3 - Well log - Well ID 31000000370.pdf

PDF 32 KB Posted

Attached to
751/24242. TAP; McLain SP - Campgrund Improvements
Solicitation number
RFP 171 250000001967 2
Issued by
Houghton County, Michigan

About this file

This is a Water Well and Pump Record Completion form required by the State of Michigan under Part 127 Act 368 PA 1978, documenting a public water well at McLain State Park in Hancock, Michigan (Houghton County). The well, identified as Well ID 31000000370, was drilled using cable tool methodology to a depth of 46 feet and completed on May 24, 1972. The well serves as a Type II public water supply system for the state park concessions facility. The drilling was performed under the supervision of D. Brackenbury, with a 4-inch steel casing installed to 33 feet depth and a 4-inch neoprene packer screen set between 33 and 39 feet. Geological testing revealed stratified sand formations of varying grades, with a static water level measured at 22 feet below grade. The well was properly grouted and equipped with a pitless adapter wellhead completion positioned 12 inches above grade.

The well remains active as of the record date with a pump installation completed, though specific pump specifications including horsepower, manufacturer, model, capacity, and voltage were not documented in this record. A septic tank was identified as the nearest potential contamination source, located approximately 300 feet to the southwest of the well site. The geographic coordinates, determined through GPS Differential methodology, are 47.230231 latitude and -88.622306 longitude at an elevation of 643 feet. No pressure tank or pressure relief valve was installed, and no filter pack was used during construction. This compliance documentation is required under state law, with non-compliance constituting a misdemeanor offense.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Water Well And Pump Record Completion is required under authority of Part 127 Act 368 PA 1978.

Failure to comply is a misdemeanor.Import ID: 31563421401 Tax No: Permit No: County: Houghton Township: Hancock

Well ID: 31000000370 Elevation: 643 ft.

Latitude: 47.230231

Longitude: -88.622306

Method of Collection: GPS Differential (DGPS)

Source ID/Well No:

WSSN:

2006031

Section:

Well Status:

Active

Town/Range:

56N 34W

Distance and Direction from Road Intersection:

2006031, MCLAIN STATE PARK - CONCESSIONS

Well Owner: MCLAIN STATE PARK Well Address:

HANCOCK, MI 49930

Owner Address:

HANCOCK, MI 49930

Drilling Machine Operator Name: D. BRACKENBURY Employment: Unknown

Drilling Method: Cable Tool Well Depth: 46.00 ft. Well Use: Type II public Well Type: New Date Completed: 5/24/1972

Pump Installed: Yes Pump Installation Only: No Pump Installation Date: HP:

Manufacturer: Pump Type: Submersible Model Number: Pump Capacity:

Drop Pipe Length: 0.00 ft.

Drilling Record ID:Drop Pipe Diameter:

Pump Voltage:

Draw Down Seal Used: No Pressure Tank Installed: No Pressure Relief Valve Installed: No

Casing Joint: Unknown

Diameter: 4.00 in. to 33.00 ft. depth

Borehole:

Casing Type: Steel - black Height:

Casing Fitting: None

SAND. [12] [10] [12] SAND FINE TO COARSE. [10] [13] [22] SAND MEDIUM.

[6] [12] [28] SAND MEDIUM TO COARSE. [6] [12] [34] SAND FINE TO

MEDIUM. [1] [11] [35] SAND FINE TO MEDIUM. [4] [11] [39] SAND SILTY. [7]

[11] [46]

Geology Remarks:

Formation Description Thickness Depth to Bottom

Sand 12.00 12.00 Sand Fine To Coarse 10.00 22.00 Sand Medium 6.00 28.00 Sand Medium To Coarse 6.00 34.00 Sand Fine To Medium 1.00 35.00 Sand Fine To Medium 4.00 39.00 Sand Silty 7.00 46.00

Static Water Level: 22.00 ft. Below Grade Well Yield Test: Yield Test Method: Unknown

Well Grouted: Yes Grouting Material Unknown

Bags Additives Depth

0.00 0.00 ft. to 0.00 ft.None

Grouting Method: Unknown

Wellhead Completion: Pitless adapter, Other, 12 inches above grade

Screen Installed: Yes

Slot 10.00

Set Between

33.00 ft. and 39.00 ft.6.00 ft.

Length

Filter Packed: No Blank: 0.00 ft. AboveScreen Diameter: 4.00 in.

Screen Material Type:

Fittings: Neoprene packer

Type Septic tank

Nearest Source of Possible Contamination:

Distance 300 ft.

Direction Southwest

Contractor Type: Unknown

Business Address:

Reg No:

Business Name:

Water Well Contractor's Certification This well was drilled under my supervision and this report is true to the best of my knowledge and belief.

Signature of Registered Contractor Date

EQP-2017 (4/2010) LHD 2/20/2001 8:39 PMPage 1 of 1

Other Remarks:

General Remarks:

File details come from the government source that posted it. Updated .