This document is a combined synopsis/solicitation for commercial services for the tri-annual testing and maintenance of the electrical distribution system at the VA Connecticut Healthcare System West Haven and Newington campuses. The Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 1 is seeking a Service-Disabled Veteran-Owned Small Business (SDVOSB) to provide all labor, transportation, parts, and expertise necessary to conduct this work in accordance with NETA Maintenance and Testing Specifications. The contract will have a 30-day base period, with the majority of the work required to be performed outside of regular business hours to minimize disruption. Qualified contractors must have experience with electrical systems in healthcare facilities, be NETA certified, and have trained technicians. Proposals are due by August 16, 2024, and award will be made to the most advantageous offer based on price, capabilities, and past performance. The solicitation provides detailed requirements for the scope of work, deliverables, and scheduling of power outages required to complete the testing and maintenance.

View the file

Other files

File Type Posted
P01_Arc Flash Hazard Analysis Newington.pdf PDF
Item List.pdf PDF
P01_Arc Flash Hazard Analysis West Haven.pdf PDF
P01_Drawings Newington.pdf PDF
P01_Arc Flash Evaluation Report West Haven.pdf PDF
36C24124Q0631_2.docx DOCX document
P01_Drawings West Haven.pdf PDF
36C24124Q0631_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

6.5. Arc Flash Evaluation Report

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-116 (Rm. 116) 01-6110-0446-1 0.208 5.46 2.37 VCB 12 14 10 PNL 25 2 18 0.04 (*S1)

01-5925-0001-1 (Rm. 1S-179) 30-MDP-A-6 0.208 8.47 3.82 VCB 12 14 10 PNL 25 17 18 1.12 (*S1)

01-5925-0001-2 (Rm. 1S-179) 30-MDP-A-6 0.208 8.61 3.89 VCB 12 14 10 PNL 25 17 18 1.14 (*S1)

01-6110-0012-1 (Rm. 1S-179) 30-MDP-A-10 0.208 5.53 2.4 VCB 12 14 10 PNL 25 69 18 10.25 (*N9) (*S1)

01-6110-0012-2 (Rm. 1S-179) 30-MDP-A-10 0.208 5.65 2.46 VCB 12 14 10 PNL 25 70 18 10.51 (*N9) (*S1)

01-6110-0013 (Rm. 1N-110) 30-MDP-A-8 0.208 7.64 3.42 VCB 12 14 10 PNL 25 86 18 14.60 (*N9) (*S1)

01-6110-0014 (Rm. 1N-110) 30-MDP-A-8 0.208 7.81 3.5 VCB 12 14 10 PNL 25 87 18 14.94 (*N9) (*S1)

01-6110-0024-1 (Rm. 1N-206) 01-6110-0013-1 0.208 6.65 2.94 VCB 12 14 10 PNL 25 73 18 11.34 (*S2)

01-6110-0024-2 (Rm. 1N-206) 01-6110-0013-1 0.208 6.49 2.86 VCB 12 14 10 PNL 25 75 18 11.75 (*S2)

01-6110-0263 (LS) (B.1C Attic) 01-6110-0263-MB 0.208 5.41 2.35 VCB 12 14 10 PNL 25 69 18 10.33 (*N9) (*S1)

01-6110-0264 (B.1 Attic) 01-6110-0386-1 0.208 6.45 2.45 VCB 12 14 10 PNL 25 70 18 10.55 (*N3) (*N9) (*S1)

01-6110-0291 (Attic) 01-6110-0385-5 0.208 6.03 2.64 VCB 12 14 10 PNL 25 72 18 11.05 (*N9) (*S1)

01-6110-0292 (B.1 Attic) (01-6110-0292-MB

LineSide)

01-6110-0385-6 0.208 6.03 2.64 VCB 12 14 10 PNL 25 72 18 11.05 (*N9) (*S1)

01-6110-0295 (Rm. 1N-206) 1-XRAY-FDS-FU 0.480 4.04 2.96 VCB 12 14 10 PNL 25 78 18 12.46 (*N9) (*S1)

01-6110-0301 (Rm. 1S-179) 30-MDP-A-4 0.208 6.24 2.36 VCB 12 14 10 PNL 25 69 18 10.16 (*N3) (*N9) (*S1)

01-6110-0302-1 (Rm. 1S-179) 30-MDP-B-7 0.208 6.09 2.3 VCB 12 14 10 PNL 25 69 18 10.24 (*N3) (*N9) (*S1)

01-6110-0302-2 (Rm. 1S-179) 30-MDP-B-7 0.208 5.97 2.25 VCB 12 14 10 PNL 25 68 18 10.01 (*N3) (*N9) (*S1)

01-6110-0304 (Rm. 1N-110) 01-6110-0304-MB 0.208 2.16 0.86 VCB 12 14 10 PNL 25 30 18 2.68 (*N9) (*S2)

01-6110-0385 (Rm. 1S-162-0) 03-G7MDP-3 0.208 3.86 1.62 VCB 12 14 10 PNL 25 35 18 3.54 (*N9) (*S2)

01-6110-0386 (Rm. 1S-162-0) 03-G7MDP-2 0.208 3.24 1.34 VCB 12 14 10 PNL 25 36 18 3.55 (*N9) (*S2)

01-6110-0427 (Rm. 1S-179) 01-6110-0385-8 0.208 2.12 0.84 VCB 12 14 10 PNL 25 28 18 2.41 (*N9) (*S2)

01-6110-0428 (Rm. 1S-179) 30-MDP-A-13 0.208 5.96 2.24 VCB 12 14 10 PNL 25 66 18 9.66 (*N3) (*N9) (*S1)

01-6110-0429 (Rm. 1N-110) 30-MDP-A-8 0.208 7.49 3.34 VCB 12 14 10 PNL 25 85 18 14.27 (*N9) (*S1)

01-6110-0431 (Rm. 141) 01-6110-0386-2 0.208 2.89 1.18 VCB 12 14 10 PNL 25 34 18 3.28 (*N9) (*S2)

01-6110-0432 (Rm. 1C-143) 01-6110-0304-1 0.208 0.66 0.24 VCB 12 14 10 PNL 25 16 18 0.95 (*N9) (*S3)

01-6110-0434 (Rm. 1N-206) 01-6110-0013-1 0.208 6.65 2.94 VCB 12 14 10 PNL 25 73 18 11.34 (*S2)

01-6110-0436 (Rm. 1N-206) 01-6110-0013-1 0.208 6.65 2.94 VCB 12 14 10 PNL 25 73 18 11.34 (*S2)

01-6110-0437 (Rm. 1C-241) 01-6110-0386-4 0.208 2.67 1.08 VCB 12 14 10 PNL 25 33 18 3.13 (*N9) (*S2)

01-6110-0445 (B.1 Attic) 01-6110-0264-1 0.240 0.17 0.17 VCB 12 14 10 PNL 25 7 18 0.20 (*N9) (*N_ka) (*S0)

01-6110-0446 (Rm. 1N-110) 30-MDP-A-8 0.208 7.97 3.58 VCB 12 14 10 PNL 25 88 18 15.28 (*N9) (*S3)

01-6110-0457 (IRM) 01-6110-0457-MB 0.208 2.53 1.02 VCB 20 36 6 PNL 25 37 18 3.75

(*N2) (*N8) (*N9)

(*S2)

01-6110-0458 (IRM) 01-6110-0458-MB 0.208 2.53 1.02 VCB 20 36 6 PNL 25 37 18 3.75

(*N2) (*N8) (*N9)

(*S2)

01-6110-0459 (Rm. 3-101A) 01-ADP-2 0.208 4.01 1.69 VCB 12 14 10 PNL 25 2 18 0.04 (*S1)

6.5-1

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-6110-0461 (IRM) 01-ADP-1 0.208 6.74 2.98 VCB 12 14 10 PNL 25 8 18 0.33 (*S3)

01-ADP (IRM) (01-ADP-MB LineSide) 30-MDP-A-9 0.208 9.34 4.24 VCB 12 14 10 PNL 25 12 18 0.64 (*S1)

01-AIR-HANDLER-FDS (Rm. 1S-162-0) (01-AIR-

HANDLER-FDS-FU LineSide)

30-MDP-B-3 0.208 13.73 6.37 VCB 12 14 10 PNL 25 16 18 0.98 (*S1)

01-ATS-7-2-LD (Rm. 1S-162-0) 03-G7MDP-2 0.208 3.29 1.36 VCB 12 14 10 PNL 25 36 18 3.59 (*N9) (*S2)

01-ATS-7-3-LD (Rm. 1S-162-0) 03-G7MDP-3 0.208 3.88 1.63 VCB 12 14 10 PNL 25 36 18 3.57 (*N9) (*S2)

01-BOILER RM-FDS (Rm. 1S-162-0)

01-BOILER RM-FDS-

FU

0.208 5.55 2.41 VCB 12 14 10 PNL 25 70 18 10.62 (*N9) (*S1)

01-EDP (Rm. 1N-112) (01-EDP-MB LineSide) 30-EDP-FDS-FU 0.480 3.62 2.64 VCB 12 14 10 PNL 25 72 18 11.01 (*N9) (*N21a) (*S1)

01-EL1P (Rm. 1N-110) (01-EL1P-MB LineSide) 01-6110-0385-4 0.208 2.44 0.85 VCB 12 14 10 PNL 25 27 18 2.31 (*N3) (*N9) (*S2)

01-EL3P (Rm. 1-310A) 01-6110-0385-2 0.208 2.27 0.91 VCB 12 14 10 PNL 25 28 18 2.38 (*S2)

01-EL3Q (Rm. 1-341) 01-6110-0385-1 0.208 2.53 0.88 VCB 12 14 10 PNL 25 28 18 2.37 (*N3) (*N9) (*S2)

01-EL4Q (Rm. 15-440A) 01-EL3Q-1 0.208 3.77 1.58 VCB 12 14 10 PNL 25 2 18 0.03 (*S1)

01-EL5P (Rm. 1-511) 01-EL3P-2 0.208 2.81 1.15 VCB 12 14 10 PNL 25 1 18 0.02 (*S1)

01-EL5Q (Rm. 1-535) 01-EL3Q-2 0.208 3.27 1.35 VCB 12 14 10 PNL 25 2 18 0.02 (*S1)

01-ELAR (6110-3137) (B.1 Attic) 01-6110-0386-6 0.208 2.4 0.97 VCB 12 14 10 PNL 25 31 18 2.90 (*N9) (*S2)

01-ELEV-P4-ECB (Elev Rm. in Attic) (01-ELEV-P4-

ECB-CB LineSide)

01-6110-0385-3 0.208 8.15 3.16 VCB 12 14 10 PNL 25 75 18 11.74 (*N3) (*S0)

01-ELEV-P5-ECB (Elev Rm. in Attic) (01-ELEV-P5-

ECB-CB LineSide)

01-6110-0385-3 0.208 8.56 3.33 VCB 12 14 10 PNL 25 72 18 10.90 (*N3) (*S0)

01-ELP4 (Rm. 1-413) 01-EL3P-1 0.208 2.79 0.98 VCB 12 14 10 PNL 25 38 18 3.91 (*N3) (*S1)

01-FP-01-FPC-LD (Rm. 1S-180) MV-SSW-9-FU 0.208 7.44 3.32 VCB 12 14 10 PNL 25 77 18 11.76 (*N9) (*S1)

01-MDP (Rm. 1N-112) (01-MDP-MB LineSide) 30-MDP-FDS-FU 0.480 3.82 2.79 VCB 12 14 10 PNL 25 72 18 11.08 (*N9) (*N21a) (*S1)

01-NL1P (Rm. 1N-110) (01-NL1P-MB LineSide) 30-MDP-A-3 0.208 9.46 4.3 VCB 12 14 10 PNL 25 12 18 0.65 (*S1)

01-NL3P1 (Rm. 1-310A) 30-MDP-A-3 0.208 9.54 4.34 VCB 12 14 10 PNL 25 12 18 0.66 (*S1)

01-NL3P2 (Rm. 1-310A) 30-MDP-A-3 0.208 9.14 4.15 VCB 12 14 10 PNL 25 12 18 0.63 (*S1)

01-NL3Q1 (Rm. 1-341) 30-MDP-A-7 0.208 9.96 3.92 VCB 12 14 10 PNL 25 85 18 14.22 (*N3) (*N9) (*S1)

01-NL3Q2 (Rm. 1-341) 30-MDP-A-7 0.208 9.79 3.85 VCB 12 14 10 PNL 25 83 18 13.88 (*N3) (*N9) (*S1)

01-NL4P (Rm. 1-413) 01-NL3P2-1 0.208 7.39 3.3 VCB 12 14 10 PNL 25 3 18 0.06 (*S1)

01-NL4P2 (Rm-1-413) 01-NL3P2-2 0.208 7.02 3.12 VCB 12 14 10 PNL 25 3 18 0.06 (*S1)

01-NL4P2-ECB (Rm. 1-413) 01-NL3P2-2 0.208 7.39 3.3 VCB 12 14 10 PNL 25 3 18 0.06 (*S1)

01-NL4Q (Rm. 15-440A) 01-NL3Q1-1 0.208 8.92 4.04 VCB 12 14 10 PNL 25 3 18 0.08 (*S1)

01-NL5P (Rm. 1-511) 01-NL3P2-3 0.208 6.68 2.95 VCB 12 14 10 PNL 25 3 18 0.05 (*S1)

01-NL5Q (Rm. 1-535) 01-NL3Q1-2 0.208 7.98 3.58 VCB 12 14 10 PNL 25 3 18 0.07 (*S1)

6.5-2

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

01-TE164 (Rm. 1S-164) (01-TE164-MB LineSide) 01-6110-0385-9 0.208 3.46 1.44 VCB 12 14 10 PNL 25 34 18 3.31 (*N9) (*S2)

01-T-MOBILE (Roof Adjacent Elev.) 01-6110-0291-1 0.208 4.73 1.74 VCB 12 14 10 PNL 25 42 18 4.64 (*N3) (*S3)

01-UPSSUB (Rm. 1S-164) 01-TE164-1 0.208 5.51 2.39 VCB 12 14 10 PNL 25 4 18 0.09 (*S0)

01-XF-6110-0445-1-SEC (B.1 Attic) 01-6110-0264-1 0.240 0.22 0.22 VCB 12 14 10 PNL 25 8 18 0.25 (*N9) (*N_ka) (*S1)

01-XF-6110-0445-2-SEC (B.1 Attic) 01-6110-0264-1 0.240 0.17 0.17 VCB 12 14 10 PNL 25 7 18 0.21 (*N9) (*N_ka) (*S1)

01-XRAY1-ECB (Rm. 213) 01-6110-0295-1 0.480 3.68 2.68 VCB 12 14 10 PNL 25 4 18 0.11 (*S1)

01-XRAY2-ECB (Rm. 214) 01-6110-0295-2 0.480 3.68 2.68 VCB 12 14 10 PNL 25 4 18 0.11 (*S1)

03-6110-0088 (Rm. 3-110) 03-6110-0383-4 0.208 6.36 2.8 VCB 12 14 10 PNL 25 4 18 0.11 (*S1)

03-6110-0090-1 (Rm. 3-110) 06-6110-0090-1-MB 0.208 5.71 2.49 VCB 12 14 10 PNL 25 72 18 10.96 (*N9) (*S0)

03-6110-0090-2 (Rm. 3-110) 03-R&G1-1 0.208 5.54 2.41 VCB 12 14 10 PNL 25 70 18 10.60 (*N9) (*S0)

03-6110-0096 (B.3 3rd Fl. Elec. Rm.) 03-6110-0090-2-1 0.208 3.2 1.14 VCB 12 14 10 PNL 25 40 18 4.27 (*N3) (*S0)

03-6110-0183 (Boiler Plant) 03-6110-0183-MB 0.208 0.72 0.26 VCB 12 14 10 PNL 25 17 18 1.05 (*N9) (*S1)

03-6110-0183-FDS (Rm. 3-128D) 03-6110-0183-FDS-FU 0.208 0.75 0.27 VCB 12 14 10 PNL 25 17 18 1.09 (*N9) (*S1)

03-6110-0188 (Rm. 3-128D) 03-6110-0188-MB 0.208 0.75 0.27 VCB 12 14 10 PNL 25 17 18 1.09 (*N9) (*S1)

03-6110-0225 (Rm. 3-110) 03-6110-0423-2 0.208 5.64 2.45 VCB 12 14 10 PNL 25 7 18 0.25 (*S3)

03-6110-0261 (Rm. 3-128E) 03-6110-0261-MB 0.208 0.51 0.18 VCB 12 14 10 PNL 25 12 18 0.63 (*N9) (*S3)

03-6110-0261-NFDS (Rm. 3-128E) 03-BPMCC-2 0.240 0.75 0.31 VCB 12 14 10 PNL 25 18 18 1.23 (*N9) (*S1)

03-6110-0273 (B.3 3rd Fl. Elec. Rm.) 30-MDP-B-8 0.208 6.36 2.41 VCB 12 14 10 PNL 25 71 18 10.76 (*N3) (*N9) (*S0)

03-6110-0275 (B.3 Attic) 01-6110-0385-7 0.208 0.45 0.45 VCB 12 14 10 PNL 25 11 18 0.44 (*N_ka) (*S0)

03-6110-0276 (Attic) 03-6110-0383-6 0.208 3.34 1.19 VCB 12 14 10 PNL 25 30 18 2.76 (*N3) (*S2)

03-6110-0277 (Attic) 03-6110-0277-MB 0.208 5.78 2.52 VCB 12 14 10 PNL 25 71 18 10.73 (*N9) (*S1)

03-6110-0278 (B.3 2nd Fl. Elec. Rm.) 03-6110-0282-3 0.208 5.74 2.5 VCB 12 14 10 PNL 25 71 18 10.66 (*N9) (*S1)

03-6110-0279 (B.3 2nd Fl. Elec. Rm.) 03-R&G1-3 0.208 4.81 1.78 VCB 12 14 10 PNL 25 4 18 0.10 (*N3) (*S0)

03-6110-0282 (Rm. 3-113) 03-6110-0282-MB 0.208 7.31 3.26 VCB 12 14 10 PNL 25 83 18 13.91 (*N9) (*S1)

03-6110-0305 (Rm. 3-110) 30-MDP-A-5 0.208 6.07 2.29 VCB 12 14 10 PNL 25 67 18 9.83 (*N3) (*N9) (*S1)

03-6110-0310 (Boiler Plant) 03-6110-0310-MB 0.240 0.74 0.31 VCB 12 14 10 PNL 25 18 18 1.22 (*N9) (*S1)

03-6110-0311 (Rm. 3-110) 30-MDP-B-9 0.208 9.15 4.15 VCB 12 14 10 PNL 25 18 18 1.24 (*S1)

03-6110-0383 (Rm. 3-113) 03-6110-0282-1 0.208 6.71 2.55 VCB 12 14 10 PNL 25 72 18 10.97 (*N3) (*N9) (*S1)

03-6110-0423 (Rm. 3-110) 03-6110-0282-2 0.208 6.79 3 VCB 12 14 10 PNL 25 4 18 0.11 (*S1)

03-6110-0462 (Rm. 3-101) 03-6110-0383-3 0.208 2.95 1.21 VCB 20 36 6 PNL 25 2 18 0.04 (*N8) (*S2)

03-6110-0463 (Rm. 3-102) 03-6110-0282-5 0.208 3.17 1.13 VCB 12 14 10 PNL 25 33 18 3.11 (*N3) (*N9) (*S2)

6.5-3

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

03-ATS-6-LD (Rm. 3-128D)

01-BOILER RM-FDS-

FU

0.208 2.79 1.14 VCB 12 14 10 PNL 25 43 18 4.84 (*N9) (*S1)

03-ATS-7-1-FDS (Rm. 3-113) (03-ATS-7-1-FDS-FU

LineSide)

30-MDP-A-14 0.208 8.44 3.81 VCB 12 14 10 PNL 25 92 18 16.25 (*N9) (*S1)

03-ATS-7-1-LD (Rm. 3-113) 03-G7MDP-1 0.208 5.31 2.3 VCB 12 14 10 PNL 25 43 18 4.84 (*N9) (*S2)

03-BP1 (Boiler Plant) 03-BPMCC-4 0.240 0.74 0.31 VCB 12 14 10 PNL 25 18 18 1.22 (*N9) (*S1)

03-BPMCC (Rm. 3-128D) 03-BPMCC-FDS-FU 0.240 0.78 0.32 VCB 12 14 10 PNL 25 19 18 1.29 (*N9) (*S1)

03-BPMCCF (Rm. 3-128D) 03-BPMCCF-MB 0.240 0.76 0.32 VCB 12 14 10 PNL 25 19 18 1.25 (*N9) (*S1)

03-BPMCC-FDS (Rm. 3-1238D) 03-BPMCC-FDS-FU 0.208 2.75 1.12 VCB 12 14 10 PNL 25 43 18 4.77 (*N9) (*S1)

03-EP-1 (EMS Storage) 03-6110-0282-4 0.208 4.61 1.7 VCB 12 14 10 PNL 25 4 18 0.11 (*N3) (*S2)

03-G7MDP (Rm. 3-113) 03-G7MDP-ECB-CB 0.208 6.07 2.66 VCB 12 14 10 MCC 25 48 18 5.72 (*N9) (*S3)

03-GEN-2-ECB (Rm. 3-128G) (03-G7MDP-ECB-CB

LineSide) MaxTripTime @2.0s 0.208 7.9 3.54 VCB 12 14 10 PNL 25 51 18 6.32 (*N2) (*N9) (*S2)

03-GEN-MB-ECB (Rm. 3-128G) 03-GEN-MB 0.208 4.04 1.71 VCB 12 14 10 PNL 25 34 18 3.36 (*N9) (*S3)

03-LD-CENTER (Gated Area) 03-6110-0305-1 0.208 5.64 2.45 VCB 12 14 10 PNL 25 2 18 0.05 (*S1)

03-PP (Rm. EMS Storage) 03-6110-0282-3 0.208 5.74 2.5 VCB 12 14 10 PNL 25 71 18 10.66 (*N9) (*S1)

03-R&G1 (Grounds Shop) 30-MDP-B-8 0.208 6.64 2.93 VCB 12 14 10 PNL 25 15 18 0.86 (*S0)

03-R&G2 (Grounds Shop) 03-R&G1-2 0.208 6.52 2.88 VCB 12 14 10 PNL 25 79 18 12.77 (*N9) (*S0)

03-R&G3 (Grounds Shop) 03-R&G1-2 0.208 6.26 2.75 VCB 12 14 10 PNL 25 77 18 12.18 (*N9) (*S0)

03-XF-6110-0183/0183-SEC (Rm. 3-128D) 03-BPMCC-1 0.208 0.77 0.2 HOA 28 32 14 AIR 32 18 18 1.22 (*N9) (*S0)

03-XF-6110-0261-SEC (Rm. 3-128E) 03-BPMCC-2 0.208 0.51 0.13 HOA 16 30 16 AIR 32 14 18 0.71 (*N9) (*S2)

03-XF-BUCK-BOOST-SEC (Rm. 3-128E) 03-BPMCC-FDS-FU 0.240 0.79 0.24 HOA 16 30 16 AIR 32 20 18 1.44 (*N9) (*S0)

06A-DIST (B. 6A) 07-EXT-MDP-01 0.240 4.26 2.03 VCB 12 14 10 PNL 25 63 18 8.82 (*N9) (*S0)

06A-MDP (B. 6A) 06A-MDP-MB 0.240 4.06 1.92 VCB 12 14 10 PNL 25 61 18 8.33 (*N9) (*S0)

06B-MDP (B. 6B) 06B-MDP-MB 0.240 3.87 1.82 VCB 12 14 10 PNL 25 58 18 7.89 (*N9) (*S0)

07A-MDP (B. 7) (07A-MDP-MB LineSide) 07-EXT-MDP-02 0.240 5.09 2.46 VCB 12 14 10 PNL 25 71 18 10.81 (*N9) (*S0)

07B-MDP (B. 7) (07B-MDP-MB LineSide) 07-EXT-MDP-02 0.240 5.7 2.78 VCB 12 14 10 PNL 25 77 18 12.31 (*N9) (*S0)

07-EXT-MDP (Ext. B.7) 07-EXT-MDP-MB 0.240 10.3 5.26 VCB 12 14 10 PNL 25 118 18 24.10 (*N9) (*S3)

08-MDP (B. 8) 08-MDP-MB 0.240 2.99 1.38 VCB 12 14 10 PNL 25 49 18 5.88 (*N9) (*S0)

11-FP-03-LD (Rm. 11-101A) MV-SW-2W-FU 0.208 4.43 1.88 VCB 12 14 10 PNL 25 47 18 5.51 (*N9) (*S1)

11-GEN-MB-ECB (Rm. 11-101A) MaxTripTime @2.0s 0.208 13.88 6.44 VCB 12 14 10 PNL 25 74 18 11.40 (*N2) (*N9) (*S2)

11-LP (Rm. 11-101) 03-6110-0183-MB 0.208 0.69 0.25 VCB 12 14 10 PNL 25 16 18 1.00 (*N9) (*S1)

12-6110-0026 (Basement) (12-6110-0026-MB

LineSide)

12-6110-0440-6 0.208 3.83 1.61 VCB 12 14 10 PNL 25 54 18 6.95 (*N9) (*S0)

12-6110-0121 (B.12 Basement) (12-6110-0121-MB

LineSide)

12-6110-0121-FU 0.208 4.19 1.53 VCB 12 14 10 PNL 25 17 18 1.12 (*N3) (*S2)

6.5-4

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

12-6110-0121-FDS (B.12 Basement) (12-6110-0121-

FU LineSide)

30-MDP-B-6 0.208 4.37 1.86 VCB 12 14 10 PNL 25 59 18 8.07 (*N9) (*S1)

12-6110-0146 (Upstairs B.12) (12-6110-0146-MB

LineSide)

12-6110-0440-2 0.208 3.43 1.42 VCB 12 14 10 PNL 25 46 18 5.41 (*S3)

12-6110-0358 (Upstairs B. 12) 12-6110-0440-3 0.208 3.43 1.42 VCB 12 14 10 PNL 25 46 18 5.41 (*S0)

12-6110-0359 (Basement) 12-6110-0359-MB 0.208 2.71 1.1 VCB 12 14 10 PNL 25 42 18 4.70 (*N9) (*S0)

12-6110-0360 (Basement) 12-6110-0360-MB 0.208 1.88 0.74 VCB 12 14 10 PNL 25 33 18 3.09 (*N9) (*S1)

12-6110-0360/12-6110-0426-FDS (B.12 Basement)

(12-6110-0360-FU LineSide)

30-MDP-B-6 0.208 4.23 1.79 VCB 12 14 10 PNL 25 58 18 7.79 (*N9) (*S1)

12-6110-0440 (B.12 Basement) (12-6110-0440-MB

LineSide)

3-12-6110-0440-FDS-

FU

0.208 4.47 1.91 VCB 12 14 10 PNL 25 60 18 8.30 (*N9) (*S1)

12-6110-0441 (Upstairs B. 12) 12-6110-0441-MB 0.208 3.66 1.53 VCB 20 36 6 PNL 25 48 18 5.72 (*N2) (*N8) (*N9)

(*S2)

14-EXT-PNL (B. 14) 12-6110-0440-4 0.208 1.88 0.74 VCB 12 14 10 PNL 25 33 18 3.09 (*N9) (*S0)

1-XRAY-FDS (South Courtyard) (1-XRAY-FDS-

FU LineSide)

MV-SSW-6-FU 0.480 5.01 3.71 VCB 12 14 10 PNL 25 90 18 15.79 (*N9) (*S1)

21-MDP (B. 21) 21-MDP-MB 0.240 0.79 0.33 VCB 20 36 6 PNL 25 17 18 1.13

(*N2) (*N8) (*N9)

(*S2)

24-MTR-FDS (South Courtyard) 24-MTR-FDS-FU 0.480 5.44 3.55 VCB 12 14 10 PNL 25 26 18 2.17 (*N3) (*S2)

24-NL-FDS (South Courtyard) (24-NL-FDS-FU

LineSide)

MV-SSW-5-FU 0.480 5.78 4.31 VCB 12 14 10 PNL 25 91 18 15.91 (*N9) (*S1)

2C-6110-0055 (Rm. 2C-2101 Corridor) 2C-6110-0055-FDS-FU 0.208 3.5 1.26 VCB 12 14 10 PNL 25 29 18 2.62 (*N3) (*S2)

2C-6110-0055-FDS (Rm. 2C-2124) (2C-6110-0055-

FDS-FU LineSide)

2C-NH2F-1 0.208 4.03 1.7 VCB 12 14 10 PNL 25 56 18 7.28 (*N9) (*S1)

2C-6110-0056 (Rm. 2C-2101 Corridor) 2C-6110-0055-FDS-FU 0.208 3.48 1.25 VCB 12 14 10 PNL 25 30 18 2.69 (*N3) (*S2)

2C-6110-0442 (B.2C Attic) 2C-QLPA-1 0.208 0.92 0.34 VCB 12 14 10 PNL 25 18 18 1.22 (*N9) (*S1)

2C-ATS-10-4 (CRATS)-LD (2C-1164) 2C-MDP-8 0.480 9.45 7.2 VCB 12 14 10 PNL 25 7 18 0.24 (*S1)

2C-ATS-10-5 (EQATS)-LD (Rm. 2C-1164) 2C-EDP2C-1 0.480 3.96 2.54 VCB 12 14 10 PNL 25 34 18 3.35 (*N3) (*N9) (*S2)

2C-ATS-10-6 (LSATS)-LD (Rm. 2C-1164) 2C-MDP-9 0.480 9.45 7.2 VCB 12 14 10 PNL 25 7 18 0.24 (*S1)

2C-CH1D (Rm. 2C-1122) 2E-CR2EDP-6 0.480 3.08 2.22 VCB 12 14 10 PNL 25 3 18 0.09 (*S1)

2C-CH1F (Rm. 2C-1135) 2C-CRDP2C-1 0.480 5.3 3.45 VCB 12 14 10 PNL 25 6 18 0.21 (*N3) (*S3)

2C-CH2F (Rm. 2C-2124) 2C-CRDP2C-2 0.480 5.8 3.79 VCB 12 14 10 PNL 25 6 18 0.21 (*N3) (*S3)

2C-CH3F (Rm. 2C-3124) 2C-CH2F-2 0.480 4.38 2.82 VCB 12 14 10 PNL 25 6 18 0.22 (*N3) (*S3)

2C-CL1D (Rm. 2C-1122) 2C-CL1D-MB 0.208 1.26 0.48 VCB 12 14 10 PNL 25 25 18 1.97 (*N9) (*S1)

2C-CL1F (Rm. 2C-1135) 2C-CL1F-MB 0.208 0.98 0.37 VCB 12 14 10 PNL 25 20 18 1.47 (*N9) (*S1)

2C-CL2F (Rm. 2C-2124) 2C-CL2F-MB 0.208 0.97 0.36 VCB 12 14 10 PNL 25 20 18 1.47 (*N9) (*S1)

2C-CL2F1 (Rm. 2C-2115) 2C-CL2F1-MB 0.208 0.95 0.35 VCB 12 14 10 PNL 25 20 18 1.42 (*N9) (*S1)

6.5-5

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

2C-CL3F (Rm. 2C-3124) 2C-CL3F-MB 0.208 1.28 0.49 VCB 12 14 10 PNL 25 25 18 1.99 (*N9) (*S1)

2C-CRDP2C (Rm. 2C-1164) 2C-MDP-8 0.480 9.22 7.02 VCB 12 14 10 PNL 25 6 18 0.24 (*S1)

2C-EDP2C (Rm. 2C-1164) 2W-EDP2W-1 0.480 3.98 2.91 VCB 12 14 10 PNL 25 37 18 3.82 (*N9) (*S2)

2C-EH1F (Rm. 2C-1135) 2C-LSDP2C-1 0.480 7.11 5.35 VCB 12 14 10 PNL 25 7 18 0.24 (*S3)

2C-EH2F (Rm. 2C-2124) 2C-LSDP2C-2 0.480 4.52 2.91 VCB 12 14 10 PNL 25 6 18 0.22 (*N3) (*S3)

2C-EH3F (Rm. 2C-3124) 2C-EH2F-1 0.480 1.72 1.06 VCB 12 14 10 PNL 25 6 18 0.23 (*N3) (*S2)

2C-EL1F (Rm. 2C-1135) 2C-EL1F-MB 0.208 0.79 0.29 VCB 12 14 10 PNL 25 18 18 1.16 (*N9) (*S1)

2C-ELBB (Rm. 2C-B00) 2C-ELBB-MB 0.208 0.72 0.26 VCB 12 14 10 PNL 25 17 18 1.05 (*N9) (*S1)

2C-ELEV-P6-ECB (Rm. 2C-1163) 2C-EQDP2C-3 0.480 7.49 5.65 VCB 12 14 10 PNL 25 4 18 0.11 (*S1)

2C-ELEV-P7-ECB (Rm. 2C-B00) (2C-ELEV P7-ECB-

CB LineSide)

2C-EQDP2C-4 0.480 2.65 1.66 VCB 12 14 10 PNL 25 42 18 4.66 (*N3) (*S0)

2C-EQDP2C (Rm. 2C-1164) 2C-EQDP2C-MB 0.480 3.95 2.88 VCB 12 14 10 PNL 25 37 18 3.80 (*N9) (*S2)

2C-LSDP2C (Rm. 2C-1164) (2C-LSDP2C-MB

LineSide)

2C-MDP-9 0.480 9.22 7.02 VCB 12 14 10 PNL 25 6 18 0.24 (*S1)

2C-MDP (Rm. C1-1164) 2C-MDP-MB 0.480 10.02 7.66 VCB 12 14 10 PNL 25 34 18 3.27 (*S1)

2C-NH1D (Rm. 2C-1122) 2C-MDP-6 0.480 5.23 3.88 VCB 12 14 10 PNL 25 14 18 0.83 (*S1)

2C-NH1F (Rm. 2C-1135) 2C-MDP-4 0.480 8.51 6.46 VCB 12 14 10 PNL 25 6 18 0.23 (*S1)

2C-NH2F (Rm. 2C-2124) 2C-MDP-3 0.480 8.41 6.38 VCB 12 14 10 PNL 25 6 18 0.23 (*S1)

2C-NH3F (Rm. 2C-3124) 2C-MDP-2 0.480 7.64 5.06 VCB 12 14 10 PNL 25 10 18 0.49 (*N3) (*S3)

2C-NHPA (B.2C Attic) 2C-MDP-1 0.480 7.29 4.82 VCB 12 14 10 PNL 25 6 18 0.23 (*N3) (*S2)

2C-NL1D (Rm. 2C-1122) 2C-NL1D-MB 0.208 0.97 0.36 VCB 12 14 10 PNL 25 20 18 1.47 (*N9) (*S1)

2C-NL1F1 (Rm. 2C-1135) 2C-NL1F1-MB 0.208 2.36 0.95 VCB 12 14 10 PNL 25 38 18 3.99 (*N9) (*S1)

2C-NL1F2 (Rm. 2C-1135) 2C-NL1F2-MB 0.208 2.32 0.93 VCB 12 14 10 PNL 25 38 18 3.90 (*N9) (*S1)

2C-NL2F1 (Rm. 2C-2124) 2C-NL2F1-MB 0.208 2.39 0.96 VCB 12 14 10 PNL 25 38 18 4.03 (*N9) (*S1)

2C-NL2F2 (Rm. 2C-2124) 2C-NL2F2-MB 0.208 2.36 0.95 VCB 12 14 10 PNL 25 38 18 3.98 (*N9) (*S1)

2C-NL3F (Rm, 2C-3124) 2C-NL3F-MB 0.208 2.37 0.95 VCB 12 14 10 PNL 25 38 18 3.99 (*N9) (*S1)

2C-NLBF (Rm. 2C-0001) 2C-NLBF-MB 0.208 1.26 0.48 VCB 12 14 10 PNL 25 24 18 1.95 (*N9) (*S1)

2C-NLCAP (Rm. 2C-1104) 2C-MDP-5 0.208 1.2 0.46 VCB 12 14 10 PNL 25 24 18 1.87 (*N9) (*S1)

2C-NLCAP-NFDS (Rm. 2C-1122) 2C-MDP-5 0.208 1.75 0.68 VCB 12 14 10 PNL 25 32 18 2.83 (*N9) (*S1)

2C-NLPA (B.2C Attic) 2C-NLPA-MB 0.208 3.28 1.36 VCB 12 14 10 PNL 25 48 18 5.77 (*N9) (*S1)

2C-QHPA (B.2C Attic) 2C-EQDP2C-5 0.480 6.05 3.96 VCB 12 14 10 PNL 25 6 18 0.21 (*N3) (*S3)

2C-QL1F (Rm. 2C-1163) 2C-QL1F-MB 0.208 0.73 0.27 VCB 12 14 10 PNL 25 17 18 1.06 (*N9) (*S1)

2C-QLBB (Rm. 2C-B00) 2C-QLBB-MB 0.208 0.7 0.26 VCB 12 14 10 PNL 25 16 18 1.02 (*N9) (*S1)

2C-QLPA (B.2C Attic) 2C-QLPA-MB 0.208 1.11 0.42 VCB 12 14 10 PNL 25 21 18 1.49 (*N9) (*S1)

2C-XF-6110-0055-SEC (Rm. 2C-2115) 2C-NH2F-1 0.208 4.13 1.75 VCB 12 14 10 PNL 25 57 18 7.50 (*N9) (*S1)

2C-XF-CL1F-SEC (Rm. 2C-1135) 2C-CH1F-1 0.208 0.99 0.26 HOA 20 30 14 AIR 32 21 18 1.58 (*N9) (*S0)

6.5-6

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

2C-XF-CL2F-SEC (Rm. 2C-2124) 2C-CH2F-1 0.208 0.99 0.26 HOA 20 30 14 AIR 32 21 18 1.59 (*N9) (*S0)

2C-XF-CL3F-SEC (Rm. 2C-3124) 2C-CH3F-1 0.208 1.32 0.35 HOA 20 14 10 AIR 32 25 18 2.14 (*N9) (*S0)

2C-XF-EL1F-SEC (Rm. 2C-1135) 2C-LSDP2C-3 0.208 0.81 0.21 HOA 14 20 10 AIR 32 19 18 1.29 (*N9) (*S0)

2C-XF-ELBB-SEC (Rm. 2C-B00) 2C-EH1F-1 0.208 0.75 0.2 HOA 20 14 10 AIR 32 18 18 1.19 (*N9) (*S0)

2C-XF-NH/CAP-NFDS (Rm. 2C-1122) 2C-MDP-5 0.480 3.31 2.39 VCB 12 14 10 PNL 25 11 18 0.50 (*S1)

2C-XF-NH/CAP-SEC (Rm. 2C-1122) 2C-MDP-5 0.208 1.82 0.49 HOA 23 30 17 AIR 32 32 18 3.03 (*N9) (*S2)

2C-XF-NL1D-SEC (Rm. 2C-1122) 2C-NH1D-1 0.208 0.98 0.26 HOA 20 30 14 AIR 32 21 18 1.58 (*N9) (*S2)

2C-XF-NL1F1-SEC (Rm. 2C-1135) 2C-NH1F-1 0.208 2.41 0.97 VCB 12 14 10 PNL 25 39 18 4.07 (*N9) (*S1)

2C-XF-NL2F1-SEC (Rm. 2C-2124) 2C-NH2F-2 0.208 2.41 0.97 VCB 12 14 10 PNL 25 39 18 4.08 (*N9) (*S1)

2C-XF-NL3F-SEC (Rm. 2C-3124) 2C-NH3F-1 0.208 2.39 0.96 VCB 12 14 10 PNL 25 38 18 4.04 (*N9) (*S1)

2C-XF-NLBF-NFDS (Rm. 2C-0001) 2C-MDP-10 0.480 4.17 3.06 VCB 12 14 10 PNL 25 9 18 0.35 (*S1)

2C-XF-NLBF-SEC (Rm. 2C-0001) 2C-MDP-10 0.208 1.31 0.35 HOA 0 0 10 AIR 32 24 18 2.14 (*N9) (*S2)

2C-XF-NLPA-SEC (B.2C Attic) 2C-NHPA-1 0.208 3.32 1.37 VCB 12 14 10 PNL 25 48 18 5.84 (*N9) (*S1)

2C-XF-QL1F-SEC (Rm. 2C-1163) 2C-EQDP2C-2 0.208 0.76 0.2 HOA 20 14 10 AIR 32 18 18 1.20 (*N9) (*S0)

2C-XF-QLBB-SEC (Rm. 2C-B00) 2C-EQDP2C-1 0.208 0.73 0.19 HOA 20 14 10 AIR 32 18 18 1.16 (*N9) (*S0)

2C-XF-QLPA-SEC (B.2C Attic) 2C-QHPA-1 0.208 1.12 0.3 HOA 20 30 14 AIR 32 21 18 1.60 (*N9) (*S0)

2E-CH1A (Rm. 2E-1166) 2E-CR2EDP-3 0.480 5.46 4.06 VCB 12 14 10 PNL 25 10 18 0.44 (*S3)

2E-CH1B (2E-1187) 2E-CR2EDP-7 0.480 4.03 2.95 VCB 12 14 10 PNL 25 8 18 0.31 (*S3)

2E-CH1C (Rm. 2E-1204) 2E-CR2EDP-8 0.480 3.28 2.38 VCB 12 14 10 PNL 25 7 18 0.25 (*S3)

2E-CH2A (Rm. 2E-2137) 2E-CR2EDP-4 0.480 4.77 3.52 VCB 12 14 10 PNL 25 9 18 0.38 (*S3)

2E-CH2B (Rm. 2E-2123) 2E-CR2EDP-1 0.480 1.67 1.02 VCB 12 14 10 PNL 25 14 18 0.83 (*N3) (*S3)

2E-CH2C (Rm. 2E-2175) 2E-CR2EDP-2 0.480 3.3 2.39 VCB 12 14 10 PNL 25 7 18 0.25 (*S3)

2E-CH3A (Rm. 2E-3130) 2E-CH2A-2 0.480 4.63 2.99 VCB 12 14 10 PNL 25 6 18 0.22 (*N3) (*S3)

2E-CH3B (Rm. 3106) 2E-CR2EDP-10 0.480 4.64 3 VCB 12 14 10 PNL 25 13 18 0.67 (*N3) (*S3)

2E-CH3C (Rm. 2E-3157) 2E-CH2C-2 0.480 3.51 2.55 VCB 12 14 10 PNL 25 2 18 0.05 (*S1)

2E-CH4A (Rm. 2E-4129) 2E-CR2EDP-5 0.480 5.5 3.58 VCB 12 14 10 PNL 25 11 18 0.58 (*N3) (*S3)

2E-CH4C (Rm. 2E-4150) 2E-CR2EDP-9 0.480 2.82 2.03 VCB 12 14 10 PNL 25 10 18 0.50 (*S3)

2E-CH5A (Rm. 2E-5118) 2E-CH4A-1 0.480 5.36 3.98 VCB 12 14 10 PNL 25 9 18 0.43 (*S3)

2E-CH5C (2E-5150) 2E-CH4C-1 0.480 2.77 1.99 VCB 12 14 10 PNL 25 6 18 0.21 (*S3)

2E-CHBA (Rm. 2E-B139) 2E-CH1A-2 0.480 4.19 3.07 VCB 12 14 10 PNL 25 6 18 0.06 (*N21a) (*N21b)

(*S1)

2E-CHBB (Rm. B-162) 2E-CH1B-2 0.480 3.24 2.34 VCB 12 14 10 PNL 25 7 18 0.24 (*S3)

2E-CHBC (Rm. 2E.B162) 2E-CH1C-2 0.480 3.18 2.3 VCB 12 14 10 PNL 25 7 18 0.24 (*S3)

2E-CL1A (Rm. 2E-1166) 2E-CL1A-MB 0.208 0.99 0.37 VCB 12 14 10 PNL 25 21 18 1.51 (*N9) (*S1)

2E-CL1A1 (Rm. 1050) 2E-CL1A-1 0.208 0.95 0.36 VCB 12 14 10 PNL 25 20 18 1.44 (*N9) (*S1)

2E-CL1B (Rm. 2E-1187) 2C-CL1B-MB 0.208 1.29 0.49 VCB 12 14 10 PNL 25 25 18 2.03 (*N9) (*S1)

6.5-7

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

2E-CL1C (Rm. 2E-1204) 2E-CL1C-MB 0.208 1.27 0.48 VCB 12 14 10 PNL 25 25 18 1.98 (*N9) (*S1)

2E-CL2A (Rm. 2E-2123) 2E-CL2A-MB 0.208 1.32 0.51 VCB 12 14 10 PNL 25 25 18 2.08 (*N9) (*S1)

2E-CL2B (Rm. 2E-2123) 2E-CL2B-MB 0.208 1.14 0.43 VCB 12 14 10 PNL 25 23 18 1.75 (*N9) (*S1)

2E-CL2C (Rm. 2E-2175) 2E-CL2C-MB 0.208 1.26 0.48 VCB 12 14 10 PNL 25 25 18 1.96 (*N9) (*S1)

2E-CL3B (Rm. 2E-3106) 2E-CL3B-MB 0.208 3.2 1.32 VCB 12 14 10 PNL 25 48 18 5.67 (*N9) (*S1)

2E-CLBA (Rm. 2E-B139) 2E-CLBA-MB 0.208 1.26 0.48 VCB 12 14 10 PNL 25 24 18 1.96 (*N9) (*S1)

2E-CLBB (Rm. B-162) 2E-CLBB-MB 0.208 1.28 0.49 VCB 12 14 10 PNL 25 25 18 2.00 (*N9) (*S1)

2E-CLBC (Rm. 2E-B162) 2E-CLBC-MB 0.208 1.27 0.48 VCB 12 14 10 PNL 25 25 18 1.98 (*N9) (*S1)

2E-CR2EATS-LD (Rm. 2E-1161B) 2E-MDP-W-14 0.480 17.33 13.34 VCB 12 14 10 PNL 25 33 18 3.09 (*S1)

2E-CR2EDP (Rm. 2E-1161B) 2E-MDP-W-14 0.480 16.62 12.81 VCB 12 14 10 PNL 25 32 18 2.95 (*S1)

2E-EDP2E (Rm. 2E-1161B) 2E-GEN-11-MB 0.480 11.82 9.08 VCB 12 14 10 PNL 25 77 18 12.15 (*N9) (*S2)

2E-EH1A (Rm. 2E-1161) 2E-LS2EDP-1 0.480 3.86 2.82 VCB 12 14 10 PNL 25 3 18 0.05 (*S1)

2E-EH1C (Rm. 2E-1204) 2E-LS2EDP-4 0.480 2.3 1.64 VCB 12 14 10 PNL 25 2 18 0.03 (*S1)

2E-EH2A (Rm. 2E-2137) 2E-LS2EDP-3 0.480 3.86 2.82 VCB 12 14 10 PNL 25 3 18 0.05 (*S1)

2E-EH2C (Rm. 2E-2175) 2E-LS2EDP-6 0.480 2.21 1.57 VCB 12 14 10 PNL 25 2 18 0.03 (*S1)

2E-EH3A (Rm. 2E-3130) 2E-EH2A-1 0.480 3.6 2.29 VCB 12 14 10 PNL 25 7 18 0.24 (*N3) (*S3)

2E-EH3C (Rm. 2E-3157) 2E-EH2C-1 0.480 2.12 1.5 VCB 12 14 10 PNL 25 5 18 0.15 (*S3)

2E-EH4A (Rm. 2E-4129) 2E-LS2EDP-5 0.480 3.09 2.23 VCB 12 14 10 PNL 25 2 18 0.04 (*S1)

2E-EH4C (Rm. 2E-4150) 2E-LS2EDP-2 0.480 2.75 1.98 VCB 12 14 10 PNL 25 2 18 0.04 (*S1)

2E-EH5A (Rm. 2E-5118) 2E-EH4A-1 0.480 2.92 2.1 VCB 12 14 10 PNL 25 6 18 0.22 (*S3)

2E-EH5C (Rm. 2E-5150) 2E-EH4C-1 0.480 2.62 1.88 VCB 12 14 10 PNL 25 6 18 0.19 (*S3)

2E-EHBA (Rm. 2E-B139) 2E-EH1A-1 0.480 2.85 2.05 VCB 12 14 10 PNL 25 6 18 0.21 (*S3)

2E-EHBC (Rm. 2E-B162) 2E-EH1C-1 0.480 2.21 1.57 VCB 12 14 10 PNL 25 5 18 0.16 (*S3)

2E-EL1N (Rm. 2E-1161) 2E-EL1N-MB 0.208 0.79 0.29 VCB 12 14 10 PNL 25 18 18 1.16 (*N9) (*S1)

2E-ELEV-P1-ECB (Rm. 2E-6102) 2E-ELEV-P1-ECB-CB 0.480 7.04 5.3 VCB 12 14 10 PNL 25 11 18 0.58 (*S3)

2E-ELEV-P2-ECB (Rm. 2E-6102) (2E-ELEV-P2-

ECB-CB LineSide)

2E-EQ2EDP-5 0.480 6.34 4.16 VCB 12 14 10 PNL 25 57 18 7.47 (*N3) (*N9) (*S2)

2E-ELEV-P3-ECB (Rm. 2E-6102) (2E-ELEV-P3-

ECB-CB LineSide)

2E-EQ2EDP-5 0.480 6.34 4.16 VCB 12 14 10 PNL 25 57 18 7.47 (*N3) (*N9) (*S2)

2E-ELEV-S1-ECB (Rm. 2E-6102) (2E-ELEV-S1-

ECB-CB LineSide)

2E-EQ2EDP-5 0.480 6.34 4.16 VCB 12 14 10 PNL 25 57 18 7.47 (*N3) (*N9) (*S2)

2E-ELEV-S2-ECB (Rm. 2E-6102) 2E-ELEV-S2-ECB-CB 0.480 7.04 5.3 VCB 12 14 10 PNL 25 11 18 0.58 (*S3)

2E-ELPP (2E-Elev. Penthouse) 2E-ELPP-MB 0.208 0.67 0.24 VCB 12 14 10 PNL 25 16 18 0.96 (*N9) (*S1)

2E-EQ2EATS-LD (2E-1161B) 2E-EDP2E-3 0.480 11.76 9.03 VCB 12 14 10 PNL 25 76 18 12.08 (*N9) (*N21a) (*S2)

6.5-8

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

2E-EQ2EDP (Rm. 2E-1161B) 2E-EDP2E-3 0.480 11.73 9.01 VCB 12 14 10 PNL 25 76 18 12.04 (*N9) (*N21a)

(*N21b) (*S2)

2E-GEN-11-ECB (Rm. 2E-1161B) 2E-GEN-11-MB 0.480 11.83 9.09 VCB 12 14 10 PNL 25 77 18 12.17 (*N9) (*S2)

2E-LS2EATS-LD (Rm. 2E-1161B) 2E-MDP-W-12 0.480 13.05 10.05 VCB 12 14 10 PNL 25 10 18 0.46 (*S3)

2E-LS2EDP (Rm. 2E-1161B) 2E-MDP-W-12 0.480 10.09 6.77 VCB 12 14 10 PNL 25 10 18 0.44 (*N3) (*S3)

2E-MDP-E (Rm. 2E-1161) (2E-MDP-E-MB

LineSide)

MV-SW-2E-E-FU 0.480 24.34 16.12 VCB 12 14 10 PNL 25 48 18 5.67 (*N3) (*S3)

2E-MDP-W (Rm. 2E-1161) 2E-MDP-W-MB 0.480 19.33 14.83 VCB 12 14 10 PNL 25 69 18 10.34 (*S3)

2E-NH1A (Rm. 2E-1166) 2E-MDP-W-5 0.480 11.7 8.99 VCB 12 14 10 PNL 25 7 18 0.28 (*S1)

2E-NH1B (Rm. 2E-1187) 2E-MDP-W-9 0.480 9.2 7.01 VCB 12 14 10 PNL 25 6 18 0.23 (*S1)

2E-NH1C (Rm. 2E-1204) 2E-MDP-W-7 0.480 16.1 12.41 VCB 12 14 10 PNL 25 8 18 0.35 (*S1)

2E-NH1N (Rm. 2E-1161) 2E-MDP-E-3 0.480 16.45 12.67 VCB 12 14 10 PNL 25 8 18 0.35 (*S1)

2E-NH2A (Rm. 2E-2137) 2E-MDP-W-1 0.480 12.08 9.29 VCB 12 14 10 PNL 25 7 18 0.28 (*S1)

2E-NH2B (Rm. 2E-2123) 2E-MDP-W-2 0.480 9.32 7.1 VCB 12 14 10 PNL 25 7 18 0.24 (*S1)

2E-NH2C (Rm. 2E-2175) 2E-MDP-W-4 0.480 7.71 5.83 VCB 12 14 10 PNL 25 6 18 0.22 (*S1)

2E-NH2S (Rm. 2E-277) 2E-MDP-W-10 0.480 8.18 6.2 VCB 12 14 10 PNL 25 6 18 0.22 (*S1)

2E-NH3A (Rm. 2E-3130) 2E-NH2A-2 0.480 11.54 7.77 VCB 12 14 10 PNL 25 13 18 0.68 (*N3) (*S3)

2E-NH3B (Rm. 2E-3106) 2E-MDP-W-3 0.480 8.86 6.74 VCB 12 14 10 PNL 25 6 18 0.23 (*S1)

2E-NH3C (Rm. 2E-3157) 2E-NH2C-2 0.480 7.36 5.55 VCB 12 14 10 PNL 25 4 18 0.10 (*S1)

2E-NH4A (Rm. 2E-4129) 2E-MDP-W-6 0.480 11.8 9.07 VCB 12 14 10 PNL 25 7 18 0.28 (*S1)

2E-NH4C (Rm. 2E-4150) 2E-MDP-W-8 0.480 7.24 4.78 VCB 12 14 10 PNL 25 6 18 0.23 (*N3) (*S2)

2E-NH5A (Rm. 2E-5118) 2E-NH4A-1 0.480 11.15 8.55 VCB 12 14 10 PNL 25 7 18 0.26 (*S1)

2E-NH5C (Rm. 2E-5150) 2E-NH4C-3 0.480 6.99 5.26 VCB 12 14 10 PNL 25 4 18 0.10 (*S1)

2E-NHBA (Rm. 2E-B139) 2E-NH1A-2 0.480 10.03 7.66 VCB 12 14 10 PNL 25 7 18 0.24 (*S1)

2E-NHBB (Rm. B-162) 2E-MDP-W-11 0.480 10.04 7.67 VCB 12 14 10 PNL 25 10 18 0.46 (*S3)

2E-NHBC (Rm. 2E-B126) 2E-NH1C-2 0.480 7.31 5.51 VCB 12 14 10 PNL 25 5 18 0.18 (*N21a) (*S1)

2E-NHPP (Penthouse) 2E-NMCC2-1 0.480 6.15 4.6 VCB 12 14 10 PNL 25 5 18 0.15 (*S1)

2E-NL1A (Rm. 2E-1166) 2E-NL1A-MB 0.208 1.02 0.38 VCB 12 14 10 PNL 25 21 18 1.55 (*N9) (*S1)

2E-NL1B (Rm. 2E-1187) 2E-NL1B-MB 0.208 1.01 0.38 VCB 12 14 10 PNL 25 21 18 1.53 (*N9) (*S1)

2E-NL1C (Rm. 2E-1204) 2E-NL1C-MB 0.208 1.03 0.39 VCB 12 14 10 PNL 25 21 18 1.57 (*N9) (*S1)

2E-NL1N (Rm. 2E-1161) 2E-NL1N-MB 0.208 1.4 0.54 VCB 12 14 10 PNL 25 26 18 2.19 (*N9) (*S1)

2E-NL2A (Rm. 2E-2137) 2E-NL2A-MB 0.208 1.02 0.38 VCB 12 14 10 PNL 25 21 18 1.55 (*N9) (*S1)

2E-NL2B (Rm. 2E-2123) 2E-NL2B-MB 0.208 1.01 0.38 VCB 12 14 10 PNL 25 21 18 1.53 (*N9) (*S1)

2E-NL2C (Rm. 2E-2175) 2E-NL2C-MB 0.208 3.3 1.37 VCB 12 14 10 PNL 25 49 18 5.88 (*N9) (*S1)

2E-NL2S (Rm. 2E-277) 2E-NL2S-MB 0.208 1.34 0.51 VCB 12 14 10 PNL 25 26 18 2.11 (*N9) (*S3)

2E-NL3A1 (Rm. 2E-3130) 2E-NL3A1-MB 0.208 3.48 1.45 VCB 12 14 10 PNL 25 51 18 6.25 (*N9) (*S1)

6.5-9

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

2E-NL3A2 (Rm. 2E-3130) 2E-NL3A2-MB 0.208 3.5 1.46 VCB 12 14 10 PNL 25 51 18 6.29 (*N9) (*S1)

2E-NL3A3 (Rm. 2E-3130) 2E-NL3A3-MB 0.208 1.02 0.38 VCB 12 14 10 PNL 25 21 18 1.55 (*N9) (*S1)

2E-NL3B (Rm. 2E-3106) 2E-NL3B-MB 0.208 2.42 0.97 VCB 12 14 10 PNL 25 39 18 4.12 (*N9) (*S1)

2E-NL3C1 (Rm. 2E-3157) 2E-NL3C1-MB 0.208 1 0.37 VCB 12 14 10 PNL 25 21 18 1.51 (*N9) (*S1)

2E-NL3C2 (Rm. 2E-3157) 2E-NL3C2-MB 0.208 1.32 0.51 VCB 12 14 10 PNL 25 25 18 2.08 (*N9) (*S3)

2E-NL4A1 (Rm. 2E-4129) 2E-NL4A1-MB 0.208 3.48 1.45 VCB 12 14 10 PNL 25 50 18 6.24 (*N9) (*S1)

2E-NL4A2 (Rm. 2E-4129) 2E-NL4A2-MB 0.208 3.5 1.46 VCB 12 14 10 PNL 25 51 18 6.28 (*N9) (*S1)

2E-NL4A3 (Rm. 2E-4129) 2E-NL4A3-MB 0.208 1.02 0.38 VCB 12 14 10 PNL 25 21 18 1.55 (*N9) (*S1)

2E-NL4C1 (2E-4150) 2E-NL4C1-MB 0.208 2.36 0.95 VCB 12 14 10 PNL 25 38 18 4.02 (*N9) (*S1)

2E-NL4C2 (Rm. 2E-4150) 2E-NL4C2-MB 0.208 1 0.37 VCB 12 14 10 PNL 25 21 18 1.51 (*N9) (*S1)

2E-NL5A1 (Rm. 2E-5118) 2E-NL5A1-MB 0.208 3.45 1.43 VCB 12 14 10 PNL 25 50 18 6.18 (*N9) (*S1)

2E-NL5A2 (Rm. 2E-5118) 2E-NL5A2-MB 0.208 3.47 1.44 VCB 12 14 10 PNL 25 50 18 6.22 (*N9) (*S1)

2E-NL5A3 (Rm. 2E-5118) 2E-NL5A3-MB 0.208 1.02 0.38 VCB 12 14 10 PNL 25 21 18 1.54 (*N9) (*S1)

2E-NL5C1 (2E-5150) 2E-NL5C1-MB 0.208 1.33 0.51 VCB 12 14 10 PNL 25 25 18 2.09 (*N9) (*S3)

2E-NL5C2 (Rm. 2E-5150) 2E-NL5C2-MB 0.208 1.32 0.51 VCB 12 14 10 PNL 25 25 18 2.07 (*N9) (*S3)

2E-NLBA1 (Rm. 2E-B139) 2E-NLBA1-MB 0.208 2.4 0.97 VCB 12 14 10 PNL 25 39 18 4.08 (*N9) (*S1)

2E-NLBA2 (Rm. 2E-B139) 2E-NLBA2-MB 0.208 2.37 0.95 VCB 12 14 10 PNL 25 38 18 4.03 (*N9) (*S1)

2E-NLBA3 (Rm. 2E-B139) 2E-NLBA1-1 0.208 2.34 0.94 VCB 12 14 10 PNL 25 1 18 0.02 (*S1)

2E-NLBA4 (2E-1160) 2E-NLBA4-MB 0.208 4.78 2.05 VCB 12 14 10 PNL 25 63 18 8.97 (*N9) (*S1)

2E-NLBB1 (Rm. B-162) 2E-NLBB1-MB 0.208 5.73 2.5 VCB 12 14 10 PNL 25 72 18 11.05 (*N9) (*S1)

2E-NLBB-2-L (Rm. 2E-B111) 2E-NLBB1-1 0.208 4.68 2 VCB 12 14 10 PNL 25 62 18 8.76 (*N9) (*S1)

2E-NLBB-2-R (Rm. 2E-B111) 2E-NLBB1-1 0.208 4.8 2.06 VCB 12 14 10 PNL 25 64 18 9.02 (*N9) (*S1)

2E-NLBC (Rm. 2E-B126) 2E-NLBC-MB 0.208 1 0.38 VCB 12 14 10 PNL 25 21 18 1.52 (*N9) (*S1)

2E-NLPP (Penthouse) 2E-NLPP-MB 0.208 1.26 0.48 VCB 12 14 10 PNL 25 24 18 1.96 (*N9) (*S1)

2E-NMCC1 (Rm. 2E-1160) 2E-MDP-E-2 0.480 18.17 13.98 VCB 12 14 10 MCC 25 9 18 0.38 (*S1)

2E-NMCC2 (Penthouse) 2E-MDP-E-4 0.480 7.13 4.71 VCB 12 14 10 MCC 25 7 18 0.26 (*N3) (*S2)

2E-POWERWARE-UPS-PRI (Rm. 2E-5118) 2E-CH5A-1 0.480 7.6 5.74 VCB 12 14 10 PNL 25 4 18 0.11 (*S1)

2E-POWERWARE-UPS-SEC (Rm. 2E-5118) 2E-CH5A-1 0.208 15.41 4.19 HOA 20 36 6 AIR 32 6 18 0.14 (*S1)

2E-QH1A (2E-1166) 2E-EQ2EDP-3 0.480 6.94 5.22 VCB 12 14 10 PNL 25 5 18 0.17 (*N21a) (*S1)

2E-QH1C (Rm. 2E-1204) 2E-EQ2EDP-2 0.480 4.03 2.95 VCB 12 14 10 PNL 25 7 18 0.11 (*N21a) (*S1)

2E-QH1N (Rm. 2E-1161B) 2E-EQ2EDP-1 0.480 16.65 12.83 VCB 12 14 10 PNL 25 12 18 0.60 (*N21b) (*S3)

2E-QH3N (Rm. 3100B-2E-N) 2E-QMCC2-2 0.480 5.71 4.26 VCB 12 14 10 PNL 25 5 18 0.14 (*S1)

2E-QH4A (Rm. 2E-4129) 2E-EQ2EDP-8 0.480 6.02 4.5 VCB 12 14 10 PNL 25 5 18 0.15 (*N21a) (*S1)

2E-QH4C (Rm. 2E-4150) 2E-EQ2EDP-7 0.480 3.57 2.6 VCB 12 14 10 PNL 25 4 18 0.10 (*N21a) (*S1)

2E-QHPP (Penthouse) 2E-QMCC2-1 0.480 7.3 4.82 VCB 12 14 10 PNL 25 10 18 0.49 (*N3) (*S3)

2E-QHSW (B. 168) 2E-EQ2EDP-6 0.480 5.65 4.2 VCB 12 14 10 PNL 25 5 18 0.15 (*S1)

6.5-10

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

2E-QL1N (Rm. 2E-1161B) 2E-QL1N-MB 0.208 1.4 0.54 VCB 12 14 10 PNL 25 26 18 2.19 (*N9) (*S1)

2E-QL3N (Rm. 3100B-2E-N) (2E-QL3N-MB

LineSide)

2E-QH3N-1 0.208 1.37 0.53 VCB 12 14 10 PNL 25 26 18 2.14 (*N9) (*S1)

2E-QLBC (Rm. 2E-B162) 2E-QLBC-MB 0.208 0.97 0.36 VCB 12 14 10 PNL 25 20 18 1.46 (*N9) (*S1)

2E-QLPP (Penhouse) 2E-QLPP-MB 0.208 0.99 0.37 VCB 12 14 10 PNL 25 21 18 1.49 (*N9) (*S1)

2E-QLPP1 (Rm. 2E-6102) 2E-QLPP1-MB 0.208 0.74 0.27 VCB 12 14 10 PNL 25 17 18 1.07 (*N9) (*S1)

2E-QLSW (B. 168) 2E-QLSW-MB 0.208 1.31 0.5 VCB 12 14 10 PNL 25 25 18 2.04 (*N9) (*S1)

2E-QMCC1 (Rm. 2E-1160) 2E-EQ2EDP-4 0.480 14.08 10.85 VCB 12 14 10 MCC 25 8 18 0.30 (*S1)

2E-QMCC2 (Penthouse) 2E-EQ2EDP-10 0.480 9.3 7.09 VCB 12 14 10 MCC 25 17 18 1.11 (*S3)

2E-XF-CL1A-SEC (Rm. 2E-1166) 2E-CH1A-1 0.208 1.01 0.38 VCB 12 14 10 PNL 25 21 18 1.53 (*N9) (*N21a) (*S1)

2E-XF-CL1B-SEC (2E-1187) 2E-CH1B-1 0.208 1.33 0.35 HOA 20 14 10 AIR 32 26 18 2.18 (*N9) (*S0)

2E-XF-CL1C-SEC (Rm. 2E-1204) 2E-CH1C-1 0.208 1.29 0.34 HOA 20 14 10 AIR 32 25 18 2.11 (*N9) (*S0)

2E-XF-CL1D-SEC (2E-1122) 2C-CH1D-1 0.208 1.29 0.34 HOA 20 14 10 AIR 32 25 18 2.10 (*N9) (*S0)

2E-XF-CL2A-SEC (Rm. 2E-2137) 2E-CH2A-1 0.208 1.36 0.36 HOA 20 14 10 AIR 32 26 18 2.23 (*N9) (*S0)

2E-XF-CL2B-SEC (Rm. 2E-2123) 2E-CH2B-1 0.208 1.18 0.31 HOA 20 14 10 AIR 32 23 18 1.91 (*N9) (*S0)

2E-XF-CL2C-SEC (Rm. 2E-2175) 2E-CH2C-1 0.208 1.3 0.34 HOA 20 14 10 AIR 32 25 18 2.12 (*N9) (*S0)

2E-XF-CL3B-SEC (Rm. 2E-3106) 2E-CH3B-1 0.208 3.23 1.34 VCB 12 14 10 PNL 25 48 18 5.74 (*N9) (*S1)

2E-XF-CLBA-SEC (Rm. 2E-B139) 2E-CHBA-1 0.208 1.32 0.5 VCB 12 14 10 PNL 25 25 18 2.07 (*N9) (*N21a) (*S1)

2E-XF-CLBB-SEC (Rm. B-162) 2E-CHBB-1 0.208 1.3 0.35 HOA 20 14 10 AIR 32 25 18 2.13 (*N9) (*S0)

2E-XF-CLBC-SEC (Rm. 2E-B162) 2E-CHBC-1 0.208 1.29 0.34 HOA 10 14 20 AIR 32 25 18 2.11 (*N9) (*S0)

2E-XF-ELPP-SEC (2E-Elev. Penthouse) 2E-EH5C-1 0.208 0.68 0.18 HOA 14 20 10 AIR 32 17 18 1.08 (*N9) (*S0)

2E-XF-NL1A-SEC (Rm. 2E-1166) 2E-NH1A-1 0.208 1.02 0.27 HOA 20 30 14 AIR 32 21 18 1.65 (*N9) (*S0)

2E-XF-NL1B-SEC (Rm. 2E-1187) 2E-NH1B-1 0.208 1.02 0.27 HOA 20 30 14 AIR 32 21 18 1.64 (*N9) (*S0)

2E-XF-NL1C-SEC (Rm. 2E-1204) 2E-NH1C-1 0.208 1.04 0.27 HOA 20 30 14 AIR 32 21 18 1.67 (*N9) (*N21a) (*S0)

2E-XF-NL1N-SEC (Rm. 2E-1161) 2E-NH1N-1 0.208 1.42 0.38 HOA 14 10 20 AIR 32 27 18 2.32 (*N9) (*N21a) (*S0)

2E-XF-NL2A-SEC (Rm. 2E-2137) 2E-NH2A-1 0.208 1.03 0.27 HOA 20 30 14 AIR 32 21 18 1.66 (*N9) (*S0)

2E-XF-NL2B-SEC (Rm. 2E-2123) 2E-NH2B-1 0.208 1.02 0.27 HOA 20 30 14 AIR 32 21 18 1.64 (*N9) (*S0)

2E-XF-NL2C-SEC (Rm. 2E-2175) 2E-NH2C-1 0.208 3.34 1.38 VCB 12 14 10 PNL 25 49 18 5.95 (*N9) (*S1)

2E-XF-NL2S-SEC (Rm. 2E-277) 2E-NH2S-1 0.208 1.38 0.37 HOA 20 14 10 AIR 32 26 18 2.26 (*N9) (*S2)

2E-XF-NL3A2-SEC (Rm. 2E-3130) 2E-NH3A-1 0.208 3.54 1.48 VCB 12 14 10 PNL 25 51 18 6.37 (*N9) (*S1)

2E-XF-NL3A3-SEC (Rm. 2E-3130) 2E-NH3A-2 0.208 1.02 0.27 HOA 20 42 6 AIR 32 21 18 1.65 (*N9) (*S0)

2E-XF-NL3B-SEC (Rm. 2E-3106) 2E-NH3B-1 0.208 2.44 0.99 VCB 12 14 10 PNL 25 39 18 4.17 (*N9) (*S1)

2E-XF-NL3C1-SEC (Rm. 2E-3157) 2E-NH3C-1 0.208 1 0.27 HOA 20 30 14 AIR 32 21 18 1.62 (*N9) (*S0)

6.5-11

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

2E-XF-NL3C2-SEC (Rm. 2E-3157) 2E-NH3C-2 0.208 1.36 0.36 HOA 20 14 10 AIR 32 26 18 2.23 (*N9) (*S2)

2E-XF-NL4A2-SEC (Rm. 2E-4129) 2E-NH4A-2 0.208 3.54 0.95 HOA 26 36 19 AIR 32 41 18 6.09 (*N9) (*N20a) (*S0)

2E-XF-NL4A3-SEC (Rm. 2E-4129) 2E-NH4A-3 0.208 1.02 0.27 HOA 0 0 0.0000 AIR 32 21 18 1.65 (*N9) (*S0)

2E-XF-NL4C1-SEC (Rm. 2E-4150) 2E-NH4C-1 0.208 2.39 0.96 VCB 12 14 10 PNL 25 39 18 4.07 (*N9) (*S1)

2E-XF-NL4C2-SEC (Rm. 2E-4150) 2E-NH4C-2 0.208 1 0.27 HOA 20 30 14 AIR 32 21 18 1.62 (*N9) (*S0)

2E-XF-NL5A2-SEC (Rm. 2E-5118) 2E-NH5A-1 0.208 3.51 1.46 VCB 12 14 10 PNL 25 51 18 6.31 (*N9) (*S1)

2E-XF-NL5A3-SEC (Rm. 2E-5118) 2E-NH5A-2 0.208 1.02 0.27 HOA 20 30 14 AIR 32 21 18 1.65 (*N9) (*S0)

2E-XF-NL5C1-SEC (Rm. 2E-5150) 2E-NH5C-1 0.208 1.34 0.36 HOA 20 30 14 AIR 32 26 18 2.19 (*N9) (*S2)

2E-XF-NL5C2-SEC (Rm. 2E-5150) 2E-NH5C-2 0.208 1.33 0.35 HOA 20 30 14 AIR 32 26 18 2.18 (*N9) (*S2)

2E-XF-NLBA1/2-SEC (Rm. 2E-B139) 2E-NHBA-1 0.208 2.47 1 VCB 12 14 10 PNL 25 40 18 4.22 (*N9) (*S1)

2E-XF-NLBA4-SEC (Rm. 2E-116O) 2E-NH1A-3 0.208 5.1 2.2 VCB 12 14 10 PNL 25 66 18 9.68 (*N9) (*S1)

2E-XF-NLBB1-SEC (Rm. B-162) 2E-NHBB-1 0.208 5.78 2.52 VCB 12 14 10 PNL 25 73 18 11.17 (*N9) (*S1)

2E-XF-NLBC-SEC (Rm. 2E-B162) 2E-NHBC-1 0.208 1.01 0.27 HOA 20 30 14 AIR 32 21 18 1.63 (*N9) (*S0)

2E-XF-NLPP-SEC (Penthouse) 2E-NHPP-1 0.208 1.34 0.36 HOA 20 14 10 AIR 32 25 18 2.17 (*N9) (*S0)

2E-XF-QL1N-SEC (Rm. 2E-1161B) 2E-QH1N-1 0.208 1.42 0.38 HOA 20 24 6 AIR 32 27 18 2.32 (*N9) (*N21a) (*S0)

2E-XF-QL3N-SEC (Rm. 3100B-2E-N) 2E-QH3N-1 0.208 1.46 0.39 HOA 25 32 20 AIR 32 27 18 2.37 (*N9) (*S0)

2E-XF-QLBC-SEC (Rm. B-162) 2E-QH1C-1 0.208 0.98 0.26 HOA 20 30 14 AIR 32 21 18 1.57 (*N9) (*S0)

2E-XF-QLPP-SEC (Penthouse) 2E-QHPP-1 0.208 1 0.26 HOA 20 30 14 AIR 32 21 18 1.59 (*N9) (*S0)

2E-XF-QLSW-SEC (B. 168) 2E-QHSW-1 0.208 1.35 0.36 HOA 10 14 19 AIR 32 26 18 2.19 (*N9) (*S0)

2E-XR-ELIN-SEC (Rm. 2E-1161) 2E-LS2EDP-7 0.208 0.8 0.21 HOA 16 12 10 AIR 32 19 18 1.27 (*N9) (*S0)

2W-ATS QMCC-LD (Rm. 2W-B00B) 2W-EDP2W-2 0.480 4.31 3.16 VCB 12 14 10 PNL 25 38 18 4.00 (*N9) (*S2)

2W-EDP2W (Rm. 2W-B00B) 2W-GEN-MB 0.480 4.32 3.17 VCB 12 14 10 PNL 25 38 18 4.01 (*N9) (*S2)

2W-EHBM (Rm. 2W-B00A) (2W-EHBM-MB

LineSide)

2W-MDP-2 0.480 4.71 3.47 VCB 12 14 10 PNL 25 13 18 0.74 (*S1)

2W-ELBM (2W-B00A) 2W-ELBM-MB 0.208 0.77 0.28 VCB 12 14 10 PNL 25 17 18 1.12 (*N9) (*S1)

2W-EQATS-LD (Rm. 2W-B00A) 2W-MDP-6 0.480 14.24 10.98 VCB 12 14 10 PNL 25 8 18 0.32 (*S1)

2W-GEN-MB-ECB (Rm. 2W-B00B) 2W-GEN-MB 0.480 4.32 3.18 VCB 12 14 10 PNL 25 38 18 4.02 (*N9) (*S2)

2W-LSATS-LD (Rm. 2W-B00A) 2W-MDP-2 0.480 9.27 7.06 VCB 12 14 10 PNL 25 7 18 0.24 (*S1)

2W-MDP (Rm. 2W-B00) 2W-MDP-MB 0.480 35.72 25.26 VCB 12 14 10 PNL 25 270 18 90.97 (*N9) (*S1)

2W-NH1M (Rm. 2W-129) 2W-MDP-4 0.480 21.03 16.07 VCB 12 14 10 PNL 25 9 18 0.42 (*S1)

2W-NHBM (2C-ATTIC) 2W-MDP-3 0.480 15.83 12.2 VCB 12 14 10 PNL 25 8 18 0.34 (*N21b) (*S1)

2W-NL1M (Rm. 2W-129) 2W-NL1M-MB 0.208 2.56 1.04 VCB 12 14 10 PNL 25 40 18 4.34 (*N9) (*S1)

2W-NLBM (B.2C Attic) 2W-NLBM-MB 0.208 1.35 0.52 VCB 12 14 10 PNL 25 26 18 2.11 (*N9) (*S1)

2W-NMCCW (Rm. 2W-B02) 2W-MDP-1 0.480 27.06 20.19 VCB 12 14 10 MCC 25 20 18 1.42 (*S1)

6.5-12

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

2W-QHBM (2W-B00A) (2W-QHBM-MB LineSide) 2W-MDP-6 0.480 10.08 7.71 VCB 12 14 10 PNL 25 7 18 0.25 (*S1)

2W-QLBM (Rm. 2W-B00A) 2W-QLBM-MB 0.208 1.01 0.38 VCB 12 14 10 PNL 25 21 18 1.53 (*N9) (*S1)

2W-QMCCW (Rm. 2W-B02) 2W-EDP2W-2 0.480 4.02 2.94 VCB 12 14 10 MCC 25 37 18 3.84 (*N9) (*S2)

2W-XF-ELBM-SEC (Rm. 2W-B00A) 2W-EHBM-1 0.208 0.79 0.21 HOA 20 14 10 AIR 32 18 18 1.26 (*N9) (*S0)

2W-XF-FP-SEC (B.2C Attic) MV-SW-2W-FU 0.208 5.99 2.62 VCB 12 14 10 PNL 25 63 18 8.94 (*N9) (*S1)

2W-XF-NL1M-SEC (Rm. 2W-129) 2W-NH1M-1 0.208 2.61 1.06 VCB 12 14 10 PNL 25 41 18 4.44 (*N9) (*S1)

2W-XF-NLBM-SEC (B.2C Attic) 2W-NHBM-1 0.208 1.42 0.38 HOA 20 14 10 AIR 32 27 18 2.31 (*N9) (*S0)

2W-XF-QLBM-SEC (Rm. 2W-B00A) 2W-QHBM-1 0.208 1.03 0.27 HOA 20 30 14 AIR 32 21 18 1.65 (*N9) (*S0)

30-EDP-FDS (Outside B. 30) 30-EDP-FDS-FU 0.480 3.97 2.9 VCB 12 14 10 PNL 25 77 18 12.14 (*N21a) (*S2)

30-ELP(LEP) (B.30) 01-6110-0386-5 0.208 1.69 0.57 VCB 12 14 10 PNL 25 24 18 1.95

(*N3) (*N9) (*N21b)

(*S2)

30-LP (B.30) 30-MDP-A-11 0.208 12.48 5.77 VCB 12 14 10 PNL 25 5 18 0.15 (*N21a) (*S1)

30-MDP-A (Bldg. 30) 30-MDP-A-MB 0.208 25.32 10.7 VCB 20 20 20 SWG 32 183 24 30.84 (*N9) (*S1)

30-MDP-B (Bldg. 30) 30-MDP-B-MB 0.208 22.62 9.74 VCB 20 20 20 SWG 32 185 24 31.30 (*N9) (*S1)

30-MDP-FDS (Outside B. 30) 30-MDP-FDS-FU 0.480 4.07 2.98 VCB 12 14 10 PNL 25 74 18 11.47 (*N21a) (*S2)

30-NL-1 (B.30) 30-MDP-B-5 0.208 17.42 8.07 VCB 12 14 10 PNL 25 19 18 1.27 (*S1)

30-XF-EDP-SEC (Outside B. 30) 30-MDP-B-10 0.480 4.03 1.89 HOA 37 48 32 AIR 32 22 18 1.79 (*N3) (*S3)

30-XF-MDP-SEC (Outside B. 30) 30-MDP-A-12 0.480 4.26 2 HOA 37 48 32 AIR 32 21 18 1.63 (*N3) (*S3)

3-12-6110-0121-ECB (Rm. 3-128D) 30-MDP-B-6 0.208 5.93 2.59 VCB 12 14 10 PNL 25 74 18 11.45 (*N9) (*S1)

3-12-6110-0440-FDS (Rm. 3-128D) (3-12-6110-0440-

FDS-FU LineSide)

30-MDP-B-4 0.208 5.93 2.59 VCB 12 14 10 PNL 25 74 18 11.45 (*N9) (*S1)

32-5930-0176-FDS (Across Rm. 32-102) (32-5930-

0176-FDS-FU LineSide)

03-6110-0383-5 0.208 3.99 1.45 VCB 12 14 10 PNL 25 50 18 6.18 (*N3) (*N9) (*S3)

32-6110-0166 (PP1) (Rm. 32-105A) 32-MAIN-FDS-FU 0.208 7.19 2.76 VCB 12 14 10 PNL 25 71 18 10.66 (*N3) (*S3)

32-6110-0174 (PP1) (Rm. 32-105A) 32-MAIN-FDS-FU 0.208 6.63 2.52 VCB 12 14 10 PNL 25 72 18 11.06 (*N3) (*N9) (*S1)

32-6110-0175 (PP1) (Rm. 32-105A) 32-MAIN-FDS-FU 0.208 6.91 2.64 VCB 12 14 10 PNL 25 74 18 11.57 (*N3) (*N9) (*S1)

32-6110-0347 (LP1) (Rm. 32-105A) 32-MAIN-FDS-FU 0.208 6.93 2.65 VCB 12 14 10 PNL 25 75 18 11.62 (*N3) (*N9) (*S1)

32-MAIN-FDS (Rm. 33-101A) (32-MAIN-FDS-FU

LineSide)

MV-TAP1-FU 0.208 9.1 3.56 VCB 12 14 10 PNL 25 61 18 8.51 (*N3) (*S2)

32-UNK-FDS (Across Rm. 32-102) (32-UNK-FDS-

FU LineSide)

32-5930-0176-FDS-FU 0.208 2.67 0.94 VCB 12 14 10 PNL 25 13 18 0.74 (*N3) (*S2)

6.5-13

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

33-5925-0069-ECB (Rm. 33-103A) 33-5925-0069-ECB-CB 0.208 6.87 2.62 VCB 12 14 10 PNL 25 73 18 11.28 (*N3) (*N9) (*S1)

33-5930-0176-MTS-LD (Rm. 33-103A) 33-5925-0069-ECB-CB 0.208 6.65 2.53 VCB 12 14 10 PNL 25 71 18 10.85 (*N3) (*N9) (*S1)

33-6110-0150 (3) (Rm. 33-101A) 33-5925-0069-ECB-CB 0.208 5.97 2.61 VCB 12 14 10 PNL 25 72 18 11.08 (*N9) (*S1)

33-6110-0167 (2) (Rm. 33-101A) 33-5925-0069-ECB-CB 0.208 6.19 2.72 VCB 12 14 10 PNL 25 74 18 11.54 (*N9) (*S1)

33-6110-0169 (LP2) (Rm. 33-101A) 33-5925-0069-ECB-CB 0.208 6.28 2.76 VCB 12 14 10 PNL 25 75 18 11.75 (*N9) (*N20b) (*S1)

33-6110-0170 (1) (Rm. 33-101A) 33-5925-0069-ECB-CB 0.208 6.43 2.83 VCB 12 14 10 PNL 25 76 18 12.04 (*N9) (*S1)

33-6110-0182 (Rm. 33-103A) 33-6110-0182-MB 0.208 2.73 1.11 VCB 12 14 10 PNL 25 41 18 4.42 (*S0)

34-5925-0068-ECB (Rm. 32-105A) 34-5925-0068-ECB-CB 0.208 7.02 3.12 VCB 12 14 10 PNL 25 84 18 13.95 (*N9) (*S2)

34-6110-0453 (Rm. 32-114) 34-5925-0068-ECB-CB 0.208 5.71 2.49 VCB 12 14 10 PNL 25 71 18 10.79 (*N9) (*S1)

42-6110-0449 (Rm. 42-101) (42-6110-0449-MB

LineSide)

30-MDP-B-2 0.208 8.4 3.79 VCB 12 14 10 PNL 25 11 18 0.57 (*S1)

42-6110-0450 (Rm. 42-101) 42-6110-0450-MB 0.208 0.78 0.29 VCB 12 14 10 PNL 25 17 18 1.15 (*N9) (*S1)

42-6110-0451 (42-A) (42 Hall) 42-6110-0451 (42-A)-

MB

0.208 7.71 2.97 VCB 12 14 10 PNL 25 74 18 11.52 (*N3) (*S2)

46-WJ (Bldg. 46) MV-XF-46-WJ-FU 0.208 1.33 0.51 VCB 12 14 10 PNL 25 26 18 2.10 (*N9) (*S0)

4-MAIN-ECB (Bldg. 4 Bsmt) (4-MAIN-ECB-CB

LineSide)

MV-SW-XF-4-FU 0.208 18.51 8.55 VCB 12 14 10 PNL 25 162 18 40.07 (*N9) (*S1)

50-6110-0426 (B.50) 50-6110-0426-MB 0.208 1.15 0.43 VCB 12 14 10 PNL 25 23 18 1.77 (*N9) (*S1)

64-6110-0455 (B. 64) 64-6110-0445-MB 0.208 1.37 0.53 VCB 20 32 6 PNL 25 24 18 1.93 (*N2) (*N8) (*N9)

(*S2)

65-ATS SB-LD (Rm. 65-109) 65-LPN4CHP11-1 0.480 11.13 8.53 VCB 12 14 10 PNL 25 8 18 0.34 (*N21a) (*S1)

65-ATS-LS-LD (Rm. 65-109) 65-LPN4CHP11-2 0.480 10.87 8.33 VCB 12 14 10 PNL 25 8 18 0.33 (*N21a) (*S1)

65-DPE4CHP11 (Rm-114) 2W-EDP2W-5 0.480 4.15 3.04 VCB 12 14 10 PNL 25 38 18 3.94 (*N9) (*S2)

65-DPS4CHP11 (Rm. 65-109) 65-DPE4CHP11-2 0.480 4.04 2.96 VCB 12 14 10 PNL 25 4 18 0.12 (*N21b) (*S2)

65-DPS4CHP11-CTS (COVID Test Site) 65-DPS4CHP11-2 0.480 3.19 2.31 VCB 12 14 10 PNL 25 6 18 0.23 (*N20b) (*N21a)

(*S1)

65-GEN-MDP-FDS (Ext. 65) (65-GEN-MDP-FDS-

FU LineSide)

UTIL-4A12-408-FU 0.480 39.02 26.92 VCB 12 14 10 PNL 25 307 18 111.42 (*N9) (*S1)

65-GPL2CHP11 (65-109) 65-GPL2CHP11-MB 0.208 1.01 0.38 VCB 12 14 10 PNL 25 21 18 1.52 (*N9) (*S0)

6.5-14

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

65-GPN2CHP11(A) (Rm. 65-109) 65-XF-GPL2CHP12 0.208 5.25 2.27 VCB 12 14 10 PNL 25 4 18 0.12 (*S0)

65-GPN2CHP11(B) (Rm. 65-109) 65-XF-GPL2CHP12 0.208 4.95 2.13 VCB 12 14 10 PNL 25 4 18 0.12 (*S0)

65-GPS2CHP11 (65-109) 65-GPS2CHP11-MB 0.208 1.83 0.72 VCB 12 14 10 PNL 25 32 18 2.98 (*N9) (*S0)

65-GPS2CHP11-CTS (COVID Test Site) 65-GPS2CHP11-1 0.208 1.01 0.38 VCB 12 14 10 PNL 25 21 18 1.53 (*N9) (*S1)

65-LPL4CHP11 (Rm. 65-109) 65-LPN4CHP11-2 0.480 10.35 7.92 VCB 12 14 10 PNL 25 8 18 0.31 (*N21a) (*S1)

65-LPN4CHP11 (Rm. 65-109) 2W-MDP-7 0.480 11.57 8.88 VCB 12 14 10 PNL 25 7 18 0.28 (*N21a) (*N21b)

(*S1)

65-MCCN4CHP11 (Rm. 114) 65-N4CHP11-1 0.480 20.48 15.67 VCB 12 14 10 MCC 25 26 18 2.21 (*S0)

65-N4CHP11 (Rm. 114) (65-N4CHP11-MB

LineSide)

65-GEN-MDP-FDS-

FU

0.480 36.81 22.65 VCB 12 14 10 PNL 25 205 18 58.51 (*N3) (*S1)

65-XF-GPL2CHP11-SEC (Rm. 65-109) 65-GPL2CH11-1 0.208 1.04 0.39 VCB 12 14 10 PNL 25 21 18 1.57 (*N9) (*N21a) (*S1)

65-XF-GPN2CHP11(A/B)-SEC (Rm. 65-109) 65-LPN4CHP11-3 0.208 5.43 1.48 HOA 30 36 20 AIR 32 7 18 0.16 (*N21a) (*S2)

65-XF-GPS2CH11-SEC (Rm. 65-109) 65-DPS4CHP11-1 0.208 1.9 0.75 VCB 12 14 10 PNL 25 33 18 3.10 (*N9) (*N21a) (*S1)

MV-168-SE (Bldg. 168) UTIL-4A12-408-FU 23.000 3.67 3.67 VCB 30 45 30 SWG 152 85 36 6.61 (*N_kv) (*S1)

MV-46-MDP (Bldg. 46)

MV-168-SE-FDR-A-

50/51

4.800 3.53 3.07 VCB 30 45 30 SWG 104 48 36 1.87 (*N3) (*S2)

MV-SSW-5 (South Courtyard) MV-46-FDR-1A-50/51 4.800 3.65 3.24 VCB 30 45 30 SWG 104 13 36 0.25 (*S1)

MV-SSW-6 (South Courtyard) MV-46-FDR-1A-50/51 4.800 3.65 3.24 VCB 30 45 30 SWG 104 13 36 0.25 (*S1)

MV-SSW-8 (South Courtyard) MV-46-FDR-3A-50/51 4.800 3.65 3.24 VCB 30 45 30 SWG 104 13 36 0.25 (*S1)

MV-SSW-9 (South Courtyard) MV-46-FDR-3A-50/51 4.800 3.65 3.24 VCB 30 45 30 SWG 104 13 36 0.25 (*S1)

MV-SW-1 (South Courtyard)

MV-168-SE-FDR-A-

50/51

23.000 3.63 3.63 VCB 30 45 30 SWG 152 61 36 3.41 (*N_kv) (*S1)

MV-SW-10 (South Courtyard) MV-46-FDR-1A-50/51 4.800 3.64 3.23 VCB 30 45 30 SWG 104 13 36 0.25 (*S1)

MV-SW-2C (Ext. 2C)

MV-168-SE-FDR-C-

50/51

23.000 3.61 3.61 VCB 30 45 30 SWG 152 61 36 3.39 (*N_kv) (*S1)

6.5-15

Bus Name Protective Bus Bus Bus Electrode Box Box Box Equip Gap Arc Working Incident PPE Level / Notes

(*N)

Device kV Bolted Arcing Config Width Height Depth Type (mm) Flash Distance Energy

Name Fault Fault (in) (in) (in) Boundary (in) (cal/cm2)

(kA) (kA) (in)

MV-SW-2E-E (Rm 2E-1161)

MV-168-SE-FDR-B-

50/51

23.000 3.66 3.66 VCB 30 45 30 SWG 152 61 36 3.43 (*N_kv) (*S1)

MV-SW-2E-W (Rm. 2E-1161)

MV-168-SE-FDR-C-

50/51

23.000 3.65 3.65 VCB 30 45 30 SWG 152 61 36 3.43 (*N_kv) (*S1)

MV-SW-2W (Ext. 2W)

MV-168-SE-FDR-B-

50/51

23.000 3.6 3.6 VCB 30 45 30 SWG 152 61 36 3.38 (*N_kv) (*S1)

MV-TAP1 (South Courtyard) MV-46-FDR-1A-50/51 4.800 3.63 3.22 VCB 30 45 30 SWG 104 13 36 0.25 (*S1)

MV-XF-1-XRAY-FDS-PRI (South Courtyard) MV-SSW-6-FU 4.800 3.6 3.14 VCB 18 40 55 SWG 104 8 36 0.11 (*N3) (*S0)

MV-XF-1-XRAY-FDS-SEC (South Courtyard) MV-SSW-6-FU 0.480 5.16 3.82 VCB 12 14 10 PNL 25 92 18 16.30 (*N9) (*S1)

MV-XF-2C-MDP-SEC (Ext. 2C) MV-SW-2C-FU 0.480 10.49 7.04 VCB 12 14 10 PNL 25 21 18 1.57 (*N3) (*S3)

MV-XF-2E-MDP-E-SEC (Rm. 2E-1161) MV-SW-2E-E-FU 0.480 24.36 16.13 VCB 12 14 10 PNL 25 48 18 5.66 (*N3) (*S3)

MV-XF-2E-MDP-W-SEC (Rm. 2E-1161) MV-SW-2E-W-FU 0.480 19.75 13.27 VCB 12 14 10 PNL 25 43 18 4.83 (*N3) (*S0)

MV-XF-2W-SEC (Ext. 2W) MV-SW-2W-FU 0.480 36.36 22.45 VCB 12 14 10 PNL 25 98 18 18.00 (*N3) (*S3)

MV-XF-30-A-PRI (South Courtyard) MV-SSW-9-FU 4.800 3.61 3.21 VCB 30 45 30 SWG 104 4 36 0.04 (*S1)

MV-XF-30-A-SEC (South Courtyard) MV-SSW-9-FU 0.208 26.22 11.54 VCB 12 14 10 PNL 25 184 18 49.32 (*N9) (*S1)

MV-XF-30-B-PRI (South Courtyard) MV-SSW-8-FU 4.800 3.61 3.2 VCB 30 45 30 SWG 104 4 36 0.04 (*S1)

MV-XF-30-B-SEC (South Courtyard) MV-SSW-8-FU 0.208 23.08 10.41 VCB 12 14 10 PNL 25 184 18 49.07 (*N9) (*S1)

MV-XF-33-PRI (South Courtyard) MV-TAP1-FU 4.800 3.61…