This document is a combined synopsis/solicitation for commercial services issued by the Department of Veterans Affairs (VA) Veterans Health Administration Veterans Integrated Service Network 1. The VA is seeking services for tri-annual electrical testing and maintenance of the electrical power distribution system at the VA Connecticut Healthcare System's West Haven and Newington campuses. The required services include infrared scanning, system function testing, and participation in a 4-hour power outage test. The contract is a SDVOSB set-aside, with a period of performance of 30 days from award. Interested vendors must demonstrate experience with electrical testing and maintenance in healthcare facilities, possess required certifications, and submit a proposal package detailing their qualifications, schedule, cost, and quality control plan. Responses are due by August 16, 2024.

View the file

Other files

File Type Posted
P01_Arc Flash Hazard Analysis Newington.pdf PDF
P01_Arc Flash Evaluation Report Newington.pdf PDF
Item List.pdf PDF
P01_Arc Flash Hazard Analysis West Haven.pdf PDF
P01_Drawings Newington.pdf PDF
36C24124Q0631_2.docx DOCX document
P01_Drawings West Haven.pdf PDF
36C24124Q0631_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

6.5. Arc Flash Evaluation Report

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

MV-T-LCB-B-SEC (Rm. New Elec.) MV-FU-01-SS1B-B 0.480 55.12 20.5 HOA 33 100 70 AIR 32 201 18 146.58 (*N3) (*N9) (*S3)

MV-T-LCB-A-SEC (Rm. New Elec.) MV-FU-01-SS1B-A 0.480 55.12 20.5 HOA 33 100 70 AIR 32 201 18 146.58 (*N3) (*N9) (*S3)

MV-TR-N-USS-1-B-SEC (Rm. 19 202) MV-52-B1-50/51 0.480 61.18 25.11 HOA 26 110 95 AIR 32 198 18 141.94 (*N5) (*S0)

MV-TR-N-USS-1-A-SEC (Rm. 19 202) MV-52-A1-50/51 0.480 59.44 24.75 HOA 26 110 95 AIR 32 196 18 138.87 (*N5) (*S1)

MV-TR-02-SS2B-6A-SEC (Rm. G-136) MV-FU-02-SS2A 0.480 33.55 16.98 HOA 28 84 70 AIR 32 173 18 108.54 (*N5) (*N9) (*S2)

MV-TR-02-SS2B-6B-SEC (Rm. G-136) MV-FU-02-SS2A 0.480 30.15 15.57 HOA 28 84 70 AIR 32 171 18 105.59 (*N5) (*N9) (*S2)

MV-T-B1-LC7-MSB4-SEC (Ext. Bld. 1

PET)

MV-T-B1-LC7-MSB4-

BAY

0.480 28.19 14.7 HOA 30 60 30 AIR 32 169 18 103.69 (*N9) (*N21a) (*S2)

01-LC1B-A (Rm. New Elec.) (01-LC1B-

AM-MB LineSide)

MV-FU-01-SS1B-A 0.480 55.12 32.93 VCB 22 22 20 PNL 25 292 18 102.79 (*N9) (*S3)

01-LC1B-B (Rm. New Elec.) (01-LC1B-

BM-MB LineSide)

MV-FU-01-SS1B-B 0.480 55.12 32.93 VCB 22 22 20 PNL 25 291 18 102.43 (*N9) (*S3)

MV-TR-01-SSB1-4B-SEC (Rm. SG110)

MV-FU-SW-01-SSB1-

4B

0.480 46.72 21.58 HOA 31 60 55 AIR 32 154 18 86.08 (*N9) (*S2)

MV-TR-01-SSB1-2B-SEC (Rm. SG110)

MV-FU-SW-01-SSB1-

2B

0.208 69.13 12.25 HOA 22 66 70 AIR 32 152 18 83.61 (*N9) (*N21a) (*S2)

MV-TR-01-SSB1-2A-SEC (Rm. SG110)

MV-FU-SW-01-SSB1-

2A

0.208 67.37 12.14 HOA 22 66 70 AIR 32 151 18 83.07 (*N9) (*S2)

01-TR-FDR-BKR-#1-SSB1-2B-SEC (Rm.

SG110)

39-EM-SWGR-1 0.208 67.41 12.14 HOA 72 90 54 AIR 32 151 18 82.78 (*N9) (*S4)

01-TR-FDR-BKR-#4-SSB1-2A-SEC (Rm.

SG110)

39-EM-SWGR-4 0.208 65 11.99 HOA 72 90 64 AIR 32 151 18 82.16 (*N9) (*S4)

MV-TR-01-SSB1-4A-SEC (Rm. SG110)

MV-FU-SW-01-SSB1-

4A

0.480 25.05 13.26 HOA 22 66 70 AIR 32 147 18 77.87 (*N9) (*S2)

MV-TR-02-LC2B-SEC (Rm. G145A) MV-FU-02-SS6B 0.480 21.18 11.39 HOA 25 80 70 AIR 32 145 18 76.10 (*N9) (*S2)

MV-TR-02-LC2A-SEC (Rm. G145A) MV-FU-02-SS6A 0.480 21.99 11.79 HOA 25 80 70 AIR 32 144 18 75.42 (*N9) (*S2)

02-LC2B (Rm. G145A) (02-LC2B-MB

LineSide)

MV-FU-02-SS6B 0.480 21.16 16.17 VCB 20 22 25 PNL 25 231 18 70.71 (*N9) (*S2)

02-LC2A (Rm. G145A) (02-LC2A-MB

LineSide)

MV-FU-02-SS6A 0.480 21.98 16.75 VCB 20 22 25 PNL 25 229 18 70.04 (*N9) (*S2)

MV-T-PET-MDP-SEC (Ext. Bld. 1 PET) MV-T-PET-MDP-BAY 0.480 15.32 8.37 HOA 30 60 30 AIR 32 125 18 56.63 (*N9) (*N21a) (*S2)

01-FDR-BKR-#1-SSB1-2B (Rm. SG110) 01-SSB1-2B-MB 0.208 67.45 17.6 VCB 42 90 54 PNL 25 200 18 56.15 (*N5) (*N9) (*S4)

16-LC3-B (Rm. 102) (16-LC3-B-MB

LineSide)

MV-FU-SW-LC3-B 0.208 24.78 11.04 VCB 18 25 25 PNL 25 188 18 51.16 (*N9) (*S2)

6.5-1

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

16-LC3-D (Rm. 102) (16-LC3-D-MB

LineSide)

MV-FU-SW-LC3-D 0.208 28.04 12.14 VCB 18 25 25 PNL 25 188 18 51.00 (*N9) (*S2)

MV-T-B16-TLC3-B-SEC (Rm. 102) MV-FU-SW-LC3-B 0.208 25.35 6.61 HOA 22 66 70 AIR 32 112 18 45.51 (*N9) (*S2)

02-TR-NLDP-1A-SEC (Rm. G136) 02-SSB2-6B-1 0.208 24.39 6.39 HOA 60 76 50 AIR 32 109 18 43.14 (*N9) (*S2)

01-LC7-MSB4 (Rm. SG109A) (01-LC7-

MSB4-MB LineSide)

MV-T-B1-LC7-MSB4-

BAY

0.480 26.9 17.61 VCB 30 52 8 PNL 25 169 18 42.25 (*N3) (*N21a) (*S0)

01-FDR-BKR-#4-SSB1-2A (Rm. SG110)

01-FDR-BKR-#4-SSB1-

2A-CB

0.208 65.77 17.53 VCB 42 40 38 PNL 25 234 18 40.28 (*N9) (*N21a) (*S2)

01-SPD-MCB (Ext. Bld. 1) (01-SPD-MCB-

CB LineSide) MaxTripTime @2.0s 0.480 14.36 11.07 VCB 30 45 8 PNL 25 161 18 39.78 (*N2) (*N9) (*S0)

01-PET-MDP (Rm. SG123) (01-PET-MDP-

MB LineSide) MV-T-PET-MDP-BAY 0.480 14.53 11.2 VCB 30 52 8 PNL 25 157 18 38.36 (*N9) (*N21a) (*S2)

11-MS-1-11 (Rm. B06A) (11-MS-1-11-MB

LineSide) MaxTripTime @2.0s 0.208 22.39 10.15 VCB 26 74 13 PNL 25 156 18 37.84 (*N2) (*N9) (*S0)

16-LC3-PORT-GEN (Rm. 102) MV-FU-SW-LC3-D 0.208 24.12 10.8 VCB 38 90 32 PNL 25 152 18 36.24 (*N5) (*N9) (*S4)

38-EM-SWGR (Rm. 101) 38-EM SWGR-GB1 0.480 21.02 16.07 VCB 12 14 10 PNL 25 146 18 33.85 (*N9) (*S4)

38-MTS-GB2-16-LD (Rm. 102) 38-GEN-1-MB 0.480 20.97 16.03 VCB 12 14 10 PNL 25 145 18 33.84 (*N9) (*S4)

38-GEN-1-LD (Rm. 102) MaxTripTime @2.0s 0.480 20.96 16.02 VCB 12 14 10 PNL 25 145 18 33.84 (*N2) (*N9) (*S4)

38-GEN-2-LD (Rm. 102) MaxTripTime @2.0s 0.480 20.94 16.01 VCB 12 14 10 PNL 25 145 18 33.84 (*N2) (*N9) (*S4)

02-NLDP-1A (Rm. G136) 02-NLDP-1A-MB 0.208 23.5 9.11 VCB 36 90 20 PNL 25 145 18 33.61 (*N3) (*N9) (*S3)

02-NLDP-1 (Rm. G136) 02-NLDP-1A-MB 0.208 23.56 9.13 VCB 36 90 20 PNL 25 145 18 33.49 (*N3) (*N9) (*S2)

01-FDR-BKR-#2-SSB1-4A/4B (Rm.

SG110)

01-SSB1-4B-MB 0.480 47.29 30.41 VCB 42 90 54 PNL 25 143 18 32.84 (*S2)

02-LC2D (Rm. G145B) 02-LC2D-MB 0.208 16.01 7.43 VCB 12 14 10 PNL 25 141 18 32.11 (*N9) (*S2)

02-LC2C (Rm. G145A) 02-LC2C-MB 0.208 17.87 8.27 VCB 12 14 10 PNL 25 140 18 31.90 (*N9) (*S2)

MV-TR-34-SEC (Ext. Bld. 34) MV-FU-TR-34 0.480 8.15 4.47 HOA 30 48 10 AIR 32 90 18 29.82 (*N9) (*N21a) (*S2)

02-TR-LC2D-SEC (Rm. G145A) 02-LC2B-1 0.208 16.56 4.49 HOA 47 65 38 AIR 32 88 18 28.03 (*N9) (*S2)

02-TR-LC2C-SEC (Rm. G145A) 02-LC2A-2 0.208 18.39 4.96 HOA 47 65 38 AIR 32 87 18 27.84 (*N9) (*S2)

35A-MDP (Ext. Bld. 35A) 35A-MDP-MB 0.208 16.88 7.83 VCB 36 48 48 PNL 25 129 18 27.77 (*N9) (*S4)

01-TR-NL-MDP-SEC (Rm. G291B) 01-LC1B-EQ-DP-3 0.208 15.02 4.09 HOA 44 72 36 AIR 32 87 18 27.33 (*N9) (*S2)

01-E-P-1-E2-BP (Rm. 1122) 01-SSB1-2A-4 0.208 12.92 5.98 VCB 12 20 6 PNL 25 127 18 27.10 (*N9) (*N21a) (*S2)

35-MDP (Rm. B06) 35-MDP-MB 0.208 15.41 7.16 VCB 36 40 30 PNL 25 126 18 26.94 (*N9) (*S0)

01-EA-NP-SG-EA-BP (Rm. SG101) 01-SSB1-2A-2 0.208 13.11 6.07 VCB 12 14 10 PNL 25 125 18 26.60 (*N9) (*N21a) (*S2)

01-EA-A-BP (Rm. SG101) 01-SSB1-2A-2 0.208 13 6.02 VCB 12 14 10 PNL 25 124 18 26.37 (*N9) (*N21a) (*S2)

6.5-2

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

38-MTS-GB2-17-LD (Rm. 102) 38-GEN-2-MB 0.480 20.95 16.01 VCB 30 72 20 PNL 25 123 18 25.96 (*N9) (*S4)

01-EA-FDS-BP (Rm. SG021) 01-SSB1-2A-2 0.208 14.22 5.69 VCB 12 14 10 PNL 25 121 18 25.31 (*N3) (*N9) (*N21a)

(*S2)

01-E-P3E3-1-BP (Rm. 3129E) 01-SSB1-2A-4 0.208 12.15 5.61 VCB 12 14 10 PNL 25 121 18 25.30 (*N9) (*N21a) (*S2)

01-E-L-4-E-BP (Rm. 4129) 01-SSB1-2A-4 0.208 11.8 5.44 VCB 12 14 10 PNL 25 119 18 24.48 (*N9) (*N21a) (*S2)

02-ESS-1 (Rm. G145B) 02-ESS-1-MB 0.480 14.65 9.9 VCB 12 14 10 PNL 25 117 18 23.75 (*N3) (*N9) (*S4)

MV-T-B16-TLC3-D-SEC (Rm. 102) MV-FU-SW-LC3-D 0.208 28.61 9.27 VOA 22 66 70 AIR 32 117 18 23.74 (*N9) (*S2)

02-ESS-2 (Rm. G145B) 02-ESS-TIE 0.480 14.63 9.88 VCB 12 14 10 PNL 25 117 18 23.73 (*N3) (*N9) (*S4)

01-SSB1-4B (Rm. SG110) 01-SSB1-4B-MB 0.480 46.65 46.65 VCB 30 30 30 SWG 104 160 36 23.56 (*N_gap) (*N21b)

(*S0)

01-EA-P-G-E-1-BP (Rm. G169) 01-SSB1-2A-2 0.208 11.5 5.3 VCB 12 14 10 PNL 25 114 18 23.03 (*N9) (*N21a) (*S2)

01-E-NL-6-E-B1-A-BP (Rm. 6120E) 01-SSB1-2A-4 0.208 11.14 5.12 VCB 12 14 10 PNL 25 114 18 22.98 (*N9) (*N21a) (*S2)

01-NL-MDP (Rm. G291B) 01-NL-MDP-MB 0.208 13.71 6.36 VCB 32 68 12 PNL 25 113 18 22.57 (*N9) (*S2)

01-E-L-7-E-BP (Rm. 7129) 01-SSB1-2A-4 0.208 10.88 5 VCB 12 14 10 PNL 25 112 18 22.40 (*N9) (*N21a) (*S2)

02-N-P-G-N-BP (Rm. 1324) 02-LC2C-2 0.208 12.17 5.62 VCB 12 14 10 PNL 25 112 18 22.37 (*N9) (*S4)

01-E-DP-9-E-BP (Rm. 7129) 01-SSB1-2A-4 0.208 10.81 4.96 VCB 12 14 10 PNL 25 112 18 22.23 (*N9) (*N21a) (*S2)

MV-N-SWGR-1-A (Rm. 19 300) (MV-52-

L1-751-51 LineSide) UTIL-FDR-626-VISTA 13.800 16.88 15.27 HCB 38 34 30 SWG 152 209 36 22.16 (*N5) (*S2)

01-EA-P-SG-E-BP (Rm. SG101) 01-SSB1-2A-2 0.208 12.9 5.97 VCB 12 40 8 PNL 25 111 18 21.90 (*N9) (*N21a) (*S2)

01-E-8-TERM-BD (Rm. 8124) 01-SSB1-2A-4 0.208 10.61 4.87 VCB 12 14 10 PNL 25 110 18 21.79 (*N9) (*N21a) (*S2)

02-N-PAC-35-2-BP (Rm. 2247) 02-LC2C-2 0.208 11.74 5.42 VCB 12 14 10 PNL 25 110 18 21.61 (*N9) (*S4)

02-N-P-2-N-BP (Rm. 3234) 02-LC2C-2 0.208 11.47 5.28 VCB 12 14 10 PNL 25 108 18 21.12 (*N9) (*S4)

MV-N-SWGR-1-B (Rm. 19 300) MV-52-L1-751-51 13.800 16.21 14.65 HCB 38 34 30 SWG 152 203 36 21.10 (*S2)

01-EA-DP-1-3-E-BP (Rm. 3129) 01-SSB1-2A-2 0.208 10.57 4.85 VCB 12 14 10 PNL 25 108 18 20.99 (*N9) (*N21a) (*S2)

01-NA-P-SG-NA-2-BP (Rm. SG184) 01-SSB1-2B-4 0.208 10.05 4.59 VCB 12 14 10 PNL 25 108 18 20.89 (*N9) (*N21a) (*S2)

02-N-P-3-N-1-BP (Rm. 4231) 02-LC2C-2 0.208 11.26 5.18 VCB 12 14 10 PNL 25 107 18 20.75 (*N9) (*S4)

02-N-P-3-N-BP (Rm. 4231) 02-LC2C-2 0.208 11.19 5.15 VCB 12 14 10 PNL 25 107 18 20.61 (*N9) (*S4)

01-DP21 (Rm. SG184) 01-SSB1-2B-7 0.208 13.88 6.44 VCB 41 88 12 PNL 25 106 18 20.49 (*N9) (*N21a) (*S2)

02-N-PAC-41-BP (Rm. 4231) 02-LC2C-2 0.208 11.11 5.11 VCB 12 14 10 PNL 25 106 18 20.47 (*N9) (*S4)

6.5-3

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-NA-P-SG-NA-BP (Rm. S21G) 01-SSB1-2B-4 0.208 9.71 4.43 VCB 12 14 10 PNL 25 105 18 20.12 (*N9) (*N21a) (*S2)

11A-SW-UTIL-FDS (Ext. Bld. 11A) (11A-

SW-UTIL-FDS-FU LineSide) MaxTripTime @2.0s 0.208 12.02 5.55 VCB 25 58 8 PNL 25 105 18 19.95 (*N2) (*N9) (*S0)

02-N-L-1-N-BP (Rm. 2247) 02-LC2C-2 0.208 11.88 5.48 VCB 10 27 7 PNL 25 104 18 19.88 (*N9) (*S4)

19-GEN-LD (Ext. Bld. 19) (19-GEN-MB

LineSide) MaxTripTime @2.0s 0.480 26.69 19.95 VCB 32 57 14 PNL 25 104 18 19.87 (*N2) (*N9) (*S3)

01-NA-L-SG-NA-BP (Rm. S21G) 01-SSB1-2B-4 0.208 9.59 4.37 VCB 12 14 10 PNL 25 104 18 19.84 (*N9) (*N21a) (*S2)

02-N-P-4-N-BP (Rm. 5141) 02-LC2C-2 0.208 10.75 4.93 VCB 12 14 10 PNL 25 104 18 19.81 (*N9) (*S4)

02-N-NL-4-1-B2-1-BP (Rm. 5141) 02-LC2C-2 0.208 10.68 4.9 VCB 12 14 10 PNL 25 104 18 19.68 (*N9) (*S4)

01-N-FDS-BP (Rm. SG021) 01-SSB1-2A-1 0.208 9.65 4.4 VCB 12 14 10 PNL 25 104 18 19.64 (*N9) (*N21a) (*S2)

01-E-5150-BP (Rm. 5129) 01-SSB1-2A-4 0.208 11.46 5.28 VCB 10 42 8 PNL 25 103 18 19.61 (*N9) (*N21a) (*S2)

19-1PGH1 (Rm. 19 202) 19-1PGH1-MB 0.480 18.54 14.25 VCB 38 40 35 PNL 25 102 18 19.30 (*N9) (*S4)

02-N-L-5-N-BP (Rm. 6222) 02-LC2C-2 0.208 10.45 4.79 VCB 12 14 10 PNL 25 102 18 19.27 (*N9) (*S4)

01-NA-NL-B1-H1-B1-BP (Rm. SG184) 01-SSB1-2B-4 0.208 9.31 4.23 VCB 12 14 10 PNL 25 102 18 19.18 (*N9) (*N21a) (*S2)

02-N-P-5-NA-BP (Rm. 6223) 02-LC2C-2 0.208 10.38 4.75 VCB 12 14 10 PNL 25 102 18 19.14 (*N9) (*S4)

01-W-P-SG-W2-BP (Ext. Rm. SG171) 01-SSB1-2B-2 0.208 9.28 4.22 VCB 12 14 10 PNL 25 102 18 19.11 (*N9) (*N21a) (*S2)

02-N-P-6-N-BP (Rm. 7231) 02-LC2C-2 0.208 10.17 4.65 VCB 12 14 10 PNL 25 101 18 18.74 (*N9) (*S4)

02-P-SG-E1-BP (Rm. G145) 02-LC2D-2 0.208 12.38 5.72 VCB 12 14 10 PNL 25 100 18 18.65 (*N9) (*N21b) (*S4)

01-EA-L-1-E-BP (Rm. 1122) 01-SSB1-2A-2 0.208 11.18 5.14 VCB 10 42 8 PNL 25 100 18 18.46 (*N9) (*N21a) (*S2)

02-N-P-7-N-BP (Rm. 8152A) 02-LC2C-2 0.208 10 4.57 VCB 12 14 10 PNL 25 99 18 18.44 (*N9) (*S4)

05-P-CBD-2 (Corr. CBC4) 16-LC3-B-1 0.208 11.23 5.17 VCB 30 78 8 PNL 25 99 18 18.36 (*N9) (*S4)

02-N-L-7-N-BP (Rm. 8152A) 02-LC2C-2 0.208 9.96 4.55 VCB 12 14 10 PNL 25 99 18 18.36 (*N9) (*S4)

02-N-L-BP (Rm. 8152A) 02-LC2C-2 0.208 9.86 4.5 VCB 12 14 10 PNL 25 99 18 18.17 (*N9) (*S4)

02-NA-P-8-N-BP (9th Flr. Penthouse) 02-LC2C-1 0.208 11.74 5.41 VCB 12 14 10 PNL 25 98 18 18.14 (*N9) (*N21a) (*S4)

15-SOLAR-AC-FDS-2 (Rm. 102) 16-LC3-B-MB 0.208 8.68 3.93 VCB 12 20 8 PNL 25 98 18 18.11 (*N9) (*S2)

02-NA-MCC-BP (9th Flr. Penthouse) 02-LC2C-1 0.208 11.69 5.39 VCB 12 14 10 PNL 25 98 18 18.03 (*N9) (*N21a) (*S4)

01-EA-01-L-2-E-BP (Rm. 2130) 01-SSB1-2A-2 0.208 10.88 4.99 VCB 10 42 8 PNL 25 98 18 17.90 (*N9) (*N21a) (*S2)

01-W-P1-WA-1-BP (Rm. 1161) 01-SSB1-2B-2 0.208 8.73 3.95 VCB 12 14 10 PNL 25 97 18 17.83 (*N9) (*N21a) (*S2)

6.5-4

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

34-DISC (Ext. Bld. 34) MV-FU-TR-34 0.480 8.11 5.39 VCB 23 46 8 PNL 25 98 18 17.82 (*N3) (*N5) (*N21a)

(*S0)

36-MDP (Basement) (36-MDP-MB

LineSide)

35-MDP-13 0.208 10.6 4.86 VCB 20 78 6 PNL 25 97 18 17.79 (*N9) (*S0)

01-NA-L-1-NA-1-BP (Rm. 1200) 01-SSB1-2B-4 0.208 8.7 3.93 VCB 12 14 10 PNL 25 97 18 17.77 (*N9) (*N21a) (*S2)

01-W-L-1-W-1-BP (Rm. 1161) 01-SSB1-2B-2 0.208 8.69 3.93 VCB 12 14 10 PNL 25 97 18 17.75 (*N9) (*N21a) (*S2)

01-NA-P-1-NA-1-BP (Rm. 1200) 01-SSB1-2B-4 0.208 8.67 3.92 VCB 12 14 10 PNL 25 97 18 17.70 (*N9) (*N21a) (*S2)

02-NA-AHU-BP (10th Flr. Penthouse) 02-LC2C-1 0.208 11.44 5.27 VCB 12 14 10 PNL 25 97 18 17.67 (*N9) (*N21a) (*S4)

02-EA-P-SG-E3-BP (Ext. Rm. G145) 02-LC2D-1 0.208 11.9 5.49 VCB 12 14 10 PNL 25 97 18 17.66 (*N9) (*N21a)

(*N21b) (*S4)

01-WA-P-SG-W-BP (Ext. Rm. SG171) 01-SSB1-2B-6 0.208 8.62 3.89 VCB 12 14 10 PNL 25 97 18 17.56 (*N9) (*N21a) (*S2)

34-MTS-LD (Ext. Bld. 34) MV-FU-TR-34 0.480 7.61 5.04 VCB 20 60 14 PNL 25 96 18 17.42 (*N3) (*N5) (*N9)

(*N21a) (*S2)

MV-TR-24-SEC (Ext. Bld. 24) MV-FU-SW-24 0.208 9.41 2.57 HOA 20 33 30 AIR 32 69 18 17.39 (*N9) (*S2)

01-W-NL-2-F2-B1-BP (Rm. 2178) 01-SSB1-2B-2 0.208 8.5 3.84 VCB 12 14 10 PNL 25 96 18 17.32 (*N9) (*N21a) (*S2)

01-NA-P2NA-BP (Rm. 2213A) 01-SSB1-2B-4 0.208 8.48 3.83 VCB 12 14 10 PNL 25 95 18 17.26 (*N9) (*N21a) (*S2)

01-KIT-PG-NA-BP (Rm. G253) 01-SSB1-2B-1 0.208 8.36 3.77 VCB 12 14 10 PNL 25 94 18 16.97 (*N9) (*N21a) (*S2)

01-W-NL-3-F1-B1-BP (Rm. 3178) 01-SSB1-2B-2 0.208 8.35 3.76 VCB 12 14 10 PNL 25 94 18 16.97 (*N9) (*N21a) (*S2)

39-GEN-2-LD (Rm. 102) (39-GEN-2-MB

LineSide)

39-GEN-2-MB 0.480 53.82 32.55 VCB 25 40 14 PNL 25 94 18 16.93 (*N9) (*S2)

02-EA-TP-BP (Ext. Rm. G145) 02-LC2D-1 0.208 11.19 5.15 VCB 12 14 10 PNL 25 94 18 16.80 (*N9) (*N20b)

(*N21a) (*S4)

01-WA-LP1-BP (Rm. G212) 01-SSB1-2B-6 0.208 8.21 3.69 VCB 12 14 10 PNL 25 93 18 16.61 (*N9) (*N21a) (*S2)

01-N-CS-42-BP (Rm. SG184) 01-SSB1-2A-1 0.208 8.32 3.75 VCB 12 14 10 PNL 25 93 18 16.57 (*N9) (*N21a) (*S2)

01-W-L-4-W-BP (Rm. 4177) 01-SSB1-2B-2 0.208 8.18 3.68 VCB 12 14 10 PNL 25 93 18 16.56 (*N9) (*N21a) (*S2)

02-EB-04/05-BP (Ext. Rm. G140) 02-LC2D-4 0.208 10.65 4.89 VCB 12 14 10 PNL 25 93 18 16.49 (*N9) (*N20b) (*S4)

02-WA-P-SW-G3B-BP (Ext. Rm. G101B) 02-LC2C-4 0.208 9.35 4.25 VCB 12 14 10 PNL 25 92 18 16.41 (*N9) (*S4)

34-NH-34-DP1 (Rm. 156A) (34-NH-34-

DP1-MB LineSide) MV-FU-TR-34 0.480 7.37 5.56 VCB 44 74 13 PNL 25 92 18 16.37 (*N5) (*N21a) (*S0)

6.5-5

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-WA-L-1-W-BP (Rm. 1161) 01-SSB1-2B-6 0.208 8.09 3.64 VCB 12 14 10 PNL 25 92 18 16.36 (*N9) (*N21a) (*S2)

02-EA-Z-6-BP (Ext. Rm. G140) 02-LC2D-1 0.208 10.82 4.97 VCB 12 14 10 PNL 25 92 18 16.34 (*N9) (*N21a) (*S4)

01-W-EP5-BP (Rm. 5170) 01-SSB1-2B-2 0.208 8.06 3.62 VCB 12 20 6 PNL 25 92 18 16.30 (*N9) (*N21a) (*S2)

01-WA-P-1-W-1-BP (Rm. 1161) 01-SSB1-2B-6 0.208 8.05 3.62 VCB 12 14 10 PNL 25 92 18 16.27 (*N9) (*N21a) (*S2)

02-EA-P-SG-E5-BP (Ext. Rm. G140) 02-LC2D-1 0.208 10.71 4.91 VCB 12 14 10 PNL 25 92 18 16.20 (*N9) (*N21a) (*S4)

01-W-L-G-W-1A-BP (Rm. G212) 01-SSB1-2B-2 0.208 8.93 4.04 VCB 12 24 6 PNL 25 92 18 16.13 (*N9) (*N21a) (*S2)

01-W-EP5A-BP (Rm. 5170) 01-SSB1-2B-2 0.208 7.98 3.58 VCB 12 14 10 PNL 25 91 18 16.11 (*N9) (*N21a) (*S2)

01-DP-PAD (Corr. SG165) 01-DP-PAD-MB 0.208 10.51 4.82 VCB 12 40 18 PNL 25 91 18 16.05 (*N9) (*N21b) (*S2)

01-WA-PAC-7-BP (Rm. 2178) 01-SSB1-2B-6 0.208 7.92 3.55 VCB 12 14 10 PNL 25 91 18 15.96 (*N9) (*N21a) (*S2)

02-E-L-6-E-BP (Rm. 7120) 02-LC2D-2 0.208 9.35 3.66 VCB 12 14 10 PNL 25 91 18 15.94 (*N3) (*N9) (*S2)

01-SPD-GEN-LD (Ext. Bld. 1) (01-SPD-

GEN-MB LineSide) MaxTripTime @2.0s 0.480 10.01 7.65 VCB 12 14 10 PNL 25 91 18 15.91 (*N2) (*N9) (*S0)

01-P-SG-NA-1A (Rm. S21G) 01-DP21-1 0.208 10.45 4.12 VCB 20 30 6 PNL 25 91 18 15.90 (*N3) (*N9) (*N21b)

(*S2)

01-WA-NL-2-F1-B1-BP (Rm. 2178) 01-SSB1-2B-6 0.208 7.88 3.53 VCB 12 14 10 PNL 25 91 18 15.87 (*N9) (*N21a) (*S2)

01-W-P6W-BP (Rm. 6117) 01-SSB1-2B-2 0.208 7.87 3.53 VCB 10 20 6 PNL 25 91 18 15.87 (*N9) (*N21a) (*S2)

02-WA-PAC-31-BP (Rm. G116) 02-LC2C-4 0.208 9.06 4.11 VCB 12 14 10 PNL 25 90 18 15.84 (*N9) (*S4)

01-N-P-BL1-BP (Rm. 1200) 01-SSB1-2A-1 0.208 7.99 3.59 VCB 12 14 10 PNL 25 90 18 15.81 (*N9) (*N21a) (*S2)

02-E-P-7-E-BP (Rm. 7119) 02-LC2D-2 0.208 9.28 3.63 VCB 12 14 10 PNL 25 90 18 15.81 (*N3) (*N9) (*S2)

02-WA-P-SG-W-BP (Rm. G116) 02-LC2C-4 0.208 8.99 4.07 VCB 12 14 10 PNL 25 90 18 15.73 (*N9) (*S4)

01-W-P-6-W-BP (Rm. 6117) 01-SSB1-2B-2 0.208 7.81 3.5 VCB 12 14 10 PNL 25 90 18 15.72 (*N9) (*N21a) (*S2)

MV-T-PET-MDP-PRI (Ext. Bld. 1 PET) MV-52-A2-50/51 13.800 14.77 13.11 HOA 60 37 30 AIR 152 87 18 15.69 (*N5) (*N21a) (*S2)

MV-T-LC7-MSB4-PRI (Ext. Bld. 1 PET) MV-52-A2-50/51 13.800 14.76 13.1 HOA 60 37 30 AIR 152 87 18 15.67 (*N5) (*N21a) (*S2)

01-WA-L-3-W-BP (Rm. 3128) 01-SSB1-2B-6 0.208 7.75 3.47 VCB 12 14 10 PNL 25 90 18 15.58 (*N9) (*N21a) (*S2)

02-E-P-1-E-1-BP (Rm. 2215A) 02-LC2D-2 0.208 9.9 4.52 VCB 12 14 10 PNL 25 89 18 15.51 (*N9) (*S4)

6.5-6

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-WA-NL-3-F2-B1-BP (Rm. 3178) 01-SSB1-2B-6 0.208 7.72 3.45 VCB 12 14 10 PNL 25 89 18 15.50 (*N9) (*N21a) (*S2)

01-N-PAC-8-BP (Rm. 2213A) 01-SSB1-2A-1 0.208 7.83 3.51 VCB 12 14 10 PNL 25 89 18 15.46 (*N9) (*N21a) (*S2)

01-W-L-7-W-BP (Rm. 7177) 01-SSB1-2B-2 0.208 7.68 3.44 VCB 12 14 10 PNL 25 89 18 15.42 (*N9) (*N21a) (*S2)

02-WA-SWING SPACE-BP (Rm. 1348A) 02-LC2C-4 0.208 8.84 4 VCB 12 14 10 PNL 25 89 18 15.42 (*N9) (*S4)

02-E-P-1-E-2-BP (Rm. 2215A) 02-LC2D-2 0.208 9.82 4.48 VCB 12 14 10 PNL 25 89 18 15.41 (*N9) (*S4)

01-N-P-2-N-2-BP (Rm. 2213A) 01-SSB1-2A-1 0.208 7.81 3.5 VCB 12 14 10 PNL 25 89 18 15.40 (*N9) (*N21a) (*S2)

01-NL-8-E-B1-1-ECB (Rm. 8124E) (01-NL-

8-E-B1-1-ECB-CB LineSide) 01-SSB1-2A-4 0.208 9.9 4.52 VCB 8 23 5 PNL 25 89 18 15.34 (*N9) (*N21a) (*S2)

02-WA-EQ1AB2-BP (Rm. 2105) 02-LC2C-4 0.208 8.76 3.96 VCB 12 14 10 PNL 25 88 18 15.26 (*N9) (*N21a) (*S4)

02-WA-P-1-W-BP (Rm. 2105) 02-LC2C-4 0.208 8.68 3.92 VCB 12 14 10 PNL 25 88 18 15.12 (*N9) (*S4)

01-P-SG-NA-1B (Rm. S21G) 01-DP21-1 0.208 10.41 4.11 VCB 20 36 6 PNL 25 88 18 15.08 (*N3) (*N9) (*N21b)

(*S2)

01-N-P-3N-A-BP (Rm. 3229) 01-SSB1-2A-1 0.208 7.66 3.43 VCB 12 14 10 PNL 25 88 18 15.06 (*N9) (*N21a) (*S2)

02-E-P-1-E-5-BP (Rm. 3124) 02-LC2D-2 0.208 9.54 4.35 VCB 12 14 10 PNL 25 88 18 15.03 (*N9) (*S4)

02-E-L-2-E-BP (Rm. 3124) 02-LC2D-2 0.208 9.51 4.33 VCB 12 14 10 PNL 25 87 18 14.98 (*N9) (*S4)

39-EM-SWGR (Rm. 101) 39-EM-SWGR-2 0.480 60.49 34.28 VCB 26 39 60 PNL 25 223 18 14.96 (*N20a) (*N21a)

(*S2)

02-E-LP2-BP (Rm. 3124) 02-LC2D-2 0.208 9.47 4.31 VCB 12 14 10 PNL 25 87 18 14.93 (*N9) (*S4)

01-DP22 (Rm. SG184) 01-SSB1-2A-3 0.208 9.56 4.35 VCB 40 80 12 PNL 25 87 18 14.77 (*N9) (*N21a) (*S2)

01-W-L-9-W-BP (Rm. 9144) 01-SSB1-2B-2 0.208 7.39 3.29 VCB 12 14 10 PNL 25 87 18 14.76 (*N9) (*N21a) (*S2)

01-N-P4NA-BP (Rm. 4218) 01-SSB1-2A-1 0.208 7.52 3.36 VCB 12 14 10 PNL 25 86 18 14.74 (*N9) (*N21a) (*S2)

02-E-L-3-E-BP (Rm. 4124) 02-LC2D-2 0.208 9.33 4.24 VCB 12 14 10 PNL 25 86 18 14.73 (*N9) (*S4)

35A-1DP (Rm. 106) 35A-1DP-MB 0.208 10.31 4.07 VCB 20 60 6 PNL 25 86 18 14.71 (*N3) (*N9) (*S4)

01-N-L4NA-BP (Rm. 4218) 01-SSB1-2A-1 0.208 7.5 3.35 VCB 12 14 10 PNL 25 86 18 14.68 (*N9) (*N21a) (*S2)

02-E-PAC-40-2-BP (Rm. 4124) 02-LC2D-2 0.208 9.28 4.21 VCB 12 14 10 PNL 25 86 18 14.66 (*N9) (*S4)

02-E-L-4-E-BP (Rm. 5124) 02-LC2D-2 0.208 9.11 4.13 VCB 12 14 10 PNL 25 85 18 14.43 (*N9) (*S4)

01-N-PP1-BP (Rm. 5201) 01-SSB1-2A-1 0.208 7.36 3.28 VCB 12 14 10 PNL 25 85 18 14.37 (*N9) (*N21a) (*S2)

01-P-SG-NA-1 (Rm. S21G) 01-DP21-1 0.208 10.71 4.23 VCB 20 64 6 PNL 25 85 18 14.30 (*N3) (*N9) (*N21b)

(*S2)

6.5-7

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-TR-PP-2C-SEC (Rm. 1123) 01-MDP-F-BUSS-2 0.240 7.2 2.24 HOA 35 44 26 AIR 32 62 18 14.29 (*N9) (*S4)

16-TR-1T2-SEC (Rm. 112) 19-N-USS-1-B-4 0.208 8.95 2.45 HOA 32 46 28 AIR 32 62 18 14.28 (*N9) (*S2)

01-N-MCC-6-N-R-BP (Rm. 5201) 01-SSB1-2A-1 0.208 7.31 3.26 VCB 12 14 10 PNL 25 85 18 14.27 (*N9) (*N21a) (*S2)

02-E-PP-1-BP (Rm. 6120) 02-LC2D-2 0.208 8.94 4.05 VCB 12 14 10 PNL 25 84 18 14.20 (*N9) (*S4)

02-NB-LP2N-BP (Rm. 7231) 02-LC2D-3 0.208 9.02 4.09 VCB 12 14 10 PNL 25 84 18 14.19 (*N9) (*S4)

16-XA/XB-ECB (Rm. 112) (16-XA/XB-

ECB-CB LineSide)

19-N-USS-1-B-4 0.208 8.76 3.96 VCB 14 30 5 PNL 25 84 18 14.18 (*N9) (*S2)

02-E-L-5-E-BP (Rm. 6120) 02-LC2D-2 0.208 8.89 4.03 VCB 12 14 10 PNL 25 84 18 14.13 (*N9) (*S4)

02-W-P-SG-W4-BP (Rm. G116) 02-LC2C-3 0.208 7.68 3.44 VCB 12 14 10 PNL 25 84 18 14.08 (*N9) (*S4)

02-E-NL1-A2-B2-BP (Rm. 1288C) 02-LC2D-2 0.208 10.16 4.65 VCB 13 23 7 PNL 25 84 18 13.98 (*N9) (*S4)

01-KIT-LG-NA-1-BP (Rm. G253) 01-SSB1-2B-1 0.208 8.33 3.75 VCB 10 42 8 PNL 25 84 18 13.98 (*N9) (*N21a) (*S2)

02-E-NL1-A1-B2-BP (Rm. 1288C) 02-LC2D-2 0.208 10.1 4.62 VCB 13 23 7 PNL 25 83 18 13.91 (*N9) (*S4)

01-WA-L-G-W-BP (Rm. G212) 01-SSB1-2B-6 0.208 8.25 3.71 VCB 10 42 8 PNL 25 83 18 13.82 (*N9) (*N21a) (*S2)

02-W-P-G-W-5-BP (Rm. 2105) 02-LC2C-3 0.208 7.54 3.37 VCB 12 14 10 PNL 25 83 18 13.80 (*N9) (*S4)

02-EA-LP-BP (Ext. Rm. G145) 02-LC2D-1 0.208 11.31 5.21 VCB 12 21 7 PNL 25 82 18 13.65 (*N9) (*N20b)

(*N21a) (*S4)

24-SOLAR-FDS (Ext. Bld. 24) MV-FU-SW-24 0.208 6.76 2.99 VCB 12 20 8 PNL 25 82 18 13.63 (*N5) (*S3)

02-NB-AHU-1-T7W-VSD-BP (9th Flr.

Penthouse)

02-LC2D-3 0.208 8.56 3.86 VCB 12 14 10 PNL 25 82 18 13.54 (*N9) (*S4)

02-W-LL1-A2-B2-BP (Rm. 2106) 02-LC2C-3 0.208 7.28 3.24 VCB 12 14 10 PNL 25 81 18 13.31 (*N9) (*S4)

01-PP-2C (Rm. 1123) (01-PP-2C-MB

LineSide)

01-MDP-F-BUSS-2 0.240 6.99 3.47 VCB 20 32 6 PNL 25 81 18 13.29 (*N9) (*S4)

02-W-P-1-W-1-BP (Rm. 2106) 02-LC2C-3 0.208 7.23 3.22 VCB 12 14 10 PNL 25 81 18 13.20 (*N9) (*S4)

01-KIT-PG-N2-BP (Rm. G253) 01-SSB1-2B-1 0.208 8.3 3.74 VCB 11 21 8 PNL 25 81 18 13.17 (*N9) (*N21a) (*S2)

02-W-L-2-W-BP (Rm. 3195) 02-LC2C-3 0.208 7.14 3.17 VCB 12 14 10 PNL 25 80 18 13.03 (*N9) (*S4)

01-N-ML-B1-N1-B1-BP (Rm. G275A) 01-SSB1-2A-1 0.208 8.15 3.67 VCB 12 21 6 PNL 25 80 18 13.03 (*N9) (*N21a) (*S2)

01-ATS-EL-30-3-LD (Rm. SG184) 01-SSB1-2A-6 0.208 9.06 4.11 VCB 34 90 28 PNL 25 80 18 13.03 (*N9) (*N21a) (*S2)

02-W-LP1-BP (Rm. 3195) 02-LC2C-3 0.208 7.12 3.16 VCB 12 14 10 PNL 25 80 18 12.99 (*N9) (*S4)

01-SSD-2 (Rm. G291B)

01-UPS-2/IRM-FDS-

FU

0.208 7.19 1.96 HOA 24 30 18 AIR 32 59 18 12.84 (*N9) (*S0)

02-W-L-3-W-BP (Rm. 4195) 02-LC2C-3 0.208 7.03 3.12 VCB 12 14 10 PNL 25 79 18 12.83 (*N9) (*S4)

01-DP21-2 (Rm. SG184) (01-DP21-2-MB

LineSide) 01-SSB1-2A-6 0.208 8.95 4.06 VCB 40 76 15 PNL 25 79 18 12.78 (*N9) (*N21a) (*S2)

01-SPD-DP (Rm. SG184) 01-DP22-3 0.208 8.12 3.65 VCB 20 65 6 PNL 25 79 18 12.74 (*N9) (*S2)

6.5-8

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

02-W-PAC-39A-BP (Rm. 4195) 02-LC2C-3 0.208 6.98 3.1 VCB 12 14 10 PNL 25 79 18 12.73 (*N9) (*S4)

01-DP-1 (Rm. SG129) (01-DP-1-MB

LineSide)

01-SSB1-2A-5 0.208 8.99 3.51 VCB 24 45 6 PNL 25 79 18 12.67

(*N3) (*N9) (*N21a)

(*S2)

02-W-HEMODIALYSIS-BP (Rm. 5195) 02-LC2C-3 0.208 6.94 3.08 VCB 12 14 10 PNL 25 79 18 12.65 (*N9) (*S4)

02-W-PAC-42-BP (Rm. 5195) 02-LC2C-3 0.208 6.91 3.06 VCB 12 14 10 PNL 25 78 18 12.59 (*N9) (*S4)

02-W-L-4-W-BP (Rm. 5195) 02-LC2C-3 0.208 6.86 3.04 VCB 12 14 10 PNL 25 78 18 12.49 (*N9) (*S4)

02-WA-P-SG-W3-BP (Rm. G116) 02-LC2C-3 0.208 7.71 3.45 VCB 10 26 6 PNL 25 78 18 12.46 (*N9) (*S4)

02B-PP-2 (Bld. 2B) (02B-PP-2-MB

LineSide)

02-NLDP-1A-9 0.208 6.7 2.96 VCB 14 24 4 PNL 25 78 18 12.40 (*N9) (*S2)

02-W-L-5-W-BP (Rm. 6188) 02-LC2C-3 0.208 6.76 2.99 VCB 12 14 10 PNL 25 77 18 12.30 (*N9) (*S4)

01-SSD-1 (Rm. SG109) 01-NEDP-1-2 0.208 6.98 1.91 HOA 24 30 18 AIR 32 58 18 12.19 (*N9) (*S0)

34-TR-34-T1-SEC (Rm. 156A) 34-NH-34-DP1-1 0.208 6.85 1.87 HOA 32 56 24 AIR 32 58 18 12.18 (*N9) (*S2)

30-GEN-LD (Gen Enclosure) 30-GEN-MB 0.480 10.5 8.04 VCB 12 14 10 PNL 25 76 18 12.03 (*N9) (*S3)

02-W-L-6-W-BP (Rm. 7189) 02-LC2C-3 0.208 6.61 2.92 VCB 12 14 10 PNL 25 76 18 12.03 (*N9) (*S4)

02B-PP-1 (Bld. 2B) (02B-PP-1-MB

LineSide)

02-NLDP-1A-9 0.208 6.51 2.87 VCB 14 24 4 PNL 25 76 18 12.01 (*N9) (*S2)

02-W-LP1-W-BP (Rm. 7189) 02-LC2C-3 0.208 6.59 2.91 VCB 12 14 10 PNL 25 76 18 11.97 (*N9) (*S4)

01-L-G-W (Rm. G212) 01-WA-L-G-W-BP-CB 0.208 7.93 3.07 VCB 20 36 6 PNL 25 76 18 11.96 (*N3) (*N9) (*N21a)

(*S2)

02-W-P-6-W-1-BP (Rm. 7189) 02-LC2C-3 0.208 6.57 2.9 VCB 12 14 10 PNL 25 76 18 11.94 (*N9) (*S4)

01-P-SG-NA-2 (Rm. S21G)

01-NA-P-SG-NA-2-BP-

CB

0.208 8.11 3.14 VCB 20 40 6 PNL 25 76 18 11.92

(*N3) (*N9) (*N21a)

(*S2)

02-W-P-7-W-BP (Rm. 8132) 02-LC2C-3 0.208 6.49 2.86 VCB 12 14 10 PNL 25 75 18 11.80 (*N9) (*S4)

02-W-PAC-57-BP (Rm. 8132) 02-LC2C-3 0.208 6.46 2.85 VCB 12 14 10 PNL 25 75 18 11.73 (*N9) (*S4)

14-MAIN (Rm. Elec.) 14-FDS-FU 0.208 7.67 3.43 VCB 20 48 6 PNL 25 74 18 11.56 (*N5) (*N9) (*S4)

01-TR-EL-B2-N1-B1A-SEC (Rm. S21G)

01-TR-EL-B2-N1-B1A-

BP-CB

0.208 6.44 1.75 HOA 32 42 28 AIR 32 56 18 11.48 (*N9) (*S2)

05-P-CBD-1 (Corr. CB15) 16-LC3-D-1 0.208 8.65 3.91 VCB 30 60 10 PNL 25 74 18 11.44 (*N9) (*S2)

01-TR-T-1-SEC (Rm. 1124) 01-PNL-DP-1-1 0.208 6.57 1.79 HOA 30 34 24 AIR 32 56 18 11.41 (*N9) (*S2)

01-TR-MDP-G249A-SEC (Rm. G249A) 01-SSB1-4A-6 0.208 6.54 1.78 HOA 38 45 28 AIR 32 56 18 11.40 (*N9) (*S2)

05-2-C371 (Corr. C3C5) 05-P-CBD-2-5 0.208 7.44 2.86 VCB 15 34 4 PNL 25 74 18 11.40 (*N3) (*N9) (*S2)

04-4C/4-ECB (No Access) (04-4C/4-ECB-

CB LineSide)

02-LC2D-4 0.208 6.05 2.65 VCB 12 14 10 PNL 25 74 18 11.39 (*N5) (*N9) (*S2)

05-C219 (Corr. C276C) (05-C219-MB

LineSide)

05-P-CBD-2-3 0.208 7.7 2.97 VCB 20 35 6 PNL 25 74 18 11.38 (*N3) (*S3)

02-PP-1 (Rm. 7105) (02-PP-1-MB LineSide) 02-LC2D-2 0.208 7.44 3.32 VCB 20 72 6 PNL 25 74 18 11.37 (*N5) (*N9) (*N21b)

(*S1)

6.5-9

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

05-BCBD-2-ECB (No Access) 02-LC2D-4 0.208 6.03 2.64 VCB 12 14 10 PNL 25 73 18 11.35 (*N5) (*N9) (*S2)

01-TR-LL-LC7-DP-SEC (Rm. SG109) 01-LH-LC7-DP-1 0.208 6.35 1.73 HOA 36 36 22 AIR 32 56 18 11.33 (*N9) (*S2)

05-C125-ECB (No Access) (05-C125-ECB-

CB LineSide)

02-LC2D-4 0.208 5.99 2.62 VCB 12 14 10 PNL 25 73 18 11.26 (*N5) (*N9) (*S2)

01-UPS-1/RPP-1-A (Rm. SG105) 01-UPS-1/RPP-1-A-MB 0.208 6.76 2.99 VCB 24 36 12 PNL 25 73 18 11.20 (*N9) (*S0)

01-UPS-2/RPP-2-A (Rm. SG105) 01-UPS-2/RPP-2-A-MB 0.208 6.76 2.99 VCB 24 36 12 PNL 25 73 18 11.20 (*N9) (*S0)

02-PP-2 (Rm. 7105) 02-LC2D-2 0.208 7.31 3.26 VCB 20 72 6 PNL 25 73 18 11.14 (*N5) (*N9) (*N21b)

(*S1)

02-TR-ELTRAN-10-D3-B2-SEC (10th Flr.

Penthouse)

02-EHDP-10-D1-B2-2 0.208 6.36 1.73 HOA 36 40 38 AIR 32 55 18 11.09 (*N9) (*S2)

01-UPS-3/RPP-3-A (Rm. SG105) 01-UPS-3/RPP-3-A-MB 0.208 6.63 2.93 VCB 24 36 12 PNL 25 72 18 10.95 (*N9) (*S0)

01-UPS-4/RPP-4-A (Rm. SG105) 01-UPS-4/RPP-4-A-MB 0.208 6.63 2.93 VCB 24 36 12 PNL 25 72 18 10.95 (*N9) (*S0)

01-PAC-3 (Rm. G212) 01-WA-L-G-W-BP-CB 0.208 7.47 2.87 VCB 20 40 6 PNL 25 71 18 10.85 (*N3) (*N9) (*N21a)

(*S2)

01-PAC-3A (Rm. G212) 01-WA-L-G-W-BP-CB 0.208 7.63 2.94 VCB 20 44 6 PNL 25 71 18 10.83 (*N3) (*N9) (*N21a)

(*S2)

05-ELEV-FDS (Rm. CB19) (05-ELEV-FDS-

FU LineSide)

05-P-CBD-1-2 0.208 6.52 2.87 VCB 12 14 10 PNL 25 71 18 10.80 (*N9) (*S2)

MV-PT1-SEC (Ext. Bld. 19) MV-52-G1-50/51 13.800 16.24 14.39 HOA 36 66 30 AIR 152 69 18 10.75 (*S2)

01-UPS-1/RPP-1-B (Rm. SG105) 01-UPS-1/RPP-1-B-MB 0.208 6.58 2.91 VCB 24 36 12 PNL 25 70 18 10.62 (*N9) (*S0)

01-UPS-2/RPP-2-B (Rm. SG105) 01-UPS-2/RPP-2-B-MB 0.208 6.58 2.91 VCB 24 36 12 PNL 25 70 18 10.62 (*N9) (*S0)

01-UPS-3/RPP-3-B (Rm. SG105) 01-UPS-3/RPP-3-B-MB 0.208 6.58 2.91 VCB 24 36 12 PNL 25 70 18 10.62 (*N9) (*S0)

01-UPS-4/RPP-4-B (Rm. SG105) 01-UPS-4/RPP-4-B-MB 0.208 6.58 2.91 VCB 24 36 12 PNL 25 70 18 10.62 (*N9) (*S0)

24-LC4 (Rm. B04) MV-FU-SW-24 0.208 8.67 3.37 VCB 17 27 12 PNL 25 70 18 10.56 (*N3) (*N5) (*S3)

01-EDS-ECB (Rm. S21G) 01-EDSN-2 0.208 10.84 4.98 VCB 12 14 10 PNL 25 70 18 10.48 (*N5) (*N9) (*S3)

34-DP-F-ECB (Rm. 120A) 34-NL-34-DP1-1 0.208 5.48 2.38 VCB 12 14 10 PNL 25 70 18 10.47 (*N9) (*S2)

16-XA (Rm. Boiler) (16-XA-MB LineSide) 19-N-USS-1-B-4 0.208 7.63 3.41 VCB 20 50 6 PNL 25 70 18 10.44 (*N5) (*N9) (*S2)

16-XB (Rm. Boiler) 19-N-USS-1-B-4 0.208 7.54 3.37 VCB 20 50 6 PNL 25 69 18 10.32 (*N5) (*N9) (*S4)

MV-PT2-SEC (Ext. Bld. 19) MV-52-G2-50/51 13.800 15.62 13.85 HOA 36 66 30 AIR 152 67 18 10.31 (*S2)

01-TR-EP-3-N-A/B-SEC (Rm. G291B) 01-B1-CP-DP-1 0.208 5.72 1.56 HOA 30 40 24 AIR 32 53 18 10.11 (*N9) (*S2)

6.5-10

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

02-TR-NLDP-2-SEC (Rm. G141) 02-SSB2-6B-2 0.208 5.71 1.55 HOA 26 144 20 AIR 32 52 18 10.08 (*N9) (*S2)

05-5-1-P3 (Corr. C1C4) (05-5-1-P3-MB

LineSide)

05-P-CBD-2-1 0.208 7.89 3.05 VCB 20 70 6 PNL 25 68 18 10.06 (*N3) (*S3)

34-NL-34-DP1 (Rm. 156A) 34-NL-34-DP1-MB 0.208 6.7 2.96 VCB 36 90 11 PNL 25 68 18 10.06 (*N9) (*S2)

01-P-G-W (Rm. G240) 01-WA-L-G-W-BP-CB 0.208 6.3 2.77 VCB 20 44 6 PNL 25 68 18 10.05 (*N9) (*N21a) (*S2)

01-LSI-FDS (Rm. 5150) (01-LSI-FDS-FU

LineSide)

01-E-5150-BP-CB 0.208 6.11 2.31 VCB 12 20 6 PNL 25 68 18 10.03

(*N3) (*N9) (*N21a)

(*S2)

19-2T2-SEC (Rm. 19 200) 19-N-USS-1-B-5 0.208 5.69 1.55 HOA 31 40 24 AIR 32 52 18 9.97 (*N9) (*S2)

01-MCC-6-N-L (Rm. 6221) (01-MCC-6-N-L-

MB LineSide)

01-DP22-1 0.208 6.18 2.71 VCB 6 28 20 MCC 25 67 18 9.89 (*N9) (*S2)

01-EL-B2-N1-B1A (Rm. S21G) 01-EL-B2-N1-B1A-MB 0.208 6.33 2.78 VCB 20 56 6 PNL 25 67 18 9.87 (*N9) (*S2)

01-TLP-1 (Rm. G253) 01-DP-PAD-4 0.208 6.87 3.05 VCB 20 48 6 PNL 25 67 18 9.83 (*N9) (*N21a) (*S2)

01-EP5 (Rm. 5171) (01-EP5-MB LineSide) 01-W-EP5-BP-CB 0.208 7.18 2.75 VCB 20 50 6 PNL 25 67 18 9.82 (*N3) (*N9) (*S2)

14-ELEV-FDS (Rm. Elec.) (14-ELEV-FDS-

FU LineSide)

14-MAIN-4 0.208 5.53 2.4 VCB 12 14 10 PNL 25 67 18 9.78 (*N9) (*S0)

01-TR-L5DP-SEC (Rm. 6180) 01-TR-L5DP-FDS-FU 0.208 5.76 1.57 HOA 28 44 23 AIR 32 52 18 9.77 (*N9) (*S2)

01-TR-EDS-SEC (Rm. S21G) 01-EDSN-2 0.208 10.91 2.99 HOA 41 46 32 AIR 32 51 18 9.67 (*N9) (*S3)

14-C (Rm. Elec.) 14-MAIN-3 0.208 7.37 2.83 VCB 20 48 6 PNL 25 66 18 9.59 (*N3) (*N9) (*S0)

36A-PP-1 (Corr. 1C1) (36A-PP-1-MB

LineSide)

35-MDP-15 0.208 6.18 2.34 VCB 13 24 6 PNL 25 66 18 9.55 (*N3) (*N9) (*S0)

12-DP-2-12 (Rm. B04) 12-DP-2-12-MB 0.208 6.61 2.51 VCB 20 40 6 PNL 25 66 18 9.51 (*N3) (*N9) (*S0)

15A-MDP (Ext. Bld. 15) (15A-MDP-MB

LineSide)

16-LC3-D-5 0.208 6.29 2.77 VCB 20 56 6 PNL 25 66 18 9.50 (*N9) (*S2)

14-B (Rm. Elec.) 14-MAIN-2 0.208 7.28 2.8 VCB 20 48 6 PNL 25 66 18 9.47 (*N3) (*N9) (*S0)

01-MDP-G249A (Rm. G249A) 01-SSB1-4A-6 0.208 6.47 2.85 VCB 40 62 12 PNL 25 66 18 9.46 (*N5) (*N9) (*S2)

14-A (Rm. Elec.) 14-MAIN-1 0.208 7.24 2.78 VCB 20 48 6 PNL 25 65 18 9.41 (*N3) (*N9) (*S0)

02-TR-NL-1-H1-B2-1-SEC (Rm. 240E) 02-NH-1-H1-B2-1 0.208 5.29 1.44 HOA 28 32 26 AIR 32 50 18 9.25 (*N9) (*S2)

01-240/120-VIP-ECB (Rm. 1123)

01-240/120-VIP-ECB-

CB

0.208 5.28 2.28 VCB 12 14 10 PNL 25 65 18 9.23 (*N9) (*S2)

35-G2 (Rm. B22) (35-G2-MB LineSide) 35-MDP-5 0.208 5.89 2.57 VCB 20 66 6 PNL 25 64 18 9.10 (*N9) (*S0)

05-N/N-C243 (Corr. C276B) 05-P-CBD-2-4 0.208 5.5 2.39 VCB 20 38 6 PNL 25 64 18 9.00 (*N9) (*S2)

16-TR-1T3-SEC (Rm. 112) 19-N-USS-1-A-10 0.208 5.12 1.39 HOA 31 40 24 AIR 32 49 18 8.95 (*N9) (*S2)

6.5-11

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

02A-PNL-2 (Bld. 2A) 02-NLDP-1A-7 0.208 5.55 2.41 VCB 20 40 6 PNL 25 63 18 8.94 (*N9) (*S2)

05-1-C359 (Corr. C3C3) 05-P-CBD-2-5 0.208 5.53 2.4 VCB 20 40 6 PNL 25 63 18 8.93 (*N5) (*N9) (*S2)

01-ALADDIN-SYS-DISC (Rm. G249) 01-SSB1-4A-6 0.208 5.94 2.6 VCB 22 48 9 PNL 25 63 18 8.92 (*N5) (*N9) (*S2)

35-A (Rm. 132A) 35-A-MB 0.208 5.76 2.51 VCB 20 48 6 PNL 25 63 18 8.91 (*N9) (*S0)

02-W-NL1-A1-B2-BP (Rm. 2106) 02-LC2C-3 0.208 7.3 3.25 VCB 10 16 5 PNL 25 63 18 8.89 (*N9) (*S4)

06A-MDP (Ext. Bld. 6A) 01-DP22-2 0.208 6.01 2.63 VCB 30 56 8 PNL 25 63 18 8.87 (*N9) (*S2)

01-TR-CL-MDP-E61-SEC (Rm. 2222) 01-CH-MDP-E61-7 0.208 5.03 1.37 HOA 26 36 20 AIR 32 49 18 8.83 (*N9) (*S2)

39-PP-GB1 (Rm. 101) 39-PP-GB1-MB 0.208 5.75 2.51 VCB 20 48 6 PNL 25 63 18 8.83 (*N9) (*S4)

02-TR-CL-MDP-SEC (Rm. G136) 02-NHDP-2-4 0.208 4.98 1.35 HOA 26 36 20 AIR 32 49 18 8.73 (*N5) (*N9) (*S2)

35-C (Rm. 132A) 35-C-MB 0.208 5.63 2.45 VCB 20 48 6 PNL 25 62 18 8.69 (*N9) (*S0)

01-EDSN (Rm. S21G) 30-GEN-MB 0.480 9.96 7.61 VCB 40 76 15 PNL 25 62 18 8.66 (*N5) (*N9) (*S3)

01-N/N-G95A-D (Rm. G95A-D) 01-DP22-4 0.208 5.93 2.23 VCB 13 34 4 PNL 25 62 18 8.62 (*N3) (*N9) (*S2)

16-XC-ECB (Rm. 112) 16-XC-ECB-CB 0.208 5.06 2.18 VCB 14 30 6 PNL 25 62 18 8.62 (*N9) (*S2)

02-PAC-39B (Rm. 4195) 02-W-PAC-39A-BP-CB 0.208 6.51 2.47 VCB 20 40 6 PNL 25 62 18 8.59 (*N3) (*N9) (*N21b)

(*S4)

08-P3 (Corr. 100) 08-MDP-6 0.208 5.19 2.24 VCB 20 36 6 PNL 25 62 18 8.56 (*N9) (*S2)

01-NL-8-E-B1-3 (Rm. 8124E) 01-NL-8-E-B1-1-MB 0.208 8.02 3.1 VCB 20 60 6 PNL 25 62 18 8.55 (*N3) (*S4)

01-T-RP1-SEC (Ext. SPD Trailer) 01-SPD-PB1-1 0.208 4.86 1.32 HOA 36 38 28 AIR 32 48 18 8.55 (*N9) (*S0)

02-EL-8-D1-B2 (Rm. 8152) (02-EL-8-D1-

B2-MB LineSide)

02-EHDP-10-D1-B2-2 0.208 5.65 2.46 VCB 20 48 6 PNL 25 61 18 8.52 (*N9) (*S2)

05-PNL-2 (Rm. C270A) (05-PNL-2-MB

LineSide)

05-P-CBD-1-8 0.208 6.25 2.75 VCB 20 52 6 PNL 25 61 18 8.51 (*N9) (*S2)

05-PNL-1 (Rm. C270A) 05-P-CBD-1-1 0.208 6.93 3.07 VCB 20 55 6 PNL 25 61 18 8.48 (*S3)

35-D (Rm. 132A) 35-D-MB 0.208 5.51 2.39 VCB 20 48 6 PNL 25 61 18 8.48 (*N9) (*S0)

08-MDP (Rm. B03) 16-LC3-B-2 0.208 5.75 2.51 VCB 44 84 12 PNL 25 61 18 8.45 (*N9) (*S2)

02-NLDP-2 (Rm. G141) 02-SSB2-6B-2 0.208 5.62 2.45 VCB 24 58 11 PNL 25 61 18 8.40 (*N5) (*N9) (*S2)

02-PAC-42 (Rm. 5195) 02-W-PAC-42-BP-CB 0.208 6.5 2.47 VCB 20 44 6 PNL 25 61 18 8.36 (*N3) (*N9) (*N21b)

(*S4)

02-NL-1-H1-B2-1 (Rm. 240E) (02-NL-1-H1-

B2-1-MB LineSide)

02-NH-1-H1-B2-1 0.208 5.2 2.24 VCB 20 38 6 PNL 25 61 18 8.34 (*N9) (*S2)

02A-PNL-1 (Bld. 2A) 02-NLDP-1A-8 0.208 5.21 2.25 VCB 20 40 6 PNL 25 60 18 8.31 (*N9) (*S2)

01-ALADDIN (Rm. G252) 01-SSB1-4A-6 0.208 5.54 2.4 VCB 20 56 6 PNL 25 60 18 8.28 (*N5) (*N9) (*S2)

08-PP2 (Corr. 232) 08-MDP-7 0.208 5.03 2.17 VCB 20 36 6 PNL 25 60 18 8.25 (*N9) (*S2)

19-2PNL1 (Rm. 19 200) 19-N-USS-1-B-5 0.208 5.61 2.44 VCB 31 96 15 PNL 25 60 18 8.20 (*N5) (*N9) (*S2)

02-P-1-W-1 (Rm. 2113) 02-P-1-W-1-MB 0.208 5.63 2.45 VCB 20 48 6 PNL 25 59 18 8.09 (*N9) (*S4)

6.5-12

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-CL-MDP-E61 (Rm. 2222) 01-CH-MDP-E61-7 0.208 4.95 2.13 VCB 20 36 6 PNL 25 59 18 8.06 (*N5) (*N9) (*S2)

02-LP1-W (Rm. 7192G) (02-LP1-W-MB

LineSide)

02-W-LP1-W-BP-CB 0.208 5.62 2.44 VCB 20 68 6 PNL 25 59 18 8.02 (*N9) (*S4)

01-LP1 (Rm. SG106) 01-LP1-MB 0.208 4.7 2.01 VCB 20 30 6 PNL 25 59 18 7.97 (*N9) (*S2)

01-MCC-6-N-R (Rm. 6221) (01-MCC-6-N-

R-MB LineSide)

01-N-MCC-6-N-R-BP-

CB

0.208 5.36 2 VCB 20 28 6 MCC 25 59 18 7.92

(*N3) (*N9) (*N21a)

(*S2)

01-EDS (Rm. SG184) 01-EDSN-2 0.208 10.72 4.92 VCB 38 70 14 PNL 25 59 18 7.91 (*N5) (*N9) (*S3)

01-PNL-A (Rm. 10-E) 01-PNL-A-MB 0.480 8.34 6.33 VCB 20 76 6 PNL 25 59 18 7.90 (*N9) (*S3)

05-PCBA (Corr. CB15) 16-LC3-B-3 0.208 5.34 2.31 VCB 30 66 9 PNL 25 58 18 7.86 (*N9) (*S2)

01-L5DP (Rm. 6180) 01-TR-L5DP-FDS-FU 0.208 5.58 2.42 VCB 36 74 12 PNL 25 58 18 7.83 (*N5) (*N9) (*S2)

08-P2 (Rm. 106) 08-MDP-8 0.208 4.8 2.06 VCB 16 36 4 PNL 25 58 18 7.82 (*N9) (*S2)

02-TR-S1-NFDS-SEC (Ext. Bld. 2) 02-NH2-C1-B2-2 0.208 4.52 1.22 HOA 35 40 30 AIR 32 46 18 7.82 (*N9) (*S2)

34-DP-F (Rm.120A) 34-NL-34-DP1-1 0.208 5.35 2.32 VCB 40 90 12 PNL 25 58 18 7.75 (*N5) (*N9) (*S2)

36A-PP-2 (Corr. 1C1) (36A-PP-2-MB

LineSide)

35-MDP-15 0.208 7.64 2.94 VCB 13 24 6 PNL 25 58 18 7.73 (*N3) (*S0)

08A-A (Rm. 130) (08A-A-MB LineSide) 08-MDP-2 0.208 4.48 1.91 VCB 16 28 6 PNL 25 58 18 7.72 (*N9) (*S2)

08A-B (Rm. 130) (08A-B-MB LineSide) 08-MDP-2 0.208 4.48 1.91 VCB 16 28 6 PNL 25 58 18 7.72 (*N9) (*S2)

01-RP1 (Ext. SPD Trailer) 01-RP1-MB 0.208 4.78 2.05 VCB 20 38 6 PNL 25 57 18 7.67 (*N9) (*S0)

01-240/120-VIP (Rm. 1123)

01-240/120-VIP-ECB-

CB

0.208 5.04 2.17 VCB 20 35 6 PNL 25 57 18 7.62 (*N9) (*S2)

01-PP2A (Rm. 1123) 01-DP21-4 0.208 5.36 2.32 VCB 20 58 6 PNL 25 56 18 7.43 (*N9) (*S2)

01-TR-RP-SEC (Rm. SG148) 01-LP-1 0.208 4.34 1.18 HOA 26 36 20 AIR 32 45 18 7.43 (*N9) (*S2)

08-P1 (Corr. 202) 08-MDP-9 0.208 4.59 1.96 VCB 20 36 6 PNL 25 56 18 7.42 (*N9) (*S2)

01-SPD-A (Adj. SG201) 01-SPD-DP-1 0.208 4.9 2.1 VCB 20 42 6 PNL 25 56 18 7.37 (*N9) (*S2)

02-L (Rm. 8132) 02-L-MB 0.208 5.03 2.17 VCB 20 44 6 PNL 25 56 18 7.33 (*N9) (*S2)

34-B (Corr. 1C2) 34-DP-F-2 0.208 4.88 2.09 VCB 20 48 6 PNL 25 56 18 7.32 (*N9) (*S2)

01-L-6-N (Rm. 6221)

01-N-MCC-6-N-R-BP-

CB

0.208 5.35 2 VCB 20 38 6 PNL 25 56 18 7.30

(*N3) (*N9) (*N21a)

(*S2)

01-P-SG-E (Corr. SG024) 01-EA-P-SG-E-BP-CB 0.208 5.31 1.98 VCB 20 38 6 PNL 25 56 18 7.28 (*N3) (*N9) (*N21a)

(*S2)

01-DISHWPNL (Rm. G249A) 01-DP-PAD-5 0.208 4.61 1.97 VCB 20 30 6 PNL 25 55 18 7.25 (*N9) (*N21a) (*S2)

06A-PP5 (Rm. 101) 06A-PP5-MB 0.208 4.69 2.01 VCB 20 42 6 PNL 25 55 18 7.20 (*N9) (*S2)

01-N-ML-B1-N1-B1 (Rm. G278) (01-N-ML-

B1-N1-B1-MB LineSide)

01-N-ML-B1-N1-B1-BP-

CB

0.208 5.5 2.06 VCB 20 64 6 PNL 25 55 18 7.16 (*N3) (*N9) (*S2)

6.5-13

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

MV-SW-LC2A-1 (Rm. G145A) MV-52-A2-50/51 13.800 12.94 11.95 VCB 27 44 45 PNL 152 56 18 7.14 (*N3) (*N5) (*S2)

MV-SW-LC2A-2 (Rm. G145A) MV-52-A2-50/51 13.800 12.94 11.95 VCB 27 44 45 PNL 152 56 18 7.14 (*N3) (*N5) (*S2)

02-E-5185 (Rm. 5185) (02-E-5185-MB

LineSide)

02-W-HEMODIALYSIS-

BP-CB

0.208 5.37 2.01 VCB 20 38 6 PNL 25 55 18 7.10 (*N3) (*N9) (*S4)

02-CL-MDP (Rm. G136) 02-CL-MDP-MB 0.208 4.84 2.08 VCB 24 60 12 PNL 25 55 18 7.08 (*N9) (*S2)

01-ATS-30-2-LD (Rm. 11th Pent.) 01-EDSN-1 0.480 8.89 5.93 VCB 30 62 30 PNL 25 54 18 6.99 (*N3) (*N9) (*S3)

34-DP-B (Rm. 108) 34-NL-34-DP1-2 0.208 4.69 2.01 VCB 20 54 6 PNL 25 54 18 6.95 (*N9) (*S2)

MV-SW-LC2B-2 (Rm. G145A) MV-52-B2-50/51 13.800 12.47 11.51 VCB 27 44 45 PNL 152 55 18 6.92 (*N3) (*N5) (*S2)

MV-SW-LC2B-1 (Rm. G145A) MV-52-B2-50/51 13.800 12.47 11.51 VCB 27 44 45 PNL 152 55 18 6.92 (*N3) (*N5) (*S2)

01-MDP-11 (Rm. 11th Pent.) 01-EDSN-1 0.480 8.83 5.89 VCB 42 68 10 PNL 25 54 18 6.87 (*N3) (*N5) (*N9)

(*S3)

34-DP-B-ECB (Rm. 108) 34-NL-34-DP1-2 0.208 4.75 2.03 VCB 30 70 12 PNL 25 53 18 6.83 (*N9) (*S2)

02-LP2-W (Rm. 7192G) (02-LP2-W-MB

LineSide)

02-W-LP1-W-BP-CB 0.208 5.52 2.06 VCB 20 68 6 PNL 25 53 18 6.82 (*N3) (*N9) (*S4)

01-RPA-ECB (Rm. SG148) 01-RPA-ECB-CB 0.208 4.25 1.8 VCB 10 26 5 PNL 25 53 18 6.80 (*N9) (*S2)

16-XC (Rm. 112) 16-XC-ECB-CB 0.208 4.6 1.97 VCB 20 68 6 PNL 25 53 18 6.79 (*N5) (*N9) (*S2)

06A-PP4 (Rm. 101) 06A-PP4-MB 0.208 4.44 1.89 VCB 20 42 6 PNL 25 53 18 6.77 (*N9) (*S2)

MV-SW-16-LC3-B-SW (Rm. 102) MV-52-A2-50/51 13.800 12.68 11.71 VCB 30 75 45 PNL 152 54 18 6.77 (*N3) (*N5) (*S2)

34-DP1 (Rm. 108) 34-NL-34-DP1-2 0.208 4.66 1.99 VCB 24 66 6 PNL 25 53 18 6.76 (*N9) (*S2)

04-P-CBD-1-A (Rm. D300) 05-P-CBD-1-5 0.208 5.05 2.18 VCB 20 42 6 PNL 25 53 18 6.64 (*N9) (*S2)

01-TR-EL-B2-N1-B1-SEC (Rm. S21G) 01-EH-B2-N1-B1-1 0.208 3.82 1.03 HOA 32 42 28 AIR 32 42 18 6.63 (*N9) (*S2)

MV-SW-16-LC3-D-SW (Rm. 102) MV-52-B2-50/51 13.800 12.27 11.34 VCB 30 75 45 PNL 152 53 18 6.58 (*N3) (*N5) (*S2)

02-207A (Rm. 5206) (02-207A-MB

LineSide)

02-W-HEMODIALYSIS-

BP-CB

0.208 4.67 2 VCB 20 56 6 PNL 25 52 18 6.58 (*N9) (*S4)

02-TR-EL-MDP-SEC (Rm. G136) 02-EH-MDP-1 0.208 3.81 1.03 HOA 26 36 19 AIR 32 42 18 6.56 (*N9) (*S2)

02-207B (Rm. 5206) (02-207B-MB

LineSide)

02-W-HEMODIALYSIS-

BP-CB

0.208 4.66 1.99 VCB 20 52 6 PNL 25 52 18 6.56 (*N9) (*S4)

34-A (Rm. 115) 34-DP-F-1 0.208 4.44 1.89 VCB 20 51 6 PNL 25 52 18 6.53 (*N9) (*S2)

01-LP (Rm. SG148) (01-LP-MB LineSide) 01-SSB1-4A-7 0.480 10.51 8.05 VCB 20 90 6 PNL 25 52 18 6.53 (*S4)

06A-PP3 (Rm. 101) 06A-PP3-MB 0.208 4.29 1.82 VCB 20 42 6 PNL 25 52 18 6.51 (*N9) (*S2)

01-P-4-NA-1 (Rm. 4254) 01-P4NA-1-ECB-CB 0.208 3.96 1.67 VCB 20 30 6 PNL 25 52 18 6.47 (*N9) (*S2)

34-D (Corr. 1C4) 34-DP-F-4 0.208 4.35 1.85 VCB 20 48 6 PNL 25 51 18 6.42 (*N9) (*S2)

08.5-A (Rm. 14) 08.5-A-MB 0.208 3.81 1.6 VCB 16 28 6 PNL 25 51 18 6.40 (*N9) (*S2)

6.5-14

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-EP-3-N-A/B-ECB (Rm. G291B)

01-EP-3-N-A/B-ECB-

CB

0.208 5.63 2.45 VCB 8 12 4 PNL 25 51 18 6.38 (*N9) (*S2)

34-TR-34-T2-SEC (Rm. 156A) 34-NH-34-DP1-3 0.208 3.69 1 HOA 29 39 22 AIR 32 42 18 6.36 (*N9) (*S2)

34-C (Corr. 1C4) 34-DP-F-3 0.208 4.26 1.81 VCB 20 48 6 PNL 25 51 18 6.28 (*N9) (*S2)

01-PET-TR-P1-SEC (Rm. SG123) 01-PET-MDP-3 0.208 3.62 0.98 HOA 35 40 34 AIR 32 41 18 6.25 (*N9) (*S2)

01-RP (Rm. SG148) 01-RP-MB 0.208 4.3 1.82 VCB 20 48 6 PNL 25 50 18 6.23 (*N9) (*S2)

01-P-4-NA-2 (Rm. 4254) 01-P4NA-1-ECB-CB 0.208 3.87 1.63 VCB 14 32 6 PNL 25 50 18 6.20 (*N9) (*S2)

06-A-ECB (Corr. BBC1) (06-A-ECB-CB

LineSide) 05-PCBA-1-1 0.208 3.43 1.43 VCB 12 14 10 PNL 25 50 18 6.17 (*N9) (*N21a) (*S2)

06A-PP1 (Rm. 101) 06A-PP1-MB 0.208 4.08 1.73 VCB 20 42 6 PNL 25 50 18 6.15 (*N9) (*S2)

06A-PP2 (Rm. 101) 06A-PP2-MB 0.208 4.08 1.73 VCB 20 42 6 PNL 25 50 18 6.15 (*N9) (*S2)

19-1PNL1 (Rm. 19 100) (19-1PNL1-MB

LineSide)

19-2PNL1-3 0.208 4.93 1.82 VCB 31 90 14 PNL 25 50 18 6.14 (*N3) (*N9) (*S2)

MV-SW-B1-LC7-LD (Ext. Bld. 1 PET) MV-52-A2-50/51 13.800 14.94 13.5 HCB 26 60 30 SWG 152 96 36 6.08 (*N5) (*N21a) (*S2)

05-P-CZA (Corr. C258A) 05-PCBA-3 0.208 4.48 1.64 VCB 20 40 6 PNL 25 50 18 6.08 (*N3) (*N9) (*N21a)

(*S2)

19-3PNL1 (Rm. 19 300) (19-3PNL1-MB

LineSide)

19-2PNL1-1 0.208 4.88 1.8 VCB 31 90 15 PNL 25 50 18 6.07 (*N3) (*N9) (*S2)

05-NEW-PNL (Corr. C258A) (05-NEW-PNL-

MB LineSide)

05-PCBA-3 0.208 4.27 1.56 VCB 20 33 6 PNL 25 50 18 6.07

(*N3) (*N9) (*N21a)

(*S2)

04-LD1-LD2-ECB (Corr. D102) 04-LD1-LD2-ECB-CB 0.208 3.37 1.4 VCB 12 14 10 PNL 25 49 18 6.04 (*N9) (*S2)

04-LE1-ECB (Corr. D102) 04-LE1-ECB-CB 0.208 3.37 1.4 VCB 12 14 10 PNL 25 49 18 6.04 (*N9) (*S2)

04-DB4-ECB (Corr. D102) (04-DB4-ECB-

CB LineSide) 05-PCBA-2 0.208 3.35 1.39 VCB 12 14 10 PNL 25 49 18 6.01 (*N9) (*N21a) (*S2)

04-LD1A-ECB (Corr. D102) 04-LD1A-ECB-CB 0.208 3.35 1.39 VCB 12 14 10 PNL 25 49 18 5.99 (*N9) (*S2)

04-4 (Corr. D222) 02-LC2D-4 0.208 4.12 1.74 VCB 20 46 6 PNL 25 49 18 5.98 (*N5) (*N9) (*S2)

05-PNL-3 (Rm. C270A) 05-PCBA-3 0.208 3.88 1.63 VCB 20 40 6 PNL 25 49 18 5.96 (*N9) (*N21a) (*S2)

06-07-ECB (Corr. BBC1) 06-07-ECB-CB 0.208 3.52 1.47 VCB 12 28 4 PNL 25 49 18 5.85 (*N9) (*S2)

19-N-USS-1-A (Rm. 19 202) (19-N-USS-1-

A-MB LineSide) MV-N-USS-1-SWA-FU 0.480 59.41 59.41 VCB 29 32 30 SWG 104 79 36 5.82 (*N_gap) (*S1)

02-P-G-W-5 (Rm. 1122) 02-W-P-G-W-5-BP-CB 0.208 3.86 1.62 VCB 20 36 6 PNL 25 48 18 5.81 (*N9) (*S4)

19-N-USS-1-B (Rm. 19 202) (19-N-USS-1-

B-MB LineSide) MV-N-USS-1-SWB-FU 0.480 61.15 61.15 VCB 29 32 30 SWG 104 79 36 5.78 (*N_gap) (*S0)

02-NL-1-E3-B2 (Rm. 1275) 02-NL-1-E3-B2-MB 0.208 3.94 1.66 VCB 20 48 6 PNL 25 48 18 5.73 (*N9) (*S2)

6.5-15

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-TR-LC1B-LP-1-SEC (Ess. Elec. Rm.) 01-LC1B-EQ-DP-2 0.208 3.34 0.9 HOA 24 30 18 AIR 32 39 18 5.73 (*N9) (*S2)

02-P-G-W-6 (Rm. 1122) 02-W-P-G-W-5-BP-CB 0.208 3.81 1.6 VCB 20 36 6 PNL 25 48 18 5.73 (*N9) (*S4)

01-1-104-C (Rm. 1195) 01-MDP-G249A-2 0.208 4.41 1.62 VCB 20 44 6 PNL 25 48 18 5.73 (*N3) (*N9) (*S2)

06-N/N-TUNNEL (Corr. BBC1) 05-PCBA-1-1 0.208 3.49 1.45 VCB 20 30 6 PNL 25 48 18 5.68 (*N9) (*N21a) (*S2)

02-NL-1-E2-B2 (Rm. 1275) 02-NL-1-E2-B2-MB 0.208 3.89 1.63 VCB 20 48 6 PNL 25 47 18 5.65 (*N9) (*S2)

02-S1 (Germ Free Trailer) 02-NH2-C1-B2-2 0.208 3.64 1.52 VCB 14 36 4 PNL 25 47 18 5.63 (*N5) (*N9) (*S2)

MV-N-USS-1-SWA (Rm. 19 202) MV-52-A1-50/51 13.800 16.71 15.39 VCB 27 44 45 PNL 152 48 18 5.59 (*N3) (*S2)

04-4A (Corr. D222) 05-P-CBD-1-6 0.208 4.12 1.74 VCB 20 50 6 PNL 25 47 18 5.51 (*N5) (*N9) (*S2)

05-LCBB (Corr. CB11) 05-PCBA-5 0.208 3.39 1.41 VCB 20 30 6 PNL 25 47 18 5.50 (*N9) (*S2)

01-EH-DP (Rm. 6221) (01-EH-DP-MB

LineSide)

01-SSB1-4A-4 0.480 14.98 11.55 VCB 40 78 14 PNL 25 46 18 5.42 (*S4)

MV-N-USS-1-SWB (Rm. 19 202) MV-52-B1-50/51 13.800 16.04 14.78 VCB 27 44 45 PNL 152 47 18 5.38 (*N3) (*S2)

06-1 (Corr. B2C1) 05-P-CBD-1-4 0.208 4.02 1.69 VCB 20 50 6 PNL 25 46 18 5.37 (*N9) (*S2)

21-B21-GRG (Rm. 110A) 21-B21-GRG-MB 0.208 3.69 1.54 VCB 20 58 6 PNL 25 46 18 5.36 (*N9) (*S2)

02-EL-MDP (Rm. G136) 02-EH-MDP-1 0.208 3.77 1.58 VCB 24 58 12 PNL 25 46 18 5.28 (*N5) (*N9) (*S2)

34-E (Rm. 109) 34-DP-F-5 0.208 3.66 1.53 VCB 20 48 6 PNL 25 45 18 5.27 (*N9) (*S2)

08.5-B (Rm. 14) (08.5-MB LineSide) 08.5-A-1 0.208 3.74 1.35 VCB 16 28 6 PNL 25 45 18 5.26 (*N3) (*S3)

01-EL-B2-N1-B1 (Rm. S21G) 01-EH-B2-N1-B1-1 0.208 3.65 1.53 VCB 20 66 6 PNL 25 45 18 5.25 (*N5) (*N9) (*S2)

01-EP-3-N-A (Rm. 3231) 01-EP-3-N-A-MB 0.208 3.64 1.52 VCB 20 54 6 PNL 25 45 18 5.21 (*N9) (*S2)

01-EP-3-N-B (Rm. 3231) 01-EP-3-N-B-MB 0.208 3.64 1.52 VCB 20 50 6 PNL 25 45 18 5.21 (*N9) (*S2)

02-TR-NL-1-H2-B2-SEC (Rm. 240E) 02-NH-1-H2-B2-1 0.208 3.04 0.82 HOA 24 24 20 AIR 32 38 18 5.18 (*N9) (*S2)

01-RPA (Rm. SG142) 01-RPA-MB 0.208 3.64 1.52 VCB 20 48 6 PNL 25 45 18 5.17 (*N9) (*S2)

01-PET-P1 (Rm. SG123) 01-PET-P1-MB 0.208 3.58 1.49 VCB 20 78 6 PNL 25 45 18 5.12 (*N9) (*S2)

04-4C (Corr. 2D18) 04-4C-MB 0.208 3.46 1.44 VCB 20 40 6 PNL 25 45 18 5.11 (*N9) (*S2)

02-TR-CL-1-D1-B2-SEC (Rm. 1135BE) 02-CPHV-1 0.208 2.99 0.8 HOA 24 24 20 AIR 32 37 18 5.07 (*N9) (*S2)

01-PAC-8-ECB (Rm. 2130) 01-PAC-8-ECB-CB 0.208 2.92 1.19 VCB 12 14 10 PNL 25 44 18 5.06 (*N9) (*S2)

02-TR-NL-G142A-1-SEC (Rm. G142A)

02-NH-B2-G142A-

NHDP-1-1

0.208 2.98 0.8 HOA 25 28 25 AIR 32 37 18 5.06 (*N9) (*S2)

05-PNL-4 (Corr. C268) (05-4-MB LineSide) 05-P-CBD-1-3 0.208 3.5 1.46 VCB 20 36 6 PNL 25 44 18 5.04 (*N9) (*S2)

06-2 (Corr. B2C1) 05-P-CBD-1-7 0.208 3.79 1.59 VCB 20 50 6 PNL 25 44 18 5.04 (*N9) (*S2)

01-LC1B-LP-1 (Ess. Elec. Rm.) 01-LC1B-LP-1-MB 0.208 3.3 1.37 VCB 20 38 6 PNL 25 44 18 4.99 (*N9) (*S2)

34-NL-34-P1 (Rm. 156A) 34-NL-34-P1-MB 0.208 3.5 1.46 VCB 20 72 6 PNL 25 44 18 4.99 (*N9) (*S2)

6.5-16

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes (*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-PAC-8-CONTACTOR (Rm.2130) 01-PAC-8-ECB-CB 0.208 2.87 1.17 VCB 12 14 10 PNL 25 44 18 4.97 (*N9) (*S2)

01-LP5/LSP5-ECB (Rm. 5170) (01-

LP5/LSP5-ECB-CB LineSide)

01-EDP-2 0.208 2.88 1.18 VCB 12 14 10 PNL 25 43 18 4.89 (*N9) (*S2)

01-LL-1-N1-B1-BP (Rm. 1199) 01-LH-LC7-DP-1 0.208 4.09 1.73 VCB 12 12 8 PNL 25 43 18 4.79 (*N5) (*N9) (*S4)

04-DB5-4-W (Rm. DB9) 04-DB4-ECB-CB 0.208 3.13 1.29 VCB 20 36 6 PNL 25 43 18 4.78 (*N9) (*S2)

01-LL-2-N1-B1-BP (Rm. 2213) 01-LH-LC7-DP-1 0.208 4.06 1.71 VCB 12 12 8 PNL 25 43 18 4.74 (*N5) (*N9) (*S4)

04-PPA (Corr. D203) 04-PPA-MB 0.208 3.26 1.35 VCB 20 42 6 PNL 25 42 18 4.71 (*N9) (*S2)

01-EMERG-P1/L-6-W-ECB (Rm. 6177) (01-

EMERG-P1/L-6-W-ECB-CB LineSide)

01-EDP-2 0.208 2.78 1.13 VCB 12 14 10 PNL 25 42 18 4.68 (*N9) (*S2)

03-A-1 (Rm. E101) 04-A-1-ECB-CB 0.208 3.1 1.28 VCB 16 36 4 PNL 25 42 18 4.65 (*N9) (*S2)

01-LL-4-N1-B1-BP (Rm. 4217) 01-LH-LC7-DP-1 0.208 3.98 1.68 VCB 12 12 8 PNL 25 42 18 4.64 (*N5) (*N9) (*S4)

01-SPD-B (Rm. SG174) 01-SPD-B-MB 0.208 3.76 1.36 VCB 20 42 6 PNL 25 42 18 4.63 (*N3) (*S4)

01-LL-5-N1-B1-BP (Rm. 5201A) 01-LH-LC7-DP-1 0.208 3.95 1.66 VCB 12 12 8 PNL 25 42 18 4.59 (*N5) (*N9) (*S4)

01-LL-B2-N1-B1-BP (Rm. S21G) 01-LH-LC7-DP-1 0.208 4.13 1.75 VCB 10 11 7 PNL 25 42 18 4.57 (*N5) (*N9) (*S4)

02-TR-LLMDP-SEC (Rm. G136) 02-LH-MDP-8 0.208 2.67 0.72 HOA 20 28 14 AIR 32 35 18 4.53 (*N9) (*S2)

01-LL-1-E1-B1-BP (Rm. 1120) 01-LH-LC7-DP-1 0.208 4.61 1.7 VCB 10 11 7 PNL 25 41 18 4.49 (*N3) (*N5) (*N9)

(*S4)

09-RPB9B (Rm. B102) 09-RPB9B-MB 0.208 3.09 1.27 VCB 20 44 6 PNL 25 41 18 4.47 (*N9) (*S0)

22-B22-GRG (Rm. 101) 22-B22-GRG-MB 0.208 3.16 1.3 VCB 20 83 6 PNL 25 41 18 4.47 (*N9) (*S2)

02-NL-1-H2-B2 (Rm. 240E) 02-NL-1-H2-B2-MB 0.208 2.99 1.23 VCB 20 38 6 PNL 25 41 18 4.45 (*N9) (*S2)

03-NEW-PANEL (Rm. E207) (03-NEW-

PANEL-MB LineSide)

03-OLD-PANEL-E207-

MB

0.208 2.95 1.21 VCB 20 35 6 PNL 25 41 18 4.44 (*N9) (*S2)

03-N/N-BASEMENT (Rm. EB01)

03-N/N-BASEMENT-

MB

0.208 3.2 1.32 VCB 20 50 6 PNL 25 41 18 4.43 (*N9) (*S2)

02-EL-1-D1-B2 (Rm. 1187) (02-EL-1-D1-

B2-MB LineSide)

02-EL-MDP-1 0.208 3.42 1.22 VCB 20 40 6 PNL 25 41 18 4.42 (*N3) (*N9) (*S2)

01-1LCL1 (Rm. G220A) 01-DP-PAD-3 0.208 3.09 1.27 VCB 20 38 6 PNL 25 41 18 4.42 (*N9) (*N21a) (*S2)

39-GEN-3-LD (Rm. 102A) Syn Gen/Mtr Decay

@10cycles

0.480 49.05 31.04 VCB 25 40 14 PNL 25 41 18 4.40…