Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

SIGNOFF / APPROVAL NOTES

1. The facility structure capacity must be able to support the load specified on the installation drawing.

2. Electrical power source provided by the facility, position to be verified in the field.

3. Guldmann Inc. reserves the right to slightly modify the track layout if necessary without Facility approval.

This includes lowering the system to avoid ceiling objects.

4. Guldmann Inc. will not be held responsible for any damages, inconvenience, resulting from hitting any non visible conduits during our installation process of which we have not been advised.

5. Modifications of door headers by the facility.

6. Signed drawings are required prior to ordering and installation of ceiling lifts.

This signature of each drawing confirms agreement of all the conditions listed above.

7. Systems are tested at 1.5 times capacity.

550 lbs. tested at 825 lbs.; 770 lbs. tested at 1155 lbs.; 825 lbs. tested at 1238 lbs.; 1100 lbs. tested at 1650 lbs.

MY SIGNATURE BELOW VERIFIES THAT I HAVE:

Reviewed all _____ pages, with a total quantity of _____ room(s), _____ system(s) for the approbation of layout for each room and the approbation of structure for each room.

CUSTOMER

APPROVAL: _____________________________________ DATE: _______________

DATE: DRAWN BY:

ACCURATE TO 4" BASED

ON PDF CONVERSION

Albany Stratton VAMC Stratton ED

113 Holland Ave Albany NY, 12208

PROJECT ID:103177

Stratton ED

FACILITY SIGNOFF

GUL101

KCA07/26/2022

16 16 17

HOIST = 770 LBS, 1100 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 8' - 11", 9' - 0", 9' - 6''3.

ATTACHMENT TYPE = I-BEAM4.

ALL BUILD TO 1100 LBS

SPAN = 5' - 0"

ADJUST END STOPS TO AVOID BOOM5.

AFF TO DECK = 14' - 0''

Revision Schedule

Date Issued by Letter Description

EACH FIXED RAIL TO

HAVE x1 PARALLEL & x2 PERPENDICULAR

STABILIZERS

ALL JOINTS MUST HAVE x1 PARALLEL & x1

PERPENDICULAR STABILIZER

SEE SPAN CHART

S E

E S

P A

N C

H A

R T

SEE SPAN CHART

± 22°

STABILIZERS CAN BE ROTATED 180°

Fixed rail systems Fixed rail systems must be connected by Guldmann Service Team or by a qualified installer.

A Guldmann class I transformer must be used.

Installation to follow existing rules for authorized electricians and according to IEC/UL 60601-1.

Terminals on transformers Class I Double-insulated UL approved cable must be used (Cable specification: UL category: AVLV2, min.300V, min.

80° C, min. 18AWG (1 mm2 )) Transformer DK-13991 In:

Terminal 1 = N Terminal 2 = 100-115V AC Terminal 3 = 230V AC Terminal 4 = Protective ground Out:

Terminal 5 = 33V AC Terminal 6 = 33V AC

POWER TO BE WITHIN 15 FT OF END OF FIXED RAIL

Guldmann permanent mounted ceiling aluminium rail

Hoist with trolleys movable in rail

Protective Plast Enclosure

UL approved 400V cable, green, min. 14 AWG

Protective Ground

M1

UL approved 400V double isolated cable, min. 18 AWG

ON/OFF

UL approved 400V double isolated cable, min. 18 AWG

T ra n s fo rm e r

D K

-1

Main power Permanent installation Specification of breaker:

≥ 2.5 Amp capacity Line must always be broken

L1

AC/DC charger

Main Motor Control

Emergency Stop

Safety Circuit Emergency down

Motor Function Selector Switch0 1

V A

C

U S

V

A C

P ro te c tiv e G ro u nd

V A

C

V A

C1 A

T

.5

A T

Green Light ON (or ON / OFF - sign)

Licensed Electrician to perform hardwire to transformer

MAX

PROJECTION

MAX DISTANCE BETWEEN VERTICAL SUPPORTS

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

X

X

X

RAIL

RAIL

RAIL

RAIL

RAIL

RAIL

INCH

METER

,23

,7

1,2

39 49 59 68 78 118 137 147 157 177 187 206 215 236 246 264

1,0 1,25 1,5 1,75 2,0 3,0 3,5 3,75 4,0 4,5 4,75 5,25 5,5 6,0 6,25 6,75

MAX. 175 KG (385 LBS.)

MAX. 205 KG (450 LBS.)

MAX. 255 KG (560 LBS.)

MAX. 300 KG (660 LBS.)

MAX. 350 KG (770 LBS.)

MAX. 375 KG (825 LBS.)

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

A-RAIL

WEIGHT: 2.6 KG/M

(1.75 LBS/FT)

B-RAIL

WEIGHT: 5.0 KG/M

(3.36 LBS/FT)

C-RAIL

WEIGHT: 6.0 KG/M

(4.03 LBS/FT)

(2 1/2")

62 mm.

(2

/4

,5 m m

(2 1/2")

62 mm.

(5 m m

(2 1/2")

62 mm.

(6

/3 m m

A

B

C

RAIL MAX. 400 KG (880 LBS.)

X

X

X

A

B

C

RAIL MAX. 500 KG (1100 LBS.)

X

X

X

7,25

8,0

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

A

B

C

D

E

F

G

H

I

J

K

Ceiling bracket standard

A / B / C

Basic High M

Basic High M

Dimensions

205 mm

580 mm

345 mm

24 mm

58.5 / 125 / 170 mm

156 mm

184 mm

425 mm

2500 mm

970 mm

340 mm

8"

22.8"

13.5"

1.5"

2.2 / 4.9 / 6.6"

6.29"

7.2"

16.75"

98"

38"

13.3"

H

A

E D

F

C

G I

B

K J

SPRING PLATE

AVAILABLE FOR A & B RAIL

FLUSH CEILING PROFILE LIP IS 7/16" X 3/8"

CUT 12 - 15 MM OF THE 2 LONGITUDE

SCREW FOR

PROFILE END

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

Stratton ED

GEN. INFO

GUL102

KCA07/26/2022

PROJECT ID:103177

NTS

BRACING + SUPPORT

NTS

GH3 TRANSFORMER

HOIST = 770 LBS, 1100 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 8' - 11", 9' - 0", 9' - 6''3.

ATTACHMENT TYPE = I-BEAM4.

NTS

RAIL SPAN CHART

NTS

GH3 PATIENT SLING DIMS

NTS

FLUSH CEILING PROFILE

ALL BUILD TO 1100 LBS

SPAN = 5' - 0"

Revision Schedule

Date Issued by Number

ADJUST END STOPS TO AVOID BOOM5.

AFF TO DECK = 14' - 0''

DRAWINGS APPROVED FOR THE GULDMANN

GH-3 LIFTER SYSTEM STANDARD INSTALLATION

OF SUPPORT AND CONNECTION TO I - BEAM.

SYSTEMS INSTALLED FOR 1100 POUNDS WILL BE

TESTED AT 1650 POUNDS.

SYSTEMS INSTALLED FOR 770 POUNDS WILL BE

TESTED AT 1155 POUNDS.

SYSTEMS INSTALLED FOR 550 POUNDS WILL BE

TESTED AT 825 POUNDS.

I - BEAM

TAG ITEM NUMBER DESCRIPTION

10 113024 3/8" NYLOCK NUT

6,7,12

A

GULDMANN RAIL

M A

X

V A

R

IE

S

1 556241 2-7/16' X 10' BACK/BACK PG SOLID

2 HTHR037 12B7 3/8" B7 THREADED ROD

3 550439 STABILIZER BRACKET KIT - GULDMANN

4 550481-US 1" Ø-6013-T6 AL TUBE - GULDMANN

5 550435 CEILING BRACKET KIT - GULDMANN

6 377882 MQM-F WINGNUT 3/8"

7 411764 3/8" X 1-1/4" HEX BOLT

8 11101273 3/8" X 1-1/4" X 1/8" WASHER (THICK)

9 P2787 8-1/4" Beam Clamp

90º

0º

HVAC / MECH

BASEPLATE x4

STABILIZERS x3

STABILIZERS

± 22°

BRIDGE SECTION

BRIDGE / RAIL TOP

8,10

11 411752 3/8" HEX NUT

SPAN

EXISTING I-BEAM

12 370632 MQZ-L BASEPLATE 3/8"

13 377885 MQA-F SADDLE NUT 3/8"

OPTIONAL A

DETAIL A

(OPTIONAL)

40° T O 90°

B

DETAIL B

ALTERNATE STABILIZER CONNECTION

STABILIZER

P1000T

I-BEAM

P2785

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

Stratton ED

ATTACHMENT

GUL103

KCA07/26/2022

PROJECT ID:103177

HOIST = 770 LBS, 1100 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 8' - 11", 9' - 0", 9' - 6''3.

ATTACHMENT TYPE = I-BEAM4.

ALL BUILD TO 1100 LBS

SPAN = 5' - 0"

Revision Schedule

Date Issued by Number

AFF TO DECK = 14' - 0''

/8

H O

IS

T

/2

T R

A V

E R

S E

C E

IL

IN

G

GUL104

8'' MIN

/8

/2

/8

27" MAX

20" MIN

27" MAX

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

Stratton ED

PROJECT DETAILS

GUL104

KCA07/26/2022

PROJECT ID:103177

HOIST = 770 LBS, 1100 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 8' - 11", 9' - 0", 9' - 6''3.

ATTACHMENT TYPE = I-BEAM4.

Revision Schedule

Date Issued by Number

1" = 1'-0"

ELEVATION - TYPE G

1 1/2" = 1'-0"

CEILING DETAIL - TYPE G

ALL BUILD TO 1100 LBS

SPAN = 5' - 0"

ADJUST END STOPS TO AVOID BOOM5.

AFF TO DECK = 14' - 0''

3/4" = 1'-0"

CEILING - 1100 LBS TWIN HOIST

E105

GUL104

9' - 10 1/8"

8' - 2 3/8"

/8

1' - 3 5/8"

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E105

GUL105

KCA07/26/2022

PROJECT ID:103177

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

3/4" = 1'-0"

RM E105

REFERENCE ROOM (2):

E105, E106

Revision Schedule

Date Issued by Number

HOIST =770 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 0''3.

ATTACHMENT TYPE = I-BEAM4.

SPAN = 5' - 0''

E107

/8

/8

1' - 1 1/4"12' - 0"

/8

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E107

GUL106

KCA07/26/2022

PROJECT ID:103177

3/4" = 1'-0"

RM E107

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

Revision Schedule

Date Issued by Number

HOIST =770 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 0''3.

ATTACHMENT TYPE = I-BEAM4.

E108

/8

9' - 11 1/2"

/4

1"

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E108

GUL107

KCA07/26/2022

PROJECT ID:103177

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

3/4" = 1'-0"

RM E108

REFERENCE ROOM (2):

E108, E113

Revision Schedule

Date Issued by Number

HOIST =770 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 0''3.

ATTACHMENT TYPE = I-BEAM4.

E112

10 7/8" 10' - 1 3/4"

/2

10' - 8"10 7/8"

/8

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E112

GUL108

KCA07/26/2022

PROJECT ID:103177

B rail

Ceiling bracket, Extended

Ceiling bracket, Standard

Hoist

Stabilizers

KEY

Hoist Transformer

Revision Schedule

Date Issued by Number

1/2" = 1'-0"

RM E112

Trolley Cut-Out

HOIST =1100 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 0''3.

ATTACHMENT TYPE = I-BEAM4.

SPAN = 5' - 0''

B-RAIL SPAN LIMIT BETWEEN SUPPORTS IS 11' - 5" FOR 1100 LBS

E116

/8

8' - 2 3/8"

11' - 5"

3' - 9"

GUL104

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E116

GUL109

KCA07/26/2022

PROJECT ID:103177

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

3/4" = 1'-0"

RM E116

Revision Schedule

Date Issued by Number

HOIST =1100 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 0''3.

ATTACHMENT TYPE = I-BEAM4.

SPAN = 5' - 0''

B-RAIL SPAN LIMIT BETWEEN SUPPORTS IS 11' - 5" FOR 1100 LBS

E118

/8

9' - 10 1/8"

8' - 0"1' - 6 1/8"

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E118

GUL110

KCA07/26/2022

PROJECT ID:103177

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

3/4" = 1'-0"

RM E118

Revision Schedule

Date Issued by Number

HOIST =770 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 0''3.

ATTACHMENT TYPE = I-BEAM4.

E119

/8

/8

9' - 10 1/8"

8' - 0"1' - 9 1/2"

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E119

GUL111

KCA07/26/2022

PROJECT ID:103177

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

3/4" = 1'-0"

RM E119

Revision Schedule

Date Issued by Number

HOIST =770 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 0''3.

ATTACHMENT TYPE = I-BEAM4.

E121

1" 12' - 8 1/4"

/8

/8

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E121

GUL112

KCA07/26/2022

PROJECT ID:103177

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

3/4" = 1'-0"

RM E121

REFERENCE ROOM (2):

E121 - E122

Revision Schedule

Date Issued by Number

HOIST =770 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 0''3.

ATTACHMENT TYPE = I-BEAM4.

E123

12' - 7 7/8" 1"

/8

/4

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E123

GUL113

KCA07/26/2022

PROJECT ID:103177

Revision Schedule

Date Issued by Number

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

3/4" = 1'-0"

RM E123

REFERENCE ROOM (2):

E123 - E124

HOIST =770 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 6''3.

ATTACHMENT TYPE = I-BEAM4.

E125 8

12' - 8 1/8" 1"

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E125

GUL114

KCA07/26/2022

PROJECT ID:103177

3/4" = 1'-0"

RM E125

Revision Schedule

Date Issued by Number

HOIST =770 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 0''3.

ATTACHMENT TYPE = I-BEAM4.

SPAN = 5' - 0''

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

E151

12' - 11 5/8" 1"

/2

/8

/4

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

RM E151

GUL115

KCA07/26/2022

PROJECT ID:103177

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

1/2" = 1'-0"

RM E151

Revision Schedule

Date Issued by Number

HOIST =770 LBS1.

FLUSH RECESSED, TYPE G2.

CEILING HEIGHT = 9' - 6''3.

ATTACHMENT TYPE = I-BEAM4.

LMC-2

14'-6"

14'-6"

/8

16' - 7 1/4"

16' - 4 7/8"

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Stratton ED

AMBULANCE CANOPY

GUL116

KCA07/26/2022

PROJECT ID:103177

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

C rail

HOIST = 1100 LBS1.

NON-RECESSED, TYPE C2.

CEILING HEIGHT = UNKNOWN3.

ATTACHMENT TYPE = I-BEAM4.

SPAN = 5' - 0''

Revision Schedule

Date Issued by Number

AFF TO DECK = UNKNOWN

1/4" = 1'-0"

AMBULANCE CANOPY

VERIFY SYSTEM SIZE AND LOCATION IN FIELD

VERIFY CEILING AND DECK HEIGHTS

Sheets
GUL101 - FACILITY SIGNOFF
GUL102 - GEN. INFO
GUL103 - ATTACHMENT
GUL104 - PROJECT DETAILS
GUL105 - RM E105
GUL106 - RM E107
GUL107 - RM E108
GUL108 - RM E112
GUL109 - RM E116
GUL110 - RM E118
GUL111 - RM E119
GUL112 - RM E121
GUL113 - RM E123
GUL114 - RM E125
GUL115 - RM E151
GUL116 - AMBULANCE CANOPY