Appendix A - Specifications MasterPact NT and NW Universal Power Circuit Breakers.pdf
PDF 789 KB Posted
- Attached to
- AITC Critical Spare Circuit Breaker
- Solicitation number
- 36C10X25Q0110
About this file
This document is a technical specification sheet for MasterPact NT and NW Universal Power Circuit Breakers, detailing their technical characteristics, ratings, and design features. The circuit breakers are designed to protect electrical systems from damage caused by overloads, short circuits, and ground faults, with amperage ranges from 800-6300A. Key technical features include adjustable overcurrent protection, integral ground-fault protection, high interrupting ratings, communications capabilities, power monitoring, protective relaying functions, and zone-selective interlocking.
The specifications cover multiple circuit breaker variants across different standards (ANSI, UL, IEC), providing comprehensive technical details including interrupting current ratings, short-time withstand current, close and latch ratings, and endurance ratings. The document includes detailed tables showing performance characteristics for different frame ratings, connector types, and voltage configurations. Circuit breakers are available in drawout or fixed mount configurations, with 3-pole and 4-pole options, and are tested to meet various industrial and safety standards including IEC 60947-2, ANSI C37, and UL listings. The specifications also provide temperature and altitude correction factors, shipping weights, and design schematics for MasterPact NW and NT circuit breaker models.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MasterPact™ Circuit Breakers Class 0613
MasterPact™ Circuit Breakers
Introduction
800–1600 A MasterPact NT Drawout Circuit Breaker
MasterPact™ NT/NW Universal Power Circuit Breakers are designed to protect electrical systems from damage caused by overloads, short circuits and equipment ground faults. All MasterPact circuit breakers are designed to open and close a circuit manually, and to open the circuit automatically at a predetermined overcurrent setting. MasterPact circuit breakers can also:
• Enhance coordination by their adjustability.
• Provide integral ground-fault protection for equipment.
• Provide high interrupting ratings and withstand ratings.
• Provide communications.
• Provide power monitoring.
• Provide protective relaying functions.
• Provide zone-selective interlocking (ZSI) which can reduce damage in the event of a fault.
Figure 1 - MasterPact NW Drawout Circuit Breakers
NX 0 8 HA10
Ui 1000V Uimp 12kV
Ue
(V)
50kA/1 s
IEC 94 7-2 50 /60Hz
EN 60947-2
UTE VDE BS CEI UNE AS NBMA
800–3200 A MasterPact NW Drawout Circuit Breaker 4000–6300 A MasterPact NW Drawout
Circuit Breaker
Codes and Standards MasterPact circuit breakers are manufactured and tested in accordance with the following standards:
Low-Voltage Power Circuit Breaker
Insulated Case Circuit Breaker
IEC Rated Circuit Breaker
IEC Extreme Atmospheric Conditions
ANSI C37.13
ANSI C37.16
ANSI C37.17
ANSI C37.50
UL 1066 (cULus Listed)
NEMA SG3
UL 489 (UL Listed)
NEMA AB1
CSA C22.2 No. 5
NMX J-266-ANCE
IEC 60947-2
IEC 60947-3
IEC 68-2-1: Dry cold at –55°C IEC 68-2-2: Dry heat at +85°C IEC 68-2-30: Damp heat (temp. +55°C, rel.
humidity 95%) IEC 68-2-52 Level 2:
Salt mist
NOTE: Throughout this document, the phrase “ANSI® Certified” means the product meets the requirements of UL 1066 and ANSI C37. When “UL® Listed” appears, the product meets the requirements of UL 489.
0613CT0001 9
Class 0613 MasterPact™ Circuit Breakers
The 800–2000 A ANSI Low Voltage Power Circuit Breakers type L1F and Insulated Case Circuit Breaker type LF are tested to show the arc flash hazard risk category as referenced by NFPA® 70E.
Circuit breakers should be applied according to guidelines detailed in the National Electrical Code® (NEC®) and other local wiring codes.
MasterPact circuit breakers are available in Square D™ or Schneider Electric™ brands.
UL File Numbers:
• MasterPact NW: E161835 Vol. 2 Sec. 1
• MasterPact NT: E161835 Vol. 2 Sec. 2
Features and Benefits High Ampere Interrupting Rating (AIR): ANSI Certified MasterPact NW circuit breakers have an interrupting rating of 200,000 A at 508 Vac without fuses.
High Short-Time Current Rating: MasterPact NW circuit breakers have exceptional short-time ratings—up to 100,000 A.
100% Rated Circuit Breaker: MasterPact circuit breakers are designed for continuous operation at 100% of their current rating.
Reverse Fed Circuit Breaker: MasterPact circuit breakers can be fed either from the top of the circuit breaker or from the bottom.
Two-Step Stored Energy Mechanism: MasterPact circuit breakers are operated via a stored-energy mechanism which can be charged manually or by a motor.
The closing time is less than five cycles. Closing and opening operations can be initiated by remote control or by push buttons on the circuit breaker front cover. An O–C–O cycle is possible without recharging.
Drawout or Fixed Mount, 3-Pole (3P) or 4-Pole (4P) Construction: ANSI Rated, UL Listed and IEC Rated MasterPact circuit breakers are available in drawout or fixed mounts, with either three-pole or four-pole construction.
Field-Installable Trip Units, Sensor Plugs and Accessories: Trip units, sensor plugs and most accessories are field installable with only the aid of a screwdriver and without adjusting the circuit breaker. The uniform design of the circuit breaker line allows most accessories to be common for the whole line.
Reinforced Insulation: Two insulation barriers separate the circuit breaker front from the current path.
Isolation Function by Positive Indication of Contact Status: The mechanical indicator is truly representative of the status of all the main contacts.
Segregated Compartment: Once the accessory cover has been removed to provide access to the accessory compartment, the main contacts remain fully isolated. Furthermore, interphase partitioning allows full insulation between each pole even if the accessory cover has been removed.
Front Connection of Secondary Circuits: All accessory terminals (ring terminals are available as an option) are located on a connecting block which is accessible from the front in the connected, test and disconnected positions. This is particularly useful for field inspection and modification.
Anti-Pumping Feature: All MasterPact NTand NW circuit breakers are designed with an anti-pumping feature that causes an opening order to always takes priority over a closing order. Specifically, if opening and closing orders occur simultaneously, the charged mechanism discharges without any movement of the main contacts keeping the circuit breaker in the open (OFF) position.
In the event that opening and closing orders are simultaneously maintained, the standard mechanism provides an anti-pumping function which continues to keep the main contacts in the open position.
10 0613CT0001
In addition, after fault tripping or opening the circuit breaker intentionally (using the manual or electrical controls and with the closing coil continuously energized) the circuit breaker cannot be closed until the power supply to the closing coil is discontinued and then reactivated.
NOTE:When the automatic reset after fault trip (RAR) option is installed, the automatic control system must take into account the information supplied by the circuit breaker before issuing a new closing order or before blocking the circuit breaker in the open position. The information is on the type of fault, e.g.
overload, short-circuit or ground fault.
Disconnection Through the Front Door: The racking handle and racking mechanism are accessible through the front door cutout. Disconnecting the circuit breaker is possible without opening the door and exposing live parts.
Figure 2 - Racking Handle and Mechanism
Door Escutcheon
Closing and Opening Push Buttons
Racking Handle Storage Space
Racking Handle
Racking Mechanism
Disconnected Position (Cluster Shield Not Shown)
Drawout Mechanism: The drawout assembly mechanism allows the circuit breaker to be racked in four positions (connected, test, disconnected, or withdrawn), as shown in the figure below.
NOTE: For UL/ANSI circuit breakers, the clusters are mounted on the circuit breaker; for IEC circuit breakers, the clusters are mounted on the cradle.
Figure 3 - Racking Positions (Cluster Shield Not Shown)
Secondary Contacts
Connected Position
Stabs (IEC) Clusters (UL/ANSI)
Clusters (IEC) Stabs (UL/ANSI)
Test Position
Disconnected Position Withdrawn Position
Maintenance: To maintain MasterPact's operating and safety characteristics from the beginning to the end of its service life, Schneider Electric recommends that systematic checks and periodic on-site maintenance be carried out by qualified personnel, as indicated in bulletin 0613IB1202, "Maintenance and Field Testing Guide for MasterPact NTand NW Circuit Breakers".
0613CT0001 11
Schneider Electric Field Services offers a wide portfolio of field maintenance services named ONSITE MAINTENANCE which offers four types of services:
• OnSite Repair, which repairs a system in view of fulfilling a required function
• OnSite Preventive Maintenance, which carries out, at predetermined intervals, checks intended to reduce the probability of a failure or deterioration in the operation of a system
• Onsite Condition Maintenance, based on the recording and analysis of system parameters in addition to preventive checks, detects drift from the initial state and/or significant trends in performance. Using OnSite Condition Maintenance makes it possible to anticipate any necessary corrective action required to ensure equipment safety and continuity of service, and make repairs immediately if spare parts are onsite, or to plan the repair for a more convenient time.
• On-Site Asset Diagnostic, which is used to identify symptoms of malfunction or degradation before problems occur, things not possible to detect during standard preventive maintenance. It detects functional deviations versus original (new device) specifications. A repair plan is recommended to recover the original conditions when deviations are diagnosed.
The Maintenance Guide is available on the Internet (www.se.com) and provides detailed information on:
• types of maintenance required, depending on the criticality of the protected circuit, risks involved if the component ceases to operate correctly,
• what is understood by the terms normal, improved and severe environment and operating conditions,
• periodic preventive maintenance operations that should be carried out under normal environment and operating conditions as well as the level of competence required for the operations,
• the environment and operating conditions that accelerate device aging,
• the recommended timing of on-site maintenance according to equipment criticality and the environmental conditions in which the equipment operates.
Arc Chamber An example of preventive maintenance: the arc chambers are removed to allow visual inspection of the contacts and wear indicator groove (see Contact Wear Indicators, page 12 for how wear is indicated). The operation counter can also indicate when inspections and possible maintenance should be done. The life of the circuit breaker may be extended by replacing the arc chamber and/or spring-charging motor of ANSI Certified circuit breakers. See bulletin 0613IB1202, available at www.se.com, for information on normal and adverse operating conditions.
Figure 4 - Contact Wear Indicators
Wear Indicator Groove Wear Indicator Groove
Good Contacts
Worn Contacts
12 0613CT0001
Ambient Temperature:
MasterPact circuit breakers can operate under the following temperature conditions:
• The electrical and mechanical characteristics are stipulated for an ambient temperature between -13°F (25°C) and 158°F (70°C).
• Mechanical closing of the circuit breaker (by pushbutton) is possible down to
-31°F (-35°C) and at an altitude up to +13,000 ft. (3900 m).
MasterPact circuit breakers have been tested for operation in industrial atmospheres. It is recommended that the equipment be cooled or heated to the proper operating temperature and kept free of excessive vibration and dust.
Operation at temperatures above 104°F (40°C) may require derating or overbussing the circuit breaker. See the appropriate instruction bulletin and Temperature Correction Factors, page 25 of this catalog for additional information.
Storage Temperature
Circuit breakers with trip units without LCD displays may be stored in the original packaging at temperatures between -40°F (-40°C) and 185°F (85°C).
For circuit breakers with trip units with LCD displays, this range is -13°F (-25°C) to 185°F (85°C).
Altitude:
MasterPact circuit breakers are suitable for use at altitudes of 13,000 ft. (3900 m) and below. See Altitude Correction Factors per ANSI C37.20.1 par. 7.1.4.1 (Table 10), page 25 for altitude correction factors.
Vibration:
MasterPact circuit breakers meet IEC 60068-2-6 Standards for vibration.
• 2 to 13.2 Hz and amplitude 0.039 in. (1 mm)
• 13.2 to 100 Hz constant acceleration 0.024 oz. (0.7 g)
Humidity:
MasterPact circuit breakers have been tested to the following:
• IEC68-2-30—damp heat (temperature +55°C and relative humidity of 95%)
• IEC 68-2-52 level 2—salt mist The materials used in MasterPact NTand NW circuit breakers will not support the growth of fungus and mold.
0613CT0001 13
MasterPact NW Circuit Breaker Design NOTE: For UL Listed and ANSI Certified circuit breakers, the clusters are mounted on the circuit breaker; for IEC Rated circuit breakers, the clusters are mounted on the cradle.
A
F
E
T
C
B
AC
AD
AE
N
O
P Q
R
S
V U
H
G
X
W
M
L
K J
I
AF
AA
Z Y
AB
D
A Overcurrent Trip Switch (SDE1)
B Circuit Breaker Communication Module
C Overcurrent Trip Switch (SDE2) or Electric Reset
D Cluster
E Cradle Rejection Kit
F Lifting Tab
G Trip Connection to Overcurrent Trip Switch
H Auxiliary Control Connection
I Shunt Trip (MX2) or Undervoltage Trip Device
J Arc Chamber
K Shunt Trip (MX1)
L Auxiliary Contact Connection
M
Two Blocks of Four Additional Switches (OF) or Combined “Connected,Closed” Switches
(EF)
N Block of Four Form C Auxiliary Contacts (OF)
O Shunt Close (XF)
P Ready-to-Close Contact (PF)
Q Charging Handle
R Spring-Charging Motor (MCH)
S Closing Push Button
T Opening Push Button
U Operations Counter
V Trip Unit
W Accessory Cover
X Open/Close Push Button Close (Lockable with Padlock)
Y Faceplate
Z Charged/Discharged Indicator
AA Open/Close Indicator
AB Push-to-Reset on Fault Trip
AC Electrical Close Push Button
(BPFE)
AD Padlock Attachment
AE Key Interlock
AF Mounting Plate for Fixed Circuit Breaker
14 0613CT0001
MasterPact NW Cradle Design
P
O
N
M
L
K
J
I
H
F
G
E
D
C
B
A
W
U
T
S
R
Q
V
X
Y
A Stop Release Button
B Padlock Provision
C Key Interlock
D Door Interlock for Connected Device
E Pull-Out Hand Grip
F Rejection Feature
G Primary Stabs (UL)/Clusters
(IEC)
H Lifting Tab
I Cradle Back Mold
J Position Indicating Contact Terminal Block
K Overcurrent Trip Switch Terminal Block
L Arc Chamber Cover
M Tool Shield
N Position Indicating Contact Terminal Block
O Accessory Control Terminal Block
P Auxiliary Contact Terminal Block
Q Terminal Cover
R Position Indicating Contact Terminal Block
S Wiring Cover
T Shutter
U Racking Interlock for Open Door
V Crank Storage Space
W Racking Crank
X Position Indicator
Y Crank Insertion Opening
0613CT0001 15
MasterPact NW with ArcBlock™ Technology The MasterPact NW low-voltage power circuit breaker and insulated case circuit breaker are available with ArcBlok technology designed to mount in an ArcBlok drawout cradle.
The MasterPact NW with ArcBlok technology interfaces with the ArcBlok cradle to prevent arcing events by enclosing the phases at the primary connection of the cradle. If for any reason an arcing event happens, with the separation between phase to phase and phase to ground, the arc is extinguished in less than 12 ms to reduce arc flash energy.
The MasterPact NW with ArcBlok technology is tested as part of Arc Resistant Equipment to ANSI C37.20.7.
A Terminal Cover
Figure 5 - MasterPact NW Circuit Breaker and Cradle with ArcBlok Technology
O
L M
N
D E G
I
A
B
C
J K
P
Racking Handle
Drawout Circuit Breaker
Cradle
Q
I
J K
O
Q
H C
D E G
F P
B
A
B
N
M L
B Lifting Flanges
C Extension Rail Handle
D Padlock Provision
E Stop Release Button
F Racking Handle Insertion Opening
G Position Indicator
H Racking Handle Storage Space
I Fault Trip Reset Button
J Trip Unit
K Push to Open Button
L Push to Close Button
M Charging Handle
N Faceplate
O Accessory Cover
P Cradle Date Code
Q ArcBlok Shield (rotated for clarity)
16 0613CT0001
MasterPact NT Circuit Breaker and Cradle Design
M
N O
P
K
J
I
C
B
A
L
D
E
F
H G
NT Cradle
NT Drawout Circuit Breaker
N
M
L
I
J
K
O
P
NT Fixed Circuit Breaker
A Extension Rail Handle
B Lifting Handle
C Terminal Cover
D Padlock Provision
E Position Indicator
F Racking Handle Insertion Opening
G Stop Release Button
H Racking Handle Storage Space
I Lifting Tab
J Fault Trip Reset Button
K Trip Unit
L Accessory Cover
M Charging Handle
N :Push-to-close” Button
O “Push-to-open” Button
P Faceplate
0613CT0001 17
Ratings
Table 1 - Ratings for ANSI C37 Certified MasterPact NW Circuit Breakers 800–2000 A
Frame Rating 800/1600 A 2000 A
Interrupting Rating Code N1 H1 H2 H3 L112 L1F2 H1 H2 H3 L112 L1F2
Interrupt-ing Current (kAIR)
254 Vac 50/60 Hz 42 65 85 100 200 200 65 85 100 200 200
508 Vac 50/60 Hz 42 65 85 100 200 200 65 85 100 200 200
635 Vac 50/60 Hz 42 65 85 85 130 130 65 85 85 130 130
Short- Time Withstand Current (kA)
Vac 50/60 Hz,
0.5 s 42 65 85 85 30 22 65 85 85 30 22
Built In Instantaneous Override (Peak kA ±10%)
—3 —3 —3 190 805 55 — — 190 80 55
Close and Latch Ratings (Peak kA)
Vac 50/60 Hz 90 150 90 90 55 50 150 90 90 55 50
Tested to show arc flash hazard risk category as referenced by NFPA70E
— — — — — Yes — — — — Yes
Breaking Time 25 to 30 ms (with no intentional delay) 9 ms for L1 and L1F
Closing Time 70 ms
Sensor Rating 100–800 A 800–1600 A 1000–2000 A
Endurance Rating (C/ O Cycles) (with no mainte-nance)
Mechanical 12,500 10,000
Electrical 2800 1000
Table 2 - Ratings for ANSI C37 Certified MasterPact NW Circuit Breakers 3200–6000 A
Frame Rating 3200/4000 A4 4000/5000/6000 A5
Interrupting Rating Code H1 H2 H3 L112 H2 H3 L112
Interrupting Current (kAIR)
254 Vac 50/60 Hz 65 85 100 200 85 100 200
508 Vac 50/60 Hz 65 85 100 200 85 100 200
635 Vac 50/60 Hz 65 85 85 130 85 85 130
Short-Time Withstand Current (kA)
Vac 50/60 Hz, 0.5 s 65 85 85 100 85 85 100
Built In Instantaneous Override (Peak kA ±10%) — — 190 270 — — 270
Close and Latch Ratings (Peak kA)
Vac 50/60 Hz 150 90 90 90 170 170 90
18 0613CT0001
1. Interrupting ratings (kAIR) at 50 Hz: 200 kA (254 Vac), 150 kA (508 Vac), 100 kA (635 Vac).
2. The interrupting ratings L1 and L1F are available only in 3P, drawout construction.
3. 55 kA for 800 A circuit breaker frame with 100 A or 250 A sensor.
4. 4000 A standard width circuit breaker is not available in L1 interrupting rating code or drawout construction.
5. ArcBlok circuit breakers are available only to 5000 A.
Table 2 - Ratings for ANSI C37 Certified MasterPact NW Circuit Breakers 3200–6000 A (Continued)
Frame Rating 3200/4000 A6 4000/5000/6000 A7
Tested to show arc flash hazard risk category as referenced by
NFPA70E
Breaking Time
Closing Time
Sensor Rating 1600–4000 A 2000–4000 A 2500–5000 A 3000–6000 A
Endurance Rating (C/O Cycles) (with no mainte-nance)
Mechanical 10,000 5000 5000
Electrical 1000 1000 1000
Table 3 - Ratings for ANSI C37 Certified MasterPact NW Non-Automatic Switches
Frame Rating 800 A 1600 A 2000 A 3200 A 4000 A 5000 A
Withstand Rating Code HA HA HA HA HA HA
Breaking Capacity with External Relay (kA), 50/60 Hz
254 Vac 65 65 65 65 85 85
508 Vac 65 65 65 65 85 85
635 Vac 65 65 65 65 85 85
Short-Time Withstand Current (kA) Vac 50/60 Hz, 0.5 s 65 65 65 65 85 85
Table 4 - Ratings for ANSI C37 Certified MasterPact NWAutomatic Switches
Frame Rating 800 A 1600 A 2000 A 3200 A 4000 A8 5000 A
Withstand Rating Code HF HC HF HC HF HC HF HC HF HC HF HC
Breaking Capacity with External Relay (kA), 50/60 Hz
254 Vac 100 200 100 200 100 200 100 200 100 200 100 200
508 Vac 100 200 100 200 100 200 100 200 100 200 100 200
635 Vac 85 130 85 130 85 130 85 130 85 130 85 130
Short-Time Withstand Current (kA) 50/60 Hz, 1.5 s 85 30 85 30 85 30 85 100 85 100 85 100
Table 5 - Ratings for UL 489 Listed MasterPact NW Circuit Breakers
Frame Rating 800/1200/1600/2000 A 2500/3000 A 4000/5000/6000 A
Interrupting Rating Code N H L LF H L H L
Interrupting Current (kAIR)
240 Vac 50/60 Hz 65 100 200 200 100 200 100 200
480 Vac 50/60 Hz 65 100 150 150 100 150 100 150
600 Vac 50/60 Hz 50 85 100 100 85 100 85 100
Short-Time Withstand Current (kA)
Vac 50/60 Hz, 0.5 s 429 659 30910 22 65 65 85 100
Built-In Instantaneous Override (Peak kA ±10%) 90 90 801112 55 150 150 170 170
0613CT0001 19
6. 4000 A standard width circuit breaker is not available in L1 interrupting rating code or drawout construction.
7. ArcBlok circuit breakers are available only to 5000 A.
8. 4000 A standard width automatic switch is not available in HC withstand rating code or drawout construction.
9. 24 kA for 800 A circuit breaker frame with 100 A or 250 A sensor.
10. 65 kA for 2000 A.
11. 55 kA for 800 A circuit breaker frame with 100 A or 250 A sensor.
12. 150 kA for 200 A sensor.
Table 5 - Ratings for UL 489 Listed MasterPact NW Circuit Breakers (Continued)
Frame Rating 800/1200/1600/2000 A 2500/3000 A 4000/5000/6000 A
Close and Latch Ratings (Peak kA) Vac 50/60 Hz 90 90 5513 50 90 90 90 90
Tested to show arc flash hazard risk category as referenced by NFPA70E — — — Yes — — — —
Breaking Time 25 to 30 ms (with no intentional delay) 9 ms for L and LF
Closing Time 70 ms
Sensor Rating 100–250 A / 400–800 A / 600–1200 A / 800– 1600 A / 1000–2000 A
1200–2500 A / 1600–3000 A
2000–4000 A / 2500–5000 A / 3000–6000 A
Endurance Rating (C/O Cycles) (with no maintenance)
Mechanical 12,50014 12,50014 12,50014 12,50014 10,000 10,000 5000 5000
Electrical 280014 280014 280014 280014 1000 1000 1000 1000
Table 6 - Ratings for UL 489 Listed MasterPact NWAutomatic Switches
Frame Rating 800 A 1200 A 1600 A 2000 A 2500 A 3000 A 4000 A 5000 A 6000 A
Withstand Rating Code HF HB HF HB HF HB HF HB HF HB HF HB HF HB HF HB HF HB
With-stand Ratings15 (kA) Vac, 50/60 Hz
240 10- 0 200 100 200 10-
0 200 100 20- 0 100 20-
0 100 20- 0 100 200 100 20-
0 100 200
480 10- 0 150 100 150 10-
0 150 100 15- 0 100 15-
0 100 15- 0 100 150 100 15-
0 100 150
600 85 100 85 100 85 100 85 10- 0 85 10-
0 85 10- 0 85 100 85 10-
0 85 100
Instantaneous Override (Peak kA)
90 80 90 50 90 80 90 80 150 15- 0 150 15-
0 170 170 170 17- 0 170 170
Table 7 - Ratings for IEC 60947-2 Rated MasterPact NW Circuit Breakers 800–2000 A
Frame Rating 800/1000/1250/1600 A 2000 A
Interrupting Rating Code N1 H1 H2 L1 H10 N1 H1 H2 H3 L1 H10
Ultimate Breaking Capacity (kA) 50/60 Hz
Icu
220/415 Vac 42 65 100 150 — 42 65 100 150 150 —
440 Vac 42 65 100 150 — 42 65 100 150 150 —
525 Vac 42 65 85 130 — 42 65 85 130 130 —
690 Vac 42 65 85 100 — 42 65 85 100 100 —
1150 Vac — — — — 50 — — — — — 50
Service Breaking Capacity
Ics %Icu 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Short-Time Withstand Current (kA)
Icw
Vac 50/60 Hz, 1 s 42 65 85 30 50 42 65 85 65 30 50
Vac 50/60 Hz, 3 s 22 36 50 30 50 22 36 75 65 30 50
Built-In Instantaneous Override (Peak kA ±10%) — — 19016 8016 — — — 190 150 80 —
Rated making Current (Peak kA)50/60 Hz
Icm 220/415 Vac 88 143 220 330 — 88 88 220 330 330 —
440 Vac 88 143 220 330 — 88 88 220 330 330 —
20 0613CT0001
13. 90 kA for 2000 A.
14. The endurance rating for 2000 A, N/H/L/LF is 10,000 for mechanical and 1000 for electrical.
15. The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit breaker with an equal continuous current rating.
16. 55 kA for 800 A circuit breaker frame with 100 A or 250 A sensor.
Table 7 - Ratings for IEC 60947-2 Rated MasterPact NW Circuit Breakers 800–2000 A (Continued)
Frame Rating 800/1000/1250/1600 A 2000 A
525 Vac 88 143 187 286 — 88 88 187 286 286 —
690 Vac 88 143 187 220 — 88 88 187 220 220 —
1150 Vac — — — — 105 — — — — — 105
Break Time ms 25 25
Closing Time ms < 70 < 70
Endurance Rating (with no maint.) C/O Cycles x 1000
Mechani-cal 12.5 10
Electrical 440 V 10 10 10 3 — 8 8 8 3 3 —
Electrical 1150 V — — — — 0.5 — — — — — 0.5
Table 8 - Ratings for IEC 60947-2 Rated MasterPact NW Circuit Breakers 2500–6300 A
Frame Rating 2500/3200/4000 A 4000B/5000/6300 A
Interrupting Rating Code H1 H2 H3 H10 H1 H2
Ultimate Breaking Capacity (kA) 50/60 Hz
Icu
220/415 Vac 65 100 150 — 100 150
440 Vac 65 100 150 — 100 150
525 Vac 65 85 130 — 100 130
690 Vac 65 85 100 — 100 100
1150 Vac — — — 50 — —
Service Breaking Capacity Ics %Icu 100% 100% 100% 100% 100% 100%
Short-Time Withstand Current (kA)
Icw Vac 50/60 Hz, 1 s 65 85 65 50 100 100
Vac 50/60 Hz, 3 s 65 75 65 50 100 100
Built-In Instantaneous Override (Peak kA ±10%) — 190 150 — — 117
Rated making Current (Peak kA) 50/60 Hz
Icm
220/415 Vac 143 220 330 — 220 330
440 Vac 143 220 330 — 220 330
525 Vac 143 189 286 — 187 286
690 Vac 143 189 220 — 187 220
1150 Vac — — — 105 — —
Break Time ms 25 25
Closing Time ms < 70 < 80
Endurance Rating (with no maint.)
C/O Cycles x 1000
Mechanical 10 5
Electrical 440 V 5 5 1.25 — 1.5 1.5
Electrical 1150 V — — — 0.5 — —
Table 9 - Ratings for IEC 60947-3 Rated MasterPact NW Switches
Frame Rating 800/1000/1250/1600 A 2000 A 2500/3200/4000 A 4000B/
5000/6300 A
Withstand Rating Code17 NA HA HF HA10 HA HF HA10 HA HF HA10 HA
Rated Making Current (Peak kA)
Icm
220/415 Vac, 50/60 Hz 88 105 187 — 105 187 — 121 189 — 187
440 Vac, 50/60 Hz 88 105 187 — 105 187 — 121 189 — 187
500/690 Vac, 50/60 Hz 88 105 187 — 105 187 — 121 189 — 187
0613CT0001 21
17. NA, HA, and HA10 are non-automatic switches; HF is an automatic switch.
Table 9 - Ratings for IEC 60947-3 Rated MasterPact NW Switches (Continued)
Frame Rating 800/1000/1250/1600 A 2000 A 2500/3200/4000 A 4000B/
5000/6300 A
1150 Vac, 50/60 Hz — — — 105 — — 105 121 — 105 —
Short- Time Withstand Current (kA)
Icw Vac 50/60 Hz, 1 s 42 50 85 50 50 85 50 50 85 50 85
Ultimate Breaking Capacity (with external protection relay) (kA)
Icu Maximum
Delay 350 ms 42 50 85 50 50 85 50 50 85 50 85
Table 10 - Ratings for ANSI C37 Certified MasterPact NT Circuit Breakers
Frame Rating 800 A
Interrupting Rating Code N1
Interrupting Current (kAIR)
254 Vac 60 Hz 42
508 Vac 60 Hz 42
635 Vac 60 Hz N/A
Short-Time Withstand Current (kA) ac 60 Hz, 0.5 s 42
Built-In Instantaneous Override (Peak kA ±10%) —
Close and Latch Ratings (Peak kA) ac 60 Hz 90
Tested to show arc flash hazard risk category as referenced by NFPA70E —
Breaking Time 25 to 30 ms (with no intentional time delay)
Closing Time < 50 ms
Sensor Rating 100 to 250 A / 400 to 800 A
Endurance Rating (C/O Cycles) (with no maintenance) Mechanical 12,500
Electrical 2800
Table 11 - Ratings for ANSI C37 Certified MasterPact NT Non-Automatic Switches
Frame Rating 800 A
Withstand Rating Code NA
Short-Time Withstand Current Rating (kA) Vac 50/60 Hz, 0.5 s 42
Breaking Capacity (with external protection relay) (kA) 254/508/635 Vac, 60 Hz 42/42/NA
Table 12 - Ratings for UL 489 Listed MasterPact NT Circuit Breakers
Frame Rating 800 A 1200 A 1600 A18
Interrupting Rating Code N H L1 L LF N H L1 L LF N H L1 L
Interrupting Current (kAIR)
240 Vac, 60 Hz 50 65 100 200 200 50 65 100 200 200 50 65 100 200
480 Vac, 60 Hz 50 50 65 100 100 50 50 65 100 100 50 50 65 100
600 Vac, 60 Hz 35 50 N/A N/A N/A 35 50 N/A N/A N/A 35 50 N/A N/A
22 0613CT0001
18. Fixed-mounted only. 1600 A UL489 drawout circuit breakers are not available.
Table 12 - Ratings for UL 489 Listed MasterPact NT Circuit Breakers (Continued)
Frame Rating 800 A 1200 A 1600 A19
Short-Time Withstand Current Rating (kA)
Vac 60 Hz,
0.5 s 35 35 10 10 10 35 35 10 10 10 35 35 10 10
Built-In Instantaneous Override (Peak kA ±10%) 90 90 22 22 22 90 90 22 22 22 90 90 22 22
Close and Latch Ratings (Peak kA)
Vac 60 Hz 55 55 22 22 22 55 55 22 22 22 55 55 22 22
Tested to show arc flash hazard risk category as referenced by NFPA70E
— — — — Yes — — — — Yes — — — —
Breaking Time 25 to 30 ms (with no intentional time delay) 9 ms for L and LF
Closing Time < 50 ms
Sensor Rating 100–250 A / 400–800 A 600–1200 A 800–1600 A
Endurance Rating (C/O Cycles) (with no maintenance)
Mechanical 12,500
Electrical 2800
Table 13 - Ratings for UL 489 Listed MasterPact NTAutomatic Switches
Frame Rating 800 A 1200 A 1600 A
Withstand Rating Code HF HB HF HB HF HB
Withstand Rating20 (kA) Vac, 50/60 Hz
240 65 200 65 200 65 200
480 50 100 50 100 50 100
600 50 NA 50 NA 50 NA
Instantaneous Override (Peak kA) 90 22 90 22 90 22
0613CT0001 23
19. Fixed-mounted only. 1600 A UL489 drawout circuit breakers are not available.
20. The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit breaker with an equal continuous current rating.
Table 14 - Ratings for IEC 60947-2 Rated MasterPact NT Circuit Breakers
Frame Rating 800/1000 A 1250/1600 A
Interrupting Rating Code H1 H2 L1 H1 H2
Ultimate Breaking Capacity (kA) Icu
220/415 Vac, 50/60 Hz 42 50 150 42 50
440 Vac, 50/60 Hz 42 50 130 42 50
525 Vac, 50/60 Hz 42 42 100 42 42
690 Vac, 50/60 Hz 42 42 25 42 42
1000 Vac, 50/60 Hz — — — — —
Service Breaking Capacity (kA) Ics %Icu 100% 100% 100% 100% 100%
Short-Time Withstand Current (kA)
Icw Vac 50/60 Hz, 1 s 42 42 10 x In21 42 36
Built-In Instantaneous Override (kA ±10%) — 90 1022 — —
Rated Making Capacity (Peak kA) Icm
220/415 Vac, 50/60 Hz 88 105 330 88 105
440 Vac, 50/60 Hz 88 105 286 88 105
525 Vac, 50/60 Hz 88 88 220 88 88
690 Vac, 50/60 Hz 88 88 52 88 88
1000 Vac, 50/60 Hz — — — — —
Break Time ms 25 25 9 25 25
Closing Time ms 50 50 50 50 50
Endurance Rating (C/O cycles) (with no maintenance)
Mechanical 12,500 12,500 12,500 12,500 12,500
Electrical 440 V 6000 6000 3000 600023 600023
Electrical 1000 V — — — — —
Table 15 - Ratings for IEC 60947-3 Rated Non-Automatic MasterPact NT Switches
Frame Rating 800/1000 A 1250/1600 A
Withstand Rating Code HA HA
Rated Making Capacity (Peak kA) Icm
220/415 Vac, 50/60 Hz 75 75
440 Vac, 50/60 Hz 75 75
500/690 Vac, 50/60 Hz 75 75
1000 Vac, 50/60 Hz — —
Short-Time Withstand Current (kA) Icw Vac 50/60 Hz, 0.5 s 36 36
Breaking Capacity (kA at 690 Vac) (with external protection relay) Icu maximum delay 350 ms 36 36
24 0613CT0001
21. For Icw, 10 kA is for 0.5 s.
22. SELLIM system.
23. 1600 A at 690 V is 3000 electrical operations.
Correction Factors Table 16 - Temperature Correction Factors
Maximum Ambient Temperature
°F 158 140 122 104 86 77 68 50 32 14 -4 -13 -22
°C 70 60 50 40 30 25 20 10 0 -10 -20 -25 -30
Current 0.75 0.83 0.92 1 1.07 1.11 1.14 1.21 1.27 1.33 1.39 1.42 1.44
Table 17 - Altitude Correction Factors per ANSI C37.20.1 par. 7.1.4.1 (Table 10)
< 6600 ft. (2000 m) 8500 ft (2600 m) 13,000 ft. (3900 m)
Voltage 1 0.95 0.80
Current 1 0.99 0.96
Shipping Weights
Table 18 - Shipping Weights for UL Listed/ANSI Certified MasterPact NW Circuit Breakers
Circuit Breaker Rating (A)
Circuit Breaker24 (lb/kg) Cradle (lb/kg) Connector Type and Weight
(lb/kg) Pallet (lb/kg)
Total Weight (lb/kg)
3P 4P 3P 4P Type 3P 4P 3P 4P
109/50 142/65 97/44 116/53
FCF 42/19 55/25 17/8 265/121 320/151
FCT 84/38 109/50 17/8 307/140 384/176
RCTH or
RCTV 17/8 22/10 17/8 240/110 297/136
3000 127/58 165/75 124/57 149/68
FCT 80/36 104/47 17/8 348/159 435/198
RCTH or
RCTV 26/12 34/15 17/8 294/135 365/166
(L1, L1F)
(H1, H2, H3)
127/58 165/75 124/57 149/68
RCOV
(standard 100/46 130/59
17/8
368/169 461/210
W-Frame
(H1, H2, H3)
RCOV
(ArcBlok) 153/69 NA 421/191 NA
RCOV
(special) 115/52 145/66 259/118 327/149
3200 (L1) 4000 227/103 295/134 278/126 334/152
FCF 84/38 109/50 39/18 628/285 777/354
FCT 168/77 218/99 39/18 712/324 886/403
RCTH or
RCTV 52/24 68/31 39/18 596/271 736/335
5000 227/103 295/134 278/126 334/152
FCT 168/77 218/99 39/18 712/324 886/403
RCTH or
RCTV 52/24 68/31 39/18 596/271 736/335
6000 227/103 295/134 278/126 334/152 RCTH or
RCTV 396/180 528/240 39/18 940/427 1196/544
0613CT0001 25
24. Fixed circuit breaker weight = total weight – cradle weight.
Table 19 - Shipping Weights for IEC 60947-2 Rated MasterPact NW Circuit Breakers
Circuit Breaker Rating (A)
Circuit Breaker25 (lb/kg) Cradle (lb/kg) Connector Type and Weight
(lb/kg) Pallet (lb/kg)
Total Weight (lb/kg)
3P 4P 3P 4P Type 3P 4P 3P 4P
109/50 132/60 97/44 116/53
FCF 42/19 55/25 17/8 265/121 320/145
1000, 1250, 1600, 2000
RCTH or
RCTV 17/8 22/10 17/8 240/110 287/131
3200 127/58 165/75 124/57 149/68
FCF 42/19 55/25 17/8 310/142 386/175
RCTH or
RCTV 17/8 22/10 17/8 285/131 353/161
4000 127/58 165/75 124/57 149/68 RCTH or
RCTV 42/19 55/25 17/8 310/142 386/176
4000b, 5000, 6300 227/103 295/134 278/126 334/152 RCTH or
RCTV 52/24 68/31 39/18 596/271 736/335
Table 20 - Shipping Weights for UL Listed/ANSI Certified MasterPact NT Circuit Breakers
Circuit Breaker Rating (A)
Circuit Breaker25 (lb/kg) Cradle (lb/kg) Connector Type and Weight
(lb/kg) Pallet (lb/kg)
Total Weight (lb/kg)
3P 4P 3P 4P Type 3P 4P 3P 4P
1200 40/18 52/24 36/16 43/20
FCF 15/7 20/9 10/5 101/46 125/58
RCTH or
RCTV 6/3 8/4 10/5 92/42 113/53
160026 40/18 52/24 N/A N/A RCTV 18/8 20/9 10/5 68/31 82/38
Table 21 - Shipping Weights for IEC 60947-2 Rated MasterPact NT Circuit Breakers
Circuit Breaker Rating (A)
Circuit Breaker25 (lb/kg) Cradle (lb/kg) Connector Type and Weight
(lb/kg) Pallet (lb/kg)
Total Weight (lb/kg)
3P 4P 3P 4P Type 3P 4P 3P 4P
35/16 46/21 31/14 37/17
FCF 15/7 20/9 10/5 91/41 113/52
1000, 1250, RCTH or
RCTV 6/3 8/4 10/5 82/38 101/47
26 0613CT0001
25. Fixed circuit breaker weight = total weight – cradle weight.
26. Fixed circuit breaker only.
File details come from the government source that posted it. Updated .