3534-20260416111921 COLUMBUS.pdf
PDF 686 KB Posted
- Attached to
- 3534-20260416111921 Columbus
- Solicitation number
- 3170035534
- Issued by
- Lee County, Mississippi
About this file
Summary
This is a Request for Bids (RFB) document issued by the Columbus Redevelopment Authority in Columbus, Mississippi, for the procurement of electric distribution materials and appurtenances (material only) for the Parkview Development Electrical Site Package on a re-bid basis. The project requires bidders to supply 101 bid items organized into 17 groups, including steel distribution poles (3 poles total), overhead utility wire in various gauges and types (approximately 12,000 linear feet), distribution crossarms and supports (20 items), distribution insulators (132 items), conductor accessories (15 items), distribution switches and arresters (8 items), guying components (12 items), grounding materials (6 items), overhead transformers (7 units consisting of 15 kVA, 25 kVA, and 50 kVA single-phase units), hardware (12 items), equipment brackets (3 items), underground cable wire (8,690 linear feet combined), underground conductor accessories (8 items), pad-mounted transformers (13 units), secondary pedestals (6 units), and conduit materials (3 items). Sealed bids must be received by 11:30 A.M. Local Time on April 22, 2026, either in person at Columbus City Hall, 523 Main Street, Columbus, MS 39701, or electronically via https://www.atwellandgentprojects.com. Bids must be submitted in sealed envelopes or as PDF files through the designated website. The bid documents are available through Plan House Printing at (662) 407-0193, with technical questions directed to the project engineer, Jeffrey Atwell, at jatwell@atwellandgent.com.
Bidders are not required to bid all items but must bid all items within any specific group to have their bid considered; failure to do so may result in bid rejection. Unusually long delivery promises may also cause bids to be disregarded. The contract will be awarded on an aggregate-low basis within each of the 17 groups to the lowest and best responsive bidder. All quoted prices must be firm if accepted within thirty days and include delivery to the Columbus Light & Water Electric Warehouse at 1601 Waterway Drive, Columbus, Mississippi 39701, with the owner responsible for unloading. Prices do not include applicable taxes, which will be added to the purchase price if applicable. Title of equipment passes to the owner upon delivery to the specified location, satisfactory inspection for in-transit damage, and acceptance by the owner. The Columbus Redevelopment Authority affirmatively ensures that disadvantaged and women's business enterprises will have full opportunity to submit bids and will not be discriminated against on grounds of race, color, or national origin. No bidder may withdraw its bid within thirty days after the actual date of opening. The owner reserves the right to reject any or all bids and waive any informalities or irregularities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ADDENDUM_1_2023-04-162 (1).pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specifications & Materialman’s Proposal for
Electric Distribution Materials and Appurtenances (Material Only) for Parkview Development
Electrical Site Package (Re-Bid)
March 25, 2026
Prepared for:
Columbus Redevelopment Authority
523 Main Street Columbus, Mississippi, 39701
Prepared by:
Atwell & Gent, P.A.
Consulting Engineers 309 University Drive Starkville, MS 39759
A&G Job No.: 119E3031
Request for Bids Electric Distribution Materials and Poles (Material Only)
ADVERTISEMENT FOR BIDS
ELECTRIC DISTRIBUTION MATERIALS & APPURTENANCES (MATERIAL
ONLY) FOR PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS, MS
Sealed bids will be received by the Columbus Redevelopment Authority in Columbus City Hall, 523 Main Street, Columbus, MS 39701, or electronically via https://www.atwellandgentprojects.com until 11:30 A.M., Local Time, on April 22, 2026 for supplying "ELECTRIC DISTRIBUTION
MATERIALS & APPURTENANCES (MATERIAL ONLY) FOR PARKVIEW
DEVELOPMENT".
SUBMITTAL OF SEALED PROPOSAL: Proposals shall be submitted in a sealed envelope and deposited with the Columbus Redevelopment Authority prior to the hour and date herein before designated.
SUBMITTAL OF ELECTRONIC BID: Electronic bids shall be submitted through https://www.atwellandgentprojects.com. Please contact Plan House Printing at (662) 407-0193 with questions regarding website registration, electronic bidding, and online orders. Each electronically submitted bid must be submitted in “pdf” format and shall contain the same information and forms as required for the paper bids. In the event that an electronically submitted bid has a corrupted attachment, the bid will be considered null and void.
CONTRACT DOCUMENTS: Bid documents are being made available via digital or paper copy.
Plan holders are required to register for an account at https://www.atwellandgentprojects.com to view and order Bid Documents. All plan holders are required to have a valid email address for registration.
Bid documents are non-refundable and must be purchased through the website. Questions are to be directed to Jeffrey Atwell via jatwell@atwellandgent.com.
The Columbus Redevelopment hereby notifies all Bidders that it will affirmatively ensure that in any contract entered into pursuant to this advertisement, disadvantaged and women's business enterprises will be afforded the full opportunity to submit bids in response to this invitation and will not be discriminated against on the grounds of race, color, or national origin in consideration for an award.
No bidder may withdraw his bid within thirty (30) days after the actual date of the opening thereof.
The Columbus Redevelopment Authority reserves the right to reject any and all bids and to waive any informalities or irregularities therein.
BY: Isl Marthalie Porter Marthalie Porter, Board President Columbus Redevelopment Authority
Advertisement Dates:
April 1, 2026 April 8, 2026 https://www.atwellandgentprojects.com/ https://www.atwellandgentprojects.com/ https://www.atwellandgentprojects.com/ mailto:jatwell@atwellandgent.com
TABLE OF CONTENTS
ELECTRIC DISTRIBUTION MATERIALS AND APPURTENANCES (MATERIAL ONLY)
FOR PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
TITLE PAGE NO.
COVER SHEET
NOTICE TO BIDDERS
TABLE OF CONTENTS
INSTRUCTION TO BIDDERS....................................................................................................................... 4-6
PROPOSAL FORM ......................................................................................................................................... 7-9
APPENDIX A - DETAILED BID FORM ..................................................................................................APP A
APPENDIX B - BILL OF MATERIALS ................................................................................................... APP B
APPENDIX C - SPECIFICATIONS FOR STEEL DISTRIBUTION POLES .......................................... APP C
APPENDIX D - SPECIFICATIONS FOR POLE MOUNTED TRANSFORMERS .................................APP D
INSTRUCTIONS TO BIDDERS
ELECTRIC DISTRIBUTION MATERIALS AND APPURTENANCES (MATERIAL ONLY)
FOR PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
SUBMITTAL OF SEALED BIDS: Each bid must be submitted in accordance with the instructions to bidders which are bound in the Project Manual. The Owner reserves the right to waive irregularities and to reject any or all bids.
Bids that are sent by parcel delivery service or mail shall be clearly marked "Bid Enclosed" or "Bid Envelope Enclosed" as appropriate. The sealed envelope containing the bid shall have the following information shown on the envelope:
BID ENCLOSED
ITEM: ELECTRIC DISTRIBUTION MATERIALS AND APPURTENANCES (MATERIAL
ONLY)
OWNER: COLUMBUS REDEVELOPMENT AUTHORITY
BIDDER:
ADDRESS:
BID DUE: REFER TO ADVERTISEMENT FOR BIDS
Bids that are sent by mail should be addressed to:
Columbus Redevelopment Authority 523 Main Street Columbus, Mississippi 39701
Bids that are sent by parcel delivery service should be addressed to:
Columbus Redevelopment Authority 523 Main Street Columbus, Mississippi 39701
SUBMITTAL OF ELECTRONIC BIDS: Electronic bids can be submitted at www.atwellandgentprojects.com. Each electronically submitted bid must be submitted in “pdf” format and shall contain the same information and forms as required for the paper bids. In the event that an electronically submitted bid has a corrupted attachment, the bid will be considered null and void.
The Engineer for this project is:
Atwell & Gent, P.A.
P.O. Box 2558 Starkville, Mississippi 39760-2558 Telephone (662) 324-5658 http://www.atwellandgentprojects.com/
The Engineer will represent the Owner in all matters pertaining to this project, including but not limited to, answering technical questions of prospective bidders and recommendations of lowest and best bid, acceptance of shop drawings and similar documents, and approval of invoices prior to payment by the Owner.
Submit all questions about the specifications to the Engineer, in writing. Replies will be issued to all prospective Bidders of Record. Neither the Engineer nor the Owner will be responsible for oral clarifications.
BID PREPARATION:
Bidders shall complete all blank spaces on both the Materialman’s Proposal Form and the Detailed Bid Form for each item of equipment being bid in accordance with these specifications and terms and conditions.
Bidder should insert the unit price in the blank under the Unit Price heading and multiply this unit price by the number shown in the Number Required heading and enter the product of this multiplication in the blank under the heading Total Price for each bid item on the Detailed Bid Form. The bidder shall sum the Total Bid Price for each Bid Item and enter this sum in the Total Bid Price.
Bidder shall insert the delivery time in weeks after receipt of an order for each item of equipment bid in the blank provided on the Detailed Bid Form. Bidder shall also indicate equipment being bid by the manufacturer’s name and catalog number in the blanks provided on the Proposal Form.
Bidder shall supply all information requested in the blanks provided on the Materialman's Proposal Form and Detailed Bid Form for the electric distribution equipment being bid. Bidders taking exceptions to any part of the specifications, conditions, or payment terms specified herein shall show such exception on the Materialman's Proposal Form in the space provided. If exceptions are not shown on the Materialman's Proposal Form, Bidder shall supply equipment specified herein under the terms and conditions specified herein.
Bidder shall submit Materialman’s Proposal Form and the Detailed Bid Form as a part of their bid.
Proposals that are incomplete, modified, excepted, or in any way changed from the proposal that the OWNER is requesting in this request for proposals may be rejected by the OWNER.
BID AWARD:
Group #1: Bid Items No. 1 through No. 3 will be awarded on an aggregate–low basis to the bidder with lowest and best responsive bid for Bid Items No. 1 through No. 3 inclusive.
Group #2: Bid Items No. 4 through No. 14 will be awarded on an aggregate–low basis to the bidder with lowest and best responsive bid for Bid Items No. 4 through No. 14 inclusive.
Group #3: Bid Items No. 15 through No. 24 will be awarded to the bidder with lowest and best responsive bid for Bid Items No. 15 through No. 24 inclusive.
Group #4: Bid Items No. 25 through No. 27 will be awarded on an aggregate–low basis to the bidder with lowest and best responsive bid for Bid Items No. 25 through No. 27 inclusive.
Group #5: Bid Items No. 28 through No. 42 will be awarded on an aggregate–low basis to the bidder with lowest and best responsive bid for Bid Items No. 28 through No. 42 inclusive.
Group #6: Bid Items No. 43 through No. 50 will be awarded on an aggregate–low basis to the bidder with lowest and best responsive bid for Bid Items No. 43 through No. 50 inclusive.
Group #7: Bid Items No. 51 through No. 62 will be awarded on an aggregate–low basis to the bidder with lowest and best responsive bid for Bid Items No. 51 through No. 62 inclusive.
Group #8: Bid Items No. 63 through No. 68 will be awarded on an aggregate–low basis to the bidder with lowest and best responsive bid for Bid Items No. 63 through No. 68 inclusive.
Group #9: Bid Items No. 69 through No. 71 will be awarded on an aggregate–low basis to the bidder with lowest and best responsive bid for Bid Items No. 69 through No. 71 inclusive.
Group #10: Bid Items No. 72 through No. 83 will be awarded on an aggregate–low basis to the bidder with lowest and best responsive bid for Bid Items No. 72 through No. 83 inclusive.
Group #11: Bid Items No. 84 through No. 86 will be awarded on an aggregate-low basis to the bidder with lowest and best responsive bid for Bid Items No. 84 through No. 86.
Group #12: Bid Item No. 87 will be awarded on an aggregate-low basis to the bidder with lowest and best responsive bid for Bid Item No. 87.
Group #13: Bid Item No. 88 will be awarded on an aggregate-low basis to the bidder with lowest and best responsive bid for Bid Item No. 88.
Group #14: Bid Items No. 89 through No. 96 will be awarded on an aggregate-low basis to the bidder with lowest and best responsive bid for Bid Items No. 89 through No. 96.
Group #15: Bid Item No. 97 will be awarded on an aggregate-low basis to the bidder with lowest and best responsive bid for Bid Item No. 97.
Group #16: Bid Item No. 98 will be awarded on an aggregate-low basis to the bidder with lowest and best responsive bid for Bid Item No. 98.
Group #17: Bid Items No. 99 through No. 101 will be awarded on an aggregate-low basis to the bidder with lowest and best responsive bid for Bid Items No. 99 through No. 101.
Note: It is not necessary to bid all bid items; however, it is necessary to bid all bid items within any specific group (e.g., bid all items in Group #3).
Failure to bid all items within a group may cause bid to be disregarded. Unusually long delivery promises may cause bid to be disregarded.
MATERIALMAN'S PROPOSAL
ELECTRIC DISTRIBUTION MATERIALS AND APPURTENANCES (MATERIAL ONLY)
FOR PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
Attn: Columbus Redevelopment Authority 523 Main Street Columbus, Mississippi 39701
The undersigned (hereinafter called the MATERIALMAN) acknowledges by his signature that he has received and examined the documents entitled "Specifications and Materialman's Proposal for ELECTRIC DISTRIBUTION MATERIALS AND APPURTENANCES (MATERIAL ONLY) for the Columbus Redevelopment Authority (hereinafter called the OWNER), dated March 25, 2026, and has included the provisions of the Specifications in his Proposal. The Materialman further acknowledges that he has received the following addenda.
Addendum No. Dated
Addendum No. Dated
The Materialman hereby proposes to sell and deliver to the OWNER, upon the terms and conditions herein stated, the equipment specified in the attached specification for the following sums shown below:
TOTAL BID FOR BID ITEMS #1 THROUGH #3 (GROUP #1) INCLUSIVE
TOTAL BID FOR BID ITEMS #4 THROUGH #14 (GROUP #2) INCLUSIVE
TOTAL BID FOR BID ITEM #15 THROUGH #24 (GROUP #3) INCLUSIVE
TOTAL BID FOR BID ITEMS #25 THROUGH #27 (GROUP #4) INCLUSIVE
TOTAL BID FOR BID ITEMS #28 THROUGH #42 (GROUP #5) INCLUSIVE
TOTAL BID FOR BID ITEMS #43 THROUGH #50 (GROUP #6) INCLUSIVE
TOTAL BID FOR BID ITEMS #51 THROUGH #62 (GROUP #7) INCLUSIVE
TOTAL BID FOR BID ITEMS #63 THROUGH #68 (GROUP #8) INCLUSIVE
TOTAL BID FOR BID ITEMS #69 THROUGH #71 (GROUP #9) INCLUSIVE
TOTAL BID FOR BID ITEMS #72 THROUGH #83 (GROUP #10) INCLUSIVE
TOTAL BID FOR BID ITEMS #84 THROUGH #86 (GROUP #11) INCLUSIVE
TOTAL BID FOR BID ITEM #87 (GROUP #12) INCLUSIVE
TOTAL BID FOR BID ITEM #88 (GROUP #13) INCLUSIVE
TOTAL BID FOR BID ITEMS #89 THROUGH #96 (GROUP #14) INCLUSIVE
TOTAL BID FOR BID ITEM #97 (GROUP #15) INCLUSIVE
TOTAL BID FOR BID ITEM #98 (GROUP #16) INCLUSIVE
TOTAL BID FOR BID ITEMS #99 THROUGH #101 (GROUP #17) INCLUSIVE
Note: Refer to Instructions to Bidders. It is not necessary to bid all bid items; however, it is necessary to bid all bid items within any specific group (e.g., bid all items in Group #6).
Bid Form
The Detailed Bid Form complete with item description and required quantities for each Bid Item is included with this RFQ in Appendix A.
Bill of Materials
The Bill of Materials complete with item description and catalog numbers for each Bid Item is included with this RFQ in Appendix B.
Technical Specifications
Technical specifications for select Bid Items are included with this RFQ in Appendix C through Appendix I.
Other Considerations
A. The total prices set forth above shall be firm if accepted by the OWNER within thirty (30) days and shall include delivery to the Columbus Light & Water’s Electric Warehouse; 1601 Waterway Drive, Columbus, Mississippi 39701, ready for OWNER's use. The OWNER will unload electric distribution materials and poles at OWNER’s Warehouse.
B. The prices set forth herein do not include any sums which are, or which may be payable by the MATERIALMAN on account of taxes imposed by any taxing authority upon the sale, purchase, or use of the equipment. If any such tax is applicable to the sale, purchase, or use of the equipment, the amount thereof shall be added to the purchase price and paid by the OWNER.
C. Title of the equipment shall pass to the Owner upon:
1. Delivery to location specified.
2. Satisfactory inspection for in-transit damage.
3. Acceptance by the Owner.
D. Exceptions:
E. It is understood by the undersigned that the OWNER retains the privilege of accepting or rejecting all or any part of this proposal and to waive any informalities or technicalities therein.
Counterproposals or qualified bids shall be subject to rejection at the discretion of the OWNER.
It is also understood by the undersigned that the OWNER reserves the right to conduct investigations to evaluate the proposals received and to award the bid for this equipment to the lowest Bidder, who in the OWNER’s evaluation will provide the equipment which will be in the best interest of the OWNER.
MATERIALMAN:
BY:
TITLE:
COMPANY:
ADDRESS:
TELEPHONE NO.:
EMAIL:
DATE SIGNED:
Appendix A
APPENDIX A
DETAILED BID FORM
MATERIALMAN'S DETAILED BID FORM
ELECTRIC DISTRIBUTION MATERIALS AND APPURTENANCES (MATERIAL ONLY)
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
30/4 STEEL POLE. REFER TO TECHNICAL SPECIFICATION IN
APPENDIX C.
1 EA
45/H1 STEEL POLE. REFER TO TECHNICAL SPECIFICATION IN
APPENDIX C.
9 EA
50/H1 STEEL POLE. REFER TO TECHNICAL SPECIFICATION IN
APPENDIX C.
6 EA
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
4 WIRE, COVERED, THHN, #4 COPPER 20 LF
5 WIRE, COVERED, THHN, #2 COPPER 40 LF
6 WIRE, COVERED, THHN, #1/0 COPPER 20 LF
7 WIRE, COVERED, THHN, #2/0 COPPER 60 LF
8 WIRE, 336.4 KCMIL 18/1 ACSR "MERLIN" 5,694 LF
9 WIRE, 477.0 kCMIL 18/1 ACSR "PELICAN" 4,015 LF
10 WIRE, #1/0 AL TRIPLEX "NERTINA" 250 LF
11 WIRE, #2 AL TRIPLEX "CONCH" 500 LF
12 WIRE, GROUND, #4 SD BARE SOLID COPPER 1,000 LF
13 WIRE, GROUND, #2 SD BARE STRANDED COPPER 300 LF
14 WIRE, WILDLIFE, 15 KV, #4 COPPER 250 LF
TOTAL BID FOR GROUP #1 (BID ITEMS #1 THROUGH #3)
GROUP #1 (STEEL POLES)
GROUP #2 (OVERHEAD UTILITY WIRE)
TOTAL BID FOR GROUP #2 (BID ITEMS #4 THROUGH #14)
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
15 CROSSARM, TANGENT, FIBERGLASS, 8', GRAY 9 EA
16 CROSSARM, TANGENT, FIBERGLASS, 10' GRAY 2 EA
17 CROSSARM, DEADEND, FIBERGLASS, 8', GRAY 4 EA
18 CROSSARM, DEADEND, FIBERGLASS, 10', GRAY 5 EA
19 PIN, CROSSARM, CLAMP TYPE 14 EA
20 PIN, CROSSARM, PIN TYPE 14 EA
21 CLEVIS, SECONDARY, ONE SPOOL 8 EA
22 PIN, RIDGE, FIBERGLASS, 2" x 18" 14 EA
23 PIN, HORIZONTAL, FIBERGLASS, 1-1/2" x 18" 1 EA
24 FIBERGLASS EXTENSION LINK, CLEVIS-EYE, 12" 18 EA
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
25 INSULATOR, DEADEND, POLYMER, 35 KV 60 EA
26 INSULATOR, PIN TYPE, 15 KV 48 EA
27 INSULATOR, SPOOL 24 EA
TOTAL BID FOR GROUP #4 (BID ITEMS #25 THROUGH #27)
GROUP #3 (STEEL POLES)
TOTAL BID FOR GROUP #3 (BID ITEMS #15 THROUGH #24)
GROUP #4 (DISTRIBUTION INSULATORS)
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
28 CLAMP, DEADEND, #336.4 KCMIL - 954 kCMIL ACSR 70 EA
29 CLAMP, DEADEND, #4/0 ACSR - 556 KCMIL ACSR 10 EA
30 CLAMP, HOTLINE, #8 - #2/0 CU 25 EA
31 CLAMP, STIRRUP, #6- #2/0 ACSR 25 EA
32 CONNECTOR, MULTI TAP 21 EA
33 SERVICE GRIP, #2 AL TRIPLEX 5 EA
34 SERVICE GRIP, #1/0 AL TRIPLEX 10 EA
35 CONNECTOR, COMPRESSION, #4-6 CU-#4-6 CU 50 EA
36 CONNECTOR, COMPRESSION, #336.4 KCMIL ACSR-#2-#6 CU 50 EA
37 CONNECTOR, COMPRESSION, #2 CU-#4 CU 10 EA
CONNECTOR, COMPRESSION, #4/0-477.0 KCMIL ACSR-#4/0-
477.0 kCMIL ACSR
30 EA
39 CONNECTOR, COMPRESSION, #6 CU- GUY STRAND 10 EA
40 TOP TIE, 477.0 ACSR 50 EA
41 ALUMINUM TIE WIRE, #4 (25 LB SPOOL) 1 EA
TERMINAL, COMPRESSION, ALUMINUM OR COPPER, CABLE
TO NEMA 2 HOLE PAD, 477/0 KCMIL ACSR
6 EA
GROUP #5 (DISTRIBUTION CONDUCTOR ACCESSORIES)
TOTAL BID FOR GROUP #5 (BID ITEMS #28 THROUGH #42)
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
SWITCH, LOADBREAK, THREE POLE SIDEBREAK, 25 KV, 600
AMPERES, UNITIZED, HOOKSTICK TYPE, COMPLETE WITH
ALL MOUNTING HARDWARE
1 EA
44 SWITCH, FUSED CUTOUT, 15 KV, 100 AMPERE 26 EA
45 ARRESTER, SURGE, DISTRIBUTION CLASS, 10 KV 16 EA
46 ARRESTER, SURGE, RISER CLASS, 10 KV 10 EA
47 FUSE, EXPULSUION, 15 KV, 65 AMP TYPE "T" 10 EA
48 FUSE, EXPULSUION, 15 KV, 3 AMP TYPE "K" 3 EA
49 FUSE, EXPULSUION, 15 KV, 6 AMP TYPE "K" 2 EA
50 FUSE, EXPULSUION, 15 KV, 10 AMP TYPE "K" 2 EA
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
51 3/8" H.S. STEEL GUY STRAND, FURNISH ON 250' COILS 250 EA
52 7/16" E.H.S. STEEL GUY STRAND, FURNISH ON 250' COILS 250 EA
53 ANCHOR, POWER SCREW, 1-1/2" SS, 8/10" DOUBLE HELIX 5 EA
54 SQUARE SHAFT EXTENSION, 1-1/2" x 5' 10 EA
55 GUY TERMINATION, TWINEYE, 1-1/2" SS 5 EA
GUY STRAIN INSULATOR, FIBERGLASS, CLEVIS- ROLLER,
15,000 LB RATING, 144" LENGTH
2 EA
GUY STRAIN INSULATOR, FIBERGLASS, CLEVIS- ROLLER,
21,000 LB RATING, 144" LENGTH
4 EA
58 GUY GRIP, 3/8", PREFORMED 50 EA
59 GUY GRIP, 7/16", PREFORMED 25 EA
POLE EYE PLATE, WITHOUT CLEATS, 3" BOLT SPACING
REQUIRED
25 EA
61 GUY THIMBLE, CLEVIS TYPE 25 EA
62 GUY MARKER, YELLOW PLASTIC, 8' LENGTH 30 EA
TOTAL BID FOR GROUP #6 (BID ITEMS #43 THROUGH #50)
GROUP #7 (GUYING)
TOTAL BID FOR GROUP #7 (BID ITEMS #51 THROUGH #62)
GROUP #6 (DISTRIBUTION SWITCHES & ARRESTERS)
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
63 GROUND ROD, COPPER CLAD, 5/8" X 8' 16 EA
64 CLAMP, GROUND ROD, BRONZE, 5/8" 16 EA
65 GROUND ROD, COPPER CLAD, 3/4" X 10' 17 EA
66 CONNECTOR, COMPRESSION, 3/4" ROD - #2 CU 17 EA
67 CONNECTOR, COMPRESSION, #4/0-#2 CU - #4/0-#2 CU 75 EA
TRANSFORMER TANK GROUND LUG, #8-#2/0 CU, 1/2"-13
THREAD
50 EA
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
TRANSFORMER, CONVENTIONAL, SINGLE PHASE, 15 KVA,
12470Y/7200-120/240 VOLTS. REFER TO TECHNICAL
SPECIFICATION IN APPENDIX D.
3 EA
TRANSFORMER, CONVENTIONAL, SINGLE PHASE, 25 KVA,
12470Y/7200-120/240 VOLTS. REFER TO TECHNICAL
SPECIFICATION IN APPENDIX D.
2 EA
TRANSFORMER, CONVENTIONAL, SINGLE PHASE, 50 KVA,
12470Y/7200-120/240 VOLTS. REFER TO TECHNICAL
SPECIFICATION IN APPENDIX D.
2 EA
GROUP #9 (OVERHEAD TRANSFORMERS)
TOTAL BID FOR GROUP #9 (BID ITEMS #69 THROUGH #71)
GROUP #8 (GROUNDING)
TOTAL BID FOR GROUP #8 (BID ITEMS #63 THROUGH #68)
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
72 BOLT, MACHINE, 5/8" X 12" 75 EA
73 BOLT, MACHINE, 5/8" X 14" 75 EA
74 BOLT, MACHINE, 5/8" X 16" 50 EA
75 EYEBOLT, 5/8" X 12" 25 EA
76 EYEBOLT, 5/8" X 14" 25 EA
77 EYEBOLT, 5/8" X 16" 25 EA
78 EYENUT, 5/8" 25 EA
79 LOCKNUT, MF, 3/4" 25 EA
80 LOCKNUT, MF, 5/8" 200 EA
81 WASHER, SQUARE, 2-1/4", 11/16" HOLE 200 EA
82 WASHER, 3" SQUARE, CURVED, 11/16" HOLE 50 EA
83 WASHER, 3" SQUARE, CURVED, 13/16" HOLE 50 EA
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
84 BRACKET, EQUIPMENT, SINGLE PHASE, FIBERGLASS 17 EA
85 BRACKET, EQUIPMENT, THREE PHASE, FIBERGLASS 1 EA
BRACKET, TRANSFORMER CLUSTER MOUNT, COMPLETE
WITH MOUNTING HARDWARE
1 EA
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
87 WIRE, #1/0 ALUMINUM 15KV UD CABLE 5,690 LF
TOTAL BID FOR GROUP #10 (BID ITEMS #72 THROUGH #83)
GROUP #11 (EQUIPMENT BRACKETS)
TOTAL BID FOR GROUP #11 (BID ITEMS #84 THROUGH #86)
GROUP #12 (UTILITY UNDERGROUND PRIMARY CABLE WIRE)
TOTAL BID FOR GROUP #12 (BID ITEM #87)
NOTE: MAXIMUM REEL SIZE SHALL BE 72" FLANGE HEIGHT x 56" OUTSIDE WIDTH. ACTUAL CABLE
LENGTHS PER REEL SHALL NOT BE LESS THAN SPECIFIED OR MORE 5% GREATER THAN SPECIFIED
(MINIMUM TOLERANCE 0%, MAXIMUM TOLERANCE 5%)
GROUP #10 (HARDWARE)
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
CABLE, UNDERGROUND TRIPLEX, #4/0 ALUMINUM,
RUGGEDIZED OR HI-SCORE, SWEETBRIAR, PACKAGED ON
THREE (3) 1000' REELS
3,000 LF
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
89 200A 15 KV 3-WAY CABLE JUNCTION ENCLOSURE 2 EA
200A 15 KV KV 3-WAY CABLE JUNCTION ENCLOSURE BOX
PAD
2 EA
91 15 KV 200A LOADBREAK JUNCTION BARS, THREE-POSITION 3 EA
92 15 KV 200A FEEDTHRU PARKING STAND, 2-WAY 1 EA
200A 15 KV LOADBREAK ELBOW TERMINATION, #4/0 AL WITH
CABLE SHIELD
43 EA
94 BUSHING CAP, 15 kV, 200A LOADBREAK 6 EA
CABLE TERMINATOR, 15 KV, FOR #4/0 AL 15 KV 220 MIL JCN
CABLE
13 EA
96 10KV ELBOW SURGE ARRESTER 1 EA
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
97 LUMINAIRE, STREETLIGHT, COBRA, LED, 73 WATT 13 EA
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
SECONDARY PEDESTAL, BASE & COVER, WITH HEX HEAD
BOLTS & 3-350 MCM CONNECTORS
6 EA
TOTAL BID FOR GROUP #14 (BID ITEMS #89 THROUGH #96)
TOTAL BID FOR GROUP #15 (BID ITEM #97)
GROUP #15 (PAD MOUNTED TRANSFORMERS)
TOTAL BID FOR GROUP #16 (BID ITEM #98)
GROUP #16 (SECONDARY PEDESTALS)
GROUP #13 (UTILITY UNDERGROUND SECONDARY CABLE WIRE)
TOTAL BID FOR GROUP #13 (BID ITEM #88)
GROUP #14 (UNDERGROUND CONDUCTOR ACCESSORIES)
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
Bid
Item Description Unit Price
No.
Req'd Unit Extended Price Manufacturer & Catalog No. Delivery Time
99 CONDUIT, CABLE RISER, SCHEDULE 80 PVC, 2" 330 LF
CONDUIT STANDOFF BRACKET AND T-SLOT BAR,
ALUMINUM
32 EA
101 CONDUIT STRAP, 2" 44 EA
TOTAL BID FOR GROUP #17 (BID ITEMS #99 THROUGH #101)
GROUP #17 (CONDUIT)
Appendix B
APPENDIX B
BILL OF MATERIALS
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
ITEM # ITEM MANUFACTURER & CATLOG NO.
QTY
REQ'D
GROUP #1 (STEEL POLES)
1 30/4 STEEL POLE. REFER TO TECHNICAL SPECIFICATION IN APPENDIX C. VALMONT, MEYERS, GRID STRUCTURES, OR MD HENRY 1
2 45/H1 STEEL POLE. REFER TO TECHNICAL SPECIFICATION IN APPENDIX C. VALMONT, MEYERS, GRID STRUCTURES, OR MD HENRY 9
3 50/H1 STEEL POLE. REFER TO TECHNICAL SPECIFICATION IN APPENDIX C. VALMONT, MEYERS, GRID STRUCTURES, OR MD HENRY 6
GROUP #2 (OVERHEAD UTILITY WIRE)
4 WIRE, COVERED, THHN, #4 COPPER SOUTHWIRE OR EQUAL 20
5 WIRE, COVERED, THHN, #2 COPPER SOUTHWIRE OR EQUAL 40
6 WIRE, COVERED, THHN, #1/0 COPPER SOUTHWIRE OR EQUAL 20
7 WIRE, COVERED, THHN, #2/0 COPPER SOUTHWIRE OR EQUAL 60
8 WIRE, 336.4 KCMIL 18/1 ACSR "MERLIN" SOUTHWIRE OR EQUAL 5,694
9 WIRE, 477.0 kCMIL 18/1 ACSR "PELICAN" SOUTHWIRE OR EQUAL 4,015
10 WIRE, #1/0 AL TRIPLEX "NERTINA" SOUTHWIRE OR EQUAL 250
11 WIRE, #2 AL TRIPLEX "CONCH" SOUTHWIRE OR EQUAL 500
12 WIRE, GROUND, #4 SD BARE SOLID COPPER SOUTHWIRE OR EQUAL 1,000
13 WIRE, GROUND, #2 SD BARE STRANDED COPPER SOUTHWIRE OR EQUAL 300
14 WIRE, WILDLIFE, 15 KV, #4 COPPER SOUTHWIRE OR EQUAL 250
GROUP #3 (DISTRIBUTION CROSSARMS & SUPPORTS)
15 CROSSARM, TANGENT, FIBERGLASS, 8', GRAY PUPI "TB2000-096-04X2", ALFO "FTA20-4-096-A-IP" OR EQUAL 9
16 CROSSARM, TANGENT, FIBERGLASS, 10' GRAY PUPI "TB2000-120-05X2", ALFO "FTA20-6-120-A-IP" OR EQUAL 2
17 CROSSARM, DEADEND, FIBERGLASS, 8', GRAY PUPI "DA3000-096-E2-B7X2", ALFO "FDA30-2-96-EB-IP-FG" OR EQUAL 4
18 CROSSARM, DEADEND, FIBERGLASS, 10', GRAY PUPI "DA3000-120-E2-B9X2", ALFO "FDA30-2-120-EB-IP-FG" OR EQUAL 5
19 PIN, CROSSARM, CLAMP TYPE MPS "J3322Z", HPS "14322P", ALFO "AF3322" 14
20 PIN, CROSSARM, PIN TYPE "MPS "J626Z", HPS "883P", ALFO "AF207" 14
21 CLEVIS, SECONDARY, ONE SPOOL MPS "J251", HPS "C2070024", ALFO "AF1300", ALLIED BOLT "8479" 8
22 PIN, RIDGE, FIBERGLASS, 2" x 18" MPS "G1HDR118AS1", HPS "RPH181", ALFO "F1CS-HV-V18-RHP1" 14
23 PIN, HORIZONTAL, FIBERGLASS, 1-1/2" x 18" MPS "G1MDA118AS1", HPS "1SBM18H1", ALFO "F1CS-MV-18-BHP-1" 1
24 FIBERGLASS EXTENSION LINK, CLEVIS-EYE, 12" MPS "GTCE15-12R", HPS "GS16012CE", ALFO "FGS16-12CT" 18
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
ITEM # ITEM MANUFACTURER & CATLOG NO.
QTY
REQ'D
GROUP #4 (DISTRIBUTION INSULATORS)
25 INSULATOR, DEADEND, POLYMER, 35 KV MPS "DS35M", PPC "PDEI-35", GAMMA "PS035", ALFO "DEI-35" 60
26 INSULATOR, PIN TYPE, 15 KV PPC "366-S", VICTOR "6R", GAMMA "6183-R" 48
27 INSULATOR, SPOOL PPC "5101", VICTOR "VI 2612", GAMMA "8442-70" 24
GROUP #5 (DISTRIBUTION CONDUCTOR ACCESSORIES)
28 CLAMP, DEADEND, #336.4 KCMIL - 954 kCMIL ACSR MPS "HDSO-116-2", HPS "ADEZ116N", ALFO "DES-HDSO-116" 70
29 CLAMP, DEADEND, #4/0 ACSR - 556 KCMIL ACSR MPS "ASO-858-2-N", HPS "ADEZ88N", ALFO "DES-ASO-858-2-N" 10
30 CLAMP, HOTLINE, #8 - #2/0 CU MPS "C-1520", HPS "BC20", ALFO "AF-BC20", R1MA "BHLC-100" 25
31 CLAMP, STIRRUP, #6- #2/0 ACSR MPS "L8-0-N", HPS "AHLS022019E" 25
32 CONNECTOR, MULTI TAP UTILICO "PTT4-250", BLACKBURN "ABP440", POLARIS "PPT250-4" 21
33 SERVICE GRIP, #2 AL TRIPLEX PREFORMED "SG4504" OR EQUAL 5
34 SERVICE GRIP, #1/0 AL TRIPLEX PREFORMED "SG4506" OR EQUAL 10
35 CONNECTOR, COMPRESSION, #4-6 CU-#4-6 CU BLACKBURN "CF-44-1" OR EQUAL 50
36 CONNECTOR, COMPRESSION, #336.4 KCMIL ACSR-#2-#6 CU BURNDY "YHN-500", BLACKBURN "WR699" OR EQUAL 50
37 CONNECTOR, COMPRESSION, #2 CU-#4 CU BLACKBURN "CF-44-1" OR EQUAL 10
38 CONNECTOR, COMPRESSION, #4/0-477.0 KCMIL ACSR-#4/0-477.0 kCMIL ACSR BURNDY "YHN-525" OR BLACKBURN "WR885" 30
39 CONNECTOR, COMPRESSION, #6 CU- GUY STRAND BURNDY "UCK1UL", BLACKBURN "K1" 10
40 TOP TIE, 477.0 ACSR PLP UTF-1211 50
41 ALUMINUM TIE WIRE, #4 (25 LB SPOOL) PRIORITY WIRE & CABLE "AL-TIEWIRE-4" OR EQUAL 1
TERMINAL, COMPRESSION, ALUMINUM OR COPPER, CABLE TO NEMA 2 HOLE PAD,
477/0 KCMIL ACSR SEFCOR "AL-90-2B" OR EQUAL 6
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
ITEM # ITEM MANUFACTURER & CATLOG NO.
QTY
REQ'D
GROUP #6 (DISTRIBUTION SWITCHES & ARRESTERS)
SWITCH, LOADBREAK, THREE POLE SIDEBREAK, 25 KV, 600 AMPERES, UNITIZED,
HOOKSTICK TYPE, COMPLETE WITH ALL MOUNTING HARDWARE S&C "147442R4-H-A2", HPS "AR113FHHL" 1
44 SWITCH, FUSED CUTOUT, 15 KV, 100 AMPERE MPS "SC15HG116-D", HPS "CP710114PB", ALFO "CSG15-100A-110-CB-16KA" 26
45 ARRESTER, SURGE, DISTRIBUTION CLASS, 10 KV MPS "ZHP010-0C00100", HPS "2137097324", ALFO "AHD10B-1GA-4X1-4X" 16
46 ARRESTER, SURGE, RISER CLASS, 10 KV MPS "ZRP010-0C00100", HPS "2216097324", ALFO "ARP10B-1GA-4X1-4X" 10
47 FUSE, EXPULSUION, 15 KV, 65 AMP TYPE "T" HPS "M65T23" OR EQUAL 10
48 FUSE, EXPULSUION, 15 KV, 3 AMP TYPE "K" HPS "M3K23" OR EQUAL 3
49 FUSE, EXPULSUION, 15 KV, 6 AMP TYPE "K" HPS "M6K23" OR EQUAL 2
50 FUSE, EXPULSUION, 15 KV, 10 AMP TYPE "K" HPS "M10K23" OR EQUAL 2
GROUP #7 (GUYING)
51 3/8" H.S. STEEL GUY STRAND, FURNISH ON 250' COILS NATIONAL STRAND, AMERICAN WIRE GROUP OR EQUAL 250
52 7/16" E.H.S. STEEL GUY STRAND, FURNISH ON 250' COILS NATIONAL STRAND, AMERICAN WIRE GROUP OR EQUAL 250
53 ANCHOR, POWER SCREW, 1-1/2" SS, 8/10" DOUBLE HELIX MPS "D6632", HPS "012642AE" 5
54 SQUARE SHAFT EXTENSION, 1-1/2" x 5' MPS "D6620-U", HPS "12656" 10
55 GUY TERMINATION, TWINEYE, 1-1/2" SS MPS "D6604US", HPS "C1020024" 5
GUY STRAIN INSULATOR, FIBERGLASS, CLEVIS- ROLLER, 15,000 LB RATING, 144"
LENGTH MPS "GCC15-144R", HPS "GS16144CC1", ALFO "FGS16-144CR" 2
GUY STRAIN INSULATOR, FIBERGLASS, CLEVIS- ROLLER, 21,000 LB RATING, 144"
LENGTH MPS "GCC21-144R", HPS "GS21144CC1", ALFO "FGS21-144CR" 4
58 GUY GRIP, 3/8", PREFORMED PLP "GDE-1107", HPS "FWDE1107" 50
59 GUY GRIP, 7/16", PREFORMED PLP "GDE-1108", HPS "FWDE1108" 25
60 POLE EYE PLATE, WITHOUT CLEATS, 3" BOLT SPACING REQUIRED MPS "MGA-345N", ALLIED BOLT "22002" 25
61 GUY THIMBLE, CLEVIS TYPE MPS "CT88", HPS "TC1", ALFO "AFCT88" 25
62 GUY MARKER, YELLOW PLASTIC, 8' LENGTH PLP "PG6500SC", MPS "J1493Y" 30
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
ITEM # ITEM MANUFACTURER & CATLOG NO.
QTY
REQ'D
GROUP #8 (GROUNDING)
63 GROUND ROD, COPPER CLAD, 5/8" X 8' ERICO "615883" OR EQUAL 16
64 CLAMP, GROUND ROD, BRONZE, 5/8" ERICO "HDC58R", BURNDY "GRC58" OR EQUAL 16
65 GROUND ROD, COPPER CLAD, 3/4" X 10' ERICO "615883" OR EQUAL 17
66 CONNECTOR, COMPRESSION, 3/4" ROD - #2 CU BURNDY "YSHG3429" OR EQUAL 17
67 CONNECTOR, COMPRESSION, #4/0-#2 CU - #4/0-#2 CU BURNDY "YH2929" OR EQUAL 75
68 TRANSFORMER TANK GROUND LUG, #8-#2/0 CU, 1/2"-13 THREAD MPS "TG-820", HPS "GTCL34A" OR EQUAL 50
GROUP #9 (OVERHEAD TRANSFORMERS)
TRANSFORMER, CONVENTIONAL, SINGLE PHASE, 15 KVA, 12470Y/7200-120/240
VOLTS. REFER TO TECHNICAL SPECIFICATION IN APPENDIX D. ABB/HITACHI, ERMCO, EATON, POWER PARTNERS, HOWARD 3
TRANSFORMER, CONVENTIONAL, SINGLE PHASE, 25 KVA, 12470Y/7200-120/240
VOLTS. REFER TO TECHNICAL SPECIFICATION IN APPENDIX D. ABB/HITACHI, ERMCO, EATON, POWER PARTNERS, HOWARD 2
TRANSFORMER, CONVENTIONAL, SINGLE PHASE, 50 KVA, 12470Y/7200-120/240
VOLTS. REFER TO TECHNICAL SPECIFICATION IN APPENDIX D. ABB/HITACHI, ERMCO, EATON, POWER PARTNERS, HOWARD 2
GROUP #10 (HARDWARE)
72 BOLT, MACHINE, 5/8" X 12" MPS "J8812", HPS "8812", ALFO "AF8812" 75
73 BOLT, MACHINE, 5/8" X 14" MPS "J8814", HPS "8814", ALFO "AF8814" 75
74 BOLT, MACHINE, 5/8" X 16" MPS "J8816", HPS "8816", ALFO "AF8816" 50
75 EYEBOLT, 5/8" X 12" MPS "J9412", HPS "29962", ALFO "AF9412" 25
76 EYEBOLT, 5/8" X 14" MPS "J9414", HPS "29964", ALFO "AF9414" 25
77 EYEBOLT, 5/8" X 16" MPS "J9416", HPS "29966", ALFO "AF9416" 25
78 EYENUT, 5/8" MPS "J1092", HPS "6502", ALFO "AF1092", ALLIED BOLT "5876" 25
79 LOCKNUT, MF, 3/4" MPS "J8583", HPS "3512", ALFO, "AF8583", ALLIED BOLT "22010" 25
80 LOCKNUT, MF, 5/8" MPS "J8584", HPS "3513", ALFO "AF8584", ALLIED BOLT "22011" 200
81 WASHER, SQUARE, 2-1/4", 11/16" HOLE MPS "J1075", HPS "6813", ALFO "AF1075", ALLIED BOLT "11500" 200
82 WASHER, 3" SQUARE, CURVED, 11/16" HOLE MPS "J113", HPS "682312", ALFO "AF113", ALLIED BOLT "233" 50
83 WASHER, 3" SQUARE, CURVED, 13/16" HOLE MPS "J6823", HPS "682312", ALFO "AF6823", ALLIED BOLT "244" 50
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
ITEM # ITEM MANUFACTURER & CATLOG NO.
QTY
REQ'D
GROUP #11 (EQUIPMENT BRACKETS)
84 BRACKET, EQUIPMENT, SINGLE PHASE, FIBERGLASS MPS "G1MA0HBDDB", HPS "1SBM18CTB", ALFO "F1CA-MV-H18-D3-H" 17
85 BRACKET, EQUIPMENT, THREE PHASE, FIBERGLASS MPS "G3MA014824DDB", HPS "3SBM4818CTB", ALFO "F3CA-MV-H4824-D3-H" 1
BRACKET, TRANSFORMER CLUSTER MOUNT, COMPLETE WITH MOUNTING
HARDWARE MPS "C15M39", HPS "C15M3-9", ALFO "15M3-9" 1
GROUP #12 (UTILITY UNDERGROUND PRIMARY CABLE WIRE)
87 WIRE, #1/0 ALUMINUM 15KV UD CABLE
OKONITE "162-23-3081", OR EQUAL BY PRYSMIAN, KERITE, SOUTHWIRE -
FURNISHED ON THREE (3) 830 FOOT REELS AND ONE (1) 3,200 FOOT REEL 5,690
GROUP #13 (UTILITY UNDERGROUND SECONDARY CABLE WIRE)
CABLE, UNDERGROUND TRIPLEX, #4/0 ALUMINUM, RUGGEDIZED OR HI-SCORE,
SWEETBRIAR, PACKAGED ON THREE (3) 1000' REELS SOUTHWIRE OR EQUAL 3,000
GROUP #14 (UNDERGROUND CONDUCTOR ACCESSORIES)
89 200A 15 KV 3-WAY CABLE JUNCTION ENCLOSURE HOWARD "4584-268-770-4YY" OR EQUAL 2
90 200A 15 KV KV 3-WAY CABLE JUNCTION ENCLOSURE BOX PAD CONCAST "FC-23-85-32-1880" OR EQUAL 2
91 15 KV 200A LOADBREAK JUNCTION BARS, THREE-POSITION 3M "215J3B", ELASTIMOLD "164J3-5", OR EQUAL 3
92 15 KV 200A FEEDTHRU PARKING STAND, 2-WAY ELASTIMOLD "164FT", EATON "LPF215H", OR EQUAL 1
93 200A 15 KV LOADBREAK ELBOW TERMINATION, #4/0 AL WITH CABLE SHIELD
3M "215LB508B", ELASTIMOLD "162LR-C5270-S", EATON "LE215-CC-09-CS" OR
EQUAL 43
94 BUSHING CAP, 15 kV, 200A LOADBREAK 3M "215LBI", ELASTIMOLD "167DRG", OR EQUAL 6
95 CABLE TERMINATOR, 15 KV, FOR #4/0 AL 15 KV 220 MIL JCN CABLE
3M “7652-S-4(L)” (TERMINATOR), CROSS ARM MOUNTING BRACKET "MB-4",
AND “SC0030”(STEM CONNECTOR), OR EQUAL 13
96 10KV ELBOW SURGE ARRESTER 3M "215SA10", ELASTIMOLD "167ESA-10", EATON "3238018C10M", OR EQUAL 1
GROUP #15 (PAD MOUNTED TRANSFORMERS)
97 50 KVA 1P PAD-MOUNTED TRANSFORMER ERMCO, HOWARD, OR HITACHI 13
GROUP #16 (SECONDARY PEDESTALS)
SECONDARY PEDESTAL, BASE & COVER, WITH HEX HEAD BOLTS & 3-350 MCM
CONNECTORS PENCELL "AG18-L350" 16
NOTE: MAXIMUM REEL SIZE SHALL BE 72" FLANGE HEIGHT x 56" OUTSIDE WIDTH. ACTUAL CABLE LENGTHS PER REEL SHALL NOT BE LESS THAN SPECIFIED OR MORE 5% GREATER
THAN SPECIFIED (MINIMUM TOLERANCE 0%, MAXIMUM TOLERANCE 5%)
CONSTRUCTION OF PARKVIEW DEVELOPMENT ELECTRICAL SITE PACKAGE (RE-BID)
COLUMBUS REDEVELOPMENT AUTHORITY
COLUMBUS, MISSISSIPPI
ITEM # ITEM MANUFACTURER & CATLOG NO.
QTY
REQ'D
GROUP #17 (CONDUIT)
99 CONDUIT, CABLE RISER, SCHEDULE 80 PVC, 2" CARLON, CANTEX, ALLIED TUBE & CONDUIT, OR EQUAL 330
100 CONDUIT STANDOFF BRACKET AND T-SLOT BAR, ALUMINUM HPS "C6CSO24" 32
101 CONDUIT STRAP, 2" HPS "CSTK2", ALFO "STK2", OR EQUAL 44
Appendix C
APPENDIX C
SPECIFICATIONS FOR STEEL DISTRIBUTION POLES
1.1 METAL POLES
A. Manufacturers
1. McWane, M.D. Henry, Valmont, Meyer Steel Poles, or as accepted.
2. Substitutions: As accepted by the Engineer.
B. Product Description:
1. Metal distribution poles, galvanized steel or ductile iron, designed, detailed, and fabricated in accordance with the requirements of this Specification.
2. Poles shall have a neat and pleasing appearance. The shafts of poles shall be tapered one-piece or multi piece sections having a circular cross section. Shafts shall be provided with holes for attaching accessories consisting of horizontal post insulators, miscellaneous attachment brackets, and bolting materials. The drilling and structural information for each type of pole will be provided on the attachments for each pole type.
3. Poles shall be furnished with top cap and a bottom plate.
4. Climbing provisions (steps, ladders) are not required.
5. Poles will be direct embedded.
C. Quality Assurance:
1. Pole manufacturer must have sufficient metal poles in service by utility companies to allow verification of service operation by Engineer.
2. The manufacturer shall have a minimum of 5 years of experience in the design and production of metal distribution poles.
D. References:
1. Galvanized Steel materials and construction furnished shall conform to ASCE Manual No 48, Design of Steel Transmission Pole Structures.
2. Ductile Iron materials and construction shall conform to all applicable ANSI standards.
E. Design:
1. Wood Pole Equivalents: For poles designated by height and class, metal structures shall be equivalent to southern yellow pine treated poles of the height and class.
2. The maximum design unit stress shall be the minimum yield strength as stated in applicable
ASTM specifications for the particular application and types of loads, including load factors.
3. Pole shall be designed with the minimum number of joints. Field welding shall not be allowed as a part of the design of a new pole. The shaft joints to be made in the field shall be slip joints or bolted flange joints. Slip joints shall be designed for a nominal lap that will develop the full required design strength of the pole at that point. The minimum lap shall meet the requirements of ASCE Manual No. 48.
4. Manufacturer shall verify slip joint fit before shipment. Joints should not interfere with joints, step nuts, ladder clips, or jacking nuts. Sufficient jacking lugs and permanent orientation marks shall be provided at all slip joints to ensure proper alignment and complete overlap of the joint.
5. Minimum plate thickness for all pole components is 3/16”.
6. Poles shall have nearly a uniform taper throughout their entire length. The maximum difference in tapers between two pole sections measured by the diameters shall be 0.20
Appendix C inch/ft. for poles with variable taper.
7. In the design of connections for brackets, or stiffeners attached to the pole shaft, care shall be taken to distribute the loads sufficiently to protect the wall of the pole from loyal buckling.
F. Fabrication:
1. All welding shall be in accordance with the American Welding Society Code AWS D1.1, latest edition. Welders shall be qualified in accordance with AWS D1.1 welding procedures.
2. Welding materials are to be compatible with the parent material. Welding electrodes shall meet the Charpy impact requirements as the parent material.
3. Non-destructive testing shall be performed in accordance with the requirements of AWS
D1.1.
4. Holes for connection bolts shall be 1/8 inch larger than the nominal diameter of the bolts.
5. Holes which are punched must be smooth and cylindrical without excessive tear-out or depressions. Any burrs that remain after punching shall be removed by grinding, reaming, etc.
6. Holes of any diameter may be drilled in plate of any thickness. Care shall be taken to maintain accuracy when drilling stacks of plates.
7. Holes may be made by use of a machine-guided oxygen torch. Flame-cut edges shall be reasonably smooth and suitable for the stresses transmitted to them.
8. For steel poles, all drilling shall be performed prior to galvanizing.
G. Finishes:
1. Steel Structures:
a. All structures and structural components shall be hot-dip galvanized to meet all the requirements of ASTM A123 or ASTM A153. Measures shall be taken to prevent warping and distortion according to ASTM A384 and to prevent embrittlement according
ASTM A143.
b. Embedded Portion of Structure: Structures shall be provided with a 16 mil (minimum dry film thickness), two component hydrocarbon extended polyurethane coating that is resistant to ultraviolet light shall be applied on the exposed surface of the embedded portion of the pole. The coating shall extend from the butt to the top of the ground sleeve.
Other coatings shall be approved by the owner prior to their use.
c. Quality Assurance: Compliance with coating thickness requirements shall be checked with a magnetic thickness gauge.
2. Ductile Iron Structures:
a. Poles shall receive a base coat of arc-melted 100% zinc at a minimum rate of 0.13 grams per square inch. Poles shall be provided with self-protecting weathered finish.
b. Additional corrosion protection shall begin one-foot above ground and extend to the butt, both inside and outside, using ceramic epoxy coating, 20 mil (minimum dry film thickness).
c. Quality Assurance: Compliance with coating thickness requirements shall be checked with a magnetic thickness gauge.
3. Bolts and Nuts:
a. Bolts and nuts with yield strengths under 100,000 psi shall be hot-dip galvanized per
ASTM A153 and ASTM A143, or mechanically coated with zinc in accordance with ASTM B454, Class 50. Bolting materials with yield strengths in excess of 100,000 psi shall not be hot dip galvanized. Instead, they shall be painted with zinc enriched paint or mechanically coated with zinc per ASTM B454, Class 50.
Appendix C
H. Features:
1. Ground Collars: All metal poles shall be furnished with ground collars. Ground collars shall have a minimum thickness of 3/16″, a minimum length of 48″, and shall be located on the centerline of the designated ground line. Ground collars shall not be considered in strength calculations. A seal weld shall be provided around the ground collar at the top and bottom of the ground collar.
2. Pole Drilling: All metal distribution poles shall be fabricated with holes at the proper locations as shown in Pole Drilling Drawing furnished to Manufacturer by the OWNER.
OWNER will confirm that all poles are drilled properly (size, location and quadrant) at delivery. OWNER will reject any poles improperly drilled.
3. Bearing Plate: All metal distribution poles shall have bearing plates. Bearing plates shall have a diameter not more than 2 inches greater than the maximum diameter at the pole butt.
Each bearing plate shall have a drain hole at the bottom which is not greater than 30 percent of the bearing pate area.
4. Top Plate: All metal distribution poles shall be permanently covered with a structural metal plate bolted or permanently attached to the pole. The pole shall be delivered with the pole cover attached in place.
5. Inserts: Plastic plugs shall be installed in all nuts welded to the structure and all tapped holes.
6. Grounding: All metal distribution poles shall have threaded ½”-13 UNC threaded square or hex nut grounding connections welded to the structure at locations as shown on the Pole Drilling Detail drawings. Threads shall be protected during galvanizing.
7. Nameplates: Metal poles shall have a permanently mounted nameplate approximately 5 feet above the ground line. Name plate shall show the following data as a minimum:
a. Manufacturer's name.
b. Month and year of manufacture.
c. Length and ultimate moment capacity of the pole.
d. Owner’s name.
e. Pole weight.
f. Pole Number. Number shall be assigned according to Pole Drilling Drawings furnished to Materialman by OWNER.
1.2 OTHER CONSIDERATIONS
A. The total prices shall be firm if accepted by the OWNER within forty-five (45) days and shall include the cost of delivery.
B. The MATERIALMAN shall supply with his proposal, descriptive literature on the metal distribution poles bid. This literature shall include, be not be limited to the following data:
1. Structure dimensions, geometry and weight.
2. Structure ultimate moment capacity.
3. Preliminary structure loading calculations.
C. The MATERIALMAN shall acknowledge in writing to the Engineer that the Owner's Purchase Order or acceptance has been received. The acknowledgement shall include the date that the Purchase Order or acceptance is received and the date that equipment delivery is expected.
D. As soon as practicable after receipt of Owner's Purchase Order or acceptance of MATERIALMAN's Proposal, submit to the ENGINEER at least four (4) bound copies of shop drawings and final structure loading calculations or the specified equipment. Each submittal shall
Appendix C be clearly marked with the project name, dated, and accompanied by a letter of transmittal listing all items included in the submittal. After the ENGINEER has reviewed the shop drawings, satisfactory shop drawings will be accepted and dated, three sets will be retained by the ENGINEER, and the remaining sets will be returned to the MATERIALMAN. If the shop drawings are not accepted, one set will be retained by the ENGINEER and the remaining sets will be returned to the MATERIALMAN, with indications of the required corrections and changes made on one of the sets. Make such corrections and changes as indicated. Resubmit shop drawings as specified above, until acceptance has been obtained. No corrections or changes indicated on shop drawings shall be considered as an extra work order.
E. Acceptance of shop drawings by the ENGINEER will be general only, and such acceptance will not relieve the MATERIALMAN of responsibility for accuracy of such shop drawings, proper fitting, coordination, construction of work, and furnishing materials required by the Specifications but not indicated on shop drawings. The MATERIALMAN shall submit in writing any requests for modifications to the Specifications. Shop drawings submitted to the ENGINEER do not constitute "in writing" unless it is brought to the attention of the ENGINEER that specific changes are being suggested. Acceptance of shop drawings shall not be construed as approving departures from the Specifications.
F. Metal distribution poles shall be new and shall be designed and manufactured in the United States of America.
Appendix D
APPENDIX D
SPECIFICATIONS FOR POLE MOUNTED TRANSFORMERS
GENERAL
1.1 Section Includes:
A. Pole-Mounted Transformers.
1.2 STANDARDS
A. American National Standards Institute:
1. ANSI C57.12.10 - Requirements for Overhead-Type Distribution Transformers, 500 kVA and Smaller, High Voltage, 34 500 Volts and Below; Low Voltage, 7970/13800Y Volts and Below.
2. ANSI C57.12.31 - ANSI Standard for Pole Mounted Equipment - Enclosure Integrity.
3. ANSI C57.12.90 - Test Code for Liquid-Immersed Distribution, Power and Regulation Transformers and Guide for Short-Circuit Testing of Distribution and Power Transformers.
4. ANSI C57.91 - Guide for Loading Mineral Oil Transformers.
B. Institute of Electrical and Electronics Engineers:
1. IEEE C57.12.00 - Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers.
2. IEEE C57.106 - Guide for Acceptance and Maintenance of Insulating Oil in Equipment.
C. National Electrical Manufacturers Association:
1. NEMA TR1 - Transformers, Regulators and Reactors.
D. Department of Energy:
1. 10 CFR Part 431 - Department of Energy - Energy Conservation Program for Commercial Equipment: Distribution Transformers Energy Conservation Standards; Final Rule.
1.3 MATERIALS
A. All materials, equipment and appurtenances furnished shall be new.
1.4 SUBMITTALS
A. Submit shop drawings and product data on all equipment items specified in this section to be utilized on this Project.
1. Shop Drawings: Indicate electrical characteristics and connection requirements, outline dimensions, connection and support points, weight, specified ratings, and materials.
2. Product Data: Submit electrical characteristics and connection requirements, standard model design tests, and options.
Appendix D
PRODUCTS
2.1 SINGLE-PHASE POLE MOUNTED TRANSFROMERS
A. Manufacturers: Hitachi/ABB, Eaton; Howard Industries; ERMCO.
B. Product Description: ANSI C57.12.20, single phase, pole mounted, self-cooled transformer unit.
Transformers shall be new and shall be manufactured in the United States of America.
C. Cooling and Temperature Rise: IEEE C57.12.00, Class OA, 65 degrees C, self-cooled.
D. Insulating Liquid: Furnish with new (unused) mineral oil conforming to IEEE C57.106.
E. Service Conditions:
1. Meet requirements for usual service conditions described in IEEE C57.12.00.
2. Maximum Ambient Temperature: 104 degrees F.
F. Type: Conventional.
G. Ratings:
1. Capacity:
a. Three (3) 15 kVA single-phase pole mounted transformers.
b. Two (2) 25 kVA single-phase pole mounted transformers.
c. Two (2) 50 kVA single-phase pole mounted transformers.
2. Primary Voltage: 12470Y/7200 volts.
3. Taps: Standard primary taps, 2 FCAN and 2FCBN. Taps shall be suitable for de-energized operation only.
4. Secondary Voltage: 240/120 volts.
5. Impedance: ANSI C57.12.00 standard impedance.
6. Basic Impulse Level: 95 kV primary, 30 kV secondary.
H. Accessories:
1. Primary Bushings: Furnish with cover-mounted, wet process porcelain high voltage bushings (two bushings) with clamp style terminals in accordance with ANSI C57.12.20. The bushings shall be light gray in color.
2. Secondary Bushings: Furnish with sidewall-mounted porcelain low voltage bushings with clamp type terminals in accordance with ANSI C57.12.20. Number and arrangement of low voltage bushings shall be in accordance with ANSI C57.12.20.
3. Overvoltage Protection: Primary overvoltage protection shall be provided by using a direct connected, tank mounted, normal duty polymer surge arrester.
4. Grounding: Furnish with tank ground per ANSI C57.12.20 with connector to accept AWG 6 solid copper ground wire. Furnish with a tank ground for ground strap connection, properly sized to carry load and fault current, connected between the secondary neutral terminal and the tank ground.
Appendix D
5. Nameplate: Furnish stainless steel or anodized aluminum instruction nameplate in accordance with ANSI C57.12.00.
This is the start of the file's text. The full file is on GovTribe.