528A7-17-732 5A Rehab Unit - Pre-bid RFIs 2.docx
DOCX document 20 KB Posted
- Solicitation number
- 36C24221B0033
About this file
This document contains a pre-bid request for information and related federal contract opportunity for renovations to the Syracuse VA Medical Center. The project will renovate approximately 7,200 square feet of existing ward space to construct a new 14-bed inpatient rehabilitation unit meeting CARF requirements. It will also serve as a negative pressure contingency ward. Renovations will include abatement of known and unforeseen asbestos and hazardous materials, demolition, and construction of walls, electric, lighting, ceilings, floors, mechanical equipment, HVAC, plumbing, windows and other appurtenances for an inpatient rehabilitation care area. The pre-bid RFI clarifies that the fiber optic cable run is from the electrical room to the CCTV head end room, requiring a 24-port Cisco switch and single mode fiber with LC connectors. The related federal contract opportunity is solicitation number 36C24221B0033 for the renovation project, to be issued by the Department of Veterans Affairs Veterans Health Administration VISN 2 on or around April 21, 2021.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24221B0033 0004.docx | DOCX document | |
| site visit attendance sheet.pdf | ||
| 05.13.21 Pre-Bid Site Visit #2.pdf | ||
| 528A7-17-732 Renovate 5A for Rehab Unit - SOW Revised.docx | DOCX document | |
| 05.12.21 Pre-Bid Site Visit #1.pdf | ||
| 528A7-17-732 Renovate 5A for Rehab Unit - Bid Specifications REVISED.pdf | ||
| 528A7-17-732 5A Rehab Unit - Pre-bid RFIs REVISED.docx | DOCX document | |
| General Wage Decision NY20210026 21 May 2021.pdf | ||
| 36C24221B0033 0003.docx | DOCX document | |
| 36C24221B0033 0002.docx | DOCX document | |
| 36C24221B0033 0001.docx | DOCX document | |
| Y 26 1-1-21.pdf | ||
| 36C24221B0033_1.docx | DOCX document | |
| 528A7-17-732 Renovate 5A for Rehab Unit - Bid Specifications.pdf | ||
| 528A7-17-732 Renovate 5A for Rehab Unit - Bid Drawings.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
528A7-17-732 Renovate 5A for Rehabilitation Unit RFIs – Pre-Bid
1. Drawing E501 Typical #9 calls for a fiber optic cable to run from room A503 to CB4.
· What type of fiber?
· How many strands
· What type of connectors
· What type of Patch panels
VA Response: Cable run is from electrical room A503 to CCTV head end room C134 near the main entrance on the 1st floor; CB4 was a typo. Contractor shall provide a 24-port Cisco 9300 series POE switch in room A503.
Fiber (6 fiber count) and LC connectors shall be single mode (OS2) category; only one fiber cable is required from new switch in A503 to C134.
Corning Cable Systems offers Wall-Mountable Interconnect Centers, Closet Connector Housings and Panel Adapters, etc. that are currently being used at this facility as part of a camera system upgrade.