36C24119R0029-004.pdf

PDF 12 MB Posted

Attached to
631-17-004 Renovate Building 20 for Call Center
Solicitation number
36C24119R0029
Issued by

About this file

36C24119R0029 S02 00-General.pdf

View the file

Other files

File Type Posted
36C24119R0029-0002000.docx DOCX document
36C24119R0029-0002001.pdf PDF
36C24119R0029-0002002.pdf PDF
36C24119R0029-0001001.pdf PDF
36C24119R0029-0001000.docx DOCX document
36C24119R0029-001.docx DOCX document
36C24119R0029-005.pdf PDF
36C24119R0029-008.pdf PDF
36C24119R0029-002.pdf PDF
36C24119R0029-003.pdf PDF
36C24119R0029-009.pdf PDF
36C24119R0029-006.pdf PDF
36C24119R0029-010.pdf PDF
36C24119R0029-011.pdf PDF
36C24119R0029-007.pdf PDF
36C24119R0029-000.docx DOCX document
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER SHEET

& DRAWING INDEX

GI001

DSTH

NORTHAMPTON VAMC

RENOVATION OF BLDG. 20

631-17-004

BID DOCUMENTS

NO. DESCRIPTION DATE

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0506-0003

B

A

C

D

E

F

U.S. Department of Veterans Affairs

MATERIAL SYMBOLS

CONCRETE MASONRY UNITS

(CMU)

CONCRETE

BRICK

CEMENT, SAND, GROUT, PLASTER, OR

GYPSUM WALL BOARD

EARTH

STONE, GRAVEL, OR POROUS

FILL

CARPET

PLYWOOD

WOOD (FINISHED)

WOOD (ROUGH)

RIGID INSULATION

BATT. OR LOOSE INSULATION

STEEL

WOOD (BLOCKING)

PARTICLE BOARD

ARCHITECTURAL DRAWINGS SYMBOLS

MATCH LINE

ELEVATION LINE

COLUMN LINE REFERENCES

DOOR TAGS

BUILDING SECTIONS

WALL SECTIONS

ARCHITECTURAL ABBREVIATIONS

A

X-XXX

X-XXX

X-XXX

DETAIL NO

SHEET NO

DETAIL NO

SHEET NO

A

B

CENTER LINE OF GYP

BD/STUD PARTITION

(U.O.N.)

NOMINAL FACE

OF MASONRY AND CONCRETE

WALL / PARTITIONS

(U.O.N.)

CENTER LINE

OF COLUMN

(U.O.N.)

TYPICAL PLAN DIMENSIONING

NOMINAL FACE OF

EXISTING PARTITION

(U.O.N.)

B

A: Area AB: Anchor Bolt ABV: Above ACC: Access ACOUST: Acoustical ACR: Acrylic ACST: Acoustic ACT: Acoustical Tile AD: Access Door ADH: Adhesive ADJ: Adjust, Adjustable, Adjacent AFF: Above Finished Floor AGGR: Aggregate ALT: Alternate ALUM: Aluminum ANOD: Anodized AP: Access Panel APPROX: Approximate ATC: Acoustical Tile Ceiling

BDRM: Bedroom BETW: Between BF: Board Foot BIT: Bituminous BLDG: Building BLKG: Blocking BOT: Bottom BPL: Bearing Plate BRG: Bearing BRK: Brick BRZ: Bronze BS: Both Sides BSMT: Basement BUR: Built-up Roof

C/C: Center to Center CAB: Cabinet CAR: Carpet CAV: Cavity CCW: Counter Clockwise CCTV: Closed Circuit TV CEM: Cement CER: Ceramic CF: Cubic Feet CHAM: Chamfer CJ: Control Joint CK: Caulking CL: Centerline CLG: Ceiling CLKG: Caulking CLR: Clear CLR OPG: Clear Opening CMT: Ceramic Mosaic Tile CMU: Concrete Masonry Unit COL: Column CONC: Concrete CONSTR: Construction CONT: Continuous CONTR: Contractor COP: Copper CPR: Copper CPT: Carpet CT: Ceramic Tile CW: Clockwise

EA: Each EB: Expansion Bolt EE: Each End EF: Each Face EIFS: Exterior Insulation and Finish System EJ: Expansion Joint EL: Elevation, Elevator ELEC: Electrical ELEV: Elevator, Elevation ENCL: Enclosure EPDM: Ethylene Propylene Diene Monomer EQ: Equal EQUIP: Equipment EW: Each Way EXG: Existing EXH: Exhaust EXIST: Existing EXP: Exposed

GA: Gauge, Gage GALV: Galvanized GC: General Contractor GL: Glass GL BLK: Glass Block GRND: Ground GRTG: Grating GVL: Gravel GYP: Gypsum GYP BD: Gypsum Board

WINDOW TAG/LOUVER TAG

DETAIL SECTIONS

X-XXX

DETAIL NO

SHEET NO

P. LAM: Plastic Laminate PAR: Parallel PBD: Particle Board PERIM: Perimeter PERP: Perpendicular PL: Plate PLBG: Plumbing PLYWD: Plywood PLUMB: Plumbing PP: Push-Plate Operator PR: Pair PREFAB: Prefabricated PRES: Pressure PRESS: Pressure PRMLD: Premolded PRTN: Partition PSF: Pounds per square foot PSI: Pounds per square inch

PT: PAINT

PTD: Painted, Paper Towel Dispenser PTD/R: Combination Paper Towel Dispenser/Receptacle PTN: Partition

EXTERIOR ELEVATIONS

INTERIOR ELEVATIONS

DETAIL CALL OUTS

DETAIL NO0

X-XXX

DETAIL NO

SHEET NO

X-XXX2 4

SHEET NO

WALL TYPE

ROOM TAGROOM #

ROOM AREA

# PLAN/ELEVATION KEYNOTE

REVISION SYMBOL AND

CLOUD

C

D

E

F

G P

H

I

J

L

M

N

O

Q

R

S

T

DBL: Double DEG: Degree DEMO: Demolition DF: Drinking Fountain DIAG: Diagonal DIA: Diameter DIAM: Diameter DIFF: Diffuser DN: Down DR: Door DWG: Drawing DWGS: Drawings DWR: Drawer

FB: Face Brick FD: Floor drain FDC: Fire Department Connection FDN: Foundation FDTN: Foundation FE: Fire Extinguisher FEC: Fire Extinguisher Cabinet FFE: Finished Floor Elevation FF&E: Fixtures, Furnishings & Equipment FFL: Finished Floor Line FGL: Fiberglass FHC: Fire Hose Cabinet FIN: Finish, finished FIXT: Fixture

HDCP: Handicapped (better called "Accessible") HDW: Hardware HDWD: Hardwood HGT: Height HM: Hollow Metal HORIZ: Horizontal HR: Hour HWD: Hardwood

ID: Inside Diameter IN: Inch INCL: Include INFO: Information INSTL: Install INSUL: Insulation INT: Interior INTERM: Intermediate

JAN: Janitor JC: Janitor's Closet JT: Joint

FINISH KEYNOTE

LAB: Laboratory, Labor LAV: Lavatory LB: Pound (weight) LBL: Label LINO: Linoleum LNTL: Lintel

MAINT: Maintenance MAN; Manual MAR: Marble MARB: Marble MAS: Masonry MAT: Material MATL: Material MAX: Maximum MECH: Mechanical MEMB: Membrane MFD: Manufactured MFG: Manufacturer, Manufacturing MFR: Manufacture, Manufacturer MI: Malleable Iron, Miles MIKE: Microphone MIN: Minimum MIR: Mirror MISC: Miscellaneous MK: Mark ML&P: Metal Lath & Plaster MLD: Molding MLDG: Molding MM: Millimeter MMB: Membrane MO: Masonry Opening MOD: Module MONO: Monolithic MOV: Movable MP: Metal Acoustal Panel MPS: Medium Pressure Steam MR: Mop Receptor MRD: Metal Roof Deck MT: Mount, Mounted MTD: Mounted MTL: Material, Metal MTR: Motor MUL: Mullion MULL: Mullion MV: Mercury Vapor MWP: Maximum Working Pressure MWK: Millwork

N: North, Nitrogen NAP: Napkin NAT: Natural NATL: Natural NB: "Nota Bene" Latin phrase for "Take Special Note" NC: Normally Closed, Noise Criteria NEC: National Electrical Code NEUT: Neutral NF: Near Face NFWH: Non-freeze Wall Hydrant NI: Nickel NIC: Not In Contract NK: Neck NMT: Non-Metallic NO: Number, Normally Open NOM: Nominal NR: Noise Reduction NRC: Noise Reduction Coefficient NTS: Not To Scale

OB: Obscure OBS: Obscure OC: On Center OD: Outside Diameter OF: Outside Face OFF: Office OH: Overhead OHD: Overhead Door OPNG: Opening OPP: Opposite OPP H: Opposite Hand

QUAL: Quality QT: Quarry Tile, Quart QTY: Quantity

RB: Rubber Base RCP: Reflected Ceiling Plan RD: Roof Drain, Round, Receptacle Distribution Panel REBAR: Reinforcing Bar REF: Refer, Reference, Refrigerator REFL: Reflected, REFR: Refrigerate, Refrigerator REINF: Reinforcement, or Reinforce REQD: Required RESIL: Resilient RF: Roof RGH: Rough RGH OPNG: Rough Opening RO: Rough Opening RT: Rubber Tile

SALV: Salvage SCHED: Schedule SF: Square Foot SHR: Shower SHT: Sheet SPEC: Specification, Specifications SPECS: Specifications SQ: Square SS: Stainless Steel STC: Sound Transmission Class STD: Standard STL: Steel STOR: Storage STRT: Straight STRUC: Structural STRUCT: Structural SUR: Surface SUSP: Suspended, Suspend

T&B: Top and Bottom T&G: Tongue & Groove TB: Towel Bar TD: Trench Drain TERR: Terrazzo THK: Thick, Thickness THRU: Through TLT: Toilet TPD: Toilet paper Dispenser TPH: Toilet Paper Holder TPTN: Toilet Partition TYP: Typical TZ: Terrazzo

UNFIN: Unfinished UNO: Unless Noted Otherwise UON: Unless Otherwise Noted UP: Unpainted UR: Urinal

VAT: Vinyl Asbestos Tile VBC: Vinyl Base (Coved) VCT: Vinyl Composition Tile VERT: Vertical VEST: Vestibule VIF: Verify In the Field VT: Vinyl Tile VTR: Vent Through Roof VWC: Vinyl Wall Covering

W/: With W/O: Without WAINS: Wainscot WC: Watercloset WD: Wood

U

V

W

A101

SIM

CS12.0b

W-

ROOM NAME

150 SF

XXX

F FL: Floor FLR: Floor FO: Finished Opening FOF: Face of Finish FOS: Face of Studs FP: Fireproof FRT: Fire Retardant FT: Foot, Feet, FTG: Footing, Fitting FURN: Furnish, Furniture FURR: Furring

X-XXX

DETAIL NO

SHEET NO

UNLESS OTHERWISE NOTED, ALL MASONRY DIMENSIONING IS NOMINAL TO FACE OF MASONRY, ALL

NON-MASONRY DIMENSIONING IS TO CENTER OF PARTITIONS OR WALLS AND ALL CONCRETE

DIMENSIONING IS FACE TO FACE OF WALL.

PROVIDE CONCEALED BLOCKING IN ALL STUD PARTITIONS AND WALLS BEHIND SURFACE FOR SEMI-

RECESSED, FULLY RECESSED OR SURFACE MOUNTED ACCESSORIES AND MILLWORK.

DIMENSIONS NOTED AS “CLEAR” ARE TO FINISHED SURFACE AND ARE CRITICAL FOR ACCESSIBILITY

REQUIREMENTS OR BUILT-IN FURNISHINGS.

CONTRACTOR SHALL FIELD VERIFY FINISHED DIMENSIONS AND CLEARANCES IN SPACES INDICATED TO

RECEIVE BUILT-IN FURNISHINGS OR CASEWORK PRIOR TO FABRICATION.

ALL VERTICAL CONCRETE SURFACES WHICH WILL BE EXPOSED TO VIEW UPON COMPLETION OF WORK

SHALL RECEIVE A SMOOTH RUBBED FINISH.

ALL ENDS OF MASONRY WALLS THAT WILL BE EXPOSED TO VIEW UPON COMPLETION OF WORK SHALL

BE PLAIN END UNITS.

FINISHED DOOR OPENINGS SHALL BE NOMINAL 6” FROM FINISHED CORNER OF ROOM EXCEPT WHERE

DIMENSIONED OTHERWISE.

SEALANT SHALL BE PROVIDED AT THE INTERIOR AND EXTERIOR PERIMETER OF ALL WINDOWS, DOOR

FRAMES, LOUVERS OR OTHER ITEMS INSERTED IN AN EXTERIOR WALL.

SUSPENDED GRID CEILINGS SHALL BE ARRANGED SO THAT A GRID IS SPACED EQUALLY FROM EACH

MOST REMOTE WALL, IN EACH DIRECTION, WITH NO TILES LESS THAN 6” UNLESS OTHERWISE

INDICATED.

WOOD USED FOR BLOCKING OR OTHER PURPOSES ON OR ABOVE THE ROOF DECK, WITHIN 2'-0” OF

GRADE AND IN OTHER LOCATIONS OUTSIDE THE BUILDING ENVELOPE WHERE EXPOSED TO THE

WEATHER SHALL BE PRESSURE TREATED LUMBER OR PLYWOOD.

INSTALL ALL WORK AS INDICATED AND VERIFY EXACT LOCATION AND ELEVATIONS ON THE JOB.

DO NOT SCALE DRAWINGS. REFER TO DIMENSIONS AND SPECIFIED MATERIALS. CONTACT THE

ARCHITECT IF ADDITIONAL DIMENSIONS ARE REQUIRED.

COORDINATE ALL DOOR HARDWARE, TRIM AND FINISHES TO MEET INTENT AND COMPLIANCE.

FIRST FLOOR LEVEL DATUM ELEVATION (0'-0") IS EQUAL TO ACTUAL

ELEVATION (383'-0"). ARCHITECTURAL ELEVATIONS U.O.N. ARE TAKEN FROM FINISHED FIRST FLOOR

LEVEL DATUM ELEVATION (0'-0").

INTERIOR WALL AND CEILING FINISH MINIMAL REQUIREMENTS (FINISH CLASSIFICATIONS IN

ACCORDANCE WITH ASTM E84) ARE AS FOLLOWS:

VERTICAL EXITS AND EXIT PASSAGEWAYS - CLASS B

EXIT ACCESS CORRIDORS AND OTHER EXITWAYS - CLASS C

ROOMS AND ENCLOSED SPACES - CLASS C

GENERAL ARCHITECTURAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

OVERHEAD

VISIBLE ITEMS

BREAK LINE

HIDDEN OR NOT IN CONTRACT

CENTER LINE OR COLUMN GRID

C.M.U. WALL / PARTITION - SEE PARTITION TYPES

EXISTING WALL CONSTRUCTION

METAL STUD PARTITION - SEE PARTITION TYPES

WALL/ PARTITION DESIGNATIONS

BRICK FACE

LINE TYPES

GRAB BAR

AT REAR OF TOILET

(SURFACE MTD.)

GRAB BAR

TO SIDE OF TOILET

(SURFACE MTD.)

WALL-MOUNTED

TOILET

NOTE: FLUSH CONTROLS

FOR THE TOILET SHALL BE

MOUNTED ON THE OPEN

SIDE OF THE TOILET AREA

NO MORE THAN 44" A.F.F.

LIQUID SOAP DISPENSER

TOUCH FREE DISPENSER

(SURFACE MTD.)

O R

A B

O V

E

C O

U N

TE

R

PAPER TOWEL DISPENSER

(SURFACE MTD.)

ACCESSIBLE

TOILET ROOM DOOR

PROVIDE SIGNAGE (MIN

LETTER HEIGHT 1 1/4") CODE

REQUIREMENTS. "TACTILE"

PER ADA & SYMBOL

COMPLIANCE. REFER TO

SIGNAGE DWGS. FOR

SIGNAGE TYPE.

MIRROR

(SURFACE MTD.)

WALL-MOUNTED

LAVATORY

WRIST BLADE TYPE

HANDLES. SEE PLUMBING

DRAWINGS FOR FIXTURE

AND HARDWARE

SPECIFICATIONS

PROTECT

PIPES

VARIES

SANITARY NAPKIN

DISPOSAL

(SURFACE MTD.)

MOP AND BROOM

HOLDER

(SURFACE MTD.)

6' -0

TOILET SEAT COVER

DISPENSER

(SURFACE MTD.)

GRAB BAR IN

FOREGROUND

FIRE

EXTINGUISHER

CABINET

(RECESSED)

HEIGHT OF FIRE

EXTINGUISHER

OPERATING

MECHANISM AT

48" A.F.F. MAX.

TOILET TISSUE

DISPENSER

(SURFACE MTD.)

39"-41"

12" MAX. 42" MIN.

1' -6

1'-6" 1'-6"

CL CL

16" - 18"

54" MIN.

M A

X.

T

O B

O

TT

M

F R

EF

LE

C

TI

V E

S U

R

FA

C E

2' -9

3' -4

2' -1

0"

1' -8

4' -0

2' -5

" 4' -0

4' -0

FINISH FLOOR

FINISH FLOOR 17

1' -8

5' -0

4' -0

GLOVE HOLDER

(SURFACE MTD.)

SHARPS DISPOSAL

(SURFACE MTD.)

7' -6

CLOCK

(SURFACE MTD.)

CL

3' -7

36" MIN.

4' -0

SHOWER CONTROLS

(SURFACE MTD.)

O R

A B

O

U N

TE

R

TO

P

O

IN

T O

F D

IS

P

O S

A L

COAT HOOKS

(SURFACE MTD.)

4' -0

" 5' -1

0"

O R

A B

O

U N

TE

R

7"-9"

4' -0

NURSE CALL

(SURFACE MTD.)

THERMOSTAT

(SURFACE MTD.)

4' -0

*NOTE: 24" MIN. APPLIES WHERE WALL

SPACE IS PROVIDED. OTHERWISE 12"

MIN. WHERE RECESSED FIXTURE

IS ADJACENT.

12" MIN. 24" MIN.*

36" MIN.

3' - 6"

4'

M A

X.

WATER BOTTLE FILLER

(SURFACE MTD.)

www.chacompanies.com

Powers Building, 16 West Main Street, Suite 830

Main: (585) 262-2640

Rochester, NY 14614-1607

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0084

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER. NORTHAMPTON VAMC

RENOVATION OF BLDG. 20

LEEDS, MASSACHUSETTS

631-17-004

20A Se rv ic e D i s a b l e d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

U.S. Department of Veterans Affairs

C U s e rs \A

B ra d fo rd \D o c u m e n ts \R e v it L o c a l F ile s \2

N o rt h a m p to n V

A M

C B ld g

A rc h a b ra d fo rd .r v t

09-21-2018 Checker Author

G-002

NOTES, SYMBOLS & ABBREVIATIONS

BID DOCUMENTS

GENERAL

G-002 NOTES, SYMBOLS & ABBREVIATIONS

G-003 BASEMENT & FIRST FLOOR CODE COMPLIANCE PLANS

G-004 SECOND & ATTIC FLOOR CODE COMPLIANCE PLAN

ARCHITECTURAL

A-002 PARTITION TYPES

A-010 BASEMENT & FIRST FLOOR DEMOLITION PLAN

A-011 SECOND FLOOR & ATTIC DEMOLITION PLAN

A-012 ROOF & ENLARGED DEMOLITION PLANS

A-100 ARCHITECTURAL SITE PLAN

A-101 OVERALL BASEMENT & FIRST FLOOR PLAN

A-102 OVERALL SECOND FLOOR PLAN & ATTIC PLAN

A-103 ROOF PLAN & ROOF DETAILS

A-110 BASEMENT & FIRST FLOOR REFLECTED CEILING PLANS

A-111 SECOND FLOOR & ATTIC REFLECTED CEILING PLAN & CEILING DETAILS

A-201 PARTIAL EXTERIOR ELEVATIONS

A-301 BUILDING SECTIONS

A-310 WALL SECTIONS AND DETAILS

A-401 ENLARGED BASEMENT PLAN - AREA A

A-402 ENLARGED BASEMENT PLAN - AREA B

A-403 ENLARGED FIRST FLOOR PLAN - AREA A

A-404 ENLARGED FIRST FLOOR PLAN - AREA B

A-405 ENLARGED SECOND FLOOR PLAN - AREA A

A-406 ENLARGED SECOND FLOOR PLAN - AREA B

A-410 ELEVATOR PLANS, SECTIONS, & DETAILS

A-411 STAIR PLANS, SECTION, & DETAILS

A-501 INTERIOR ELEVATIONS

A-502 INTERIOR ELEVATIONS

A-503 INTERIOR ELEVATIONS

A-601 DOOR SCHEDULE & DETAILS

A-602 WINDOW TYPES & DETAILS

A-701 MILLWORK DETAILS

A-702 PLAN & MISCELLANEOUS DETAILS

INTERIORS

I-001 FINISH LEGEND, SIGNAGE SCHEDULE, AND INTERIOR DETAILS

I-101 BASEMENT FINISH PLAN

I-102 FIRST FLOOR FINISH PLAN

I-103 SECOND FLOOR FINISH PLAN

I-301 BASEMENT FURNITURE & EQUIPMENT PLAN

I-302 FIRST FLOOR FURNITURE & EQUIPMENT PLAN

I-303 SECOND FLOOR FURNITURE & EQUIPMENT PLAN

ARCH. SHEET LIST

TYP. MOUNTING HEIGHTS

1HR 1HR1HR 1HR

2HR 2HR2HR 2HR

SP SPSP SP

(E)1HR (E)1HR(E)1HR (E)1HR

UP

UP

UP

UP

UP

1HR 1HR

H

R

H R

H

R

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

1HR 1HR

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

2HR 2HR

H

R

H R

H

R

H R

2HR 2HR

S P

S P

1HR 1HR

H

R

H R

1HR 1HR1HR 1HR 1HR 1HR

H

R

H R

H

R

H

R

H R

H

R

S P

S P

H

R

H R

H

R

H R

S P

S P

S P

SP SP

S P

S P

S P

S P

SP SPSP SP

S P

S P

S P

S P

DN DN

DN

DN

UP UP

2HR 2HR

H

R

H R

H

R

H R

2HR 2HR

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

1HR 1HR

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

H

R

H R

H

R

H R

2HR2HR

H

R

H R

H

R

H R

2HR2HR

S P

S P

S P

S P

H

R

H R

H

R

H R

2HR2HR

2HR2HR 2

H

R

H R

H

R

H R

1HR 1HR

H

R

H R

H

R

H R

2HR2HR

H

R

H R

H

R

H R

H

R

H R

H

R

H R

2HR2HR

EXIT DISCHARGE

TRAVEL DISTANCE AND DIRECTION OF TRAVEL

COMMON PATH OF EGRESS

REMOTE POINT OF TRAVEL

XX'-XX"

EXIT

EXITE

FIRE EXTINGUISHER CABINET

(1 PER 75 FT RADIUS)

FX

1 HOUR FIRE RATED ASSEMBLY

2 HOUR FIRE RATED ASSEMBLY

SMOKE PARTITION - NON-FIRE RATED

ASSEMBLY DESIGNED AND CONSTRUCTED TO

LIMIT THE PASSAGE OF SMOKE

50 x 0.2" 10" (32")

OCCUPANT LOAD AT EXIT

MIN. WIDTH PER OCCUPANT

MIN. CODE EXIT WIDTH

MIN. CALCULATED EXIT WIDTH

EXISTING WALL - PRESUMED 1 HOUR FIRE

RATED ASSEMBLY

EXIT SIGN

64 SF

TOILET

123 SF

VEST.

279 SF

MECH.

ELEVATOR

100 SF

IT

OCC. LOAD

362 SF

CONFERENCE

RM

165 SF

SHARED

OFFICE - ENG.

100 SF

OFFICE - ENG.

94 SF

OFFICE -

SAFETY

OCC. LOAD

221 SF

STAFF LOUNGE

100 SF

OFFICE -

CLINICAL

ENG.

19 x 0.3" 5.7" (32")

48 x 0.2" 9.6" (32")

582 SF

OFFICE /

WORK AREA-

SAFETY

425 SF

CORR.

93 SF

ELEV. VEST.

359 SF

CORR.

20 x 0.2" 4" (32")

18 x 0.3" 5.4" (32")

81 x 0.3" 24.3" (32")

102 x 0.3" 30.6" (32")

E E

E

E

190 SF

SHARED

OFFICE - ENG.

106 SF

OFFICE - ENG.

180 SF

SHARED

OFFICE - ENG.

201 SF

INTERIOR

DESIGNER

123 SF

OFFICE - ENG.

240 SF

PLANS ROOM

/ STORAGE

91 SF

ELEV.

MACHINE RM

36 SF

CLOSET

155 SF

SHARED

OFFICE - ENG.

47 SF

JAN.

102 SF

ELEC.

96 SF

FILE STOR.

OCC. LOAD

153 SF

CONFERENCE

RM

101 SF

OFFICE

100 SF

OFFICE

99 SF

OFFICE

96 SF

OFFICE

195 SF

WORK AREA /

COPIER

96'-2"

EXIST

STAIR

EXIST

STAIR

90 SF

VESTIBULE

143 SF

CORR.

64 SF

TOILET

53 SF

TOILET

OCC. LOAD

49 SF

WAITING

EXIT

FX

FX

FX C

LE

A R

5'

CLEAR

5' - 3 1/2"

CLEAR

6' - 2"

ELEVATOR

OCC. LOAD

360 SF

CONFERENCE

RM

358 SF

OFFICE - PIV

239 SF

STAFF

LOUNGE

21 x 0.3" 6.3" (32")

38 x 0.2" 7.6" (32")

44 x 0.3" 13.2" (32")

121 SF

OFFICE - HR

164 SF

SHARED

OFFICE - HR

OCC. LOAD

194 SF

WAITING

158 SF

ELEC. / IT

301 SF

SHARED

OFFICE - HR

146 SF

WORK RM /

COPIER

101 SF

OFFICE - HR

168 SF

SHARED

OFFICE - HR

153 SF

SHARED

OFFICE - HR

153 SF

SHARED

OFFICE - HR

159 SF

SHARED

OFFICE - HR

63 SF

JAN.

174 SF

SHARED

OFFICE -

CONTRACTING

157 SF

SHARED

OFFICE -

CONTRACTING

156 SF

SHARED

OFFICE -

CONTRACTING

170 SF

SHARED

OFFICE -

CONTRACTING

101 SF

OFFICE -

LEGAL

222 SF

WORK RM /

COPIER

100 SF

OFFICE -

LEGAL

96 SF

OFFICE -

LEGAL

114 SF

WORK RM /

COPIER

123115 SF

OFFICE -

CONTRACT

EXIST

STAIR

EXIST

STAIR

448 SF

CORR.

145 SF

CORR.

10451 SF

TOILET

57 SF

TOILET

52 SF

ELEV. VEST.

90 SF

VESTIBULE

48 SF

TOILET

376 SF

CORR.

23'-7"

E

EXIT

FXFX C

LE

A R

5'

99 SF

OFFICE - HR

FX

CODE REVIEW INFORMATION

2015 INTERNATIONAL BUILDING CODE & NFPA 101 LIFE SAFETY CODE 2015

BUILDING DATA FIRE RESISTANCE RATINGS

ICC REQ'D NFPA REQ'D PROVIDED

USE DESCRIPTION

OCCUPANCY

ICC CH. 3

NFPA 6.1.1

CLASSIFICATION OF WORK NFPA 4.6.7

CONSTRUCTION TYPE

ICC CH. 6

NFPA TABLE A.8.2.1.2

NO. OF STORIES

BUILDING HEIGHT

ICC CH. 5

NFPA TABLE

AUTOMATIC SPRINKLER SYSTEM

ICC CH. 9

NFPA 9.7.1

ALLOWABLE BUILDING AREA (At) ICC TABLE 506.2

INCREASE FOR FRONTAGE (If) ICC CH. 5

TOTAL ALLOWABLE BUILDING AREA (Aa) ICC CH. 5

SF

SF

TOTAL GROSS BUILDING AREA ICC CH. 5

NUMBER OF OCCUPANTS

ICC TABLE 1004.1.2

NFPA TABLE 7.3.1.2

SEE OCCUPANCY

CALCULATION BELOW

MIN. NUMBER OF EXITS ICC TABLE 1006.3.1

NFPA 7.4.1.2

MIN. EXIT WIDTH PER OCCUPANT ICC 1006.3.1

NFPA 7.4.1.2

PER OCC. PER OCC.

x

MIN. DOOR WIDTH ICC 1010.1.1

NFPA 7.2.1.2.3.2 / 18.2.3.6

COMPLIES

MIN. STAIRWAY WIDTH

ICC 1011.2

NFPA 7.2.2.2

COMPLIES

MIN. CORRIDOR WIDTH

ICC 1020.2

NFPA 7.3.4.1

COMPLIES

MAX. TRAVEL DISTANCE

ICC TABLE 1017.2

NFPA TABLE A.7.6 COMPLIES

MAX. COMMON

PATH OF TRAVEL

ICC TABLE 1006.2.1

NFPA TABLE A.7.6 COMPLIES

MAX. DEAD END CORRIDOR

ICC 1020.4

NFPA TABLE A.7.6 COMPLIES

ICC 718

NFPA 8.6.11

CONCEALED SPACE

DRAFTSTOPPING

SMOKE COMPARTMENT ICC 407.5 / NFPA 18.3.7.1

INTERIOR FINISHES CLASS

INTERIOR EXIT STAIRWAYS AND RAMPS AND

EXIT PASSAGEWAYS

ICC TABLE 803.11

CORRIDORS AND ENCLOSURE FOR EXIT ACCESS

STAIRWAYS AND RAMPS

ROOMS AND ENCLOSED SPACES

COMPLIES

COMPLIES

COMPLIES

ICC TABLE 906.3

NFPA 9.9

FIRE EXTINGUISHER SPACING COMPLIES

STANDPIPE SYSTEM

ICC 905.3.1

NFPA 9.10

COMPLIES

SMOKE AND FIRE DETECTION

ICC 907.2

NFPA 9.6

COMPLIES

FIRE ALARM SYSTEM

ICC 907.2

NFPA 9.6 COMPLIES

VERTICAL ACCESS REQUIRED ICC 1104.4 COMPLIES

ACCESSIBLE ENTRANCE ICC 1105.1 COMPLIES

PASSENGER LOADING ZONES ICC 1106.7

BUILDING ELEMENT TABLE ICC REQ'D NFPA REQ'D PROVIDED

PRIMARY STRUCTURAL FRAME

EXTERIOR BEARING WALLS

SUPPORTING MORE THAN ONE FLOOR,

COLUMNS , OR OTHER BEARING WALLS

SUPPORTING ONE FLOOR ONLY

SUPPORTING A ROOF ONLY

INTERIOR BEARING WALLS

SUPPORTING MORE THAN ONE FLOOR,

COLUMNS , OR OTHER BEARING WALLS

SUPPORTING ONE FLOOR ONLY

SUPPORTING A ROOF ONLY

COLUMNS

SUPPORTING MORE THAN ONE FLOOR,

COLUMNS , OR OTHER BEARING WALLS

SUPPORTING ONE FLOOR ONLY

SUPPORTING A ROOF ONLY

BEAMS, GIRDERS, TRUSSES, AND ARCHES

SUPPORTING MORE THAN ONE FLOOR,

COLUMNS , OR OTHER BEARING WALLS

SUPPORTING ONE FLOOR ONLY

SUPPORTING A ROOF ONLY

FLOOR-CEILING ASSEMBLIES

ROOF-CEILING ASSEMBLIES

INTERIOR NON-BEARING WALLS

EXTERIOR NON-BEARING WALLS

FLOOR CONSTRUCTION AND

ASSOCIATED SECONDARY MEMBERS

ROOF CONSTRUCTION AND

ASSOCIATED SECONDARY MEMBERS

ABBREVIATIONS:

N/A

NC

C

NR

B

NOT APPLICABLE / NOT PART OF THIS PROJECT

NON-COMBUSTIBLE

COMBUSTIBLE

NOT REQUIRED

BARRIER TO LIMIT TRANSFER OF SMOKE

STRUCTURAL DESIGN:

REFER TO SPECIFIC DRAWING AND

SPECIFICATION SECTIONS FOR ADDITIONAL

STRUCTURAL DESIGN CRITERIA INCLUDING BUT

NOT LIMITED TO, LIVE LOAD, DEAD LOAD, AND

LATERAL LOADS APPLICABLE TO THIS PROJECT.

NOTES:

FIRE WALLS

ICC TABLE 601

NFPA TABLE A.8.2.1.2

ICC TABLE 706.4

FIRE BARRIERS ICC TABLE 707.3.10

VERTICAL EXIT ENCLOSURE

ICC 1023

NFPA 7.1.3.2

FIRE PARTITIONS ICC 708

EXIT PASSAGEWAY

ICC 1024

NFPA 7.1.3.2

HORIZONTAL EXIT

SEPARATION

ICC 1026

NFPA 7.2.4

INCIDENTAL USE

AREAS

ICC 509

NFPA 18.3.2.1

OCCUPANCY

SEPARATION

ICC 508

NFPA TABLE 6.1.14.4.1

SHAFT ENCLOSURE ICC 713.4

NFPA TABLE 8.3.4.2

CORRIDOR WALLS

ICC TABLE 1020.1

NFPA 18.3.6.1

SMOKE BARRIERS

ICC 709.3

NFPA 18.3.7

FIRE PROOFING ASSEMBLIES: BEAMS, COLUMNS, FLOOR SYS. ROOF SYS.

CONTRACTOR TO VERIFY /

MAINTAIN / PATCH ANY

AND ALL AREAS OF

FIREPROOFING OR UL

ASSEMBLIES WITHIN

SCOPE OF WORK

COMPLIES

COMPLIES

COMPLIES

(REFER TO CODE PLAN)

(REFER TO CODE PLAN)

(REFER TO CODE PLAN)

0.346421

50903

2 2

21.68

OFFICE OFFICE

'B' BUSINESS BUSINESS

CHANGE OF USE

TYPE V-B TYPE V [000]

MAINTAIN

EXISTING

38.1.6 60'

N/A

N/A

44'-6"

YES

27000

22708 SF

0.3 0.3

0.3 289

32" 32"

44" 44"

44" 44"

300' 300'

100' 100'

50' 50'

NR NR NR

N/A N/A N/A

CLASS B

CLASS C

CLASS C

1/3,000 SF

75'

1/3,000 SF

75'

NO NO

YES YES

YES YES

YES

YES

NO

0 EXISTING

EXISTING

EXISTING

N/A

N/A

EXISTING

EXISTING

N/A

N/A

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

2 2

1 1

1 1

EXISTING

COMPLIES

1 1 N/A

2 1 N/A

1 1

SEE CODE

PLAN

N/A N/A N/A

2 2 2

0 0 0

1 1 N/A

NO NO

-ACCESSIBLE MEANS OF EGRESS ARE NOT REQUIRED TO BE PROVIDED IN

EXISTING BUILDINGS (ICC 1009.1)

-REFER TO CODE COMPLIANCE PLAN FOR ADDITIONAL INFORMATION ON

EGRESS, PARTITION RATINGS AND OTHER CODE RELATED INFORMATION.

MIN. NUMBER OF REQUIRED PLUMBING

FIXTURES (ICC TABLE 2902.1)

TOTAL OCCUPANTS:

WATER CLOSETS:

REQUIRED: 1:25(FIRST 50) 1:50 (REMAINING)=

PROVIDED =

LAVATORIES:

REQUIRED: 1:40 (FIRST 80) 1:80 (REMAINING) =

PROVIDED =

DRINKING FOUNTAINS:

REQUIRED: 1:100 =

PROVIDED =

SERVICE SINKS:

REQUIRED =

PROVIDED =

ACCESSIBLE ROUTE:

PATIENT CARE AREA WIDTH

ADMINISTRATIVE AREA WIDTH

MAX. SLOPE

MIN. GRADIENT OF WALK

REQUIRING REST AREA EVERY 200'

TURNING RADIUS

TURNING RADIUS, BARIATRIC

FLOOR SURFACES:

CHANGES IN LEVEL

CARPET CUSHION OR PADDING

PARKING AND PASSENGER

LOADING ZONES:

ACCESS AISLE REQUIREMENT FOR

ACCESSIBLE PARKING SPACES

PASSENGER LOADING AREA

SUPPLEMENT TO THE ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)

MINIMUM REQUIREMENTS

ACCESSIBLE PARKING SPACES

SCI/D FACILITIES

HOSPITAL OUTPATIENT FACILITIES

REHABILITATION AND OUTPATIENT

PHYSICAL THERAPY FACILITIES

BUILDINGS - ACCESSIBLE SEATING,

ASSEMBLY AREAS

1% GREATER THAN ABAAS

2% ACCESSIBLE SPACES PER INPATIENT

BED; 0.5 PER LONG-TERM CARE BED; 5.6

PER OUTPATIENT EXAM ROOM. DEDICATED

FOR SCI/D PATIENTS

10% OF TOTAL SPACES

20% OF TOTAL SPACES

20% OF TOTAL SPACES

1% GREATER THAN ABAAS

REQUIREMENT VA ABAAS

10% OF TOTAL SPACES

20% OF TOTAL SPACES

20% OF TOTAL SPACES

6'-0" 5'-0" 1:33 (3%) 1:50

5'-6" 6'-0"

3'-0" 3'-0" 1:20 (5%) 1:33

5'-0" 5'-0"

NOT PERMITTED ON SCI FLOORS

NOT PERMITTED

NO REQUIREMENT

PERMITTED

5'-0" EACH SIDE

YES

5'-0" EACH SIDE

1 PER 2 SPACES

NO REQUIREMENT

CURB RAMPS:

MIN. WIDTH 4'-0" 3'-0"

RAMPS:

MAX. SLOPE

MAX. LENGTH, (1:33-1:26)

MAX. LENGTH, (1:25-1:20)

MIN. CLEAR WIDTH

MIN. SIZE LEVEL LANDING, WHERE

DOORS SWING INTO LANDING

1:20 40' 35' 4'-0" 6'-0" X 6'-0"

1:12 200' 200' 3'-0" 5'-0" X 5'-0"

STAIRS:

HANDRAIL HEIGHT 34" 30"-34"

ELEVATORS (PASSENGER):

MIN. WIDTH OF ELEVATOR DOORS

MIN. CAR SIZE

DOUBLE SET OF HANDRAILS

4'-0"

8'-0" X 6'-2" (PLATFORM SIZE)

YES

3'-0"

68" X 51" (CAR INSIDE DIM.)

NO REQUIREMENT

DOORS AND DOORWAYS:

PATIENT CARE DELIVERY AREAS

WITH PATIENT BED, STRETCHER OR

GURNEY ACCESS, MIN. WIDTH

4'-0" 3'-8"

WINDOWS:

SILL HEIGHT IN PATIENT

BEDROOMS

24" MAX. NO REQUIREMENT

WATER CLOSETS:

GRAB BAR CONFIGURATION DOUBLE SWING-UP BARS FOR

ALL PATIENT TOILETS/SHOWER

ROOMS ON NURSING UNITS

SIDE & BACK BARS FOR ALL

ACCESSIBLE WATER CLOSETS

TOILET STALLS:

MIN. ACCESSIBLE STALL SIZE

MIN. SIZE WHEELCHAIR "FRONT

TRANSFER" STALL

GRAB BARS

5'-6" X 6'-0" 3'-6" X 6'-0"

REQUIRED IN ALL STALLS

5'-0" X 4'-8" 3'-0" X 5'-6"

REQUIRED IN ACCESSIBLE STALLS

SHOWER STALLS (PATIENT):

MIN. STALL DIMENSIONS

GRAB BARS

4'-0" X 4'-0"

HORIZONTAL PLUS VERTICAL BARS

3'-0" X 3'-0" OR 2'-6" X 5'-0"

HORIZONTAL BARS ONLY

TOILET ROOMS:

INPATIENT BEDROOM TOILET

ROOMS, MIN. WIDTH OF ENTRANCE

48" 34"

CAFETERIAS:

KNEE CLEARANCE (MIN. 5% TABLES)

CUTLERY AND SUPPLY HEIGHT

2'-3" AND 2'-5" FOR AT LEAST 5%

40" - 48"

2'-3"

54" MAX.

HEALTH CARE FACILITIES:

MED/SURG % OF ACCESSIBLE

BEDROOMS

MED/SURG % OF ACCESSIBLE

TOILETS

100%

100%

10%

10%

BASEMENT 7,207 GROSS SF

FLOOR TOTAL

GROSS AREA

NET AREA OF

ASSEMBLY USE

568 NET SF

TOTAL GROSS LESS

NET ASSEMBLY

6,639 SF

OCCUPANCY

(BUSINESS USE, 1:100)

67 OCCUPANTS

OCCUPANCY

(ASSEMBLY USE, 1:15)

38 OCCUPANTS

TOTAL OCCUPANCY

105 OCCUPANTS

FIRST FLOOR 7,013 GROSS SF 557 NET SF 6,456 SF 65 OCCUPANTS 38 OCCUPANTS 103 OCCUPANTS

SECOND FLOOR 6,708 GROSS SF 235 NET SF 6,473 SF 65 OCCUPANTS 16 OCCUPANTS 81 OCCUPANTS

TOTAL OCCUPANTS 289 OCCUPANTS

www.chacompanies.com

Powers Building, 16 West Main Street, Suite 830

Main: (585) 262-2640

Rochester, NY 14614-1607

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0084

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

PLAN

NORTH

NORTHAMPTON VAMC

RENOVATION OF BLDG. 20

LEEDS, MASSACHUSETTS

631-17-004

20A Se rv ic e D i s a b l e d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

U.S. Department of Veterans Affairs

ACTUAL

NORTH

C U s e rs \A

B ra d fo rd \D o c u m e n ts \R e v it L o c a l F ile s \2

N o rt h a m p to n V

A M

C B ld g

A rc h a b ra d fo rd .r v t

09-21-2018 Checker Author

G-003

BASEMENT & FIRST FLOOR CODE

COMPLIANCE PLANS

BID DOCUMENTS

LEGEND

SCALE: 1/8" = 1'-0"G-003

1 BASEMENT CODE COMPLIANCE PLAN

SCALE: 1/8" = 1'-0"G-003

2 FIRST FLOOR CODE COMPLIANCE PLAN

VA BARRIER FREE DESIGN STANDARDS

OCCUPANCY CALCULATION

1HR 1HR1HR 1HR

2HR 2HR2HR 2HR

SP SPSP SP

(E)1HR (E)1HR(E)1HR (E)1HR

UP

DN DN

1HR 1HR

H

R

H R

H

R

H R

1HR 1HR

H

R

H R

H

R

H R

2HR2HR

2HR2HR 2

H

R

H R

H

R

H R

H

R

H R

2HR2HR

H

R

H R

H

R

H R

1HR1HR

H

R

H R

2HR2HR

2HR 2HR

H

R

H R

H

R

H R

2HR 2HR

H

R

H R

S P

S P

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

(E )1

H R

H

R

H R

H

R

H R

2HR2HR

H

R

H R

H

R

H R

2HR2HR

H

R

H R

H

R

H R

1HR 1HR1HR S

P

S P

DN

H

R

H R

H

R

H R

2HR2HR

H

R

H R

H

R

H R

2HR2HR

H

R

H R

H

R

H R

2HR2HR

2HR2HR

H

R

H R

H

R

H R

1HR1HR

2HR2HR

2HR2HR 2

H

R

H R

H

R

H R

2HR 2HR

H

R

H R

H

R

H R

2HR 2HR

H

R

H R

H

R

H R

H

R

H R

H

R

H R

1HR 1HR

1HR1HR

H

R

H R

S P

S P

EXIT DISCHARGE

TRAVEL DISTANCE AND DIRECTION OF TRAVEL

COMMON PATH OF EGRESS

REMOTE POINT OF TRAVEL

XX'-XX"

EXIT

EXITE

FIRE EXTINGUISHER CABINET

(1 PER 75 FT RADIUS)

FX

1 HOUR FIRE RATED ASSEMBLY

2 HOUR FIRE RATED ASSEMBLY

SMOKE PARTITION - NON-FIRE RATED

ASSEMBLY DESIGNED AND CONSTRUCTED TO

LIMIT THE PASSAGE OF SMOKE

50 x 0.2" 10" (32")

OCCUPANT LOAD AT EXIT

MIN. WIDTH PER OCCUPANT

MIN. CODE EXIT WIDTH

MIN. CALCULATED EXIT WIDTH

EXISTING WALL - PRESUMED 1 HOUR FIRE

RATED ASSEMBLY

EXIT SIGN

CODE REVIEW INFORMATION

2015 INTERNATIONAL BUILDING CODE & NFPA 101 LIFE SAFETY CODE 2015

BUILDING DATA FIRE RESISTANCE RATINGS

ICC REQ'D NFPA REQ'D PROVIDED

USE DESCRIPTION

OCCUPANCY

ICC CH. 3

NFPA 6.1.1

CLASSIFICATION OF WORK NFPA 4.6.7

CONSTRUCTION TYPE

ICC CH. 6

NFPA TABLE A.8.2.1.2

NO. OF STORIES

BUILDING HEIGHT

ICC CH. 5

NFPA TABLE

AUTOMATIC SPRINKLER SYSTEM

ICC CH. 9

NFPA 9.7.1

ALLOWABLE BUILDING AREA (At) ICC TABLE 506.2

INCREASE FOR FRONTAGE (If) ICC CH. 5

TOTAL ALLOWABLE BUILDING AREA (Aa) ICC CH. 5

SF

SF

TOTAL GROSS BUILDING AREA ICC CH. 5

NUMBER OF OCCUPANTS

ICC TABLE 1004.1.2

NFPA TABLE 7.3.1.2

SEE OCCUPANCY

CALCULATION BELOW

MIN. NUMBER OF EXITS ICC TABLE 1006.3.1

NFPA 7.4.1.2

MIN. EXIT WIDTH PER OCCUPANT ICC 1006.3.1

NFPA 7.4.1.2

PER OCC. PER OCC.

x

MIN. DOOR WIDTH ICC 1010.1.1

NFPA 7.2.1.2.3.2 / 18.2.3.6

COMPLIES

MIN. STAIRWAY WIDTH

ICC 1011.2

NFPA 7.2.2.2

COMPLIES

MIN. CORRIDOR WIDTH

ICC 1020.2

NFPA 7.3.4.1

COMPLIES

MAX. TRAVEL DISTANCE

ICC TABLE 1017.2

NFPA TABLE A.7.6 COMPLIES

MAX. COMMON

PATH OF TRAVEL

ICC TABLE 1006.2.1

NFPA TABLE A.7.6 COMPLIES

MAX. DEAD END CORRIDOR

ICC 1020.4

NFPA TABLE A.7.6 COMPLIES

ICC 718

NFPA 8.6.11

CONCEALED SPACE

DRAFTSTOPPING

SMOKE COMPARTMENT ICC 407.5 / NFPA 18.3.7.1

INTERIOR FINISHES CLASS

INTERIOR EXIT STAIRWAYS AND RAMPS AND

EXIT PASSAGEWAYS

ICC TABLE 803.11

CORRIDORS AND ENCLOSURE FOR EXIT ACCESS

STAIRWAYS AND RAMPS

ROOMS AND ENCLOSED SPACES

COMPLIES

COMPLIES

COMPLIES

ICC TABLE 906.3

NFPA 9.9

FIRE EXTINGUISHER SPACING COMPLIES

STANDPIPE SYSTEM

ICC 905.3.1

NFPA 9.10

COMPLIES

SMOKE AND FIRE DETECTION

ICC 907.2

NFPA 9.6

COMPLIES

FIRE ALARM SYSTEM

ICC 907.2

NFPA 9.6 COMPLIES

VERTICAL ACCESS REQUIRED ICC 1104.4 COMPLIES

ACCESSIBLE ENTRANCE ICC 1105.1 COMPLIES

PASSENGER LOADING ZONES ICC 1106.7

BUILDING ELEMENT TABLE ICC REQ'D NFPA REQ'D PROVIDED

PRIMARY STRUCTURAL FRAME

EXTERIOR BEARING WALLS

SUPPORTING MORE THAN ONE FLOOR,

COLUMNS , OR OTHER BEARING WALLS

SUPPORTING ONE FLOOR ONLY

SUPPORTING A ROOF ONLY

INTERIOR BEARING WALLS

SUPPORTING MORE THAN ONE FLOOR,

COLUMNS , OR OTHER BEARING WALLS

SUPPORTING ONE FLOOR ONLY

SUPPORTING A ROOF ONLY

COLUMNS

SUPPORTING MORE THAN ONE FLOOR,

COLUMNS , OR OTHER BEARING WALLS

SUPPORTING ONE FLOOR ONLY

SUPPORTING A ROOF ONLY

BEAMS, GIRDERS, TRUSSES, AND ARCHES

SUPPORTING MORE THAN ONE FLOOR,

COLUMNS , OR OTHER BEARING WALLS

SUPPORTING ONE FLOOR ONLY

SUPPORTING A ROOF ONLY

FLOOR-CEILING ASSEMBLIES

ROOF-CEILING ASSEMBLIES

INTERIOR NON-BEARING WALLS

EXTERIOR NON-BEARING WALLS

FLOOR CONSTRUCTION AND

ASSOCIATED SECONDARY MEMBERS

ROOF CONSTRUCTION AND

ASSOCIATED SECONDARY MEMBERS

ABBREVIATIONS:

N/A

NC

C

NR

B

NOT APPLICABLE / NOT PART OF THIS PROJECT

NON-COMBUSTIBLE

COMBUSTIBLE

NOT REQUIRED

BARRIER TO LIMIT TRANSFER OF SMOKE

STRUCTURAL DESIGN:

REFER TO SPECIFIC DRAWING AND

SPECIFICATION SECTIONS FOR ADDITIONAL

STRUCTURAL DESIGN CRITERIA INCLUDING BUT

NOT LIMITED TO, LIVE LOAD, DEAD LOAD, AND

LATERAL LOADS APPLICABLE TO THIS PROJECT.

NOTES:

FIRE WALLS

ICC TABLE 601

NFPA TABLE A.8.2.1.2

ICC TABLE 706.4

FIRE BARRIERS ICC TABLE 707.3.10

VERTICAL EXIT ENCLOSURE

ICC 1023

NFPA 7.1.3.2

FIRE PARTITIONS ICC 708

EXIT PASSAGEWAY

ICC 1024

NFPA 7.1.3.2

HORIZONTAL EXIT

SEPARATION

ICC 1026

NFPA 7.2.4

INCIDENTAL USE

AREAS

ICC 509

NFPA 18.3.2.1

OCCUPANCY

SEPARATION

ICC 508

NFPA TABLE 6.1.14.4.1

SHAFT ENCLOSURE ICC 713.4

NFPA TABLE 8.3.4.2

CORRIDOR WALLS

ICC TABLE 1020.1

NFPA 18.3.6.1

SMOKE BARRIERS

ICC 709.3

NFPA 18.3.7

FIRE PROOFING ASSEMBLIES: BEAMS, COLUMNS, FLOOR SYS. ROOF SYS.

CONTRACTOR TO VERIFY /

MAINTAIN / PATCH ANY

AND ALL AREAS OF

FIREPROOFING OR UL

ASSEMBLIES WITHIN

SCOPE OF WORK

COMPLIES

COMPLIES

COMPLIES

(REFER TO CODE PLAN)

(REFER TO CODE PLAN)

(REFER TO CODE PLAN)

0.346421

50903

2 2

21.68

OFFICE OFFICE

'B' BUSINESS BUSINESS

CHANGE OF USE

TYPE V-B TYPE V [000]

MAINTAIN

EXISTING

38.1.6 60'

N/A

N/A

44'-6"

YES

27000

22708 SF

0.3 0.3

0.3 289

32" 32"

44" 44"

44" 44"

300' 300'

100' 100'

50' 50'

NR NR NR

N/A N/A N/A

CLASS B

CLASS C

CLASS C

1/3,000 SF

75'

1/3,000 SF

75'

NO NO

YES YES

YES YES

YES

YES

NO

0 EXISTING

EXISTING

EXISTING

N/A

N/A

EXISTING

EXISTING

N/A

N/A

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

2 2

1 1

1 1

EXISTING

COMPLIES

1 1 N/A

2 1 N/A

1 1

SEE CODE

PLAN

N/A N/A N/A

2 2 2

0 0 0

1 1 N/A

NO NO

-ACCESSIBLE MEANS OF EGRESS ARE NOT REQUIRED TO BE PROVIDED IN

EXISTING BUILDINGS (ICC 1009.1)

-REFER TO CODE COMPLIANCE PLAN FOR ADDITIONAL INFORMATION ON

EGRESS, PARTITION RATINGS AND OTHER CODE RELATED INFORMATION.

MIN. NUMBER OF REQUIRED PLUMBING

FIXTURES (ICC TABLE 2902.1)

TOTAL OCCUPANTS:

WATER CLOSETS:

REQUIRED: 1:25(FIRST 50) 1:50 (REMAINING)=

PROVIDED =

LAVATORIES:

REQUIRED: 1:40 (FIRST 80) 1:80 (REMAINING) =

PROVIDED =

DRINKING FOUNTAINS:

REQUIRED: 1:100 =

PROVIDED =

SERVICE SINKS:

REQUIRED =

PROVIDED =

49 SF

TOILET

149 SF

STAIR

103 SF

OFFICE - SUP.

ELEVATOR

40 x 0.3" 12" (32")

1689 SF

OPEN CALL

CENTER

1400 SF

OPEN CALL

CENTER

101 SF

COPY / STOR.

151 SF

SHARED

OFFICE

167 SF

SHARED

OFFICE

153 SF

SHARED

OFFICE

165 SF

SHARED

OFFICE

51 SF

IT CL

84 SF

COPY / STOR.

249 SF

STAFF

LOUNGE

111 SF

OFFICE - SUP.

100 SF

OFFICE - SUP.

52 SF

ELEV. VEST.

EXIST

STAIR

EXIST

STAIR

47 SF

TOILET

349 SF

CORR.

84'-0"

MAX OVERALL

DIAGONAL

181'-3"

EXIT SEPARATION

DISTANCE

134'

OCC. LOAD

235 SF

MULTI-PURPOSE

44 SF

JAN.

41 x 0.3" 12.3" (32")

FX

FX

C

LE

A R

5'

FXC

LE

A R

5'

ACCESSIBLE ROUTE:

PATIENT CARE AREA WIDTH

ADMINISTRATIVE AREA WIDTH

MAX. SLOPE

MIN. GRADIENT OF WALK

REQUIRING REST AREA EVERY 200'

TURNING RADIUS

TURNING RADIUS, BARIATRIC

FLOOR SURFACES:

CHANGES IN LEVEL

CARPET CUSHION OR PADDING

PARKING AND PASSENGER

LOADING ZONES:

ACCESS AISLE REQUIREMENT FOR

ACCESSIBLE PARKING SPACES

PASSENGER LOADING AREA

SUPPLEMENT TO THE ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)

MINIMUM REQUIREMENTS

ACCESSIBLE PARKING SPACES

SCI/D FACILITIES

HOSPITAL OUTPATIENT FACILITIES

REHABILITATION AND OUTPATIENT

PHYSICAL THERAPY FACILITIES

BUILDINGS - ACCESSIBLE SEATING,

ASSEMBLY AREAS

1% GREATER THAN ABAAS

2% ACCESSIBLE SPACES PER INPATIENT

BED; 0.5 PER LONG-TERM CARE BED; 5.6

PER OUTPATIENT EXAM ROOM. DEDICATED

FOR SCI/D PATIENTS

10% OF TOTAL SPACES

20% OF TOTAL SPACES

20% OF TOTAL SPACES

1% GREATER THAN ABAAS

REQUIREMENT VA ABAAS

10% OF TOTAL SPACES

20% OF TOTAL SPACES

20% OF TOTAL SPACES

6'-0" 5'-0" 1:33 (3%) 1:50

5'-6" 6'-0"

3'-0" 3'-0" 1:20 (5%) 1:33

5'-0" 5'-0"

NOT PERMITTED ON SCI FLOORS

NOT PERMITTED

NO REQUIREMENT

PERMITTED

5'-0" EACH SIDE

YES

5'-0" EACH SIDE

1 PER 2 SPACES

NO REQUIREMENT

CURB RAMPS:

MIN. WIDTH 4'-0" 3'-0"

RAMPS:

MAX. SLOPE

MAX. LENGTH, (1:33-1:26)

MAX. LENGTH, (1:25-1:20)

MIN. CLEAR WIDTH

MIN. SIZE LEVEL LANDING, WHERE

DOORS SWING INTO LANDING

1:20 40' 35' 4'-0" 6'-0" X 6'-0"

1:12 200' 200' 3'-0" 5'-0" X 5'-0"

STAIRS:

HANDRAIL HEIGHT 34" 30"-34"

ELEVATORS (PASSENGER):

MIN. WIDTH OF ELEVATOR DOORS

MIN. CAR SIZE

DOUBLE SET OF HANDRAILS

4'-0"

8'-0" X 6'-2" (PLATFORM SIZE)

YES

3'-0"

68" X 51" (CAR INSIDE DIM.)

NO REQUIREMENT

DOORS AND DOORWAYS:

PATIENT CARE DELIVERY AREAS

WITH PATIENT BED, STRETCHER OR

GURNEY ACCESS, MIN. WIDTH

4'-0" 3'-8"

WINDOWS:

SILL HEIGHT IN PATIENT

BEDROOMS

24" MAX. NO REQUIREMENT

WATER CLOSETS:

GRAB BAR CONFIGURATION DOUBLE SWING-UP BARS FOR

ALL PATIENT TOILETS/SHOWER

ROOMS ON NURSING UNITS

SIDE & BACK BARS FOR ALL

ACCESSIBLE WATER CLOSETS

TOILET STALLS:

MIN. ACCESSIBLE STALL SIZE

MIN. SIZE WHEELCHAIR "FRONT

TRANSFER" STALL

GRAB BARS

5'-6" X 6'-0" 3'-6" X 6'-0"

REQUIRED IN ALL STALLS

5'-0" X 4'-8" 3'-0" X 5'-6"

REQUIRED IN ACCESSIBLE STALLS

SHOWER STALLS (PATIENT):

MIN. STALL DIMENSIONS

GRAB BARS

4'-0" X 4'-0"

HORIZONTAL PLUS VERTICAL BARS

3'-0" X 3'-0" OR 2'-6" X 5'-0"

HORIZONTAL BARS ONLY

TOILET ROOMS:

INPATIENT BEDROOM TOILET

ROOMS, MIN. WIDTH OF ENTRANCE

48" 34"

CAFETERIAS:

KNEE CLEARANCE (MIN. 5% TABLES)

CUTLERY AND SUPPLY HEIGHT

2'-3" AND 2'-5" FOR AT LEAST 5%

40" - 48"

2'-3"

54" MAX.

HEALTH CARE FACILITIES:

MED/SURG % OF ACCESSIBLE

BEDROOMS

MED/SURG % OF ACCESSIBLE

TOILETS

100%

100%

10%

10%

EXIST

ATTIC

TYP.

40 SF

MECH.

149 SF

STAIR

FLOOR

PENETRATIONS

BASEMENT 7,207 GROSS SF

FLOOR TOTAL

GROSS AREA

NET AREA OF

ASSEMBLY USE

568 NET SF

TOTAL GROSS LESS

NET ASSEMBLY

6,639 SF

OCCUPANCY

(BUSINESS USE, 1:100)

67 OCCUPANTS

OCCUPANCY

(ASSEMBLY USE, 1:15)

38 OCCUPANTS

TOTAL OCCUPANCY

105 OCCUPANTS

FIRST FLOOR 7,013 GROSS SF 557 NET SF 6,456 SF 65 OCCUPANTS 38 OCCUPANTS 103 OCCUPANTS

SECOND FLOOR 6,708 GROSS SF 235 NET SF 6,473 SF 65 OCCUPANTS 16 OCCUPANTS 81 OCCUPANTS

TOTAL OCCUPANTS 289 OCCUPANTS

www.chacompanies.com

Powers Building, 16 West Main Street, Suite 830

Main: (585) 262-2640

Rochester, NY 14614-1607

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0084

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

PLAN

NORTH

NORTHAMPTON VAMC

RENOVATION OF BLDG. 20

LEEDS, MASSACHUSETTS

631-17-004

20A Se rv ic e D i s a b l e d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

U.S. Department of Veterans Affairs

ACTUAL

NORTH

C U s e rs \A

B ra d fo rd \D o c u m e n ts \R e v it L o c a l F ile s \2

N o rt h a m p to n V

A M

C B ld g

A rc h a b ra d fo rd .r v t

09-21-2018 Checker Author

G-004

SECOND & ATTIC FLOOR CODE

COMPLIANCE PLAN

BID DOCUMENTS

LEGEND

SCALE: 1/8" = 1'-0"G-004

1 SECOND FLOOR CODE COMPLIANCE PLAN

VA BARRIER FREE DESIGN STANDARDS

SCALE: 1/8" = 1'-0"G-004

3 ATTIC CODE COMPLIANCE PLAN

OCCUPANCY CALCULATION

GI001
GI001
GI001
G-002
G-003
G-004