36C24119R0029-004.pdf
PDF 12 MB Posted
- Attached to
- 631-17-004 Renovate Building 20 for Call Center
- Solicitation number
- 36C24119R0029
About this file
36C24119R0029 S02 00-General.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24119R0029-0002000.docx | DOCX document | |
| 36C24119R0029-0002001.pdf | ||
| 36C24119R0029-0002002.pdf | ||
| 36C24119R0029-0001001.pdf | ||
| 36C24119R0029-0001000.docx | DOCX document | |
| 36C24119R0029-001.docx | DOCX document | |
| 36C24119R0029-005.pdf | ||
| 36C24119R0029-008.pdf | ||
| 36C24119R0029-002.pdf | ||
| 36C24119R0029-003.pdf | ||
| 36C24119R0029-009.pdf | ||
| 36C24119R0029-006.pdf | ||
| 36C24119R0029-010.pdf | ||
| 36C24119R0029-011.pdf | ||
| 36C24119R0029-007.pdf | ||
| 36C24119R0029-000.docx | DOCX document |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER SHEET
& DRAWING INDEX
GI001
DSTH
NORTHAMPTON VAMC
RENOVATION OF BLDG. 20
631-17-004
BID DOCUMENTS
NO. DESCRIPTION DATE
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0506-0003
B
A
C
D
E
F
U.S. Department of Veterans Affairs
MATERIAL SYMBOLS
CONCRETE MASONRY UNITS
(CMU)
CONCRETE
BRICK
CEMENT, SAND, GROUT, PLASTER, OR
GYPSUM WALL BOARD
EARTH
STONE, GRAVEL, OR POROUS
FILL
CARPET
PLYWOOD
WOOD (FINISHED)
WOOD (ROUGH)
RIGID INSULATION
BATT. OR LOOSE INSULATION
STEEL
WOOD (BLOCKING)
PARTICLE BOARD
ARCHITECTURAL DRAWINGS SYMBOLS
MATCH LINE
ELEVATION LINE
COLUMN LINE REFERENCES
DOOR TAGS
BUILDING SECTIONS
WALL SECTIONS
ARCHITECTURAL ABBREVIATIONS
A
X-XXX
X-XXX
X-XXX
DETAIL NO
SHEET NO
DETAIL NO
SHEET NO
A
B
CENTER LINE OF GYP
BD/STUD PARTITION
(U.O.N.)
NOMINAL FACE
OF MASONRY AND CONCRETE
WALL / PARTITIONS
(U.O.N.)
CENTER LINE
OF COLUMN
(U.O.N.)
TYPICAL PLAN DIMENSIONING
NOMINAL FACE OF
EXISTING PARTITION
(U.O.N.)
B
A: Area AB: Anchor Bolt ABV: Above ACC: Access ACOUST: Acoustical ACR: Acrylic ACST: Acoustic ACT: Acoustical Tile AD: Access Door ADH: Adhesive ADJ: Adjust, Adjustable, Adjacent AFF: Above Finished Floor AGGR: Aggregate ALT: Alternate ALUM: Aluminum ANOD: Anodized AP: Access Panel APPROX: Approximate ATC: Acoustical Tile Ceiling
BDRM: Bedroom BETW: Between BF: Board Foot BIT: Bituminous BLDG: Building BLKG: Blocking BOT: Bottom BPL: Bearing Plate BRG: Bearing BRK: Brick BRZ: Bronze BS: Both Sides BSMT: Basement BUR: Built-up Roof
C/C: Center to Center CAB: Cabinet CAR: Carpet CAV: Cavity CCW: Counter Clockwise CCTV: Closed Circuit TV CEM: Cement CER: Ceramic CF: Cubic Feet CHAM: Chamfer CJ: Control Joint CK: Caulking CL: Centerline CLG: Ceiling CLKG: Caulking CLR: Clear CLR OPG: Clear Opening CMT: Ceramic Mosaic Tile CMU: Concrete Masonry Unit COL: Column CONC: Concrete CONSTR: Construction CONT: Continuous CONTR: Contractor COP: Copper CPR: Copper CPT: Carpet CT: Ceramic Tile CW: Clockwise
EA: Each EB: Expansion Bolt EE: Each End EF: Each Face EIFS: Exterior Insulation and Finish System EJ: Expansion Joint EL: Elevation, Elevator ELEC: Electrical ELEV: Elevator, Elevation ENCL: Enclosure EPDM: Ethylene Propylene Diene Monomer EQ: Equal EQUIP: Equipment EW: Each Way EXG: Existing EXH: Exhaust EXIST: Existing EXP: Exposed
GA: Gauge, Gage GALV: Galvanized GC: General Contractor GL: Glass GL BLK: Glass Block GRND: Ground GRTG: Grating GVL: Gravel GYP: Gypsum GYP BD: Gypsum Board
WINDOW TAG/LOUVER TAG
DETAIL SECTIONS
X-XXX
DETAIL NO
SHEET NO
P. LAM: Plastic Laminate PAR: Parallel PBD: Particle Board PERIM: Perimeter PERP: Perpendicular PL: Plate PLBG: Plumbing PLYWD: Plywood PLUMB: Plumbing PP: Push-Plate Operator PR: Pair PREFAB: Prefabricated PRES: Pressure PRESS: Pressure PRMLD: Premolded PRTN: Partition PSF: Pounds per square foot PSI: Pounds per square inch
PT: PAINT
PTD: Painted, Paper Towel Dispenser PTD/R: Combination Paper Towel Dispenser/Receptacle PTN: Partition
EXTERIOR ELEVATIONS
INTERIOR ELEVATIONS
DETAIL CALL OUTS
DETAIL NO0
X-XXX
DETAIL NO
SHEET NO
X-XXX2 4
SHEET NO
WALL TYPE
ROOM TAGROOM #
ROOM AREA
# PLAN/ELEVATION KEYNOTE
REVISION SYMBOL AND
CLOUD
C
D
E
F
G P
H
I
J
L
M
N
O
Q
R
S
T
DBL: Double DEG: Degree DEMO: Demolition DF: Drinking Fountain DIAG: Diagonal DIA: Diameter DIAM: Diameter DIFF: Diffuser DN: Down DR: Door DWG: Drawing DWGS: Drawings DWR: Drawer
FB: Face Brick FD: Floor drain FDC: Fire Department Connection FDN: Foundation FDTN: Foundation FE: Fire Extinguisher FEC: Fire Extinguisher Cabinet FFE: Finished Floor Elevation FF&E: Fixtures, Furnishings & Equipment FFL: Finished Floor Line FGL: Fiberglass FHC: Fire Hose Cabinet FIN: Finish, finished FIXT: Fixture
HDCP: Handicapped (better called "Accessible") HDW: Hardware HDWD: Hardwood HGT: Height HM: Hollow Metal HORIZ: Horizontal HR: Hour HWD: Hardwood
ID: Inside Diameter IN: Inch INCL: Include INFO: Information INSTL: Install INSUL: Insulation INT: Interior INTERM: Intermediate
JAN: Janitor JC: Janitor's Closet JT: Joint
FINISH KEYNOTE
LAB: Laboratory, Labor LAV: Lavatory LB: Pound (weight) LBL: Label LINO: Linoleum LNTL: Lintel
MAINT: Maintenance MAN; Manual MAR: Marble MARB: Marble MAS: Masonry MAT: Material MATL: Material MAX: Maximum MECH: Mechanical MEMB: Membrane MFD: Manufactured MFG: Manufacturer, Manufacturing MFR: Manufacture, Manufacturer MI: Malleable Iron, Miles MIKE: Microphone MIN: Minimum MIR: Mirror MISC: Miscellaneous MK: Mark ML&P: Metal Lath & Plaster MLD: Molding MLDG: Molding MM: Millimeter MMB: Membrane MO: Masonry Opening MOD: Module MONO: Monolithic MOV: Movable MP: Metal Acoustal Panel MPS: Medium Pressure Steam MR: Mop Receptor MRD: Metal Roof Deck MT: Mount, Mounted MTD: Mounted MTL: Material, Metal MTR: Motor MUL: Mullion MULL: Mullion MV: Mercury Vapor MWP: Maximum Working Pressure MWK: Millwork
N: North, Nitrogen NAP: Napkin NAT: Natural NATL: Natural NB: "Nota Bene" Latin phrase for "Take Special Note" NC: Normally Closed, Noise Criteria NEC: National Electrical Code NEUT: Neutral NF: Near Face NFWH: Non-freeze Wall Hydrant NI: Nickel NIC: Not In Contract NK: Neck NMT: Non-Metallic NO: Number, Normally Open NOM: Nominal NR: Noise Reduction NRC: Noise Reduction Coefficient NTS: Not To Scale
OB: Obscure OBS: Obscure OC: On Center OD: Outside Diameter OF: Outside Face OFF: Office OH: Overhead OHD: Overhead Door OPNG: Opening OPP: Opposite OPP H: Opposite Hand
QUAL: Quality QT: Quarry Tile, Quart QTY: Quantity
RB: Rubber Base RCP: Reflected Ceiling Plan RD: Roof Drain, Round, Receptacle Distribution Panel REBAR: Reinforcing Bar REF: Refer, Reference, Refrigerator REFL: Reflected, REFR: Refrigerate, Refrigerator REINF: Reinforcement, or Reinforce REQD: Required RESIL: Resilient RF: Roof RGH: Rough RGH OPNG: Rough Opening RO: Rough Opening RT: Rubber Tile
SALV: Salvage SCHED: Schedule SF: Square Foot SHR: Shower SHT: Sheet SPEC: Specification, Specifications SPECS: Specifications SQ: Square SS: Stainless Steel STC: Sound Transmission Class STD: Standard STL: Steel STOR: Storage STRT: Straight STRUC: Structural STRUCT: Structural SUR: Surface SUSP: Suspended, Suspend
T&B: Top and Bottom T&G: Tongue & Groove TB: Towel Bar TD: Trench Drain TERR: Terrazzo THK: Thick, Thickness THRU: Through TLT: Toilet TPD: Toilet paper Dispenser TPH: Toilet Paper Holder TPTN: Toilet Partition TYP: Typical TZ: Terrazzo
UNFIN: Unfinished UNO: Unless Noted Otherwise UON: Unless Otherwise Noted UP: Unpainted UR: Urinal
VAT: Vinyl Asbestos Tile VBC: Vinyl Base (Coved) VCT: Vinyl Composition Tile VERT: Vertical VEST: Vestibule VIF: Verify In the Field VT: Vinyl Tile VTR: Vent Through Roof VWC: Vinyl Wall Covering
W/: With W/O: Without WAINS: Wainscot WC: Watercloset WD: Wood
U
V
W
A101
SIM
CS12.0b
W-
ROOM NAME
150 SF
XXX
F FL: Floor FLR: Floor FO: Finished Opening FOF: Face of Finish FOS: Face of Studs FP: Fireproof FRT: Fire Retardant FT: Foot, Feet, FTG: Footing, Fitting FURN: Furnish, Furniture FURR: Furring
X-XXX
DETAIL NO
SHEET NO
UNLESS OTHERWISE NOTED, ALL MASONRY DIMENSIONING IS NOMINAL TO FACE OF MASONRY, ALL
NON-MASONRY DIMENSIONING IS TO CENTER OF PARTITIONS OR WALLS AND ALL CONCRETE
DIMENSIONING IS FACE TO FACE OF WALL.
PROVIDE CONCEALED BLOCKING IN ALL STUD PARTITIONS AND WALLS BEHIND SURFACE FOR SEMI-
RECESSED, FULLY RECESSED OR SURFACE MOUNTED ACCESSORIES AND MILLWORK.
DIMENSIONS NOTED AS “CLEAR” ARE TO FINISHED SURFACE AND ARE CRITICAL FOR ACCESSIBILITY
REQUIREMENTS OR BUILT-IN FURNISHINGS.
CONTRACTOR SHALL FIELD VERIFY FINISHED DIMENSIONS AND CLEARANCES IN SPACES INDICATED TO
RECEIVE BUILT-IN FURNISHINGS OR CASEWORK PRIOR TO FABRICATION.
ALL VERTICAL CONCRETE SURFACES WHICH WILL BE EXPOSED TO VIEW UPON COMPLETION OF WORK
SHALL RECEIVE A SMOOTH RUBBED FINISH.
ALL ENDS OF MASONRY WALLS THAT WILL BE EXPOSED TO VIEW UPON COMPLETION OF WORK SHALL
BE PLAIN END UNITS.
FINISHED DOOR OPENINGS SHALL BE NOMINAL 6” FROM FINISHED CORNER OF ROOM EXCEPT WHERE
DIMENSIONED OTHERWISE.
SEALANT SHALL BE PROVIDED AT THE INTERIOR AND EXTERIOR PERIMETER OF ALL WINDOWS, DOOR
FRAMES, LOUVERS OR OTHER ITEMS INSERTED IN AN EXTERIOR WALL.
SUSPENDED GRID CEILINGS SHALL BE ARRANGED SO THAT A GRID IS SPACED EQUALLY FROM EACH
MOST REMOTE WALL, IN EACH DIRECTION, WITH NO TILES LESS THAN 6” UNLESS OTHERWISE
INDICATED.
WOOD USED FOR BLOCKING OR OTHER PURPOSES ON OR ABOVE THE ROOF DECK, WITHIN 2'-0” OF
GRADE AND IN OTHER LOCATIONS OUTSIDE THE BUILDING ENVELOPE WHERE EXPOSED TO THE
WEATHER SHALL BE PRESSURE TREATED LUMBER OR PLYWOOD.
INSTALL ALL WORK AS INDICATED AND VERIFY EXACT LOCATION AND ELEVATIONS ON THE JOB.
DO NOT SCALE DRAWINGS. REFER TO DIMENSIONS AND SPECIFIED MATERIALS. CONTACT THE
ARCHITECT IF ADDITIONAL DIMENSIONS ARE REQUIRED.
COORDINATE ALL DOOR HARDWARE, TRIM AND FINISHES TO MEET INTENT AND COMPLIANCE.
FIRST FLOOR LEVEL DATUM ELEVATION (0'-0") IS EQUAL TO ACTUAL
ELEVATION (383'-0"). ARCHITECTURAL ELEVATIONS U.O.N. ARE TAKEN FROM FINISHED FIRST FLOOR
LEVEL DATUM ELEVATION (0'-0").
INTERIOR WALL AND CEILING FINISH MINIMAL REQUIREMENTS (FINISH CLASSIFICATIONS IN
ACCORDANCE WITH ASTM E84) ARE AS FOLLOWS:
VERTICAL EXITS AND EXIT PASSAGEWAYS - CLASS B
EXIT ACCESS CORRIDORS AND OTHER EXITWAYS - CLASS C
ROOMS AND ENCLOSED SPACES - CLASS C
GENERAL ARCHITECTURAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
OVERHEAD
VISIBLE ITEMS
BREAK LINE
HIDDEN OR NOT IN CONTRACT
CENTER LINE OR COLUMN GRID
C.M.U. WALL / PARTITION - SEE PARTITION TYPES
EXISTING WALL CONSTRUCTION
METAL STUD PARTITION - SEE PARTITION TYPES
WALL/ PARTITION DESIGNATIONS
BRICK FACE
LINE TYPES
GRAB BAR
AT REAR OF TOILET
(SURFACE MTD.)
GRAB BAR
TO SIDE OF TOILET
(SURFACE MTD.)
WALL-MOUNTED
TOILET
NOTE: FLUSH CONTROLS
FOR THE TOILET SHALL BE
MOUNTED ON THE OPEN
SIDE OF THE TOILET AREA
NO MORE THAN 44" A.F.F.
LIQUID SOAP DISPENSER
TOUCH FREE DISPENSER
(SURFACE MTD.)
O R
A B
O V
E
C O
U N
TE
R
PAPER TOWEL DISPENSER
(SURFACE MTD.)
ACCESSIBLE
TOILET ROOM DOOR
PROVIDE SIGNAGE (MIN
LETTER HEIGHT 1 1/4") CODE
REQUIREMENTS. "TACTILE"
PER ADA & SYMBOL
COMPLIANCE. REFER TO
SIGNAGE DWGS. FOR
SIGNAGE TYPE.
MIRROR
(SURFACE MTD.)
WALL-MOUNTED
LAVATORY
WRIST BLADE TYPE
HANDLES. SEE PLUMBING
DRAWINGS FOR FIXTURE
AND HARDWARE
SPECIFICATIONS
PROTECT
PIPES
VARIES
SANITARY NAPKIN
DISPOSAL
(SURFACE MTD.)
MOP AND BROOM
HOLDER
(SURFACE MTD.)
6' -0
TOILET SEAT COVER
DISPENSER
(SURFACE MTD.)
GRAB BAR IN
FOREGROUND
FIRE
EXTINGUISHER
CABINET
(RECESSED)
HEIGHT OF FIRE
EXTINGUISHER
OPERATING
MECHANISM AT
48" A.F.F. MAX.
TOILET TISSUE
DISPENSER
(SURFACE MTD.)
39"-41"
12" MAX. 42" MIN.
1' -6
1'-6" 1'-6"
CL CL
16" - 18"
54" MIN.
M A
X.
T
O B
O
TT
M
F R
EF
LE
C
TI
V E
S U
R
FA
C E
2' -9
3' -4
2' -1
0"
1' -8
4' -0
2' -5
" 4' -0
4' -0
FINISH FLOOR
FINISH FLOOR 17
1' -8
5' -0
4' -0
GLOVE HOLDER
(SURFACE MTD.)
SHARPS DISPOSAL
(SURFACE MTD.)
7' -6
CLOCK
(SURFACE MTD.)
CL
3' -7
36" MIN.
4' -0
SHOWER CONTROLS
(SURFACE MTD.)
O R
A B
O
U N
TE
R
TO
P
O
IN
T O
F D
IS
P
O S
A L
COAT HOOKS
(SURFACE MTD.)
4' -0
" 5' -1
0"
O R
A B
O
U N
TE
R
7"-9"
4' -0
NURSE CALL
(SURFACE MTD.)
THERMOSTAT
(SURFACE MTD.)
4' -0
*NOTE: 24" MIN. APPLIES WHERE WALL
SPACE IS PROVIDED. OTHERWISE 12"
MIN. WHERE RECESSED FIXTURE
IS ADJACENT.
12" MIN. 24" MIN.*
36" MIN.
3' - 6"
4'
M A
X.
WATER BOTTLE FILLER
(SURFACE MTD.)
www.chacompanies.com
Powers Building, 16 West Main Street, Suite 830
Main: (585) 262-2640
Rochester, NY 14614-1607
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0084
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER. NORTHAMPTON VAMC
RENOVATION OF BLDG. 20
LEEDS, MASSACHUSETTS
631-17-004
20A Se rv ic e D i s a b l e d
Ve t e r an Owned S m a l l B u s iness
SDVOSB
CVE
U.S. Department of Veterans Affairs
C U s e rs \A
B ra d fo rd \D o c u m e n ts \R e v it L o c a l F ile s \2
N o rt h a m p to n V
A M
C B ld g
A rc h a b ra d fo rd .r v t
09-21-2018 Checker Author
G-002
NOTES, SYMBOLS & ABBREVIATIONS
BID DOCUMENTS
GENERAL
G-002 NOTES, SYMBOLS & ABBREVIATIONS
G-003 BASEMENT & FIRST FLOOR CODE COMPLIANCE PLANS
G-004 SECOND & ATTIC FLOOR CODE COMPLIANCE PLAN
ARCHITECTURAL
A-002 PARTITION TYPES
A-010 BASEMENT & FIRST FLOOR DEMOLITION PLAN
A-011 SECOND FLOOR & ATTIC DEMOLITION PLAN
A-012 ROOF & ENLARGED DEMOLITION PLANS
A-100 ARCHITECTURAL SITE PLAN
A-101 OVERALL BASEMENT & FIRST FLOOR PLAN
A-102 OVERALL SECOND FLOOR PLAN & ATTIC PLAN
A-103 ROOF PLAN & ROOF DETAILS
A-110 BASEMENT & FIRST FLOOR REFLECTED CEILING PLANS
A-111 SECOND FLOOR & ATTIC REFLECTED CEILING PLAN & CEILING DETAILS
A-201 PARTIAL EXTERIOR ELEVATIONS
A-301 BUILDING SECTIONS
A-310 WALL SECTIONS AND DETAILS
A-401 ENLARGED BASEMENT PLAN - AREA A
A-402 ENLARGED BASEMENT PLAN - AREA B
A-403 ENLARGED FIRST FLOOR PLAN - AREA A
A-404 ENLARGED FIRST FLOOR PLAN - AREA B
A-405 ENLARGED SECOND FLOOR PLAN - AREA A
A-406 ENLARGED SECOND FLOOR PLAN - AREA B
A-410 ELEVATOR PLANS, SECTIONS, & DETAILS
A-411 STAIR PLANS, SECTION, & DETAILS
A-501 INTERIOR ELEVATIONS
A-502 INTERIOR ELEVATIONS
A-503 INTERIOR ELEVATIONS
A-601 DOOR SCHEDULE & DETAILS
A-602 WINDOW TYPES & DETAILS
A-701 MILLWORK DETAILS
A-702 PLAN & MISCELLANEOUS DETAILS
INTERIORS
I-001 FINISH LEGEND, SIGNAGE SCHEDULE, AND INTERIOR DETAILS
I-101 BASEMENT FINISH PLAN
I-102 FIRST FLOOR FINISH PLAN
I-103 SECOND FLOOR FINISH PLAN
I-301 BASEMENT FURNITURE & EQUIPMENT PLAN
I-302 FIRST FLOOR FURNITURE & EQUIPMENT PLAN
I-303 SECOND FLOOR FURNITURE & EQUIPMENT PLAN
ARCH. SHEET LIST
TYP. MOUNTING HEIGHTS
1HR 1HR1HR 1HR
2HR 2HR2HR 2HR
SP SPSP SP
(E)1HR (E)1HR(E)1HR (E)1HR
UP
UP
UP
UP
UP
1HR 1HR
H
R
H R
H
R
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
1HR 1HR
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
2HR 2HR
H
R
H R
H
R
H R
2HR 2HR
S P
S P
1HR 1HR
H
R
H R
1HR 1HR1HR 1HR 1HR 1HR
H
R
H R
H
R
H
R
H R
H
R
S P
S P
H
R
H R
H
R
H R
S P
S P
S P
SP SP
S P
S P
S P
S P
SP SPSP SP
S P
S P
S P
S P
DN DN
DN
DN
UP UP
2HR 2HR
H
R
H R
H
R
H R
2HR 2HR
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
1HR 1HR
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
H
R
H R
H
R
H R
2HR2HR
H
R
H R
H
R
H R
2HR2HR
S P
S P
S P
S P
H
R
H R
H
R
H R
2HR2HR
2HR2HR 2
H
R
H R
H
R
H R
1HR 1HR
H
R
H R
H
R
H R
2HR2HR
H
R
H R
H
R
H R
H
R
H R
H
R
H R
2HR2HR
EXIT DISCHARGE
TRAVEL DISTANCE AND DIRECTION OF TRAVEL
COMMON PATH OF EGRESS
REMOTE POINT OF TRAVEL
XX'-XX"
EXIT
EXITE
FIRE EXTINGUISHER CABINET
(1 PER 75 FT RADIUS)
FX
1 HOUR FIRE RATED ASSEMBLY
2 HOUR FIRE RATED ASSEMBLY
SMOKE PARTITION - NON-FIRE RATED
ASSEMBLY DESIGNED AND CONSTRUCTED TO
LIMIT THE PASSAGE OF SMOKE
50 x 0.2" 10" (32")
OCCUPANT LOAD AT EXIT
MIN. WIDTH PER OCCUPANT
MIN. CODE EXIT WIDTH
MIN. CALCULATED EXIT WIDTH
EXISTING WALL - PRESUMED 1 HOUR FIRE
RATED ASSEMBLY
EXIT SIGN
64 SF
TOILET
123 SF
VEST.
279 SF
MECH.
ELEVATOR
100 SF
IT
OCC. LOAD
362 SF
CONFERENCE
RM
165 SF
SHARED
OFFICE - ENG.
100 SF
OFFICE - ENG.
94 SF
OFFICE -
SAFETY
OCC. LOAD
221 SF
STAFF LOUNGE
100 SF
OFFICE -
CLINICAL
ENG.
19 x 0.3" 5.7" (32")
48 x 0.2" 9.6" (32")
582 SF
OFFICE /
WORK AREA-
SAFETY
425 SF
CORR.
93 SF
ELEV. VEST.
359 SF
CORR.
20 x 0.2" 4" (32")
18 x 0.3" 5.4" (32")
81 x 0.3" 24.3" (32")
102 x 0.3" 30.6" (32")
E E
E
E
190 SF
SHARED
OFFICE - ENG.
106 SF
OFFICE - ENG.
180 SF
SHARED
OFFICE - ENG.
201 SF
INTERIOR
DESIGNER
123 SF
OFFICE - ENG.
240 SF
PLANS ROOM
/ STORAGE
91 SF
ELEV.
MACHINE RM
36 SF
CLOSET
155 SF
SHARED
OFFICE - ENG.
47 SF
JAN.
102 SF
ELEC.
96 SF
FILE STOR.
OCC. LOAD
153 SF
CONFERENCE
RM
101 SF
OFFICE
100 SF
OFFICE
99 SF
OFFICE
96 SF
OFFICE
195 SF
WORK AREA /
COPIER
96'-2"
EXIST
STAIR
EXIST
STAIR
90 SF
VESTIBULE
143 SF
CORR.
64 SF
TOILET
53 SF
TOILET
OCC. LOAD
49 SF
WAITING
EXIT
FX
FX
FX C
LE
A R
5'
CLEAR
5' - 3 1/2"
CLEAR
6' - 2"
ELEVATOR
OCC. LOAD
360 SF
CONFERENCE
RM
358 SF
OFFICE - PIV
239 SF
STAFF
LOUNGE
21 x 0.3" 6.3" (32")
38 x 0.2" 7.6" (32")
44 x 0.3" 13.2" (32")
121 SF
OFFICE - HR
164 SF
SHARED
OFFICE - HR
OCC. LOAD
194 SF
WAITING
158 SF
ELEC. / IT
301 SF
SHARED
OFFICE - HR
146 SF
WORK RM /
COPIER
101 SF
OFFICE - HR
168 SF
SHARED
OFFICE - HR
153 SF
SHARED
OFFICE - HR
153 SF
SHARED
OFFICE - HR
159 SF
SHARED
OFFICE - HR
63 SF
JAN.
174 SF
SHARED
OFFICE -
CONTRACTING
157 SF
SHARED
OFFICE -
CONTRACTING
156 SF
SHARED
OFFICE -
CONTRACTING
170 SF
SHARED
OFFICE -
CONTRACTING
101 SF
OFFICE -
LEGAL
222 SF
WORK RM /
COPIER
100 SF
OFFICE -
LEGAL
96 SF
OFFICE -
LEGAL
114 SF
WORK RM /
COPIER
123115 SF
OFFICE -
CONTRACT
EXIST
STAIR
EXIST
STAIR
448 SF
CORR.
145 SF
CORR.
10451 SF
TOILET
57 SF
TOILET
52 SF
ELEV. VEST.
90 SF
VESTIBULE
48 SF
TOILET
376 SF
CORR.
23'-7"
E
EXIT
FXFX C
LE
A R
5'
99 SF
OFFICE - HR
FX
CODE REVIEW INFORMATION
2015 INTERNATIONAL BUILDING CODE & NFPA 101 LIFE SAFETY CODE 2015
BUILDING DATA FIRE RESISTANCE RATINGS
ICC REQ'D NFPA REQ'D PROVIDED
USE DESCRIPTION
OCCUPANCY
ICC CH. 3
NFPA 6.1.1
CLASSIFICATION OF WORK NFPA 4.6.7
CONSTRUCTION TYPE
ICC CH. 6
NFPA TABLE A.8.2.1.2
NO. OF STORIES
BUILDING HEIGHT
ICC CH. 5
NFPA TABLE
AUTOMATIC SPRINKLER SYSTEM
ICC CH. 9
NFPA 9.7.1
ALLOWABLE BUILDING AREA (At) ICC TABLE 506.2
INCREASE FOR FRONTAGE (If) ICC CH. 5
TOTAL ALLOWABLE BUILDING AREA (Aa) ICC CH. 5
SF
SF
TOTAL GROSS BUILDING AREA ICC CH. 5
NUMBER OF OCCUPANTS
ICC TABLE 1004.1.2
NFPA TABLE 7.3.1.2
SEE OCCUPANCY
CALCULATION BELOW
MIN. NUMBER OF EXITS ICC TABLE 1006.3.1
NFPA 7.4.1.2
MIN. EXIT WIDTH PER OCCUPANT ICC 1006.3.1
NFPA 7.4.1.2
PER OCC. PER OCC.
x
MIN. DOOR WIDTH ICC 1010.1.1
NFPA 7.2.1.2.3.2 / 18.2.3.6
COMPLIES
MIN. STAIRWAY WIDTH
ICC 1011.2
NFPA 7.2.2.2
COMPLIES
MIN. CORRIDOR WIDTH
ICC 1020.2
NFPA 7.3.4.1
COMPLIES
MAX. TRAVEL DISTANCE
ICC TABLE 1017.2
NFPA TABLE A.7.6 COMPLIES
MAX. COMMON
PATH OF TRAVEL
ICC TABLE 1006.2.1
NFPA TABLE A.7.6 COMPLIES
MAX. DEAD END CORRIDOR
ICC 1020.4
NFPA TABLE A.7.6 COMPLIES
ICC 718
NFPA 8.6.11
CONCEALED SPACE
DRAFTSTOPPING
SMOKE COMPARTMENT ICC 407.5 / NFPA 18.3.7.1
INTERIOR FINISHES CLASS
INTERIOR EXIT STAIRWAYS AND RAMPS AND
EXIT PASSAGEWAYS
ICC TABLE 803.11
CORRIDORS AND ENCLOSURE FOR EXIT ACCESS
STAIRWAYS AND RAMPS
ROOMS AND ENCLOSED SPACES
COMPLIES
COMPLIES
COMPLIES
ICC TABLE 906.3
NFPA 9.9
FIRE EXTINGUISHER SPACING COMPLIES
STANDPIPE SYSTEM
ICC 905.3.1
NFPA 9.10
COMPLIES
SMOKE AND FIRE DETECTION
ICC 907.2
NFPA 9.6
COMPLIES
FIRE ALARM SYSTEM
ICC 907.2
NFPA 9.6 COMPLIES
VERTICAL ACCESS REQUIRED ICC 1104.4 COMPLIES
ACCESSIBLE ENTRANCE ICC 1105.1 COMPLIES
PASSENGER LOADING ZONES ICC 1106.7
BUILDING ELEMENT TABLE ICC REQ'D NFPA REQ'D PROVIDED
PRIMARY STRUCTURAL FRAME
EXTERIOR BEARING WALLS
SUPPORTING MORE THAN ONE FLOOR,
COLUMNS , OR OTHER BEARING WALLS
SUPPORTING ONE FLOOR ONLY
SUPPORTING A ROOF ONLY
INTERIOR BEARING WALLS
SUPPORTING MORE THAN ONE FLOOR,
COLUMNS , OR OTHER BEARING WALLS
SUPPORTING ONE FLOOR ONLY
SUPPORTING A ROOF ONLY
COLUMNS
SUPPORTING MORE THAN ONE FLOOR,
COLUMNS , OR OTHER BEARING WALLS
SUPPORTING ONE FLOOR ONLY
SUPPORTING A ROOF ONLY
BEAMS, GIRDERS, TRUSSES, AND ARCHES
SUPPORTING MORE THAN ONE FLOOR,
COLUMNS , OR OTHER BEARING WALLS
SUPPORTING ONE FLOOR ONLY
SUPPORTING A ROOF ONLY
FLOOR-CEILING ASSEMBLIES
ROOF-CEILING ASSEMBLIES
INTERIOR NON-BEARING WALLS
EXTERIOR NON-BEARING WALLS
FLOOR CONSTRUCTION AND
ASSOCIATED SECONDARY MEMBERS
ROOF CONSTRUCTION AND
ASSOCIATED SECONDARY MEMBERS
ABBREVIATIONS:
N/A
NC
C
NR
B
NOT APPLICABLE / NOT PART OF THIS PROJECT
NON-COMBUSTIBLE
COMBUSTIBLE
NOT REQUIRED
BARRIER TO LIMIT TRANSFER OF SMOKE
STRUCTURAL DESIGN:
REFER TO SPECIFIC DRAWING AND
SPECIFICATION SECTIONS FOR ADDITIONAL
STRUCTURAL DESIGN CRITERIA INCLUDING BUT
NOT LIMITED TO, LIVE LOAD, DEAD LOAD, AND
LATERAL LOADS APPLICABLE TO THIS PROJECT.
NOTES:
FIRE WALLS
ICC TABLE 601
NFPA TABLE A.8.2.1.2
ICC TABLE 706.4
FIRE BARRIERS ICC TABLE 707.3.10
VERTICAL EXIT ENCLOSURE
ICC 1023
NFPA 7.1.3.2
FIRE PARTITIONS ICC 708
EXIT PASSAGEWAY
ICC 1024
NFPA 7.1.3.2
HORIZONTAL EXIT
SEPARATION
ICC 1026
NFPA 7.2.4
INCIDENTAL USE
AREAS
ICC 509
NFPA 18.3.2.1
OCCUPANCY
SEPARATION
ICC 508
NFPA TABLE 6.1.14.4.1
SHAFT ENCLOSURE ICC 713.4
NFPA TABLE 8.3.4.2
CORRIDOR WALLS
ICC TABLE 1020.1
NFPA 18.3.6.1
SMOKE BARRIERS
ICC 709.3
NFPA 18.3.7
FIRE PROOFING ASSEMBLIES: BEAMS, COLUMNS, FLOOR SYS. ROOF SYS.
CONTRACTOR TO VERIFY /
MAINTAIN / PATCH ANY
AND ALL AREAS OF
FIREPROOFING OR UL
ASSEMBLIES WITHIN
SCOPE OF WORK
COMPLIES
COMPLIES
COMPLIES
(REFER TO CODE PLAN)
(REFER TO CODE PLAN)
(REFER TO CODE PLAN)
0.346421
50903
2 2
21.68
OFFICE OFFICE
'B' BUSINESS BUSINESS
CHANGE OF USE
TYPE V-B TYPE V [000]
MAINTAIN
EXISTING
38.1.6 60'
N/A
N/A
44'-6"
YES
27000
22708 SF
0.3 0.3
0.3 289
32" 32"
44" 44"
44" 44"
300' 300'
100' 100'
50' 50'
NR NR NR
N/A N/A N/A
CLASS B
CLASS C
CLASS C
1/3,000 SF
75'
1/3,000 SF
75'
NO NO
YES YES
YES YES
YES
YES
NO
0 EXISTING
EXISTING
EXISTING
N/A
N/A
EXISTING
EXISTING
N/A
N/A
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
2 2
1 1
1 1
EXISTING
COMPLIES
1 1 N/A
2 1 N/A
1 1
SEE CODE
PLAN
N/A N/A N/A
2 2 2
0 0 0
1 1 N/A
NO NO
-ACCESSIBLE MEANS OF EGRESS ARE NOT REQUIRED TO BE PROVIDED IN
EXISTING BUILDINGS (ICC 1009.1)
-REFER TO CODE COMPLIANCE PLAN FOR ADDITIONAL INFORMATION ON
EGRESS, PARTITION RATINGS AND OTHER CODE RELATED INFORMATION.
MIN. NUMBER OF REQUIRED PLUMBING
FIXTURES (ICC TABLE 2902.1)
TOTAL OCCUPANTS:
WATER CLOSETS:
REQUIRED: 1:25(FIRST 50) 1:50 (REMAINING)=
PROVIDED =
LAVATORIES:
REQUIRED: 1:40 (FIRST 80) 1:80 (REMAINING) =
PROVIDED =
DRINKING FOUNTAINS:
REQUIRED: 1:100 =
PROVIDED =
SERVICE SINKS:
REQUIRED =
PROVIDED =
ACCESSIBLE ROUTE:
PATIENT CARE AREA WIDTH
ADMINISTRATIVE AREA WIDTH
MAX. SLOPE
MIN. GRADIENT OF WALK
REQUIRING REST AREA EVERY 200'
TURNING RADIUS
TURNING RADIUS, BARIATRIC
FLOOR SURFACES:
CHANGES IN LEVEL
CARPET CUSHION OR PADDING
PARKING AND PASSENGER
LOADING ZONES:
ACCESS AISLE REQUIREMENT FOR
ACCESSIBLE PARKING SPACES
PASSENGER LOADING AREA
SUPPLEMENT TO THE ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
MINIMUM REQUIREMENTS
ACCESSIBLE PARKING SPACES
SCI/D FACILITIES
HOSPITAL OUTPATIENT FACILITIES
REHABILITATION AND OUTPATIENT
PHYSICAL THERAPY FACILITIES
BUILDINGS - ACCESSIBLE SEATING,
ASSEMBLY AREAS
1% GREATER THAN ABAAS
2% ACCESSIBLE SPACES PER INPATIENT
BED; 0.5 PER LONG-TERM CARE BED; 5.6
PER OUTPATIENT EXAM ROOM. DEDICATED
FOR SCI/D PATIENTS
10% OF TOTAL SPACES
20% OF TOTAL SPACES
20% OF TOTAL SPACES
1% GREATER THAN ABAAS
REQUIREMENT VA ABAAS
10% OF TOTAL SPACES
20% OF TOTAL SPACES
20% OF TOTAL SPACES
6'-0" 5'-0" 1:33 (3%) 1:50
5'-6" 6'-0"
3'-0" 3'-0" 1:20 (5%) 1:33
5'-0" 5'-0"
NOT PERMITTED ON SCI FLOORS
NOT PERMITTED
NO REQUIREMENT
PERMITTED
5'-0" EACH SIDE
YES
5'-0" EACH SIDE
1 PER 2 SPACES
NO REQUIREMENT
CURB RAMPS:
MIN. WIDTH 4'-0" 3'-0"
RAMPS:
MAX. SLOPE
MAX. LENGTH, (1:33-1:26)
MAX. LENGTH, (1:25-1:20)
MIN. CLEAR WIDTH
MIN. SIZE LEVEL LANDING, WHERE
DOORS SWING INTO LANDING
1:20 40' 35' 4'-0" 6'-0" X 6'-0"
1:12 200' 200' 3'-0" 5'-0" X 5'-0"
STAIRS:
HANDRAIL HEIGHT 34" 30"-34"
ELEVATORS (PASSENGER):
MIN. WIDTH OF ELEVATOR DOORS
MIN. CAR SIZE
DOUBLE SET OF HANDRAILS
4'-0"
8'-0" X 6'-2" (PLATFORM SIZE)
YES
3'-0"
68" X 51" (CAR INSIDE DIM.)
NO REQUIREMENT
DOORS AND DOORWAYS:
PATIENT CARE DELIVERY AREAS
WITH PATIENT BED, STRETCHER OR
GURNEY ACCESS, MIN. WIDTH
4'-0" 3'-8"
WINDOWS:
SILL HEIGHT IN PATIENT
BEDROOMS
24" MAX. NO REQUIREMENT
WATER CLOSETS:
GRAB BAR CONFIGURATION DOUBLE SWING-UP BARS FOR
ALL PATIENT TOILETS/SHOWER
ROOMS ON NURSING UNITS
SIDE & BACK BARS FOR ALL
ACCESSIBLE WATER CLOSETS
TOILET STALLS:
MIN. ACCESSIBLE STALL SIZE
MIN. SIZE WHEELCHAIR "FRONT
TRANSFER" STALL
GRAB BARS
5'-6" X 6'-0" 3'-6" X 6'-0"
REQUIRED IN ALL STALLS
5'-0" X 4'-8" 3'-0" X 5'-6"
REQUIRED IN ACCESSIBLE STALLS
SHOWER STALLS (PATIENT):
MIN. STALL DIMENSIONS
GRAB BARS
4'-0" X 4'-0"
HORIZONTAL PLUS VERTICAL BARS
3'-0" X 3'-0" OR 2'-6" X 5'-0"
HORIZONTAL BARS ONLY
TOILET ROOMS:
INPATIENT BEDROOM TOILET
ROOMS, MIN. WIDTH OF ENTRANCE
48" 34"
CAFETERIAS:
KNEE CLEARANCE (MIN. 5% TABLES)
CUTLERY AND SUPPLY HEIGHT
2'-3" AND 2'-5" FOR AT LEAST 5%
40" - 48"
2'-3"
54" MAX.
HEALTH CARE FACILITIES:
MED/SURG % OF ACCESSIBLE
BEDROOMS
MED/SURG % OF ACCESSIBLE
TOILETS
100%
100%
10%
10%
BASEMENT 7,207 GROSS SF
FLOOR TOTAL
GROSS AREA
NET AREA OF
ASSEMBLY USE
568 NET SF
TOTAL GROSS LESS
NET ASSEMBLY
6,639 SF
OCCUPANCY
(BUSINESS USE, 1:100)
67 OCCUPANTS
OCCUPANCY
(ASSEMBLY USE, 1:15)
38 OCCUPANTS
TOTAL OCCUPANCY
105 OCCUPANTS
FIRST FLOOR 7,013 GROSS SF 557 NET SF 6,456 SF 65 OCCUPANTS 38 OCCUPANTS 103 OCCUPANTS
SECOND FLOOR 6,708 GROSS SF 235 NET SF 6,473 SF 65 OCCUPANTS 16 OCCUPANTS 81 OCCUPANTS
TOTAL OCCUPANTS 289 OCCUPANTS
www.chacompanies.com
Powers Building, 16 West Main Street, Suite 830
Main: (585) 262-2640
Rochester, NY 14614-1607
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0084
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
PLAN
NORTH
NORTHAMPTON VAMC
RENOVATION OF BLDG. 20
LEEDS, MASSACHUSETTS
631-17-004
20A Se rv ic e D i s a b l e d
Ve t e r an Owned S m a l l B u s iness
SDVOSB
CVE
U.S. Department of Veterans Affairs
ACTUAL
NORTH
C U s e rs \A
B ra d fo rd \D o c u m e n ts \R e v it L o c a l F ile s \2
N o rt h a m p to n V
A M
C B ld g
A rc h a b ra d fo rd .r v t
09-21-2018 Checker Author
G-003
BASEMENT & FIRST FLOOR CODE
COMPLIANCE PLANS
BID DOCUMENTS
LEGEND
SCALE: 1/8" = 1'-0"G-003
1 BASEMENT CODE COMPLIANCE PLAN
SCALE: 1/8" = 1'-0"G-003
2 FIRST FLOOR CODE COMPLIANCE PLAN
VA BARRIER FREE DESIGN STANDARDS
OCCUPANCY CALCULATION
1HR 1HR1HR 1HR
2HR 2HR2HR 2HR
SP SPSP SP
(E)1HR (E)1HR(E)1HR (E)1HR
UP
DN DN
1HR 1HR
H
R
H R
H
R
H R
1HR 1HR
H
R
H R
H
R
H R
2HR2HR
2HR2HR 2
H
R
H R
H
R
H R
H
R
H R
2HR2HR
H
R
H R
H
R
H R
1HR1HR
H
R
H R
2HR2HR
2HR 2HR
H
R
H R
H
R
H R
2HR 2HR
H
R
H R
S P
S P
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
H
R
H R
H
R
H R
2HR2HR
H
R
H R
H
R
H R
2HR2HR
H
R
H R
H
R
H R
1HR 1HR1HR S
P
S P
DN
H
R
H R
H
R
H R
2HR2HR
H
R
H R
H
R
H R
2HR2HR
H
R
H R
H
R
H R
2HR2HR
2HR2HR
H
R
H R
H
R
H R
1HR1HR
2HR2HR
2HR2HR 2
H
R
H R
H
R
H R
2HR 2HR
H
R
H R
H
R
H R
2HR 2HR
H
R
H R
H
R
H R
H
R
H R
H
R
H R
1HR 1HR
1HR1HR
H
R
H R
S P
S P
EXIT DISCHARGE
TRAVEL DISTANCE AND DIRECTION OF TRAVEL
COMMON PATH OF EGRESS
REMOTE POINT OF TRAVEL
XX'-XX"
EXIT
EXITE
FIRE EXTINGUISHER CABINET
(1 PER 75 FT RADIUS)
FX
1 HOUR FIRE RATED ASSEMBLY
2 HOUR FIRE RATED ASSEMBLY
SMOKE PARTITION - NON-FIRE RATED
ASSEMBLY DESIGNED AND CONSTRUCTED TO
LIMIT THE PASSAGE OF SMOKE
50 x 0.2" 10" (32")
OCCUPANT LOAD AT EXIT
MIN. WIDTH PER OCCUPANT
MIN. CODE EXIT WIDTH
MIN. CALCULATED EXIT WIDTH
EXISTING WALL - PRESUMED 1 HOUR FIRE
RATED ASSEMBLY
EXIT SIGN
CODE REVIEW INFORMATION
2015 INTERNATIONAL BUILDING CODE & NFPA 101 LIFE SAFETY CODE 2015
BUILDING DATA FIRE RESISTANCE RATINGS
ICC REQ'D NFPA REQ'D PROVIDED
USE DESCRIPTION
OCCUPANCY
ICC CH. 3
NFPA 6.1.1
CLASSIFICATION OF WORK NFPA 4.6.7
CONSTRUCTION TYPE
ICC CH. 6
NFPA TABLE A.8.2.1.2
NO. OF STORIES
BUILDING HEIGHT
ICC CH. 5
NFPA TABLE
AUTOMATIC SPRINKLER SYSTEM
ICC CH. 9
NFPA 9.7.1
ALLOWABLE BUILDING AREA (At) ICC TABLE 506.2
INCREASE FOR FRONTAGE (If) ICC CH. 5
TOTAL ALLOWABLE BUILDING AREA (Aa) ICC CH. 5
SF
SF
TOTAL GROSS BUILDING AREA ICC CH. 5
NUMBER OF OCCUPANTS
ICC TABLE 1004.1.2
NFPA TABLE 7.3.1.2
SEE OCCUPANCY
CALCULATION BELOW
MIN. NUMBER OF EXITS ICC TABLE 1006.3.1
NFPA 7.4.1.2
MIN. EXIT WIDTH PER OCCUPANT ICC 1006.3.1
NFPA 7.4.1.2
PER OCC. PER OCC.
x
MIN. DOOR WIDTH ICC 1010.1.1
NFPA 7.2.1.2.3.2 / 18.2.3.6
COMPLIES
MIN. STAIRWAY WIDTH
ICC 1011.2
NFPA 7.2.2.2
COMPLIES
MIN. CORRIDOR WIDTH
ICC 1020.2
NFPA 7.3.4.1
COMPLIES
MAX. TRAVEL DISTANCE
ICC TABLE 1017.2
NFPA TABLE A.7.6 COMPLIES
MAX. COMMON
PATH OF TRAVEL
ICC TABLE 1006.2.1
NFPA TABLE A.7.6 COMPLIES
MAX. DEAD END CORRIDOR
ICC 1020.4
NFPA TABLE A.7.6 COMPLIES
ICC 718
NFPA 8.6.11
CONCEALED SPACE
DRAFTSTOPPING
SMOKE COMPARTMENT ICC 407.5 / NFPA 18.3.7.1
INTERIOR FINISHES CLASS
INTERIOR EXIT STAIRWAYS AND RAMPS AND
EXIT PASSAGEWAYS
ICC TABLE 803.11
CORRIDORS AND ENCLOSURE FOR EXIT ACCESS
STAIRWAYS AND RAMPS
ROOMS AND ENCLOSED SPACES
COMPLIES
COMPLIES
COMPLIES
ICC TABLE 906.3
NFPA 9.9
FIRE EXTINGUISHER SPACING COMPLIES
STANDPIPE SYSTEM
ICC 905.3.1
NFPA 9.10
COMPLIES
SMOKE AND FIRE DETECTION
ICC 907.2
NFPA 9.6
COMPLIES
FIRE ALARM SYSTEM
ICC 907.2
NFPA 9.6 COMPLIES
VERTICAL ACCESS REQUIRED ICC 1104.4 COMPLIES
ACCESSIBLE ENTRANCE ICC 1105.1 COMPLIES
PASSENGER LOADING ZONES ICC 1106.7
BUILDING ELEMENT TABLE ICC REQ'D NFPA REQ'D PROVIDED
PRIMARY STRUCTURAL FRAME
EXTERIOR BEARING WALLS
SUPPORTING MORE THAN ONE FLOOR,
COLUMNS , OR OTHER BEARING WALLS
SUPPORTING ONE FLOOR ONLY
SUPPORTING A ROOF ONLY
INTERIOR BEARING WALLS
SUPPORTING MORE THAN ONE FLOOR,
COLUMNS , OR OTHER BEARING WALLS
SUPPORTING ONE FLOOR ONLY
SUPPORTING A ROOF ONLY
COLUMNS
SUPPORTING MORE THAN ONE FLOOR,
COLUMNS , OR OTHER BEARING WALLS
SUPPORTING ONE FLOOR ONLY
SUPPORTING A ROOF ONLY
BEAMS, GIRDERS, TRUSSES, AND ARCHES
SUPPORTING MORE THAN ONE FLOOR,
COLUMNS , OR OTHER BEARING WALLS
SUPPORTING ONE FLOOR ONLY
SUPPORTING A ROOF ONLY
FLOOR-CEILING ASSEMBLIES
ROOF-CEILING ASSEMBLIES
INTERIOR NON-BEARING WALLS
EXTERIOR NON-BEARING WALLS
FLOOR CONSTRUCTION AND
ASSOCIATED SECONDARY MEMBERS
ROOF CONSTRUCTION AND
ASSOCIATED SECONDARY MEMBERS
ABBREVIATIONS:
N/A
NC
C
NR
B
NOT APPLICABLE / NOT PART OF THIS PROJECT
NON-COMBUSTIBLE
COMBUSTIBLE
NOT REQUIRED
BARRIER TO LIMIT TRANSFER OF SMOKE
STRUCTURAL DESIGN:
REFER TO SPECIFIC DRAWING AND
SPECIFICATION SECTIONS FOR ADDITIONAL
STRUCTURAL DESIGN CRITERIA INCLUDING BUT
NOT LIMITED TO, LIVE LOAD, DEAD LOAD, AND
LATERAL LOADS APPLICABLE TO THIS PROJECT.
NOTES:
FIRE WALLS
ICC TABLE 601
NFPA TABLE A.8.2.1.2
ICC TABLE 706.4
FIRE BARRIERS ICC TABLE 707.3.10
VERTICAL EXIT ENCLOSURE
ICC 1023
NFPA 7.1.3.2
FIRE PARTITIONS ICC 708
EXIT PASSAGEWAY
ICC 1024
NFPA 7.1.3.2
HORIZONTAL EXIT
SEPARATION
ICC 1026
NFPA 7.2.4
INCIDENTAL USE
AREAS
ICC 509
NFPA 18.3.2.1
OCCUPANCY
SEPARATION
ICC 508
NFPA TABLE 6.1.14.4.1
SHAFT ENCLOSURE ICC 713.4
NFPA TABLE 8.3.4.2
CORRIDOR WALLS
ICC TABLE 1020.1
NFPA 18.3.6.1
SMOKE BARRIERS
ICC 709.3
NFPA 18.3.7
FIRE PROOFING ASSEMBLIES: BEAMS, COLUMNS, FLOOR SYS. ROOF SYS.
CONTRACTOR TO VERIFY /
MAINTAIN / PATCH ANY
AND ALL AREAS OF
FIREPROOFING OR UL
ASSEMBLIES WITHIN
SCOPE OF WORK
COMPLIES
COMPLIES
COMPLIES
(REFER TO CODE PLAN)
(REFER TO CODE PLAN)
(REFER TO CODE PLAN)
0.346421
50903
2 2
21.68
OFFICE OFFICE
'B' BUSINESS BUSINESS
CHANGE OF USE
TYPE V-B TYPE V [000]
MAINTAIN
EXISTING
38.1.6 60'
N/A
N/A
44'-6"
YES
27000
22708 SF
0.3 0.3
0.3 289
32" 32"
44" 44"
44" 44"
300' 300'
100' 100'
50' 50'
NR NR NR
N/A N/A N/A
CLASS B
CLASS C
CLASS C
1/3,000 SF
75'
1/3,000 SF
75'
NO NO
YES YES
YES YES
YES
YES
NO
0 EXISTING
EXISTING
EXISTING
N/A
N/A
EXISTING
EXISTING
N/A
N/A
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
2 2
1 1
1 1
EXISTING
COMPLIES
1 1 N/A
2 1 N/A
1 1
SEE CODE
PLAN
N/A N/A N/A
2 2 2
0 0 0
1 1 N/A
NO NO
-ACCESSIBLE MEANS OF EGRESS ARE NOT REQUIRED TO BE PROVIDED IN
EXISTING BUILDINGS (ICC 1009.1)
-REFER TO CODE COMPLIANCE PLAN FOR ADDITIONAL INFORMATION ON
EGRESS, PARTITION RATINGS AND OTHER CODE RELATED INFORMATION.
MIN. NUMBER OF REQUIRED PLUMBING
FIXTURES (ICC TABLE 2902.1)
TOTAL OCCUPANTS:
WATER CLOSETS:
REQUIRED: 1:25(FIRST 50) 1:50 (REMAINING)=
PROVIDED =
LAVATORIES:
REQUIRED: 1:40 (FIRST 80) 1:80 (REMAINING) =
PROVIDED =
DRINKING FOUNTAINS:
REQUIRED: 1:100 =
PROVIDED =
SERVICE SINKS:
REQUIRED =
PROVIDED =
49 SF
TOILET
149 SF
STAIR
103 SF
OFFICE - SUP.
ELEVATOR
40 x 0.3" 12" (32")
1689 SF
OPEN CALL
CENTER
1400 SF
OPEN CALL
CENTER
101 SF
COPY / STOR.
151 SF
SHARED
OFFICE
167 SF
SHARED
OFFICE
153 SF
SHARED
OFFICE
165 SF
SHARED
OFFICE
51 SF
IT CL
84 SF
COPY / STOR.
249 SF
STAFF
LOUNGE
111 SF
OFFICE - SUP.
100 SF
OFFICE - SUP.
52 SF
ELEV. VEST.
EXIST
STAIR
EXIST
STAIR
47 SF
TOILET
349 SF
CORR.
84'-0"
MAX OVERALL
DIAGONAL
181'-3"
EXIT SEPARATION
DISTANCE
134'
OCC. LOAD
235 SF
MULTI-PURPOSE
44 SF
JAN.
41 x 0.3" 12.3" (32")
FX
FX
C
LE
A R
5'
FXC
LE
A R
5'
ACCESSIBLE ROUTE:
PATIENT CARE AREA WIDTH
ADMINISTRATIVE AREA WIDTH
MAX. SLOPE
MIN. GRADIENT OF WALK
REQUIRING REST AREA EVERY 200'
TURNING RADIUS
TURNING RADIUS, BARIATRIC
FLOOR SURFACES:
CHANGES IN LEVEL
CARPET CUSHION OR PADDING
PARKING AND PASSENGER
LOADING ZONES:
ACCESS AISLE REQUIREMENT FOR
ACCESSIBLE PARKING SPACES
PASSENGER LOADING AREA
SUPPLEMENT TO THE ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
MINIMUM REQUIREMENTS
ACCESSIBLE PARKING SPACES
SCI/D FACILITIES
HOSPITAL OUTPATIENT FACILITIES
REHABILITATION AND OUTPATIENT
PHYSICAL THERAPY FACILITIES
BUILDINGS - ACCESSIBLE SEATING,
ASSEMBLY AREAS
1% GREATER THAN ABAAS
2% ACCESSIBLE SPACES PER INPATIENT
BED; 0.5 PER LONG-TERM CARE BED; 5.6
PER OUTPATIENT EXAM ROOM. DEDICATED
FOR SCI/D PATIENTS
10% OF TOTAL SPACES
20% OF TOTAL SPACES
20% OF TOTAL SPACES
1% GREATER THAN ABAAS
REQUIREMENT VA ABAAS
10% OF TOTAL SPACES
20% OF TOTAL SPACES
20% OF TOTAL SPACES
6'-0" 5'-0" 1:33 (3%) 1:50
5'-6" 6'-0"
3'-0" 3'-0" 1:20 (5%) 1:33
5'-0" 5'-0"
NOT PERMITTED ON SCI FLOORS
NOT PERMITTED
NO REQUIREMENT
PERMITTED
5'-0" EACH SIDE
YES
5'-0" EACH SIDE
1 PER 2 SPACES
NO REQUIREMENT
CURB RAMPS:
MIN. WIDTH 4'-0" 3'-0"
RAMPS:
MAX. SLOPE
MAX. LENGTH, (1:33-1:26)
MAX. LENGTH, (1:25-1:20)
MIN. CLEAR WIDTH
MIN. SIZE LEVEL LANDING, WHERE
DOORS SWING INTO LANDING
1:20 40' 35' 4'-0" 6'-0" X 6'-0"
1:12 200' 200' 3'-0" 5'-0" X 5'-0"
STAIRS:
HANDRAIL HEIGHT 34" 30"-34"
ELEVATORS (PASSENGER):
MIN. WIDTH OF ELEVATOR DOORS
MIN. CAR SIZE
DOUBLE SET OF HANDRAILS
4'-0"
8'-0" X 6'-2" (PLATFORM SIZE)
YES
3'-0"
68" X 51" (CAR INSIDE DIM.)
NO REQUIREMENT
DOORS AND DOORWAYS:
PATIENT CARE DELIVERY AREAS
WITH PATIENT BED, STRETCHER OR
GURNEY ACCESS, MIN. WIDTH
4'-0" 3'-8"
WINDOWS:
SILL HEIGHT IN PATIENT
BEDROOMS
24" MAX. NO REQUIREMENT
WATER CLOSETS:
GRAB BAR CONFIGURATION DOUBLE SWING-UP BARS FOR
ALL PATIENT TOILETS/SHOWER
ROOMS ON NURSING UNITS
SIDE & BACK BARS FOR ALL
ACCESSIBLE WATER CLOSETS
TOILET STALLS:
MIN. ACCESSIBLE STALL SIZE
MIN. SIZE WHEELCHAIR "FRONT
TRANSFER" STALL
GRAB BARS
5'-6" X 6'-0" 3'-6" X 6'-0"
REQUIRED IN ALL STALLS
5'-0" X 4'-8" 3'-0" X 5'-6"
REQUIRED IN ACCESSIBLE STALLS
SHOWER STALLS (PATIENT):
MIN. STALL DIMENSIONS
GRAB BARS
4'-0" X 4'-0"
HORIZONTAL PLUS VERTICAL BARS
3'-0" X 3'-0" OR 2'-6" X 5'-0"
HORIZONTAL BARS ONLY
TOILET ROOMS:
INPATIENT BEDROOM TOILET
ROOMS, MIN. WIDTH OF ENTRANCE
48" 34"
CAFETERIAS:
KNEE CLEARANCE (MIN. 5% TABLES)
CUTLERY AND SUPPLY HEIGHT
2'-3" AND 2'-5" FOR AT LEAST 5%
40" - 48"
2'-3"
54" MAX.
HEALTH CARE FACILITIES:
MED/SURG % OF ACCESSIBLE
BEDROOMS
MED/SURG % OF ACCESSIBLE
TOILETS
100%
100%
10%
10%
EXIST
ATTIC
TYP.
40 SF
MECH.
149 SF
STAIR
FLOOR
PENETRATIONS
BASEMENT 7,207 GROSS SF
FLOOR TOTAL
GROSS AREA
NET AREA OF
ASSEMBLY USE
568 NET SF
TOTAL GROSS LESS
NET ASSEMBLY
6,639 SF
OCCUPANCY
(BUSINESS USE, 1:100)
67 OCCUPANTS
OCCUPANCY
(ASSEMBLY USE, 1:15)
38 OCCUPANTS
TOTAL OCCUPANCY
105 OCCUPANTS
FIRST FLOOR 7,013 GROSS SF 557 NET SF 6,456 SF 65 OCCUPANTS 38 OCCUPANTS 103 OCCUPANTS
SECOND FLOOR 6,708 GROSS SF 235 NET SF 6,473 SF 65 OCCUPANTS 16 OCCUPANTS 81 OCCUPANTS
TOTAL OCCUPANTS 289 OCCUPANTS
www.chacompanies.com
Powers Building, 16 West Main Street, Suite 830
Main: (585) 262-2640
Rochester, NY 14614-1607
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0084
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
PLAN
NORTH
NORTHAMPTON VAMC
RENOVATION OF BLDG. 20
LEEDS, MASSACHUSETTS
631-17-004
20A Se rv ic e D i s a b l e d
Ve t e r an Owned S m a l l B u s iness
SDVOSB
CVE
U.S. Department of Veterans Affairs
ACTUAL
NORTH
C U s e rs \A
B ra d fo rd \D o c u m e n ts \R e v it L o c a l F ile s \2
N o rt h a m p to n V
A M
C B ld g
A rc h a b ra d fo rd .r v t
09-21-2018 Checker Author
G-004
SECOND & ATTIC FLOOR CODE
COMPLIANCE PLAN
BID DOCUMENTS
LEGEND
SCALE: 1/8" = 1'-0"G-004
1 SECOND FLOOR CODE COMPLIANCE PLAN
VA BARRIER FREE DESIGN STANDARDS
SCALE: 1/8" = 1'-0"G-004
3 ATTIC CODE COMPLIANCE PLAN
OCCUPANCY CALCULATION
| GI001 |
| GI001 |
| GI001 |
| G-002 |
| G-003 |
| G-004 |