313332_MECH.pdf
PDF 4 MB Posted
- Attached to
- Repair Building Landing Zone K16 (MATOC ONLY)
- Solicitation number
- W90VN824R0047
About this file
This document appears to be a set of mechanical drawings and specifications related to the repair of Building S-302 (Landing Zone) on K-16 for the Department of the Army. The work includes repairs to the HVAC, plumbing, and fire protection systems. Key details include:
The mechanical scope of work involves repairing the heating and cooling system, plumbing system, and fire protection sprinkler system. This includes installing new square supply diffusers, plumbing fixtures, and quick response upright sprinkler heads. The contractor must submit shop drawings for approval prior to installation. The drawings provide details on the locations and specifications of the new mechanical systems. The contract is being solicited only to contractors under the MATOC contract for Areas I and II.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W90VN824R0047.pdf | ||
| 313332_DWG_TITLE-SHEET.pdf | ||
| 313332_DWG_ELEC.pdf | ||
| 313332_DWG_ARCH.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M-1
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SYMBOLS
MECHANICAL MATERIAL INDICATIONS &
M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S
NTS
PD
Pa
OS&Y
OXY
OD
OAIL
OA
QT
PRV
PPM
POL
POC
PLMB
PH
PG
RT
RPM
RH
RDTR
RA
R12, R22
QTY
A B B R E V I A T I O N S
SBM
SAN
SA
SCH
FLOWMETER, ORIFICEBUTTERFLY
REFRIGERANT LIQUID
CHILLED WATER SUPPLY
CHILLED WATER RETURN
AIR COOLED CONDENSING UNIT
AIR CONDITION UNIT (S)
APPARATUS DEW POINT
AIR CONDITION (-ING,-ED)
CHILLED/HOT WATER RETURN
AMERICAN WIRE GAUGE
PRESSURE, BAROMETRIC
CUBIC METER PER HOUR
CHILLED/HOT WATER SUPPLY
CAPACITYCAP
CONNECTION
CONTINUE
COMPRESSOR
CUBIC METER
CPRSR
CONN
CONT
CU M
CHILLED WATER
CAST IRON PIPE
CIRCUIT
CLASSIFICATION
COOLING LOAD
COEFFICIENT
COUNTER CLOCKWISE
CLASS
CLG LOAD
COEF
CMH
CIP
CCW
CHW
CKT
ACV ALARM CHECK VALVE
AVERAGEAVG
BOILING POINT
CENTIGRADE
BAROMETER(-TRIC)
BRAKE HORSEPOWER
BP
BHP
C
BARO PR
AWG
BARO
ALUMINUM
ALTITUDE
AMBIENT
AIR HANDLING UNIT
AMPERE(AMP, AMPS)
APPROXIMATEAPPROX
ALT
AMB
AMP
AIR COND
ADP
AL
AHU
AIR COOLED
ACCU
ACLD
ACU
CHR
C/HWR
C/HWS
CHS
RL
D DRAIN
DIAMETER, INSIDE
ISOMETRIC
IRON PIPE SIZE
JOULE
THERMAL CONDUCTIVITY
KILOGRAM
KILOGRAM PER SQ. CENTIMETER (GAUGE)
KILOGRAM PER SQ. CENTIMETER
KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)
KILOCALORIE PER HOUR
EXPANSION JOINT
EXPLOSION PROOF
FIRE HOSE CABINET
FULL LOAD AMPERES
ENTERING WATER TEMP
EVAPORAT (-E,-ING,-ED,-OR)
EXTERNAL STATIC PRESSURE
FACE AREA OR FRESH AIRFA
FHC
FHY
FLA
FIRE HYDRANT
ESP
EXPJT
EWT
EVAP
EP
EQPT
ENT
EFF
EQUIPMENT
ENTERING
EFFICIENCY
KG/SQ CM
KG/SQ CM A
KG/SQ CM G
KG
KCAL/HR
J
K
ID
ISO
IPS
NO
N.O.
NIC
NPT
MPS
NC
N/A
N.C.
MAX
MIN
MPH
MM
NOT IN CONTRACT
NATIONAL TAPER PIPE (THREAD)
NUMBER
NORMALLY OPEN
MINIMUM OR MINUTE
METERS PER HOUR
METERS PER SECOND
NORMALLY CLOSED
NOISE CRITERIA
NOT APPLICABLE
MAXIMUM
MILLIMETER R
FEMALE PIPE THREAD
FUEL OIL
GALVANIZED STEEL
GAGE OR GAUGE
FIXTURE
FEED WATER PUMP
FACE VELOCITY
FLUSH VALVE
FREQUENCY
FIBERGLASS REINFORCED PLASTIC
HORIZONTAL
HOT WATER HEATER
HOT WATER
HOUR(S)
HORSEPOWER
MERCURY
HEAD
HOSE BIBB
HERTZ
GRAMS
FRPCWP CIRCULATING WATER PUMP
DIRECT EXPANSION
DRY PIPE VALVE
EQUIVALENT DIRECT RADIATION
ENTERING AIR TEMPERATURE
DOUBLE POLE DOUBLE THROW
DEWPOINT TEMPERATURE
DRY BULB TEMPERATURE
DECIBEL OR DRY BULB
DIESEL OILDO
ECON
ECC
EAT
EDR
DX
DPV
DPDT
DPT
ECONOMIZER
ECCENTRIC
o
DIFF
DIAG
DIA or
DIV
DBT
DB
DIFFERENCE
DIAGRAM
DIAMETER
DIVISION
DEGREE
HR
HORIZ
HWH
HW
HZ
HP
HG
HD
HB
GALVS
GA
GR
FXTR
FWP
FVEL
FV
CUBIC MILLIMETER
CLOCKWISE OR COLD WATER
COEFFICIENT, VALVE FLOWCv
CU MM
CW
PLUG VALVE
THREE WAY
FPT
FO
FREQ
GATE, ANGLE
GATE, GLOBE
GLOBE
GATE
CONTROL
KJ KILOJOULE
LH
LT
LWT
LPS
M
LL
LPD
LPH
LM
LAV
LAT
LBS
LG
KW
KWH
L
LATENT HEAT
LEAVING WATER TEMPERATURE
LITERS PER HOUR
LITERS PER SECOND
LAUNDRY TRAY
METERS
LIQUID LINE
LITERS PER DAY
LINEAR METER
LEAVING AIR TEMPERATURE
LAVATORY
POUNDS
LENGTH
KILOWATT
KILOWATT HOUR
LITERS
P
FLOWMETER, VENTURI
FLOW SWITCH
PRESSURE SWITCH
PRESSURE GAUGE AND COCK
PUMP (INDICATE USE)
STRAINER
STRAINER, BLOW OFF
KG/SM
KG/SM A
KG/SM G
PS
P
OFM
FS
VFM
KILOGRAM PER SQ. METER
KILOGRAM PER SQ. METER (ABSOLUTE)
KILOGRAM PER SQ. METER (GAUGE)
JACKET WATER RETURN
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
PUMPED CONDENSATE
JACKET WATER SUPPLY
VACUUM PUMP DISCHARGE
FUEL OIL TANK VENT
CONDENSATE WATER SUPPLY
CONDENSATE WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
MEDIUM TEMPERATURE HOT WATER RETURN
LOW TEMPERATURE HOT WATER SUPPLY
LOW TEMPERATURE HOT WATER RETURN
PIPE TO BE REMOVED
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
LPS
CONTROL AIR MAIN
air conditioning and refrigeration
RD
RS
(NAME)E
(NAME)
M
EXISTING PIPE
COMPRESSED AIR
VACUUM (AIR)
HWR
VAC
A
MTWS
MTWR
HWS
FOD FUEL OIL DRAIN
FOR
CS
CR
FOV
FOG
FOS FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL GAUGE
PC
VPD
MU
LPC
BBD
MAKE UP WATER
MPS
MPC
JWR
JWS
heating
PIPING
CHECK, SWINGSANITARY DRAIN
PITCH OR PIPE, UP(U), DOWN(D)
FLOOR SINK (200mm x 200mm)
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
valves : (for selective actuators)
PLAN
HOSE BIBB
AIR LINEA
BALL
ELEV.
BACKFLOW PREVENTER
PIPE SLEEVE
(NAME)
ACID
200mm x 200mm
SURFACE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
CHEMICAL SUPPLY PIPES
FUNNEL DRAIN, OPEN
FCO
FD
SCO
FLOOR OR GRADE
FLOOR OR GRADE
CONDENSATE DRAIN BELOW
CONDENSATE DRAIN ABOVE
ACID WASTE
GASG
CD
CD
AIR VENT, MANUAL
AIR VENT, AUTOMATIC
W/ MEASURING TAP
EXPANSION LOOP
EXPANSION JOINT
BALL JOINT
ANCHOR, MAIN
ANCHOR, INTERMEDIATE
ALIGNMENT GUIDE
AIR SEPARATOR
FLEXIBLE CONNECTOR
SQUARE HEAD BALANCING COCK
EJ
S
MV
AVV
CHECK, NON-SLAM
CONTROL, ELECTRIC-PNEUMATIC
CONTROL, PNEUMATIC-ELECTRIC
QUICK OPENING
PRESSURE REDUCING
NEEDLE
LOCK SHIELD
HOSE END DRAIN
SAFETY
RELIEF
SQUARE HEAD BALANCING COCK
QUICK CLOSING, FUSIBLE LINK
R
S
PE
EP
plumbing
COLD WATER
HOT WATER RETURN
HOT WATER SUPPLY
VENT
MOTOR ELECTRIC
DIAPHRAGM
valves, special duty :
SOLENOIDS
valve actuators
M
FDAD
SUCTIONQUANTITY SUCT
TONS OF REFRIGERATION
TEMPERATURE DIFFERENCE
HEAT TRANSFER COEFFICIENT
SANITARY
SUBMERSIBLE
SUPPLY AIR
SCHEDULE
RADIATOR
REFRIGERATION TON
REVOLUTIONS PER MINUTE
RELATIVE HUMIDITY
RETURN AIR
THERMAL RESISTANCE
REFRIGERANT (12, 22, ETC)
TYPICALTYP
URINAL
UNIT HEATER
UR
UH
U
THERMOSTAT
THICKNESS
THERMOMETER
TEMPERATURE
SYMBOL
TSTAT
TONS
THERM
THK
TEMP
TD
SYM
SINGLE POLE DOUBLE THROW
LPH, STANDARD CONDITIONS
LPS, STANDARD CONDITIONS
LPD, STANDARD CONDITIONS
SAYBOLT SECONDS UNIVERSAL
SAYBOLT SECONDS FUROL
SENSIBLE HEATOUTSIDE AIR INTAKE LOUVER SH
PRESSURE DROP OR DIFFERENCE
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PERCENT
PARTS PER MILLION
POINT OF CONNECTION
PLUMBING
PETROLEUM, OIL AND LUBRICANTS
QUART
OUTSIDE SCREW & YOKE
DIAMETER, OUTSIDE
PRESSURE GAGE
POLE
PASCAL
OXYGEN
SPRINKLERSPR
STEEL
STANDARD
STEAM
SQUARE
STAINLESS STEEL
STORAGESTOR
STL
STD
ST
SSU
SST
SSF
SQ
SENSIBLE LOAD
STATIC PRESSURE
SQUARE METER
SPECIFICATION
SPDT
SPEC
SM
SP
SLPH
SLPS
SLPD
SL
ALARM CHECK VALVE
SIDEWALL SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
FIRE DEPARTMENT CONNECTION
PRE-ACTION VALVE
NOT TO SCALE
OUTSIDE AIR
(2-WAY SHOWN)
DRY-PIPE VALVE
SECOND
SAFETY FACTOR
SPECIFIC GRAVITYSG
SF
SEC
VARIABLE AIR VOLUMEVAV
VENTILATION
PRESSURE, DYNAMIC(VELOCITY)
WATER-COOLED
WATER CLOSET
WATTHOUR OR WATER HEATER
WET BULB TEMPERATURE
WATERPROOF
WSHR
WCLD
WTRPRF
WH
WT
W/
WD
WC
WBT
WEIGHT
WITH
WASHER
WIDTH
VP
VOL
WB
W
VISC
VERT
VENT
VEL
VOLUME
WET BULB
WATT
VISCOSITY
VERTICAL
VELOCITY
MANUAL VOLUME DAMPER
SMOKE DAMPER (PROVIDE ACCESS DOOR)
PNEUMATIC OPERATED DAMPER
VLV
V
VAC
M
VALVE
VOLT
VACUUM
SPLITTER DAMPER
SD
AD
VD
grilles, registers and diffusers :
SG
SR
600/300
300x150
200mm NCD
FIGURE IS ON TOP
810mm x 400mm dampers
ELBOW, TURNED DOWN
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
TEE, OUTLET DOWN
TEE, SINGLE SWEEP
sprinkler
UNION, SCREWED
UNION, FLANGED
TEE, OUTLET UP
TEE
LATERAL
CONNECTION, BOTTOM
CONNECTION, TOP
ELBOW, TURNED UP
BUSHING
CAP
WELDED
FLANGED
SOLDERED
SCREWED BELL AND SPIGOT
SOLVENT CEMENT
SOUND ATTENUATOR
DETECTORS, FIRE AND/OR SMOKE
ELECTRIC MOTOR OPERATED DAMPER
FIRE DAMPER (PROVIDE ACCESS DOOR)
BACKDRAFT DAMPER
BDD
S
TRANSITION
TURNING VANES
SF
CHANGE OF ELEVATION, RISE(R), DOWN(D)
DUCT SECTION, NEGATIVE PRESS., FIRST
ACCESS DOOR, VERTICAL OR HORIZONTAL
COWL, (GOOSENECK) AND FLASHING
ACOUSTICAL LINING
FLEXIBLE DUCT
FLEXIBLE CONNECTIONFC
FIGURE IS ON TOP
R
AD
47.2
TG
94.4
UC 13mm
DG
500/300L
DUCT WORK
810mm x 400mm
810mm x 400mm
THERMOSTAT, ELECTRIC
TRAP, ELECTRIC (INDICATE TYPE)
fitting :
R
THERMOMETER
EXHAUST AIR GRILLE OR REGISTER, CEILING
DUCT SECTION, POSITIVE PRESS., FIRST
DIRECTION OF FLOW
SR
DIFFUSER, LINEAR
RETURN AIR GRILLE OR REGISTER, CEILING
CEILING DIFFUSER, SQUARE TYPE
CEILING DIFFUSER, ROUND TYPE (200mm
(600mm x 300mmH, 472 LPS)
UNDERCUT DOOR (13mm, 47.2 LPS)
DOOR GRILLE (300mmx150mmH)
NECK DIAMETER)
TRANSFER GRILLE ASSEMBLY
LOUVER, DOOR OR WALL
(500mmWx300mmH, 94.4 LPS)
RG
RR
SUPPLY AIR GRILLE OR REGISTER, SIDEWALL
EXHAUST AIR GRILLE OR REGISTER, CEILING
SUPPLY AIR GRILLE OR REGISTER, CEILING
ER
SG
EG
EXISTING WORK TO BE REMOVED.
POINT OF CONNECTION NEW TO EXISTING
OR END OF DEMOLITION WORK
EXISTING WORK TO REMAIN.(E)
(R) REMOVE EXIST WORK
C
A
REPAIR LANDING ZONE AREA
BLDG. S-302
K-16CHONG, ST
313332
M-2
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SCOPE OF WORK MECHANICAL GENERAL NOTES
3. MARK ALL EXPOSED INTERIOR PIPING AT 8 METER(26 FT) INTERVALS, WITH PLASTIC WRAPAROUND TYPE PIPE LABLES
CONFORMING TO ASME/ANSI A13,1-1996 "SCHEME FOR IDENTIFICATION OF PIPING SYSTEMS", INDICATING THE TYPE
OF FLUID CARRIED AND DIRECTION OF FLOW. LABELS ARE NOT REQUIRED ON SPRINKLER SYSTEM BRANCH LINES AND
PIPES LESS THAN 50MM (2 INCHES) IN NOMINAL.
4. PROVIDE ALL SEISMIC PROTECTION MEASURES FOR THE FIRE PROTECTION SYSTEM IAW NFPA 13 FOR "PROTECTION OF
PIPING AGAINST DAMAGE WHERE SUBJECT TO EARTHQUAKES". INCLUDING, BUT NOT LIMITED TO, SWAY BRACINGS, FLEXIBLE COUPLINGS, CLEARANCES, AND SEPARATION ASSEMBLES.
5. PROVIDE LABEL TAG INDICATING "NORMALLY OPEN" OR "NORMALLY CLOSED" ON ALL VALVES INCLUDING AND NOT LIMITED
TO ALL RISER AND TRIM, SECTIONAL VALVES, INSPECTIORS TEST VALVES AND DRAINS.
6. SPRINKLERS WITH O-RINGS ARE NOT PERMITTED. PLUG TYPE TAMPER SWITCH SHALL NOT BE USED.
7. INSATLL SYSTEM TEST CONNECTION ON WET PIPE SYSTEM AND SHALL BE LOCATED AT THE MOST REMOTE BRANCH LINE.
8. ALL VALVES ON WET PIPE SYSTEM SHALL MEET NFPA 13 REQUIREMENT.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS PRIOR TO
COMMENCING ANY CONSTRUCTION OR RENOVATION.
10. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE CLEARANCE, EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.
13. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE THE EXISTING EQUIPMENT ANY
14. CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY GOVERNMENT.
15. FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS PROJECT. THE
DETAILS WILL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK AT NO ADDITIONAL COST TO THE U.S.
GOVERNMENT.
16. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH DETAILS SHALL BE
PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE
CONTRACTING OFFICER FOR APPROVAL.
17. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN STRICT ACCORDANCE WITH
APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL, O & MA STANDARD TECHNICAL SPECIFICATIONS FOR
MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, ADJUSTING AND BALANCING (TAB) REPORT SHALL BE SUBMITTED
TO THE PROJECT COR FOR GOVERNMENT REVIEW AND APPROVAL.
18. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA STATIC PRESSURE
CALSS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.
28. PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE DRAWINGS OR NOT.
PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD OR CONCEALED CEILINGS.
30. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/NEW) SHALL BE SEALED PER SPEC.
31. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE AND SHALL BE VERIFIED
AT THE JOB SITE.
1. THE EQUIPMENT SHOWN ARE SUGGESTED LOCATIONS HOWEVER FINAL LAYOUT SHALL BE IN ACCORDANCE
WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND EQUIPMENT LISTINGS. CONTRACTOR
SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH, LIGHTING FIXTURES, AND HVAC DEVICES. ALL EQUIPMENT
SHALL BE UL LISTED AND/OR FM APPROVED IN ACCORDANCE WITH NFPA 13, NFPA 20 AND THE PROJECT SPECIFICATION.
2. THE CLEARANCES AROUND PIPE PENETRATION AT FIRE RATED WALLS AND/OR FLOOR SHALL BE PROPERLY SEALED
WITH APPROVED FIRE STOPPING MATERIAL IAW SPECIFICATION 07 84 00.
11. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS
CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AS DIRECTED BY THE CONTRACTING OFFICER.
19. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PROVIDE ACCESS DOORS
IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE
DETECTOR, BACKDRAFT DAMPERS AND FOR ANY ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION
12"X12" ACCESS PANELS FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANEL TO INSURE THAT
THE EQUIPMENT CAN BE MAINTAINED ADEQUATELY. PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH
WITH GYPBOARD OR CONCEALED CEILINGS.
20. INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1 / 4INCH PER 1FOOT. INSULATE ALL SEWER PIPING
RECEIVING AIR CONDITIONING CONDENSATE DRAINS, OR ANY OTHER COLD LIQUID WHICH MAY CREATE
CONDENSATION, FROM SINK BODIES EXPOSED TO AIR BELOW THE FLOOR.
21. PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN 30 DEGREES OR USE
RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH TAKE-OFFS FROM THE MAIN DUCT.
PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.
22. PIPING SYSTEM SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS AND FLUSHED UNTIL
ALL WATER BEING FLUSHED IS CLEAR AS TAP WATER.
23. ALL CONDENSATE DRAINS FROM COOLING UNIT (AS NOTED ON THE DRAWINGS) SHALL BE PROVIDED WITH
SHUT-OFF VALVE WITHIN 1M OF THE UNIT.
24. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION ACTIVITIES, AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE U.S. GOVERNMENT.
25. ALL EQUIPMENT CONNECTIONS TO DUCTWORK SHALL HAVE A MIN. OF 100MM OF REINFORCED CANVAS FLEXIBLE
DUCTWORK FOR VIBRATION ISOLATION.
26. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES, REFER TO
ARCHHITECTURAL DRAWINGS FOR CEILING TYPES.
27. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS. FIRE DAMPER
RATINGS SHALL BE COMPATIBLE WITH THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL LISTED.
29. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, CONDUITS
AND ALL NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.
32. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS. SHOP DRAWING SHALL NOT
BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO THE WORK PERFORMED UNDER THIS CONTRACT SHALL
BE REPAIRED OR REPLACED BY THIS CONTRACTOR.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS AS
NECESSARY TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE PROTECTION SYSTEM AT
NO ADDITIONAL COST TO THE GOVERNMENT, INCLUDING, BUT NOT NECESSARILY LIMITED TO ITEMS SUCH AS WALLS, CEILLING, ROOF, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.
33. PRIOR TO INSTALL NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST COORDINATE WITH THE EXIST
DUCTWORK AND PIPING ELEVATION/LOCATION. IF THE EXIST DUCT ELEVATION IS CONFLICTED WITH NEW PIPING
INSTALLATION. REMOVE THE EXIST DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL NECESSARY DUCT
CONNECTION TO FUNCTION AS ORIGINALLY INTENDED.
MECHANICAL GENERAL NOTES AND
SCOPE OF WORK
WORK CLASS "K" (REPAIR AND MAINTENANCE WORK)
REPAIR LANDING ZONE AREA
BLDG. S-302
K-16CHONG, ST
313332
SPRINKLER HEADS, AND ALL ASSOCIATED PIPES AS SHOWN ON DRAWINGS.
3. REPAIR THE FIRE PROTECTION SYSTEM BY INSTALLING NEW QUICK RESPONSE UP-RIGHT TYPE
AND ASSOCIATED ACCESSORIES AS SHOWN ON DRAWINGS.
2. REPAIR THE PLUMBING SYSTEM BY INSTALLING NEW PLUMBING FIXTURES, P-TRAPS WITH FLOOR DRAIN
AND ASSOCIATED DUCTS FOR HVAC SYSTEM AS SHOWN ON DRAWINGS
1. REPAIR THE HEATING AND COOLING SYSTEM BY INSTALLING NEW SQUARE SUPPLY DIFFUSERS, B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-3
K E Y P L A N
NOT TO SCALE
ELEV1
STAIR1
ATM
DN
UP
ELEV2
(33EA)
OFFICE
VEST
LOCKER
LOBBY
MEN
WOMEN
EWC
ANTE
COOLER FREEZER
KITCHEN
COUNTER
SERVING
STO
KITCHEN
STO
CLUB
DINING
TELS
STO
CAC
STAIR2
UP
DN
BAR
BAR STO
(132)
CLUB LOUNGE
JAN.
OFFICE
PIZZA HUT
SUBWAY
A&W
REFR
SINK
MW
FEC
FEC
FEC
FEC
WOMEN
MEN
MW
CORRIDOR
JC
VESTIBULE
MECH ROOM
C O
R R
ID
O R
CORRIDOR
C O
R R
ID
O R
CORRIDOR
REFR
REFR
BANK
102A
108C
BREAK
ROOM
TRAVEL
OFFICE
ELEV
HALL
109A
109B
117A
CLUB
ENTRY
126120
SERVICE
ENTRY
CLUB
ENTERTAINMENT
SLOT
MACHINE
ROOM
(SMOKING)
SLOT
MACHINE
118C
118B
BEER
COOLER
118A
DRINK
CENTER
WAIT
AREA
COMM
ROOM
DJ
BOOTH
TRASH
ENCLOSURE
111A
B-9
B-6 B-5A B-4 B-1
B-1A
B-2
B-7A
B-7
B-8
B-10
B-10
C A
R R
IE
R
Q
N B
B-5
REMOVE EXISTING SLOTS SUPPLY LINEAR DIFFUSERS
AND ASSOCIATED FLEXIBLE DUCTS(TYP).
EXIST/REMOVAL HVAC FLOOR PLAN1
M3 SCALE : 1 / 50-
REPAIR LANDING ZONE AREA
BLDG. S-302
K-16CHONG, ST
313332
EXIST/REMOVAL HVAC PLAN
AND KEY PLAN
POCPOC
REMOVE EXISTING SLOTS SUPPLY LINEAR DIFFUSERS
POC
POC
REMOVE EXISTING SLOTS SUPPLY LINEAR DIFFUSERS
REMOVE EXISTING SLOTS SUPPLY LINEAR DIFFUSERS
POC
REMOVE EXISTING SLOTS SUPPLY LINEAR DIFFUSERS
POC
POC
REMOVE EXISTING SLOTS SUPPLY LINEAR DIFFUSERS
AND ASSOCIATED FLEXIBLE DUCTS(TYP OF 5).
AND ASSOCIATED FLEXIBLE DUCTS(TYP OF 6).
AND ASSOCIATED FLEXIBLE DUCTS(TYP OF 4).
AND ASSOCIATED FLEXIBLE DUCTS(TYP OF 2).
AND ASSOCIATED FLEXIBLE DUCTS(TYP OF 2).
R
D
D
R
D
VD
ELEV2
STO
CLUB
STAIR2
BAR
BAR STO
400x300 D
R
D
D
D
R
R
117A
CLUB
ENTERTAINMENT
118C
118B
BEER
COOLER
BOOTH
700x900 OAIL
(UPPER & LOWER)
Series 1510
CLUB LOUNGE
MECH ROOM
SLOT
MACHINE
118A
POC
POC
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-4
K E Y P L A N
NOT TO SCALE
ELEV1
STAIR1
ATM
DN
UP
ELEV2
(33EA)
OFFICE
VEST
LOCKER
LOBBY
MEN
WOMEN
EWC
ANTE
COOLER FREEZER
KITCHEN
COUNTER
SERVING
STO
KITCHEN
STO
CLUB
DINING
TELS
STO
CAC
STAIR2
UP
DN
BAR
BAR STO
(132)
CLUB LOUNGE
JAN.
OFFICE
PIZZA HUT
SUBWAY
A&W
REFR
SINK
MW
FEC
FEC
FEC
FEC
WOMEN
MEN
MW
CORRIDOR
JC
VESTIBULE
MECH ROOM
C O
R R
ID
O R
CORRIDOR
C O
R R
ID
O R
CORRIDOR
REFR
REFR
BANK
102A
108C
BREAK
ROOM
TRAVEL
OFFICE
ELEV
HALL
109A
109B
117A
CLUB
ENTRY
126120
SERVICE
ENTRY
CLUB
ENTERTAINMENT
SLOT
MACHINE
ROOM
(SMOKING)
SLOT
MACHINE
118C
118B
BEER
COOLER
118A
DRINK
CENTER
WAIT
AREA
COMM
ROOM
DJ
BOOTH
TRASH
ENCLOSURE
111A
B-9
B-7
B-8
B-10
B-10
C A
R R
IE
R
Q
N B
B-5
M5 SCALE : 1 / 50-
CLUB LOUNGE
COOLER
BEER
118C
BAR STO
STAIR2
118A
MACHINE
SLOT 124
MEN
WOMEN
C O
R R
ID
O R
OFFICE
CORRIDOR
ENTERTAINMENT
CLUB
SP
D (5 0)
117A
BOOTH
DJ
DINING
ELEV2
REMOVE EXISTING QUICK RESPONSE RECESSED PENDENT TYPE
SPRINKLER HEADS AND ASSOCIATED FLEXIBLE DUCTS(TYP OF 36).
REMOVE EXISTING QUICK RESPONSE RECESSED PENDENT TYPE
SPRINKLER HEADS AND ASSOCIATED FLEXIBLE DUCTS(TYP OF 36).
EXIST/REMOVAL SPRINKLER HEAD FLOOR PLAN
REPAIR LANDING ZONE AREA
BLDG. S-302
K-16CHONG, ST
313332
EXIST/REMOVAL SPRINKLER HEAD
FLOOR PLAN AND KEY PLAN
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-5
K E Y P L A N
NOT TO SCALE
ELEV1
STAIR1
ATM
DN
UP
ELEV2
(33EA)
OFFICE
VEST
LOCKER
LOBBY
MEN
WOMEN
EWC
ANTE
COOLER FREEZER
KITCHEN
COUNTER
SERVING
STO
KITCHEN
STO
CLUB
DINING
TELS
STO
CAC
STAIR2
UP
DN
BAR
BAR STO
(132)
CLUB LOUNGE
JAN.
OFFICE
PIZZA HUT
SUBWAY
A&W
REFR
SINK
MW
FEC
FEC
FEC
FEC
WOMEN
MEN
MW
CORRIDOR
JC
VESTIBULE
MECH ROOM
C O
R R
ID
O R
CORRIDOR
C O
R R
ID
O R
CORRIDOR
REFR
REFR
BANK
102A
108C
BREAK
ROOM
TRAVEL
OFFICE
ELEV
HALL
109A
109B
117A
CLUB
ENTRY
126120
SERVICE
ENTRY
CLUB
ENTERTAINMENT
SLOT
MACHINE
ROOM
(SMOKING)
SLOT
MACHINE
118C
118B
BEER
COOLER
118A
DRINK
CENTER
WAIT
AREA
COMM
ROOM
DJ
BOOTH
TRASH
ENCLOSURE
111A
B-9
B-7
B-8
B-10
B-10
C A
R R
IE
R
Q
N B
B-5
M5 SCALE : 1 / 50-
x
D x3
D
R
200x150 x3 x2 x3 x5
SMD
200x200
VD
VDVD
VD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD
VD
VDVD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
300x150
400x300 350x200
350x200
D
60 LPS 60 LPS
350X250 200X200
350x250 200x200
200x200 350X250
R
200x
200x
350x
900x
350x
200x
150 200x
300x
REPLACE EXISTING SLOT SUPPLY LINEAR DIFFUSERS WITH
ELEV2
OFFICE
BAR
COOLER
BEER BAR STO
CLUB LOUNGE
WOMEN
MEN
CORRIDOR
C O
R R
ID
O R
BOOTH
DJ
AREA
DANCE FLOOR
FEC
REF
REPLACE EXISTING SLOT SUPPLY LINEAR DIFFUSERS WITH
SQUARE SUPPLY DIFFUSERS, 75LPS AND ASSOCIATED
DUCTS(TYP OF 11).
SQUARE SUPPLY DIFFUSERS, 85LPS AND ASSOCIATED DUCTS(TYP OF 8).
REPAIR LANDING ZONE AREA
BLDG. S-302
K-16CHONG, ST
313332
1st FLOOR HVAC PLAN
1st FLOOR HVAC PLAN AND KEY PLAN
VD
VD
200x200
VD
VD
NOTES :
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND
DIRECTION OF DIFFUSERS AND DUCTS IN FIELD (TYP.).
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DIFFUSERS AND DUCTS
PRIOR TO DIFFUSERS AND DUCTS INSTALLATION.
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
WASTE
PIPE CONNECTION
H.W. VENT
BACK
R E M A R K S
C.W.
NOTES :
QTY.SYMBOL
F I X T U R E
LAVATORY 15
2P-3 URINAL 25 -
RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENTS
1. QUANTITIES ARE SHOWN FOR ESTIMATION PURPOSE ONLY, THE CONTRACTOR SHALL BE
REQUIREMENTS.
2. ALL PLUMBING DEVICES FOR POTABLE SERVICE HAS TO CONFIRM TO NSF 61, CHAPTER 8&9
M-6
- SCALE : 1 / 25
P-5
-2 25
HANDICAPPED
WATER CLOSET
W/.16 LPS FLUSH
K E Y P L A N
NOT TO SCALE
ELEV1
STAIR1
ATM
DN
UP
ELEV2
(33EA)
OFFICE
VEST
LOCKER
LOBBY
MEN
WOMEN
EWC
ANTE
COOLER FREEZER
KITCHEN
COUNTER
SERVING
STO
KITCHEN
STO
CLUB
DINING
TELS
STO
CAC
STAIR2
UP
DN
BAR
BAR STO
(132)
CLUB LOUNGE
JAN.
OFFICE
PIZZA HUT
SUBWAY
A&W
REFR
SINK
MW
FEC
FEC
FEC
FEC
WOMEN
MEN
MW
CORRIDOR
JC
VESTIBULE
MECH ROOM
C O
R R
ID
O R
CORRIDOR
C O
R R
ID
O R
CORRIDOR
REFR
REFR
BANK
102A
108C
BREAK
ROOM
TRAVEL
OFFICE
ELEV
HALL
109A
109B
117A
CLUB
ENTRY
126120
SERVICE
ENTRY
CLUB
ENTERTAINMENT
SLOT
MACHINE
ROOM
(SMOKING)
SLOT
MACHINE
118C
118B
BEER
COOLER
118A
DRINK
CENTER
WAIT
AREA
COMM
ROOM
DJ
BOOTH
TRASH
ENCLOSURE
111A
B-9
B-7
B-8
B-10
B-10
C A
R R
IE
R
Q
N B
B-5
OFFICE
WOMEN
MEN
CORRIDOR
C O
R R
ID
O R
SLOT
MACHINE
118A
P-2
P-3P-3
P-5
P-5 P-5
REPLACE EXISTING DETERIORATED PLUMBING FIXTURES
AND ASSOCIATED ACCESSORIES WITN NEW.
AND ASSOCIATED ACCESSORIES WITN NEW.
REPLACE EXISTING DETERIORATED PLUMBING FIXTURES
P-2
FCO
FD
FD
CLEAN EXISTING SEWER PIPING
CLEAN EXISTING SEWER PIPING
TOILET PLUMBING FIXTURE PARTIAL PLAN
6LITERS/FLUSH, FLUSH VALVE TYPE
W/3.8 LPS FLUSH, FLUSH VALVE TYPE
AMERICAN STANDARD
AMERICAN STANDARD
AMERICAN STANDARD
WATER CLOSET URINAL LAVATORY
REPAIR LANDING ZONE AREA
BLDG. S-302
K-16CHONG, ST
313332
M6
TOILET PLUMBING FIXTURE PARTIAL PLAN,
PLUMBING FIXTURE SCHEDULE - 1
PLUMBING FIXTURE SCHEDULE-1
AND KEY PLAN
P-2
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
- SCALE : 1 / 25
K E Y P L A N
NOT TO SCALE
BAR
COOLER
BEER BAR STO
ELEV2
OFFICE
BAR
COOLER
BEER BAR STO
CLUB LOUNGE
FEC
WOMEN
MEN
CORRIDOR
C O
R R
ID
O R
BOOTH
DJ
AREA
DANCE FLOOR
FEC
REF
REF
REF
15 BELOW SLAB
PLUMBING FIXTURES QTY
COLD HOT TRAP VENT
REMARKSSYMBOL
PIPE CONNECTIONS
1DISHWASHER
1 15 15
15 -
15 INDIRECT DRAIN
INDIRECT DRAIN
SINK
COCTAIL TABLE
ICE MACHINE
BAR TABLE PLUMBING FIXTURE PIPING PARTIAL PLAN
B-1 B-2 B-3 B-4
INDIRECT DRAIN
15 15
INDIRECT DRAIN
BAR TABLE TOPCOLD PLATE
S
20 15
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING
PRIOR TO PLUMBING PIPING INSTALLATION.
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND
DIRECTION OF HOT/COLD WATER AND SEWER PIPING IN FIELD (TYP.).
REPAIR LANDING ZONE AREA
BLDG. S-302
K-16CHONG, ST
313332
M-7
PLUMBING FIXTURES SCHEDULE-2
M7
BAR TABLE PLUMBING FIXTURE PARTIAL
PLAN, PLUMBING FIXTURE SCHEDULE-2,
KEY PLAN AND NOTES
POC
B-1
B-2
B-3
B-4
200x200 FLOOR DRAIN(TYP OF 3)
NEW P-TRAP(TYP OF 3)
200x200 EXISTING FLOOR DRAIN
200x200 EXISTING FLOOR DRAIN
P-TRAP
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND
NOTES-1 :
NOTES-2 :
DIRECTION OF P-TRAPS WITH FLOOR DRAIN IN FIELD (TYP.).
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR P-TRAP WITH FLOOR DRAIN
PRIOR TO P-TRAP WITH FLOOR DRAIN INSTALLATION.
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-8
1st FLOOR FIRE PROTECTION PIPING PLAN, SPRINKLER Q'TY LIST, NOTE AND KEY PLAN
K E Y P L A N
NOT TO SCALE
ELEV1
STAIR1
ATM
DN
UP
ELEV2
(33EA)
OFFICE
VEST
LOCKER
LOBBY
MEN
WOMEN
EWC
ANTE
COOLER FREEZER
KITCHEN
COUNTER
SERVING
STO
KITCHEN
STO
CLUB
DINING
TELS
STO
CAC
STAIR2
UP
DN
BAR
BAR STO
(132)
CLUB LOUNGE
JAN.
OFFICE
PIZZA HUT
SUBWAY
A&W
REFR
SINK
MW
FEC
FEC
FEC
FEC
WOMEN
MEN
MW
CORRIDOR
JC
VESTIBULE
MECH ROOM
C O
R R
ID
O R
CORRIDOR
C O
R R
ID
O R
CORRIDOR
REFR
REFR
BANK
102A
108C
BREAK
ROOM
TRAVEL
OFFICE
ELEV
HALL
109A
109B
117A
CLUB
ENTRY
126120
SERVICE
ENTRY
CLUB
ENTERTAINMENT
SLOT
MACHINE
ROOM
(SMOKING)
SLOT
MACHINE
118C
118B
BEER
COOLER
118A
DRINK
CENTER
WAIT
AREA
COMM
ROOM
DJ
BOOTH
TRASH
ENCLOSURE
111A
B-9
B-7
B-8
B-10
B-10
C A
R R
IE
R
Q
N B
B-5
M5 SCALE : 1 / 50-
SP
D (5 0)
DINING
SPRINKLER Q'TY LIST
SPRINKLER HEAD TYPE
US/(METRIC)
"K" FACTOR
SIZE
A R E ASYMBOL
THREAD
SPRINKLER Q'TY LIST
TOTAL
37QUICK RESPONSE PENDENT TYPE SPRINKLER HEAD
TOTAL NUMBER OF SPRINKLER OF SYSTEM 37
REPLACE EXISTING 20mm QUICK RESPONSE UP-RIGHT TYPE
8.0/(115)3/4" NPT
ELEV2
OFFICE
BAR
COOLER
BEER BAR STO
CLUB LOUNGE
WOMEN
MEN
CORRIDOR
C O
R R
ID
O R
BOOTH
DJ
AREA
DANCE FLOOR
FEC
REF
DJ BOOTH, DANCE FLOOR AREA, BAR
1st FLOOR FIRE PROTECTION PIPING PLAN
SPRINKLER HEADS AND ASSOCIATED PIPING WITH NEW(TYP OF 37).
REPAIR LANDING ZONE AREA
BLDG. S-302
K-16CHONG, ST
313332
NOTES :
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND
DIRECTION OF SPRINKLER HEADS AND PIPING IN FIELD (TYP.).
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR SPRINKLER HEADS AND PIPING
PRIOR TO SPRINKLER HEADS AND PIPING INSTALLATION.
| 313332_REPAIR-LANDING-ZONE-S-302_K-16_M1 |
| 313332_REPAIR-LANDING-ZONE-S-302_K-16_M2 |
| 313332_REPAIR-LANDING-ZONE-S-302_K-16_M3 |
| 313332_REPAIR-LANDING-ZONE-S-302_K-16_M4 |
| 313332_REPAIR-LANDING-ZONE-S-302_K-16_M5 |
| 313332_REPAIR-LANDING-ZONE-S-302_K-16_M6 |
| 313332_REPAIR-LANDING-ZONE-S-302_K-16_M7 |
| 313332_REPAIR-LANDING-ZONE-S-302_K-16_M8 |
File details come from the government source that posted it. Updated .