528A7-24-0112 Facility Alarm Upgrade SOW Rev02.pdf
PDF 138 KB Posted
- Attached to
- Z1DA--36C242-25-AP-1993 | 528-25-2-7192-0009 528A7-24-111 D-Wing GD-DP Electrical Upgrade (VA-25-00055192)
- Solicitation number
- 36C24225B0030
About this file
This Statement of Work (SOW) details a fire alarm system upgrade project for the Syracuse Veterans Administration Medical Center. The project involves replacing the obsolete Edwards EST-3 Fire Alarm system with a new Edwards EST-4 Fire Alarm System across multiple buildings, including the main building, EMS-FMS, training, garage, and Spinal Cord Injury facility. The scope requires an electrical contractor to provide labor and materials, with tasks including reviewing project documents, submitting material specifications, installing fiber and conduit for a fiber ring connecting control panels, and potentially working 20 days of off-hours or weekends to complete installation and commissioning.
Key technical requirements include following NFPA 70, NFPA 72, and NEC codes, with specific deliverables such as fiber cable testing reports, source code files, fiber routing tables, and as-built prints. Personnel qualifications are stringent, mandating union journeymen electricians with at least 3-5 years of experience, certifications in electrical safety and fiber installation, and authorization as an Edwards Fire and Life Safety partner. The project has a 240-day performance period, with work primarily conducted during the medical center's administrative hours (7:00am to 4:00pm EST, Monday through Friday), excluding federal holidays.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 528A7-24-0111 SOW EEQ-GD-DP.pdf | ||
| 36C24225B0030 0002.pdf | ||
| 36C24225B0030 0001.docx | DOCX document | |
| 36C24225B0030_1.docx | DOCX document | |
| P07 Wage Determination NY20250026.pdf | ||
| FAR 52.225-2 Buy American Certification.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date: 5-7-2025
Statement Of Work Project: 528A7-24-112 Facility Fire Alarm Upgrade
B.4 SCOPE
The Integrator shall provide labor and materials to install and commission a new Edwards EST-4 Fire Alarm System at the Syracuse Veterans Administration Medical Center, 800 Irving Ave. Syracuse, New York, 13210.
B.4.1. REQUIREMENTS
The Syracuse VA Medical Center has a need to replace the obsolete Edwards EST-3 Fire Alarm system. The integrator shall provide labor and materials to replace the Edwards Fire Alarm System.
Electrical Work will Involve the Following Tasks, but not limited to.
1. Electrical Contractor will review project and attached documents.
2. Contractor will provide submittals for materials to be used on project. Basis of design was using Edwards
EST-4 System products. Other products may not work in this facility due to utilizing existing control panels and infrastructure with addressed field modules.
3. Fiber and some conduit will be needed for installation of fiber ring to all Control panels and remote annunciators.
4. There will be possible need to do about 20 days of off hours or Weekends to complete installation and or commissioning.
5. Buildings included in scope are building 1 (Main), 2 (EMS-FMS), 16 (training), 19 (garage), Spinal Cord Injury (SCI).
B.4.2. CONSTRUCTION
(a) Contractor to provide drawings to include plans, elevations, and details to accomplish the work
(b) Specifications to be followed are Latest versions of NFPA 70, NFPA 72 and, NEC codes.
Specification to follow:
01 00 00 Division 1 General Requirements.
27 10 00 Structured Cabling.
27 11 16 Communications Cabinets, Racks, Frames, and Enclosures.
27 11 19 Communications Termination Blocks and Patch Panels.
28 31 00 Fire Detection and Alarm
B.4.3. DELIVERABLES
(a) Fiber Cable testing reporting.
(b) Installed Fiber termination box in control panels.
(c) Source code files for programmed system as a backup.
(d) Fiber routing table for fiber ring with all panels marked with a designating number.
(e) As Built updated Prints showing controller nodes or IP, MAC addressing.
(f) Updated controllers, and any additional hardware to bring existing system up to code standards.
B.4.4. COMPETENCY OF PERSONAL
(a) Qualified, Based on electrical safety training, with at least 3 years of experience in the Electrical field as a Union Journeymen Electrician.
(b) Qualified, Certificate for Fiber installation, termination and testing, with at least 5 years of experience as a Union Journeymen Electrician.
(c) Authorized Partner with Edwards Fire and life safety. Able to purchase, install, and program EST-4 Fire and alarm control systems. Be able to follow the NFPA 72 national Fire Alarm code.
Date: 5-7-2025
(d) Qualifications of Key Personnel – Primary vendor employees should be knowledgeable of standards associated with the scope of work. Due to the location and specialized type of installation and commissioning work. Applicants will be technically assessed on this critical criterion and will be declined if not met.
(e) Certifications in running Fiber, Terminating, and testing as mentioned above.
(f) The CONTRACTING OFFICER (CO) may authenticate the training requirements, request training certificates or credentials from the Contractor at any time for any personnel who are servicing or installing any VAMC equipment. The CO and/or Contracting Officer Representative (COR) specifically reserves the right to reject any of the Contractor's personnel and refuse them permission to work on the VAMC equipment.
B.4.5. HOURS OF OPERATIONS
Work required in the performance of this contract shall be performed during the Medical Center’s regular administrative working hours, 7:00am to 4:00pm est., Monday through Friday -
Excluding Federal Holidays observed by the VAMC:
New Year's Day
Martin Luther King, Jr. Day
Washington's Birthday
Memorial Day
Juneteenth
Independence Day
Labor Day
Columbus Day
Veterans Day
Thanksgiving Day
Christmas Day
*Any day the President declares a Federal Holiday
There will be needed off hours required for installations, Tie-in, and commissioning that will be coordinated with COR.
Period of Performance: 240 days