313332_DWG_ELEC.pdf

PDF 4 MB Posted

Attached to
Repair Building Landing Zone K16 (MATOC ONLY)
Solicitation number
W90VN824R0047
Issued by

About this file

This document is an electrical drawing for the repair and renovation of Building S-302, the Landing Zone, on the K-16 military installation. The work includes interior and exterior electrical, lighting, power, and fire alarm and communication system upgrades. Key details include:

The electrical work involves replacing existing light fixtures, switches, receptacles, and wiring. New LED lighting, including pendant, recessed, and track lighting, will be installed. The power system will be upgraded, with new electrical panels, circuit breakers, and receptacles added to support kitchen equipment and other facility requirements. The fire alarm and communication systems will also be updated, with new addressable modules, detectors, speakers, and other components installed. The contractor will be required to coordinate closely with the government on equipment and system compatibility. This work is part of a larger facility renovation project being solicited under the MATOC contract vehicle to area I and II contractors only.

View the file

Other files

File Type Posted
W90VN824R0047.pdf PDF
313332_DWG_TITLE-SHEET.pdf PDF
313332_DWG_ARCH.pdf PDF
313332_MECH.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES

1.

2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE

NOTED ON THE DRAWING.

LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE

PANELBOARD SEE SPECIFICATION

SAFETY SWITCH 1524mm TO CENTER OF THE ENCL

350mm TO CENTER OF THE ENCL

MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL

3.

4.

6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION

SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE

7.

5.

CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.

INDICATEDS 2 #12AWG IN 16C

INDICATEDS 3 #12AWG IN 16C

INDICATEDS 4 #12AWG IN 16C

A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;

1219mm TO CENTER OF THE ENCLWALL SWTICH

CONDUIT UNLESS OTHERWISE INDICATED.

ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C

AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT

THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING

TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.

DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT

F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-1

12.

13.

14.

10.

11.

8.

9.

15.

SINGLE POLE TOGGLE SWITCH, 15A-277V

L E G E N D

FLEXIBLE CONDUIT W/CONNECTORS

LIGHTING

WIRING

POWER

INTERIOR

SYMBOL DESCRIPTION

DESCRIPTION

DESCRIPTION

J JUNCTION BOX

SYMBOL

SYMBOL

F FAN MOTOR (UNDER MECH. ITEM)

SAFETY SWITCH

C CONTROL CIRCUIT

AND GOVERNMENT INSTALLED

GOVERNMENT FURNISHED

GFGI

WEATHERPROOFWP

LA LIGHTNING ARRESTER

EXPLOSIONPROOFEP

DISTRIBUTIONDIST

GROUND FAULT PROTECTIONGFP

A AMPERE

AC ALTERNATING CURRENT

AF/AT AMPERE FRAME/AMPERE TRIP

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CONN CONNECTION

CT CURRENT TRANSFORMER

DET(S) DETAIL(S)

DIAG DIAGRAM

DISC DISCONNECT

DWG(S) DRAWING(S)

EA EACH

EM EMERGENCY

ENCL ENCLOSURE

EXST EXISTING

F/A FIRE ALARM

FL FLOOR

FLUOR FLUORESCENT

FXTR FIXTURE

GEN GENERATOR

GND GROUND

HP HORSE POWER

HZ HERTZ

INCAND INCANDESCENT

INSTL INSTALLATION

J-BOX JUNCTION BOX

K KILO

KV KILO VOLT

KVA KILO VOLT AMPERE

LTG LIGHTING

MAG MAGNETIC

MAX MAXIMUM

MIN MINIMUM OR MINUTE

MTG MOUNTING

NO NUMBER

O/H OVER HEAD

PH PHASE

PNLBD PANELBOARD

PRIM PRIMARY

PWR POWER

Q'TY QUANTITY

RCPT RECEPTACLE

REQ'D REQUIRED

SCHED SCHEDULE

SEC SECONDARY

SPEC SPECIFICATION

STD STANDARD

SW SWITCH

TEL TELEPHONE

TYP TYPICAL

U/G UNDERGROUND

V VOLT

VA VOLT AMPERE

W WATT

W/ WITH

XFMR TRANSFORMER

& AND

CABNET TYPE, RATED WATT ON LTG SCHEDULE

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER

FAULT PROTECTED TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED

PANELBOARD

HOMERUN CIRCUIT TO PANELBOARD

TYPE OF MTG ON LTG SCHEDULE

EXTERIOR LED LIGHTING FIXTURE, RATED WATT &

TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ABBREVIATION

THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM

IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE

MECHANICAL DRAWINGS.

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG

WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.

THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR

ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.

CATV BEFORE CONSTRUCTION.

CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,

AND GOVERNMENT ACCEPTANCE.

PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION

CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO

FIRE CODE AND SPECIFICATIONS.

OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,

ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS

OR RENOVATION.

CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION

THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING

FIXTURE A MINIMUM DISTANCE OF 458mm.

FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING

FMCP

FTR

AUXILIARY

DESCRIPTIONSYMBOL

STROBES

WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL

BUILDING TRANSMITTER UNIT FOR FIRE ALARM

SYSTEM

WP

FAULT PROTECTED TYPE, WEATHER PROOF

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED

TYPE

SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING

L

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

W/EMERGENCY BATTERY UNIT

L

W/EMERGENCY UNIT TYPE

QUADPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

L

L

UNITS.

CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER

CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY

16.

THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE

WIDTH OF DUCT EXCAVATION.

AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.

TO THEIR ORIGINAL CONDITION AND OPERATION DURING

ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES

THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING

THE MANUFACTURER AND MODEL OF NEW BUILDING TRANSMITTER EQUIPMENT

IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE TESTED WITH THE RECEIVING SYSTEM(D21)

SHALL BE COORDINATED WITH THE CENTRAL FIRE DEPARTMENT.

RECEPTACLE

AND WALL

WIRING CONCEALED OR EXPOSED IN/ON THE CEILING

CEILING OR CONCEALED IN NEW WALL.

ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS

SCOPE OF WORK

1.

A. REPAIR/MAINTENANCE ( K )

2.

FIRE ALARM & MNSCONTROL PANEL

F

F/M

FIRE ALARM & MNS CIRCUIT

T LAN/TEL LINE

ELECTRICAL

L

6.

ON LTG SCHEDULE, FOR INDIRECT LIGHT

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

SCOPE OF WORKS

LEGEND, GENERAL NOTES AND

5.

INDICATEDS 5 #12AWG IN 21C

17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING

EXISTING CCTV SYSTEM INCLUDING CCTV CAMERAS AND

COORDINATING WITH USER THRU COR.

REMOVE AND REINSTALL THEM TO BE OPERATIONAL BY

WIRING AS REQUIRED

ASSOCIATED WIRING & CONDUITS WITH NEW S SHOWN ON THE DRAWINGS.

REPLACE EXISTING CIRCUIT BREAKERS, RECEPTACLES W/COVER PLATES

WITH NEW AS SHOWN ON DRAWING.

TOGGLE SWITCHES, DIMMING SWITCHES, WIRES AND CONDUITS

REPLACE EXISTING INTERIOR LIGHTING FIXTURES, EXIT LIGHTS,

7.

8.

AS SHOWN ON DRAIWNG FOR INTERIOR WALL LINING INSTALLATION WORK.

REMOVE AND REINSTALL EXISTING FIRE ALARM SYSTEM COMPONENTS

INSTALLATION WORK AS SHOWN ON THE DRAWINGS.

REPLACE EXISTING TELEPONE OUTLETS FOR INTERIOR WALL LINING

SUPPORTS AS SHOWN ON THE DRAWING.

REMOVE AND REINSTALL EXISTING SPEAKERS WITH NEW STEEL STURCTURE

9.

IN THE PROJECTED AREA. TURN-IN REMOVED CCTV CAMERAS TO USER.

REMOVE EXISTING CCTV CAMERAS BUT THE CCTV CABLE TO BE REMAINED

ON DRAWING.

REPLACE EXISTING POWER SUPPLY FOR KITCHEN EQUIPMET AS SHOWN3.

4.

S

D

DIMMING CONTROL SWITCH, 1200W, 277V FOR LED LIGHT,

ON LTG SCHEDULE,

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

EMERGENCY LIGHT, 120V/277V, 16WATTS

EXIT SIGN, 120V/277V, 4.99WATT (MAX.)

TAK, YS K-16

BLDG. S-302

REPAIR LANDING ZONE AREA

313332

AS SHOWN ON DRAWING.

REPLACE CONDUIT AND UNIVERSAL MOUNTING UNITS FOR TELEVISIONS

TYPE (KOREAN RECEPTACLE)

DUPLEX RECEPTACLE, 2P-3W-20A-220V, GROUNDING

ASSOCIATED WIRING AND CONDUIT WITH NEW AS SHOWN ON THE DRAWINGS.

REPLACE EXISTING CATV DISTRIBUTION PULLBOX, CATV OUTLETS &

ELEV2

OFFICE

BAR

COOLER

BEER BAR STO

CLUB LOUNGE

FEC

WOMEN

MEN

CORRIDOR

C O

R R I

D O

R

BOOTH

DJ

AREA

DANCE FLOOR

FEC

55"TV

55"TV

REF

LIGHTING BOX

CEILING

TABLE

WOODEN

E-2

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15333, APO AP 96205-5333

DPW, ENGINEERING SERVICES DIVISON, DESIGN BRANCH

HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN-CASEY

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

dcc c d d ddcc c c d d ddcc a D b

D a a aa b bb

C-16 a baa b b b b b g g f f ff e

S P4-20

Sf

SCALE: 1/100

c c c d d eeeee

C-8

SWITCH "c"

TO DIMMER

SWITCH "d"

TO DIMMER

c d

C-10 c D d D d g b g

MECH ROOM

e c d

L

L

L

L

L a e

SWITCH "a"

TO DIMMER

a f

NEW TRACK LIHGT TYPE "NS-7" (TYP. OF 4)

NEW TRACK LIHGT TYPE "NS-7" (TYP. OF 4)

NEW PENDANT MOUNTED LIHGT TYPE "NS-6" (TYP. OF 47)

NEW EXIT SIGN "NS-3" (TYP. OF 4)

LIGHT TYPE "NS-8"(TYP. OF 7)

NEW CEILING RECESS MOUNTED DOWN

LIGHT TYPE "NS-8"(TYP. OF 7)

NEW CEILING RECESS MOUNTED DOWN

LIGHT(TYP. OF 4)

NEW WALL MOUNTED EMERGENCY

(TYPICAL)

DIMMING SWITCH, 1P-277V, 15A

EXIST PNL "C"

EXIST PNL "D"

EXIST PNL "DPB"

EXIST PNL "P4"

EXIST PNL "P5"

EXIST PNL "P6"

NEW LIGHTING PLAN

D e

UNDER COUNTER TOP TYPE "NS-12"

NEW TAPE LIGHT, INDIRECT,

BAR BY COORDINATING WITH USER THRU COR.

TABLE/ LOCATION OF SWITCH SHALL BE LOCATED NEAR

INCLUNDIND WIRING AND SWITCH FOR BILLIARD

REMOVE/ RESTORE EXIST LIGHTING FIXTURE

EXIST PANEL "P5A"

EXIST RELAY PACK

EXIST DIMMER PAC

C-13 g

D g

SWITCH "g"

TO DIMMER

L L

L

L

LL

PANEL LIGHT, TYPE "NS-4b" (TYP. OF 2)

NEW CEILING RECESS MOUNTED

PANEL LIGHT, TYPE "NS-4a" (TYP. OF 2)

NEW CEILING RECESS MOUNTED

PANEL LIGHT, TYPE "NS-5b"

NEW CEILING RECESS MOUNTED

PANEL LIGHT, TYPE "NS-5a"

NEW CEILING RECESS MOUNTED

FOR THE LIGHTING FIXTURES TO BE OPERATIONAL.

AND RESTORE THE POWER/CONTROL LINE (W/RECEPTACLES) AND CONTROL SYSTEM

EXIST DJ LIGHTING FIXTURES SHALL BE SECURED DURING CONSTRUCTION PERIOD

EXIST DJ LIGHTING FIXTURES

S

TAK, YS K-16

BLDG. S-302

REPAIR LANDING ZONE AREA

313332

ELECTRICAL

NEW LIGHTING PLAN

a a a a a a a a a a a c c c c c c

D-12

SWITCH "c"

TO DIMMER

ELEV1

ATM

102A

DN

UP

ELEV2

(33EA)

VEST

108C

LOCKER

(42EA)

ROOM

BREAK

OFFICE

TRAVEL

LOBBY

HALL

ELEV

MEN

WOMEN

EWC

ANTE

COOLER FREEZER

KITCHEN

COUNTER

SERVING

109A

STO

KITCHEN

STO

CLUB

117A

ENTRY

CLUB

126120

ENTRY

SERVICE

SHO

108B

108A

TELS

STO

CAC

(SMOKING)

ROOM

MACHINE

SLOT

STAIR2

UP

DN

118CCOOLER

BEER

BAR STO

W2

JAN.

OFFICE

PIZZA HUT

SUBWAY

A&W

REFR

SINK

FEC

FEC

FEC

FEC

HANDLING UNIT

PACKAGED AIR

TOILET

UNI-SEX

WOMEN

MEN

MW

CORRIDOR

JC

ROOM

COMM

VESTIBULE

MECH ROOM

C O

R R I

D O

R

C O

R R I

D O

R

CORRIDOR

BOOTH

DJ

ENCLOSURE

TRASH

111A

L3

REFR

REFR

BANK

S

J

S b

Sb

S

S

BAR

COOLER

BEER BAR STO

KEY PLAN

S g g

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-3 m m

308mm

NS-4a & 4bNS-3a & 3b

FIXTURE, 1PH, 120V, 45W, WITH CONVERTER &

ACCESSORIES AS REQUIRED, (NS-5a) & WITH EM UNIT (NS-5b)

OR APPROVED EQUAL.

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING

WITH BATTERY CHARGER, SINGLE FACE (NS-3a) OR

(MAX INPUT) OR 7.22W(MAX INPUT), BATTERY BACK-UP

DIODE(LED) EXIT LIGHT FIXTURE, 1PH, 120V, 4.99W

DOUBLE FACE (NS-3b) OR APPROVED EQUAL.

ELECTRICAL

LIGHTING FIXTURE DETAILS

TAPE LIGHT FOR INDIRECT LIGHTING, 24VDC, 4.3W/FT,

LIGHT EMITTING DIODE(LED), 3000K, WITH CONVERTER & ACCESSORIES

AS REQUIRED, UL LISTED POWER UNIT

WALL OR CEILING SURFACE MOUNTED TRACK LIGHT,

AS REQUIRED

CEILING RECESSED LIGHT EMITTING DIODE (LED)

143.9mm

.3 m m

210mm

ACCESSORIES, AS REQUIRED AND UL LISTED

NS-9

NS-7

m m

1220m m

0m m

NS-5a & 5b

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

REQUIRED (OPTION: DIMMING CONTROL DRIVER)

FIXTURE, 1PH, 120V, 50W, UL LISTED, PMMA LIGHT GUIDE WITH CONVERTER &

ACCESSORIES, (NS-5a) & WITH SELF TEST/DIAGNOSTIC EM UNIT (NS-5b) AS

FIXTURE, 1PH, 120V, 12W, C.T: 3000K, WITH CONVERTER &

C.T: 3000K, WITH CONVERTER & ACCESSORIES INCLUDING TRACK

12W, 4" dia., MOUNTING ACCESSORIES W/ DIMMING CONTROL

CEILING RECESSED LED DOWN LIGHT FIXTURE, 3000K, 1PH, 120V-277V,

7.5W, 3" dia., 600 LUMENS WITH MOUNTING ACCESSORIES W/ DIMMING

CONTROL DRIVER, AS REQUIRED AND UL LISTED POWER UNIT

CEILING RECESSED LED DOWN LIGHT FIXTURE, 3000K, 1PH, 120V-277V,

DRIVER, AS REQUIRED AND UL LISTED POWER UNIT

CEILING PENDANT MOUNTED LIGHT EMITTING DIODE (LED) FIXTURE,

NS-8

NS-11 NS-12

.6 m m

114.30mm

184mm m m

NS-6

POWER UNIT,DIMMING CONTROL

NS-10

1PH, 120V-277V, 50W, 5000lumen WITH CONVERTER & MOUNTING ACCESSORIES, AND UL LISTED, DIMMING CONTROL (0V-10VDC)

ARCHITECTURAL BLACK FINISH , C.T: 3000K, ACCESSORIES, AS REQUIRED

LIGHT EMITTING DIODE(LED) LIGHT FIXTURE, 1PH, 120V-277V, 15W,

TAK, YS K-16

BLDG. S-302

REPAIR LANDING ZONE AREA

313332

DIE CASTING ALUMINUM HOUSING

AND SEALED NICKEL CADMIUM BATTERY, DUAL

VOLTAGE 120/277VAC, 60HZ, ISOLATION TRANSFORMER,

EMERGENCY LIGHTING UNIT WITH LED LAMPS, 16WATTS,

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-4

REMARKSQ'TY

WATTS

MOUNTING METHOD

TYPE

LAMP

NAME

ROOM OCE STD DET 40-06-04

LIGHT FIXTURE SCHEDULE

TYPE

LED 27

CEILING PENDANT

LIGHT FIXTURE SCHEDULE

ELECTRICAL

NS-10

NS-12

NS-11

NS-5b

NS-5a

NS-4b

NS-4a

W/ "EM" UNIT

W/ "EM" UNIT

145NS-4a

W/ "EM" UNIT145NS-4b

DANCE FLOOR AREA

CLUB LOUNGE

BAR

BAR STOR

NS-6

NS-11 CEILING RECESSED

NS-6 50 19 CEILING PENDANT

CEILING RECESSED

NS-7

NS-8

CEILING SURFACE

NS-6

4.3/FT

7.5

W. TOILET

M. TOILET

16 4

EXIT SIGN 1/4.99NS-3

MOUNTED

WALL/CEILING SURFACE

EMERGENCY LIGHT NS-9 WALL MOUNTED M.H: 2000 FROM FLOOR

33FT

W/ "EM" UNIT

TAK, YS K-16

BLDG. S-302

REPAIR LANDING ZONE AREA

313332

W/TRACK

CEILING RECESSED

CEILING PENDANT

UNDER COUNTERTOP INDIRECT LIGHT

INDIRECT LIGHTUNDER COUNTERTOP16FT4.3/FTNS-10

BAR

COOLER

BEER BAR STO

CLUB LOUNGE

FEC

WOMEN

MEN

CORRIDOR

C O

R R I

D O

R

BOOTH

DJ

AREA

DANCE FLOOR

FEC

REF

CEILING

GWB

E-5

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15333, APO AP 96205-5333

DPW, ENGINEERING SERVICES DIVISON, DESIGN BRANCH

HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN-CASEY

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

TZ

PNL"DPB"

PNL"P4"

PNL"P5"

PNL"P6"

PNL"D"

PNL"C"

P5-24

P5-31

P5-30

P4-3

C

SCALE: 1/100

J

2134mm

2134mm

2134mm

2134mm

2134mm

2134mm

2134mm

2134mm

2134mm

2134mm

NEW POWER PLAN

VERTICAL LIFT DOORS(2SETS)

FOR MOTOR OPERATED

REMOVE EXIST CONTROLLERS

2134mm

2134mm

2134mm

S S

S S

S

S

S

S

S S

S S

S S

S S

S

S S

S S

S S

S S

S

P5-32

P5-26

P4-1

P5-22

P5-27

P5-22,23

REMOVE AND REINSTALL EXIST THERMOSTAT

P5-28

P5-29

TELEVISIONS WILL BE FURNISHED BY USER.

TELEVISIONS (VARIOUS SIZE, TOTAL 8EA).

BY USER THRU COR. CONTRACTOR SHALL INSTALL

ACTUAL MOUNTING HEIGHT SHALL BE DETERMINED

TILTING ANGLE 0-20 (TYPICAL OF 8EA)/

BRACKET 40" TO 75", VERTICAL

NEW TV UNITVERSAL MOUNT

2134mm

2134mm

SEE ENLARGED POWER PLAN ON E-7

EXPOSED ON THE CEILING (TYPICAL OF 8SETS)

WIRE (35dia C.)/ RUN CONDUIT AS

NEW EMPTY CONDUIT W/PULLING

P4-2

P4-14 P4-15

1150mm

TAK, YS K-16

BLDG. S-302

REPAIR LANDING ZONE AREA

313332

ELECTRICAL

NEW POWER PLAN

BE DETERMINED BY USING AGENCY THRU COR

TO BE DONE BY OTHER/ LOCATION OF CABLE DUCT TO

(A/V SYSTEM)/ CABLE INSTALLATION

NEW TWO SETS OF CABLE DUCT (150mmX75mm) FOR DJ SYSTEM

(TYP. OF 8)

TO BE DONE BY OTHER)

SIGNAL CABLE (SIGNAL CABLE

NEW JUCTION BOX FOR

2134mm

2134mm2134mm

2134mm 2134mm

2134mm

2134mm

2134mm

2134mm

JJ

J

J

J

J

J a a a a a a a a a a a c c c c c c

D-12

SWITCH "c"

TO DIMMER

ELEV1

ATM

102A

DN

UP

ELEV2

(33EA)

VEST

108C

LOCKER

(42EA)

ROOM

BREAK

OFFICE

TRAVEL

LOBBY

HALL

ELEV

MEN

WOMEN

EWC

ANTE

COOLER FREEZER

KITCHEN

COUNTER

SERVING

109A

STO

KITCHEN

STO

CLUB

117A

ENTRY

CLUB

126120

ENTRY

SERVICE

SHO

108B

108A

TELS

STO

CAC

(SMOKING)

ROOM

MACHINE

SLOT

STAIR2

UP

DN

118CCOOLER

BEER

BAR STO

W2

JAN.

OFFICE

PIZZA HUT

SUBWAY

A&W

REFR

SINK

FEC

FEC

FEC

FEC

HANDLING UNIT

PACKAGED AIR

TOILET

UNI-SEX

WOMEN

MEN

MW

CORRIDOR

JC

ROOM

COMM

VESTIBULE

MECH ROOM

C O

R R I

D O

R

C O

R R I

D O

R

CORRIDOR

BOOTH

DJ

ENCLOSURE

TRASH

111A

L3

REFR

REFR

BANK

S

J

S b

Sb

S

S

BAR

COOLER

BEER BAR STO

KEY PLAN

BLOCK

TO TEL

STAIR1

DN

UP

ELEV2

HALL

ELEV

EWC

ANTE

117A

DINING

ENTRY

CLUB

126120

UP

DN

118CCOOLER

BEER

BAR STO

(132)

FEC

FEC

WOMEN

MEN

CORRIDOR

JC

ROOM

COMM

MECH ROOM

C O

R R I

D O

R

BOOTH

DJ

P

P

W_

_W

F

F

F

F

F

P

T

T/L

T

F

F

T

T

L T

L

F

F

F

T L

F

F

F

F

F

BAR

55"TV 55"TV 55"TVREF

REF

75"TV

75"TV

75"TV

BOOTH

DJ

BOOTH

DJ

F

F

E-6

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15333, APO AP 96205-5333

DPW, ENGINEERING SERVICES DIVISON, DESIGN BRANCH

HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN-CASEY

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

TV

TV TV TV TV

T

T

F M

F M

F M

F M

TV

TV

TV

(TYP.)

EXIST TROUGH CABLE TRAY

FIRST FLOOR FA/TEL/LAN/CATV SYSTEMS PLAN

(TYP)

REPLACE DUAL MODULAR JACKS, 1-TEL/1-LAN OUTLET, CAT6

MOUNTED FIRE ALARM STROBE/SPEAKER

REMOVE AND REINSTALL EXIST WALL

PULL BOX (300 x 300 x 200D)

W/ 8-WAY TAP-OFF AND LOCKING

DEVICE ABOVE CEILING

(5-1000MHZ) (TYPICAL)

DETECTOR TEST SWITCH (TYP. OF 2EA)

REMOVE AND REINSTALL EXIST DUCT SMOKE

ALARM PULL STATION (TYP. OF 2EA)

REMOVE AND REINSTALL EXIST FIRE

(610 mm x 610 mm x 254 mm D)

EXIST CATV CABINET "TV1"

T V

T V

T

VT

V

T V

T V

T V

T V

EQPT RACKS

EXIST COMMUNICATIONS

(2438 mm x 3000 mm x 19 mm D)

EXIST TELECOMS BACKBOARD

EXIST CABLE RACK

ALARM ADDRESSABLE MODULE(TYP. OF 4EA)

REMOVE AND REINSTALL EXIST FIRE

COAXIAL CABLE

RG 6/U IN 16C

(TYPICAL)

CONNECT TO EXIST CATV CABINET "TV1"

COAXIAL CABLE RG 11/U IN 21C/

EQUIPMENT RACK (1-DATA & 1-TEL) (TYPICAL)

TO BE TERMINATED AT PATCH PANELS IN

2-AWG#24, CAT6, LAN CABLE IN 27mm dia C.

T/L

TAK, YS K-16

BLDG. S-302

REPAIR LANDING ZONE AREA

313332

ELECTRICAL

PLAN

FIRST FLOOR FA/TEL/LAN/CATV SYSTEMS

1/100SCALE:

TYPE CONNECTOR

W/"0.0"dB LOSS FACE

PLATE & F-81 BARREL

CEILING) (TYPICAL)

(MH:+450mm BELOW

REMOVE EXIST TV OUTLETS IN THE

WALL MOUNTED TYPE TV OUTLETS

PROJECTED AREA AND INSTALL NEW

a a a a a a a a a a a c c c c c c

D-12

SWITCH "c"

TO DIMMER

ELEV1

ATM

102A

DN

UP

ELEV2

(33EA)

VEST

108C

LOCKER

(42EA)

ROOM

BREAK

OFFICE

TRAVEL

LOBBY

HALL

ELEV

MEN

WOMEN

EWC

ANTE

COOLER FREEZER

KITCHEN

COUNTER

SERVING

109A

STO

KITCHEN

STO

CLUB

117A

ENTRY

CLUB

126120

ENTRY

SERVICE

SHO

108B

108A

TELS

STO

CAC

(SMOKING)

ROOM

MACHINE

SLOT

STAIR2

UP

DN

118CCOOLER

BEER

BAR STO

W2

JAN.

OFFICE

PIZZA HUT

SUBWAY

A&W

REFR

SINK

FEC

FEC

FEC

FEC

HANDLING UNIT

PACKAGED AIR

TOILET

UNI-SEX

WOMEN

MEN

MW

CORRIDOR

JC

ROOM

COMM

VESTIBULE

MECH ROOM

C O

R R I

D O

R

C O

R R I

D O

R

CORRIDOR

BOOTH

DJ

ENCLOSURE

TRASH

111A

L3

REFR

REFR

BANK

S

J

S b

Sb

S

S

BAR

COOLER

BEER BAR STO

KEY PLAN

CLUB LOUNGE

AREA

DANCE FLOOR

BAR

COOLER

BEER BAR STO

REF

DESCRIPTION

QTYITEM

POWER REQUIREMENTS

PH VOLT HP AMPS

SYMBOL

TERMINATION

FEEDER

GURATION

CONFI-

NEMA

5-20R

5-20R

NO.

CKT

REMARKS

ICE MACHINE

1/4

1/3

3.0

8.2

LOAD

HEIGHTS

MOUNTING

P4-11

P4-12

2-#12 AWG, 1-#12 (G) IN 16mm C

2-#12 AWG, 1-#12 (G) IN 16mm C

2-#12 AWG, 1-#12 (G) IN 16mm C

2-#12 AWG, 1-#12 (G) IN 16mm C

2-#12 AWG, 1-#12 (G) IN 16mm C

BAR EQUIPMENT SCHEDULE

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15333, APO AP 96205-5333

DPW, ENGINEERING SERVICES DIVISON, DESIGN BRANCH

HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN-CASEY

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

DISHWASHER

P

P

P

P

SCALE = 1:50

B-2 B-3 B-4 B-5

B-6

B-2

B-3

B-4

B-5

COLD PLATE & ICE BOX

CABONATOR

STAINLESS TABLE &

1B-6 COOLER

1/3 7.2

P

1.3KVA

RECOMMENDATION

MANUFACTURER'S

ENLARGED POWER PLAN (BAR RM)

P

P

P4-5

1150mm

1250mm 1050mm

1050mm

P

P4-8

P4-9

P

TAK, YS K-16

BLDG. S-302

REPAIR LANDING ZONE AREA

313332

ELECTRICAL

E-7

ENLARGED POWER PLAN (BAR RM)

NA BC G

ONLY

LUGS

100A

MAIN

GND

S/N

E-8

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15333, APO AP 96205-5333

DPW, ENGINEERING SERVICES DIVISON, DESIGN BRANCH

HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN-CASEY

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

NA B C

1 2

3 4

11 12

G

13 14

GND

S/N

21 22

23 24

ONLY

LUGS

225A

MAIN

REF.

19 EXIST LEAK DETECT PANEL.EXIST UNIT HEATER-1 18

EXIST HB-1 EXIST AU-1

EXIST EF-4 EXIST DR-1

EXIST EF-5 EXIST UH-1

EXIST DH-1 EXIST AC-1

EXIST BEER COOLER SPARE

TAK, YS K-16

BLDG. S-302

REPAIR LANDING ZONE AREA

313332

ELECTRICAL

EXIST MOTORIZED DOOR EXIST CL-1

EXIST RECEPTACLES

EXIST RECEPTACLES

EXIST RECEPTACLES

EXIST RECEPTACLES

EXIST RECEPTACLES

EXIST RECEPTACLES

EXIST RECEPTACLES

EXIST RECEPTACLES

EXIST RECEPTACLES

EXIST EF-8

EXIST RECEPTACLES EXIST EF-1a

EXIST RECEPTACLES SPARE

EXIST AH-8 SPARE

SPAREEXIST AU-2

EXIST CATV NEW RECEPTACLES

NEW RECEPTACLES NEW RECEPTACLES

NEW RECEPTACLE

NEW RECEPTACLES

NEW RECEPTACLES

NEW RECEPTACLE NEW RECEPTACLES

NEW RECEPTACLES

NEW RECEPTACLESEXIST CONTROL

SPARE

SPARE

SPARE

NEW RECEPTACLES

NEW RECEPTACLES

NEW RECEPTACLES

NEW RECEPTACLES

NEW RECEPTACLES

NEW RECEPTACLES

NEW RECEPTACLE

NEW RECEPTACLES NEW RECEPTACLES

NEW RECEPTACLE

2P-100AF-20AT (TYP. OF 5EA)

REPALCE WITH NEW CIRCUIT BREAKER,

2P-100AF-20AT

REPALCE WITH NEW CIRCUIT BREAKER,

NEW CABONATOR

NEW COOLER

NEW DISH WASHER

NEW ICE MACHINE

(G) IN 16mm C (TYP.)

NEW 2-#12 AWG, 1-#12

(G) IN 16mm C (TYP.)

NEW 2-#12 AWG, 1-#12 (G) IN 16mm C (TYP.)

NEW 2-#12 AWG, 1-#12

NOTE.

1.

LOAD SCHEDULE

EXIST PANELBOARD "P4" & "P5"

LOAD SCHEDULE

EXIST PANELBOARD "P4"

LOAD SCHEDULE

EXIST PANELBOARD "P5"

(G) IN 16mm C (TYP.)

NEW 2-#12 AWG, 1-#12

NOT TO SCALE NOT TO SCALE

OTHER EQUIPMENT THAT REQUIRE ELECTRIC POWER SOURCE FOR THIS PROJRCTS AT HIS OWN COSTS.

AND WIRING/CONDUIT TO PROVIDE APPROPRIATE POWER TO NEW RECEPTACLES AND

CONTRACTOR SHALL VERIFY EXSITING PANELBOARDS AND PROVIDE/ADJUST CIRCUIT BREAKERS

LOAD SCHEDULES SHOWN ON THIS DRAWINGS ARE ESTIMATED FOR BIDING PURPOSE ONLY.

BAR

COOLER

BEER BAR STO

CLUB LOUNGE

FEC

WOMEN

MEN

CORRIDOR

C O

R R I

D O

R

BOOTH

DJ

AREA

DANCE FLOOR

FEC

REF

REF

E-9

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15333, APO AP 96205-5333

DPW, ENGINEERING SERVICES DIVISON, DESIGN BRANCH

HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN-CASEY

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

S WW S

SS

C

CC

C CC

S S

S S

S S S

S S

S S

S

THUR COR. (TYPICAL OF 2)

WOOFER SPEAKERS SHALL BE DETERMINED BY USER

MOUNTING MATERIALS/ LOCATION OF CEILING MOUNTED

REINSTALL THE SPEAKERS ON THE CEILING WITH NECESSARY

SUPPORT/ CONTRACTOR SHALL BE RESPONSIBLE TO

MOUNTED WOOFER SPEAKERS WITH NEW STEEL STRUCTURE

REMOVE AND RELOCATE EXISTING CEILING

THUR COR. (TYPICAL OF 4)

SPEAKERS SHALL BE DETERMINED BY USER

MOUNTING MATERIALS/ LOCATION OF CEILING MOUNTED

REINSTALL THE SPEAKERS ON THE CEILING WITH NECESSARY

SUPPORT/ CONTRACTOR SHALL BE RESPONSIBLE TO

MOUNTED SPEAKERS WITH NEW STEEL STRUCTURE

REMOVE AND RELOCATE EXISTING CEILING

USER THUR COR (TYPICAL OF 8)

LOCATION OF THE SPEAKERS SHALL BE DETERMINED BY

REMOVE AND REINSTALL EXISTING WALL MOUNTED SPEAKERS/

TO BE INSTALLED BY OTHER. (TYPICAL FOR ALL SPEAKERS)

AUDIO CABLES CONNECTION TO NEW AUDIO SYSTEM

TAK, YS K-16

BLDG. S-302

REPAIR LANDING ZONE AREA

313332

ELECTRICAL

NOTE.

1.

ON THE CEILING AT HIS OWN COSTS.

NEW STEEL STRUCTURE SHALL BE INSTALLED FOR CEILING MOUNTED SPEAKERS TO BE SECURELY MOUNTED PROVIDE SHOP DRAWING FOR CEILING STEEL STRUCTURE NOUNTED SPEAKERS FOR GOVERNMENT APPROVAL.

CONTRACTOR SHALL VERIFY EXSITING SITE CONDITION AND CEILING MOUNTED SPEAKSERS, AND

SPEAKER REMOVE AND REINSTALL PLAN

SPEAKER REMOVE AND REINSTALL PLAN

SCALE:

1/100 a a a a a a a a a a a c c c c c c

D-12

SWITCH "c"

TO DIMMER

ELEV1

ATM

102A

DN

UP

ELEV2

(33EA)

VEST

108C

LOCKER

(42EA)

ROOM

BREAK

OFFICE

TRAVEL

LOBBY

HALL

ELEV

MEN

WOMEN

EWC

ANTE

COOLER FREEZER

KITCHEN

COUNTER

SERVING

109A

STO

KITCHEN

STO

CLUB

117A

ENTRY

CLUB

126120

ENTRY

SERVICE

SHO

108B

108A

TELS

STO

CAC

(SMOKING)

ROOM

MACHINE

SLOT

STAIR2

UP

DN

118CCOOLER

BEER

BAR STO

W2

JAN.

OFFICE

PIZZA HUT

SUBWAY

A&W

REFR

SINK

FEC

FEC

FEC

FEC

HANDLING UNIT

PACKAGED AIR

TOILET

UNI-SEX

WOMEN

MEN

MW

CORRIDOR

JC

ROOM

COMM

VESTIBULE

MECH ROOM

C O

R R I

D O

R

C O

R R I

D O

R

CORRIDOR

BOOTH

DJ

ENCLOSURE

TRASH

111A

L3

REFR

REFR

BANK

S

J

S b

Sb

S

S

BAR

COOLER

BEER BAR STO

KEY PLAN

E-1
E-2
E-3
E-4
E-5
E-6
E-7
E-8
E-9