This document is an Amendment to a Previous Combined Solicitation for electrical distribution system maintenance services for the Department of Veterans Affairs. The solicitation (Number 36C24225Q0696) is set aside for small businesses under NAICS code 811310 and seeks a firm fixed-price service contract for electrical distribution maintenance at Buffalo and Batavia VA Medical Centers. The contract consists of one base year with two option years, covering maintenance activities at both medical center locations.

The amendment addresses nine vendor questions, clarifying evaluation procedures, contract details, and technical specifications. Key clarifications include: all evaluation factors have equal importance, the solicitation uses Simplified Acquisition Procedures, secondary injection testing will be performed, and some previously referenced equipment (like protective relays in Buildings 6 and 20) should be disregarded. Vendors are required to submit a capability statement, pricing worksheet, staffing plan, technician documentation, performance plan, and potential subcontracting details. The response deadline is July 18, 2025, at 12:00 PM Eastern Time, with award to be made based on a comparative evaluation of price, technical capability, past performance, and veterans involvement.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

*= Required Field Amendment to a Previous Combined Solicitation

SUBJECT* FY25 Service (Base + 2) - WNY Electrical Distribution Maintenance - 528/528A4

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE* 14810

SOLICITATION NUMBER* 36C24225Q0696

RESPONSE DATE/TIME/ZONE 07-18-2025 12:00 EASTERN TIME, NEW YORK, USA

ARCHIVE 30 DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS N

SET-ASIDE SBA

PRODUCT SERVICE CODE* J061

NAICS CODE* 811310

CONTRACTING OFFICE ADDRESS Department of Veterans Affairs

RPO East, NCO 2 Contracting Office 76 Veterans Avenue Bath NY 14810

POINT OF CONTACT*

Contract Specialist Nathan Northrup nathan.northrup@va.gov

PLACE OF PERFORMANCE

ADDRESS Buffalo VA Medical Center and Batavia VA Medical Center 3495 Bailey Avenue 222 Richmond Avenue Buffalo/Batavia NY

POSTAL CODE 14215

COUNTRY USA

ADDITIONAL INFORMATION

AGENCY’S URL https://www.va.gov URL DESCRIPTION Department of Veterans Affairs Website AGENCY CONTACT’S EMAIL ADDRESS nathan.northrup@va.gov EMAIL DESCRIPTION Contract Specialist Email

DESCRIPTION

The purpose of this solicitation amendment is to answer vendor questions. Please see questions in black and VA’s answers in red below:

1. “How to score for each evaluation of section 4 of the solicitation?”

a. There is no hierarchy of value for each evaluation factor, they all have equal importance and shall be evaluated using the comparative evaluation procedures of Simplified Acquisition Procedures (SAP).

2. “The form 1449 is not included in the solicitation. Does form 1449 apply to this solicitation?”

a. This solicitation is issued as a combined synopsis and solicitation document which does not require SF 1449. The resulting contract, however, will be awarded using SF 1449 document.

3. “What is set aside for this BID?”

a. This solicitation is set-aside for small business vendors classified under the

NAICS code of 811310.

4. “Could you please confirm the solicitation to perform Maintenance, Testing, or Inspection of Buffalo and Batavia (the price sheet is not clear)?”

a. The line-items do reference both inspections and maintenance, this was unintentional and should both be labeled “annual maintenance”, though the SOW does go into further detail on what exactly is being procured here.

5. “Is it required the Primary injection for the LV circuit Breaker?”

a. There are no primary injection testing taking place on this contract, only secondary injection.

6. “How many Protective relays are in every lot (Buffalo: Building: 6, 20)?”

a. Disregard the protective relays listed under Bldgs. 6 & 20, they do not exist.

7. “Could you provide the SLD or test report of both sites, Buffalo and Batavia?”

a. Previous test reports will be provided post-award.

8. Is the “One (1) 330 kVA dry-type transformer” referenced in SOW section B.3.6.C.b.i.2.

still in use?

a. This unit was removed from service during the previous chiller project, disregard.

9. Is the “480-volt switchgear” referenced in SOW section B.3.6.F.a.iii. included? We could not find them on the site-visit.

a. After review, this equipment was found to be located in Building 12A.