This pre-solicitation notice provides details for an upcoming solicitation to renovate 11A for USP 797/800 backup at the Stratton VA Medical Center in Albany, NY. The project involves constructing a new laboratory to serve as a backup facility for IV and chemotherapy compounding currently performed in separate labs on floors 1B and 9A. The procurement will be a 100% set-aside for Service Disabled Veteran Owned Small Businesses and have a NAICS code of 236220 with a small business size standard of $39.5 million. The estimated value of construction is between $500,000 and $1 million. The solicitation materials will be posted on beta.SAM.gov in electronic format on or around July 14, 2020. All inquiries should be directed to the point of contact Tony Clemente by phone at 518-258-5483 or email.

View the file

Other files

File Type Posted
36C24220B0052 0004.docx DOCX document
36C24220B0052 0003.docx DOCX document
36C24220B0052 0002.docx DOCX document
528A8-20-816 100_ Combined Specs 2020-07-26.pdf PDF
36C24220B0052 0001.docx DOCX document
36C24220B0052_1.docx DOCX document
DB wage determinations.pdf PDF
528A8-20-816 11A Renovate 11A for USP 797 800 Backup Combined PDF.pdf PDF
528A8-20-816 95 Per Cent Specifications.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. ALL WORK SHALL COMPLY WITH ALL APPLICABLE GOVERNMENT CODES INCLUDING BUT NOT LIMITED TO NFPA 101LIFE SAFETY CODE, IBC, OSHA, AND ADA.

2. CONTRACTOR SHALL REVIEW ALL DRAWINGS AND SPECIFICATIONS AND NOTIFY COR OF ANY DISCREPANCIES.

3. THE CONTRACTOR SHALL HOLD THE VETERANS ADMINISTRATION HARMLESS AGAINST ANY AND ALL CLAIMS ARISING FROM WORK

PERFORMED BY THE CONTRACTOR ON SITE.

4. PRIOR TO START OF WORK SUBMIT FOR COR APPROVAL A DETAILED SCHEDULE OF ALL WORK THAT MIGHT AFFECT OWNER'S USE OF

BUILDING SUCH AS UTILITY SHUT DOWN AND NOISE GENERATING WORK.

5. EXISTING FACILITY SHALL REMAIN IN OPERATION DURING THIS WORK. ENSURE SAFE PASSAGE OF ALL PERSONS AROUND WORK AREA.

ERECT 1 HOUR BARRIERS AS REQUIRED OR DIRECTED BY COR. MAINTAIN ALL REQUIRED EGRESS ROUTES. DO NOT LIMIT VA'S USE OF

FACILITY WITHOUT PRIOR APPROVAL.

6. CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL REQUIRED TO PERFORM THE WORK.

7. PROVIDE ALL MATERIALS AND PERFORM ALL WORK IN ACCORDANCE WITH RECOGNIZED GOOD STANDARD PRACTICES.

8. ALL MATERIALS SHALL BE NEW AND AS SPECIFIED OR EQUAL, AS APPROVED BY THE COR. MATERIALS SPECIFIED INDICATE QUALITY

INTENT THAT WILL BE USED AS A BASIS FOR REVIEW OF SUBSTITUTES.

9. ALL ITEMS WHICH ARE NOT SPECIFICALLY REFERRED TO ON THESE DRAWINGS, OR IN THE SPECIFICATIONS, ARE TO BE SELECTED BY THE

COR FROM THE MANUFACTURER'S STANDARD OFFERINGS SHOWING FULL RANGE OF OPTIONS.

10. FOLLOW MANUFACTURER'S SPECIFICATIONS AND INSTRUCTIONS FOR INSTALLATION OF ALL MATERIALS.

11. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. CONTRACTOR TO NOTIFY COR OF ANY DISCREPANCIES PRIOR TO

BEGINNING WORK.

12. ALL DIMENSIONS SHALL BE FIELD VERIFIED, DO NOT SCALE DRAWINGS.

13. MINOR ITEMS OF WORK SUCH AS CUTTING, BLOCKING, TRIM, ETC. SHALL BE PERFORMED AS REQUIRED TO MAKE THE WORK COMPLETE

WHETHER NOTED ON THE CONTRACT DOCUMENTS OR NOT.

14. ALL NOISY OR DISRUPTIVE WORK SHALL BE SCHEDULED IN ADVANCE WITH THE COR.

15. CONTRACTOR SHALL ASSUME THAT NONE OF THE EXISTING VALVES ARE WATER TIGHT. CONTRACTOR SHALL BE PREPARED TO FREEZE

THE AFFECTED PIPE IN ORDER TO COMPLETE THE WORK. COORDINATE WITH COR ON ANY PIPE FREEZING.

16. CONTRACTOR SHALL REMOVE AND REPLACE ANY EXISTING CEILING TO REMAIN AS NEEDED TO ACCOMPLISH WORK. THOROUGHLY CLEAN

ROOMS AND OFFICES THAT WILL BE OCCUPIED AFTER WORK IS COMPLETED. CONTRACTOR SHALL REPLACE TILES OR GRID DAMAGED AS

PART OF THIS PROJECT.

17. CONTRACTOR SHALL COMPLY WITH ALL VA REGULATIONS, LOCAL AND NATIONAL, CONCERNING ACTIONS TO BE TAKEN DURING THE

COVID-19 PANDEMIC. COR SHALL BRIEF CONTRACTOR ON REQUIRED ACTIONS.

18. BACKUP COMPOUNDING SPACE LOCATED ON THE 11TH FLOOR SHALL BE OPERATIONAL BY JANUARY 29, 2021.

CS-001 COVER SHEET

HA-001 ASBESTOS REMOVAL AND ICRA PART PLANS

AD-001 ARCHITECTURAL DEMOLITION

A-001 ARCHITECTURAL PART PLANS AND DETAILS

A-002 REFLECTED CEILING PLAN AND SECTIONS

P-001 PLUMBING / FIRE PROTECTION PART PLANS

M-001 MECHANICAL DEMOLITION

M-002 MECHANICAL NEW WORK PART PLANS

M-003 LEGEND AND CONTROLS SCHEMATIC

M-004 MECHANICAL SECTION AND DETAILS

M-005 MECHANICAL SCHEDULES AND CONTROL POINTS

E-001 ELECTRICAL DEMOLITION AND NEW PART PLANS

P

A

N

E

L

M

E

R

A

PANEL

11-237(A)

EMG

PULL

BOX

PANEL

11-47

PANEL

11-38

PANEL

11-20-E

COVER SHEET

RENOVATE 11A FOR USP

797 / 800 BACKUP

528A8-20-816

11A

17 MAR 2020

TW

CS-001

FMS DESIGN TEAM

ACRONYMS USED

DEPARTMENT OF VETERANS AFFAIRS

SAMUEL S. STRATTON

MEDICAL CENTER

ALBANY, NEW YORK

RENOVATE 11A FOR USP

797 / 800 BACKUP

PROJECT 528A8-20-816

11A KEY PLAN

7/27/2020 12:01:00 PM

AutoCAD SHX Text

VETERANS WAY

AutoCAD SHX Text

ELKS MEMORIAL DRIVE

AutoCAD SHX Text

HOLLAND AVE

AutoCAD SHX Text

MYRTLE AVE

AutoCAD SHX Text

NEW SCOTLAND AVE

AutoCAD SHX Text

SAN

AutoCAD SHX Text

EL

AutoCAD SHX Text

EL

AutoCAD SHX Text

EL

AutoCAD SHX Text

EL

AutoCAD SHX Text

EL

AutoCAD SHX Text

EL

AutoCAD SHX Text

EL

AutoCAD SHX Text

EL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EL

AutoCAD SHX Text

AutoCAD SHX Text

EL

AutoCAD SHX Text

AutoCAD SHX Text

EL

AutoCAD SHX Text

AutoCAD SHX Text

EL

AutoCAD SHX Text 14?

AutoCAD SHX Text

EL

AutoCAD SHX Text

AutoCAD SHX Text

EL

AutoCAD SHX Text 1?

AutoCAD SHX Text

FFE: 189.07'

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

CONCRETE WALKWAY

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

TEL

AutoCAD SHX Text

TEL

AutoCAD SHX Text

TEL

AutoCAD SHX Text

TEL

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text V

AutoCAD SHX Text V

AutoCAD SHX Text

THIS SPOT IS ONLY FOR RED ROAD GLIDES.

AutoCAD SHX Text

MAGNETIC

AutoCAD SHX Text

PLAN

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

LOADING

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text Approved By:

AutoCAD SHX Text O/M Manager

AutoCAD SHX Text Safety Manager

AutoCAD SHX Text Infection Control

AutoCAD SHX Text Police Chief

AutoCAD SHX Text Energy Manager

AutoCAD SHX Text GEMS Coordinator

AutoCAD SHX Text Using Activity Program Manager

AutoCAD SHX Text Interior Design

AutoCAD SHX Text Approved By VAMC Director:

AutoCAD SHX Text Engineering Manager

AutoCAD SHX Text

DRAWING LIST

ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg AutoCAD SHX Text T ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg AutoCAD SHX Text T

AutoCAD SHX Text Room

AutoCAD SHX Text Toilet

AutoCAD SHX Text 11A Existing Mechanical Room

AutoCAD SHX Text 10th Floor Roof

AutoCAD SHX Text

%%UELEVENTH FLOOR PLAN

AutoCAD SHX Text

%%UWING A

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text Approved: Engineering Manager

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

DESIGNERS:

AutoCAD SHX Text ADA: AMERICANS WITH DISABILITIES ACT AFF: ABOVE FINISHED FLOOR ELEVATION ASTM: AMERICAN SOCIETY FOR TESTING MATERIALS AWWA: AMERICAN WATER WORKS ASSOCIATION BGS: BELOW GROUND SURFACE ELEVATION BOC: BOTTOM OF CONCRETE CB: STORMWATER CATCH BASIN CL: CENTER LINE, CENTER CMU: CONCRETE MASONRY UNIT CO: CONTRACTING OFFICER COR: CONTRACTING OFFICER'S REPRESENTATIVE DIA: DIAMETER DIP: DUCTILE IRON PIPE DMH: DRAINAGE MANHOLE EQ: EQUAL EX: EXISTING FT: FOOT OR FEET GRD: GROUND HDPE: HIGH DENSITY POLYETHYLENE PIPE IAW: IN ACCORDANCE WITH ICRA: INFECTION CONTROL RISK ASSESSMENT ID: INSIDE DIAMETER MAX: MAXIMUM MIN: MINIMUM NFPA: NATIONAL FIRE PROTECTION ASSOCIATION NYS: NEW YORK STATE NYSDOT: NYS DEPT. OF TRANSPORTATION NYS DEPT. OF TRANSPORTATION NYSDEC: NYS DEPT. OF ENVIRONMENTAL CONSERVATION OC: ON CENTER OD: OUTSIDE DIAMETER PVC: POLY-VINYL CHLORIDE PIPE PSI: POUNDS PER SQUARE INCH RCP: REINFORCED CONCRETE PIPE SMH:SANITARY MANHOLE TOC: TOP OF CONCRETE TOP OF CONCRETE TYP: TYPICAL UNO: UNLESS NOTED OTHERWISE UNLESS NOTED OTHERWISE VA: VETERANS ADMINISTRATION VAMC: VETERANS ADMINISTRATION MEDICAL CENTER VA: VETERANS ADMINISTRATION VAMC: VETERANS ADMINISTRATION MEDICAL CENTER VCP: VITREOUS CLAY PIPE VIF: VERIFY IN FIELD

AutoCAD SHX Text

ALBANY MED PARKING GARAGE

AutoCAD SHX Text

LOCATION PLAN: 1:200

AutoCAD SHX Text

BLDG. 1

REMOVE CONVECTORS INCLUDING COVERS AND BACK BOX AND ALL ASBESTOS CONTAINING

INSULATION.

REMOVE STEAM AND CONDENSATE PIPING AND ASSOCIATED ASBESTOS CONTAINING PIPE AND PIPE

JOINT INSULATION. OPEN PIPE CHASE SLAB TO SLAB. DO NOT REMOVE FIREPROOFING AT COLUMN

ENCLOSURE. REMOVE PIPE INSULATION INTO SLAB PENETRATION. PACK PIPE PENETRATION FULL WITH

ROCK WOOL. REMOVE PIPE RISERS LEVEL TO DECK. CUT SLOTS IN SLAB AND INSTALL RISER HANGERS.

CAP TOP OF PIPES AIR TIGHT WITH THREADED OR WELDED SCH 80 BLACK STEEL CAPS. FIELD VERIFY

PIPE SIZES. PIPE SIZES ARE ASSUMED TO BE 1". FIELD VERIFY PIPE SIZES.

REMOVE ALL ASBESTOS CONTAINING FLOOR TILE AND MASTIC. PROTECT CEILING AND ROOMS ON

A10. PERFORM WORK ON 2ND SHIFT TO AVOID NOISE IN ROOMS BELOW. INSTALL PLASTIC SHEET ABOVE

10A CEILING BELOW WORK TO PROTECT CEILING. REMOVE SHEET AS WASTE MATERIAL PRIOR TO

DRYING.

REMOVE STEAM AND CONDENSATE PIPING AND ASSOCIATED ASBESTOS CONTAINING PIPE AND PIPE

JOINT INSULATION. OPEN PIPE CHASE SLAB TO SLAB. REMOVE PIPE INSULATION INTO SLAB

PENETRATION. PACK PIPE PENETRATION FULL WITH ROCK WOOL. REMOVE PIPE RISERS TO FIRST

ELBOW. EXTEND THE LPS AND LPC PIPES INTO ROOM TO SERVE HUMIDIFIER. CUT SLOTS IN SLAB AND

INSTALL RISER HANGERS. PROVIDE BRONZE SHUT OFF VALVES. PIPE SIZES ARE ASSUMED TO BE 1".

FIELD VERIFY PIPE SIZES.

REMOVE PIPE INSULATION. ASSUME 20 LF OF 1-1/4" PIPING. RE-INSULATE PIPE IAW SPECIFICATIONS.

REMOVE CONVECTORS INCLUDING BACK BOX AND ALL ASBESTOS CONTAINING INSULATION.

RE-INSULATE BACK BOXES WITH 1" THICK CLOSED CELL SPRAY FOAM INSULATION RATED FOR 215°

MINIMUM AND RE-INSTALL. CLEAN CONVECTORS AND REPLACE. REMOVE STEAM AND CONDENSATE

ASBESTOS CONTAINING PIPE AND PIPE JOINT INSULATION. DO NOT REMOVE FIREPROOFING AT COLUMN

ENCLOSURE. REMOVE PIPE INSULATION INTO SLAB PENETRATION. PACK PIPE PENETRATION FULL WITH

ROCK WOOL. REPLACE SHUT OFF VALVES AND CONTROL VALVE TO MATCH EXISTING. FIELD VERIFY PIPE

SIZES.

A1105

HWS

HWR

CHWR

CHWS

STEAM

LPC

PUMP COND

2'-6"

3'-0"

PANEL

11-237(A)

EMG

PULL

BOX

PANEL

11-47

PANEL

11-38

PANEL

11-20-E

A1105a A1105b A1106a A1106b A1106c

A1106e A1106d

A1106f

A1107

A1108

A1109

A1106g

6 6 66

1. ASBESTOS REMOVAL SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE, AND LOCAL LAWS, GUIDELINES, REGULATIONS, ORDERS AND

DIRECTIVES INCLUDING, WITHOUT LIMITATION, THOSE OF THE RESPONSIBLE NEW YORK STATE AGENCIES, U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA), U.S.S

DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA), AND NATIONAL INSTITUTE OF OCCUPATIONAL SAFETY AND HEALTH (NIOSH).

2. CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, FACILITIES, EQUIPMENT, SERVICES, ETC., NECESSARY TO PERFORM THE WORK REQUIRED FOR ASBESTOS

ABATEMENT IN ACCORDANCE WITH THE PROJECT MANUAL, EPA AND OSHA REGULATIONS, AND NIOSH RECOMMENDATION, NYS DEPARTMENT OF LABOR, PART 56 OF

TITLE 12 'ASBESTOS' INDUSTRIAL CODE, AND ANY OTHER APPLICABLE FEDERAL, STATE, AND LOCAL GOVERNMENT REGULATIONS.

3. CONTRACTOR SHALL DEVELOP AND IMPLEMENT A WRITTEN STANDARD PROCEDURE FOR ABATEMENT WORK TO ENSURE MAXIMUM PROTECTION AND SAFEGUARDS

FROM ASBESTOS EXPOSURE OF THE WORKER, VAMC VISITORS, VAMC EMPLOYEES, GENERAL PUBLIC, AND THE ENVIRONMENT.

4. CONTRACTOR SHALL PROVIDE SIGNS, LABELS, WARNINGS, AND POSTED INSTRUCTIONS THAT ARE NECESSARY TO PROTECT, INFORM, AND WARN PEOPLE OF THE

HAZARD FROM ASBESTOS EXPOSURE. POST IN A PROMINENT AND CONVENIENT PLACE FOR THE WORKERS AND A COPY OF THE LATEST APPLICABLE REGULATION

FROM OSHA, EPA, AND NIOSH. TEN DAYS PRIOR TO START OF ASBESTOS REMOVAL THE CONTRACTOR SHALL FURNISH TO THE STRATTON VA SAFETY OFFICE A NOTICE

CONTAINING THE ASBESTOS REMOVAL START DATE SUITABLE FOR POSTING BY SAFETY AT THE MEDICAL CENTER ENTRANCE.

5. CONTRACTOR SHALL PROVIDE ALL ELECTRICAL, WATER, AND WASTE CONNECTIONS,TIE-INS, EXTENSIONS, AND CONSTRUCTION MATERIALS, SUPPLIES, ETC., AS

REQUIRED TO COMPLETE THE ASBESTOS REMOVAL.

6. CONTRACTOR SHALL PROVIDE TEMPORARY ELECTRIC AND LIGHTING AS REQUIRED, IN ACCORDANCE WITH OSHA REGULATIONS.

7. CONTRACTOR SHALL PROTECT ALL CONTROL PANELS, ELECTRICAL PANELS, EQUIPMENT, ETC., WITHIN WORK AREAS.

8. CONTRACTOR SHALL PROVIDE ISOLATION AND PROTECTION FOR ALL UN-INSULATED AND/OR NON-ASBESTOS INSULATED MECHANICAL EQUIPMENT.

9. CONTRACTOR SHALL SEAL ALL GRILLES, VENTS, DIFFUSERS, ETC., IN EACH WORK AREA AS REQUIRED BY THE CONTRACT DOCUMENTS AND AS NECESSITATED BY

FIELD CONDITIONS.

10. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING AND/OR REPAIRING ANY EQUIPMENT, MATERIALS, INSULATION, FURNISHINGS, BUILDING STRUCTURES, ETC., DAMAGED DURING THE COURSE OF THE WORK AT NO ADDITIONAL COST TO THE VA.

11. CONTRACTOR SHALL PROVIDE AS MANY SHIFTS OF WORKERS AS WILL BE NECESSARY TO COMPLETE THE JOB IN THE AMOUNT OF TIME SPECIFIED IN THE CONTRACT

DOCUMENTS.

12. CONTRACTOR SHALL PROVIDE ALL SCAFFOLDING, EQUIPMENT, TOOLS, TRANSPORTATION EQUIPMENT, VACUUM EQUIPMENT, SPRAYERS, ETC., AS REQUIRED AND/OR

NECESSARY TO COMPLETE ALL WORK REQUIRED BY THE CONTRACT DOCUMENTS.

13. CONTRACTOR SHALL ISOLATE THE WORK AREAS AS DESCRIBED IN THE CONTRACT DOCUMENTS. ALL CRITICAL BARRIERS, DECONTAMINATION UNITS, PLASTIC

SHEETING, AIR FILTRATION DEVICES, RESPECTIVE MANIFOLDS, ETC., ARE TO BE IN PLACE AND APPROVED BY THE CONSULTANT PRIOR TO ASBESTOS REMOVAL.

14. CONTRACTOR SHALL LOCATE AND SEAL ALL PENETRATIONS THROUGH THE WORK AREAS NOT LIMITED TO PIPE, DUCT, CONDUIT, CHASES, SHAFT WAYS, AND

OPENINGS IN FIRE OR SMOKE BARRIERS OR DECKS BETWEEN FLOORS AS REQUIRED BY FIELD CONDITIONS.

15. ALL LUMBER AND POLYETHYLENE MATERIALS USED FOR THIS PROJECT ARE TO BE FIRE RESISTANT.

16. CONTRACTOR SHALL COORDINATE WITH THE VA ON SHUTDOWN OF HVAC UNITS WHICH SERVE WORK AREAS.

17. SHOWER AND WASTE WATER SHALL BE TREATED AND DISPOSED OF AS SPECIFIED.

18. CONTRACTOR SHALL PROVIDE PORTABLE CABINET MOUNTED AIR FILTRATION DEVICES (AFD) EQUIPPED WITH HEPA FILTRATION AT 99.97% EFFICIENCY TO 3 MICRONS.

THE NUMBER OF AFD'S SHALL BE IN SUCH A MANNER AS TO INSURE A MINIMUM OF FOUR (4) COMPLETE AIR CHANGES PER HOUR AND MAINTAIN A MINIMUM NEGATIVE

PRESSURE DIFFERENTIAL BETWEEN THE WORK AREA AND ADJOINING SPACE OF -0.02" W.C.

19. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY CONNECTIONS, FASTENERS, FLEXIBLE DUCT, MANIFOLD, SUPPORTING SUSPENSION, ETC., FROM AFD

UNITS TO EXHAUST LOCATIONS. INSTALLATION OF AFD'S SHALL COMPLY WITH CONSULTANT'S INSTRUCTIONS AND MANUFACTURER'S REQUIREMENTS. CONTRACTOR

SHALL COORDINATE WITH THE VA ON LOCATING WINDOW TO INSTALL EXHAUST DUCT AND METHOD OF SEALING REMAINDER OF WINDOW OPENING. MATERIAL AND

SAFING WINDOW OPENINGS ARE BY CONTRACTOR.

20. CONTRACTOR SHALL REMOVE ALL ASBESTOS-CONTAINING MATERIALS FROM EACH WORK AREA INDICATED ON THE CONTRACT DOCUMENTS. CONTRACTOR IS

RESPONSIBLE FOR THE REMOVAL OF ITEMS, SUCH AS CARPET, WALL BOARD OR PLASTER, MECHANICAL EQUIPMENT, ETC., NEEDED TO ACCESS THE

ASBESTOS-CONTAINING MATERIALS.

21. DO NOT SCALE DRAWINGS, CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE PRIOR TO SUBMISSION OF BID, AND REPORT ANY

DISCREPANCIES TO THE ENGINEER IN WRITING. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON DRAWINGS, GENERAL NOTES, AND PROJECT

SPECIFICATIONS.

22. ALL AREAS OF THIS MEDICAL CENTER WITH THE EXCEPTION OF THE DESIGNATED WORK AREAS SHALL REMAIN OCCUPIED WITH VETERANS, OTHER TRADE WORKERS, AND VA PERSONNEL THROUGHOUT THE ABATEMENT PROJECT. EXTEND EVERY REASONABLE ACCOMMODATION TO THE PERSONNEL AND COMPLY WITH ALL VA

REGULATIONS AND REQUIREMENTS.

A1105

HWS

HWR

CHWR

CHWS

STEAM

LPC

PUMP COND

2'-6"

3'-0"

PANEL

11-237(A)

EMG

PULL

BOX

PANEL

11-47

PANEL

11-38

PANEL

11-20-E

A1105a A1105b A1106a A1106b A1106c

A1106e A1106d

A1106f

A1107

A1108

A1109

A1106g

WALK OFF MATS. PEEL

OFF TOP LAYER WHEN

VISIBLY SOILED. (TYP)

PROVIDE 1 HOUR RATED

ENCLOSURE, 1 LAYER OF

5/8" TYPE "X" MMR

GYPSUM TAPED AND

SEALED BOTH SIDES TO

PROVIDE RATING.

INSTALL SLAB TO SLAB.

REPAIR CORRIDOR WALL

TO MATCH EXISTING

WHEN ENCLOSURE IS

REMOVED.

ELECTRONIC PRESSURE

SENSOR TO VERIFY -0.02"

W.C. IN AREA.

PROVIDE 3/4 HOUR RATED DOOR.

PROVIDE CYPHER LOCK, VA WILL

PROVIDE BEST CORE. (TYP 2)

HEPA FILTERED

EXHAUST FAN.

OPERATE

CONTINUOUSLY TO

MAINTAIN -0.02" W.C. IN

AREA DURING

CONSTRUCTION.

7/27/2020 12:02:55 PM

AutoCAD SHX Text

CODED NOTES

AutoCAD SHX Text Toilet

AutoCAD SHX Text

AutoCAD SHX Text

SCALE: 1/4"=1'-0"

AutoCAD SHX Text

ASBESTOS REMOVAL PART PLAN

AutoCAD SHX Text

ASBESTOS ABATEMENT GENERAL NOTES

AutoCAD SHX Text Toilet

AutoCAD SHX Text

SCALE: 1/4"=1'-0"

AutoCAD SHX Text

11A ICRA PART PLAN

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text Stratton VA Medical Center Albany, NY

AutoCAD SHX Text 528A8-20-816

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text Approved By Signatures date

AutoCAD SHX Text O/M Manager

AutoCAD SHX Text Interior Design

AutoCAD SHX Text Infection Control

AutoCAD SHX Text VA Police

AutoCAD SHX Text Information Systems

AutoCAD SHX Text Fire Safety Officer

AutoCAD SHX Text Environmental Services

AutoCAD SHX Text Care Service Line Supervisor

AutoCAD SHX Text Energy Manager

AutoCAD SHX Text GEMS Coordinator

AutoCAD SHX Text Industrial Hygentist

AutoCAD SHX Text Using Activity Program Manager

AutoCAD SHX Text Approved: FMS Manager date

AutoCAD SHX Text Approved: Project Section Manager date

AutoCAD SHX Text

RENOVATE 11A FOR USP

AutoCAD SHX Text

17 MAR 2020

AutoCAD SHX Text

FAW

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS REMOVAL AND ICRA PART PLANS

AutoCAD SHX Text

797 / 800 BACKUP

AutoCAD SHX Text

HA-001

AutoCAD SHX Text

REMOVE CEILING TILES, GRIDS, SUPPORTS, DECK INSERTS, AND CEILING APPURTENANCES. REMOVE

CEILING SOFFIT IN A1105B.

REMOVE CEILING AS NEEDED FOR CONSTRUCTION. TRIM TILES AND INSTALL GRID, SUPPORTS, ETC.

NEEDED TO INSTALL A COMPLETE CEILING SYSTEM ON THE CORRIDOR SIDE OF THE CONSTRUCTION

WALL.

REMOVE WALLS INCLUDING TOP AND BOTTOM TRACKS AND DOORS AS SHOWN. PLEASE NOTE THAT

SOME WALLS MAY BE PLASTER.

REPLACE EXISTING WOODEN RAMP. PROVIDE CHROME PLATED STEEL RAMP WITH DIAMOND TREAD.

FIELD MEASURE RAMP. SUBMIT RAMP DIMENSIONS AND TECHNICAL DATA FOR COR REVIEW. LAG RAMP

TO MER WALL WITH (4)

"X 4" STAINLESS STEEL BOLTS. RAMP SHALL BE RATED TO SUPPORT 2,000#.

WALLS AND TREAD SHALL BE MINIMUM

" THICK PLATE STEEL. PROVIDE CONTINUOUS WELD ON ALL

JOINTS GROUND SMOOTH. REVISE CONSTRUCTION DOOR AS NEEDED TO ACCOMMODATE RAMP.

REPLACE EXISTING DOOR TO MER-A WITH METAL DOOR WITH 2 HOUR RATING. PROVIDE NEW LOCKSET

SUITABLE FOR BEST 7 PIN CORE. CORE BY VA. FIELD MEASURE DOOR FRAME PRIOR TO ORDERING.

REMOVE VCT TILE AND MASTIC. GRIND ANY HIGH POINTS IN CONCRETE SLAB. INSTALL LEVELING

COMPOUND FOR ENTIRE AREA TO PREPARE FOR EPOXY FLOOR SYSTEM.

REMOVE PLANK FLOORING, ROPPE VINYL PLANK. GRIND ANY HIGH POINTS. INSTALL LEVELING

COMPOUND FOR ENTIRE AREA TO PREPARE FOR EPOXY FLOOR SYSTEM. NOTE THAT NOT ALL AREAS

WILL RECEIVE EPOXY FLOORING.

REMOVE WING WALL. SEAL CORRIDOR WALL TO MATCH EXISTING. PROVIDE CORNER GUARD. PROVIDE

COVE BASE AS NEEDED TO MATCH EXISTING. PAINT TO MATCH EXISTING.

REMOVE STAINLESS STEEL COVERS AND CAULKING ON CONVECTOR GRILLES. CLEAN COVER AND

CONVECTOR. VERIFY OPERATION OF CONVECTOR.

A1105

HWS

HWR

CHWR

CHWS

STEAM

LPC

PUMP COND

2'-6"

3'-0"

PANEL

11-237(A)

EMG

PULL

BOX

PANEL

11-47

PANEL

11-38

PANEL

11-20-E

A1105a A1105b A1106a A1106b A1106c

A1106e A1106d

A1106f

A1107

A1108

A1109

A1106g

A1105

HWS

HWR

CHWR

CHWS

STEAM

LPC

PUMP COND

2'-6"

3'-0"

PANEL

11-237(A)

EMG

PULL

BOX

PANEL

11-47

PANEL

11-38

PANEL

11-20-E

A1105a A1105b A1106a A1106b A1106c

A1106e A1106d

A1106f

A1107

A1108

A1109

A1106g

7/27/2020 10:26:04 PM

AutoCAD SHX Text

CODED NOTES

AutoCAD SHX Text Toilet

AutoCAD SHX Text

AutoCAD SHX Text Toilet

AutoCAD SHX Text

AutoCAD SHX Text

SCALE: 1/4"=1'-0"

AutoCAD SHX Text

CEILING DEMOLITION

AutoCAD SHX Text

SCALE: 1/4"=1'-0"

AutoCAD SHX Text

WALL AND FLOOR DEMOLITION

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text Stratton VA Medical Center Albany, NY

AutoCAD SHX Text 528A8-20-816

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text Approved By Signatures date

AutoCAD SHX Text O/M Manager

AutoCAD SHX Text Interior Design

AutoCAD SHX Text Infection Control

AutoCAD SHX Text VA Police

AutoCAD SHX Text Information Systems

AutoCAD SHX Text Fire Safety Officer

AutoCAD SHX Text Environmental Services

AutoCAD SHX Text Care Service Line Supervisor

AutoCAD SHX Text Energy Manager

AutoCAD SHX Text GEMS Coordinator

AutoCAD SHX Text Industrial Hygentist

AutoCAD SHX Text Using Activity Program Manager

AutoCAD SHX Text Approved: FMS Manager date

AutoCAD SHX Text Approved: Project Section Manager date

AutoCAD SHX Text

17 MAR 2020

AutoCAD SHX Text

FAW

AutoCAD SHX Text

AutoCAD SHX Text

ARCHITECTURAL DEMOLITION

AutoCAD SHX Text

AD-001

AutoCAD SHX Text

RENOVATE 11A FOR USP 797 / 800 BACKUP

AutoCAD SHX Text

REFRIGERATOR

REFRIGERATOR

4' BIOLOGICAL

SAFETY CABINET

4' POSITIVE

PRESSURE HOOD

PHONE

5'-0"

HWS

HWR

CHWR

CHWS

STEAM

LPC

PUMP COND

5" STORM CONDUCTOR

FIELD VERIFY EXACT

LOCATION

AD

REFRIGERATOR

A1105a

A1105b

A1105c

A1106b

A1106c

A1106f

A1107 A1108

A1106a

A1106g

B

B

C

9"

3 4

1 2

11'-6"

21'-10

1'-8

1'-7

1 4

11'-6"

9'-10

1'-8

3'-7"

1'-5

8'-3"

9'-11

1 2

5'-1

1 4

1 2

1 2

1 2

1 2

7'-5

7'-9

6"

1 2

3 4

6'-11

11'

9'-0

3 4

11'-5

5'-10

1 4

3'-7

1 2

1 2

PROVIDE 12"X48" ACCESS

DOOR TO INSPECT

STORM CONDUCTOR

WITH BEST 7 PIN CORE.

COORDINATE DOOR

LOCATION WITH RAMP.

A6

A6

A6

A6

A6

A6

A4

A4

A4

A4

A4

A4

A4

A4

A4

A4

A-001

A6

A4

A-002

A-002

EXISTING CONCRETE SLAB.

CONTINUOUS GYPSUM COMPOUND

SEALING TRACK TO SLAB, TYPICAL

BOTH SIDES.

1 LAYER OF 5/8" TYPE "X" MMR GYPSUM

WALLBOARD EACH SIDE. PROVIDE

LEVEL 4 FINISH.

NOTE: PROVIDE CONTINUOUS BEAD OF

ACOUSTICAL SEALANT AROUND

PERIMETER OF WALL. INTENT IS TO

PROVIDE AN AIR TIGHT ENVELOPE TO

SERVE THE C-SEC AND BUFFER ROOMS

SLOTTED DEFLECTION TRACK

ATTACHED TO UNDERSIDE OF DECK.

SEAL TOP OF GYPSUM WITH 2 LAYERS

OF 100% SILICONE CAULK ON INTERIOR

WALL FOR AIR TIGHT SEAL. PROVIDE

INTUMESCENT CAULK TO SEAL

CORRIDOR SIDE.

METAL 6" (A6) OR 3-5/8" (A4) FRAMING

STUD, 18 GAUGE, 16" O.C., WITH 6" OR

4" ACOUSTICAL BATT. ATTACH STUDS

TO TOP AND BOTTOM TRACKS WITH

SCREWS ON BOTH SIDES OF STUDS.

PROVIDE BLOCKING TO SERVE

CABINETS WHERE NEEDED.

REFER TO FLOOR DETAIL FOR

SEALING WALL AT SLAB.

PANEL

11-237(A)

EMG

PULL

BOX

PANEL

11-47

PHONE

PANEL

11-38

PANEL

11-20-E

AD

A1105a

A1105b

A1105c

A1106b

A1106c

A1106f

A1107 A1108

A1106a

A1106g

PROVIDE (2) INSULATED AND

GASKETED 1 HOUR RATED ACCESS

DOORS, 28X36, FOR COIL PULL SPACE

ON EACH SIDE OF WALL. PROVIDE

LOCKED DOOR ON OFFICE SIDE, BEST

7 PIN CORES. COORDINATE EXACT

LOCATION WITH AHU.

PROVIDE 14"W x 18"H TEMPERED GLASS FRAMELESS

DOUBLE PANED LITE. LOCATE BOTTOM OF LITE AT 4'-8"

AFF. TERRA UNIVERSAL MODEL 6603-30-0906 OR

EQUAL. INTENT IS TO HAVE NO DUST GATHERING

FRAME IN BUFFER ROOM.

PROVIDE FM APPROVED

CLASS A RATED SMOOTH

FRP WALL COVERING,

CRANE GLASBORD FSFM

OR EQUAL. INSTALL

CEILING TO SLAB AND

IAW MANUFACTURER'S

INSTRUCTIONS.

PROVIDE STAINLESS STEEL

CORNER GUARDS ON ALL

OUTSIDE CORNERS, FULL

HEIGHT. PROVIDE

PAWLING CG-500 OR

EQUAL. INSTALL IAW

MANUFACTURES

DIRECTIONS. INSTALL

FLUSH BEAD OF 100%

CLEAR SILICONE BETWEEN

GUARD AND WALL.

NUMBER DENOTES

FLOOR TYPE (TYP).

ALIGN

PHARMACY OFFICE

A1105a

MECH ROOM

A1105b

RX SUPPLY & DRUG STORAGE

A1105c

ONCOLOGY BUFFER RM

A1106b

IV BUFFER RM

A1106c

ANTE ROOM

A1106a

MECH RM MER A

A1106g

LOCATION OF ROOM

SIGNS (TYP)

WALL MIRROR. COORDINATE

WITH COR ON SIZE AND

INSTALLATION.

EXISTING CONCRETE SLAB.

CONTINUOUS GYPSUM COMPOUND

SEALING TRACK TO SLAB, TYPICAL

BOTH SIDES.

1 LAYER OF 5/8" TYPE "X" MMR GYPSUM

WALLBOARD. INSTALL SMOOTH FRP

COMPOSITE PANELS, FM APROVED AND

CLASS A FIRE RATED, CRANE FSFM OR

EQUAL. INSTALL IAW MANUFACTURERS

INSTRUCTIONS.

NOTE: PROVIDE CONTINUOUS BEAD OF

ACOUSTICAL SEALANT AROUND

PERIMETER OF WALL. INTENT IS TO

PROVIDE AN AIR TIGHT ENVELOPE TO

SERVE THE ANTE AND BUFFER ROOMS

SLOTTED DEFLECTION TRACK

ATTACHED TO UNDERSIDE OF DECK.

SEAL TOP OF GYPSUM WITH 2 LAYERS

OF 100% SILICONE CAULK ON INTERIOR

WALL FOR AIR TIGHT SEAL.

METAL 2-1/2" FRAMING STUD, 20

GAUGE, 16" O.C., WITH 2-1/2"

ACOUSTICAL BATT. ATTACH STUDS TO

TOP AND BOTTOM TRACKS WITH

SCREWS ON BOTH SIDES OF STUDS.

EXISTING PLASTER AND LATH WALL.

SEAL ALL PENETRATIONS WITH

MORTAR AND ACOUSTICAL SEALANT.

REFER TO FLOOR DETAIL FOR

SEALING WALL AT SLAB.

3-5/8" STUD SHAFT WALL ASSEMBLY.

INFILL WITH 3-1/2" FACED BATT

INSULATION. FACING TO WARM SIDE.

PROVIDE AND ATTACH STUDS TO TOP

SLOTTED TRACK AND BOTTOM TRACK.

1" SHAFT WALL

2 LAYERS OF 5/8" TYPE "X" MMR GYPSUM

WALLBOARD. PROVIDE LEVEL 4 FINISH.

PRIME AND PAINT AS SPECIFIED. FINISH

WITH SMOOTH FRP COMPOSITE PANEL,

FM APPROVED AND CLASS A FIRE RATED,

CRANE FSFM OR EQUAL.

EXISTING EXTERIOR WALL

PROVIDE OPENINGS IN EXISTING

WINDOW HEAD SOFFIT TO ALLOW

AIR CIRCULATION BETWEEN

SHAFT WALL AND EXISTING

WINDOW.

REMOVE EXISTING GLASS PANES

FROM WINDOWS. REPLACE WITH

INSULATED ALUMINUM FACED

UNITS, LAMINATOR' S INC.

THERMOLITE PANEL. FIELD

VERIFY THICKNESS. UNITS SHALL

MATCH OWNER'S EXISTING UNITS.

SEAL AIR AND WATER TIGHT IAW

MANUFACTURER'S INSTRUCTIONS.

NOTE: PROVIDE CONTINUOUS BEAD OF

ACOUSTICAL SEALANT AROUND

PERIMETER OF WALL. INTENT IS TO

PROVIDE AN AIR TIGHT ENVELOPE TO

SERVE THE ANTE AND BUFFER ROOMS

EXISTING EXTERIOR WALL

REMOVE WINDOW AND HAND OVER TO VA. REPLACE WITH EXTRUDED

ALUMINUM LOUVER WITH J TYPE BLADE, 4" DEEP, 48"HX44"W, AMERICAN

WARMING AND VENTILATING MODEL LE49 OR EQUAL. PROVIDE ALUMINUM

BIRD SCREEN, KYNAR FINISH-ALUMINUM TO MATCH WINDOW FRAMES, AND

EXTENDED SILL TO COVER STONE SIMILAR TO WINDOWS. FILED MEASURE

EXACT OPENING SIZE.

PROVIDE PRESSURE TREATED, FIRE RATED WOOD BLOCKING AS NEEDED.

SEAL WITH BACKER ROD AND 2 LAYERS OF EXTERIOR GRADE SEALANT, TOP

AND BOTTOM. INSTALL STEEL ANGEL BOLTED TO MASONFY HEAD AND

ATTACHE LOUVER TO ANGLE.

EXISTING STONE SILL

STEEL ANGLE ATTACHED TO SILL AND LOUVER

INFILL CONVECTOR CAVITY WITH 3-5/8" STUDS @ 16" O.C. INSTALL 3" BATT

INSULATION WITH VAPOR BARRIER, 1" RIGID INSULATION WITH VAPOR

BARRIERS, AND

" THICK TYPE "X" MMR GYPSUM SEALED TO WALL. (TYP)

ALUMINUM DRIP EDGE

1. EPOXY FLOOR RES-6. PROVIDE SMOOTH FINISH FOR EASE OF CLEANING.

EXAMINE EXISTING FLOOR FOR SUITABILITY OF INSTALLING EPOXY FLOORING

SYSTEM. GRIND AND LEVEL FLOOR AS NEEDED. PROVIDE STAINLESS STEEL

THRESHOLD BETWEEN EPOXY AND DISSIMILAR FLOOR TYPES.

2. LUXURY VINYL TILE (LVT): VA STANDARD IS ARMSTRONG EARTHCUTS IN

VERONA WARM SUN, 18"x18"x1/8" THICK WITH 20MIL. WEAR LAYER. LOOSE

LAY INSTALLATION IS NOT ACCEPTABLE. NO SUBSTITUTIONS.

3. EXISTING FLOORING TO REMAIN. CONTRACTOR SHALL REVISE EXISTING

FLOORING AS NEEDED TO PROVIDE A HOMOGENEOUS CORRIDOR FLOOR

USING THE SAME TYPE OF FLOORING AND METHOD OF INSTALLATION.

4. PREPARE FLOOR & EXTEND EXISTING ROPPE FLOORING UNDER NEW RAMP.

PAINT ALL NEW AND EXISTING WALLS DECK TO DECK, IN A1105c, A1106a, A1106b, and A1106c AND ALL NEW GYPSUM

CEILINGS. PROVIDE SANIGLAZE HIGH BUILD WALL SYSTEM BY SHERWIN WILLIAMS. PROVIDE TWO PRIMER COATS, TWO BASE COATS, AND TWO FINISH COATS. COLOR WILL BE WHITE. INSTALL IN ACCORDANCE WITH

MANUFACTURER'S INSTRUCTIONS INCLUDING TEMPERATURE, HUMIDITY, AND DRYING TIME. MIX EPOXY ON SITE.

FINISH COATS NOT REQUIRED ON WALLS WITH FRP WALL COVERING.

PAINT ALL NEW AND EXISTING WALLS IN ROOMS A1105a, A1105b, AND ALL NEW CORRIDOR WALLS SLAB TO SLAB WITH

ONE COAT OF PRIMER AND TWO FINISH COATS, BENJAMIN MOORE ECO-SPEC WB PRIMER AND PAINT, EGGSHELL.

DOOR FRAMES SHALL BE DIRECT TO METAL SEMI-GLOSS. PROVIDE 4" COVE BASE, TYPE TS WITH TOE, ROPPE

PINNACLE OR EQUAL. COLORS TO BE SELECTED BY VA.

PROVIDE STAINLESS STEEL METAL CORNER GUARDS RECESSED INTO GYPSUM ON ALL NEW OUTSIDE CORNERS.

INSTALL VA APPROVED RED TAPE AS A DEMARCATION LINE ON FLOOR AND TO INDICATE FLOOR SWINGS.

GYPSUM WALL WITH SANIGLAZE HIGH BUILD WALL SYSTEM.

FEATHER EPOXY FILL AGAINST DRYWALL. INSTALL IAW

MANUFACTURER'S INSTRUCTIONS. PROVIDE 4" HIGH COVE

BASE WITH

" RADIUS COVE.

WHITE RESINOUS URETHANE AND EPOXY MORTAR FLOORING

SYSTEM (RES-6) WITH ORANGE PEEL FINISH.

4"

BIOLOGICAL SAFETY CABINET, BAKER STERILGARD 404E, FURNISHED BY OWNER, INSTALLED BY

CONTRACTOR INCLUDING RECEIVING AND INSPECTING ON SITE AND TRANSPORTING TO ONCOLOGY

BUFFER ROOM.

BIOLOGICAL SAFETY CABINET, BAKER EDGEGARD MODEL EG-4320, FURNISHED BY OWNER, INSTALLED BY

CONTRACTOR INCLUDING RECEIVING AND INSPECTING ON SITE AND TRANSPORTING TO IV BUFFER

ROOM.

REFRIGERATOR SUPPLIED BY OWNER, TRANSPORTED FROM LOADING DOCK AND INSTALLED BY

CONTRACTOR.

PROVIDE 14 GAUGE 304L STAINLESS STEEL SHELF ABOVE REFRIGERATORS, 14 GAUGE WITH #4 POLISH, 5'-8-1/2" (WIDE), 5'-5-3/8" (NARROW) x 2'-4" DEEP. TOP OF SHELF AT 36" AFF. FIELD MEASURE EXACT

DIMENSIONS. PROVIDE BLOCKING IN WALL TO SUPPORT SHELF. PROVIDE 1-1/2"x1/2" CAPPED STAINLESS

STEEL TUBE WELDED INTO A LEVEL FRAME AND ATTACHED TO BLOCKING WITH STAINLESS STEEL

SCREWS. INCLUDE TUBE WELDED IN MIDDLE OF FRAME LONG DIMENSION. PROVIDE 1/8" DEEP

DEPRESSION FOR ALL OF SHELF STARTING AT 3/4" FROM EDGES. SEAL EDGES AT WALLS WITH CLEAR

SILICONE CAULK.

PROVIDE NEW 42"W x 85.5"H x DOOR, LH SWING, MASONITE-MARSHFIELD ROTATY WHITE BIRCH, CARAMEL

COLOR AND NEW WELDED METAL BUCK WITH 4" HOSPITAL STOPS. PAINT BUCK TO MATCH NEARBY

DOORS WITH DIRECT TO METAL SEMI-GLOSS PAINT. INSTALL DARK BROWN KYDEX KICKPLATE, 24"H x

42"W , 0.125" THICK MECHANICALLY ATTACHED EVERY 4" TO BOTH SIDES OF DOOR. PROVIDE PEEPHOLE

CENTERED AT 60" AFF. BOTH DOOR AND BUCK SHALL BE REINFORCED FOR A CLOSER. PROVIDE (5)

5"x4-1/4" KNUCKLE BALL BEARING HINGES WITH MIDDLE HINGE WIRED. PROVIDE STANLEY LOCKSET

45HW7TDEU15S626LHIDHAM, PROXIMITY READER HID PRODUCTS MODEL 921PHRNEK0026Z. COORDINATE

WITH OPEN SYSTEM INTEGRATORS TO CONFIGURE PROXIMITY READER ON VA NETWORK. MOUNT

CONCAVE DOOR STOP ON WALL CENTERED ON LOCK CYLINDER.

PROVIDE NEW 42"W x 85.5"H x DOOR, LH SWING, MASONITE-MARSHFIELD ROTATY WHITE BIRCH, CARAMEL

COLOR AND NEW WELDED METAL BUCK. PAINT BUCK TO MATCH NEARBY DOORS WITH DIRECT TO METAL

SEMI-GLOSS PAINT. INSTALL DARK BROWN KYDEX KICKPLATE, 24"H x 42"W , 0.125" THICK MECHANICALLY

ATTACHED EVERY 4" TO BOTH SIDES OF DOOR. BOTH DOOR AND BUCK SHALL BE REINFORCED FOR A

CLOSER. PROVIDE (5) 5"x4-1/4" KNUCKLE BALL BEARING HINGES. PROVIDE STANLEY LOCKSET

45HW7TDEU15S626LHIDHAM, PROXIMITY READER HID PRODUCTS MODEL 921PHRNEK0026Z. MOUNT

CONCAVE DOOR STOP ON WALL CENTERED ON LOCK CYLINDER.

PROVIDE NEW 36"W x 85.5"H STAINLESS STEEL DOOR WITH 24"x24" LITE WITH MOTION SENSOR, STANLEY

MAGIC FORCE OR EQUAL. LITE TO BE FLUSH ON BOTH SIDES TO AVOID DUST COLLECTION. PROVIDE

REMOVABLE GASKET ON DOOR THAT CAN BE EASILY CLEANED. PROVIDE (5) 5"x4-1/4" KNUCKLE BALL

BEARING HINGES. PROVIDE DOOR CUT OUT FOR OPENING ON INSIDE OF DOOR FOR EMERGENCY

OPERATION. BUFFER AND ANTE ROOM OPENERS TO BE INTERLOCKED SO THAT ONLY ONE DOOR CAN

NORMALLY BE OPEN AT ANY TIME. DOORS SHALL BE ABLE TO BE PUSHED OPEN FOR EMERGENCY

OPERATION.

7/27/2020 10:27:57 PM

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

FRAMING DETAIL - TYPE A6 AND A4 WALL

AutoCAD SHX Text

SCALE: 1/4"=1'-0"

AutoCAD SHX Text

ARCHITECTURAL PLAN

AutoCAD SHX Text

SCALE: 1/4"=1'-0"

AutoCAD SHX Text

ARCHITECTURAL FLOOR PLAN

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

FRAMING DETAIL - TYPE B WALL

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

FRAMING DETAIL - C

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

SECTION 1 - AT LOUVER AND CONVECTOR

AutoCAD SHX Text

FLOOR TYPE

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

EPOXY COVE BASE DETAIL

AutoCAD SHX Text

CODED NOTES

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text Stratton VA Medical Center Albany, NY

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text Approved By Signatures date

AutoCAD SHX Text O/M Manager

AutoCAD SHX Text Interior Design

AutoCAD SHX Text Infection Control

AutoCAD SHX Text VA Police

AutoCAD SHX Text Information Systems

AutoCAD SHX Text Fire Safety Officer

AutoCAD SHX Text Environmental Services

AutoCAD SHX Text Care Service Line Supervisor

AutoCAD SHX Text Energy Manager

AutoCAD SHX Text GEMS Coordinator

AutoCAD SHX Text Industrial Hygentist

AutoCAD SHX Text Using Activity Program Manager

AutoCAD SHX Text Approved: FMS Manager date

AutoCAD SHX Text Approved: Project Section Manager date

AutoCAD SHX Text

FAW

AutoCAD SHX Text

AutoCAD SHX Text

ARCHITECTURAL PART PLANS AND DETAILS

AutoCAD SHX Text 528A8-20-816

AutoCAD SHX Text

17 MAR 2020

AutoCAD SHX Text A-001

AutoCAD SHX Text

RENOVATE 11A FOR USP 797 / 800 BACKUP

AutoCAD SHX Text

11-237(A)

EMG

PULL

BOX

PANEL

11-47

USP 800

BUFFER ROOM

USP 797

BUFFER ROOM

ANTE ROOM

REFRIGERATOR

REFRIGERATOR

4' BIOLOGICAL

SAFETY CABINET

4' POSITIVE

PRESSURE HOOD

BOOTIE

SUPPLY

CART

C

A

R

T

B E

N C

H

WORK STATION

TRASH

HAND

PHONE

DRUG STORAGE

ROLLING

CART

GLOVE

STATION

FUTURE

PC

FUTURE

PC

PHONE

PHONE

HAND

STORAGE

HAND

HAND

STORAGE

HAND

STORAGE

CLEAN

SIDE

DIRTY

SIDE

5'-0"

PANEL

11-38

PANEL

11-20-E

HWS

HWR

CHWR

CHWS

STEAM

LPC

PUMP COND

CART

5" STORM CONDUCTOR

FIELD VERIFY EXACT

LOCATION

S T

O R

A G

E

AD

S U

P P

L I E

S

S U

P P

L I E

S

REFRIGERATOR

A1105 A1105a

A1105b

A1105c

A1106b

A1106c

A1106e A1106d

A1106f

A1107 A1108

A1109

Stair

A1106a

A1106g

8'-8" ACT CEILING

NO CEILING

8'-0" ACT CEILING

8'-0" GYPSUM

CEILING

8'-0" GYPSUM

CEILING

8'-0" GYPSUM

CEILING

9'-0" GYPSUM

CEILING

8'-0" ACT CEILING

8'-8" GYPSUM SOFFIT

ACT CEILING: PROVIDE

ARMSTRONG PRELUDE XL 15/16"

GRID WITH 2'X2' ARMSTRONG

1728 FINE FISSURED CEILING

TILES. THIS CEILING IS VA

STANDARD. NO SUBSTITUTIONS.

WORK ROOM CEILING: PROVIDE

ARMSTRONG CLEAN ROOM VL

868 SMOOTH TEXTURE 2'X2'

TILES. PROVIDE ARMSTRONG

PRELUDE PLUS XL ALUMINUM

15/16" GRID. NO SUBSTITUTIONS.

5'-6"

PLAN VIEW OF STAINLESS STEEL COUNTERTOP, SB-6625, WITH 4" BACKSPLASH

ON 3 SIDES, HELIARC WELDED CONSTRUCTION, 16 GAUGE T304 STAINLESS

STEEL WITH #4 POLISH, HAT UNDERSIDE CHANNEL STIFFENERS, WELDS GROUND

AND POLISHED, FLAT PERIMETER EDGE WITH CLEAR SILICONE SEAL BETWEEN

PERIMETER AND WALLS. PROVIDE INTEGRAL SINK AND PENETRATIONS AS

SHOWN. (CONSTRUCTION TYPICAL FOR ALL COUNTERTOPS)

CABINET AND COUNTERTOP INDICATION. BASIS OF DESIGN IS TBJ

INCORPORATED. PROVIDE STAINLESS STEEL GAUGES EQUAL TO OR BETTER

THAN BASIS OF DESIGN. OPEN WALLS AND INSTALL BLOCKING AS NEEDED TO

SUPPORT WALL CABINETS. REPAIR WALLS TO MATCH EXISTING.

8"

7-1/2"

19"

16"

4"

10-1/2"

SB-6625

2'-1"

S-122-18S-181-48

PROVIDE OPENING FOR EYE WASH.

SCALE:

" = 1'-0"

SB-6625 PLAN VIEW

PROVIDE SOFFIT SIZED TO CLOSE OFF TOP OF CABINET.

CONSTRUCT FROM

" GYPSUM AND 3-5/8" METAL STUDS.

SEAL SOFFIT TO WALLS AND CEILING AS DEPICTED ON

WALL TYPE DETAIL FOR AIR TIGHT ROOM. PROVIDE

BLOCKING IN WALL AS NEEDED TO SUPPORT WALL

CABINETS.

8' GYPSUM CEILING

A1106b

11A CORRIDOR

BUFFER ROOM DOOR OPENER. LOCATE DOOR OPENERS FOR

BOTH BUFFER ROOMS IN ANTE ROOM. LOCATE ANTE ROOM

DOOR OPENER IN OFFICE SPACE. ALL OPENERS SHALL BE

TOUCHLESS AND SHALL BE INTERCONNECTED SO THAT ONLY

ONE OF THE THREE DOORS IS OPEN AT ANY TIME.

5'-9 1/2"

P265-3012 P265-3012

PROVIDE 24 GAUGE 304 STAINLESS STEEL WALL

COVERING SHEET WITH #4 POLISH AS SHOWN. SEAL

BETWEEN SS SHEET AND BACKSPLASH AND WALLS

WITH 100% CLEAR SILICONE CAULK WITH CONCAVE

SEAL.

SEAL BETWEEN WALLS AND COUNTERTOP WITH CLEAR

SILICONE CAULK.

GFI OUTLET AT 46" AFF.

TOUCHLESS MOTION SENSOR

WIRED TO CONTROLLERS.

LOCATE CONTROLLERS

ABOVE WORK ROOM CEILING.

CLEAN AND SEAL ALL BACK

BOXES AND WALL

PENETRATIONS.

SOAP DISPENSER

BY OWNER

DIMMING LIGHT SWITCH

SERVING BUFFER ROOM.

1/2" UNDERCUT.

PROVIDE 3 ANALOG

MAGNAHELIC PRESSURE

GAUGES WITH SEPERATE

TUBING SERVING THE

BUFFER ROOMS AND ANTE

ROOM

S245-3016

SCALE:

" = 1'-0"

UNDER CABINET LED DIMMABLE 2'

LONG LIGHT FIXTURES, 20 GA 304

BRUSHED STAINLESS STEEL HOUSING

WITH SMOOTH SOFT WHITE ACRYLIC

LENS, 120V, 3500K, 90 CRI, 0-10V

DIMMING, ELECTRONIC DRIVER, 750

LUMENS PER FOOT, IP63 RATED,

EATON ULC OR EQUAL. SEAL CONDUIT

CONNECTION IN BACK OF FIXTURE.

(TYP 5)

S124-30

S245-3016

S121-30

SB-6025

4'-6"

COORDINATE HEIGHT OF CEILING

WITH CABINETS. SEAL ANY

SPACE BETWEEN TOP OF

CABINETS AND CEILING.

PROVIDE BLOCKING IN WALL AS

NEEDED TO SUPPORT WALL

CABINETS.

UNDER CABINET LED DIMMABLE

LIGHT FIXTURES. PROVIDE

DIMMING SWITCH ON WALL.

PROVIDE 24 GAUGE 304

STAINLESS STEEL WALL

COVERING SHEET WITH #4

POLISH AS SHOWN. SEAL

BETWEEN SS SHEET AND

BACKSPLASH WITH 100%

SILICONE CLEAR SILICONE

CAULK WITH CONCAVE SEAL.

SEAL BETWEEN WALLS AND

COUNTERTOP WITH CLEAR

SILICONE CAULK.

NOTE: THIS ELEVATION SIMILAR

FOR BOTH BUFFER ROOMS AND

ANTE ROOM. COORDINATE WITH

PHARMACY ON LOCATION OF 4

DRAWER AND 8 DRAWER

CABINETS.

2-1/2" METAL WALL FRAMING. SEAL

FRAMING TO WALL IN BED OF CAULK

SUSPENDED GWB METAL

FRAMING SYSTEM

HANGER WIRE

5/8" TYPE X MMR GYPSUM WALL BOARD AS SPECIFIED. PAINT WITH WHITE SANIGLAZE

HIGH BUILD WALL SYSTEM BY SHERWIN WILLIAMS. PROVIDE TWO PRIMER COATS, TWO

BASE COATS, AND TWO FINISH COATS. INSTALL IAW MANUFACTURER'S DIRECTIONS.

METAL J TRIM

7/27/2020 10:30:05 PM

AutoCAD SHX Text Room

AutoCAD SHX Text Toilet

AutoCAD SHX Text

11A REFLECTED CEILING PLAN

AutoCAD SHX Text SECTION 2 - ANTE-ROOM A1105a CASEWORK ELEVATION

AutoCAD SHX Text

SECTION 3 - CASEWORK ELEVATION

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

QUANTITY

AutoCAD SHX Text

UNITS

AutoCAD SHX Text

SHELVES

AutoCAD SHX Text

DRAWERS

AutoCAD SHX Text P265-3012

AutoCAD SHX Text A1106a

AutoCAD SHX Text 30"

AutoCAD SHX Text 18"

AutoCAD SHX Text

AutoCAD SHX Text 12"

AutoCAD SHX Text 35.5"

AutoCAD SHX Text

GLASS DOORS, HANDLES

AutoCAD SHX Text N/A

AutoCAD SHX Text A1106a

AutoCAD SHX Text 18"

AutoCAD SHX Text

AutoCAD SHX Text

BASE CABINET

AutoCAD SHX Text

WALL CABINET

AutoCAD SHX Text

HANDLES

AutoCAD SHX Text N/A

AutoCAD SHX Text

CASEWORK TAG

AutoCAD SHX Text

CABINET SCHEDULE

AutoCAD SHX Text

TYPE

AutoCAD SHX Text A1106a

AutoCAD SHX Text

HEIGHT

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text 22"

AutoCAD SHX Text

WIDTH

AutoCAD SHX Text

- UNIT TAG CORRESPONDS TO BASIS OF DESIGN MODEL. BASIS IS TBJ INC. PROVIDE 304 STAINLESS STEEL UNITS WITH #4 FINISH, MIN. 20 GA PANELS, UNIT TAG CORRESPONDS TO BASIS OF DESIGN MODEL. BASIS IS TBJ INC. PROVIDE 304 STAINLESS STEEL UNITS WITH #4 FINISH, MIN. 20 GA PANELS, 16 GA RAILS, 14 GA CHANNELS AND HINGES, AND 12 GA BOTTOM GUSSETS. COUNTERTOPS SHALL BE MIN. 16 GA 304 STAINLESS STEEL WITH 16 GA CHANNELS. INSTALL IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. ALL WELDS SHALL BE CONTINUOUS AND GROUND SMOOTH. PROVIDE AND WIRE UNDERCABINET LED LIGHTS WHERE INDICATED. - COUNTER TOPS SHALL HAVE ROUNDED CORNERS ON BACKSPLASHES. COUNTER TOPS SHALL HAVE ROUNDED CORNERS ON BACKSPLASHES.

AutoCAD SHX Text

DEPTH

AutoCAD SHX Text

SB-6625

AutoCAD SHX Text

COUNTER TOP

AutoCAD SHX Text A1106a

AutoCAD SHX Text 5.25"

AutoCAD SHX Text 25"

AutoCAD SHX Text

AutoCAD SHX Text N/A

AutoCAD SHX Text N/A

AutoCAD SHX Text

4" BACKSPLASH,SINK,FAUCET

AutoCAD SHX Text

AutoCAD SHX Text S245-3016

AutoCAD SHX Text

WALL CABINET

AutoCAD SHX Text 30"

AutoCAD SHX Text A1106a,b,c

AutoCAD SHX Text 42"

AutoCAD SHX Text 16"

AutoCAD SHX Text S122-18

AutoCAD SHX Text N/A

AutoCAD SHX Text

HANDLES

AutoCAD SHX Text 22"

AutoCAD SHX Text

AutoCAD SHX Text

BASE CABINET

AutoCAD SHX Text 35.5"

AutoCAD SHX Text

AutoCAD SHX Text 30"

AutoCAD SHX Text

AutoCAD SHX Text

BASE CABINET

AutoCAD SHX Text N/A

AutoCAD SHX Text S121-30

AutoCAD SHX Text A1106a,b,c

AutoCAD SHX Text

AutoCAD SHX Text 5'-0"

AutoCAD SHX Text

HANDLES

AutoCAD SHX Text S181-48

AutoCAD SHX Text

BASE CABINET

AutoCAD SHX Text

COUNTER TOP

AutoCAD SHX Text 35.5"

AutoCAD SHX Text 48"

AutoCAD SHX Text

AutoCAD SHX Text N/A

AutoCAD SHX Text N/A

AutoCAD SHX Text

AutoCAD SHX Text

DOOR, HANDLES, SINK

AutoCAD SHX Text 5'-6"

AutoCAD SHX Text 22"

AutoCAD SHX Text

GLASS DOORS, HANDLES

AutoCAD SHX Text

AutoCAD SHX Text N/A

AutoCAD SHX Text 22"

AutoCAD SHX Text

AutoCAD SHX Text A1106a,b,c

AutoCAD SHX Text 35.5"

AutoCAD SHX Text S124-30

AutoCAD SHX Text

AutoCAD SHX Text

SB-6025

AutoCAD SHX Text 5.25"

AutoCAD SHX Text A1106a,b,c

AutoCAD SHX Text

AutoCAD SHX Text 30"

AutoCAD SHX Text 25"

AutoCAD SHX Text N/A

AutoCAD SHX Text

4" BACKSPLASH

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

GYPSUM CEILING FRAMING DETAIL

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text Stratton VA Medical Center Albany, NY

AutoCAD SHX Text 528A8-20-816

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text Approved By Signatures date

AutoCAD SHX Text O/M Manager

AutoCAD SHX Text Interior Design

AutoCAD SHX Text Infection Control

AutoCAD SHX Text VA Police

AutoCAD SHX Text Information Systems

AutoCAD SHX Text Fire Safety Officer

AutoCAD SHX Text Environmental Services

AutoCAD SHX Text Care Service Line Supervisor

AutoCAD SHX Text Energy Manager

AutoCAD SHX Text GEMS Coordinator

AutoCAD SHX Text Industrial Hygentist

AutoCAD SHX Text Using Activity Program Manager

AutoCAD SHX Text Approved: FMS Manager date

AutoCAD SHX Text Approved: Project Section Manager date

AutoCAD SHX Text

17 MARCH 2020

AutoCAD SHX Text

FAW

AutoCAD SHX Text

AutoCAD SHX Text

REFLECTED CEILING PLAN AND SECTIONS

AutoCAD SHX Text A-002

AutoCAD SHX Text

RENOVATE 11A FOR USP 797 / 800 BACKUP

AutoCAD SHX Text

EMG

PULL

BOX

PANEL

11-47

REFRIGERATOR

REFRIGERATOR

4' BIOLOGICAL

SAFETY CABINET

4' POSITIVE

PRESSURE HOOD

PHONE

5'-0"

PANEL

11-38

PANEL

11-20-E

HWS

HWR

CHWR

CHWS

STEAM

LPC

PUMP COND

5" STORM CONDUCTOR

FIELD VERIFY EXACT

LOCATION

AD

REFRIGERATOR

A1105 A1105a

A1105b

A1105c

A1106b

A1106c

A1106e A1106d

A1106f

A1107 A1108

A1109

A1104

A1106a

A1106g

A1110

1/2" DHWR

1/2" DHW

1/2" DCW

A1105

HWS

HWR

CHWR

CHWS

STEAM

LPC

PUMP COND

2'-6"

3'-0"

PANEL

11-237(A)

EMG

PULL

BOX

PANEL

11-47

PANEL

11-38

PANEL

11-20-E

A1105a A1105b A1106a A1106b A1106c

A1106e A1106d

A1106f

A1107

A1108

A1109

A1104

A1106g

Stair

A1110

REMOVE SPRINKLER HEADS AND ASSOCIATED DISTRIBUTION PIPING. PROVIDE PERMANENT CAP AT MAIN.

REMOVE SUPPORTS AND APPURTENANCES.

RELOCATE EXISTING SPRINKLER HEADS AND EXTEND ARM OVERS TO PROVIDE CORRIDOR PROTECTION DURING

CONSTRUCTION. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS. EXISTING SPRINKLER HEADS IN ROOMS

AND CORRIDORS TO REMAIN OPERATIONAL DURING CONSTRUCTION. REMOVE HEADS, PIPING AS NEEDED, AND

SUPPORTS WHEN NEW HEADS ARE INSTALLED.

SHUT OFF VALVE FOR SPRINKLERS IN STEM IS LOCATED IN STAIRWELL 4. CONTRACTOR SHALL COORDINATE WITH

VA PLUMBING SHOP FOR SHUTTING AND DRAINING SYSTEM AS WELL AS RE-FILLING.

REMOVE LAVATORY, FAUCET, AND DOMESTIC AND SANITARY PIPING AND VENTS. DOMESTIC PIPING TO BE

EXTENDED TO NEW SINK. REMOVE SANITARY PIPING BACK TO MAINS ABOVE 10A CEILING. PROVIDE NO-HUB CAPS

ON SANITARY AT MAIN. REPAIR HOLES IN SLAB TO MATCH EXISTING CONSTRUCTION.

REMOVE DOMESTIC AND SANITARY PIPING AND VENTS. REMOVE PIPING BACK TO MAINS ABOVE 10A CEILING.

PROVIDE SOLDERED CAPS ON DOMESTIC AND NO-HUB CAPS ON SANITARY. REPAIR HOLES IN SLAB TO MATCH

EXISTING CONSTRUCTION.

REMOVE 2" VENT. RE-CONNECT TO EXISTING 4" VTR. LOCATE VENT IN BEAM SPACE.

EXISTING 5" ROOF DRAIN AND CONDUCTOR TO REMAIN. CONTRACTOR AND COR TO DETERMINE STATE OF

EXISTING PIPING. REMOVE EXISTING INSULATION. RE-INSULATE WITH 1-1/2" THICK FLEXIBLE ELASTOMERIC PIPE

INSULATION. INSULATE ROOF BOWL WITH 1-1/2" THICK ELASTOMERIC INSULATION GLUED TO BOWL.

FIELD VERIFY TYPE AND LOCATION OF PIPE. PIPE IS ASSUMED TO BE DCW. REMOVE PIPE IF NOT IN USE.

RE-INSULATE IF PIPE IS BEING USED.

EXISTING PLUMBING VENT TO REMAIN.

EXISTING LAVATORY TO REMAIN.

EXISTING SANITARY VENT TO VTR. FIELD VERIFY EXACT LOCATION.

PROVIDE 2" SANITARY DRAIN SERVING SINK. CORE DRILL SLAB. INSTALL ABOVE 10A CEILING. COORDINATE WITH

EXISTING DUCTS AND PIPING ABOVE 10A CEILING. CONNECT TO EXISTING 4" SANITARY RISER AT SANITARY STACK

S43. FIELD VERIFY EXACT LOCATION. WORK ABOVE 10A CEILING SHALL BE COORDINATED WITH VA COR AND

PERFORMED OFF HOURS.

PROVIDE 2" PLUMBING VENT TO SERVE SINK. CONNECT TO EXITING 4" VTR AT S43. FIELD VERIFY EXACT LOCATION.

LOCATE VENT IMMEDIATELY BELOW BEAMS.

SINK PROVIDED BY CABINET MANUFACTURER. CONTRACTOR SHALL PROVIDE DOMESTIC AND SANITARY PIPING TO

SERVE SINK. PROVIDE

" DCW AND

" DHW. PROVIDE

" DHWR CONNECTED BELOW SINK WITH SHUT OFF, BALANCE,

ANE CHECK VALVES. CONNECT TO EXISTING DHW RISER. REFER TO DETAIL. PROVIDE 1-1/2" SANITARY ENLARGING

TO 2" THROUGH SLAB. PROVIDE 2" VENT.

EXTEND EXISTING DCW/DHW RISERS TO SERVE NEW SINK. PROVIDE BRONZE BALL VALVE SHUT OFFS ABOVE

A1105C TO SERVE PIPES. SEAL EXISTING SLAB PENETRATIONS TO MAINTAIN FIRE BARRIER. PROVIDE SHUT OFF

VALVES AND TAPS TO SERVE PIPE CLEANING AND DISINFECTION. PROVIDE ANSI Z358.1 DECK MOUNTED BRONZE

SWING DOWN HALO EYE/FACE WASH AND ASSE 1071 MIXING VALVE LOCATED UNDER SINK WITH SHUT OFFS AND

DRAIN VALVES TO SERVE EYE/FACE WASH. SET FOR 83°F. PROVIDE BRONZE DECK MOUNTED BATTERY OPERATED

SENSOR…