Z1DA--528A7-23-102 ADD CHILLER ROME VA CBOC
Solicitation number
36C24222B0076
Issued by

About this file

This document package includes construction drawings and specifications for a federal contract opportunity to install a new water-cooled chiller and relocate an existing chiller at a VA medical facility in Rome, New York. The scope of work involves demolishing existing structures, installing a new government-furnished chiller, and moving an existing chiller to new locations as shown on the plans. Mechanical drawings depict demolition plans, new equipment layouts, piping schematics and details. Electrical drawings show demolition requirements, new power plans and details. Specifications cover general project notes, abbreviations and symbols. The opportunity is issued by the Department of Veterans Affairs for the Veterans Health Administration network in that region.

View the file

Other files

File Type Posted
36C24222B0076 0003.docx DOCX document
split shipped chiller dimensions.pdf PDF
36C24222B0076 0002.docx DOCX document
york chilller selection.pdf PDF
36C24222B0076 0001.docx DOCX document
Wage Detrmination NY20220013 8-5-22.pdf PDF
Combined Specifications 528A723102.pdf PDF
36C24222B0076_1.docx DOCX document
CONTINUATION OF SF 1442 BLOCK 17 ROME CHILLER.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWINGS INDEX

SHEET NO. DRAWING TITLE

GENERAL

1. GI-001 COVER SHEET

MECHANICAL

2. MG-001 MECHANICAL ABBREVIATIONS, SYMBOLS & NOTES

3. MD-101 MECHANICAL DEMOLITION PLAN

4. M-101 MECHANICAL PLAN

5. MG-501 MECHANICAL DETAILS

6. MG-601 MECHANICAL SCHEDULES

7. MI-701 CONTROLS DIAGRAMS

8. MI-702 SEQUENCE OF OPERATIONS & CONTROL POINTS

ELECTRICAL

9. EG-001 ELECTRICAL ABBREVIATIONS, SYMBOLS & NOTES

10. ED-101 ELECTRICAL DEMOLITION

11. EP-101 ELECTRICAL POWER PLAN

12. EG-501 ELECTRICAL DETAILS

DEPARTMENT OF VETERANS AFFAIRS PROJECT NO. 528A7-23-102

VA ROME OUTPATIENT CLINIC

BUILDING 510

125 BROOKLEY ROAD

ROME, NEW YORK 13441

ADD CHILLER AT ROME CBOC

AREA OF WORK

GROUND FLOOR

MECHANICAL ROOM

KEY PLAN

SCALE: NONE

o n e e i g h t h i n c h o n e f o o t

B

A

C

D

E

F t h r e i c h e s e f o o t o a d o n e h a l f i n c h e e f o o t o c f o t t h r e e q u a r t e r s i n c e f o o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISION DATE

SYRACUSE

VA MEDICAL

CENTER

ENGINEERING

DEPARTMENT

VA ROME OUTPATIENT CLINIC, ROME, NY

06/28/2022

GENERAL PROJECT INFORMATION

100% SPRINKLERED

DWG.

U.S. Department of Veterans Affairs

B

A

C

D

E

F

528A7-23-102

ADD CHILLER AT ROME CBOC

S S

Y R

M

S M

S E n g i n e e r i n g P

R O

J E

C T

S A

C T

I V

E

P

R O

J E

C T

S

A

A d

C i l l e r a t

R o m e

C

B O

C D e s i g n

P h a s e

D r a w i n g s C

A D

M e c h a n i c a l

A

M

M

E C

H d w g

OF 12

GI-001

JDMA

COVER SHEET

N

VA ROME CBOC

GENERAL PIPING SYMBOLS

@ AT

℄ CENTERLINE

° DEGREES

Δ DELTA

ɸ ELECTRICAL PHASE

∅ ROUND / DIAMETER

A/E ARCHITECT / ENGINEER

AAV AUTOMATIC AIR VENT

AD ACCESS DOOR

AF AFTER FILTER

AFF ABOVE FINISHED FLOOR

AHU AIR-HANDLING UNIT

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATION, AIR CONDITIONING

ENGINEERS

AW AIR WASHER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BG BOTTOM GRILLE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CG CEILING GRILLE

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CO CLEAN OUT

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONDENSATE PUMP

CR CEILING REGISTER

CRAC COMPUTER ROOM AIR CONDITIONING

UNIT

CU CONDENSING UNIT

CW COLD WATER (POTABLE)

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN (TO

COOLING TOWER)

CWS CONDENSER WATER SUPPLY

(FROM COOLING TOWER)

D DAMPER - AUTOMATIC

D-1 OUTDOOR AIR DAMPER

D-2 RETURN AIR DAMPER

D-3 RELIEF AIR DAMPER

DB DECIBELS

Db DRY-BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DF DIFFUSER

DIA DIAMETER

DOM DOMESTIC

DP DEW POINT TEMPERATURE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DSS DUCTLESS SPLIT-SYSTEM (EVAPORATOR)

DX DIRECT EXPANSION

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EH EXHAUST HOOD

EJ EXPANSION JOINT

ENT ENTERING

ER EXHAUST REGISTER

(ER) EXISTING TO REMAIN

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EXIST EXISTING

(E) EXISTING

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

FM FLOW METER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FR FLOOR REGISTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLON(S)

GF/CI GOVERNMENT FURNISHED/CONTRACTOR

INSTALLED

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GRR GLYCOL-WATER RUN AROUND RETURN

GRS GLYCOL-WATER RUN AROUND SUPPLY

GS GALVANIZED STEEL

H HUMIDIFIER

H&CW HOT & COLD WATER

HC HEATING COIL

HD HEAD

HD HOOD

HOA HAND/OFF/AUTOMATIC

HP HORSEPOWER

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

Hz HERTZ

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

J (INTENTIONALLY LEFT BLANK)

KPA KILOPASCAL

KW KILOWATT

L/S LITERS PER SECOND

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LH LATENT HEAT

LPR LOW PRESSURE RETURN (STEAM

CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN

(CLEAN)

LPS LOW PRESSURE STEAM

LPSC LOW PRESSURE STEAM (CLEAN)

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

MA MIXED AIR

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MD MOTORIZED DAMPER

MIN MINIMUM

MM MILLIMETER

MOD MOTOR OPERATED DAMPER

MOV MOTOR OPERATED VALVE

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

(N) NEW

NA NOT APPLICABLE

NC NORMALLY CLOSED

NO NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

OA OUTSIDE AIR

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PG PRESSURE GAGE

PHC PREHEAT COIL

PPM PARTS PER MILLION

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH –

ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSV PRESSURE SAFETY VALVE

REL RELOCATE / RELOCATED

R/E RETURN OR EXHAUST

RA RETURN AIR

RAT RETURN AIR TEMPERATURE

RCP RADIANT CEILING PANEL

REA RELIEF AIR

RF RETURN FAN

RG RETURN AIR GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RTU ROOF TOP UNIT

RV RELIEF VALVE

SA SUPPLY AIR

SAD SOUND ATTENUATOR DEVICE

SAT SUPPLY AIR TEMPERATURE

SCFM STANDARD CUBIC FEET PER MINUTE

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SDPR SMOKE DAMPER

SDR SMOKE DAMPER (RETURN)

SDS SMOKE DAMPER (SUPPLY)

SEN SENSIBLE HEAT

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SR SUPPLY AIR REGISTER

SS STAINLESS STEEL

ST STEAM TRAP

SVS STEAM VENT SILENCER

T&PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TG TRANSFER GRILLE

TP TRAP

TR TOP REGISTER

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TYP TYPICAL

UC or U/C UNDER CUT

UL UNDERWRITERS LABORATORY

V VALVE

VAMC SYRACUSE VA MEDICAL CENTER

VAV VARIABLE AIR VOLUME

VB VACUUM BREAKER

VD VOLUME DAMPER (MANUAL OPPOSED

BLADE)

VFD VARIABLE FREQUENCY DRIVE

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE)

RETURN

W WATTS

WB WET-BULB (TEMPERATURE)

WC WATER COOLED

WCACU WATER-COOLED COMP RM A/C

WEF WALL EXHAUST FAN

WF WATER FILTER

WFCV WATER FLOW CONTROL VALVE

WFM WATER FLOW METER

WFMD WATER FLOW MEASURING DEVICE

WG WATER GAGE

WHA WATER HAMMER ARRESTOR

GENERAL NOTES AND CONDITIONS

1. THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE AVAILABLE

BUILDING DRAWINGS, ARCHITECTURAL BACKGROUNDS PROVIDED AND FIELD SURVEY

INFORMATION COMPILED BY THE VA ENGINEERING DESIGN TEAM FOR THE PURPOSE OF

ENGINEERING DESIGN. EXISTING CONDITIONS ARE SHOWN AS ACCURATELY AS

POSSIBLE. THERE IS THE POSSIBILITY THAT CONDITIONS SHOWN ARE NOT EXACTLY AS

EXISTING. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, LOCATIONS,

SIZES AND CONDITIONS AT THE SITE AND REPORT ANY DISCREPANCIES TO THE

ENGINEER PRIOR TO BEGINNING INSTALLATION OR FABRICATION WORK.

1.1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REVIEW THE PLANS AND

SPECIFICATIONS, AS WELL AS ALL RELATED PROJECT PLANS AND SPECIFICATIONS

FROM OTHER DISCIPLINES, TO BECOME FAMILIAR WITH THE FULL PROJECT SCOPE

AND COORDINATED RESPONSIBILITIES.

1.2. SHOULD IT APPEAR THAT THE WORK INTENDED TO BE DESCRIBED OR RELATED

WORK ARE NOT SUFFICIENTLY DETAILED OR EXPLAINED ON THE DRAWINGS, OR IN

THE SPECIFICATIONS, CONSULT THE COR FOR NECESSARY CLARIFICATIONS, AND

CONFORM TO THOSE CLARIFICATIONS INSOFAR AS THEY ARE CONSISTENT WITH

THE ORIGINAL DRAWINGS AND SPECIFICATIONS. IN NO CASE SHALL WORK

PROCEED IN UNCERTAINTY.

1.3. EQUIPMENT ARRANGEMENTS ARE DESIGNED TO SHOW PREFERRED

CONFIGURATIONS TO SUIT KNOWN CONDITIONS. ACTUAL INSTALLATION BY

CONTRACTOR MAY BE ALTERED AS REQUIRED TO SUIT FIELD CONDITIONS

ENCOUNTERED DURING CONSTRUCTION WITHOUT COMPROMISING THE INTENT OF

THE ORIGINAL DESIGN. COORDINATE ANY MODIFICATIONS WITH THE COR PRIOR

TO STARTING WORK IN AREAS AFFECTED.

1.4. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS

AT SITE PRIOR TO STARTING WORK.

1.5. DO NOT SCALE DRAWINGS.

2. THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND

REGULATIONS, INCLUDING THOSE WHICH MAY BE ISSUED BY THE OWNER, ARE BEING

OBSERVED, PARTICULARLY WORKPLACE SAFETY AND THE CONDUCT OF ALL THOSE

EMPLOYED DIRECTLY AND INDIRECTLY ON THE PREMISES, AND THE OWNER'S

EMPLOYEES WHO MAY BE IMPACTED OR AFFECTED BY CONSTRUCTION ACTIVITIES. THE

CONTRACTOR WILL INSTALL SIGNAGE, BARRIERS, AND OTHER MEANS TO PROVIDE

WARNING AND PERSONNEL SAFETY. PLACEMENT OF THESE ITEMS WILL BE

COORDINATED WITH THE OWNER AND HIS ONGOING OPERATIONS AND WILL PROMPTLY

BE REVISED WHEN WORK IN A PARTICULAR AREA HAS BEEN COMPLETED.

2.1. DURING PERFORMANCE OF WORK, THE CONTRACTOR SHALL BE RESPONSIBLE

FOR PROVISION AND MAINTENANCE OF WARNING SIGNS, LIGHT SIGNAL DEVICES,

GUARD LIGHTS, BARRICADES, GUARD RAILS, FENCES AND OTHER DEVICES,

APPROPRIATELY LOCATED ON AND AROUND THE JOB SITE WHICH GIVE PROPER

AND UNDERSTANDABLE WARNING TO PERSONS WITH REGARD TO HAZARDOUS

CONDITIONS, EQUIPMENT AND OPERATIONS BEING PERFORMED IN CONJUNCTION

WITH THE WORK.

3. THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH OTHER TRADES FOR

ITEMS IN THEIR SCOPE OF WORK WHICH COULD REQUIRE ADDITIONAL

MECHANICAL/PLUMBING WORK, AND ITEMS THAT ARE NOT INDICATED ON THE

DRAWINGS.

4. THIS INSTALLATION WILL CONFORM TO ALL CODES AND THE REQUIREMENTS OF

FEDERAL, STATE, AND LOCAL REGULATORY AGENCIES HAVING JURISDICTION. IN

PARTICULAR, THE WORK WILL BE IN ACCORDANCE WITH THE CURRENT ADOPTED

EDITION OF THE NEW YORK STATE UNIFORM FIRE PROTECTION AND BUILDING CODE

AND ALL OF ITS APPLICABLE SUBCODES AND AMENDMENTS.

5. ALL WORK WILL BE LAWFULLY EXECUTED IN A NEAT AND WORKMANLIKE MANNER AND

WILL BE COMPLETED IN ACCORDANCE WITH THE GOVERNING CODES (ABOVE),

INDUSTRY STANDARDS, AND IN CONFORMANCE WITH THE MANUFACTURERS

RECOMMENDATIONS AND REQUIREMENTS.

6. WORK UNDER THIS CONTRACT SHALL CONSIST OF THE CONTRACTOR PROVIDING ALL

LABOR, MATERIALS, AND SERVICES, INCLUDING WORK NOT SPECIFICALLY SHOWN BUT

REASONABLY IMPLIED. THIS SHALL INCLUDE CUTTING, PATCHING AND RESTORATION OF

EXISTING SURFACES DAMAGED DURING THE CONSTRUCTION. CONTRACTOR SHALL

ALSO PROVIDE ALL EQUIPMENT SHOWN OR SPECIFIED OR AN APPROVED EQUIVALENT.

SUBSTITUTED EQUIPMENT OR MATERIALS SHALL NOT BE INSTALLED UNTIL GIVEN

WRITTEN APPROVAL BY THE OWNER.

7. CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS INCURRED FOR NONCOMPLIANCE

WITH THESE CONTRACT DOCUMENTS. CONTRACTOR WILL NOT BE ALLOWED CHANGE

ORDERS FOR PROBLEMS ARISING FROM NEGLECT OF PROVISIONS INCLUDED IN THESE

CONDITIONS.

8. MAINTAIN ORDERLY HOUSEKEEPING DURING CONSTRUCTION, AND UPON SUBSTANTIAL

COMPLETION PERFORM FINAL CLEANUP. REMOVE CONSTRUCTION RUBBISH,

SCAFFOLDING, EQUIPMENT, TEMPORARY PROTECTION, TEMPORARY FIELD

STRUCTURES, AND OTHER MATERIALS OR EQUIPMENT THAT WAS REQUIRED IN

CONNECTION WITH THE CONSTRUCTION, BUT NOT A PERMANENT PART THEREOF.

9. THOSE PERFORMING WORK AS A CONTRACTOR MUST EXAMINE SUBSTRATES AND

CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED AND NOTIFY THE

CONTRACTOR IN WRITING, OF CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY

COMPLETION OF THE WORK. COMMENCEMENT OF WORK BY A TRADE ON A SURFACE OR

CONSTRUCTION SHALL IMPLY ACCEPTANCE OF SUCH SURFACE OR CONSTRUCTION. DO

NOT PROCEED WITH INSTALLATION UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN

CORRECTED.

10. THE CONTRACTOR SHALL SECURE ALL PERMITS AND APPLICATIONS AND PAY ANY AND

ALL FEES AS REQUIRED. THE CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES AND

CERTIFICATES OF INSPECTION REQUIRED BY THE AUTHORITIES HAVING JURISDICTION.

DELIVER ALL PERMITS, CERTIFICATES AND APPROVALS TO THE OWNER AGENT PRIOR

TO FINAL ACCEPTANCE OF THE WORK. THE CONTRACTOR MUST FILE NECESSARY

DRAWINGS, PREPARE DOCUMENTS AND MAKE APPLICATIONS FOR EACH REQUIRED

PERMIT AND INSPECTION, PRIOR TO COMMENCING WORK TO AVOID DELAYS DURING

CONSTRUCTION.

11. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND MANUFACTURERS DATA SHEETS ON

ALL EQUIPMENT AND MATERIALS SPECIFIED ON DRAWINGS FOR APPROVAL BY OWNER.

THESE DRAWINGS OR SHEETS SHALL CONTAIN ALL NECESSARY DATA, I.E.,

MANUFACTURER, CATALOG NUMBER, SIZE, DIMENSIONS, CAPACITY, WIRING DETAILS

AND ALL OTHER ENGINEERING DATA AND DETAILS NECESSARY FOR COMPLETE CLARITY

AND INSTALLATION.

12. THE CONTRACTOR SHALL KEEP ONE SET OF THE LATEST ISSUE OF DRAWINGS WHICH

SHALL REFLECT THE ACTUAL INSTALLED CONDITIONS AND CONNECTIONS OF ALL

EQUIPMENT AND DEVICES. THE CONTRACTOR SHALL PROVIDE COPIES OF ALL

MAINTENANCE INFORMATION AND INSTRUCTIONS RECEIVED WITH EQUIPMENT AND

SYSTEMS. ALL "AS-BUILT" DRAWINGS AND MISCELLANEOUS INFORMATION SHALL BE

GIVEN TO THE OWNER AND ENGINEER AT COMPLETION OF WORK. THE CONTRACTOR

SHALL GUARANTEE ALL MATERIAL AND LABOR TO BE FREE FROM DEFECTS FOR A ONE

YEAR PERIOD FROM THE TIME OF OWNER ACCEPTANCE. ANY DEFECTS OCCURRING

DURING THIS PERIOD SHALL BE CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL

COST TO THE OWNER.

13. AS DIRECTED BY THE OWNER, ALL EXISTING EQUIPMENT AND MATERIAL IN USABLE

CONDITION THAT IS REMOVED SHALL REMAIN THE PROPERTY OF THE OWNER, OR

HANDLED AS INSTRUCTED BY THE OWNER, BE DISPOSED OF BY THE CONTRACTOR. ALL

MATERIALS DEEMED FOR REMOVAL SHALL BE RECYCLED WHENEVER POSSIBLE, IN

ACCORDANCE WITH THE REQUIREMENTS SET FORTH WITHIN SPECIFICATION SECTION 01

74 19 (CONSTRUCTION WASTE MANAGEMENT).

14. CONTRACTOR IS TO PROVIDE ALL REQUIRED SCAFFOLDING, LADDERS, RIGGING,

HOISTING AND ALL OTHER EQUIPMENT REQUIRED FOR THE INSTALLATION OF THEIR

WORK.

15. ESTABLISH PASSAGE CLEARANCES REQUIRED TO DELIVER, INSTALL AND ERECT ALL

REQUIRE EQUIPMENT. IF STRUCTURES, EQUIPMENT AND SYSTEMS MUST BE ALTERED

TO PROVIDE PASSAGE OF EQUIPMENT, THE CONTRACTOR SHALL RESTORE

STRUCTURES, EQUIPMENT AND SYSTEMS TO THEIR ORIGINAL CONDITION AT THE

CONTRACTOR'S EXPENSE; INCLUDING REMOVING AND REPLACEMENT OF ALL CEILING

AS REQUIRED TO COMPLETE THE WORK.

16. ALL INTERIOR AND EXTERIOR WALL, CEILING AND ROOF OPENINGS AND DUCT AND PIPE

THROUGH WALL PENETRATIONS, FRAMING, SLEEVES, WEATHERPROOFING AND FIRE

SEALING SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR, UNLESS NOTED

OTHERWISE.

17. INSULATE PER SPECIFICATION SECTION 23 07 11.

18. CONTRACTOR SHALL TEST ADJUST & BALANCE THE COMPLETED SYSTEM. ALL

BALANCING WORK SHALL BE DONE UNDER THE DIRECT SUPERVISION OF AN AABC OR

NEBB-QUALIFIED SUPERVISOR WHO SHALL CERTIFY THE RESULTS.

19. TEST, ADJUST AND BALANCE WORK WILL DEMONSTRATE THAT ALL SYSTEMS OPERATE

AS THEY WERE INTENDED TO. UPON COMPLETION OF THE WORK A WRITTEN TEST AND

BALANCE REPORT WILL BE SUBMITTED TO THE OWNER. FORMS AND PROCEDURES

UTILIZED FOR THIS WORK WILL BE AS PROPOSED BY THE AABC OR OTHER NATIONALLY

RECOGNIZED ORGANIZATION ACCEPTABLE TO THE OWNER.

20. ALL DUCTWORK, PIPING AND EQUIPMENT SHOWN ON NEW WORK PLANS AND DETAILS

SHALL BE CONSIDERED AS NEW UNLESS IDENTIFIED AS EXISTING TO REMAIN.

PIPING NOTES

1. ALL PIPING MATERIALS AND COMPONENTS INCLUDING FITTINGS, PIPE, FLANGES,

VALVES, ETC. SHALL BE DESIGNED, FABRICATED AND INSTALLED PER

APPROPRIATE SECTIONS OF THE LATEST ANSI AND ASTM CODES AND STANDARDS

AND THE MATERIAL SPECIFICATIONS FOUND IN THE PROJECT DOCUMENTS.

2. CONTRACTOR TO INSTALL HIGH POINT VENTS AT ALL SYSTEM HIGH POINTS AND

LOW POINT DRAINS AT SYSTEM LOW POINTS. VENTS AND DRAINS ARE REQUIRED

TO FACILITATE SYSTEM DRAINING AND VENTING DURING TESTING AND START-UP.

3. SURFACES TO BE SOLDERED SHALL BE CLEANED BRIGHT. THE JOINTS SHALL BE

PROPERLY FLUXED AND MADE WITH APPROVED SOLDER. SOLDER JOINTS FOR

POTABLE WATER SHALL BE MADE WITH A SOLDER CONTAINING NOT MORE THAN

0.2 PERCENT LEAD.

4. UNIONS SHALL BE INSTALLED AT ALL EQUIPMENT. THE USE OF DIELECTRIC

UNIONS MUST BE INSTALLED IN AREAS WHERE JOINING OF DISSIMILAR METALS (ie

CARBON STEEL TO COPPER OR BRONZE, ETC.). THIS IS TO FACILITATE PIPING

REMOVAL AND REASSEMBLY FOR FUTURE MAINTENANCE WORK AND/OR PREVENT

GALVANIC CORROSION.

5. CONTRACTOR SHALL PROPERLY BRACE, ANCHOR, AND SUPPORT ALL PIPING,

VALVES ETC. UNLESS SHOWN OTHERWISE, ALL PIPE HANGERS AND SUPPORTS

SHALL BE DESIGNED, MANUFACTURED AND INSTALLED PER MSS SP-58, MSS SP-69

AND MSS SP-89.

6. ALL ABOVEGROUND PIPING SHALL BE INSULATED AND JACKETED AS NOTED IN THE

SPECIFICATIONS.

7. ALL PIPES THAT PASS THROUGH EXTERIOR WALLS SHALL BE SLEEVED AND MADE

WEATHER TIGHT.

8. ALL PIPING AND VALVES MUST BE PROPERLY IDENTIFIED AND LABELED PER ANSI

13.1, ENTITLED "SCHEME FOR THE IDENTIFICATION OF PIPING SYSTEMS". ALL

VALVES MUST BE IDENTIFIED AND TAGGED WITH WEATHERPROOF TAGS.

9. ALL PIPES OR TUBING WHICH PASS THROUGH RATED AND NON-RATED WALLS,

FLOORS AND FOUNDATION WALLS, SHALL PASS THROUGH A SCHEDULE 40

CARBON STEEL PIPE SLEEVE. SLEEVES WHICH PASS THROUGH MASONRY SHALL

BE GALVANIZED COATED. ALL SLEEVES SHALL BE INSTALLED FLUSH ON BOTH

SIDES OF WALL PENETRATION.

NON-RATED WALL: THE SLEEVE SHALL BE SIZED TO ALLOW FREE PASSAGE OF

INSULATED AND NON-INSULATED PIPES AND TUBING.

RATED WALL: PIPES WHICH PASS THROUGH FIRE-RATED WALLS & FLOOR SHALL

USE THE APPROPRIATE CODE APPROVED, TESTED AND INSTALLATION METHOD

OF SEALING WHILE MAINTAINING THE INTEGRITY OF THE WALL'S FIRE RATING(S).

EXTENSION WALLS & FOUNDATION WALLS: PIPES WHICH PASS THROUGH

EXTENSION WALLS OR FOUNDATION WALLS SHALL BE SEALED AND MADE

WEATHER TIGHT.

10. INSULATE COLD AND HOT WATER PIPING WITH FIRE RETARDANT VAPOR BARRIER

JACKET. PIPE INSULATION SHALL BE SEALED WITH A FIRE RESISTIVE ADHESIVE.

SEE SPECIFICATIONS.

MECHANICAL ABBREVIATIONS

SYMBOL LIST SHOWN IS FOR GENERAL REFERENCE ONLY. THE

PRESENCE OF A SYMBOL DOES NOT IMPLY ITS USE ON THIS PROJECT.

REFER TO THE DRAWINGS FOR SPECIFIC SYMBOLS USED.

(NOTE: NOT ALL ABBREVIATIONS MAY APPEAR ON DRAWINGS)

DRAWING SYMBOLS

DIRECTION OF PIPE PITCH (DOWN);

" PER FOOT

DIRECTION OF FLOW

ANCHOR

REDUCER OR INCREASER

ECCENTRIC REDUCER

TOP CONNECTION, 45° OR 90°

BOTTOM CONNECTION, 45° OR 90°

SIDE CONNECTION

CAPPED OUTLET

RISE OR DROP IN PIPE

UNION

PIPE UP

PIPE DOWN

INVERTED BUCKET TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

FLOAT & THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

THERMOSTATIC TRAP SET INCLUDING PIPING

ACCESSORIES SEE DETAIL

THERMOMETER

PRESSURE GAGE

FLOW ELEMENT

SIGHT GLASS

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

MANUAL AIR VENT

QUICK-COUPLE HOSE CONNECTOR

HIGH PRESSURE STEAM (60 PSIG AND ABOVE)

HIGH PRESSURE STEAM CONDENSATE RETURN

MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)

MEDIUM PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG AND BELOW)

LOW PRESSURE STEAM CONDENSATE RETURN

CONDENSATE PUMP DISCHARGE

HOT WATER HEATING SUPPLY

HOT WATER HEATING RETURN

GLYCOL-WATER HEATING SUPPLY

GLYCOL-WATER HEATING RETURN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

CHILLED WATER SUPPLY

MAKE-UP WATER

DRAIN LINE

VENT LINE

CHILLED WATER RETURN

GLYCOL-WATER RUN AROUND SUPPLY

TUBE CLEANER WATER SUPPLY

CHEMICAL FEED

OVERFLOW

COMPRESSED AIR

COLD WATER (CITY WATER)

GLYCOL-WATER RUN AROUND RETURN

SOFTENED WATER

HOT WATER

REVERSE OSMOSIS

EXISTING PIPE OR EQUIPMENT TO BE REMOVED

GATE VALVE - THREADED / FLANGED

GLOBE VALVE - THREADED / FLANGED

GATE VALVE WITH

" HOSE ADAPTER

CHECK VALVE

WYE STRAINER (WITH BALL VALVE &

HOSE CONNECTION)

WYE STRAINER WITH VALVED DRAIN AND

QUICK COUPLE HOSE CONNECTION

FLEXIBLE CONNECTION

ANGLE GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

MODULATING CONTROL VALVE

MODULATING CONTROL BUTTERFLY VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

THREE-WAY TWO POSITION CONTROL VALVE

PRESSURE REGULATING VALVE

PRESSURE SAFETY VALVE

PRESSURE REDUCING VALVE (PRV)

CONTROL VALVE (CV) - FLOAT-OPERATED

PLUG VALVE

GATE VALVE WITH GLOBE-VALVED BYPASS

CIRCUIT SETTER VALVE

WATER BALANCE DEVICE

KEY NOTE SYMBOL

MULTIPLE KEY NOTES APPLYING TO THE SAME ITEM

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

SECTION NUMBER

DRAWING NUMBER WHERE DRAWN

AHU THAT SERVES THE EQUIPMENT

EQUIPMENT ABBREVIATION (SUPPLY FAN)

EQUIPMENT NUMBER

PIPING SYMBOLS

VALVE SYMBOLS

AUTOMATIC BALANCING CONTROL VALVE

M-103

M-103

TYPICAL DRAWING

BLOCK OR DETAIL TITLE

FLOW SWITCH HIGH

FLOW SWITCH LOW

ROOM THERMOSTAT / TRANSMITTER - WALL MOUNT

ROOM HUMIDISTAT (MOISTURE) / TRANSMITTER - WALL MOUNT

TEMPERATURE TRANSMITTER

MOISTURE (HUMIDITY) TRANSMITTER

PRESSURE TRANSMITTER

STATIC PRESSURE SENSOR

FLOW TRANSMITTER

SMOKE DETECTOR

PRESSURE DIFFERENTIAL TRANSMITTER

PRESSURE DIFFERENTIAL SWITCH

HAND SWITCH (HAND-OFF-AUTO SWITCH)

TEMPERATURE SWITCH, LOW (FREEZESTAT)

TEMPERATURE SWITCH, HIGH (FREEZESTAT)

LEVEL CONTROLLER

LEVEL TRANSMITTER

VARIABLE SPEED MOTOR CONTROLLER

HVAC CONTROL PANEL

LOCAL TEMPERATURE CONTROL PANEL

OCCUPANCY SENSOR

CARBON MONOXIDE TRANSMITTER

CARBON DIOXIDE TRANSMITTER

PRESSURE SWITCH LOW

PRESSURE SWITCH HIGH

TEMPERATURE SENSING ELEMENT FOR TRANSMITTING

TEMPERATURE TO EMCS (PROVIDE 12 INCHES MINIMUM

LENGTH IN DUCT WHEN SPACE PERMITS.)

MOTOR STARTER

ELECTRIC OPERATED CONTROL DAMPER / OR VALVE

CONTROLS SYMBOLS

FIRE AND SMOKE DETECTOR

PIPE CAP OR PLUG

HEATING / COOLING VALVE BOX ASSEMBLY

DRAWING TITLE

SCALE: NONE

NOTE:

SYMBOL LIST SHOWN IS FOR GENERAL

REFERENCE ONLY. THE PRESENCE OF A

SYMBOL DOES NOT IMPLY THAT IT IS USED

ON THIS PROJECT. REFER TO THE

DRAWINGS FOR SPECIFIC SYMBOLS USED.

o n e e i g h t h i n c e f o o t

B

A

C

D

E

F t h r c h e e f o o t o d o n e h a l f i n c h e e f o o t o o t t h r e e q u a r t e r s i n c e f o o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISION DATE

SYRACUSE

VA MEDICAL

CENTER

ENGINEERING

DEPARTMENT

VA ROME OUTPATIENT CLINIC, ROME, NY

06/28/2022

GENERAL PROJECT INFORMATION

100% SPRINKLERED

DWG.

U.S. Department of Veterans Affairs

B

A

C

D

E

F

528A7-23-102

ADD CHILLER AT ROME CBOC

S S

Y R

M

S M

S E n g i n e e r i n g P

R O

J E

C T

S A

C T

I V

E

P

R O

J E

C T

S

A i l l e r a t

R o m e

C

B O

C D e s i g n

P h a s e

D r a w i n g s C

A D

M e c h a n i c a l

A

M

M

E C

H d w g

OF 12

MG-001

JDMA

MECHANICAL ABBREVIATIONS,

SYMBOLS & NOTES

1 2

1-SF-1

CONNECT NEW TO EXISTING

LIMIT OF DEMOTION

AutoCAD SHX Text

AT

AutoCAD SHX Text

OC

AutoCAD SHX Text

FE

AutoCAD SHX Text

AV

AutoCAD SHX Text

MV

AutoCAD SHX Text

SD

AutoCAD SHX Text

FSD

AutoCAD SHX Text

AT

AutoCAD SHX Text

CO2

AutoCAD SHX Text

AT

AutoCAD SHX Text

CO

AutoCAD SHX Text

HS

AutoCAD SHX Text Rh

AutoCAD SHX Text

FT

AutoCAD SHX Text

MT

AutoCAD SHX Text M

AutoCAD SHX Text

LT

AutoCAD SHX Text

LC

AutoCAD SHX Text

PT

AutoCAD SHX Text

PSH

AutoCAD SHX Text

TT

AutoCAD SHX Text T

AutoCAD SHX Text

SPS

AutoCAD SHX Text

PDT

AutoCAD SHX Text

PDS

AutoCAD SHX Text

TSL

AutoCAD SHX Text

TSH

AutoCAD SHX Text

PSL

AutoCAD SHX Text

FSH

AutoCAD SHX Text

FSL

AutoCAD SHX Text

HVAC

AutoCAD SHX Text

LTCP

AutoCAD SHX Text M

AutoCAD SHX Text

VSMC

D

G127

FMS

G124

WAREHOUSE STORAGE

G134

MECHANICAL ROOM

G128

CLOSET

G129

ROOM

GS2

STAIR #2

G130

FMS

G131

ELECTRICAL ROOM

G134A

GENERATOR ROOM

HE-SP

EXISTING AHU-5 EXISTING AHU-6

EXISTING AHU-8

EXISTING AHU-7

3"

3"

1"

VENT

TO & FROM STEAM MANHOLE

WALL SLEEVE

(BELOW GRADE)

2" VENT

WALL SLEEVE

3"

" PC (CAPPED

FOR FUTURE)

CONCRETE PAD

CRS-SP

3" HPS

3" HPS

5"

LPC FROM FLASH TANK

PRESSURE REDUCING

STATION PRS-SP

COMPLETE WITH METER

5" VENT FROM

SAFETY RELIEF

VALVE DISCHARGE

5"

4"

3"

5" 3"

CV-SP-2

CV-SP-1

3"

3"

5"

4"

5"

2"

4"

3"

ABANDONED STEAM

SERVICE ENTRANCE

EXIST. CONC. PAD

EXIST. DOMESTIC

WATER HEATER

CHILLER

WC-2

2"

2"

AS

EXIST. CONC. PAD

4"

4"

3"

4"

5"

5"

5"

5"

5"

8"

AS

" TO EXPANSION

TANKS

NC

NO

5"

5"

5"

5"

3"

5"

5" 5"

5"

EXISTING

BOILER B-1

(GAS ONLY)

EXISTING

BOILER B-2

(GAS / OIL)

8"

EXIST. CONC.

PAD

EXIST. 8" CWS &

CWR TO & FROM

COOLING TOWER

(BELOW GRADE)

5"

5"

5"

8"

PUMP P-HWG-1 PUMP P-HWG-2

5"

6"

5"

DN TO EXIST.

2" DRAIN

EXIST. 8" VENT

UP THRU ROOF

HHW PUMPS

P-HW-1 &

P-HW-2

8"

CHW PUMP

P-1

CHW PUMP

P-2

6"

8"

6"

EXIST.

EMERGENCY

GENERATOR

EXIST. OIL

150 GAL.

DAY TANK

2'-0"

4"

CW PUMP

P-3

CW PUMP

P-4

EXIST. TRENCH

15'-0"

2 APPROX. NEW

LOCATION OF

CHILLER WC-2,

SEE M-101

APPROX. NEW

LOCATION OF

PUMPS P-1 & P-2,

SEE M-101

5"

4"

5"

CV-CO

EXIST.

EXHAUST FAN

EF-14, EF-13

BELOW

EXIST.

EXHAUST

FAN EF-17

MECHANICAL DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

MECHANICAL DEMOLITION GENERAL NOTES:

1. REMOVE EVERYTHING WITHIN WORK AREA AS SHOWN AND INDICATED; TO

INCLUDE BUT NOT LIMITED TO: ELECTRICAL CONDUITS, PIPING, VALVES,

CONTROLS, AND INSULATION.

2. ALL ABANDONED PIPING & CONDUITS IN THE WORK AREA SHALL BE REMOVED.

COORDINATE WITH VAMC COR PRIOR TO REMOVAL.

3. SCHEDULE ALL SHUTDOWNS REQUIRED WITH VAMC COR AT LEAST 48 HOURS IN

ADVANCE. SHUTDOWNS SHALL NOT INTERFERE WITH ANY FACILITY OPERATIONS.

WORK SHALL BE SCHEDULED DURING THE MONTHS OF NOVEMBER THROUGH

MARCH.

MECHANICAL DEMOLITION KEYED NOTES:

DISCONNECT EXISTING CHILLED WATER PUMPS P-1, P-2 AND AIR SEPARATOR.

DEMO PIPING, VALVES AND ACCESSORIES, SAVE FOR RE-USE TO EXTENT

POSSIBLE. REMOVE CONCRETE HOUSEKEEPING PAD AS SHOWN. PUMPS TO BE

RE-INSTALLED AT NEW LOCATION SHOWN, SEE M-101. COORDINATE WITH

ELECTRICAL CONTRACTOR AND VAMC COR.

DISCONNECT EXISTING CHILLER WC-2. DEMO PIPING, VALVES AND

ACCESSORIES AS SHOWN. CHILLER TO BE RE-INSTALLED AT NEW LOCATION

SHOWN, SEE M-101. COORDINATE WITH ELECTRICAL CONTRACTOR, HVAC

CONTROLS CONTRACTOR AND VAMC COR.

REMOVE EXISTING 3" PVC REFRIGERANT VENT PIPING. DISCONNECT AND

DEMOLISH HALOGUARD II REFRIGERANT MONITOR AFTER NEW REFRIGERANT

MONITOR IS INSTALLED AND OPERATIONAL.

o n e e i g h t h i n c e f o o t

B

A

C

D

E

F t h r e e i n c h e e f o o t o n e a n d o l f i n c h e o t o n e i n c e f o o t t h r q u a r t e r s i n o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISION DATE

SYRACUSE

VA MEDICAL

CENTER

ENGINEERING

DEPARTMENT

VA ROME OUTPATIENT CLINIC, ROME, NY

06/28/2022

GENERAL PROJECT INFORMATION

100% SPRINKLERED

DWG.

U.S. Department of Veterans Affairs

B

A

C

D

E

F

528A7-23-102

ADD CHILLER AT ROME CBOC

S S

Y R

M

S M

S E n g i n e e r i n g P

R O

J E

C T

S A

C T

I V

E

P

R O

J E

C T

S

A i l l e r a t

R o m e

C

B O

C D e s i g n

P h a s e

D r a w i n g s C

A D

M e c h a n i c a l

A

M

M

E C

H d w g

OF 12

MD-101

JDMA

MECHANICAL DEMOLITION PLAN

N

AutoCAD SHX Text P

P

D

G127

FMS

G124

WAREHOUSE STORAGE

G134

MECHANICAL ROOM

G128

CLOSET

G129

ROOM

GS2

STAIR #2

G130

FMS

G131

ELECTRICAL ROOM

G134A

GENERATOR ROOM

HE-SP

EXISTING AHU-5 EXISTING AHU-6

EXISTING AHU-8

EXISTING AHU-7

3"

3"

1"

VENT

TO & FROM STEAM MANHOLE

WALL SLEEVE

(BELOW GRADE)

2" VENT

WALL SLEEVE

3"

" PC (CAPPED

FOR FUTURE)

CONCRETE PAD

CRS-SP

3" HPS

3" HPS

5"

LPC FROM FLASH TANK

PRESSURE REDUCING

STATION PRS-SP

COMPLETE WITH METER

5" VENT FROM

SAFETY RELIEF

VALVE DISCHARGE

5"

4"

3"

5" 3"

CV-SP-2

CV-SP-1

3"

3"

5"

4"

5"

2"

4"

3"

ABANDONED STEAM

SERVICE ENTRANCE

EXIST. CONC. PAD

EXIST. DOMESTIC

WATER HEATER

2"

2"

EXIST. CONC. PAD

4"

4"

3"

4"

5"

5"

5"

5"

5"

8"

AS

" TO EXPANSION

TANKS

NC

NO

5"

5"

5"

5"

3"

5"

5" 5"

5"

EXISTING

BOILER B-1

(GAS ONLY)

EXISTING

BOILER B-2

(GAS / OIL)

8"

EXIST. CONC.

PAD

EXIST. 8" CWS &

CWR TO & FROM

COOLING TOWER

(BELOW GRADE)

5"

5"

5"

8"

PUMP P-HWG-1 PUMP P-HWG-2

5"

6"

5"

DN TO EXIST.

2" DRAIN

EXIST. 8" VENT

UP THRU ROOF

HHW PUMPS

P-HW-1 &

P-HW-2

8"

AS

CHW PUMP

P-1

CHW PUMP

P-2

6"

8"

6"

15'-6"

RELOCATED

CHILLER WC-2

EXIST.

EMERGENCY

GENERATOR

EXIST. OIL

150 GAL.

DAY TANK

15'-0"

RELOCATED PUMPS

& NEW CONC. PAD

6"

6"

5"

5"

6"

6"

4"

NEW

CHILLER

WC-1

CW PUMP

P-3

CW PUMP

P-4

EXIST. TRENCH

5"

4"

5"

COND.

EVAPORATOR

CV-CO

3"

3"

CONNECT TO

(6) EXIST.

VENT RISERS

CONNECT TO

(3) 1-1/2"

VENT RISERS

M-101

CORE THRU WALL;

REUSE (1) EXIST.

OPNG IF POSSIBLE

FT4

FT3

FT1

FT2

CHW-ISO-1

CHW-ISO-2

CW-ISO-2

CW-ISO-1

EXIST.

EXHAUST FAN

EF-14, EF-13

BELOW

EXIST.

EXHAUST

FAN EF-17

EXISTING AHU-1A

EXISTING AHU-1B

EXISTING AHU-2

EXISTING AHU-4

3"

MECH. PENTHOUSE

3S1

STAIR #1

ROOM

CHASE CHASE

ROOF

ROOF

1"

1" CAP

4"

TO COOLING COIL

TO HUMIDIFIER

TO HEATING COIL

2"

3"

4"

2"

1" DN

" DN

" DN

3" DN

2" DN

2"

4"

4" DN

2"

EXISTING

CSG-1A

EXISTING

CSG-1B

DP

CHW-DP

MECHANICAL DRAWING GENERAL NOTES:

1. PROVIDE ALL CONTROL COMPONENTS, CONTROL WIRING, AND CONNECTIONS

TO PROPERLY INTERFACE WITH THE EXISTING DELTA TEMPERATURE CONTROL

SYSTEM AND CONTROL OPERATING SYSTEMS. ALL NEW CONTROL

COMPONENTS, CONTROL VALVES, THERMOSTATS, SENSORS, ETC. SHALL BE

ELECTRIC TYPE. COORDINATE WITH VAMC COR.

2. MAINTAIN THE INTEGRITY OF ALL EXISTING EQUIPMENT AND SYSTEMS

LOCATED OUTSIDE THE WORK AREA AND INTERRUPTED BY THE RENOVATION

WORK. PROVIDE ALL ADDITIONAL PIPING, FITTINGS, DUCTWORK, ACCESSORIES,

ETC. REQUIRED TO EXTEND AND RECONNECT REMAINING EQUIPMENT AND

SYSTEMS.

3. SCHEDULE ALL SHUTDOWNS REQUIRED WITH VAMC COR AT LEAST 48 HOURS IN

ADVANCE. SHUTDOWNS SHALL NOT INTERFERE WITH ANY FACILITY

OPERATIONS. PROVIDE TEMPORARY SYSTEMS DURING SHUTDOWNS AS

REQUIRED.

4. SYSTEMS INDICATED ON DRAWINGS SHALL BE INSTALLED AS SHOWN.

ADJUSTMENT TO LOCATIONS OF VARIOUS ITEMS MAY BE REQUIRED BY FIELD

CONDITIONS. VERIFY AND COORDINATE WITH COR PRIOR TO INSTALLATION.

5. PROVIDE SERVICE CLEARANCE FOR ALL HVAC EQUIPMENT AS RECOMMENDED

BY MANUFACTURER.

6. INSULATE ALL CHILLED WATER SUPPLY AND RETURN LINES PER SPECIFICATION

230711.

o n e e i g h t h i n c e f o o t

B

A

C

D

E

F t h r e e i n c h e e f o o t o n e a n d o l f i n c h e o t o n e i n c e f o o t t h r a r t e r s i n o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISION DATE

SYRACUSE

VA MEDICAL

CENTER

ENGINEERING

DEPARTMENT

VA ROME OUTPATIENT CLINIC, ROME, NY

06/28/2022

GENERAL PROJECT INFORMATION

100% SPRINKLERED

DWG.

U.S. Department of Veterans Affairs

B

A

C

D

E

F

528A7-23-102

ADD CHILLER AT ROME CBOC

S S

Y R

M

S M

S E n g i n e e r i n g P

R O

J E

C T

S A

C T

I V

E

P

R O

J E

C T

S

A i l l e r a t

R o m e

C

B O

C D e s i g n

P h a s e

D r a w i n g s C

A D

M e c h a n i c a l

A

M

M

E C

H d w g

OF 12

M-101

JDMA

MECHANICAL PLAN

MECHANICAL DRAWING KEYED NOTES:

INSTALL NEW CHILLER WC-1 AT LOCATION SHOWN, SEE DETAIL ON MG-501.

RE-INSTALL EXISTING CHILLER WC-2 AT NEW LOCATION AS SHOWN. SEE

DEMOLITION PLAN ON MP-101 AND DETAILS ON MG-501.

RELOCATE EXISTING CHILLED WATER PUMP ASSEMBLY (PUMPS P-1, P-2 AND

AIR SEPARATOR) APPROXIMATELY 30" WEST AND 24" SOUTH. REUSE EXISTING

VALVES, GAUGES, ETC. TO EXTENT POSSIBLE. DEMO EXISTING CONCRETE

PAD AND PROVIDE A NEW CONCRETE PAD. SEE DEMOLITION PLAN MD-101

AND DETAILS ON MG-501.

NEW VFD'S FOR EXISTING CHW PUMPS P-3 AND P-4 TO BE PROVIDED AND

INSTALLED BY ELECTRICAL CONTRACTOR. PUMP VFD'S TO BE CONTROLLED

BY CHILLER CONDENSER BARREL DIFFERENTIAL PRESSURE OR FLOW

METERS BY MECHANICAL CONTRACTOR. COORDINATE ALL WORK WITH

ELECTRICAL CONTRACTOR AND HVAC CONTROLS CONTRACTOR.

EXISTING VARIABLE FREQUENCY DRIVES (VFD'S) SHALL CONTROL CHILLED

WATER TO NEW DIFFERENTIAL PRESSURE SENSOR IN PENTHOUSE, SEE

PENTHOUSE PLAN 2/M-101.

MOUNT NEW REFRIGERANT GAS DETECTOR; SHERLOCK 202 BY GENESIS

INTERNATIONAL (OR EQUAL). INCLUDE REFRIGERANT SENSORS FOR R-1233ZD

AND R-134A AND HORN/STROBE. COORDINATE WITH HVAC CONTROLS

CONTRACTOR FOR INTEGRATION TO THE DELTA BAS CONTROL SYSTEM TO

START THE MECHANICAL ROOM EXHAUST FAN, OPEN MAKE-UP AIR DAMPERS

AND INITIATE A CRITICAL ALARM.

CONNECT NEW 3" COPPER REFRIGERANT VENT LINE TO CHILLER REFRIGERANT

VENTS. PROVIDE A STAINLESS STEEL FLEXIBLE CONNECTOR WITH DIELECTRIC

FLANGES/UNIONS ON THE 3" VENT LINE FOR EACH CHILLER.

PROVIDE VIBRATION ISOLATION PADS AND CONCRETE ANCHORS ON EACH

CHILLER. PROVIDE STAINLESS STEEL SHIMS UNDER ISOLATORS TO LEVEL

ISOLATION PADS PRIOR TO SETTING THE CHILLER IN PLACE, IF NECESSARY.

PROVIDE NEW 6" THICK CONCRETE HOUSEKEEPING PAD, REFER TO DETAIL 5 ON

DRAWING MG-501.

MECHANICAL PLAN

SCALE: 1/4" = 1'-0"

N

PENTHOUSE MECHANICAL PLAN

SCALE: 1/4" = 1'-0"

N

M-101

RUPTURE DISC RELIEF PIPING DETAIL

SCALE: NONE

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text

VSMC

AutoCAD SHX Text

VSMC

AutoCAD SHX Text

INTERIOR

AutoCAD SHX Text

EXTERIOR

AutoCAD SHX Text

SEAL PENETRATION W/NON-SHRINK GROUT

AutoCAD SHX Text

GALV. STEEL PIPE SLEEVE

AutoCAD SHX Text

MODULAR-TYPE WALL PENETRATION SEAL AT CORE-THRU OPENINGS

AutoCAD SHX Text

EXIST. MASONRY WALL

AutoCAD SHX Text

FLEXIBLE SST CONN. W/DIELECTRIC SEPARATION

AutoCAD SHX Text

RUPTURE DISC ASSEMBLY

AutoCAD SHX Text

SCREENED OUTLET

AutoCAD SHX Text

14" DRAIN VALVE

AutoCAD SHX Text

3" DRIP LEG (LENGTH AS REQ'D FOR ACCESS)

AutoCAD SHX Text

3" COPPER REFRIGERANT VENT FROM CHILLER (TYP 2 PLCS)

DETAIL NOTES: 1. ALL REFRIGERANT VENT PIPING SHALL BE COPPER UNLESS NOTED OTHERWISE. ALL REFRIGERANT VENT PIPING SHALL BE COPPER UNLESS NOTED OTHERWISE. 2. SUPPORT ALL PIPE AND FITTINGS WITH HANGERS AS REQUIRED.SUPPORT ALL PIPE AND FITTINGS WITH HANGERS AS REQUIRED.

SCALE: NONE

RATED BARRIER PENETRATION-INSULATED PIPE

o n e e i g h t h i n c e f o o t

B

A

C

D

E

F t h r e e i n c h e e f o o t o n e a n d o l f i n c h e o t o n e i n c e f o o t t h r a r t e r s i n o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISION DATE

SYRACUSE

VA MEDICAL

CENTER

ENGINEERING

DEPARTMENT

VA ROME OUTPATIENT CLINIC, ROME, NY

06/28/2022

GENERAL PROJECT INFORMATION

100% SPRINKLERED

DWG.

U.S. Department of Veterans Affairs

B

A

C

D

E

F

528A7-23-102

ADD CHILLER AT ROME CBOC

S S

Y R

M

S M

S E n g i n e e r i n g P

R O

J E

C T

S A

C T

I V

E

P

R O

J E

C T

S

A i l l e r a t

R o m e

C

B O

C D e s i g n

P h a s e

D r a w i n g s C

A D

M e c h a n i c a l

A

M

M

E C

H d w g

OF 12

MG-501

JDMA

MECHANICAL DETAILS

WATER-COOLED CHILLER PIPING DETAIL

SCALE: NONE

PIPE HANGERS

SCALE: NONE

INTERIOR CONCRETE

EQUIPMENT PAD DETAIL

SCALE: NONE

SECURING PIPE OR DUCTWORK HANGER

RODS FROM CONCRETE DECK DETAILS

SCALE: NONE

TYPICAL PIPE OR DUCTWORK HANGER ROD

CLAMP TO BUILDING STEEL DETAILS

SCALE: NONE

TYPICAL PUMP PIPING CONNECTIONS DETAIL

SCALE: NONE

CHILLED WATER PIPING SCHEMATIC

SCALE: NONE

CONDENSER WATER PIPING SCHEMATIC

SCALE: NONE

FLOW METER INSTALLATION DETAIL

SCALE: NONE

AutoCAD SHX Text

PIPE INSULATION (2" THICK MAX.)

AutoCAD SHX Text

THROUGH-PENETRANT STEEL PIPE OR COPPER TUBE

AutoCAD SHX Text SEALANT: MIN. " THICK 12" THICK UL-LISTED, FIRE-RATED CAULK APPLIED WITHIN ANNULUS FLUSH WITH FINISHED SURFACE OF WALL ASSEMBLY

AutoCAD SHX Text

2-HR. RATED SHAFT WALL ASSEMBLY

AutoCAD SHX Text

GYPSUM BOARD OR MASONRY WALL

AutoCAD SHX Text

STEEL SLEEVE FLUSH WITH FACE OF WALL (BOTH SIDES)

AutoCAD SHX Text

PACKING MATERIAL - MIN. 3 " 14" WIDE OF MIN. 4 PCF MINERAL WOOL BATT INSULATION

AutoCAD SHX Text WALL STRIP - " TH'K x 1 " WIDE 316" TH'K x 1 " WIDE 34" WIDE INTUMESCENT STRIP WRAPPED TIGHTLY AROUND PIPE COVERING

AutoCAD SHX Text

NOTE: UL SYSTEM W-J-5048

AutoCAD SHX Text

NOTE: SEE SPECIFICATIONS FOR DETAILED HANGER REQUIREMENTS.

AutoCAD SHX Text

5 FT

AutoCAD SHX Text

AutoCAD SHX Text

THRU [20]

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text [32]

AutoCAD SHX Text [25]

AutoCAD SHX Text [40]

AutoCAD SHX Text

AutoCAD SHX Text [65]

AutoCAD SHX Text

AutoCAD SHX Text [50]

AutoCAD SHX Text

AutoCAD SHX Text [75]

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text [125]

AutoCAD SHX Text [100]

AutoCAD SHX Text

AutoCAD SHX Text [150]

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2 12

AutoCAD SHX Text 1 12

AutoCAD SHX Text

AutoCAD SHX Text 1 14

AutoCAD SHX Text [5200]

AutoCAD SHX Text [4100]

AutoCAD SHX Text [4900]

AutoCAD SHX Text [3700]

AutoCAD SHX Text [3000]

AutoCAD SHX Text [3400]

AutoCAD SHX Text [2700]

AutoCAD SHX Text [2100]

AutoCAD SHX Text [4100]

AutoCAD SHX Text [3700]

AutoCAD SHX Text [4000]

AutoCAD SHX Text [3000]

AutoCAD SHX Text [2400]

AutoCAD SHX Text [1800]

AutoCAD SHX Text [1500]

AutoCAD SHX Text

THRU 34

AutoCAD SHX Text

AutoCAD SHX Text [2100]

AutoCAD SHX Text [2100]

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text [2100]

AutoCAD SHX Text

AutoCAD SHX Text [2700]

AutoCAD SHX Text

AutoCAD SHX Text [2400]

AutoCAD SHX Text

SIDE VIEW TRAPEZE HANGER FOR UP TO 1000 LB. [453KG] UNIFORM LOAD

AutoCAD SHX Text

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE SPECIFICATIONS

AutoCAD SHX Text

ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE SPECIFICATIONS

AutoCAD SHX Text

MAXIMUM PIPE/TUBING SUPPORT SPACING

AutoCAD SHX Text

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

AutoCAD SHX Text

NOM. SIZE

AutoCAD SHX Text

PIPE

AutoCAD SHX Text

TUBING

AutoCAD SHX Text

IN.

AutoCAD SHX Text [mm]

AutoCAD SHX Text

FT.

AutoCAD SHX Text [mm]

AutoCAD SHX Text

FT.

AutoCAD SHX Text [mm]

AutoCAD SHX Text

HANGER ROD

AutoCAD SHX Text

INSULATION (VAPOR BARRIER TYPE IS REQUIRED FOR LOW TEMPERATURE PIPE)

AutoCAD SHX Text PROVIDE HIGH COMPRESSIVE STRENGTH INSULATION (9 PSF MIN. DENSITY) UNDER INSULATION SHIELD

AutoCAD SHX Text

INSULATION SHIELD AT HANGER

AutoCAD SHX Text

WELD

AutoCAD SHX Text

SADDLE

AutoCAD SHX Text 12" [15mm] DIA. HANGER RODS W/36" [900mm] MAX. SPACING ON EACH CHANNEL

AutoCAD SHX Text

BAND

AutoCAD SHX Text 1 " [43mm] 12 GA. 58" [43mm] 12 GA. CHANNEL OR 2"x2"x " 14" [50x50x6.4mm] ANGLE

AutoCAD SHX Text PROVIDE INSULATION SHIELD & INSERT FOR ALL PIPING (8" [200mm] MIN.)

AutoCAD SHX Text

1" MAX.

AutoCAD SHX Text

1" MAX.

AutoCAD SHX Text

FIN. FLOOR

AutoCAD SHX Text NOTE: LENGTH AND WIDTH DIMENSIONS OF THE CONCRETE PAD SHALL BE 6" GREATER THAN THE BASE OF THE EQUIPMENT.

AutoCAD SHX Text

EDGE OF EQUIPMENT

AutoCAD SHX Text

CONCRETE PAD: 3000 PSI @ 28 DAYS

AutoCAD SHX Text #4 @ 12" O.C. E.W., T&B

AutoCAD SHX Text

1" CHAMFER ENTIRE PAD PERIMETER (TYP)

AutoCAD SHX Text

PROVIDE #3 BARS 12" O.C. EACH WAY IN CONCRETE PAD, DOWEL PAD TO FLOOR

AutoCAD SHX Text NOTE: REFER TO PIPE HANGER OR DUCTWORK SUPPORT DETAILS FOR HANGER ROD SIZE. FOR CEILING SUSPENDED EQUIPMENT REFER TO PIPE HANGER OR DUCTWORK SUPPORT DETAILS FOR HANGER ROD SIZE. FOR CEILING SUSPENDED EQUIPMENT PROVIDE MIN. " DIA. HANGER ROD (REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS).38" DIA. HANGER ROD (REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS).

AutoCAD SHX Text

CONCRETE SLAB OR BEAM

AutoCAD SHX Text STEEL EXPANSION SHIELD ANCHOR IN (E) CONCRETE & INSERTS FOR NEW CONCRETE; THIS TYPE SHALL ONLY BE USED IN SLABS OR BEAMS OF 4" MIN. DEPTH

AutoCAD SHX Text

38" MIN. DIA. EXPANSION BOLTS FOR (E) CONCRETE & INSERTS FOR NEW CONCRETE (TYP)

AutoCAD SHX Text FOR PIPES UNDER 2" USE 1 "x1 "x " ANGLE, 12"x1 "x " ANGLE, 12"x " ANGLE, 14" ANGLE, FOR PIPES LARGER THAN 2" USE 3"x3"x " ANGLE14" ANGLE

AutoCAD SHX Text

NUTS & WASHERS (TYP)

AutoCAD SHX Text

38" MIN. DIA. HANGER RODS (TYP)

AutoCAD SHX Text

TURNBUCKLE

AutoCAD SHX Text

STRUCTURAL STEEL OR WEB STEEL JOISTS (TYP)

AutoCAD SHX Text

CONCRETE FLOOR OR ROOF SLAB

AutoCAD SHX Text

METAL DECKING (IF APPLICABLE)

AutoCAD SHX Text

METAL CHANNEL STRUT

AutoCAD SHX Text

NUT & WASHER (TYP)

AutoCAD SHX Text

BEAM CLAMP (TYP)

AutoCAD SHX Text

DOUBLE-SIDED BEAM CLAMP

AutoCAD SHX Text

HANGER ROD (TYP-SEE NOTE)

AutoCAD SHX Text

SIDE BEAM CLAMP

AutoCAD SHX Text

TOP BEAM C-CLAMP FOR PIPING 3" & LARGER

AutoCAD SHX Text

C-CLAMP FOR PIPING 2 " & SMALLER14" & SMALLER

AutoCAD SHX Text

VIBRATION ISOLATOR (TYP)

AutoCAD SHX Text

CONTROL & VSD PANELS

AutoCAD SHX Text

RELIEF VENT (SEE PLAN)

AutoCAD SHX Text

CONDENSER WATER SUPPLY

AutoCAD SHX Text

CONDENSER WATER RETURN

AutoCAD SHX Text

CHILLED WATER SUPPLY

AutoCAD SHX Text

CHILLED WATER RETURN

AutoCAD SHX Text

COMPRESSOR

AutoCAD SHX Text

MOTOR

AutoCAD SHX Text

BUTTERFLY VALVE (TYP)

AutoCAD SHX Text

THERMOMETER (TYP)

AutoCAD SHX Text

PRESSURE GAUGE (TYP)

AutoCAD SHX Text

FLEXIBLE CONNECTION (TYP)

AutoCAD SHX Text

EVAPORATOR

AutoCAD SHX Text

CONDENSER

AutoCAD SHX Text

FIN. FLR

AutoCAD SHX Text

SUCTION

AutoCAD SHX Text

DISCHARGE

AutoCAD SHX Text

UNIVERSAL TEST STATION PLUG (TYP)

AutoCAD SHX Text

SILENT CHECK VALVE (TYP)

AutoCAD SHX Text

THERMOMETER (TYP)

AutoCAD SHX Text

INCREASER

AutoCAD SHX Text

PUMP MOUNTING

AutoCAD SHX Text

COUPLING

AutoCAD SHX Text

PRESSURE GAUGE (TYP)

AutoCAD SHX Text

BUTTERFLY VALVE (TYP)

AutoCAD SHX Text

STRAINER

AutoCAD SHX Text

LONG RADIUS ELBOW

AutoCAD SHX Text

PIPE SUPPORT; SEE DETAIL

AutoCAD SHX Text

FLEX CONN. (TYP)

AutoCAD SHX Text

REDUCER

AutoCAD SHX Text

SPRING VIBRATION ISOLATOR

AutoCAD SHX Text

1 " CW14" CW

AutoCAD SHX Text

5" CHWR

AutoCAD SHX Text

5" CHWR

AutoCAD SHX Text

5" CHWS

AutoCAD SHX Text

ROTARY SCREW CHILLER WC-2 EVAPORATOR

AutoCAD SHX Text

ROTARY SCREW CHILLER WC-2 CONDENSER

AutoCAD SHX Text

CENTRIFUGAL CHILLER WC-1 EVAPORATOR

AutoCAD SHX Text

AS-3

AutoCAD SHX Text P-2

AutoCAD SHX Text P-1

AutoCAD SHX Text

5" CHWS

AutoCAD SHX Text

5" CHWS

AutoCAD SHX Text

5" CHWS

AutoCAD SHX Text

5" CHWS

AutoCAD SHX Text

5" CHWR

AutoCAD SHX Text

5" CHWR

AutoCAD SHX Text

5" CHWR

AutoCAD SHX Text

EXPANSION TANK

AutoCAD SHX Text

CENTRIFUGAL CHILLER WC-1 CONDENSER

AutoCAD SHX Text

TRIPLE DUTY VALVE (TYP)

AutoCAD SHX Text

BUTTERFLY VALVE (TYP)

AutoCAD SHX Text

SUCTION DIFFUSER (TYP)

AutoCAD SHX Text

2" DRAIN VALVE (TYP)

AutoCAD SHX Text S

AutoCAD SHX Text

FLOW SWITCH

AutoCAD SHX Text

5" CHWS

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text

FS

AutoCAD SHX Text

EXISTING COOLING TOWER SUMP

AutoCAD SHX Text

ROTARY SCREW CHILLER WC-2 EVAPORATOR

AutoCAD SHX Text

ROTARY SCREW CHILLER WC-2 CONDENSER

AutoCAD SHX Text

CENTRIFUGAL CHILLER WC-1 EVAPORATOR

AutoCAD SHX Text

CENTRIFUGAL CHILLER WC-1 CONDENSER

AutoCAD SHX Text

2" DRAIN VALVE (TYP)

AutoCAD SHX Text P-4

AutoCAD SHX Text P-3

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text

FT

AutoCAD SHX Text

FT

AutoCAD SHX Text P

AutoCAD SHX Text

6" CWS

AutoCAD SHX Text

6" CWS

AutoCAD SHX Text

6" CWS

AutoCAD SHX Text

6" CWS

AutoCAD SHX Text

8" CWR

AutoCAD SHX Text

2" CW

AutoCAD SHX Text

8" CWS

AutoCAD SHX Text

10" CWR

AutoCAD SHX Text

8" CWR

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text

CONTROL/MODULATING VALVE

AutoCAD SHX Text

REFER TO TABLE FOR

AutoCAD SHX Text

REFER TO TABLE FOR

AutoCAD SHX Text

MINIMUM UPSTREAM STRAIGHT RUN REQUIRED

AutoCAD SHX Text

UPSTREAM

AutoCAD SHX Text

10 DIA

AutoCAD SHX Text

10 DIA

AutoCAD SHX Text

15 DIA

AutoCAD SHX Text

30 DIA

AutoCAD SHX Text

20 DIA

AutoCAD SHX Text

30 DIA

AutoCAD SHX Text

30 DIA

AutoCAD SHX Text

IN-FLOWING TEE

AutoCAD SHX Text

MULTIPLE BENDS OUT OF PLANE

AutoCAD SHX Text

OUT-FLOWING TEE/PUMP OUTFLOW

AutoCAD SHX Text

SINGLE BEND PRECEDED BY <9 DIAMETERS OF STRAIGHT PIPE RUN

AutoCAD SHX Text

PIPE SIZE REDUCTION/EXPANSION IN STRAIGHT RUN

AutoCAD SHX Text

SINGLE BEND PRECEDED BY >9 DIAMETERS OF STRAIGHT PIPE RUN

AutoCAD SHX Text

OBSTRUCTION

AutoCAD SHX Text

FLOW METER; BASIS OF DESIGN: ONICON F-3500

AutoCAD SHX Text

FULL PORT BALL VALVE

AutoCAD SHX Text

NOTE: PIPING CONFIGURATION VARIES BETWEEN NEW AND EXISTING CHILLERS.

AutoCAD SHX Text

MOTORIZED BUTTERFLY VALVE W/HAND WHEEL OPERATOR IN BYPASS MODE (TYP)

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

TEMPERATURE SENSOR (TYP)

AutoCAD SHX Text

FT

AutoCAD SHX Text

FT

AutoCAD SHX Text

FLEX CONN (TYP)

AutoCAD SHX Text

TRIPLE DUTY VALVE (TYP)

AutoCAD SHX Text

BUTTERFLY VALVE (TYP)

FLEX CONN (TYP)

e e i g h t h i n c e f o o t

B

A

C

D

E

F t h r e e i n c h e e f o o t o n e a n d o l f i n c h e o t o n e i n c e f o o t t h r a r t e r s i n o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISION DATE

SYRACUSE

VA MEDICAL

CENTER

ENGINEERING

DEPARTMENT

VA ROME OUTPATIENT CLINIC, ROME, NY

06/28/2022

GENERAL PROJECT INFORMATION

100% SPRINKLERED

DWG.

U.S. Department of Veterans Affairs

B

A

C

D

E

F

528A7-23-102

ADD CHILLER AT ROME CBOC

S S

Y R

M

S M

S E n g i n e e r i n g P

R O

J E

C T

S A

C T

I V

E

P

R O

J E

C T

S

A i l l e r a t

R o m e

C

B O

C D e s i g n

P h a s e

D r a w i n g s C

A D

M e c h a n i c a l

A

M

M

E C

H d w g

OF 12

MG-601

JDMA

MECHANICAL SCHEDULES

ABBREVIATIONS

AHU AIR HANDLING UNIT

AFMS AIR FLOW MEASURING STATION, "PIEZOMETER RINGS" ARE PROVIDED & INSTALLED BY

AHU VENDOR. TRANSDUCERS AND CONTROL WIRING BY CONTROLS CONTRACTOR.

ATU AIR TERMINAL UNIT

CC COOLING COIL

CCLT COOLING COIL LEAVING TEMPERATURE

CCET COOLING COIL ENTERING TEMPERATURE

CCV COOLING COIL CONTROL VALVE

DAT DISCHARGE AIR TEMPERATURE

DASP DISCHARGE AIR STATIC PRESSURE

DWH DOMESTIC WATER HEATER

EAD EXHAUST AIR DAMPER

EF EXHAUST FAN

EASP EXHAUST AIR STATIC PRESSURE

EAT EXHAUST AIR TEMPERATURE

EAF EXHAUST AIR FLOW

ERW ENERGY RECOVERY WHEEL

FA FAULT ALARM

FSD FIRE-SMOKE DAMPER

FE FLOW ELEMENT

GF/CI GOVERNMENT FURNISHED / CONTRACTOR INSTALLED

HC HEATING COIL

HCLT HEATING COIL LEAVING TEMPERATURE

HCET HEATING COIL ENTERING TEMPERATURE

HHWV HEATING HOT WATER CONTROL VALVE

HSCV HEATING STEAM CONTROL VALVE

HSV HUMIDIFIER STEAM VALVE

HUM-ISO HUMIDIFIER ENABLE VALVE

MPS MEDIUM PRESSURE STEAM FOR HUMIDIFIER

MPC MEDIUM PRESSURE CONDENSATE RETURN

OAT OUTDOOR AIR TEMPERATURE

OAD OUTDOOR AIR DAMPER

PF-EA PREFILTER (EXHAUST AIR)

PF-OA PREFILTER (OUTDOOR AIR)

PHT PRE-HEAT TEMPERATURE

RAT RETURN AIR TEMPERATURE

RI RUN INDICATOR

RM-A REFRIGERANT MONITOR ALARM

SAT SUPPLY AIR TEMPERATURE

SAF SUPPLY AIR FLOW

SF SUPPLY FAN

SDS SMOKE DETECTOR SUPPLY

SHP STATIC PRESSURE HIGH LIMIT

S/S START / STOP

TE TEMPERATURE ELEMENT

TU TERMINAL UNIT

VFD VARIABLE FREQUENCY DRIVE

o n e e i g h t h i n c e f o o t

B

A

C

D

E

F t h r e e i n c h e e f o o t o n e a n d o l f i n c h e o t o n e i n c e f o o t t h r a r t e r s i n o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISION DATE

SYRACUSE

VA MEDICAL

CENTER

ENGINEERING

DEPARTMENT

VA ROME OUTPATIENT CLINIC, ROME, NY

06/28/2022

GENERAL PROJECT INFORMATION

100% SPRINKLERED

DWG.

U.S. Department of Veterans Affairs

B

A

C

D

E

F

528A7-23-102

ADD CHILLER AT ROME CBOC

S S

Y R

M

S M

S E n g i n e e r i n g P

R O

J E

C T

S A

C T

I V

E

P

R O

J E

C T

S

A i l l e r a t

R o m e

C

B O

C D e s i g n

P h a s e

D r a w i n g s C

A D

M e c h a n i c a l

A

M

M

E C

H d w g

OF 12

MI-701

JDMA

CONTROLS DIAGRAMS

WC-2 EVAPORATOR

WC-2 CONDENSER

COOLING TOWER CT-1 COOLING TOWER CT-2

WC-1 EVAPORATOR

WC-1 CONDENSER

CHWP-1

CHWP-2

CWP-3

CWP-4

CHW-IS0-1

CW-IS0-1

CHW-IS0-2

CW-IS0-2

CT-IS0-1

CT-IS0-2

FROM COOLING TOWER SUMP

RETURN CHW

FROM AHU'S

CHW TO AHU'S

T P

T P

T P

T

P

FT2

FT1

FT3

FT4

CHILLED WATER & CONDENSER WATER CONTROLS DIAGRAM

SCALE: NONE

CHWS

C H

W S

CHWR

CWR CWR

CHWR

C W

S

CWS CWS

CWR

C W

R

C W

R

C H

W R

NOTE: WC-1 SHALL HAVE BACNET INTERFACE.

ENTHALPY SENSORS 1 & 2:

G.E. MODEL HUMI-EN-XR-0 (OR EQUAL),

12-30 VDC POWER, 4-20 mA SIGNAL, ± 2

BTU/LB. MOUNT ON NORTH FACE OF

PENTHOUSE MECHANICAL ROOM OR

OTHER LOCATION APPROVED BY

VAMC COR.

C W

R

T

P

FE

TE

FT

CONTROLS SYMBOLS

ROOM THERMOSTAT / TRANSMITTER - WALL MOUNT

ROOM HUMIDISTAT (MOISTURE) / TRANSMITTER - WALL MOUNT

TEMPERATURE TRANSMITTER

MOISTURE (HUMIDITY) TRANSMITTER

PRESSURE TRANSMITTER

STATIC PRESSURE SENSOR

FLOW TRANSMITTER

SMOKE DETECTOR

FIRE AND SMOKE DETECTOR

PRESSURE DIFFERENTIAL TRANSMITTER

PRESSURE DIFFERENTIAL SWITCH

HAND SWITCH (HAND-OFF-AUTO SWITCH)

TEMPERATURE SWITCH, LOW (FREEZESTAT)

TEMPERATURE SWITCH, HIGH (FREEZESTAT)

LEVEL CONTROLLER

LEVEL TRANSMITTER

PRESSURE SWITCH HIGH

PRESSURE SWITCH LOW

CARBON DIOXIDE TRANSMITTER

CARBON MONOXIDE TRANSMITTER

OCCUPANCY SENSOR

LOCAL TEMPERATURE CONTROL PANEL

HVAC CONTROL PANEL

VARIABLE SPEED MOTOR CONTROLLER

FLOW SWITCH HIGH

FLOW SWITCH LOW

TEMPERATURE SENSING ELEMENT FOR TRANSMITTING

TEMPERATURE TO EMCS (PROVIDE 12 INCHES MINIMUM

LENGTH IN DUCT WHEN SPACE PERMITS.)

MOTOR STARTER

ELECTRIC OPERATED CONTROL DAMPER / OR VALVE

TEMPERATURE SENSOR

PRESSURE SENSOR

PUMP

ISOLATION VALVE

FLOW METER

TEMPERATURE ELEMENT

FLOW ELEMENT

RI

CHILLER

WC-1

CONTROLS

FA

ENABLE

CHW TEMP SETPOINT

KW, % LOAD, TONS

CHW TO AHU'S

CHW-DP

IN PENTHOUSE

MECH. ROOM

PUMP VFD S/S

VFD-0

RI

CT-1 & CT-2

FANS VFD

FA

S/S

VFD-0

TYPICAL FOR ALL FOUR PUMPS

(CWP-1, CWP-2, CHWP-3, CHWP-4)

RM-A

S/S

MER-EF-17

REFRIGERANT MONITOR

EXHAUST FAN CONTROL

SCALE: NONE

KW

TONS

RI

CHILLER

WC-2

CONTROLS

FA

ENABLE

CHW TEMP SETPOINT

RI

FA

KW

%LOAD

KW

AutoCAD SHX Text

AT

AutoCAD SHX Text

OC

AutoCAD SHX Text

SD

AutoCAD SHX Text

FSD

AutoCAD SHX Text

AT

AutoCAD SHX Text

CO2

AutoCAD SHX Text

AT

AutoCAD SHX Text

CO

AutoCAD SHX Text

HS

AutoCAD SHX Text Rh

AutoCAD SHX Text

FT

AutoCAD SHX Text

MT

AutoCAD SHX Text M

AutoCAD SHX Text

LT

AutoCAD SHX Text

LC

AutoCAD SHX Text

PT

AutoCAD SHX Text

PSH

AutoCAD SHX Text

TT

AutoCAD SHX Text T

AutoCAD SHX Text

SPS

AutoCAD SHX Text

PDT

AutoCAD SHX Text

PDS

AutoCAD SHX Text

TSL

AutoCAD SHX Text

TSH

AutoCAD SHX Text

PSL

AutoCAD SHX Text

FSH

AutoCAD SHX Text

FSL

AutoCAD SHX Text

HVAC

AutoCAD SHX Text

LTCP

AutoCAD SHX Text M

VSMC

e e i g h t h i n c e f o o t

B

A

C

D

E

F t h r e e i n c h e e f o o t o n e a n d o l f i n c h e o t o n e i n c e f o o t t h r a r t e r s i n o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISION DATE

SYRACUSE

VA MEDICAL

CENTER

ENGINEERING

DEPARTMENT

VA ROME OUTPATIENT CLINIC, ROME, NY

06/28/2022

GENERAL PROJECT INFORMATION

100% SPRINKLERED

DWG.

U.S. Department of Veterans Affairs

B

A

C

D

E

F

528A7-23-102

ADD CHILLER AT ROME CBOC

S S

Y R

M

S M

S E n g i n e e r i n g P

R O

J E

C T

S A

C T

I V

E

P

R O

J E

C T

S

A i l l e r a t

R o m e

C

B O

C D e s i g n

P h a s e

D r a w i n g s C

A D

M e c h a n i c a l

A

M

M

E C

H d w g

OF 12

MI-702

JDMA

SEQUENCE OF OPERATIONS &

CONTROL POINTS

CHILLED WATER PLANT SEQUENCE OF OPERATIONS

CHILLED WATER PLANT MODE: The Operating Engineer shall select “WINTER” or “SUMMER” mode of operation.

Selecting “WINTER” mode shall close cooling tower isolation valves CT-ISO-1 and CT-ISO-2 and allow tower makeup water to be manually isolated and towers to be drained. Selecting “SUMMER” mode shall initiate a dialogue box stating, “Ensure Tower Make-Up Water is Active and Towers are Filled”. Upon acknowledging, CT-ISO-1 and CT-ISO-2 shall be commanded to open.

SYSTEM ENABLE: If the Chilled Water Plant Mode is in “SUMMER” mode, the DELTA Control System (aka BAS) shall enable a Water-Cooled Chiller when the Outside Air Temperature is >60F (adj) and there is a request for chilled water from an Air Handling Unit. Otherwise the system shall be disabled.

CHILLER CONTROL: The chilled water system consists of two chillers, WC-1 and WC-2. Only one chiller shall operate at any time. The active chiller shall be controlled by its own internal controls to maintain the chilled water setpoint as determined by the BAS. When the system is enabled, WC-1 shall normally be the active chiller and WC-2 shall operate only if WC-1 has failed.