This document package includes construction drawings and structural details for repairing foundation cracks at a Veterans Affairs facility, along with the corresponding federal contract opportunity on usaspending.gov. The drawings show the scope of work involving concrete repairs to cracks and spalls through methods such as sawcutting, removing unsound concrete, installing new reinforcing bars, and applying epoxy adhesives. Repairs are specified for various structural elements including walls, surfaces, corners and shallow areas. The related solicitation on usaspending.gov provides further details on the procurement as solicitation number 36C24123B0014 to repair foundation cracks at a Veterans Affairs medical center located at 421 North Main Street in Leeds, Massachusetts.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
STRUCTURAL NOTES & LEGEND FINAL BID DOCUMENTS
REPAIR FOUNDATION CRACKS
421 NORTH MAIN STREET
LEEDS, MA 01053
2023/05/31 S-002
631-19-003
DJS LAJ
GENERAL SYMBOLS
HANDRAIL
DEMO
X ROOF LEGEND KEY
X KEYED NOTE
ELEVATION LABELTOP OF SLAB
0'-0"
DEMOLISH/REMOVE
CONCRETE STEP
LINETYPE LEGEND
DEMOLITION WALL/EXTENT
UNO UNLESS NOTED OTHERWISE
BLDG BUILDING
BOT BOTTOM
℄ CENTERLINE
CMU CONCRETE MASONRY UNIT
CY CUBIC YARDS
DIA DIAMETER
EMB EMBED
(E) EXISTING
f'c CONCRETE COMPRESSIVE STRENGTH
FT FOOT
GA GUAGE
HORZ HORIZONTAL
IN INCH
KB KNEE BRACE
LB POUND
LF LINEAR FEET
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MAX MAXIMUM
MIN MINIMUM
MPH MILES PER HOUR
NOM NOMINAL
OC ON CENTER
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R RADIUS
SF SQUARE FEET
SOG SLAB ON GRADE
THK THICK
TYP TYPICAL
VERT VERTICAL
WWR WELDED WIRE REINFORCEMENT
GENERAL ABBREVIATIONS
COLUMN CENTER LINE
REV 0 - FINAL BID DOCUMENTS 2023-05-31
GENERAL NOTES:
1. THE CONTRACTOR SHALL COORDINATE ALL WORK ASSOCIATED WITH THIS PROJECT WITH THE SUB-CONTRACTORS, TO PROVIDE A
COMPLETE AND FINISHED PROJECT.
2. THIS FACILITY IS OCCUPIED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL METHODS AND MEANS OF CONSTRUCTION AND SHALL BE RESPONSIBLE TO THE VA COR FOR PROVIDING A SAFE WORK ENVIRONMENT DURING THE CONSTRUCTION PERIOD. EVERY EFFORT SHALL BE MADE BY THE CONTRACTOR TO PROTECT THE OCCUPANTS, VISITORS AND CUSTOMERS FROM THE HAZARDS OF
CONSTRUCTION.
3. ALL MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS.
4. DIMENSIONS AND DETAILS ARE BASED ON THE BEST AVAILABLE INFORMATION AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING FIELD DIMENSIONS BEFORE ORDERING MATERIALS AND PREFABRICATED ITEMS.
5. ALL WORK SHALL BE PERFORMED IN THE BEST AND MOST PROFESSIONAL MANNER BY CONTRACTORS SKILLED IN THEIR RESPECTIVE
TRADES.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSPECTING AND CORRECTING HIS OWN WORKMANSHIP TO THE EXTENT THAT SATISFIES
THE VA COR.
7. THE CONTRACTOR, AND VA COR SHALL BE RESPONSIBLE FOR SPECIFICATIONS OF ALL MATERIALS NOT SPECIFIED ON THE THE DRAWINGS OR IN THE SPECIFICATIONS. THE CONTRACTOR SHALL COORDINATE THE SELECTION OF ALL COMPONENT COLORS, MODEL NUMBERS, SIZES, ETC. OF ALL BUILDING ELEMENTS WITH THE VA COR BEFORE ORDERING MATERIALS.
8. ALL WORKMANSHIP AND MATERIALS, UNLESS CARRYING A GUARANTEE BY A MANUFACTURER FOR A LONGER PERIOD OF TIME SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL PAYMENT TO THE CONTRACTOR.
9. THE CONTRACTOR SHALL VISIT THE SITE TO VERIFY FIELD CONDITIONS, NO ADDITIONAL PAYMENT WILL BE MADE FOR FAILURE TO
ACCOUNT FOR OBSERVABLE CONDITIONS.
10. THE CONTRACTOR SHALL MAKE EVERY EFFORT TO PREVENT THE SPREAD OF DUST, SMOKE, FUMES, ETC., THROUGHOUT THE BUILDING AND NEIGHBORHOOD. ALL WINDOW AC UNITS SHOULD BE COVERED AND OFF WHEN IN CLOSE PROXIMITY.
11. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SERVICES INCLUDING, ADEQUATE LIGHTING, WATER, TOILETS, POWER, HEAT, ETC.
AS REQUIRED FOR WORKMAN, MATERIAL INSTALLATION, WORK PROTECTION, ETC. OR AS DISCUSSED AND ALLOWED BY THE VA COR.
12. THE CONTRACTOR SHALL PROVIDE THE VA COR A COMPLETE MAINTENANCE & OPERATIONAL INSTRUCTIONS IN BOTH WRITTEN & VERBAL
FORM FOR ALL CONTRACTOR PROVIDED EQUIPMENT.
13. THE CONTRACTOR SHALL REVIEW ALL CONSTRUCTION DOCUMENTS AND NOTIFY THE VA COR OF ANY INACCURACIES OR DISCREPANCIES IN THE DOCUMENTS AND IN FIELD CONDITIONS SHOWN ON THE DRAWINGS IN A TIMELY MANNER.
14. THE CONTRACTOR SHALL PERFORM ALL WORK IN STRICT ACCORDANCE WITH ALL FEDERAL CODES, RULES, REGULATIONS AND ORDINANCES INCLUDING, BUT NOT LIMITED TO, THE INTERNATIONAL ENERGY CONSERVATION CODE, THE INTERNATIONAL BUILDING CODE, AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) AND OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) WHETHER OR NOT INFORMATION AND/OR WORK IS SPECIFICALLY SHOWN ON THE
DRAWINGS.
15. THE CONTRACTOR SHALL BE AWARE THAT THE EXISTING FACILITY HAS THE POTENTIAL OF HAVING OTHER CONSTRUCTION PROJECTS
GOING ON AT THE SAME TIME. COORDINATE WITH VA COR.
16. THE CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL MATERIAL DELIVERIES WITH VA COR AND VA STAFF IN CHARGE OF THE LOADING DOCK. NO CONTRACTOR MATERIAL WILL BE STORED ON OR AROUND LOADING DOCK UNLESS AUTHORIZED BY THE VA COR. THE VA WILL
NOT RECEIVE CONTRACTOR MATERIAL.
17. CONTRACTOR TO REVIEW AND LOCATE ALL DUMPSTER LOCATIONS WITH VA COR PRIOR TO START OF WORK. CONTRACTOR TO PLACE ALL DUMPSTERS WITHIN 10 FEET OF A BUILDING. COORDINATE DUMPSTER LOCATION WITH VA COR WHEN THIS IS NOT POSSIBLE. ANY DUMPSTER WITHIN 20 FEET OF A BUILDING WILL REMAIN COVERED WHEN NOT IN USE. CONTRACTOR SHALL USE TEMPORARY MARKINGS
AND SIGNAGE TO INDICATE DUMPSTER PLACEMENT.
18. CONTRACTOR TO PROVIDE FIRE PREVENTION PLAN TO VA COR FOR REVIEW AND APPROVAL.
19. IF A SAFETY SYSTEM IS OUT OF SERVICE FOR MORE THAN (4) HOURS OR A SITUATION OCCURS THAT EFFECTS SAFETY TO PATIENT OR THE HOSPITAL FOR MORE THAN (4) HOURS, THE CONTRACTOR IS TO NOTIFY VA COR A MINIMUM OF 48 HOURS IN ADVANCE TO
COORDINATE INTERIM LIFE SAFETY MEASURES (ILSM).
20. HOT WORK SHALL FOLLOW VA REQUIREMENTS. PERMIT REQUIRED.
21. IF CONTRACTOR ENCOUNTERS MECHANICAL EQUIPMENT PREVIOUSLY ABANDONED IN PLACE, COORDINATE REMOVAL AND REPAIR WITH
THE COR ON A CASE BY CASE BASIS.
XXX
SPOT ELEVATION
LIM
IT
O F
RE
PA
IR
3" 1"
1 1/2" MINIMUM REMOVAL BEHIND REINFORCEMENT
SANDBLAST CLEAN ALL SURFACES WITHIN REPAIR
LIMITS AND THOROUGHLY WET
1" SAWCUT ALONG
ALL EDGES (TYP)
SOUND CONCRETE
NEW REINFORCEMENT SAME SIZE AS THE EXISTING
SHALL BE SPLICED (TIED OR WELDED AS ORDERED
BY THE ENGINEER) TO THE EXISTING BARS
EXPOSED FACE
OR SURFACE OF
CONCRETE
REMOVE ALL UNSOUND CONCRETE AND REPLACE
WITH NEW CONCRETE
EXISTING REINFORCEMENT TO REMAIN SHALL BE
BLAST CLEANED
EDGES OF CONCRETE REMOVAL SHALL BE
"DOVETAILED" TO CREATE A GREATER BASE CAVITY
SEE NOTES
NOTE:
1. THE EXISTING CONCRETE SURFACE CAN BE PLANAR OR CURVED.
1" SAWCUT
(TYP)
SPALL OR HOLLOW SOUND
CONCRETE (TYP)
CRACKS (TYP)
REMOVE ALL UNSOUND CONCRETE AND
REPLACE WITH NEW CONCRETE
CRACK
1" SAWCUT (TYP)
1" SAWCUT (TYP)
1 1 /2"
M
IN
SANDBLAST CLEAN ALL SURFACES WITHIN
REPAIR LIMITS AND THOROUGHLY WET
EDGES OF CONCRETE REMOVAL
SHALL BE "DOVETAILED"
SOUND CONCRETE TO REMAIN
REMOVE UNSOUND CONCRETE.
REPLACE WITH NEW CONCRETE
NEW REBARS, SAME SIZE AS THE EXISTING SHALL
BE SPLICED (TIED OR WELDED AS ORDERED BY
THE ENGINEER) TO THE EXISTING BARSEXISTING
REINFORCEMENT
TO BE CLEANED
NOTE:
1. SEE CONCRETE REPAIR NOTES THIS SHEET AND S-002.
NOTE:
1. SEE CONCRETE REPAIR NOTES THIS SHEET AND S-002.
NOTE:
1. SEE CONCRETE REPAIR NOTES THIS SHEET AND S-002.
ASTM C881 COMPLIANT LOW VISCOSITY
HIGH MODULUS EPOXY ADHESIVE
ASTM C881 COMPLIANT LOW VISCOSITY
HIGH MODULUS EPOXY ADHESIVE
ASTM C881 COMPLIANT LOW VISCOSITY
HIGH MODULUS EPOXY ADHESIVE
MINIMUM WELD LENGTHS (in)
BAR SIZE SINGLE FLARE
V-GROOVE WELD
DOUBLE FLARE
V-GROOVE WELD
#3 3 1/2 2 #4 3 3/4 2 #5 4 1/8 2 1/2 #6 4 1/2 2 3/4 #7 5 1/8 3 1/8 #8 5 1/2 3 3/8 #9 6 1/8 3 1/2
MIN SPLICE LENGTH = 30 BARØ
BARS SHALL BE WIRED
TOGETHER FOR THE LENGTH OF
THE SPLICE
LAPPED, TIED SPLICE
d
WELDED SPLICE
d/3 d = REINFORCING
BAR DIAMETER
MIN LAP LENGTH EQUALS MIN
REQUIRED WELD LENGTH PLUS 1"
L1
SECTION A-A
SINGLE FLARE V - GROOVE WELD
SECTION A-A
DOUBLE FLARE V - GROOVE WELD
"A"
"A"
L2
EFFECTIVE
THROAT (TYP)
CRACK
NOTE:
1. SEE CONCRETE REPAIR NOTES THIS SHEET AND S-002.
ATSM C881 COMPLIANT NON SAG HIGH
MODULUS EPOXY ADHESIVE
CRACK
NOTE:
1. SEE CONCRETE REPAIR NOTES THIS SHEET AND S-002.
ATSM C881 COMPLIANT NON SAG HIGH
MODULUS EPOXY ADHESIVE
DJS LAJ
SCALE: NTS
TYPICAL WALL REPAIR >3" DEEP SECTION7 SCALE: NTS
TYPICAL CONCRETE SURFACE REPAIR8 SCALE: NTS
TYPICAL CONCRETE SURFACE REPAIR9 SCALE: NTS
TYPICAL CONCRETE CORNER REPAIR10
SCALE: NTS
REINFORCEMENT SPLICE DETAILS
FOR COMPRESSION BARS11
REV 0 - FINAL BID DOCUMENTS 2023-05-31
SCALE: NTS
TYPICAL CRACK REPAIR12
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
STRUCTURAL DETAILS FINAL BID DOCUMENTS
REPAIR FOUNDATION CRACKS
421 NORTH MAIN STREET
LEEDS, MA 01053
2023/05/31 S-501
631-19-003
SCALE: NTS
TYPICAL SHALLOW PATCH REPAIR-3" MAX DEPTH13