This document includes a technical specification for a York Model YZ-MA033AN030P033NA water-cooled centrifugal chiller and details of a federal contract opportunity to install the chiller at the Rome VA CBOC.
The chiller specification provides detailed performance and technical requirements including rated and part load capacities of 265 tons, efficiencies ranging from 0.5373 to 0.3161 kW/ton, sound levels of 73 dBA, electrical and dimensional data, and specifications for evaporator and condenser components. The contract opportunity is issued by the Department of Veterans Affairs under solicitation number 36C24222B0076 to completely prepare the site and furnish and install the chiller. The scope of work involves demolition, site preparation, and installation of the chiller and relocation of an existing chiller as required by the drawings and specifications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24222B0076 0003.docx | DOCX document | |
| split shipped chiller dimensions.pdf | ||
| 36C24222B0076 0002.docx | DOCX document | |
| 36C24222B0076 0001.docx | DOCX document | |
| Wage Detrmination NY20220013 8-5-22.pdf | ||
| Combined Specifications 528A723102.pdf | ||
| 528A7-23-102_FULLSET-FINAL_06-28-2022.pdf | ||
| 36C24222B0076_1.docx | DOCX document | |
| CONTINUATION OF SF 1442 BLOCK 17 ROME CHILLER.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Unit
Number of Compressors 1
Compressor Type Centrifugal
Number of Compressor Circuits 1
Refrigerant R-1233zd(E)
Compressor AN030NA
Motor MA033AA
Variable Orifice 3
Cooling Performance
Specified Net Capacity [ton.R] 265.0
Rated Net Capacity [ton.R] 265.0
Heat Rejection Capacity [MBtu/h] 3.680
Full Load Efficiency [kW/Ton.R] 0.5373
Part Load Efficiency (NPLV.IP) [kW/Ton.R] 0.3274
Part Load Efficiency (IPLV.IP) [kW/Ton.R] 0.3254
A-Weighted Sound Pressure Level [dBA] 73
Electrical Data
Power Supply [V/ph/Hz] 460/3/60.0
Total Input Power [kW] 142.4
Min. Circuit Ampacity [amps] 251
Max. Circuit Breaker Amps (each system) [amps] 450
Full Load Amps (FLA, each system) [amps] 201
Weight & Dimensional Data
Shipping Weight [lb] 16940
Operating Weight [lb] 19091
Refrigerant Charge [lb] 771
Length [in] 173.4
Width [in] 78.4
Height [in] 94.2
Image shown for illustrative purposes only. Selected product may vary.
Performance Impacting Options
Starter Type VSD w/o Filter
Starter Model P033NA
Isolation Valves Yes
OptiSound Control Yes
Evaporator Tubes
STD 641, 0.75" OD, Copper, 0.025" thick, Enhanced
Condenser Tubes
STD 491, 0.75" OD, Copper, 0.025" thick, Enhanced
Condenser Subcooler Tubes
STD 491, 0.75" OD, Copper, 0.025" thick, Enhanced
Heat Exchanger Performance
Evaporator Condenser
Evaporator FB2912-A3D-641-2* Condenser SA2512-A3O-491-2*
Entering Fluid Temperature [°F] * 60.00 Entering Fluid Temperature [°F] * 85.00
Leaving Fluid Temperature [°F] * 44.00 Leaving Fluid Temperature [°F] 94.29
Flow Rate [gpm] 396.5 Flow Rate [gpm] * 796.5
Fouling Factor [hr-ft²-°F/Btu] * 0.000100 Fouling Factor [hr-ft²-°F/Btu] * 0.000250
Fluid Type * Water Fluid Type * Water
Passes * 2 Passes * 2
Pressure Drop [ft H2O] 9.69 Pressure Drop [ft H2O] 11.1
Fluid Volume [gal] 109 Fluid Volume [gal] 124
Minimum Flow Rate [gpm] 259.8 Minimum Flow Rate [gpm] 499.2
Maximum Flow Rate [gpm] 1039 Maximum Flow Rate [gpm] 1815
Heat Exchanger Type Falling Film Heat Exchanger Type Flooded
* Designates user specified input
YZ Water-Cooled Centrifugal Chiller Performance Specification
Project Name: VA Rome Chiller Tag: CH-1 Qty: 1 Model: YZ-MA033AN030P033NA
Version: 05/24/2022 at 13:45 Version: 21.05 (LTC Version:1.0.8154) Project Name: VA Rome Chiller
Unit Name: CH265 YORKworks 21.05 Page 1 of 3
Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Part Load Performance (Full Load with IPLV/NPLV per Std. Condition Set)
Percent Load Net Capacity [ton.R] Percent Power Input Power
[kW] Evap EFT [°F] Evap LFT [°F] Cond EFT [°F] Cond LFT [°F] Efficiency [kW/Ton.R]
100 265.0 100 142.4 60.00 44.00 85.00 94.29 0.5373
75 198.8 56 79.34 55.99 44.00 75.00 81.72 0.3992
50 132.5 26 37.18 51.99 44.00 65.00 69.34 0.2806
25 66.25 15 20.94 47.99 44.00 65.00 67.20 0.3161
Part Load Performance(Minimum CEFT)
CEFT [°F]
Percent Load
100 90 80 70 60 50 40 30 20 10
85.00 0.5373 0.5203 0.5155 0.5220 0.5334 0.5575 0.5847 0.6467 0.7736 1.378
80.00 0.4706 0.4554 0.4525 0.4571 0.4700 0.4845 0.5090 0.5559 0.6738 1.005
75.00 0.4192 0.4085 0.4032 0.3975 0.3996 0.4052 0.4215 0.4584 0.5560 0.8392
70.00 0.3725 0.3592 0.3458 0.3363 0.3342 0.3368 0.3463 0.3708 0.4513 0.6777
65.00 0.3236 0.3068 0.2927 0.2836 0.2801 0.2806 0.2838 0.2981 0.3487 0.5850
60.00 0.2807 0.2611 0.2469 0.2353 0.2291 0.2249 0.2260 0.2347 0.2575 0.4381
55.00 0.2411 0.2204 0.2052 0.1933 0.1845 0.1805 0.1781 0.1790 0.1967 0.2692
50.00 0.2011 0.1832 0.1666 0.1541 0.1434 0.1357 0.1282 0.1268 0.1377 0.1958
45.00 0.1728 0.1580 0.1442 0.1280 0.1111 0.09395 0.08809 0.1018 0.1240 0.1988
44.00 0.1709 0.1564 0.1424 0.1247 0.1067 0.09116 0.09318 0.1081 0.1326 0.2175
43.00 0.1657 0.1515 0.1365 0.1169 0.09897 0.09367 0.09436 0.1089 0.1335 0.2187
42.00 0.1602 0.1457 0.1305 0.1090 0.1016 0.09628 0.09567 0.1098 0.1344 0.2203
41.00 0.1543 0.1391 0.1228 0.1107 0.1043 0.09901 0.09739 0.1108 0.1359 0.2219
40.00 0.1475 0.1314 0.1222 0.1143 0.1071 0.1019 0.09977 0.1118 0.1374 0.2236
* Values are in kW/Ton.R
Rated point is 80% or higher efficiency compared to design operation point.
Rated point is 70% or higher efficiency compared to design operation point.
Rated point is 60% or higher efficiency compared to design operation point.
Sound Pressure Levels (Standard)
Percent Load Octave Band Center Frequency [Hz] A-Weighted
(dBA)63 125 250 500 1000 2000 4000 8000
100 61.5 61.5 67.0 66.5 65.5 67.0 66.0 60.0 73
75 62.5 61.0 63.0 62.0 62.5 63.0 62.5 61.5 70
50 63.5 64.0 58.0 57.5 59.0 59.0 62.5 63.0 68
25 63.5 69.0 59.5 57.5 58.0 58.5 63.5 64.0 69
The octave and A-weighted sound pressure levels are the levels expected to be obtained if measurements are performed in accordance with AHRI Standard 575-08, Method of Measuring Machinery Sound Within Equipment Rooms. Tolerances: The sound levels of identical unit selections can vary due to manufacturing tolerances and test repeatability. Variations of ±3 dBA on the A-weighted levels and ±5 dB on the octave band levels are possible.
Unit Configuration Details
YZ_MA033AN030P033NA_FB2912A3D6412MA1FLLBNSA2512A3O4912MA1FLLBXAAXNA_AAXACN66X114NNNNNXASTU0101YNNXX01SSN1OYTXNS ADYNENIYSXUSGNN02650.50.3CW00W00XNNLLAEANNNNNXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX000
YZ Water-Cooled Centrifugal Chiller Performance Specification
Project Name: VA Rome Chiller Tag: CH-1 Qty: 1 Model: YZ-MA033AN030P033NA
Unit Name: CH265 YORKworks 21.05 Page 2 of 3
Evaporator Condenser
FB2912-A3D-641-2* SA2512-A3O-491-2*
Design Working Pressure [psig] 150 150
Entering Water Nozzle Location L L
Leaving Water Nozzle Location L L
Water Box Weight [lb] 544 N/A
Cover Plate Weight [lb] 409 287
Return Head Weight [lb] N/A N/A
Water Weight [lb] 905 1030
Fluid Volume [gal] 109 124
Weight Breakdown Details
Operating Weight [lb] 19091 Refrigerant (R-1233zd(E)) Weight [lb] 770 Motor Weight [lb] 1956
Per Isolator [lb] 4773 Compressor Weight [lb] 1949 Shipping Weight [lb] 16940
Notes:
1. Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.
2. Compliant with ASHRAE 90.1-2004, ASHRAE 90.1-2007, ASHRAE 90.1-2010, ASHRAE 90.1-2013, ASHRAE 90.1-2013(2015) and ASHRAE 90.1- 2016.
3. Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4).
4. Materials and construction per mechanical specifications - Form 161.01-EG1.
5. Auxiliary components included in total kW - Chiller controls. FFBPN
6. IECC 2012 and IECC 2015/2018 Compliant
7. The product image shown is for illustrative purposes only and is not representative of selected options.
YZ Water-Cooled Centrifugal Chiller Performance Specification
Project Name: VA Rome Chiller Tag: CH-1 Qty: 1 Model: YZ-MA033AN030P033NA
Unit Name: CH265 YORKworks 21.05 Page 3 of 3