SHX Text
SCALE: 3"=1'-0"
AutoCAD SHX Text
ALBANY, NY
AutoCAD SHX Text 528A8-21-812
AutoCAD SHX Text 10/25/24
AutoCAD SHX Text UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN BEARING A LICENSED PROFESSIONAL ENGINEER'S SEAL IS A VIOLATION OF SECTION 7209, SUB-DIVISION 2 OF THE N.Y. STATE EDUCATION LAW.
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Engineering Manager
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
AutoCAD SHX Text
VA STRATTON FACADE A WING REPAIRS
AutoCAD SHX Text
JDF
AutoCAD SHX Text
SRB, SLB
AutoCAD SHX Text
AutoCAD SHX Text DEPT OF VETERANS AFFAIRS NETWORK CONTRACTING OFFICE 2 2875 UNION ROAD, SUITE 3500 CHEEKTOWAGA, NY 14227
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
B-WING ELEVATIONS B-1 & B-10
AutoCAD SHX Text
SS-101
AutoCAD SHX Text
User Stamp
User
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
PARTIAL KEY PLAN1
OVERHEAD VIEW2
CLEANING BRICKWORK / MASONRY PROCEDURE:
LEGEND
GENERAL NOTES:
CONSTRUCTION PHASING PLAN
30 WEEKS TOTAL
Description of Required Infection Control Precautions by Class During Construction Project Upon Completion of
1. Remove or isolate HVAC system in area where work is being done to prevent contamination of duct system.
2. Complete all critical barriers, i.e., sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with HEPA vacuum for vacuuming prior to exit) before construction begins.
3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.
4. Contain construction waste before transport in tightly covered containers.
5. Cover transport receptacles or carts. Tape covering unless solid lid.
6. All personnel entering work site are required to wear shoe covers. Shoe covers must be changed each time the worker exits the work area.
7. Do not remove barriers from work area until completed project is inspected by the owner's Safety Section and Infection Control Department, and thoroughly cleaned by the owner's Environment Services Department.
1. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
2. Contain construction waste before transportation in tightly covered containers.
3. Cover transport receptacles or carts. Tape covering unless solid lid.
4. Vacuum work area with HEPA filtered vacuums.
5. Wet mop area with disinfectant.
6. Remove isolation of HVAC system in areas where work is being performed.
C la ss
IV
C la ss
II
I
1. Remove or isolate HVAC system in area where work is being done to prevent contamination of duct system.
2. Complete all critical barriers, i.e., sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with HEPA vacuum for vacuuming prior to exit) before construction begins.
3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.
4. Contain construction waste before transport in tightly covered containers.
5. Cover transport receptacles or carts. Tape covering unless solid lid.
6. All personnel entering work site are required to wear shoe covers. Shoe covers must be changed each time the worker exits the work area.
7. Do not remove barriers from work area until completed project is inspected by the owner's Safety Section and Infection Control Department, and thoroughly cleaned by the owner's Environment Services Department.
1. Do not remove barriers from work area until completed project is inspected by the owner’s Safety Department and Infection Control Department, and thoroughly cleaned by the owner’s Environmental Services Department.
2. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
3. Vacuum work area with HEPA filtered vacuums.
4. Wet mop area with disinfectant.
5. Remove isolation of HVAC system in areas where work is being performed.
NOTES:
PATIENT RISK GROUP FOR "TYPE D" CONSTRUCTION
LOW RISK GROUP
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP Class IV
Class III / IV
Class IV Class IV
DURATION DESCRIPTION
Weeks 1-6 Submittals
Week 7 Mobilization
Weeks 8-11 PHASE 1 (A-Wing Parapet)
Weeks 12-15 PHASE 2 (A-Wing Roof)
Weeks 16-18 PHASE 3 (A-Wing Cleaning & Repairs - AS-101)
Weeks 19-22 PHASE 4 (A-Wing Cleaning & Repairs - AS-102 & AS-103)
Week 23-24 PHASE 5 (Core Entrance Area Roof )
Weeks 25-29 PHASE 6 (B-Wing 11th Floor Chapel Area)
Week 30 Project Closeout:
Including: Closeout Documents, demobilization, etc.
Project Duration: 210 Days
Notes:
1. Certain activities may be combined for expediency.
2. All phasing and work is subject to the owner occupancy schedule.
3. All work needs to be coordinated with the COR in advance.
4. There will be no re-mobilization cost permitted. All work must be completed in allotted time frame.
5. Refer to spec section 01 32 16.15 for more information on Project Scheduling
Requirements.
PERFORMANCE SPECIFICATION:
FACADE CLEANING (KEYED NOTES 60, 61 & 62)
ABBREVIATIONS
ARCHITECTURAL LINE TYPES
ELEVATION A-11
4 5
10 10 10 10 10
ELEVATION A-22
111111
50 50
31 70
10 10
A-A
A
A
PARTIAL ELEVATION CORE-11A
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
MASONRY
SEALANT
SEAL ROUND ANCHORS
REMOVE PLYWOOD AROUND A/C UNIT
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
NOT USED.
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
REPLACE WINDOW SEALANT, MISSING OR INSUFFICIENT
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN OF CORROSION & DETERIORATION
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/AS-501 &
1/AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/AS-501 &
2/AS-602
3/AS-501
4/AS-501 &
8A, 8B &
8C/AS-602
5/AS-501 & 9
& 9A/AS-602
10/AS-501 &
6/AS-602
11/AS-501 &
7/AS-602
13/AS-501 &
16/AS-602
15/AS-501 &
16/AS-602
30/AS-501 &
10-12/AS-602
31/AS-501 &
3/AS-602
41/AS-502 &
4,5&13/AS-602
42/AS-502 &
5&6/AS-602A
50/AS-502
60/AS-502
61/AS-502
62/AS-502
70/AS-502
72/AS-502
81/AS-502
90/AS-502
91/AS-502 &
15/AS-602
100/AS-502 &
4&7/AS-603
101/AS-502 &
11/AS-603
103/AS-502 &
3,4&7/AS-603
110/AS-502 &
10/AS-603
111/AS-502 &
3-5/AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/AS-501 &
3A/AS-602
51 REPLACE LOUVER WITH ALUMINUM
70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
REMOVE STAINLESS STEEL WIREWAY AND REPLACE WITH
NEW AFTER STONE SEALANT INSTALLED
92 92/AS-502
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
QUOTATION & REPAIR:
TYPICAL DETAIL3
GENERAL NOTE:
ELEVATION A-42
50 50
1111 2
ELEVATION A-31
A
A
A-A
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
MASONRY
SEALANT
SEAL ROUND ANCHORS
REMOVE PLYWOOD AROUND A/C UNIT
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
NOT USED.
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
REPLACE WINDOW SEALANT, MISSING OR INSUFFICIENT
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN OF CORROSION & DETERIORATION
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/AS-501 &
1/AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/AS-501 &
2/AS-602
3/AS-501
4/AS-501 &
8A, 8B &
8C/AS-602
5/AS-501 & 9
& 9A/AS-602
10/AS-501 &
6/AS-602
11/AS-501 &
7/AS-602
13/AS-501 &
16/AS-602
15/AS-501 &
16/AS-602
30/AS-501 &
10-12/AS-602
31/AS-501 &
3/AS-602
41/AS-502 &
4,5&13/AS-602
42/AS-502 &
5&6/AS-602A
50/AS-502
60/AS-502
61/AS-502
62/AS-502
70/AS-502
72/AS-502
81/AS-502
90/AS-502
91/AS-502 &
15/AS-602
100/AS-502 &
4&7/AS-603
101/AS-502 &
11/AS-603
103/AS-502 &
3,4&7/AS-603
110/AS-502 &
10/AS-603
111/AS-502 &
3-5/AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/AS-501 &
3A/AS-602
51 REPLACE LOUVER WITH ALUMINUM
70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
REMOVE STAINLESS STEEL WIREWAY AND REPLACE WITH
NEW AFTER STONE SEALANT INSTALLED
92 92/AS-502
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
QUOTATION & REPAIR:
GENERAL NOTES:
TYPICAL DETAIL3
ELEVATION A-51
WARD WING
50 30
ELEVATION A-9
111111
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
MASONRY
SEALANT
SEAL ROUND ANCHORS
REMOVE PLYWOOD AROUND A/C UNIT
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
NOT USED.
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
REPLACE WINDOW SEALANT, MISSING OR INSUFFICIENT
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN OF CORROSION & DETERIORATION
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/AS-501 &
1/AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/AS-501 &
2/AS-602
3/AS-501
4/AS-501 &
8A, 8B &
8C/AS-602
5/AS-501 & 9
& 9A/AS-602
10/AS-501 &
6/AS-602
11/AS-501 &
7/AS-602
13/AS-501 &
16/AS-602
15/AS-501 &
16/AS-602
30/AS-501 &
10-12/AS-602
31/AS-501 &
3/AS-602
41/AS-502 &
4,5&13/AS-602
42/AS-502 &
5&6/AS-602A
50/AS-502
60/AS-502
61/AS-502
62/AS-502
70/AS-502
72/AS-502
81/AS-502
90/AS-502
91/AS-502 &
15/AS-602
100/AS-502 &
4&7/AS-603
101/AS-502 &
11/AS-603
103/AS-502 &
3,4&7/AS-603
110/AS-502 &
10/AS-603
111/AS-502 &
3-5/AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/AS-501 &
3A/AS-602
51 REPLACE LOUVER WITH ALUMINUM
70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
REMOVE STAINLESS STEEL WIREWAY AND REPLACE WITH
NEW AFTER STONE SEALANT INSTALLED
92 92/AS-502
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
PARTIAL ELEVATIONS A-72
PARTIAL ELEVATION A-83
PARTIAL ELEVATION A-94
PARTIAL ELEVATION A-125
QUOTATION & REPAIR:
RA 18
RA 16
RA 15
RA 17
CORE
ROOF #2A
ROOF #5A
RAMP
RA 44C
R A
4E
N .I.
S.
RAMP
RA 44B
RAMP
RA 44A
RAMP
RA 44C
R A
4D
N .I.
S.
R A
4E
N .I.
S.
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
MASONRY
SEALANT
SEAL ROUND ANCHORS
REMOVE PLYWOOD AROUND A/C UNIT
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
NOT USED.
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
REPLACE WINDOW SEALANT, MISSING OR INSUFFICIENT
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN OF CORROSION & DETERIORATION
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/AS-501 &
1/AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/AS-501 &
2/AS-602
3/AS-501
4/AS-501 &
8A, 8B &
8C/AS-602
5/AS-501 & 9
& 9A/AS-602
10/AS-501 &
6/AS-602
11/AS-501 &
7/AS-602
13/AS-501 &
16/AS-602
15/AS-501 &
16/AS-602
30/AS-501 &
10-12/AS-602
31/AS-501 &
3/AS-602
41/AS-502 &
4,5&13/AS-602
42/AS-502 &
5&6/AS-602A
50/AS-502
60/AS-502
61/AS-502
62/AS-502
70/AS-502
72/AS-502
81/AS-502
90/AS-502
91/AS-502 &
15/AS-602
100/AS-502 &
4&7/AS-603
101/AS-502 &
11/AS-603
103/AS-502 &
3,4&7/AS-603
110/AS-502 &
10/AS-603
111/AS-502 &
3-5/AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/AS-501 &
3A/AS-602
51 REPLACE LOUVER WITH ALUMINUM
70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
REMOVE STAINLESS STEEL WIREWAY AND REPLACE WITH
NEW AFTER STONE SEALANT INSTALLED
92 92/AS-502
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
A-WING ROOF PLAN1
GENERAL NOTES:
LEGEND
RA-18 STAIRWELL ELEVATIONS3
RA-17 STAIRWELL ELEVATIONS4
NOTE:
PARTIAL RAMP ROOF PLAN2
LEGEND
AREAS OF WORK
SECTION AT RAMP ROOF5
SCUPPER AREA AT RAMP ROOF6
A A A A A A A A A A
ELEVATION B-102
ELEVATIONS
EXTERIOR WINDOW SCHEDULE
A
PARTIAL ELEVATION B-11
GENERAL NOTES:
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
MASONRY
SEALANT
SEAL ROUND ANCHORS
REMOVE PLYWOOD AROUND A/C UNIT
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
NOT USED.
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
REPLACE WINDOW SEALANT, MISSING OR INSUFFICIENT
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN OF CORROSION & DETERIORATION
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/AS-501 &
1/AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/AS-501 &
2/AS-602
3/AS-501
4/AS-501 &
8A, 8B &
8C/AS-602
5/AS-501 & 9
& 9A/AS-602
10/AS-501 &
6/AS-602
11/AS-501 &
7/AS-602
13/AS-501 &
16/AS-602
15/AS-501 &
16/AS-602
30/AS-501 &
10-12/AS-602
31/AS-501 &
3/AS-602
41/AS-502 &
4,5&13/AS-602
42/AS-502 &
5&6/AS-602A
50/AS-502
60/AS-502
61/AS-502
62/AS-502
70/AS-502
72/AS-502
81/AS-502
90/AS-502
91/AS-502 &
15/AS-602
100/AS-502 &
4&7/AS-603
101/AS-502 &
11/AS-603
103/AS-502 &
3,4&7/AS-603
110/AS-502 &
10/AS-603
111/AS-502 &
3-5/AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/AS-501 &
3A/AS-602
51 REPLACE LOUVER WITH ALUMINUM
70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
REMOVE STAINLESS STEEL WIREWAY AND REPLACE WITH
NEW AFTER STONE SEALANT INSTALLED
92 92/AS-502
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
GENERAL WINDOW NOTES:
TYPE A HEAD - DEMO5
TYPE A JAMB - DEMO6
TYPE A SILL - DEMO7
TYPE A HEAD - NEW8
TYPE A JAMB - NEW9
TYPE A SILL - NEW10
ENLARGED EXISTING WINDOW ELEVATION3
ENLARGED NEW WINDOW ELEVATION4
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
B-WING 11TH FLR CHAPEL AREA1
KEYED NOTES:
NOTE:
NOTES:
ROOM FINISH SCHEDULE
FINISH SCHEDULE
SUSPENDED CEILING DETAIL3
EXPOSED GRID ACOUSTICAL TILE CEILING DETAIL4
CHAPEL AREA RCP2
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
REPLACE CRACKED OR SPALLED MASONRY1
STEP CRACKS OR UNBONDED & MISSING MORTAR2
ANCHORS/FASTENERS & FILL VOID3
REPOINT OPEN MASONRY JOINTS, PARAPET WALL & BRICK VENEER5
INSUFFICIENT STONE REPAIR15REPLACE STONE UNIT & BRICK11 PATCH CRACKED STONE UNIT13
REMOVE & REBUILD
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
GENERAL MORTAR NOTES:
REPAIR SPALLED STONE OR
PROVIDE NEW SCUPPERS4
EXTERIOR VIEW CORRESPONDING SIDE
REPAIR PROCEDURE:
PATCH STONE UNIT10
REPAIR PROCEDURE: REPAIR PROCEDURE:
REPLACE OR ADD NEW SEALANT30
REPAIR PROCEDURE:
REPAIR PROCEDURE:
BACKER ROD & SEALANT32
REMOVE & REPLACE
MORTAR & SEALANT31
REMOVE & REPLACE
REMOVE ABANDONED
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
FIRE ESCAPES,BALCONIES, RAILINGS, ETC.)50
CLEAN ALGAE & DIRT BUILDUP60
STAINING ON SURFACE61
CONCRETE IN LIGHT WELLS70 DETERIORATION72
EXPOSED METAL ELEMENTS (COLUMNS,
CLEAN & REPAINT CORROSION AT
SEAL CRACKS IN EXPOSED DUE TO REINFORCEMENT
REPLACE WINDOW SEALANT, MISSING OR INSUFFICIENT81 SEAL AROUND ANCHORS90
REMOVE EXPOSED PLYWOOD AROUND A/C UNIT91
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
SECTION VIEW
PLAN VIEW
CONCRETE REPAIR NOTES:
REPAIR SPALLED CONCRETE
GENERAL FACADE CLEANING62
REPAIR PROCEDURE:
CLEAN CORROSION
AND PLATE STEEL FILLER STRIP42
DAMAGED/ CORRODED LINTEL
REPAIR PROCEDURE:
REPAIR PITCH POCKET101 AREAS ON ROOF103
REPAIR PONDING
OF CORROSION & DETERIORATION110
IS DAMAGED / BROKEN OR MISSING, PROVIDE NEW111
REPAIR ROOF DRAIN AIR TERMINAL / CABLING / GROUNDING
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE: REPAIR PROCEDURE:
ROOF & PONDING REPAIR:
¾”
ROOF REPAIR AREA100
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
RESET DISPLACED LINTEL41
REPAIR PROCEDURE:
REMOVE AND REPLACE STAINLESS STEEL COVER92
REPAIR PROCEDURE:
SCAFFOLD PLANKS:
ERECTION, ALTERATION AND DISMANTLING:
SUPERVISION:
CERTIFICATES OF COMPETENCY:
SCAFFOLDING REGISTER AND INSPECTION OF SCAFFOLDS:
PROTECTION AND MAINTENANCE:
DUTIES OF PRINCIPALS, CONTRACTORS, SCAFFOLDING
ERECTORS AND USERS OF SCAFFOLDS:
SCAFFOLDING OVER VERANDAHS, GANTRIES OR ROOFS:
LIFTING APPLIANCES MOUNTED ON SCAFFOLDING:
SUSPENDED SCAFFOLDS:
TYPES OF SUSPENDED SCAFFOLDS:
MECHANICAL OPERATION:
ANCHORAGES:
BRACKETS AND PARAPET HOOKS:
WORKING PLATFORMS, GUARDRAILS, MIDRAILS AND TOEBOARDS:
SAFETY HARNESSES AND LIFELINES:
ANTI-TILT SWITCH DEVICES:
ACCESS, WARNING NOTICES AND PROTECTION OF THE PUBLIC:
ENGINEER’S CERTIFICATE:
SCAFFOLD REGISTER:
INSPECTION RECORD:
COUNTERWEIGHTING OF OUTRIGGERS:
FOUNDATIONS:
SUSPENDED SCAFFOLDS:
SIDEWALK SHEDS:
REQUIRED TRAINING:
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
WINDOW OPENING INFILL15
MASONRY REPAIR DETAIL1
CRACKED OR SPALLED
SEALANT3
WARD WING AREA
MORTAR &
SEALANT3A
BACKER ROD
REPLACE REPLACE
ROTATED STONE REPAIR5
EXPANSION JOINT AT CORNER4
REPLACE STONE UNIT DETAIL7
STONE DIMENSIONS DETAIL 14
BRICK JOINT REPOINTING DETAIL 2
BRICK SUPPORT 13
DETAIL AT STONE/
SECTION
VIEW
PLAN
VIEW
SECTION AT PARAPET WALL9
DETAIL AT BASE OF PARAPET WALL 9A
SECTION AT PARAPET WALL8A
PATCH STONE UNIT DETAIL6
DUTCHMAN REPAIR NOTES:
DUTCHMAN REPAIR DETAIL16
STONE AT SUPPORT SPLICE 7A
DETAIL AT CRACKED
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
FIRE RATED MASONRY PARTITION10
CONDUIT PENETRATION IN
PENETRATION DETAIL11
EXTERIOR WALL TYPICAL CONCRETE WALL
PENETRATION DETAIL12TYPICAL SECTION AT SCUPPER8B TYPICAL SCUPPER ROOF VIEW8C
SECTION AT WARD PARAPET WALL2
SECTION AT STAIRWELL SIDE WALL3 SECTION AT STAIRWELL END WALL4
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
NOTE:
TYPICAL SECTION AT WINDOW LINTEL5
NOTES:
TYPICAL SECTION AT LOUVER LINTEL6
KEY PLAN
1 STAINLESS STEEL METAL ENCLOSURE DETAIL
A
A
EPDM MEMBRANE SPLICES1
4'
COVERBOARD ATTACHMENT DETAIL2
4" BEAD SPACING ADHESIVE INSULATION/
ALPHAGUARD BIO BASE COAT
W/ REINFORCEMENT
ALPHAGUARD BIO TOP COAT
(3) THREE PLIES TREMCO ROOF MEMBRANE
SET IN COLD ADHESIVE MENDED WITH
EXISTING ROOF SURFACE AND TERMINATED AT CLEAT
ON PARAPET WALL. REFER TO ROOF PLANS.
TERMINATION BAR
TWO PIECE COUNTERFLASHING
BASE FLASHING - TRA ELASTOMERIC MEMBRANE
PROVIDE & INSTALL NEW POLYISO
INSULATION, THICKNESS AND
SLOPE TOP MATCH EXISTING
EXISTING CONCRETE DECK
TREMSEAL D
REMOVE ANY RUST OR LOOSE DEBRIS
AND PRIME WITH M-PRIME BEFORE
APPLYING ALPHAGUARD BIO
ALPHAGUARD BIO W/
REINFORCEMENT
ALPHAGUARD BIO BASE
W/ REINFORCEMENT
EXISTING TREMCO
BUILT-UP ROOF
MEMBRANE
EXISTING INSULATION
EXISTING CONCRETE DECK
TWO PIECE COUNTERFLASHING
Min. 8"
REMOVE ANY RUST
OR LOOSE DEBRIS
AND PRIME WITH
M-PRIME BEFORE
APPLYING
ALPHAGUARD BIO
EXISTING RIGID INSULATION
ALPHAGUARD BIO W/
REINFORCEMENT
4"
ALPHAGUARD BIO BASE
W/ REINFORCEMENT
ALPHAGUARD BIO TOP COAT
EXISTING TREMCO
BUILT-UP ROOF
MEMBRANE
EXISTING CONCRETE DECK
ALPHAGUARD BIO BASE
W/ REINFORCEMENT
ALPHAGUARD BIO TOP COAT
EXISTING TREMCO BUILT-UP
ROOF MEMBRANE
REMOVE EXISTING CLAMPING
RING AND ROOF DRAIN DOME
& REPLACED WITH NEW . ALL
DOMES SHALL BE METAL &
PAINTED BLACK.
EXISTING 2.5" +/-
RIGID INSULATION
EXISTING 4" +/-
CONCRETE DECK
REPLACE BOLTS WITH S.S.
TYPE, (TYP.) WATER CUT-OFF MASTIC
MEMBRANE SPLICE
COMPATIBLE WITH
EXISTING ROOFING
TREMSEAL PITCH
POCKET SEALER, OR
EQUIVALENT.
COMPLETELY FILL
POCKET TO PREVENT
PONDING OF WATER.
METAL PITCH PAN
MINIMUM 4'' HEIGHT w/
METAL HOOD
EXISTING
CONCRETE DECK
EXISTING INSULATION
EXISTING BUILT-UP
ROOF MEMBRANE
NEW PITCH POCKET
ENCLOSURE
ENGINEERING LLPFE PROJECT NO:
17-103/23-030
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
RECONSTRUCTION SECTION3
CARLISLE ROOFING
EQUIPMENT PLATFORM DETAIL8
TREMCO
VENT STACK DETAIL9
TREMCO
ROOF DRAIN DETAIL10
TREMCO
ROOF REPAIR DETAIL7
TREMCO PARAPET WALL/
PITCH POCKET DETAIL11
FIELD TIE-IN DETAIL4
GARLAND ROOFING
ROOFING FIELD TIE-IN DETAIL5
GARLAND WALL PANEL REMOVAL & SCUPPER OVERFLOW DETAIL6
GARLAND ROOFING SCUPPER OVERFLOW DETAIL6A
TREMCO ROOFING
GENERAL NOTES:
GARLAND ROOF & PONDING REPAIR:
¾” ”
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
TERMINAL DETAIL3
ADHESIVE AIR
COOPER B-LINE COOPER B-LINE
COOPER B-LINE COOPER B-LINE
DURABLOK BASE DETAILS1 PIPING SUPPORT ON ROOF2
CONSTRUCTION SIGN6 SAFETY SIGN7
SPLICE
TERMINAL DETAIL4
TYPICAL RE-INSTALLATION DETAIL5
MINIMUM CLASS 1 MATERIAL REQUIREMENTS
LEGEND & SCHEDULE OF
EQUIPMENT TYPICAL OF
MANUFACTURER "HARGER"
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com 70 South Franklin Street, Wilkes-Barre, PA 18701 570 | 824-6340 info@edpons.comedpons.com
100% CONSTRUCTION DOCUMENTS
Adelaide
ENVIRONMENTAL HEALTH
1511 Route 22 - Suite C-24 Brewster, New York 10509 p: 845.278.7710 f: 845.278.7750 adelaidellc.com
Environmental Consultants
GENERAL NOTES (DETAILS 1&3):
TEMPORARY LOUVER SNORKEL/ EXTENSION DETAILS - TYPICAL1
TYPICAL AC UNIT DETAIL2
GENERAL NOTES:
FRONT VIEWS SIDE VIEW
TEMPORARY LOUVER SNORKEL/ EXTENSION @ ROOF LEVEL (TYPICAL)3
GENERAL EQUIPMENT PROTECTION NOTES:
AIR INTAKE LOUVER PROTECTION FOR USE WITH MAST SCAFFOLDING SYSTEM::
| Sheets and Views |
| GI-001-_TS |
| GI-002-1-GI-002 |
| AS-001-1-AS-001 |
| AS-101 THRU 1-AS-103 (A WING FACADE)-AS-101 |
| AS-101 THRU 1-AS-103 (A WING FACADE)-AS-102 |
| AS-101 THRU 1-AS-103 (A WING FACADE)-AS-103 |
| AS-104 (A WING ROOF)-AS-104 |
| AS-201 (B WING FACADE)-AS-201 |
| AS-301 (B WING 11TH FLR CHAPEL)-AS-301 |
| AS-501 DEFICIENCY EXAMPLES-AS-501 |
| AS-502 DEFICIENCY EXAMPLES-AS-502 |
| AS-601 SCAFFOLDING DETAILS-AS-601 |
| AS-602 & AS-602A DETAILS-AS-602 |
| AS-602 & AS-602A DETAILS-AS-602A |
| AS-603 ROOF DETAILS-AS-603 |
| AS-604 ROOF DETAILS-AS-604 |
| MH-101 (MECHANICAL SHEETS)-MH-101 |
| HA-101 100% SEALED 082424-2.pdf |
| Sheets and Views |
| AS-301 |
| 23-030 - VA Stratton Phase 100P Structural 20241025 SS.pdf |
| Sheets and Views |
| 1-AS-301 |