528A8-20-816 Combined Drawings REV-1.pdf
PDF 7 MB Posted
- Solicitation number
- 36C24220B0052
About this file
This pre-solicitation notice provides details for an upcoming solicitation to renovate 11A for USP 797/800 backup at the Stratton VA Medical Center in Albany, NY. The project involves constructing a new laboratory to serve as a backup facility for IV and chemotherapy compounding currently performed in separate labs on floors 1B and 9A. The procurement will be a 100% set-aside for Service Disabled Veteran Owned Small Businesses and have a NAICS code of 236220 with a small business size standard of $39.5 million. The estimated value of construction is between $500,000 and $1 million. The solicitation materials will be posted on beta.SAM.gov in electronic format on or around July 14, 2020. All inquiries should be directed to the point of contact Tony Clemente by phone at 518-258-5483 or email.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24220B0052 0004.docx | DOCX document | |
| 36C24220B0052 0003.docx | DOCX document | |
| 36C24220B0052 0002.docx | DOCX document | |
| 528A8-20-816 100_ Combined Specs 2020-07-26.pdf | ||
| 36C24220B0052 0001.docx | DOCX document | |
| 36C24220B0052_1.docx | DOCX document | |
| DB wage determinations.pdf | ||
| 528A8-20-816 11A Renovate 11A for USP 797 800 Backup Combined PDF.pdf | ||
| 528A8-20-816 95 Per Cent Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. ALL WORK SHALL COMPLY WITH ALL APPLICABLE GOVERNMENT CODES INCLUDING BUT NOT LIMITED TO NFPA 101LIFE SAFETY CODE, IBC, OSHA, AND ADA.
2. CONTRACTOR SHALL REVIEW ALL DRAWINGS AND SPECIFICATIONS AND NOTIFY COR OF ANY DISCREPANCIES.
3. THE CONTRACTOR SHALL HOLD THE VETERANS ADMINISTRATION HARMLESS AGAINST ANY AND ALL CLAIMS ARISING FROM WORK
PERFORMED BY THE CONTRACTOR ON SITE.
4. PRIOR TO START OF WORK SUBMIT FOR COR APPROVAL A DETAILED SCHEDULE OF ALL WORK THAT MIGHT AFFECT OWNER'S USE OF
BUILDING SUCH AS UTILITY SHUT DOWN AND NOISE GENERATING WORK.
5. EXISTING FACILITY SHALL REMAIN IN OPERATION DURING THIS WORK. ENSURE SAFE PASSAGE OF ALL PERSONS AROUND WORK AREA.
ERECT 1 HOUR BARRIERS AS REQUIRED OR DIRECTED BY COR. MAINTAIN ALL REQUIRED EGRESS ROUTES. DO NOT LIMIT VA'S USE OF
FACILITY WITHOUT PRIOR APPROVAL.
6. CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL REQUIRED TO PERFORM THE WORK.
7. PROVIDE ALL MATERIALS AND PERFORM ALL WORK IN ACCORDANCE WITH RECOGNIZED GOOD STANDARD PRACTICES.
8. ALL MATERIALS SHALL BE NEW AND AS SPECIFIED OR EQUAL, AS APPROVED BY THE COR. MATERIALS SPECIFIED INDICATE QUALITY
INTENT THAT WILL BE USED AS A BASIS FOR REVIEW OF SUBSTITUTES.
9. ALL ITEMS WHICH ARE NOT SPECIFICALLY REFERRED TO ON THESE DRAWINGS, OR IN THE SPECIFICATIONS, ARE TO BE SELECTED BY THE
COR FROM THE MANUFACTURER'S STANDARD OFFERINGS SHOWING FULL RANGE OF OPTIONS.
10. FOLLOW MANUFACTURER'S SPECIFICATIONS AND INSTRUCTIONS FOR INSTALLATION OF ALL MATERIALS.
11. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. CONTRACTOR TO NOTIFY COR OF ANY DISCREPANCIES PRIOR TO
BEGINNING WORK.
12. ALL DIMENSIONS SHALL BE FIELD VERIFIED, DO NOT SCALE DRAWINGS.
13. MINOR ITEMS OF WORK SUCH AS CUTTING, BLOCKING, TRIM, ETC. SHALL BE PERFORMED AS REQUIRED TO MAKE THE WORK COMPLETE
WHETHER NOTED ON THE CONTRACT DOCUMENTS OR NOT.
14. ALL NOISY OR DISRUPTIVE WORK SHALL BE SCHEDULED IN ADVANCE WITH THE COR.
15. CONTRACTOR SHALL ASSUME THAT NONE OF THE EXISTING VALVES ARE WATER TIGHT. CONTRACTOR SHALL BE PREPARED TO FREEZE
THE AFFECTED PIPE IN ORDER TO COMPLETE THE WORK. COORDINATE WITH COR ON ANY PIPE FREEZING.
16. CONTRACTOR SHALL REMOVE AND REPLACE ANY EXISTING CEILING TO REMAIN AS NEEDED TO ACCOMPLISH WORK. THOROUGHLY CLEAN
ROOMS AND OFFICES THAT WILL BE OCCUPIED AFTER WORK IS COMPLETED. CONTRACTOR SHALL REPLACE TILES OR GRID DAMAGED AS
PART OF THIS PROJECT.
17. CONTRACTOR SHALL COMPLY WITH ALL VA REGULATIONS, LOCAL AND NATIONAL, CONCERNING ACTIONS TO BE TAKEN DURING THE
COVID-19 PANDEMIC. COR SHALL BRIEF CONTRACTOR ON REQUIRED ACTIONS.
18. BACKUP COMPOUNDING SPACE LOCATED ON THE 11TH FLOOR SHALL BE OPERATIONAL BY JANUARY 29, 2021.
CS-001 COVER SHEET
HA-001 ASBESTOS REMOVAL AND ICRA PART PLANS
AD-001 ARCHITECTURAL DEMOLITION
A-001 ARCHITECTURAL PART PLANS AND DETAILS
A-002 REFLECTED CEILING PLAN AND SECTIONS
P-001 PLUMBING / FIRE PROTECTION PART PLANS
M-001 MECHANICAL DEMOLITION
M-002 MECHANICAL NEW WORK PART PLANS
M-003 LEGEND AND CONTROLS SCHEMATIC
M-004 MECHANICAL SECTION AND DETAILS
M-005 MECHANICAL SCHEDULES AND CONTROL POINTS
E-001 ELECTRICAL DEMOLITION AND NEW PART PLANS
P
A
N
E
L
M
E
R
A
PANEL
11-237(A)
EMG
PULL
BOX
PANEL
11-47
PANEL
11-38
PANEL
11-20-E
COVER SHEET
RENOVATE 11A FOR USP
797 / 800 BACKUP
528A8-20-816
11A
17 MAR 2020
TW
CS-001
FMS DESIGN TEAM
ACRONYMS USED
DEPARTMENT OF VETERANS AFFAIRS
SAMUEL S. STRATTON
MEDICAL CENTER
ALBANY, NEW YORK
RENOVATE 11A FOR USP
797 / 800 BACKUP
PROJECT 528A8-20-816
11A KEY PLAN
7/27/2020 12:01:00 PM
AutoCAD SHX Text
VETERANS WAY
AutoCAD SHX Text
ELKS MEMORIAL DRIVE
AutoCAD SHX Text
HOLLAND AVE
AutoCAD SHX Text
MYRTLE AVE
AutoCAD SHX Text
NEW SCOTLAND AVE
AutoCAD SHX Text
SAN
AutoCAD SHX Text
EL
AutoCAD SHX Text
EL
AutoCAD SHX Text
EL
AutoCAD SHX Text
EL
AutoCAD SHX Text
EL
AutoCAD SHX Text
EL
AutoCAD SHX Text
EL
AutoCAD SHX Text
EL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EL
AutoCAD SHX Text
AutoCAD SHX Text
EL
AutoCAD SHX Text
AutoCAD SHX Text
EL
AutoCAD SHX Text
AutoCAD SHX Text
EL
AutoCAD SHX Text 14?
AutoCAD SHX Text
EL
AutoCAD SHX Text
AutoCAD SHX Text
EL
AutoCAD SHX Text 1?
AutoCAD SHX Text
FFE: 189.07'
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
CONCRETE WALKWAY
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
TEL
AutoCAD SHX Text
TEL
AutoCAD SHX Text
TEL
AutoCAD SHX Text
TEL
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text V
AutoCAD SHX Text V
AutoCAD SHX Text
THIS SPOT IS ONLY FOR RED ROAD GLIDES.
AutoCAD SHX Text
MAGNETIC
AutoCAD SHX Text
PLAN
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
LOADING
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text Approved By:
AutoCAD SHX Text O/M Manager
AutoCAD SHX Text Safety Manager
AutoCAD SHX Text Infection Control
AutoCAD SHX Text Police Chief
AutoCAD SHX Text Energy Manager
AutoCAD SHX Text GEMS Coordinator
AutoCAD SHX Text Using Activity Program Manager
AutoCAD SHX Text Interior Design
AutoCAD SHX Text Approved By VAMC Director:
AutoCAD SHX Text Engineering Manager
AutoCAD SHX Text
DRAWING LIST
ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg AutoCAD SHX Text T ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg ftp://image.autodesk.com/drawing/110_VOLT_ELECTRICAL_OUTLET.dwg AutoCAD SHX Text T
AutoCAD SHX Text Room
AutoCAD SHX Text Toilet
AutoCAD SHX Text 11A Existing Mechanical Room
AutoCAD SHX Text 10th Floor Roof
AutoCAD SHX Text
%%UELEVENTH FLOOR PLAN
AutoCAD SHX Text
%%UWING A
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text Approved: Engineering Manager
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
DESIGNERS:
AutoCAD SHX Text ADA: AMERICANS WITH DISABILITIES ACT AFF: ABOVE FINISHED FLOOR ELEVATION ASTM: AMERICAN SOCIETY FOR TESTING MATERIALS AWWA: AMERICAN WATER WORKS ASSOCIATION BGS: BELOW GROUND SURFACE ELEVATION BOC: BOTTOM OF CONCRETE CB: STORMWATER CATCH BASIN CL: CENTER LINE, CENTER CMU: CONCRETE MASONRY UNIT CO: CONTRACTING OFFICER COR: CONTRACTING OFFICER'S REPRESENTATIVE DIA: DIAMETER DIP: DUCTILE IRON PIPE DMH: DRAINAGE MANHOLE EQ: EQUAL EX: EXISTING FT: FOOT OR FEET GRD: GROUND HDPE: HIGH DENSITY POLYETHYLENE PIPE IAW: IN ACCORDANCE WITH ICRA: INFECTION CONTROL RISK ASSESSMENT ID: INSIDE DIAMETER MAX: MAXIMUM MIN: MINIMUM NFPA: NATIONAL FIRE PROTECTION ASSOCIATION NYS: NEW YORK STATE NYSDOT: NYS DEPT. OF TRANSPORTATION NYS DEPT. OF TRANSPORTATION NYSDEC: NYS DEPT. OF ENVIRONMENTAL CONSERVATION OC: ON CENTER OD: OUTSIDE DIAMETER PVC: POLY-VINYL CHLORIDE PIPE PSI: POUNDS PER SQUARE INCH RCP: REINFORCED CONCRETE PIPE SMH:SANITARY MANHOLE TOC: TOP OF CONCRETE TOP OF CONCRETE TYP: TYPICAL UNO: UNLESS NOTED OTHERWISE UNLESS NOTED OTHERWISE VA: VETERANS ADMINISTRATION VAMC: VETERANS ADMINISTRATION MEDICAL CENTER VA: VETERANS ADMINISTRATION VAMC: VETERANS ADMINISTRATION MEDICAL CENTER VCP: VITREOUS CLAY PIPE VIF: VERIFY IN FIELD
AutoCAD SHX Text
ALBANY MED PARKING GARAGE
AutoCAD SHX Text
LOCATION PLAN: 1:200
AutoCAD SHX Text
BLDG. 1
REMOVE CONVECTORS INCLUDING COVERS AND BACK BOX AND ALL ASBESTOS CONTAINING
INSULATION.
REMOVE STEAM AND CONDENSATE PIPING AND ASSOCIATED ASBESTOS CONTAINING PIPE AND PIPE
JOINT INSULATION. OPEN PIPE CHASE SLAB TO SLAB. DO NOT REMOVE FIREPROOFING AT COLUMN
ENCLOSURE. REMOVE PIPE INSULATION INTO SLAB PENETRATION. PACK PIPE PENETRATION FULL WITH
ROCK WOOL. REMOVE PIPE RISERS LEVEL TO DECK. CUT SLOTS IN SLAB AND INSTALL RISER HANGERS.
CAP TOP OF PIPES AIR TIGHT WITH THREADED OR WELDED SCH 80 BLACK STEEL CAPS. FIELD VERIFY
PIPE SIZES. PIPE SIZES ARE ASSUMED TO BE 1". FIELD VERIFY PIPE SIZES.
REMOVE ALL ASBESTOS CONTAINING FLOOR TILE AND MASTIC. PROTECT CEILING AND ROOMS ON
A10. PERFORM WORK ON 2ND SHIFT TO AVOID NOISE IN ROOMS BELOW. INSTALL PLASTIC SHEET ABOVE
10A CEILING BELOW WORK TO PROTECT CEILING. REMOVE SHEET AS WASTE MATERIAL PRIOR TO
DRYING.
REMOVE STEAM AND CONDENSATE PIPING AND ASSOCIATED ASBESTOS CONTAINING PIPE AND PIPE
JOINT INSULATION. OPEN PIPE CHASE SLAB TO SLAB. REMOVE PIPE INSULATION INTO SLAB
PENETRATION. PACK PIPE PENETRATION FULL WITH ROCK WOOL. REMOVE PIPE RISERS TO FIRST
ELBOW. EXTEND THE LPS AND LPC PIPES INTO ROOM TO SERVE HUMIDIFIER. CUT SLOTS IN SLAB AND
INSTALL RISER HANGERS. PROVIDE BRONZE SHUT OFF VALVES. PIPE SIZES ARE ASSUMED TO BE 1".
FIELD VERIFY PIPE SIZES.
REMOVE PIPE INSULATION. ASSUME 20 LF OF 1-1/4" PIPING. RE-INSULATE PIPE IAW SPECIFICATIONS.
REMOVE CONVECTORS INCLUDING BACK BOX AND ALL ASBESTOS CONTAINING INSULATION.
RE-INSULATE BACK BOXES WITH 1" THICK CLOSED CELL SPRAY FOAM INSULATION RATED FOR 215°
MINIMUM AND RE-INSTALL. CLEAN CONVECTORS AND REPLACE. REMOVE STEAM AND CONDENSATE
ASBESTOS CONTAINING PIPE AND PIPE JOINT INSULATION. DO NOT REMOVE FIREPROOFING AT COLUMN
ENCLOSURE. REMOVE PIPE INSULATION INTO SLAB PENETRATION. PACK PIPE PENETRATION FULL WITH
ROCK WOOL. REPLACE SHUT OFF VALVES AND CONTROL VALVE TO MATCH EXISTING. FIELD VERIFY PIPE
SIZES.
A1105
HWS
HWR
CHWR
CHWS
STEAM
LPC
PUMP COND
2'-6"
3'-0"
PANEL
11-237(A)
EMG
PULL
BOX
PANEL
11-47
PANEL
11-38
PANEL
11-20-E
A1105a A1105b A1106a A1106b A1106c
A1106e A1106d
A1106f
A1107
A1108
A1109
A1106g
6 6 66
1. ASBESTOS REMOVAL SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE, AND LOCAL LAWS, GUIDELINES, REGULATIONS, ORDERS AND
DIRECTIVES INCLUDING, WITHOUT LIMITATION, THOSE OF THE RESPONSIBLE NEW YORK STATE AGENCIES, U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA), U.S.S
DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA), AND NATIONAL INSTITUTE OF OCCUPATIONAL SAFETY AND HEALTH (NIOSH).
2. CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, FACILITIES, EQUIPMENT, SERVICES, ETC., NECESSARY TO PERFORM THE WORK REQUIRED FOR ASBESTOS
ABATEMENT IN ACCORDANCE WITH THE PROJECT MANUAL, EPA AND OSHA REGULATIONS, AND NIOSH RECOMMENDATION, NYS DEPARTMENT OF LABOR, PART 56 OF
TITLE 12 'ASBESTOS' INDUSTRIAL CODE, AND ANY OTHER APPLICABLE FEDERAL, STATE, AND LOCAL GOVERNMENT REGULATIONS.
3. CONTRACTOR SHALL DEVELOP AND IMPLEMENT A WRITTEN STANDARD PROCEDURE FOR ABATEMENT WORK TO ENSURE MAXIMUM PROTECTION AND SAFEGUARDS
FROM ASBESTOS EXPOSURE OF THE WORKER, VAMC VISITORS, VAMC EMPLOYEES, GENERAL PUBLIC, AND THE ENVIRONMENT.
4. CONTRACTOR SHALL PROVIDE SIGNS, LABELS, WARNINGS, AND POSTED INSTRUCTIONS THAT ARE NECESSARY TO PROTECT, INFORM, AND WARN PEOPLE OF THE
HAZARD FROM ASBESTOS EXPOSURE. POST IN A PROMINENT AND CONVENIENT PLACE FOR THE WORKERS AND A COPY OF THE LATEST APPLICABLE REGULATION
FROM OSHA, EPA, AND NIOSH. TEN DAYS PRIOR TO START OF ASBESTOS REMOVAL THE CONTRACTOR SHALL FURNISH TO THE STRATTON VA SAFETY OFFICE A NOTICE
CONTAINING THE ASBESTOS REMOVAL START DATE SUITABLE FOR POSTING BY SAFETY AT THE MEDICAL CENTER ENTRANCE.
5. CONTRACTOR SHALL PROVIDE ALL ELECTRICAL, WATER, AND WASTE CONNECTIONS,TIE-INS, EXTENSIONS, AND CONSTRUCTION MATERIALS, SUPPLIES, ETC., AS
REQUIRED TO COMPLETE THE ASBESTOS REMOVAL.
6. CONTRACTOR SHALL PROVIDE TEMPORARY ELECTRIC AND LIGHTING AS REQUIRED, IN ACCORDANCE WITH OSHA REGULATIONS.
7. CONTRACTOR SHALL PROTECT ALL CONTROL PANELS, ELECTRICAL PANELS, EQUIPMENT, ETC., WITHIN WORK AREAS.
8. CONTRACTOR SHALL PROVIDE ISOLATION AND PROTECTION FOR ALL UN-INSULATED AND/OR NON-ASBESTOS INSULATED MECHANICAL EQUIPMENT.
9. CONTRACTOR SHALL SEAL ALL GRILLES, VENTS, DIFFUSERS, ETC., IN EACH WORK AREA AS REQUIRED BY THE CONTRACT DOCUMENTS AND AS NECESSITATED BY
FIELD CONDITIONS.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING AND/OR REPAIRING ANY EQUIPMENT, MATERIALS, INSULATION, FURNISHINGS, BUILDING STRUCTURES, ETC., DAMAGED DURING THE COURSE OF THE WORK AT NO ADDITIONAL COST TO THE VA.
11. CONTRACTOR SHALL PROVIDE AS MANY SHIFTS OF WORKERS AS WILL BE NECESSARY TO COMPLETE THE JOB IN THE AMOUNT OF TIME SPECIFIED IN THE CONTRACT
DOCUMENTS.
12. CONTRACTOR SHALL PROVIDE ALL SCAFFOLDING, EQUIPMENT, TOOLS, TRANSPORTATION EQUIPMENT, VACUUM EQUIPMENT, SPRAYERS, ETC., AS REQUIRED AND/OR
NECESSARY TO COMPLETE ALL WORK REQUIRED BY THE CONTRACT DOCUMENTS.
13. CONTRACTOR SHALL ISOLATE THE WORK AREAS AS DESCRIBED IN THE CONTRACT DOCUMENTS. ALL CRITICAL BARRIERS, DECONTAMINATION UNITS, PLASTIC
SHEETING, AIR FILTRATION DEVICES, RESPECTIVE MANIFOLDS, ETC., ARE TO BE IN PLACE AND APPROVED BY THE CONSULTANT PRIOR TO ASBESTOS REMOVAL.
14. CONTRACTOR SHALL LOCATE AND SEAL ALL PENETRATIONS THROUGH THE WORK AREAS NOT LIMITED TO PIPE, DUCT, CONDUIT, CHASES, SHAFT WAYS, AND
OPENINGS IN FIRE OR SMOKE BARRIERS OR DECKS BETWEEN FLOORS AS REQUIRED BY FIELD CONDITIONS.
15. ALL LUMBER AND POLYETHYLENE MATERIALS USED FOR THIS PROJECT ARE TO BE FIRE RESISTANT.
16. CONTRACTOR SHALL COORDINATE WITH THE VA ON SHUTDOWN OF HVAC UNITS WHICH SERVE WORK AREAS.
17. SHOWER AND WASTE WATER SHALL BE TREATED AND DISPOSED OF AS SPECIFIED.
18. CONTRACTOR SHALL PROVIDE PORTABLE CABINET MOUNTED AIR FILTRATION DEVICES (AFD) EQUIPPED WITH HEPA FILTRATION AT 99.97% EFFICIENCY TO 3 MICRONS.
THE NUMBER OF AFD'S SHALL BE IN SUCH A MANNER AS TO INSURE A MINIMUM OF FOUR (4) COMPLETE AIR CHANGES PER HOUR AND MAINTAIN A MINIMUM NEGATIVE
PRESSURE DIFFERENTIAL BETWEEN THE WORK AREA AND ADJOINING SPACE OF -0.02" W.C.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY CONNECTIONS, FASTENERS, FLEXIBLE DUCT, MANIFOLD, SUPPORTING SUSPENSION, ETC., FROM AFD
UNITS TO EXHAUST LOCATIONS. INSTALLATION OF AFD'S SHALL COMPLY WITH CONSULTANT'S INSTRUCTIONS AND MANUFACTURER'S REQUIREMENTS. CONTRACTOR
SHALL COORDINATE WITH THE VA ON LOCATING WINDOW TO INSTALL EXHAUST DUCT AND METHOD OF SEALING REMAINDER OF WINDOW OPENING. MATERIAL AND
SAFING WINDOW OPENINGS ARE BY CONTRACTOR.
20. CONTRACTOR SHALL REMOVE ALL ASBESTOS-CONTAINING MATERIALS FROM EACH WORK AREA INDICATED ON THE CONTRACT DOCUMENTS. CONTRACTOR IS
RESPONSIBLE FOR THE REMOVAL OF ITEMS, SUCH AS CARPET, WALL BOARD OR PLASTER, MECHANICAL EQUIPMENT, ETC., NEEDED TO ACCESS THE
ASBESTOS-CONTAINING MATERIALS.
21. DO NOT SCALE DRAWINGS, CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE PRIOR TO SUBMISSION OF BID, AND REPORT ANY
DISCREPANCIES TO THE ENGINEER IN WRITING. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON DRAWINGS, GENERAL NOTES, AND PROJECT
SPECIFICATIONS.
22. ALL AREAS OF THIS MEDICAL CENTER WITH THE EXCEPTION OF THE DESIGNATED WORK AREAS SHALL REMAIN OCCUPIED WITH VETERANS, OTHER TRADE WORKERS, AND VA PERSONNEL THROUGHOUT THE ABATEMENT PROJECT. EXTEND EVERY REASONABLE ACCOMMODATION TO THE PERSONNEL AND COMPLY WITH ALL VA
REGULATIONS AND REQUIREMENTS.
A1105
HWS
HWR
CHWR
CHWS
STEAM
LPC
PUMP COND
2'-6"
3'-0"
PANEL
11-237(A)
EMG
PULL
BOX
PANEL
11-47
PANEL
11-38
PANEL
11-20-E
A1105a A1105b A1106a A1106b A1106c
A1106e A1106d
A1106f
A1107
A1108
A1109
A1106g
WALK OFF MATS. PEEL
OFF TOP LAYER WHEN
VISIBLY SOILED. (TYP)
PROVIDE 1 HOUR RATED
ENCLOSURE, 1 LAYER OF
5/8" TYPE "X" MMR
GYPSUM TAPED AND
SEALED BOTH SIDES TO
PROVIDE RATING.
INSTALL SLAB TO SLAB.
REPAIR CORRIDOR WALL
TO MATCH EXISTING
WHEN ENCLOSURE IS
REMOVED.
ELECTRONIC PRESSURE
SENSOR TO VERIFY -0.02"
W.C. IN AREA.
PROVIDE 3/4 HOUR RATED DOOR.
PROVIDE CYPHER LOCK, VA WILL
PROVIDE BEST CORE. (TYP 2)
HEPA FILTERED
EXHAUST FAN.
OPERATE
CONTINUOUSLY TO
MAINTAIN -0.02" W.C. IN
AREA DURING
CONSTRUCTION.
7/27/2020 12:02:55 PM
AutoCAD SHX Text
CODED NOTES
AutoCAD SHX Text Toilet
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
ASBESTOS REMOVAL PART PLAN
AutoCAD SHX Text
ASBESTOS ABATEMENT GENERAL NOTES
AutoCAD SHX Text Toilet
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
11A ICRA PART PLAN
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text Stratton VA Medical Center Albany, NY
AutoCAD SHX Text 528A8-20-816
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text Approved By Signatures date
AutoCAD SHX Text O/M Manager
AutoCAD SHX Text Interior Design
AutoCAD SHX Text Infection Control
AutoCAD SHX Text VA Police
AutoCAD SHX Text Information Systems
AutoCAD SHX Text Fire Safety Officer
AutoCAD SHX Text Environmental Services
AutoCAD SHX Text Care Service Line Supervisor
AutoCAD SHX Text Energy Manager
AutoCAD SHX Text GEMS Coordinator
AutoCAD SHX Text Industrial Hygentist
AutoCAD SHX Text Using Activity Program Manager
AutoCAD SHX Text Approved: FMS Manager date
AutoCAD SHX Text Approved: Project Section Manager date
AutoCAD SHX Text
RENOVATE 11A FOR USP
AutoCAD SHX Text
17 MAR 2020
AutoCAD SHX Text
FAW
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS REMOVAL AND ICRA PART PLANS
AutoCAD SHX Text
797 / 800 BACKUP
AutoCAD SHX Text
HA-001
AutoCAD SHX Text
REMOVE CEILING TILES, GRIDS, SUPPORTS, DECK INSERTS, AND CEILING APPURTENANCES. REMOVE
CEILING SOFFIT IN A1105B.
REMOVE CEILING AS NEEDED FOR CONSTRUCTION. TRIM TILES AND INSTALL GRID, SUPPORTS, ETC.
NEEDED TO INSTALL A COMPLETE CEILING SYSTEM ON THE CORRIDOR SIDE OF THE CONSTRUCTION
WALL.
REMOVE WALLS INCLUDING TOP AND BOTTOM TRACKS AND DOORS AS SHOWN. PLEASE NOTE THAT
SOME WALLS MAY BE PLASTER.
REPLACE EXISTING WOODEN RAMP. PROVIDE CHROME PLATED STEEL RAMP WITH DIAMOND TREAD.
FIELD MEASURE RAMP. SUBMIT RAMP DIMENSIONS AND TECHNICAL DATA FOR COR REVIEW. LAG RAMP
TO MER WALL WITH (4)
"X 4" STAINLESS STEEL BOLTS. RAMP SHALL BE RATED TO SUPPORT 2,000#.
WALLS AND TREAD SHALL BE MINIMUM
" THICK PLATE STEEL. PROVIDE CONTINUOUS WELD ON ALL
JOINTS GROUND SMOOTH. REVISE CONSTRUCTION DOOR AS NEEDED TO ACCOMMODATE RAMP.
REPLACE EXISTING DOOR TO MER-A WITH METAL DOOR WITH 2 HOUR RATING. PROVIDE NEW LOCKSET
SUITABLE FOR BEST 7 PIN CORE. CORE BY VA. FIELD MEASURE DOOR FRAME PRIOR TO ORDERING.
REMOVE VCT TILE AND MASTIC. GRIND ANY HIGH POINTS IN CONCRETE SLAB. INSTALL LEVELING
COMPOUND FOR ENTIRE AREA TO PREPARE FOR EPOXY FLOOR SYSTEM.
REMOVE PLANK FLOORING, ROPPE VINYL PLANK. GRIND ANY HIGH POINTS. INSTALL LEVELING
COMPOUND FOR ENTIRE AREA TO PREPARE FOR EPOXY FLOOR SYSTEM. NOTE THAT NOT ALL AREAS
WILL RECEIVE EPOXY FLOORING.
REMOVE WING WALL. SEAL CORRIDOR WALL TO MATCH EXISTING. PROVIDE CORNER GUARD. PROVIDE
COVE BASE AS NEEDED TO MATCH EXISTING. PAINT TO MATCH EXISTING.
REMOVE STAINLESS STEEL COVERS AND CAULKING ON CONVECTOR GRILLES. CLEAN COVER AND
CONVECTOR. VERIFY OPERATION OF CONVECTOR.
A1105
HWS
HWR
CHWR
CHWS
STEAM
LPC
PUMP COND
2'-6"
3'-0"
PANEL
11-237(A)
EMG
PULL
BOX
PANEL
11-47
PANEL
11-38
PANEL
11-20-E
A1105a A1105b A1106a A1106b A1106c
A1106e A1106d
A1106f
A1107
A1108
A1109
A1106g
A1105
HWS
HWR
CHWR
CHWS
STEAM
LPC
PUMP COND
2'-6"
3'-0"
PANEL
11-237(A)
EMG
PULL
BOX
PANEL
11-47
PANEL
11-38
PANEL
11-20-E
A1105a A1105b A1106a A1106b A1106c
A1106e A1106d
A1106f
A1107
A1108
A1109
A1106g
7/27/2020 10:26:04 PM
AutoCAD SHX Text
CODED NOTES
AutoCAD SHX Text Toilet
AutoCAD SHX Text
AutoCAD SHX Text Toilet
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
CEILING DEMOLITION
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
WALL AND FLOOR DEMOLITION
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text Stratton VA Medical Center Albany, NY
AutoCAD SHX Text 528A8-20-816
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text Approved By Signatures date
AutoCAD SHX Text O/M Manager
AutoCAD SHX Text Interior Design
AutoCAD SHX Text Infection Control
AutoCAD SHX Text VA Police
AutoCAD SHX Text Information Systems
AutoCAD SHX Text Fire Safety Officer
AutoCAD SHX Text Environmental Services
AutoCAD SHX Text Care Service Line Supervisor
AutoCAD SHX Text Energy Manager
AutoCAD SHX Text GEMS Coordinator
AutoCAD SHX Text Industrial Hygentist
AutoCAD SHX Text Using Activity Program Manager
AutoCAD SHX Text Approved: FMS Manager date
AutoCAD SHX Text Approved: Project Section Manager date
AutoCAD SHX Text
17 MAR 2020
AutoCAD SHX Text
FAW
AutoCAD SHX Text
AutoCAD SHX Text
ARCHITECTURAL DEMOLITION
AutoCAD SHX Text
AD-001
AutoCAD SHX Text
RENOVATE 11A FOR USP 797 / 800 BACKUP
AutoCAD SHX Text
REFRIGERATOR
REFRIGERATOR
4' BIOLOGICAL
SAFETY CABINET
4' POSITIVE
PRESSURE HOOD
PHONE
5'-0"
HWS
HWR
CHWR
CHWS
STEAM
LPC
PUMP COND
5" STORM CONDUCTOR
FIELD VERIFY EXACT
LOCATION
AD
REFRIGERATOR
A1105a
A1105b
A1105c
A1106b
A1106c
A1106f
A1107 A1108
A1106a
A1106g
B
B
C
9"
3 4
1 2
11'-6"
21'-10
1'-8
1'-7
1 4
11'-6"
9'-10
1'-8
3'-7"
1'-5
8'-3"
9'-11
1 2
5'-1
1 4
1 2
1 2
1 2
1 2
7'-5
7'-9
6"
1 2
3 4
6'-11
11'
9'-0
3 4
11'-5
5'-10
1 4
3'-7
1 2
1 2
PROVIDE 12"X48" ACCESS
DOOR TO INSPECT
STORM CONDUCTOR
WITH BEST 7 PIN CORE.
COORDINATE DOOR
LOCATION WITH RAMP.
A6
A6
A6
A6
A6
A6
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A-001
A6
A4
A-002
A-002
EXISTING CONCRETE SLAB.
CONTINUOUS GYPSUM COMPOUND
SEALING TRACK TO SLAB, TYPICAL
BOTH SIDES.
1 LAYER OF 5/8" TYPE "X" MMR GYPSUM
WALLBOARD EACH SIDE. PROVIDE
LEVEL 4 FINISH.
NOTE: PROVIDE CONTINUOUS BEAD OF
ACOUSTICAL SEALANT AROUND
PERIMETER OF WALL. INTENT IS TO
PROVIDE AN AIR TIGHT ENVELOPE TO
SERVE THE C-SEC AND BUFFER ROOMS
SLOTTED DEFLECTION TRACK
ATTACHED TO UNDERSIDE OF DECK.
SEAL TOP OF GYPSUM WITH 2 LAYERS
OF 100% SILICONE CAULK ON INTERIOR
WALL FOR AIR TIGHT SEAL. PROVIDE
INTUMESCENT CAULK TO SEAL
CORRIDOR SIDE.
METAL 6" (A6) OR 3-5/8" (A4) FRAMING
STUD, 18 GAUGE, 16" O.C., WITH 6" OR
4" ACOUSTICAL BATT. ATTACH STUDS
TO TOP AND BOTTOM TRACKS WITH
SCREWS ON BOTH SIDES OF STUDS.
PROVIDE BLOCKING TO SERVE
CABINETS WHERE NEEDED.
REFER TO FLOOR DETAIL FOR
SEALING WALL AT SLAB.
PANEL
11-237(A)
EMG
PULL
BOX
PANEL
11-47
PHONE
PANEL
11-38
PANEL
11-20-E
AD
A1105a
A1105b
A1105c
A1106b
A1106c
A1106f
A1107 A1108
A1106a
A1106g
PROVIDE (2) INSULATED AND
GASKETED 1 HOUR RATED ACCESS
DOORS, 28X36, FOR COIL PULL SPACE
ON EACH SIDE OF WALL. PROVIDE
LOCKED DOOR ON OFFICE SIDE, BEST
7 PIN CORES. COORDINATE EXACT
LOCATION WITH AHU.
PROVIDE 14"W x 18"H TEMPERED GLASS FRAMELESS
DOUBLE PANED LITE. LOCATE BOTTOM OF LITE AT 4'-8"
AFF. TERRA UNIVERSAL MODEL 6603-30-0906 OR
EQUAL. INTENT IS TO HAVE NO DUST GATHERING
FRAME IN BUFFER ROOM.
PROVIDE FM APPROVED
CLASS A RATED SMOOTH
FRP WALL COVERING,
CRANE GLASBORD FSFM
OR EQUAL. INSTALL
CEILING TO SLAB AND
IAW MANUFACTURER'S
INSTRUCTIONS.
PROVIDE STAINLESS STEEL
CORNER GUARDS ON ALL
OUTSIDE CORNERS, FULL
HEIGHT. PROVIDE
PAWLING CG-500 OR
EQUAL. INSTALL IAW
MANUFACTURES
DIRECTIONS. INSTALL
FLUSH BEAD OF 100%
CLEAR SILICONE BETWEEN
GUARD AND WALL.
NUMBER DENOTES
FLOOR TYPE (TYP).
ALIGN
PHARMACY OFFICE
A1105a
MECH ROOM
A1105b
RX SUPPLY & DRUG STORAGE
A1105c
ONCOLOGY BUFFER RM
A1106b
IV BUFFER RM
A1106c
ANTE ROOM
A1106a
MECH RM MER A
A1106g
LOCATION OF ROOM
SIGNS (TYP)
WALL MIRROR. COORDINATE
WITH COR ON SIZE AND
INSTALLATION.
EXISTING CONCRETE SLAB.
CONTINUOUS GYPSUM COMPOUND
SEALING TRACK TO SLAB, TYPICAL
BOTH SIDES.
1 LAYER OF 5/8" TYPE "X" MMR GYPSUM
WALLBOARD. INSTALL SMOOTH FRP
COMPOSITE PANELS, FM APROVED AND
CLASS A FIRE RATED, CRANE FSFM OR
EQUAL. INSTALL IAW MANUFACTURERS
INSTRUCTIONS.
NOTE: PROVIDE CONTINUOUS BEAD OF
ACOUSTICAL SEALANT AROUND
PERIMETER OF WALL. INTENT IS TO
PROVIDE AN AIR TIGHT ENVELOPE TO
SERVE THE ANTE AND BUFFER ROOMS
SLOTTED DEFLECTION TRACK
ATTACHED TO UNDERSIDE OF DECK.
SEAL TOP OF GYPSUM WITH 2 LAYERS
OF 100% SILICONE CAULK ON INTERIOR
WALL FOR AIR TIGHT SEAL.
METAL 2-1/2" FRAMING STUD, 20
GAUGE, 16" O.C., WITH 2-1/2"
ACOUSTICAL BATT. ATTACH STUDS TO
TOP AND BOTTOM TRACKS WITH
SCREWS ON BOTH SIDES OF STUDS.
EXISTING PLASTER AND LATH WALL.
SEAL ALL PENETRATIONS WITH
MORTAR AND ACOUSTICAL SEALANT.
REFER TO FLOOR DETAIL FOR
SEALING WALL AT SLAB.
3-5/8" STUD SHAFT WALL ASSEMBLY.
INFILL WITH 3-1/2" FACED BATT
INSULATION. FACING TO WARM SIDE.
PROVIDE AND ATTACH STUDS TO TOP
SLOTTED TRACK AND BOTTOM TRACK.
1" SHAFT WALL
2 LAYERS OF 5/8" TYPE "X" MMR GYPSUM
WALLBOARD. PROVIDE LEVEL 4 FINISH.
PRIME AND PAINT AS SPECIFIED. FINISH
WITH SMOOTH FRP COMPOSITE PANEL,
FM APPROVED AND CLASS A FIRE RATED,
CRANE FSFM OR EQUAL.
EXISTING EXTERIOR WALL
PROVIDE OPENINGS IN EXISTING
WINDOW HEAD SOFFIT TO ALLOW
AIR CIRCULATION BETWEEN
SHAFT WALL AND EXISTING
WINDOW.
REMOVE EXISTING GLASS PANES
FROM WINDOWS. REPLACE WITH
INSULATED ALUMINUM FACED
UNITS, LAMINATOR' S INC.
THERMOLITE PANEL. FIELD
VERIFY THICKNESS. UNITS SHALL
MATCH OWNER'S EXISTING UNITS.
SEAL AIR AND WATER TIGHT IAW
MANUFACTURER'S INSTRUCTIONS.
NOTE: PROVIDE CONTINUOUS BEAD OF
ACOUSTICAL SEALANT AROUND
PERIMETER OF WALL. INTENT IS TO
PROVIDE AN AIR TIGHT ENVELOPE TO
SERVE THE ANTE AND BUFFER ROOMS
EXISTING EXTERIOR WALL
REMOVE WINDOW AND HAND OVER TO VA. REPLACE WITH EXTRUDED
ALUMINUM LOUVER WITH J TYPE BLADE, 4" DEEP, 48"HX44"W, AMERICAN
WARMING AND VENTILATING MODEL LE49 OR EQUAL. PROVIDE ALUMINUM
BIRD SCREEN, KYNAR FINISH-ALUMINUM TO MATCH WINDOW FRAMES, AND
EXTENDED SILL TO COVER STONE SIMILAR TO WINDOWS. FILED MEASURE
EXACT OPENING SIZE.
PROVIDE PRESSURE TREATED, FIRE RATED WOOD BLOCKING AS NEEDED.
SEAL WITH BACKER ROD AND 2 LAYERS OF EXTERIOR GRADE SEALANT, TOP
AND BOTTOM. INSTALL STEEL ANGEL BOLTED TO MASONFY HEAD AND
ATTACHE LOUVER TO ANGLE.
EXISTING STONE SILL
STEEL ANGLE ATTACHED TO SILL AND LOUVER
INFILL CONVECTOR CAVITY WITH 3-5/8" STUDS @ 16" O.C. INSTALL 3" BATT
INSULATION WITH VAPOR BARRIER, 1" RIGID INSULATION WITH VAPOR
BARRIERS, AND
" THICK TYPE "X" MMR GYPSUM SEALED TO WALL. (TYP)
ALUMINUM DRIP EDGE
1. EPOXY FLOOR RES-6. PROVIDE SMOOTH FINISH FOR EASE OF CLEANING.
EXAMINE EXISTING FLOOR FOR SUITABILITY OF INSTALLING EPOXY FLOORING
SYSTEM. GRIND AND LEVEL FLOOR AS NEEDED. PROVIDE STAINLESS STEEL
THRESHOLD BETWEEN EPOXY AND DISSIMILAR FLOOR TYPES.
2. LUXURY VINYL TILE (LVT): VA STANDARD IS ARMSTRONG EARTHCUTS IN
VERONA WARM SUN, 18"x18"x1/8" THICK WITH 20MIL. WEAR LAYER. LOOSE
LAY INSTALLATION IS NOT ACCEPTABLE. NO SUBSTITUTIONS.
3. EXISTING FLOORING TO REMAIN. CONTRACTOR SHALL REVISE EXISTING
FLOORING AS NEEDED TO PROVIDE A HOMOGENEOUS CORRIDOR FLOOR
USING THE SAME TYPE OF FLOORING AND METHOD OF INSTALLATION.
4. PREPARE FLOOR & EXTEND EXISTING ROPPE FLOORING UNDER NEW RAMP.
PAINT ALL NEW AND EXISTING WALLS DECK TO DECK, IN A1105c, A1106a, A1106b, and A1106c AND ALL NEW GYPSUM
CEILINGS. PROVIDE SANIGLAZE HIGH BUILD WALL SYSTEM BY SHERWIN WILLIAMS. PROVIDE TWO PRIMER COATS, TWO BASE COATS, AND TWO FINISH COATS. COLOR WILL BE WHITE. INSTALL IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS INCLUDING TEMPERATURE, HUMIDITY, AND DRYING TIME. MIX EPOXY ON SITE.
FINISH COATS NOT REQUIRED ON WALLS WITH FRP WALL COVERING.
PAINT ALL NEW AND EXISTING WALLS IN ROOMS A1105a, A1105b, AND ALL NEW CORRIDOR WALLS SLAB TO SLAB WITH
ONE COAT OF PRIMER AND TWO FINISH COATS, BENJAMIN MOORE ECO-SPEC WB PRIMER AND PAINT, EGGSHELL.
DOOR FRAMES SHALL BE DIRECT TO METAL SEMI-GLOSS. PROVIDE 4" COVE BASE, TYPE TS WITH TOE, ROPPE
PINNACLE OR EQUAL. COLORS TO BE SELECTED BY VA.
PROVIDE STAINLESS STEEL METAL CORNER GUARDS RECESSED INTO GYPSUM ON ALL NEW OUTSIDE CORNERS.
INSTALL VA APPROVED RED TAPE AS A DEMARCATION LINE ON FLOOR AND TO INDICATE FLOOR SWINGS.
GYPSUM WALL WITH SANIGLAZE HIGH BUILD WALL SYSTEM.
FEATHER EPOXY FILL AGAINST DRYWALL. INSTALL IAW
MANUFACTURER'S INSTRUCTIONS. PROVIDE 4" HIGH COVE
BASE WITH
" RADIUS COVE.
WHITE RESINOUS URETHANE AND EPOXY MORTAR FLOORING
SYSTEM (RES-6) WITH ORANGE PEEL FINISH.
4"
BIOLOGICAL SAFETY CABINET, BAKER STERILGARD 404E, FURNISHED BY OWNER, INSTALLED BY
CONTRACTOR INCLUDING RECEIVING AND INSPECTING ON SITE AND TRANSPORTING TO ONCOLOGY
BUFFER ROOM.
BIOLOGICAL SAFETY CABINET, BAKER EDGEGARD MODEL EG-4320, FURNISHED BY OWNER, INSTALLED BY
CONTRACTOR INCLUDING RECEIVING AND INSPECTING ON SITE AND TRANSPORTING TO IV BUFFER
ROOM.
REFRIGERATOR SUPPLIED BY OWNER, TRANSPORTED FROM LOADING DOCK AND INSTALLED BY
CONTRACTOR.
PROVIDE 14 GAUGE 304L STAINLESS STEEL SHELF ABOVE REFRIGERATORS, 14 GAUGE WITH #4 POLISH, 5'-8-1/2" (WIDE), 5'-5-3/8" (NARROW) x 2'-4" DEEP. TOP OF SHELF AT 36" AFF. FIELD MEASURE EXACT
DIMENSIONS. PROVIDE BLOCKING IN WALL TO SUPPORT SHELF. PROVIDE 1-1/2"x1/2" CAPPED STAINLESS
STEEL TUBE WELDED INTO A LEVEL FRAME AND ATTACHED TO BLOCKING WITH STAINLESS STEEL
SCREWS. INCLUDE TUBE WELDED IN MIDDLE OF FRAME LONG DIMENSION. PROVIDE 1/8" DEEP
DEPRESSION FOR ALL OF SHELF STARTING AT 3/4" FROM EDGES. SEAL EDGES AT WALLS WITH CLEAR
SILICONE CAULK.
PROVIDE NEW 42"W x 85.5"H x DOOR, LH SWING, MASONITE-MARSHFIELD ROTATY WHITE BIRCH, CARAMEL
COLOR AND NEW WELDED METAL BUCK WITH 4" HOSPITAL STOPS. PAINT BUCK TO MATCH NEARBY
DOORS WITH DIRECT TO METAL SEMI-GLOSS PAINT. INSTALL DARK BROWN KYDEX KICKPLATE, 24"H x
42"W , 0.125" THICK MECHANICALLY ATTACHED EVERY 4" TO BOTH SIDES OF DOOR. PROVIDE PEEPHOLE
CENTERED AT 60" AFF. BOTH DOOR AND BUCK SHALL BE REINFORCED FOR A CLOSER. PROVIDE (5)
5"x4-1/4" KNUCKLE BALL BEARING HINGES WITH MIDDLE HINGE WIRED. PROVIDE STANLEY LOCKSET
45HW7TDEU15S626LHIDHAM, PROXIMITY READER HID PRODUCTS MODEL 921PHRNEK0026Z. COORDINATE
WITH OPEN SYSTEM INTEGRATORS TO CONFIGURE PROXIMITY READER ON VA NETWORK. MOUNT
CONCAVE DOOR STOP ON WALL CENTERED ON LOCK CYLINDER.
PROVIDE NEW 42"W x 85.5"H x DOOR, LH SWING, MASONITE-MARSHFIELD ROTATY WHITE BIRCH, CARAMEL
COLOR AND NEW WELDED METAL BUCK. PAINT BUCK TO MATCH NEARBY DOORS WITH DIRECT TO METAL
SEMI-GLOSS PAINT. INSTALL DARK BROWN KYDEX KICKPLATE, 24"H x 42"W , 0.125" THICK MECHANICALLY
ATTACHED EVERY 4" TO BOTH SIDES OF DOOR. BOTH DOOR AND BUCK SHALL BE REINFORCED FOR A
CLOSER. PROVIDE (5) 5"x4-1/4" KNUCKLE BALL BEARING HINGES. PROVIDE STANLEY LOCKSET
45HW7TDEU15S626LHIDHAM, PROXIMITY READER HID PRODUCTS MODEL 921PHRNEK0026Z. MOUNT
CONCAVE DOOR STOP ON WALL CENTERED ON LOCK CYLINDER.
PROVIDE NEW 36"W x 85.5"H STAINLESS STEEL DOOR WITH 24"x24" LITE WITH MOTION SENSOR, STANLEY
MAGIC FORCE OR EQUAL. LITE TO BE FLUSH ON BOTH SIDES TO AVOID DUST COLLECTION. PROVIDE
REMOVABLE GASKET ON DOOR THAT CAN BE EASILY CLEANED. PROVIDE (5) 5"x4-1/4" KNUCKLE BALL
BEARING HINGES. PROVIDE DOOR CUT OUT FOR OPENING ON INSIDE OF DOOR FOR EMERGENCY
OPERATION. BUFFER AND ANTE ROOM OPENERS TO BE INTERLOCKED SO THAT ONLY ONE DOOR CAN
NORMALLY BE OPEN AT ANY TIME. DOORS SHALL BE ABLE TO BE PUSHED OPEN FOR EMERGENCY
OPERATION.
7/27/2020 10:27:57 PM
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FRAMING DETAIL - TYPE A6 AND A4 WALL
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
ARCHITECTURAL PLAN
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
ARCHITECTURAL FLOOR PLAN
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FRAMING DETAIL - TYPE B WALL
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FRAMING DETAIL - C
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SECTION 1 - AT LOUVER AND CONVECTOR
AutoCAD SHX Text
FLOOR TYPE
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
EPOXY COVE BASE DETAIL
AutoCAD SHX Text
CODED NOTES
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text Stratton VA Medical Center Albany, NY
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text Approved By Signatures date
AutoCAD SHX Text O/M Manager
AutoCAD SHX Text Interior Design
AutoCAD SHX Text Infection Control
AutoCAD SHX Text VA Police
AutoCAD SHX Text Information Systems
AutoCAD SHX Text Fire Safety Officer
AutoCAD SHX Text Environmental Services
AutoCAD SHX Text Care Service Line Supervisor
AutoCAD SHX Text Energy Manager
AutoCAD SHX Text GEMS Coordinator
AutoCAD SHX Text Industrial Hygentist
AutoCAD SHX Text Using Activity Program Manager
AutoCAD SHX Text Approved: FMS Manager date
AutoCAD SHX Text Approved: Project Section Manager date
AutoCAD SHX Text
FAW
AutoCAD SHX Text
AutoCAD SHX Text
ARCHITECTURAL PART PLANS AND DETAILS
AutoCAD SHX Text 528A8-20-816
AutoCAD SHX Text
17 MAR 2020
AutoCAD SHX Text A-001
AutoCAD SHX Text
RENOVATE 11A FOR USP 797 / 800 BACKUP
AutoCAD SHX Text
11-237(A)
EMG
PULL
BOX
PANEL
11-47
USP 800
BUFFER ROOM
USP 797
BUFFER ROOM
ANTE ROOM
REFRIGERATOR
REFRIGERATOR
4' BIOLOGICAL
SAFETY CABINET
4' POSITIVE
PRESSURE HOOD
BOOTIE
SUPPLY
CART
C
A
R
T
B E
N C
H
WORK STATION
TRASH
HAND
PHONE
DRUG STORAGE
ROLLING
CART
GLOVE
STATION
FUTURE
PC
FUTURE
PC
PHONE
PHONE
HAND
STORAGE
HAND
HAND
STORAGE
HAND
STORAGE
CLEAN
SIDE
DIRTY
SIDE
5'-0"
PANEL
11-38
PANEL
11-20-E
HWS
HWR
CHWR
CHWS
STEAM
LPC
PUMP COND
CART
5" STORM CONDUCTOR
FIELD VERIFY EXACT
LOCATION
S T
O R
A G
E
AD
S U
P P
L I E
S
S U
P P
L I E
S
REFRIGERATOR
A1105 A1105a
A1105b
A1105c
A1106b
A1106c
A1106e A1106d
A1106f
A1107 A1108
A1109
Stair
A1106a
A1106g
8'-8" ACT CEILING
NO CEILING
8'-0" ACT CEILING
8'-0" GYPSUM
CEILING
8'-0" GYPSUM
CEILING
8'-0" GYPSUM
CEILING
9'-0" GYPSUM
CEILING
8'-0" ACT CEILING
8'-8" GYPSUM SOFFIT
ACT CEILING: PROVIDE
ARMSTRONG PRELUDE XL 15/16"
GRID WITH 2'X2' ARMSTRONG
1728 FINE FISSURED CEILING
TILES. THIS CEILING IS VA
STANDARD. NO SUBSTITUTIONS.
WORK ROOM CEILING: PROVIDE
ARMSTRONG CLEAN ROOM VL
868 SMOOTH TEXTURE 2'X2'
TILES. PROVIDE ARMSTRONG
PRELUDE PLUS XL ALUMINUM
15/16" GRID. NO SUBSTITUTIONS.
5'-6"
PLAN VIEW OF STAINLESS STEEL COUNTERTOP, SB-6625, WITH 4" BACKSPLASH
ON 3 SIDES, HELIARC WELDED CONSTRUCTION, 16 GAUGE T304 STAINLESS
STEEL WITH #4 POLISH, HAT UNDERSIDE CHANNEL STIFFENERS, WELDS GROUND
AND POLISHED, FLAT PERIMETER EDGE WITH CLEAR SILICONE SEAL BETWEEN
PERIMETER AND WALLS. PROVIDE INTEGRAL SINK AND PENETRATIONS AS
SHOWN. (CONSTRUCTION TYPICAL FOR ALL COUNTERTOPS)
CABINET AND COUNTERTOP INDICATION. BASIS OF DESIGN IS TBJ
INCORPORATED. PROVIDE STAINLESS STEEL GAUGES EQUAL TO OR BETTER
THAN BASIS OF DESIGN. OPEN WALLS AND INSTALL BLOCKING AS NEEDED TO
SUPPORT WALL CABINETS. REPAIR WALLS TO MATCH EXISTING.
8"
7-1/2"
19"
16"
4"
10-1/2"
SB-6625
2'-1"
S-122-18S-181-48
PROVIDE OPENING FOR EYE WASH.
SCALE:
" = 1'-0"
SB-6625 PLAN VIEW
PROVIDE SOFFIT SIZED TO CLOSE OFF TOP OF CABINET.
CONSTRUCT FROM
" GYPSUM AND 3-5/8" METAL STUDS.
SEAL SOFFIT TO WALLS AND CEILING AS DEPICTED ON
WALL TYPE DETAIL FOR AIR TIGHT ROOM. PROVIDE
BLOCKING IN WALL AS NEEDED TO SUPPORT WALL
CABINETS.
8' GYPSUM CEILING
A1106b
11A CORRIDOR
BUFFER ROOM DOOR OPENER. LOCATE DOOR OPENERS FOR
BOTH BUFFER ROOMS IN ANTE ROOM. LOCATE ANTE ROOM
DOOR OPENER IN OFFICE SPACE. ALL OPENERS SHALL BE
TOUCHLESS AND SHALL BE INTERCONNECTED SO THAT ONLY
ONE OF THE THREE DOORS IS OPEN AT ANY TIME.
5'-9 1/2"
P265-3012 P265-3012
PROVIDE 24 GAUGE 304 STAINLESS STEEL WALL
COVERING SHEET WITH #4 POLISH AS SHOWN. SEAL
BETWEEN SS SHEET AND BACKSPLASH AND WALLS
WITH 100% CLEAR SILICONE CAULK WITH CONCAVE
SEAL.
SEAL BETWEEN WALLS AND COUNTERTOP WITH CLEAR
SILICONE CAULK.
GFI OUTLET AT 46" AFF.
TOUCHLESS MOTION SENSOR
WIRED TO CONTROLLERS.
LOCATE CONTROLLERS
ABOVE WORK ROOM CEILING.
CLEAN AND SEAL ALL BACK
BOXES AND WALL
PENETRATIONS.
SOAP DISPENSER
BY OWNER
DIMMING LIGHT SWITCH
SERVING BUFFER ROOM.
1/2" UNDERCUT.
PROVIDE 3 ANALOG
MAGNAHELIC PRESSURE
GAUGES WITH SEPERATE
TUBING SERVING THE
BUFFER ROOMS AND ANTE
ROOM
S245-3016
SCALE:
" = 1'-0"
UNDER CABINET LED DIMMABLE 2'
LONG LIGHT FIXTURES, 20 GA 304
BRUSHED STAINLESS STEEL HOUSING
WITH SMOOTH SOFT WHITE ACRYLIC
LENS, 120V, 3500K, 90 CRI, 0-10V
DIMMING, ELECTRONIC DRIVER, 750
LUMENS PER FOOT, IP63 RATED,
EATON ULC OR EQUAL. SEAL CONDUIT
CONNECTION IN BACK OF FIXTURE.
(TYP 5)
S124-30
S245-3016
S121-30
SB-6025
4'-6"
COORDINATE HEIGHT OF CEILING
WITH CABINETS. SEAL ANY
SPACE BETWEEN TOP OF
CABINETS AND CEILING.
PROVIDE BLOCKING IN WALL AS
NEEDED TO SUPPORT WALL
CABINETS.
UNDER CABINET LED DIMMABLE
LIGHT FIXTURES. PROVIDE
DIMMING SWITCH ON WALL.
PROVIDE 24 GAUGE 304
STAINLESS STEEL WALL
COVERING SHEET WITH #4
POLISH AS SHOWN. SEAL
BETWEEN SS SHEET AND
BACKSPLASH WITH 100%
SILICONE CLEAR SILICONE
CAULK WITH CONCAVE SEAL.
SEAL BETWEEN WALLS AND
COUNTERTOP WITH CLEAR
SILICONE CAULK.
NOTE: THIS ELEVATION SIMILAR
FOR BOTH BUFFER ROOMS AND
ANTE ROOM. COORDINATE WITH
PHARMACY ON LOCATION OF 4
DRAWER AND 8 DRAWER
CABINETS.
2-1/2" METAL WALL FRAMING. SEAL
FRAMING TO WALL IN BED OF CAULK
SUSPENDED GWB METAL
FRAMING SYSTEM
HANGER WIRE
5/8" TYPE X MMR GYPSUM WALL BOARD AS SPECIFIED. PAINT WITH WHITE SANIGLAZE
HIGH BUILD WALL SYSTEM BY SHERWIN WILLIAMS. PROVIDE TWO PRIMER COATS, TWO
BASE COATS, AND TWO FINISH COATS. INSTALL IAW MANUFACTURER'S DIRECTIONS.
METAL J TRIM
7/27/2020 10:30:05 PM
AutoCAD SHX Text Room
AutoCAD SHX Text Toilet
AutoCAD SHX Text
11A REFLECTED CEILING PLAN
AutoCAD SHX Text SECTION 2 - ANTE-ROOM A1105a CASEWORK ELEVATION
AutoCAD SHX Text
SECTION 3 - CASEWORK ELEVATION
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
QUANTITY
AutoCAD SHX Text
UNITS
AutoCAD SHX Text
SHELVES
AutoCAD SHX Text
DRAWERS
AutoCAD SHX Text P265-3012
AutoCAD SHX Text A1106a
AutoCAD SHX Text 30"
AutoCAD SHX Text 18"
AutoCAD SHX Text
AutoCAD SHX Text 12"
AutoCAD SHX Text 35.5"
AutoCAD SHX Text
GLASS DOORS, HANDLES
AutoCAD SHX Text N/A
AutoCAD SHX Text A1106a
AutoCAD SHX Text 18"
AutoCAD SHX Text
AutoCAD SHX Text
BASE CABINET
AutoCAD SHX Text
WALL CABINET
AutoCAD SHX Text
HANDLES
AutoCAD SHX Text N/A
AutoCAD SHX Text
CASEWORK TAG
AutoCAD SHX Text
CABINET SCHEDULE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text A1106a
AutoCAD SHX Text
HEIGHT
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text 22"
AutoCAD SHX Text
WIDTH
AutoCAD SHX Text
- UNIT TAG CORRESPONDS TO BASIS OF DESIGN MODEL. BASIS IS TBJ INC. PROVIDE 304 STAINLESS STEEL UNITS WITH #4 FINISH, MIN. 20 GA PANELS, UNIT TAG CORRESPONDS TO BASIS OF DESIGN MODEL. BASIS IS TBJ INC. PROVIDE 304 STAINLESS STEEL UNITS WITH #4 FINISH, MIN. 20 GA PANELS, 16 GA RAILS, 14 GA CHANNELS AND HINGES, AND 12 GA BOTTOM GUSSETS. COUNTERTOPS SHALL BE MIN. 16 GA 304 STAINLESS STEEL WITH 16 GA CHANNELS. INSTALL IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. ALL WELDS SHALL BE CONTINUOUS AND GROUND SMOOTH. PROVIDE AND WIRE UNDERCABINET LED LIGHTS WHERE INDICATED. - COUNTER TOPS SHALL HAVE ROUNDED CORNERS ON BACKSPLASHES. COUNTER TOPS SHALL HAVE ROUNDED CORNERS ON BACKSPLASHES.
AutoCAD SHX Text
DEPTH
AutoCAD SHX Text
SB-6625
AutoCAD SHX Text
COUNTER TOP
AutoCAD SHX Text A1106a
AutoCAD SHX Text 5.25"
AutoCAD SHX Text 25"
AutoCAD SHX Text
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
4" BACKSPLASH,SINK,FAUCET
AutoCAD SHX Text
AutoCAD SHX Text S245-3016
AutoCAD SHX Text
WALL CABINET
AutoCAD SHX Text 30"
AutoCAD SHX Text A1106a,b,c
AutoCAD SHX Text 42"
AutoCAD SHX Text 16"
AutoCAD SHX Text S122-18
AutoCAD SHX Text N/A
AutoCAD SHX Text
HANDLES
AutoCAD SHX Text 22"
AutoCAD SHX Text
AutoCAD SHX Text
BASE CABINET
AutoCAD SHX Text 35.5"
AutoCAD SHX Text
AutoCAD SHX Text 30"
AutoCAD SHX Text
AutoCAD SHX Text
BASE CABINET
AutoCAD SHX Text N/A
AutoCAD SHX Text S121-30
AutoCAD SHX Text A1106a,b,c
AutoCAD SHX Text
AutoCAD SHX Text 5'-0"
AutoCAD SHX Text
HANDLES
AutoCAD SHX Text S181-48
AutoCAD SHX Text
BASE CABINET
AutoCAD SHX Text
COUNTER TOP
AutoCAD SHX Text 35.5"
AutoCAD SHX Text 48"
AutoCAD SHX Text
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
AutoCAD SHX Text
DOOR, HANDLES, SINK
AutoCAD SHX Text 5'-6"
AutoCAD SHX Text 22"
AutoCAD SHX Text
GLASS DOORS, HANDLES
AutoCAD SHX Text
AutoCAD SHX Text N/A
AutoCAD SHX Text 22"
AutoCAD SHX Text
AutoCAD SHX Text A1106a,b,c
AutoCAD SHX Text 35.5"
AutoCAD SHX Text S124-30
AutoCAD SHX Text
AutoCAD SHX Text
SB-6025
AutoCAD SHX Text 5.25"
AutoCAD SHX Text A1106a,b,c
AutoCAD SHX Text
AutoCAD SHX Text 30"
AutoCAD SHX Text 25"
AutoCAD SHX Text N/A
AutoCAD SHX Text
4" BACKSPLASH
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
GYPSUM CEILING FRAMING DETAIL
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text Stratton VA Medical Center Albany, NY
AutoCAD SHX Text 528A8-20-816
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text Approved By Signatures date
AutoCAD SHX Text O/M Manager
AutoCAD SHX Text Interior Design
AutoCAD SHX Text Infection Control
AutoCAD SHX Text VA Police
AutoCAD SHX Text Information Systems
AutoCAD SHX Text Fire Safety Officer
AutoCAD SHX Text Environmental Services
AutoCAD SHX Text Care Service Line Supervisor
AutoCAD SHX Text Energy Manager
AutoCAD SHX Text GEMS Coordinator
AutoCAD SHX Text Industrial Hygentist
AutoCAD SHX Text Using Activity Program Manager
AutoCAD SHX Text Approved: FMS Manager date
AutoCAD SHX Text Approved: Project Section Manager date
AutoCAD SHX Text
17 MARCH 2020
AutoCAD SHX Text
FAW
AutoCAD SHX Text
AutoCAD SHX Text
REFLECTED CEILING PLAN AND SECTIONS
AutoCAD SHX Text A-002
AutoCAD SHX Text
RENOVATE 11A FOR USP 797 / 800 BACKUP
AutoCAD SHX Text
EMG
PULL
BOX
PANEL
11-47
REFRIGERATOR
REFRIGERATOR
4' BIOLOGICAL
SAFETY CABINET
4' POSITIVE
PRESSURE HOOD
PHONE
5'-0"
PANEL
11-38
PANEL
11-20-E
HWS
HWR
CHWR
CHWS
STEAM
LPC
PUMP COND
5" STORM CONDUCTOR
FIELD VERIFY EXACT
LOCATION
AD
REFRIGERATOR
A1105 A1105a
A1105b
A1105c
A1106b
A1106c
A1106e A1106d
A1106f
A1107 A1108
A1109
A1104
A1106a
A1106g
A1110
1/2" DHWR
1/2" DHW
1/2" DCW
A1105
HWS
HWR
CHWR
CHWS
STEAM
LPC
PUMP COND
2'-6"
3'-0"
PANEL
11-237(A)
EMG
PULL
BOX
PANEL
11-47
PANEL
11-38
PANEL
11-20-E
A1105a A1105b A1106a A1106b A1106c
A1106e A1106d
A1106f
A1107
A1108
A1109
A1104
A1106g
Stair
A1110
REMOVE SPRINKLER HEADS AND ASSOCIATED DISTRIBUTION PIPING. PROVIDE PERMANENT CAP AT MAIN.
REMOVE SUPPORTS AND APPURTENANCES.
RELOCATE EXISTING SPRINKLER HEADS AND EXTEND ARM OVERS TO PROVIDE CORRIDOR PROTECTION DURING
CONSTRUCTION. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS. EXISTING SPRINKLER HEADS IN ROOMS
AND CORRIDORS TO REMAIN OPERATIONAL DURING CONSTRUCTION. REMOVE HEADS, PIPING AS NEEDED, AND
SUPPORTS WHEN NEW HEADS ARE INSTALLED.
SHUT OFF VALVE FOR SPRINKLERS IN STEM IS LOCATED IN STAIRWELL 4. CONTRACTOR SHALL COORDINATE WITH
VA PLUMBING SHOP FOR SHUTTING AND DRAINING SYSTEM AS WELL AS RE-FILLING.
REMOVE LAVATORY, FAUCET, AND DOMESTIC AND SANITARY PIPING AND VENTS. DOMESTIC PIPING TO BE
EXTENDED TO NEW SINK. REMOVE SANITARY PIPING BACK TO MAINS ABOVE 10A CEILING. PROVIDE NO-HUB CAPS
ON SANITARY AT MAIN. REPAIR HOLES IN SLAB TO MATCH EXISTING CONSTRUCTION.
REMOVE DOMESTIC AND SANITARY PIPING AND VENTS. REMOVE PIPING BACK TO MAINS ABOVE 10A CEILING.
PROVIDE SOLDERED CAPS ON DOMESTIC AND NO-HUB CAPS ON SANITARY. REPAIR HOLES IN SLAB TO MATCH
EXISTING CONSTRUCTION.
REMOVE 2" VENT. RE-CONNECT TO EXISTING 4" VTR. LOCATE VENT IN BEAM SPACE.
EXISTING 5" ROOF DRAIN AND CONDUCTOR TO REMAIN. CONTRACTOR AND COR TO DETERMINE STATE OF
EXISTING PIPING. REMOVE EXISTING INSULATION. RE-INSULATE WITH 1-1/2" THICK FLEXIBLE ELASTOMERIC PIPE
INSULATION. INSULATE ROOF BOWL WITH 1-1/2" THICK ELASTOMERIC INSULATION GLUED TO BOWL.
FIELD VERIFY TYPE AND LOCATION OF PIPE. PIPE IS ASSUMED TO BE DCW. REMOVE PIPE IF NOT IN USE.
RE-INSULATE IF PIPE IS BEING USED.
EXISTING PLUMBING VENT TO REMAIN.
EXISTING LAVATORY TO REMAIN.
EXISTING SANITARY VENT TO VTR. FIELD VERIFY EXACT LOCATION.
PROVIDE 2" SANITARY DRAIN SERVING SINK. CORE DRILL SLAB. INSTALL ABOVE 10A CEILING. COORDINATE WITH
EXISTING DUCTS AND PIPING ABOVE 10A CEILING. CONNECT TO EXISTING 4" SANITARY RISER AT SANITARY STACK
S43. FIELD VERIFY EXACT LOCATION. WORK ABOVE 10A CEILING SHALL BE COORDINATED WITH VA COR AND
PERFORMED OFF HOURS.
PROVIDE 2" PLUMBING VENT TO SERVE SINK. CONNECT TO EXITING 4" VTR AT S43. FIELD VERIFY EXACT LOCATION.
LOCATE VENT IMMEDIATELY BELOW BEAMS.
SINK PROVIDED BY CABINET MANUFACTURER. CONTRACTOR SHALL PROVIDE DOMESTIC AND SANITARY PIPING TO
SERVE SINK. PROVIDE
" DCW AND
" DHW. PROVIDE
" DHWR CONNECTED BELOW SINK WITH SHUT OFF, BALANCE,
ANE CHECK VALVES. CONNECT TO EXISTING DHW RISER. REFER TO DETAIL. PROVIDE 1-1/2" SANITARY ENLARGING
TO 2" THROUGH SLAB. PROVIDE 2" VENT.
EXTEND EXISTING DCW/DHW RISERS TO SERVE NEW SINK. PROVIDE BRONZE BALL VALVE SHUT OFFS ABOVE
A1105C TO SERVE PIPES. SEAL EXISTING SLAB PENETRATIONS TO MAINTAIN FIRE BARRIER. PROVIDE SHUT OFF
VALVES AND TAPS TO SERVE PIPE CLEANING AND DISINFECTION. PROVIDE ANSI Z358.1 DECK MOUNTED BRONZE
SWING DOWN HALO EYE/FACE WASH AND ASSE 1071 MIXING VALVE LOCATED UNDER SINK WITH SHUT OFFS AND
DRAIN VALVES TO SERVE EYE/FACE WASH. SET FOR 83°F. PROVIDE BRONZE DECK MOUNTED BATTERY OPERATED
SENSOR…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .