FOR IN
FORMATION ONLY
LOCATION MAP
TRUE
NORTH
DRAWING TITLEDWG
NO.
INDEX OF DRAWINGS
DRAWING TITLEDWG
NO.
STATEMENT OF CONDITIONS
& LIFE SAFETY ASSESSMENT
FINAL SUBMITTAL
VA MAINE HEALTHCARE SYSTEM
1 VA CENTER,
AUGUSTA, ME 04330
AREA MAP
TRUE
NORTH
MAIN CAMPUS
COVER PAGE - G001
ALL
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
FP&C Project Number 3259.00
G001
08/18/2021 AF TK/KW
WALL:
DUCTS:
PENETRATIONS:
DOORS*:
WALL:
DUCTS:
DOORS:
WALL:
DUCTS:
PENETRATIONS:
DOORS:
SUITE DESIGNATION
2-HOUR FIRE BARRIER
THIS APPLIES TO OCCUPANCY SEPARATION WALLS, HORIZONTAL EXITS, AND STAIRWELLS OF
4 OR MORE STORIES.
2-HOUR FIRE AND SMOKE ZONE BARRIER
THIS APPLIES TO OCCUPANCY SEPARATION WALLS, HORIZONTAL EXITS, AND
STAIRWELLS OF 4 OR MORE STORIES. THIS COMBINATION WALL IS WHERE A PORTION
OF THE 2-HOUR RATED WALL IS ALSO PART OF THE SMOKE WALL.
1-HOUR FIRE BARRIER
THIS APPLIES TO 1-HOUR FIRE RATED OCCUPANCY SEPERATIONS, HAZARDOUS ROOM
ENCLOSURES PER NFPA 101 8.6.5(2) AND STAIRWELLS 3 STORIES OR LESS. PER NFPA 101 19.3.2.1
SMOKE ZONE BARRIER
SUBSTANTIAL WALLS AND DOORS TO DIVIDE EACH FLOOR INTO COMPARTMENTS FOR
DEFEND IN PLACE EMERGENCY OPERATIONS. IF THE SMOKE ZONE BARRIER WALL IS
OF MASONRY, GYPSUM BOARD, OR METAL LATH AND PLASTER CONSTRUCTION, AND
THE BARRIER WAS CONSTRUCTED POST 1948, THE SMOKE ZONE BARRIER WALLS ARE
REQUIRED TO BE OF 1 HOUR FIRE RESISTANCE RATING. (NFPA 101, 18.3.7.6) SMOKE
ZONE BARRIER WALLS OF WOOD LATH AND PLASTER CONSTRUCTION ARE PERMITTED
TO BE OF A 12 HOUR FIRE RESISTANCE RATING (NFPA 101, 19.3.7.3)
(COLOR #5)
(COLOR #4)
(COLOR #1)
(COLOR #2)
(COLOR #3)
NOTE: ALL CODE REFERENCES ARE PER THE 2018 EDITION OF NFPA 101 LIFE SAFETY CODE AND 2019 EDITION OF NFPA 80 AND NFPA 105. FEDERAL FACILITIES FOLLOW 2018 LIFE SAFETY CODE.
DOORS: DOORS THAT ARE NOT PART OF A RATED WALL:
1. NON-LABELED FRAME (NFPA 101 18.3.6.3.1, 19.3.6.3 & 19.3.6.3.3)
2. NON-RATED DOORS PERMITTED IF SPRINKLERED (NFPA 101
18.3.6.3.1, 19.3.6.3.2(2))
3. 20-MINUTE OR SOLID WOOD CORE DOOR IF NOT SPRINKLERED (NFPA 101 19.3.6.3.1) 1 3 4" THICK.
4. POSITIVE LATCHING EXCEPT TOILETS, SHOWER AND SINK
CLOSETS (NFPA 101 18.3.6.3.6 & 19.3.6.3.6)
5. SELF-CLOSING NOT REQUIRED (NFPA 101 19.3.6.3.11)
6. NO MAXIMUM GAP (NFPA 101 18.3.6.3.1 & 19.3.6.3.3)
7. MAXIMUM 1" UNDERCUT (NFPA 101 18.3.6.3.1 & 19.3.6.3.4)
8. UNLIMITED HEIGHT PROTECTIVE PLATE (NFPA 101 18/19.3.6.3.12)
9. TRANSFER GRILLS NOT PERMITTED EXCEPT TOILETS,
SHOWER AND SINK CLOSETS (NFPA 101 18/19.3.6.4)
10. SWING IN ANY DIRECTION
11. SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST ANNUALLY (NFPA 105 5.2.5.1)
(COLOR #30)
NON-RATED SMOKE ZONE PARTITION
FORMER DECOMMISSIONED SMOKE BARRIER RETAINED AS FIRE ALARM/SPRINKLER
ZONE. BUILDING OCCUPANTS PERMITTED TO DEFEND IN PLACE UNTIL DIRECTED BY
THE FIRE DEPARTMENT PER SECTION 16.7.4.3 OF NFPA 99-2018 EDITION AND PRIVATE
MODE AUDIBLE REQUIREMENTS OF SECTION 16.7.4.3 OF NFPA 72-2019 EDITION.
WALL:
DUCTS:
PENETRATIONS:
DOORS:
HEALTH CARE OCCUPANCY CORRIDORS
THE WALL SHALL FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE. THE WALL HAS NO REQUIRED FIRE RESISTANCE RATING AND MAY TERMINATE AT A CEILING CONSTRUCTED TO LIMIT TRANSFER OF SMOKE.
PENETRATIONS:
WALL EXTENDS FROM FLOOR TO DECK ABOVE.
ALL DUCT PENETRATIONS ARE PROTECTED BY FIRE DAMPERS.
ALL NEW PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS FOR
PROTECTING 2-HOUR WALL ASSEMBLIES. WALL PENETRATIONS ARE REQUIRED TO
BE FILLED ON BOTH SIDES OF THE WALL. FLOOR PENETRATIONS ARE ONLY
REQUIRED TO BE FILLED ON THE TOP OF THE FLOOR.
ALL DOORS REQUIRE THE FOLLOWING:
1. LABELED FRAMES (NFPA 80 4.2.1)
2. LABELED 1 1/2 HOUR DOOR (NFPA 80 4.3.1)
3. MAXIMUM 100 SQ. IN. WINDOW (NFPA 80 TABLE 4.4.5)-LIMITED TO MAX AREA
TESTED.
4. POSITIVE LATCHING (NFPA 80 6.4.1.4)
5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 6.4.1)
6. COORDINATING DEVICES REQUIRED (NFPA 80 6.4.1.2.1)
7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7)
8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)
9. MAXIMUM 16" PROTECTIVE PLATE OR LABELED & LISTED (NFPA 80 6.4.5)
10. SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 18/19.3.7.6).
11. PERIODIC INSPECTION AND TESTING SHALL BE PERFORMED AT LEAST
ANNUALLY (NFPA 80 5.2.4.1)
* 2 HOUR DOOR REQUIRED FOR STAIRWELLS 4 OR MORE STORIES (NFPA 101
7.1.3.2.1)(3).
WALL:
DUCTS:
PENETRATIONS:
DOORS:
WALL EXTENDS FROM FLOOR TO DECK ABOVE.
ALL DUCT PENETRATIONS ARE PROTECTED BY COMBINATION FIRE AND
SMOKE DAMPERS. SMOKE DAMPERS ARE NOT REQUIRED WHERE
ADJACENT SMOKE COMPARTMENTS ARE PROTECTED BY QUICK
RESPONSE SPRINKLERS THROUGHOUT EACH COMPARTMENT.
ALL NEW PENETRATIONS ARE SEALED WITH LISTED FIRESTOP
MATERIALS FOR PROTECTING 2-HOUR WALL ASSEMBLIES. WALL
PENETRATIONS ARE REQUIRED TO BE FILLED ON BOTH SIDES OF THE
WALL. FLOOR PENETRATIONS ARE ONLY REQUIRED TO BE FILLED ON
THE TOP OF THE FLOOR.
ALL DOORS REQUIRE THE FOLLOWING:
1. LABELED FRAMES (NFPA 80 4.2.1)
2. LABELED 1 1/2 HOUR DOOR (NFPA 80 4.3.1)
3. MAXIMUM 100 SQ. IN. WINDOW (NFPA 80 4.4.5)
4. POSITIVE LATCHING (NFPA 80 6.4.1.4)
5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 6.4.1)
6. COORDINATING DEVICES REQUIRED (NFPA 80 6.4.1.2.1)
7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7)
8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)
9. MAXIMUM 16" PROTECTIVE PLATE OR LABELED & LISTED (NFPA 80
6.4.5.1)
10. SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 18/19.3.7.6).
11. PERIODIC INSPECTION AND TESTING SHALL BE PERFORMED AT
LEAST ANNUALLY (NFPA 80 5.2.4.1)
WALL EXTENDS FROM FLOOR TO DECK ABOVE.
STEEL DUCT PENETRATIONS NOT REQUIRED TO BE PROTECTED BY FIRE
DAMPERS.
ALL NEW PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS FOR
PROTECTING 1-HOUR WALL ASSEMBLIES. WALL PENETRATIONS ARE REQUIRED
TO BE FILLED ON BOTH SIDES OF THE WALL. FLOOR PENETRATIONS ARE ONLY
REQUIRED TO BE FILLED ON THE TOP OF THE FLOOR.
ALL DOORS REQUIRE THE FOLLOWING:
1. LABELED FRAMES (NFPA 80 4.2.1)
2. LABELED 3/4 OR 1-HOUR DOOR (NFPA 80 4.3.1)*
3. MAXIMUM AREA TESTED WINDOW (NFPA 80 TABLE 4.4.5)
4. POSITIVE LATCHING (NFPA 80 6.4.1.4)
5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 6.4.1)
6. COORDINATING DEVICES REQUIRED (NFPA 80 6.4.1.2.1)
7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7)
8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)
9. MAXIMUM 16" PROTECTIVE PLATE OR LABELED & LISTED (NFPA 80 6.4.5)
10.SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 18/19.3.7.6).
11.PERIODIC INSPECTION AND TESTING SHALL BE PERFORMED AT LEAST
ANNUALLY (NFPA 80 5.2.4.1)
* 1-HOUR DOORS ARE REQUIRED IN STAIRWELLS THAT ARE 3 STORIES OR
LESS. (NFPA101 7.1.3.2.1)(1)
WALL EXTENDS FROM FLOOR TO DECK ABOVE.
ALL DUCT PENETRATIONS ARE PROTECTED BY SMOKE DAMPERS. SMOKE
DAMPERS ARE NOT REQUIRED WHERE ADJACENT SMOKE COMPARTMENTS ARE
PROTECTED BY QUICK RESPONSE SPRINKLERS THROUGHOUT EACH
COMPARTMENT.
ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS FOR
PROTECTING 1-HOUR FIRE AND SMOKE WALL ASSEMBLIES. PENETRATIONS ARE
TO BE FILLED ON BOTH SIDES OF THE WALL.
ALL DOORS FOR SMOKE BARRIERS REQUIRE THE FOLLOWING:
1. NON-LABELED FRAME (NFPA 101 18.3.7.6)
2. 20 MINUTE OR SOLID WOOD CORE (NFPA 101 18.3.7.6) 1 3 4" THICK.
3. MAXIMUM SIZE LISTED WINDOW (NFPA 80 TABLES 4.4.5)
4. POSITIVE LATCHING NOT REQUIRED (NFPA 101 18.3.7.8)
5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 101 18.3.7.8)
6. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7)
7. MAXIMUM 3/4" UNDERCUT (NFPA 101 8.5.4)
8. UNLIMITED IN HEIGHT PROTECTIVE PLATE (NFPA 101 18.3.7.6/19.3.7.6.1
9. SWING IN DIRECTION OPPOSITE OF EACH OTHER (NFPA 101 18.3.7.6)
10.SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST ANNUALLY (NFPA 105
5.2.5.1)
WALL EXTENDS FROM FLOOR TO SUSPENDED CEILING OR DECK ABOVE.
NO MINIMUM REQUIREMENTS.
NO MINIMUM REQUIREMENTS FOR WALL PENETRATIONS ABOVE A SUSPENDED
CEILING. PENETRATIONS BELOW A SUSPENDED CEILING OR DECK SEALED
WITH NON-FIRE-RATED MATERIALS TO BE SMOKE RESISTIVE.
NON-FIRE-RATED DOORS AND FRAMES SELF CLOSING OR AUTOMATIC CLOSING
IN AN EMERGENCY.
(COLOR #30)
(COLOR #2)
HEALTHCARE AREA OPEN TO CORRIDOR WITH 24
SUPERVISION - NO SMOKE DETECTION REQUIRED.
(COLOR #3)
HEALTHCARE AREA OPEN TO CORRIDOR - SMOKE
DETECTION PROVIDED.
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
(COLOR #230)
(COLOR #4)
NON-FIRE RATED SMOKE BARRIER
SUBSTANTIAL WALLS AND DOORS TO SUBDIVIDE BUILDING SPACES FOR THE PURPOSE
OF RESTRICTING THE MOVEMENT OF SMOKE.
WALL: EXTENDS FROM FLOOR TO DECK ABOVE.
DUCTS: SMOKE DAMPERS ARE NOT REQUIRED WHERE STEEL DUCTS PENETRATE SMOKE
BARRIERS FORMING A COMMUNICATING SPACE SEPARATION.
PENETRATIONS: ALL PENETRATIONS ARE SEALED WITH NON-FIRE RATED MATERIALS TO PREVENT THE
TRANSFER OF SMOKE. USE OF LISTED FIRE STOP MATERIALS IS NOT REQUIRED.
DOORS: ALL DOORS FOR SMOKE BARRIERS REQUIRE THE FOLLOWING:
1. NON LABELED FRAME (NFPA 101 8.5)
2. NON FIRE RATED DOOR (NFPA 101 8.5)
3. NO GRILLS OR LOUVERS ARE PERMITTED (NFPA 101 8.5.1)
4. POSITIVE LATCHING HARDWARE IS REQUIRES (NFPA 101 8.5.4.3)
5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 101 8.5.4.43)
6. MAXIMUM ¾” UNDERCUT (NFPA 101 8.5.4.1)
7. UNLIMITED IN HEIGHT PROTECTIVE PLATE (NFPA 101 18.3.7.6/19.3.7.6.1)
8. SWING IN ANY DIRECTION (NFPA 8.5)
9. WINDOW ASSEMBLIES ARE NOT REQUIRED TO BE FIRE RATED (NFPA 8.5)
10. SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST ANNUALLY (NFPA 105 5.2.5.1)
WALL:
DUCTS:
DOORS:
SMOKE RESISTIVE ENCLOSURE
(COLOR #230) IF THE HAZARDOUS ROOM HAS A SUSPENDED CEILING CONSTRUCTED TO LIMIT
TRANSFER OF SMOKE, THE WALL HAS NO FIRE RESISTANCE RATING AND MAY
TERMINATE AT THE CEILING PER NFPA 101 8.4.2(3). IF THE ROOM DOES NOT
HAVE A SUSPENDED CEILING, THE WALL HAS NO FIRE RESISTANCE RATING
AND SHALL EXTEND TO THE DECK ABOVE PER NFPA 101 19.3.2.1.2.
STEEL DUCT PENETRATIONS ARE NOT REQUIRED TO BE PROTECTED BY FIRE
DAMPERS OR SMOKE DAMPERS.
SEALED WITH NON-FIRE-RATED MATERIALS TO BE RESISTIVE. USE OF LISTED
FIRESTOP MATERIALS IS NOT REQUIRED.
EXISTING HAZARDOUS ROOMS:
1. NON-LABELED FRAME (NFPA 101 8.4.2)
2. 20 MINUTE OR SOLID WOOD CORE (NFPA 105 A.6.3.1) 1 3 4" THICK.
3. POSITIVE LATCHING IS REQUIRED PER (NFPA 105 6.3.4)
4. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 101 19.3.2.1.3)
5. MAXIMUM 1/8" GAP (NFPA 105 6.3.3)
6. MAXIMUM 3 4" UNDERCUT (NFPA 80 4.8.4.1)
7. MAXIMUM 48" PROTECTIVE PLATE (NFPA 101 19.3.2.1.4)
8. SWING IN ANY DIRECTION
9. SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST ANNUALLY (NFPA
105 5.2.5.1)
PENETRATIONS:
(COLOR #30)
EXIT STAIRWELL/PASSAGEWAY
ALL
FIRE/SMOKE BARRIER
DESCRIPTION
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
FP&C Project Number 3259.00
SOC X-1
APPLICABLE CODES AND STANDARDS: FIRE SPRINKLER SYSTEM:
1. THE COMBINATION STANDPIPE AND FIRE SPRINKLER SYSTEM WAS DESIGNED TO NFPA 13 AND NFPA 14.
2. QUICK RESPONSE TYPE SPRINKLERS ARE INSTALLED THROUGHOUT MOST OF THE BUILDING. STANDARD RESPONSE TYPE SPRINKLERS ARE INSTALLED IN THE ELEVATOR MACHINE ROOMS (NFPA 13 - 3.3.4.16).
3. SPRINKLERS WERE INSTALLED IN LIGHT HAZARD AREAS INCLUDING; CORRIDORS, OFFICES, PATIENT CARE AND PATIENT SLEEPING ROOMS AT LIGHT HAZARD 0.10 GPM/1500 SQ. FT. DENSITY. MAXIMUM PROTECTION AREA OF 225 SQ. FT. (NFPA 13 - TABLE 19.3.3.1.2).
4. SPRINKLERS WERE INSTALLED IN ORDINARY HAZARD GROUP I AREAS INCLUDING; LABORATORIES (WITHOUT FLAMMABLE LIQUIDS), MECHANICAL EQUIPMENT ROOMS, ELECTRICAL SWITCH GEAR ROOMS, REPAIR SHOPS AND STORAGE ROOMS UNDER 250 SQ. FT. AT A 0.15
GPM/1500 SQ. FT. DENSITY. MAXIMUM PROTECTION AREA OF 150 SQ. FT. (NFPA 13 - TABLE 19.3.3.1.2).
5. SPRINKLERS WERE INSTALLED IN ORDINARY HAZARD GROUP II AREAS INCLUDING GENERAL STORAGE ROOMS OVER 250 SQ. FT. AND LABORATORIES (WITH THE USE OF FLAMMABLE LIQUIDS) AT A 0.20 GPM/1500 SQ. FT. DENSITY.
6. MAXIMUM DISTANCE FROM SPRINKLERS TO WALLS FOR STANDARD SPRAY SPRINKLERS SHALL NOT EXCEED 7'-6" (NFPA 13 - 10.2.5.2.1). MAXIMUM DISTANCE FROM SPRINKLERS TO WALLS FOR STANDARD SPRAY SPRINKLERS IN SMALL ROOMS (800 SQ. FT. MAXIMUM) SHALL NOT
EXCEED 9' FROM ANY SINGLE WALL (NFPA 13 - 10.2.5.2.3).
7. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS (I.E. DUCTWORK) OVER 4' WIDE (NFPA 13 - 12.1.10.3.2). THE WIDTH OF DUCT INSULATION NOT A FACTOR FOR SPRINKLERS INSTALLED PRIOR TO THE 2019 EDITION ON NFPA 13. SPRINKLERS NOT REQUIRED UNDER
NON COMBUSTIBLE OBSTRUCTIONS OVER 4' WIDE WHERE THE BOTTOM OF THE OBSTRUCTION IS A MAXIMUM 24" ABOVE THE FLOOR (NFPA 13 - 9.5.5.3.1).
8. SPRINKLERS SHALL BE INSTALLED A MAXIMUM 12" BELOW A CEILING OR FLOOR/ROOF DECK (NFPA 13 - 10.2.6.1.1.1) OR A MAXIMUM 22" BELOW A FLOOR/ROOF DECK WITH STRUCTURAL MEMBER OBSTRUCTIONS (NFPA 13 - 10.2.6.1.2).
9. SHELVING ON A WALL OR SHELVING AGAINST A WALL INCLUDING STORAGE THEREON SHALL BE PERMITTED TO EXTEND WITHIN THE 18" SPRINKLERS CLEARANCE BELOW CEILING SPRINKLER DEFLECTORS (NFPA 13 - 9.5.6.1).
10. WHERE THE 18" CLEARANCE BETWEEN SPRINKLERS AND SHELVING STORAGE CANNOT BE MAINTAINED, SPRINKLERS SHALL BE INSTALLED IN EVERY AISLE PER NFPA 13 - 9.2.5(2).
11. CEILING MOUNTED OBSTRUCTIONS (I.E. PATIENT LIFT TRACKS) WITHIN THE 18" SPRINKLER DISCHARGE CLEARANCE ARE PERMITTED PER NFPA 13 - TABLE 10.2.7.1.2 AND FIGURE 10.2.7.1.2(a).
12. FLOOR MOUNTED OBSTRUCTIONS (I.E. ROOM DIVIDERS OR SHELVING) WITHIN THE 18" SPRINKLER DISCHARGE CLEARANCE ARE PERMITTED PER NFPA 13 - TABLE 10.2.7.2.2 AND FIGURE 10.2.7.2.2.
SUITES:
1. SUITES ARE UTILIZED TO ILLUSTRATE AREAS WITH THE SAME FUNCTION, USE OF HALLWAYS OR AISLES AND TO DEFINE THE END OF PUBLIC EXIT
CORRIDORS. NO EXIT SIGNS OUTSIDE OF THE SUITE MAY DIRECT OCCUPANTS INTO A SUITE TO REACH AN EXIT.
2. HEALTH CARE OCCUPANCY SUITES ARE REGULATED BY FUNCTION AND SIZE.
3. HEALTH CARE OCCUPANCY PATIENT SLEEPING SUITES:
A. SINGLE EXIT SUITE - 1,000 SQ. FT. (NFPA 101 -19.2.5.7.2.2)
B. MULTI EXIT SUITE - 5,000 SQ. FT. (NFPA 101 - 19.2.5.7.2.3.A)
C. MULTI EXIT SUITE WITH STANDARD RESPONSE SPRINKLERS OR COMPLETE SMOKE DETECTION - 7,500 SQ. FT. (NFPA 101 - 19.2.5.7.2.3.B) D. MULTI EXIT SUITE WITH DIRECT VISUAL SUPERVISION, QUICK RESPONSE SPRINKLERS AND COMPLETE SMOKE DETECTION - 10,000 SQ. FT. (NFPA
101 - 19.2.5.7.2.3.C)
4. PATIENT CARE NON - SLEEPING SUITES:
A. SINGLE EXIT SUITE - 2,500 SQ. FT. (NFPA 101 - 19.2.5.7.3.1.B)
B. MULTI EXIT SUITE - 10,000 SQ. FT. (NFPA 101 - 19.2.5.7.3.3)
5. HEALTH CARE OCCUPANCY NON - PATIENT - CARE SUITES FOLLOW THE TRAVEL DISTANCE REQUIREMENTS AS LISTED IN TABLE A.7.6 OF NFPA 101.
6. SUITES IN OTHER OCCUPANCIES ARE NOT REGULATED IN SIZE BUT STILL FOLLOW THE TRAVEL DISTANCE REQUIREMENTS AS LISTED IN TABLE A.7.6
OF NFPA 101.
1. THE ORIGINAL BUILDING WAS DESIGNED TO THE 1943 EDITION OF NFPA 101, LIFE SAFETY CODE.
2. THE 1960 PUBLIC BUILDING AMENDMENT ACT (PL100-678) REQUIRES ALL FEDERAL AGENCIES TO FOLLOW THE LATEST EDITIONS OF NATIONALLY
RECOGNIZED FIRE AND LIFE SAFETY CODES. THE VA HAS ADOPTED THE NATIONAL FIRE CODES PUBLISHED BY THE NATIONAL FIRE PROTECTION ASSOCIATION. LIFE SAFETY REQUIREMENTS ARE SPECIFICALLY ADDRESSED IN THE 2018 EDITION OF NFPA 101, LIFE SAFETY CODE.
3. ALL NEW CONSTRUCTION OR BUILDING RENOVATIONS ARE REQUIRED TO COMPLY WITH THE LATEST EDITION OF NFPA 101 OR IT'S REFERENCED STANDARDS. EXISTING BUILDING CONDITIONS ARE REQUIRED TO COMPLY WITH THE APPLICABLE CODES OR STANDARDS AT THE TIME OF BUILDING DESIGN AND THE APPLICABLE PROVISIONS FOR EXISTING BUILDINGS IN CURRENT EDITIONS OF APPLICABLE CODES AND STANDARDS.
4. OTHER NFPA CODES AND STANDARDS:
A. NFPA 10 - PORTABLE FIRE EXTINGUISHERS, 2018 EDITION
B. NFPA 13 - SPRINKLER SYSTEMS, 2019 EDITION
C. NFPA 14 - STANDPIPE SYSTEMS, 2016 EDITION
D. NFPA 20 - FIRE PUMPS, 2019 EDITION
E. NFPA 25 - WATER-BASED FIRE PROTECTION SYSTEMS 2020 EDITION
F. NFPA 70 - NATIONAL ELECTRIC CODE, 2020 EDITION
G. NFPA 72 - NATIONAL FIRE ALARM CODE, 2019 EDITION
H. NFPA 75 - ELECTRONIC COMPUTER EQUIPMENT, 2017 EDITION
I. NFPA 80 - FIRE DOORS, 2019 EDITION
J. NFPA 90A&B - HEATING AND AIR CONDITIONING SYSTEMS, 2018 EDITION
K. NFPA 96 - COMMERCIAL COOKING EQUIPMENT, 2017 EDITION
L. NFPA 99 - HEALTH CARE FACILITIES CODE, 2018 EDITION
M. NFPA 105 - SMOKE DOORS, 2019 EDITION
N. NFPA 110 - EMERGENCY POWER SYSTEMS, 2019 EDITION
O. NFPA 241 - CONSTITUTION AND DEMOLITION, 2019 EDITION
1. EXITS (STAIRWAYS, HORIZONTAL EXITS AND DIRECT EXTERIOR EXIT DOORS), OTHER THAN EXTERIOR EXIT DOORS THAT ARE OBVIOUSLY AND CLEARLY IDENTIFIABLE AS EXITS. (GLASS DOORS, VISION PANELS OR ADJACENT WINDOWS) SHALL BE MARKED WITH EXIT SIGNAGE.
(SECTION 7.10.1.2.1 OF NFPA 101-2018 EDITION)
2. DIRECTIONAL SIGNS REQUIRED WHERE DIRECTION OF TRAVEL IS NOT APPARENT IN AN EXIT ACCESS CORRIDOR. (SECTION 7.10.2.1 OF NFPA
101-2018 EDITION)
3. DIRECTIONAL SIGNAGE (EXIT PLACARDS) REQUIRED WITHIN HORIZONTAL COMPONENTS OF EXIT STAIR ENCLOSURES WHERE EGRESS PATH
IS NOT OBVIOUS (SECTIONS 7.10.2.2 AND 7.10.1.2.2 OF NFPA 101-2018 EDITION)
4. MAXIMUM VIEWING DISTANCE TO AN EXIT SIGN IN AN EXIT ACCESS CORRIDOR IS 100 FT. (SECTION 7.10.1.5.2 OF NFPA 101-2018 EDITION)
5. EXIT SIGNS SHALL BE INSPECTED MONTHLY. (SECTION 7.10.9.1 IF NFPA 101-2018 EDITION)
6. DIRECTIONAL SIGNAGE (EXIT PLACARDS OR EXIT SIGNS) WITH OR WITHOUT DIRECTIONAL ARROWS SHOULD BE PROVIDED IN SUITES USED
BY THE GENERAL PUBLIC (LESS THAN 50 TOTAL OCCUPANTS) TO DIRECT THE GENERAL PUBLIC BACK TO THE WAITING AREA. (SECTION
7.10.2.1 OF NFPA 101-2018 EDITION)
7. ROOMS OR SUITES OF ROOMS USED FOR 50 OCCUPANTS OR MORE SHALL BE PROVIDED WITH EXIT SIGNAGE. (SECTIONS 13.2.10.1 AND
3.3.196.2 OF NFPA 101-2018 EDITION)
EXIT SIGN REQUIREMENTS
OCCUPANCY TABLE
FIRE ALARM SYSTEM:
1. THE FIRE ALARM SYSTEM WAS DESIGNED TO NFPA 72, NATIONAL FIRE ALARM CODE.
2. PRIVATE MODE BUILDING OCCUPANT NOTIFICATION IS INSTALLED PER SECTIONS 19.3.4.3.1 AND 9.6.3.6.3 OF NFPA 101-2018 EDITION.
3. PRIVATE MODE AUDIBLE DEVICES (SPEAKERS) ARE INSTALLED IN CORRIDORS AND LARGER ROOMS OR SUITES PER SECTION 18.4.4.1 OF NFPA
72 - 2019 EDITION.
4. PRIVATE MODE VISIBLE DEVICES (STROBES) ARE INSTALLED AT REDUCED QUANTITY AND SPACING PER SECTION 18.6 OF THE NFPA 72 - 2019
EDITION.
5. STROBE CIRCUITS ARE REQUIRED TO BE SYNCHRONIZED IN ACCORDANCE WITH SECTION 18.5.4.3.2(3) OF NFPA 72 - 2019 EDITION.
6. TYPICAL SMOKE DETECTORS HAVE A 21 FT. RADIUS OF COVERAGE AREA (NFPA 72 - 17.7.3.2.3.1)
7. SMOKE DETECTORS THAT ARE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND LOCATED ON BOTH SIDES OF SMOKE/FIRE DOORS MAY
BE SPACED AT MAXIMUM 21' RADIUS FOR DOOR RELEASE SERVICE (NFPA 72 - 17.7.5.6.1) SMOKE DETECTORS NOT CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND USED EXCLUSIVELY FOR SMOKE/FIRE DOOR RELEASE SHALL BE LOCATED AND SPACED PER NFPA 72- 17.7.5.6.
8. CEILINGS WITH BEAM DEPTHS OF LESS THAN 10% OF CEILING HEIGHT SHALL BE CONSIDERED A SMOOTH CEILING FOR SMOKE DETECTOR COVERAGE. CEILINGS WITH BEAM DEPTHS GREATER THAN 10% OF CEILING HEIGHT SHALL HAVE REDUCED SMOKE DETECTOR SPACING
COVERAGE (NFPA 72 - 17.7.3.2.4.2).
9. SMOKE DETECTORS SHALL BE LOCATED ON THE CEILINGS THE BOTTOM OF BEAMS OR MAXIMUM 12" DOWN FROM THE CEILING TO TOP OF THE
DETECTOR (NFPA 72- 17.7.3.2.1).
10. SMOKE DETECTORS SHALL NOT BE LOCATED DIRECTLY IN THE AIR STREAM OF SUPPLY AIR REGISTERS (NFPA 72- 17.7.6.3.2).
THE VA HAS ELECTIVE ACCREDITATION WITH THE JOINT COMMISSION (TJC) FOR HEALTH CARE FACILITIES. SEE THE MEMORANDUM OF UNDERSTANDING (EFFECTIVE JANUARY 31, 2020) BETWEEN THE VA AND TJC FOR IMPLEMENTATION OF TJC ENVIRONMENT OF CARE (EC) AND
LIFE SAFETY (LS) STANDARDS.
THE VA HAS ELECTIVE ACCREDITATION WITH THE LONG-TERM CARE INSTITUTE, INC. (LTCI) FOR COMMUNITY LIVING CENTERS (CLC). SEE THE CLARIFICATION MEMORANDUM (EFFECTIVE MARCH 12, 2019) BETWEEN THE VA AND THE LTCI FOR IMPLEMENTATION OF LIFE SAFETY
REQUIREMENTS.
THE FOLLOWING NATIONWIDE VA EQUIVALENCIES HAVE BEEN REVIEWED AND APPROVED BY THE JOINT COMMISSION AND APPLY TO ALL BUILDINGS:
1. OVERSIZED PROTECTIVE PLATES PERMITTED ON FIRE RATED DOORS
2. BUSINESS OCCUPANCY DEAD END CORRIDORS PERMITTED TO EXCEED 50 FEET
3. INTERNAL SPRINKLER PIPING CONDITION AND OBSTRUCTION INVESTIGATION.
EQUIVALENCIES
Building No. Floor Health Care Ambulatory Health
Care Business Industrial Domiciliary Total 200 Ground 17,907 2,478 20,385
200 1 28,929 28,929
200 2 20,530 20,530
200 3 18,177 18,177
200 4 18,075 18,075
200 5 5,915 8,225 14,140
200 6 9,360 9,360
200 7 5,977 5,977
200 Penthouse 1,359 1,359
SUB TOTALS 36,252 5,915 90,928 3,837 0 136,932
200E Ground 37,316 37,316
200E 1 28,325 28,325
200E 2 30,286 30,286
200E 3 29,691 29,691
200E Penthouse 7,656 7,656
SUB TOTALS 29,691 37,316 58,611 7,656 0 133,274
206 1 19,673 19,673
206 2 18,306 18,306
206 3 18,420 18,420
206 Penthouse 1,550 1,550
SUB TOTALS 18,420 0 39,529 0 0 57,949
207 1 18,383 18,383
207 2 19,199 19,199
207 3 19,180 19,180
207 Penthouse 2,873 2,873
56,762 0 0 2,873 0 59,635
GRAND TOTALS 141,125 43,231 189,068 14,366 0 387,790
ALL
CODE SUMMARY AND
OCCUPANCY TABLE
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
FP&C Project Number 3259.00
SOC X-2
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
EXEX
B 200
B 200E
GROUND SOUTH GROUND NORTH
GROUND CENTER
GROUND NORTH
BUSINESS OCCUPANCY
FULLY SPRINKLERED
GROUND FLOOR
BUILDING 200
N
BUILDING 200 GROUND FLOORCONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200SOC-G
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
145A
137A
157A
166A
195A
166B
166D 166C
C102 C101
102 104
176A
2A
101 105 107 109
115 111 117 119
123 125
122 120 114 112 108
101A
116 118
142B
SI
LL
H T
M114
M112
M113
M111
M109
M110
M115M101
M107
M105 M108
M106
M100M104
M103
M120 M119 M118 M117 M116
147145A
175A
129B
142B
155B
150142A 142B
A
142B
SMOKE DOORS
155A
155155C
155D
MRI
159A
142C
141A
SILLHT SILLHT
C101A
C101B
102A
1'-8"
PARKING FOR
PORTABLE M/C
ORTHOPEDICS
SPD STORAGE
TOILET
MALE TOILET
ELECTRICAL
TOILET
ULTRA SOUND
DATA RM
PARKING FOR
PORTABLE M/C
ELECTRICAL
ELECTRICAL
TOILET
HAC
HAC
TOILET
WAITING
CHANGING RM
WAITING
CHANGING
RM
CORRIDOR
CORRIDOR
CORRIDORCORRIDOR
CONTROL RM
CT SCANS
ELECTRICAL RM
CT SCAN
EXAM RM EXAM RM
RECEPTION WAITING
OFFICE OFFICE EXAM RM EXAM RM
PHYS ADMIN
OFFICE
EXAM RMEXAM RMEXAM RM
BREAK RM
STORAGE
VESTIBULE
STAIR
STORAGE
SOILED
BIO-WASTE
SUPPLYCAST / EXAM RMLOCKER
CORRIDOR
CORRIDOR
STAIR - E
CORRIDOR
TEL
CHUTE
SOILED LINEN
STAIR
FIRE
ALARM
STORAGE
ELECTRICAL EQUIP
STORAGE
CRAWL SPACE
EMERGENCY GENERATOR
PUMP RM
COOLER
BLUE RM
LAB
CORRIDOR
OXYGEN
STORAGE
STORAGE
HISTOLOGY
STORAGE
COMP
GAS
STORAGE
STAIR
TRASH UNIT
HISTOLOGY
OXYGEN
STORAGE
HISTOLOGY LAB
RECEPTION AREA
CORRIDOR
ELECTRICAL
CLOSET
ELEVATOR
ELEVATOR
ELEVATOR
CLEAN
SUPPLY
TOILET
ULTRASOUND SUITE
ULTRA SOUND
BREAK RM
LOCKER
ROOM
PLUMBER
OFFICE
MECH
STRECHER
WC WAITING
X-RAY - 1
X-RAY - 2LIGHT RM
X-RAY - 3
PREP RM
X-RAY - 4
X-RAY - 5
CONTROL RM
CORRIDOR
LOCKER
WAITING
STORAGE
RECOVERY RM EMS
STORAGE SUPPLY
READING RM
OFFICE
STAIR
STORAGE
VESTIBULE
COMPUTER RM
MRI SCAN RM
TOILET
RECEPTION
OFFICE
TOILET
TOILET
OFFICE
OFFICE
EXAM RMEXAM RM
ELEC CLOS
BONE DENSITOMETRY
RADIOLOGY MGR
OFFICE
LINEN RM HAC
NITROGEN
STORAGE
STORAGE
MECH
DARK ROOM
EMS STORAGE
STORAGE
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
129A
UNDER
RENOVATION
LC
EX
EXEX
1 WEST
1 NORTH
1 SOUTH 1 NORTH
EX
OPEN DOCK
OPEN DOCK
1 WEST
1 SOUTH
C106 C107
C120
C105
C103 E133A
C120
C80
C104
C120
C104A
MENS
TOILET
WOMENS
TOILET
CONFERENCE
TRAVEL OFFICE
TEL CLOS
OFFICE
OFFICE
C
9 E131
C107
E133
MENS
TOILET
PHARMACYHAC
OFFICE
B 200
B 200E
1 CENTER
1 SOUTH
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200SOC-1
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
BUSINESS OCCUPANCY
FULLY SPRINKLERED
FIRST FLOOR
BUILDING 200
N
BUILDING 200 FIRST FLOOR
270E
270E1
270F
270A
270B
270D
270C
264A
264B
262A
262B
265A
257 251
C201
C202
280A
234 240
K
233 235 237 239 241 243 245
280B
258 256
242 244
230A
ICE
ICE
UP
DN
CORRIDOR
ELEVATORELEVATORELEVATOR
SILLHTSILLHT
SILLHT
S I L
L H
T
S
I
L
L
H
T
S I L
L H
T
S
I
L
L
H
T
S I L
L H
T
S
I
L
L
H
T
S I L
L H
T
S I L
L H
T S
I L
L H
T
SILLHT SILLHT
C201A
C201B
201D201C201B 201A 203
201E 205A
205 207 209
218216214212210
206204
208C
208B
208A
283282
208D
ELECTRICAL
ELECTRICAL
VASCULAR
STORAGE
COM
CORRIDOR
STAIR-D
CORRIDOR
CORRIDOR
TEL
CLOSET
LAB MGR
OFFICE
PATHOLOGY
LAB
OFFICE OFFICE
OFFICE
LOCKER
RM
KITCHEN
BIO
SAFETY
OFFICEBLOOD
BANK
OFFICE
LAB
VEST
STORAGE
LAB
CHEMISTRY
LAB
TOILET
OFFICE
HEMATOLOGY
LAB
BLOOD DONOR
RM
OFFICE
CONFERENCE
HACTOILET
ELECTRICAL
ELEVATOR
ELEVATOR
ELEVATOR
STAIR-E
CORRIDOR
PRE
EQUIP
CLEANING
EXAM RMEXAM RMEXAM RMEXAM RMEXAM RMSTORAGE
TOILET
SUPPLY RM
HAC
VASCULAR
EXAM RM
VASCULAR
EXAM RM
STAIR-C
BREAK RM
EXAM RM
EXAM RMOFFICE
PROCEDURE RM
TOILET
PROCEDURE
RM
EXAM RM
EXAM RM
OPEN OFFICE
WAITING
EYEGLASS
STAIR-1
ELECTRICAL
STORAGE
ELECTRICAL
DIRTY
LINEN
CLEAN
LINEN
SPD
STORAGE
STORAGE
STAFF
ROOMPATIENT
BATH
STAFF
BATH
HAC ELECT
WAITING
OFFICE EXAM WAITING
TELE
HEALTH
STAFF
STORAGERECEPTION
STORAGE
WAITING
MECHANICAL
OFFICE
LAB
WAITING
STAFF MECH STAFF
EXAM EXAM
CORRIDORCORRIDOR
SHAFT
SHAFT
SHAFT
LAUNDRY
CHUTESILLHT SILLHT
2 CENTER 2 NORTH
2 SOUTH 2 CENTER
EXAM RM EXAM RM
NEW
FLOORPLAN
C204 C220
CONFERENCE
ROOM
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
B 200
B 200E
LC 2 WEST
2 CENTER
2 CENTER
2 SOUTH
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200SOC-2
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
BUSINESS OCCUPANCY
FULLY SPRINKLERED
SECOND FLOOR
BUILDING 200
N
BUILDING 200 SECOND FLOOR
KEY NOTES:
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
SZ-200-3-NORTH
SZ-200-3-SOUTH SZ-200-3-CENTER
SZ-200-3-WEST
SZ-200-3-CENTER
SZ-200-3-CENTER
TEL CLOSET
OFFICESZ-200-3-CENTER
B 200E
B 200
SZ-200E-3-CENTER
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200SOC-3
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
HEALTH CARE OCCUPANCY
FULLY SPRINKLERED
THIRD FLOOR
BUILDING 200
N
BUILDING 200 THIRD FLOOR
SUITE DESCRIPTIONS
SUITE NUMBER SUITE NAME SUITE SIZE TYPE OF SUITE EXIT NUMBER
SMOKE ZONE SQ. FT. OCCUPANCY
SMOKE ZONE SIZE
CLEAN
LINEN
ASST CHIEF CONFERENCE RM
ELECTRICAL
TOILET
STORAGE
CHASE
TELECOM
BATH
TOILET
MED RM
OFFICE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
HAC
BATH
ELEVATOR
ELEVATOR
ELEVATOR
ELECTRICAL
CARDIOLOGY
OFFICE
EXAM RM
ECG
HAC
TOILET
ECG
STRESS
TESTING
ULTRA SOUND
ECHO
CARDIOLOGY TECH
OFFICE
STAIR-D OFFICE MED SVC
CHIEF
MED SVC
OFFICE
OFFICE
EXAM RM
OFFICE
OFFICE
CHIEF
STAIR
TOILET
HAC
INFUSION OFFICE
TOILET
CHEMOTHERAPY CHEMOTHERAPY
STAIR
ONCOLOGY CARE
CO-ORDR OFFICE
INFUSION
TOILET
INFUSION
STORAGE
EXAM
NURSE
STATION
ENDOCRINOLOGYWAITING
RECEPTION
EXAM RM
ONCOLOGY
OFFICERHEUMATOLOGY
OFFICE
OFFICE
CLEAN
LINEN
TOILET
SPD STORAGE
FAMILY RM
EXAM RM
CLEAN
STORAGE
CONFERENCE RM
ELECTRICAL
OFFICE
TOILET
DRESSING
RM
EEG
ROOMOFFICE
STORAGE
STORAGE
OFFICE
ELECTRICAL
HAC
OFFICE
OUPATIENT CHEMO INFUSION SUITE
OUTPATIENT SUITE NON
SLEEPING, 4,904SF
SZ-200-4-CENTER SZ-200-4-NORTHSZ-200-4-SOUTH SZ-200-4-CENTER
VACANT
LC
SZ-200-4-WEST
SZ-200-4-CENTER
DAY ROOM
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
B 200
B 200E
SZ-200-4-CENTER
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200SOC-4
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
HEALTH CARE OCCUPANCY
FULLY SPRINKLERED
FOURTH FLOOR
BUILDING 200
N
BUILDING 200 FOURTH FLOOR
SUITE DESCRIPTIONS
SUITE NUMBER SUITE NAME SUITE SIZE TYPE OF SUITE EXIT NUMBER
ELECTRICAL
STORAGE
SOILED
LINEN
TEL
CORRIDOR
CORRIDOR
VESTIBULE
CORRIDOR
LOBBY
ELECTRICAL
ELEVATOR
ELEVATOR
ELEVATOR
MECH
RM
STAIR
X-RAY
DENTAL
OFFICE
OFFICE
OFFICE
OPERATORY
SUPPLY
STAIR
ORAL
SURGY
OPERATORY
PATIENT
TOILET
SOILED
UTILITY
CLEAN
SUPPLIES
CORRIDOR
CONFERENCE/
BREAK RM STAFF
TOILET
WOMENS
LOCKER
MENS
LOCKER
OPERATORY
STAIR
OPERATORY RESIDENT
OPERATORY
RESIDENT
OPERATORY
DENTAL
LAB
RESIDENT
OPERATORY
RESIDENT
OPERATORY
SUPPLY
CLOSET
OPERATORY
RM
OPERATORY
RMOPERATORY
PANOGRAPHY
RM
HAC
CHIEF
OFFICE
RECEPTION
LINEN
WAITING
AREA
STORAGE
ELECTRICAL
CLOSET
ELEVATOR
LOBBY
ELEVATORELEVATORELEVATOR
CLINICAL
DIETITIANS
OFFICE
STAIR-1
PROCEDURE
ROOM
PROCEDURE
ROOM
PROCEDURE
ROOM
STAIR
DRESSING
RM
DRESSING
RM
DRESSING
RM
WAITING
NURSES
STATION
CORRIDOR
CORRIDOR
SOILED
UTILITY
DECON
ROOM
TREATMENT
ROOM
CLEAN
SCOPE
DRESSING
ROOM
STORAGE
OFFICE MECH
EXAM
LOUNGE
OFFICE
BATH
RECOVERY
BATH
SHAFTSHAFT
STORAGE
BATH
SZ-200-5 SOUTH 5 NORTH
AMBULATORY
HEALTHCARE
OCCUPANCY
BUSINESS
OCCUPANCY
5 WEST
5 NORTH
LC
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200SOC-5
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
MIXED OCCUPANCY
FULLY SPRINKLERED
FIFTH FLOOR
BUILDING 200
N
BUILDING 200 FIFTH FLOOR
SUITE DESCRIPTIONS
SUITE NUMBER SUITE NAME SUITE SIZE TYPE OF SUITE EXIT NUMBER
ROOF
ROOF ROOF
SILLHTSILLHTSILLHT
636 637
604 606
608600
601A
627 621
620A
HAC
613615
644 632
SILLH
T
SOILED
UTILITY
ELECTRICAL
ELECTRICAL
STORAGE
CORRIDOR
CORRIDOR
CORRIDOR
GI
GASTROENTEROLOGY
OFFICE
SLEEP
LAB
CORRIDOR
CORRIDOR
AHU
(MECH)
WAITING
HAC
PULM
OFFICE
ELEVATORELEVATORELEVATOR
RECEPTION EXAM
RM
OFFICE EXAM
RM
EXAM
RM
EXAM
RM
APNEA
CLINIC
PFT
LAB
STORAGE
GI
EXAM
RM
SUPPLY
EXAM RMEXAM
RM
TOILETSTAIR-E
IT
CLOSET
TOILET
RESP
OFFICE
PULMONOLOGIST
DOCTOR
OFFICE
OFFICE
PULMONOLOGIST
DOCTOR
OFFICE
DIRTY
EQUIP
ELEVATOR
ELEVATOR
ELEVATOR
EQUIP
STORAGE
CLEAN
SUPPLY
SLEEP CONTROL
RM
MECH RM
TOILET
STAIR
GI EXAM RM
CHIEF
GASTROENTEROLOGY
(GI)
STAIR
SLEEP
LAB
TOILET
TOILET
SLEEP
LAB
SLEEP
LAB
TOILET
TOILET
SLEEP
LAB
CORRIDOR
SHAFTSHAFT
CHUTE
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
6 CENTER 6 NORTH6 SOUTH 6 CENTER
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200SOC-6
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
BUSINESS OCCUPANCY
FULLY SPRINKLERED
SIXTH FLOOR
BUILDING 200
N
BUILDING 200 SIXTH FLOOR
ELECTRICAL
ELECTRICAL
CLOSET
CORRIDOR
CTR CANCER
REGISTRAR
OFFICE
TOILET
TOILET
ON-CALL RM
TOILET
SOCIAL
WORKER
OFFICE
CORRIDOR
CORRIDOR
PROSTHETICS
FITTING RM
PROSTHETICS
CLINIC
STAIR
TOILET
WAITING
OFFICE
ELEVATOR
ELEVATOR
ELEVATOR
CHECK-IN
SUPPLY
OFFICE
OFFICE
OFFICE
CLOSET
ELEVATOR MACH RM
LAB PROS
STAIR-1
HAC
CLOSET
CHUTE
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
7 EAST
7 WEST
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200SOC-7
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
BUSINESS OCCUPANCY
FULLY SPRINKLERED
SEVENTH FLOOR
BUILDING 200
N
BUILDING 200 SEVENTH FLOOR
ROOF
ROOF
MECH
MECH
STAIR
ELEVATOR
MACH RM
DN
UP
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200SOC-8
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
INDUSTRIAL OCCUPANCY
FULLY SPRINKLERED
PENTHOUSE FLOOR
BUILDING 200
N
BUILDING 200 PENTHOUSE FLOOR
FEMALE TOILET
CLOSET
TOILET
TOILET
COAT CLOSETSTORAGE
ELECTRICAL
PUMP RM
TRAVEL CASHIER
STORAGE
OFFICE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
TRIAGE
CORRIDOR
LOCKER RM
E R E R
E R
OBSER/TREAT
LIFE SUPPORT RMVESTIBULE
AMBULANCE AREA
STAIR - 2
SPD
SUPPLY RMON CALL RM
TOILET
EXAM RM
EXAM RM
OFFICE
SWITCHGEAR RM
SWITCHGEAR RM
OFFICE
OFFICE
MALE
TOILET
ELECTRICAL
HAC
TRIAGEE R OFFICE
BLOOD DRAW TOILET
SOILED
UTILITY
EXAM
EXAM RM
EXAM RMCOPY RM
OFFICE EXAM RM
EXAM RMEXAM RM
NURSE MGR
OFFICE
EXAM RM
OFFICE
OFFICE
TELE HEALTH
STORAGE
WAITING AREA
SOCIAL
WORKER
OFFICE
PATIENT SVC
ASSTS
PROCESSING
AREA
OFFICE NURSE
MGR
OFFICE
OFFICE
AGENT
CASHIER
OFFICEOFFICEOFFICE
OFFICEOFFICE
ELECTRICAL
EXAM
STORAGE
OFFICE
OFFICE OFFICE
OFFICEOFFICE
OFFICEOFFICE
EXAM RMEXAM RM
OFFICE
EXAM RMHAC
EXAM/ PHYSICIAN
EXAM RM
OFFICE
OFFICEOFFICE
COPY RM
OFFICEOFFICE
EXAM RM
VOLUNTARY
SVC OFFICE
TEL CLOSET
FEMALE
TOILET
VACANTHAC
MALE TOILET
OFFICE OFFICE
LOBBY
WAITING
HBA CALL CTR
CORRIDORSTAIR - 3
VAULT
PHARMACY SVC
HAC
ELECTRICALBREAK RMOFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
PHARMACY
WINDOW INPUT
OFFICE WINDOW
INPUT
OUT PATIENT
PHARMACY
MGR OFFICE
CORRIDOR
EXAM RM
STORAGE
RECEPTIONRECEPTION
CORRIDORRECEPTION
RECEPTION
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
CORRIDOR
UNDER
RENOVATION
UNDER
RENOVATION
B 200
B 200E
EX
EX
EX
EX
GROUND CENTER SZ-200E-G-NORTH
EX
GROUND SOUTH GROUND CENTER
BUSINESS
OCCUPANCY
AMBULATORY
HEALTH CARE
OCCUPANCY
GROUND CENTER
GROUND NORTH
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200ESOC-G
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
MIXED OCCUPANCY
FULLY SPRINKLERED
GROUND FLOOR
BUILDING 200E
N
200E
BUILDING 200E GROUND FLOOR
MENS
TOILET
WOMENS
TOILET
HAC
DECONTAMINATION
LOCKER RM
TOILET
TOILET
DE-IONIZED WATER
TREATMENT
PROCESSING
STORAGE
ELEC CLO
PHARMACY
DIRTY UTILITY
CLEAN UTILITY
HAC
OFFICE
LOCKER
TOILET
OFFICE
CHEMO- THERAPY
STORAGE
CORRIDOR CORRIDOR
CONFERENCE
TRAVEL OFFICE
TEL CLOS
OFFICE
CORRIDOR
STAIR 2
BREAK RM
HAC
SPD DIRTY
SPD
ETD GAS
SPD CLEAN AREA
WASHER
DISINFECTOR
EQUIPT STORAGE
AND DISPENSINGSTORAGE
ELEC CLO
DW2
OFFICE
OFFICE
EXAM RM
GENERAL SURGY
GENERAL SURGY
TOILET
EXAMOFFICE
PROCEDURE
ROOM
CORRIDOR
STORAGE
MAS SEC
GENERAL SURGY
WAITING
NUCLEAR
MEDICINE
WAITING
RECEPTIONTOILET
ELEC
HAC
HAC
TOILET
INPT
PHARMACY
MGR OFFICE
PHARMACY
TEL CLOELEC
OFFICE
STAIR 3
CLINICAL
TEACHING
CO-ORDR
OFFICE
OFFICECHIEF OFFICE
VAULT
LAB
OFFICE
PROCEDURE
ROOM
PROCEDURE
ROOM
PROCEDURE
ROOM
CONTROL
ROOM
PROCEDURE
ROOM
OFFICE
CLEAN
LINEN
SPD
STORAGE
STORAGE
READING
ELEC
LAB
LAB
CORRIDOR
CORRIDOR
OFFICE
OFFICE
OFFICE
ELEC
DUMB WAITER
UTILITY
DUMB WAITER
UTILITY
UTILITY
UTILITYUTILITY
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
OFFICE
B 200
B 200E
1 CENTER 1 NORTH1 SOUTH 1 CENTER
1 CENTER
1 SOUTH
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200ESOC-1
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
BUSINESS OCCUPANCY
FULLY SPRINKLERED
FIRST FLOOR
BUILDING 200E
N
200E
BUILDING 200E FIRST FLOOR
MENS
TOILET
WOMENS
TOILET
ELECTRICAL
SUPPLY RM
STORAGE
ELECTRICAL
CLOSET
CORRIDOR
CORRIDOR
WAITING
OT CLINIC
MECH RM
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
OFFICE
OFFICE
HAC
TEL
AUDIOLOGY
OFFICE
E N T WAITING
AREA
OFFICE
EXAM
AUDIOLOGIST
CORRIDOR
STAIR
SOUND
BOOTH
CONTROL
SOUND
BOOTH
CONTROL
BOOTH
EXAM RMEXAM RM
MICROSCOPE RM
SOILED
UTILITY
VISUAL
FIELD RM
PRE OP RM
ELECTRICAL
CLOSET
WAITING
EXAM RM
EXAM RM EXAM RM EXAM RM
EXAM RM
EXAM RM
TOILET
CORRIDOR
CONTROL
SOUND
BOOTH
AUDIOLOGY
STORAGEP T EXAM RM
AUDIO TECH
OFFICE
FEMALE
TOILET
HYDROTHERAPY OFFICE
HAC
AUDIOLOGY
TOILET
EXAM RM
STORAGE
AUDIOLOGIST
EXAM RM
CORRIDOR
STAIR-2
MECH RM
AUDIOLOGISTAUDIOLOGIST
EXAM RM
STORAGE
WOUND NURSE
PHYSICAL THERAPY CLINIC
OFFICESTORAGEO T OFFICE
OFFICE/
RECEPTION
CHIEF O T
OFFICE
OFFICE OFFICE
TECHS OFFICE A D L
KITCHEN
TOILET
EXAM RMEXAM RMEXAM RMEXAM RM
EXAM RM
MINOR SURGY
OPHTHALMOLOGY
EXAM
OFFICE
TREATMENT
ROOM
EXAM RM
CONFERENCE
ROOM
STAIR
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
2 SOUTH 2 NORTH
B200
2 CENTER
B200E
2 SOUTH
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200ESOC-2
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
BUSINESS OCCUPANCY
FULLY SPRINKLERED
SECOND FLOOR
BUILDING 200E
N
200E
BUILDING 200E SECOND FLOOR
SUITE DESCRIPTIONS
SUITE NUMBER SUITE NAME SUITE SIZE TYPE OF SUITE EXIT NUMBER
EL
EC
TR
IC
AL
R
M
OR
STORAGE
TOILET
SOILED
UTILITY
WOMENS
LOCKER RM
MENS
LOCKER
RM
TOILET
TOILET
NOURISHMENT
RM
LOCKER
TOILET
TOILET
EL
EC
TR
IC
AL
R
M
ELECTRICAL
CLEAN
UTILITY
CORRIDOR
CORRIDORCORRIDOR
CORRIDOR
MICU
SICU
CLASS RM
TEL CLOSET
TOILET
TOILET
CLEAN
LINEN
NEPHROLOGY
OFFICE
NEPHROLOGY
OFFICE
OFFICE (RENAL
CLINIC)
NEPHROLOGY
OFFICE
SURG
ADMIN
STAFF
SURGEON
STAFF
SURGEON
TREATMEN T
ROOM
STAFF
SURGEON
CHIEF
NEUROSURGERY
STAIR 2
STORAGE
STORAGE
ANEST OFFICE
SOILED
UTILITY
STORAGE
SURGICAL SVC
OR 5 OR 4
ELECTRICAL
CLOSET
HAC
STORAGE
OR 3
02/CO2
HAC
OR 2
EQUIP
OR 1
OFFICE
LOUNGE
DICTATING RM
M LOCKER RM
TOILET
F LOCKER RM
TOILET
PACU PRE OP AREA
TOILET
HAC
EXAM RM
NURSING
STATION
SUPPLY RM
ELECTRICAL RM
EXAM RM
CLEAN EQUIP
WATER
TANK
SOILED
EQUIP
SOILED
UTILITY
BREAK
CLEAN
UTILITY
WATER
TANK
HAC
DIALYSIS
ISOLATION
BED RM
LOCKER
RM
LOCKER RM
N MGR
OFFICE
CLEAN LINEN
RM
SOILED
UTILITY
CONSOLATION
RM
NURSING
STATIONSUPPLY
MED RM
BREAK
PROCEDURE RM1 BED RM1 BED RM1 BED RM
1 BED RM1 BED RM1 BED RM1 BED RM
HACSTAIR
1 BED RM
ANTE RM
1 BED RM
1 BED RM
ANTE
RM
1 BED RM
STORAGE
CORRIDOR
CORRIDOR
STAFF
SURGEON
OFFICE
CONFERENCE
ROOM
STAIR
SUITE
3,310SF
CORRIDOR
CORRIDOR
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
SZ-200E-3-SOUTH SZ-200E-3-CENTER SZ-200E-3-CENTER SZ-200E-3-NORTH
B 200
SZ-200E-3-CENTER
B 200E
SZ-200-3-CENTER
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200ESOC-3
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE
1 HOUR FIRE BARRIER HAZARDOUS ROOM ENCLOSURE
SYMBOLS LIST
HORIZONTAL EXIT
PASSAGEWAY
EXIT
EXIT PASSAGEWAY
LINEN CHUTE
TRASH CHUTE
EP
LC
TC
EX
HE
NON-RATED SMOKE BARRIER (COMMUNICATING SPACE)
EXIT STAIRWELL/PASSAGEWAY
HEALTHCARE OCCUPANCY
FULLY SPRINKLERED
THIRD FLOOR
BUILDING 200E
N
200E
BUILDING 200E THIRD FLOOR
SUITE DESCRIPTIONS
SUITE NUMBER SUITE NAME SUITE SIZE TYPE OF SUITE EXIT NUMBER
~ROOF~
~ROOF~~ROOF~
C404
E400
C402 C401
C420
C401A
MECH RM
DAY ROOM
OFFICE SERVICE
LOBBY
ELECTRCIA;L
30 ft15 ft0 ft
0 ft 25 ft 50 ft 75 ft 100 ft
B 200
B 200E
SZ-200-4-CENTER
CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT: STATEMENT OF CONDITIONS
LIFE SAFETY ASSESSMENT
590 Means Street, Suite 200 Atlanta, Georgia 30318
(404) 214-9774
1520 MAIN STREET
INDIANAPOLIS, IN 46224
(317) 486-5188
FIRE PROTECTION & CODE CONSULTANTS, L.L.C.
VISN 1 - New England Healthcare System
36C24121C0014
TOGUS VAMC
1 VA CENTER, AUGUSTA, ME 04330
APPROVED EQUIVALENCIES
1. OVERSIZED PROTECTIVE PLATES PERMITTED
ON FIRE RATED DOORS.
2. BUSINESS OCCUPANCY DEAD END CORRIDORS
PERMITTED TO EXCEED 50' FEET.
3. INTERNAL SPRINKLER PIPING CONDITION AND
OBSTRUCTION INVESTIGATION.
FP&C Project Number 3259.00
200ESOC-4
08/18/2021 AF TK/KW
AREA OPEN TO CORRIDOR WITH SMOKE DETECTION
AREA OPEN TO CORRIDOR NO SMOKE DETECTION REQUIRED
PARTITION LEGEND
2 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE ZONE BARRIER
SMOKE ZONE BARRIER
1 HOUR FIRE BARRIER
NON-RATED SMOKE ZONE PARTITION
SMOKE RESISTIVE ENCLOSURE
HEALTH CARE OCCUPANCY CORRIDORS
SUITE DESIGNATION
SMOKE RESISTIVE HAZARDOUS ROOM…