3.0 PROPOSED LOCHAB BOUNDARY WALL - REVISED STRUCTURAL DRAWINGS.pdf
PDF 1 MB Posted
- Solicitation number
- 19KE5025Q0012
- Issued by
-
Department of State
About this file
These are structural engineering drawings for a perimeter wall construction project at the LOCHAB residence for the U.S. Embassy in Nairobi, Kenya. The drawings detail the specifications for demolition of existing walls and construction of new boundary walls, including retaining walls.
The drawings include detailed layouts and elevations for 6 wall sections totaling approximately 180 meters in length, with heights varying from 2.95m to 5.95m. Key specifications include machine cut masonry blocks, 200x200mm columns, 600x200mm ground beams, 250x250x75mm coping, and three types of retaining walls based on height requirements (Type 1: 5.95m-4.95m, Type 2: 4.95m-3.95m, Type 3: 3.95m-2.95m). The drawings provide comprehensive construction details including foundations, reinforcement schedules, expansion joints, drainage specifications, and soil retention systems. The project requires coordination between demolition, new construction, and repairs to existing walls, with specific attention to ground level differences between the LOCHAB compound and neighboring properties.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AHA Sample Scaffolding.doc | DOC document | |
| Activity Hazard Analysis-Blank Work Sheet.docx | DOCX document | |
| LOCHAB Solicitation 19KE5025Q0025 Mod 1 SF30.pdf | ||
| Risk Matrix.doc | DOC document | |
| SF25-16e Performance Bond.pdf | ||
| EM 385-1-1 _EFFECTIVE 15March2024.pdf | ||
| _Minutes of the Phase Two Construction of Lochab Wall Replacement 19KE5025Q0012 Pre-Proposal Conference Site Visit.docx | DOCX document | |
| CAE-ConstrOverseas_UCF CO V11_signed.pdf | ||
| Non Disclosure Agreement 071823.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3000 3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000 3000 3000 3000 1350
180000
2800 3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000 3000 3000 3000 3000 3000
177650
48275 63825 67900
EXISTING WALL TO BE REPAIRED NEW WORKS EXISTING WORKS
E X
IS
T
IN
G
W A
L L
T O
B E
R E
P A
IR
E
D N
E W
W O
R K
S E
X
IS
T
IN
G W
A L
L T
O B
E R
E P
A
IR
E D
N E
W W
O R
K S
N E
W W
O R
K S
E X
IS
T
IN
G
W A
L L
T O
B E
R E
P A
IR
E
D
9910048275
NEW WORKSDEMOLITIONS + NEW WORKSEXISTING WALL TO BE REPAIRED
E X
IS
T
IN
G
W O
R K
S
E X
IS
T
IN
G
W O
R K
S
E X
IS
TIN
G W
O R K S
EXISTING WORKS
N E W
W O R K
SNEW WORKS
BOUNDARY WALL LAYOUT
SCALE 1:100
BOUNDARY WALL LAYOUT
Project:
NO.
Approved: PKG
Drawn: FNM
Drawing No.
Date : OCT 2024
Client:
Aegis Development Solutions Limited
Project Managers
STRUCTURAL TIMBER:
graded, seasoned and well celcured to
1. All structural timber cypres GS Grade
Drawing Title:STRUCTURAL STEEL:
B - Denotes bottom second layer
BB- Denotes bottom first layer
-bases: sides 75mm bottoms 50mm after erection.
-columns: 40mm
3. All welds shall be six millimetres fillet weld unless otherwise shown or approved.
applied to all structural members before and
2. One coat of red lead oxide paint to be
1. All structural steel shall be BS 5950.
Ministry of Public Work Standards.
CONCRETE:
GENERAL:
DATE
NOTES
and any discrepancy reported to the Engineer.
1. All dimensions shall be confirmed on siteDATE
-slabs:15mm
3. The Contractor shall be responsible for locating
4. DOS denotes Determine on Site and rerouting of all existing services.
2. All foundations shall be on firm ground as shall
4. Proper curing shall be ensured and where necessary hessian shall be used to prevent loss of moisture.
T- Denotes top second layer
6. Cover to the reinforcement:
-beams:25mm
5. TT- Denotes top first layer
1. Concrete to achieve 25n/mm2 at 28 days.
2. In absence of design mix, a nominal 1:1.5:3 shall be used. Scale: AS SHOWN
A Priority:
CADfile:
NOT BE USED OTHERWISE.
IS FOR USE ON THE SPECIFIED PROJECT ONLY AND SHALL
PERMISSION. THE INFORMATION SHOWN ON THIS DRAWING
AND MAY NOT BE REPRODUCED AND/OR COPIED WITHOUT
IS THE EXCLUSIVE PROPERTY OF BATIMENT CONSULTING
THIS DRAWING AS AN IMPORTANT INSTRUMENT OF SERVICE FACILITY MANAGEMENT
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 603, 6th FLOOR
BPCL-E-268/1
Checked : KGW
LOCHAB
ISSUESREVISION
DESCRIPTION BY
PROPOSED LOCHAB PERIMETER WALL UPGRADE
www.aegisdevelopment.co.ke
TEL 020-2730961/0733633004
be approved by the Engineer.
U.S. EMBASSY NAIROBI
P.O. BOX 606-00621
NAIROBI, KENYA
00620; NAIROBI KENYA"
MANAGEMENT, U.S. EMABSSY NAIROBI, P.O. BOX 606
THE EXPRESS WRITTEN APPROVAL OF FACILITY
AND/OR DISTRIBUTION IS PROHIBITED WITHOUT
STATES GOVERNMENT. FURTHER REPRODUCTION
"THIS DOCUMENT IS THE PROPERTY OF THE UNITED
BATIMENT PROJECT
Consultants:
NAIROBI
PO BOX 23751-00100
CONSULTING LTD.
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 307 3rd FLOOR
EMAIL- info@batimentprojects.co.ke
TEL +254 715 392 396
Project managers & Quantity Surveyors
P.O Box 2861-00100, Nairobi Kenya
WALL 1
W A
L L
W
A L
L
WALL 5
WALL 3
LEGEND
Demolitions + new works
New works
(Retaining wall + masonry)
New works ( Masonry)
Existing works
WALL 2
Existing wall to be repaired
(Retaining wall + masonry)
30275
M
IN
D O
S
600X200 BEAM
BELOW GROUND LEVEL
PLOT BOUNDARY
50 BLINDING
4D12-03
3000 3000 275 3000 3000 3000 3000 3000 3000
BOUNDARY WALL 1
200x200
MACHINE CUT
MASONRY BLOCKS
SCALE 1:50
63825 3000 3000 3000 275 3000 3000 3000 3000 3000 3000 3000 3000 3000 275 3000
GROUND 5.5
6.5
7.5
9.5
1701.5
Datum
4.5
3.5
2.5
Coping beam top level
Ground beam top level
Column base bottom level
Station
W17 W18 W20 W21 W22 W23 W24 W25 W26 W27 W28' W29 W30 W31 W32 W33 W34 W35 W36 W38W28 W37'W37
W19'W19
.0
.6
.0
.0
.4
.4
.4
.4
.4
.4
.4
.4
.4
.4
.6
.6
.6
.6
.6
.6
.6
.6
.6
.0
.0
.3
.0
.5
.5
.5
.5
.5
.5
.5
.5
.5
.8
.8
.8
.8
.8
.8
.8
.0
.0
.0
.0
.0
.0
.0
.0
1930 3025
BOUNDARY WALL 5
250x250X75 COPING
MACHINE CUT
MASONRY BLOCKS
GROUND LEVEL
1600 3000 1865 3000 1535
11000
200x200
MACHINE CUT
MASONRY BLOCKS
GROUND LEVEL
BOUNDARY WALL 4
SCALE 1:50SCALE 1:50
BOUNDARY WALL-ELEVATIONS
Project:
NO.
Approved: PKG
Drawn: FNM
Drawing No.
Date : OCT 2024
Client:
Aegis Development Solutions Limited
Project Managers
STRUCTURAL TIMBER:
graded, seasoned and well celcured to
1. All structural timber cypres GS Grade
Drawing Title:STRUCTURAL STEEL:
B - Denotes bottom second layer
BB- Denotes bottom first layer
-bases: sides 75mm bottoms 50mm after erection.
-columns: 40mm
3. All welds shall be six millimetres fillet weld unless otherwise shown or approved.
applied to all structural members before and
2. One coat of red lead oxide paint to be
1. All structural steel shall be BS 5950.
Ministry of Public Work Standards.
CONCRETE:
GENERAL:
DATE
NOTES
and any discrepancy reported to the Engineer.
1. All dimensions shall be confirmed on siteDATE
-slabs:15mm
3. The Contractor shall be responsible for locating
4. DOS denotes Determine on Site and rerouting of all existing services.
2. All foundations shall be on firm ground as shall
4. Proper curing shall be ensured and where necessary hessian shall be used to prevent loss of moisture.
T- Denotes top second layer
6. Cover to the reinforcement:
-beams:25mm
5. TT- Denotes top first layer
1. Concrete to achieve 25n/mm2 at 28 days.
2. In absence of design mix, a nominal 1:1.5:3 shall be used. Scale: AS SHOWN
A Priority:
CADfile:
NOT BE USED OTHERWISE.
IS FOR USE ON THE SPECIFIED PROJECT ONLY AND SHALL
PERMISSION. THE INFORMATION SHOWN ON THIS DRAWING
AND MAY NOT BE REPRODUCED AND/OR COPIED WITHOUT
IS THE EXCLUSIVE PROPERTY OF BATIMENT CONSULTING
THIS DRAWING AS AN IMPORTANT INSTRUMENT OF SERVICE FACILITY MANAGEMENT
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 603, 6th FLOOR
BPCL-E-268/2
Checked : KGWISSUESREVISION
DESCRIPTION BY
PROPOSED LOCHAB PERIMETER WALL UPGRADE
www.aegisdevelopment.co.ke
TEL 020-2730961/0733633004
be approved by the Engineer.
U.S. EMBASSY NAIROBI
P.O. BOX 606-00621
NAIROBI, KENYA
00620; NAIROBI KENYA"
MANAGEMENT, U.S. EMABSSY NAIROBI, P.O. BOX 606
THE EXPRESS WRITTEN APPROVAL OF FACILITY
AND/OR DISTRIBUTION IS PROHIBITED WITHOUT
STATES GOVERNMENT. FURTHER REPRODUCTION
"THIS DOCUMENT IS THE PROPERTY OF THE UNITED
BATIMENT PROJECT
Consultants:
NAIROBI
PO BOX 23751-00100
CONSULTING LTD.
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 307 3rd FLOOR
EMAIL- info@batimentprojects.co.ke
TEL +254 715 392 396
Project managers & Quantity Surveyors
P.O Box 2861-00100, Nairobi Kenya
SHEET 1 OF 2
5.5
6.5
7.5
8.5
1701.5
Datum
4.5
3.5
2.5
Coping beam top level
Ground beam top level
Column base bottom level
Station
.5
.0
5.5
6.5
7.5
8.5
1701.5
Datum
4.5
3.5
2.5
Coping beam top level
Ground beam top level
Column base bottom level
Station
.5
.0
.5
.5
.0
.5
.0
.5
.0
.5
.0
.5
.0
.5
.0
.5
.0
3000 3000 3000
MACHINE CUT
MASONRY BLOCKS
GROUND LEVEL
BOUNDARY WALL 6
SCALE 1:50
.0
5.5
6.5
7.5
1701.5
Datum
4.5
3.5
2.5
Coping beam top level
Ground beam top level
Column base bottom level
Station
.5
.5
.0
.5
.0
.5
.0
.5
S8' S9
.0
.5
S20
.5
S21 S20' S10 S11 S23
.0
.0
S23
.0
.0
.0
.0
.0
.3
.3
.3
.3
.3
.5
.5
.5
.5
.5
.5
.5
.5
.5
.5
.5
.5
.5
600x200
600x200 600x200
.5
.5
.5
.5
S22 S24 S25 S26
SECTION 1-1
SCALE 1:25
NEIGHBOURLOCHAB
GROUND BEAM
COPING BEAM
LEVEL
8.5
GROUND BEAMGROUND BEAM
COPING BEAM
600x200
GROUND BEAM
GROUND
LEVEL
LOCHAB
63825
E56E56' E39E40E41E42E43E44E45E47E47'E48E49E50E51E52E53E54E55E58E59E61 E60
1702.5
Datum
E57 E46
12.5
Masonry wall top level
Station
Retaining wall bottom level
Retaining wall top level
.1
.7
E17E18E19E19'E20E21E22E23E24E25E26E27E28E29E30E31E32E33E34E35E36E37E38E38'E39
1625 3000 3000 3000 3000 275 3000 3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000
NAIROBI
3000 3000 3000 3000 3000 3000
3000 275
Project managers & Quantity Surveyors
P.O Box 2861-00100, Nairobi Kenya
3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000 3000 3000 3000 3000 3000 3000 3000 275 3000 3000
BOUNDARY WALL- ELEVATIONS
Project:
Approved: PKG
Drawn: FNM
Drawing No.
Date : OCT 2024
Client:
Aegis Development Solutions Limited
Project Managers
STRUCTURAL TIMBER:
graded, seasoned and well celcured to
1. All structural timber cypres GS Grade
Drawing Title:STRUCTURAL STEEL:
B - Denotes bottom second layer
BB- Denotes bottom first layer
-bases: sides 75mm bottoms 50mm after erection.
-columns: 40mm
3. All welds shall be six millimetres fillet weld unless otherwise shown or approved.
applied to all structural members before and
2. One coat of red lead oxide paint to be
1. All structural steel shall be BS 5950.
Ministry of Public Work Standards.
CONCRETE:
GENERAL:
DATE
NOTES
and any discrepancy reported to the Engineer.
1. All dimensions shall be confirmed on site
-slabs:15mm
3. The Contractor shall be responsible for locating
4. DOS denotes Determine on Site and rerouting of all existing services.
2. All foundations shall be on firm ground as shall
4. Proper curing shall be ensured and where necessary hessian shall be used to prevent loss of moisture.
T- Denotes top second layer
6. Cover to the reinforcement:
-beams:25mm
5. TT- Denotes top first layer
1. Concrete to achieve 25n/mm2 at 28 days.
2. In absence of design mix, a nominal 1:1.5:3 shall be used. Scale: AS SHOWN
A Priority:
CADfile:
IS FOR USE ON THE SPECIFIED PROJECT ONLY AND SHALL
PERMISSION. THE INFORMATION SHOWN ON THIS DRAWING
AND MAY NOT BE REPRODUCED AND/OR COPIED WITHOUT
IS THE EXCLUSIVE PROPERTY OF BATIMENT CONSULTING
THIS DRAWING AS AN IMPORTANT INSTRUMENT OF SERVICE FACILITY MANAGEMENT
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 603, 6th FLOOR
BPCL-E-268/3
Checked : KGWISSUES
PROPOSED LOCHAB PERIMETER WALL UPGRADE
www.aegisdevelopment.co.ke
TEL 020-2730961/0733633004
be approved by the Engineer.
U.S. EMBASSY NAIROBI
P.O. BOX 606-00621
NAIROBI, KENYA
MANAGEMENT, U.S. EMABSSY NAIROBI, P.O. BOX 606
THE EXPRESS WRITTEN APPROVAL OF FACILITY
AND/OR DISTRIBUTION IS PROHIBITED WITHOUT
STATES GOVERNMENT. FURTHER REPRODUCTION
"THIS DOCUMENT IS THE PROPERTY OF THE UNITED
BATIMENT PROJECT
Consultants:
BLUE VIOLETS PLAZA KINDARUMA RD.
PO BOX 23751-00100
CONSULTING LTD.
SUIT 307 3rd FLOOR
EMAIL- info@batimentprojects.co.ke
TEL +254 715 392 396
LEGEND
Ground Level
.7
.1
.7
.7
NO. DATE
REVISION
DESCRIPTION BY
9.5
5.5
4.5
10.5
8.5
11.5
7.5
6.5
Datum
.3
13.5
4.5
2.5
6.5
9.5
7.5
11.5
8.5
14.5
10.5
5.5
12.5
Station
1700.5
3.5
1.5
.1
.7
(1700+)
.7
.7
.5
3.5
.1
.0
.6
.3
.3
.8
.8
.1
.2
.7
.0
(1700+)
(1700+)
(1700+)
(1700+)
(1700+)
.5
.5
.1
.1
.8
.8
.3
.3
13.5
14.5
.7
.7
.7
.7
.7
.7
.7
.7
.7
.1
.9
.9
.5
.5
Masonry wall top level
Retaining wall bottom level
.7
.7
.7
.7
.3
.2
.0
BOUNDARY WALL 2 & 3
BOUNDARY WALL 3
Retained Earth
RETAINING WALL
MACHINE CUT
MASONRY BLOCKS
RETAINED EARTH
EXISTING GROUND
MACHINE CUT
MASONRY BLOCKS
BACKFILL LEVEL
SCALE : HOR 1: 50, VER 1:50
SCALE : HOR 1: 50, VER 1:50
.1
.1
.1
.1
.1
.1
.1
.1
Retaining wall top level
.1
.1
.1
.1
.1
.0
.0
.7
Remarks
WALL 1 WALL 3
Retaining wall type
Retaining wall type
.1
.1
.0
.6
TYPE 3 TYPE 3 TYPE 3 TYPE 2 TYPE 2 TYPE 2 TYPE 2
TYPE 2 TYPE 2 TYPE 2 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 2 TYPE 3
LEVEL(LOCHAB)
LEVEL(NEIGHBORS)
FOUNDATIONS
15.5
EXISTING GROUND
LEVEL(LOCHAB)
EXISTING GROUND
LEVEL(LOCHAB)
(Lochab)
Ground Level (Neighbor's)
LOCHAB
3000 3000
100100
PLOT BOUNDARY
50 BLINDING
4D12-03
2D12-03
D O
S
M
IN
D
-0
-2
100 100
FOUNDATIONS, BEAMS & COLUMNS
D
-0
-2
M
IN
D O
S
4D12-03
50 BLINDING
4D12-03
D O
S
M
IN
D
-0
-2
600x200 GROUND BEAM(TO BE BELOW GL)
15D8-06-250
2D16-05
2D16-05
15D8-06-250
2D16-05
2D16-05
600x200 GROUND BEAM(TO BE BELOW GL)
FOUNDATIONS LAYOUT
SCALE 1:25
COLS-200x200, BASES-1300x750x250
4D12-01-200B
7D12-02-200BB
100100
SCALE 1:25
2D12-03
3000 30003000 3000 3000
ELEVATION AT EXPANSION JOINT
200x200 COPING BEAM
MACHINE CUT
TYPICAL WALL ELEVATION
BEAM R.C. DETAILS
SCALE 1:10
TYPICAL COPING
D8-09-250
2D10-08
MASONRY BLOCKS
2D10-08
TYPICAL COPING BEAM
SCALE 1:10
250x250X75 COPING
200x200RC COLUMN
550 550
100100
550 550
4D12-01-200B
7D12-02-200BB
2D12-03
550 100 100 550
50 BLINDING
0 600X200 GROUND BEAM
(TO BE BELOW GL)
2D12-03
2D12-03
4D12-01-200B
7D12-02-200BB
2D12-03
550 100 100 550
0 7
0 7
TYPICAL BEAM-COLUMN SUPPORT
D
-0
-2
M
IN
D O
S
4D12-03
50 BLINDING
SCALE 1:25
LAP=0.25L
L A
P
Ø
BOUNDARY WALL DETAILS
Project:
NO.
Approved: PKG
Drawn: FNM
Drawing No.
Date : OCT 2024
Client:
Aegis Development Solutions Limited
Project Managers
STRUCTURAL TIMBER:
graded, seasoned and well celcured to
1. All structural timber cypres GS Grade
Drawing Title:STRUCTURAL STEEL:
B - Denotes bottom second layer
BB- Denotes bottom first layer
-bases: sides 75mm bottoms 50mm after erection.
-columns: 40mm
3. All welds shall be six millimetres fillet weld unless otherwise shown or approved.
applied to all structural members before and
2. One coat of red lead oxide paint to be
1. All structural steel shall be BS 5950.
Ministry of Public Work Standards.
CONCRETE:
GENERAL:
DATE
NOTES
and any discrepancy reported to the Engineer.
1. All dimensions shall be confirmed on siteDATE
-slabs:15mm
3. The Contractor shall be responsible for locating
4. DOS denotes Determine on Site and rerouting of all existing services.
2. All foundations shall be on firm ground as shall
4. Proper curing shall be ensured and where necessary hessian shall be used to prevent loss of moisture.
T- Denotes top second layer
6. Cover to the reinforcement:
-beams:25mm
5. TT- Denotes top first layer
1. Concrete to achieve 25n/mm2 at 28 days.
2. In absence of design mix, a nominal 1:1.5:3 shall be used. Scale: AS SHOWN
A Priority:
CADfile:
NOT BE USED OTHERWISE.
IS FOR USE ON THE SPECIFIED PROJECT ONLY AND SHALL
PERMISSION. THE INFORMATION SHOWN ON THIS DRAWING
AND MAY NOT BE REPRODUCED AND/OR COPIED WITHOUT
IS THE EXCLUSIVE PROPERTY OF BATIMENT CONSULTING
THIS DRAWING AS AN IMPORTANT INSTRUMENT OF SERVICE FACILITY MANAGEMENT
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 603, 6th FLOOR
BPCL-E-268/4
Checked : KGWISSUESREVISION
DESCRIPTION BY
PROPOSED LOCHAB PERIMETER WALL UPGRADE
www.aegisdevelopment.co.ke
TEL 020-2730961/0733633004
be approved by the Engineer.
U.S. EMBASSY NAIROBI
P.O. BOX 606-00621
NAIROBI, KENYA
00620; NAIROBI KENYA"
MANAGEMENT, U.S. EMABSSY NAIROBI, P.O. BOX 606
THE EXPRESS WRITTEN APPROVAL OF FACILITY
AND/OR DISTRIBUTION IS PROHIBITED WITHOUT
STATES GOVERNMENT. FURTHER REPRODUCTION
"THIS DOCUMENT IS THE PROPERTY OF THE UNITED
BATIMENT PROJECT
Consultants:
NAIROBI
PO BOX 23751-00100
CONSULTING LTD.
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 307 3rd FLOOR
EMAIL- info@batimentprojects.co.ke
TEL +254 715 392 396
Project managers & Quantity Surveyors
P.O Box 2861-00100, Nairobi Kenya
TO BE CONSTRUCTED MID-SPAN IN
SCALE 1:10
2D12-19
D8-11-250
2D12-19
TYPICAL BRACING
100 100
DPC
8D12-03
FLEXCEL JOINT
FILLER
LAYOUT AT EXPANSION JOINT
D
-0
-2
WALLS DETAIL AT
SEALANT
APPROVED JOINT
EXPANSION JOINT
SCALE 1:25
600x200 GROUND BEAM
(TO BE BELOW GL)
SCALE 1:25
2D12-03
100 100
4D12-01-200B/T
2D12-03
2D12-032D12-03
D O
S
M
IN
50 BLINDING
7D12-02-200BB/TT
440 100
100 440
100 100 50
PROPERTY BOUNDARY
NEIGHBOUR LOCHAB
LOCHAB
BEAM R.C. DETAILS
MASONRY WALL WITH A HEIGHT MORE THAN 3M
RETAINING WALL WALL DETAILS
Project:
NO.
Approved: PKG
Drawn: FNM
Drawing No.
Date : OCT 2024
Client:
Aegis Development Solutions Limited
Project Managers
STRUCTURAL TIMBER:
graded, seasoned and well celcured to
1. All structural timber cypres GS Grade
Drawing Title:STRUCTURAL STEEL:
B - Denotes bottom second layer
BB- Denotes bottom first layer
-bases: sides 75mm bottoms 50mm after erection.
-columns: 40mm
3. All welds shall be six millimetres fillet weld unless otherwise shown or approved.
applied to all structural members before and
2. One coat of red lead oxide paint to be
1. All structural steel shall be BS 5950.
Ministry of Public Work Standards.
CONCRETE:
GENERAL:
DATE
NOTES
and any discrepancy reported to the Engineer.
1. All dimensions shall be confirmed on siteDATE
-slabs:15mm
3. The Contractor shall be responsible for locating
4. DOS denotes Determine on Site and rerouting of all existing services.
2. All foundations shall be on firm ground as shall
4. Proper curing shall be ensured and where necessary hessian shall be used to prevent loss of moisture.
T- Denotes top second layer
6. Cover to the reinforcement:
-beams:25mm
5. TT- Denotes top first layer
1. Concrete to achieve 25n/mm2 at 28 days.
2. In absence of design mix, a nominal 1:1.5:3 shall be used. Scale: AS SHOWN
A Priority:
CADfile:
NOT BE USED OTHERWISE.
IS FOR USE ON THE SPECIFIED PROJECT ONLY AND SHALL
PERMISSION. THE INFORMATION SHOWN ON THIS DRAWING
AND MAY NOT BE REPRODUCED AND/OR COPIED WITHOUT
IS THE EXCLUSIVE PROPERTY OF BATIMENT CONSULTING
THIS DRAWING AS AN IMPORTANT INSTRUMENT OF SERVICE FACILITY MANAGEMENT
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 603, 6th FLOOR
BPCL-E-268/5
Checked : KGWISSUESREVISION
DESCRIPTION BY
PROPOSED LOCHAB PERIMETER WALL UPGRADE
www.aegisdevelopment.co.ke
TEL 020-2730961/0733633004
be approved by the Engineer.
U.S. EMBASSY NAIROBI
P.O. BOX 606-00621
NAIROBI, KENYA
00620; NAIROBI KENYA"
MANAGEMENT, U.S. EMABSSY NAIROBI, P.O. BOX 606
THE EXPRESS WRITTEN APPROVAL OF FACILITY
AND/OR DISTRIBUTION IS PROHIBITED WITHOUT
STATES GOVERNMENT. FURTHER REPRODUCTION
"THIS DOCUMENT IS THE PROPERTY OF THE UNITED
BATIMENT PROJECT
Consultants:
NAIROBI
PO BOX 23751-00100
CONSULTING LTD.
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 307 3rd FLOOR
EMAIL- info@batimentprojects.co.ke
TEL +254 715 392 396
Project managers & Quantity Surveyors
P.O Box 2861-00100, Nairobi Kenya
200 100
+4750
D
-1
-2
H
IF
D10-17-200 VIF D12-18-150 VOF
B L
IN
D
IN
G
D10-15-200 VIF
D12-16-150 VOF
D
-1
-2
H
IF
D
-1
-2
H O
F
D16-16-200 2/16D10-13-150
4 %
+7300
D
-1
-2
H O
F
D O
S (M
IN
M A
S S
C O
N C
R E
T E
RETAINING WALL TYPE 1 (HEIGHT 5.95M - 4.95M )
SCALE 1:25
200 100
+3750
D
-2
-2
H
IF
D10-24-200 VIF D12-25-200 VOF
B L
IN
D
IN
G
D10-22-200 VIF D12-23-200 VOF
D
-2
-2
H O
F D
-2
-2
H
O F
D12-19-200 2/12D10-20-150
+6300
+3300
D
-2
-2
H
IF
100100
+2750
D
-2
-2
H
IF
D10-31-200 VIF D10-32-200 VOF
B L
IN
D
IN
G
D10-29-200 VIF
D10-30-200 VOF
D
-2
-2
H O
F D
-2
-2
H
O F
D10-26-200 2/8D10-27-200
D O
S
M
IN
+5300 100 100
+2300
D
-2
-2
H
IF
RETAINING WALL TYPE 2 (HEIGHT 4.95M - 3.95M )
SCALE 1:25
RETAINING WALL TYPE 3 (HEIGHT 3.95M - 2.95M )
SCALE 1:25
SHEET 1 OF 2
4 %
(M
IN
4 %
(M
IN
4 % 4 %
(M
IN
4 %
(1 :3
:6 ) 4
(M
IN
NB: THE STORM WATER DRAINAGE SHOWN HERE IS
INDICATIVE. THE STORM WATER DRAINAGE FOR THE
WHOLE SITE SHALL HAVE TO BE DESIGNED AS A DIFF-
ERENT EXERCISE
LOCHAB
0 5
D
-1
-2
H
IF
D
-1
-2
H O
F 2D10-31-200 2D10-32-200
D
-2
-2
H
IF
D
-2
-2
H
F
V A
R
IE
S F
R O
M
VARIES FROM 1400 T0 3000
VARIES FROM
B L
IN
D
IN
G
D O
S
M
IN
100 100
TYPICAL RETAINING WALL DETAILS
SCALE 1:25
DIA. 75 WEEP HOLES
1000 C/C VERTICALLY AND HORIZONTALLY
BITUMINOUS FELT
PROPERTY
LOCHAB NEIGHBOURS
UPPER GROUND
T
200 TO 300
50 SHOTCRETE ON
BS FABRIC A142 MESH
SMOOTH FINISH
TO ARCHITECT'S DETAILS
RETAINED
BEAM TO SHAPE
V A
R
IE
S
F R
O M
T O
3000 3000 3000 275
25 EXPANSION JOINT
D O
S
M
IN
MACHINE CUT STONES
RETAINING WALL
DIA 75 WEEP HOLE
V A
R
IE
S F
R O
M
T
RETAINING WALL DETAILS-TYPICAL DETAILS
Project:
NO.
Approved: PKG
Drawn: FNM
Drawing No.
Date : OCT 2024
Client:
Aegis Development Solutions Limited
Project Managers
STRUCTURAL TIMBER:
graded, seasoned and well celcured to
1. All structural timber cypres GS Grade
Drawing Title:STRUCTURAL STEEL:
B - Denotes bottom second layer
BB- Denotes bottom first layer
-bases: sides 75mm bottoms 50mm after erection.
-columns: 40mm
3. All welds shall be six millimetres fillet weld unless otherwise shown or approved.
applied to all structural members before and
2. One coat of red lead oxide paint to be
1. All structural steel shall be BS 5950.
Ministry of Public Work Standards.
CONCRETE:
GENERAL:
DATE
NOTES
and any discrepancy reported to the Engineer.
1. All dimensions shall be confirmed on siteDATE
-slabs:15mm
3. The Contractor shall be responsible for locating
4. DOS denotes Determine on Site and rerouting of all existing services.
2. All foundations shall be on firm ground as shall
4. Proper curing shall be ensured and where necessary hessian shall be used to prevent loss of moisture.
T- Denotes top second layer
6. Cover to the reinforcement:
-beams:25mm
5. TT- Denotes top first layer
1. Concrete to achieve 25n/mm2 at 28 days.
2. In absence of design mix, a nominal 1:1.5:3 shall be used. Scale: AS SHOWN
A Priority:
CADfile:
NOT BE USED OTHERWISE.
IS FOR USE ON THE SPECIFIED PROJECT ONLY AND SHALL
PERMISSION. THE INFORMATION SHOWN ON THIS DRAWING
AND MAY NOT BE REPRODUCED AND/OR COPIED WITHOUT
IS THE EXCLUSIVE PROPERTY OF BATIMENT CONSULTING
THIS DRAWING AS AN IMPORTANT INSTRUMENT OF SERVICE FACILITY MANAGEMENT
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 603, 6th FLOOR
BPCL-E-268/5
Checked : KGWISSUESREVISION
DESCRIPTION BY
PROPOSED LOCHAB PERIMETER WALL UPGRADE
www.aegisdevelopment.co.ke
TEL 020-2730961/0733633004
be approved by the Engineer.
U.S. EMBASSY NAIROBI
P.O. BOX 606-00621
NAIROBI, KENYA
00620; NAIROBI KENYA"
MANAGEMENT, U.S. EMABSSY NAIROBI, P.O. BOX 606
THE EXPRESS WRITTEN APPROVAL OF FACILITY
AND/OR DISTRIBUTION IS PROHIBITED WITHOUT
STATES GOVERNMENT. FURTHER REPRODUCTION
"THIS DOCUMENT IS THE PROPERTY OF THE UNITED
BATIMENT PROJECT
Consultants:
NAIROBI
PO BOX 23751-00100
CONSULTING LTD.
BLUE VIOLETS PLAZA KINDARUMA RD.
SUIT 307 3rd FLOOR
EMAIL- info@batimentprojects.co.ke
TEL +254 715 392 396
Project managers & Quantity Surveyors
P.O Box 2861-00100, Nairobi Kenya
SHEET 2 OF 2
EXISTING GROUND LEVEL
TYPICAL RETAINING WALL SECTION 1-1
SCALE 1:25
4 %
(M
IN
RAIN WATER CUT-OFF
BIO-SWALE DRAIN
4 %
EARTH
LEVEL
200 THICK MASONRY WALL
FINISHED TO ARCHITECT'S SPECS
TO BE AS PER DESIGN FOR
FOR SITE SWD FOR WHOLE SITE
(LOCHAB COMPOUND)
COMPOUND
200x200 COPING
BOUNDARY
FELT DPC
VARIES
PEGGED TO EXCAVATED FACE
WITH DIA.12 D12x600 PEGS
AT 1000 HOR+VERT
100010001000
NB: THE STORM WATER DRAINAGE SHOWN HERE IS
INDICATIVE. THE STORM WATER DRAINAGE FOR THE
WHOLE SITE SHALL HAVE TO BE DESIGNED AS A DIFF-
ERENT EXERCISE
D12x600 PEGS
LOCHAB
BENT TO SUIT
D12x600 PEGS DETAILS
SCALE 1:2.5
D12x600 PEGS ELEVATION
SCALE 1:2.5
Approved: PKG
Drawing No.
Date : OCT 2024
Project:Client: Project Managers
Drawing Title:
BY
ISSUES DATE
NOTES
DESCRIPTIONDATE
REVISION
NO. Scale: AS SHOWN
A
Priority:
CADfile:
NOT BE USED OTHERWISE.
IS FOR USE ON THE SPECIFIED PROJECT ONLY AND SHALL
PERMISSION. THE INFORMATION SHOWN ON THIS DRAWING
AND MAY NOT BE REPRODUCED AND/OR COPIED WITHOUT
IS THE EXCLUSIVE PROPERTY OF BATIMENT PROJECT CONSULTING
THIS DRAWING AS AN IMPORTANT INSTRUMENT OF SERVICE
BPCL-E-268/6EARTHWORKS-ANALYSIS
LOCHAB
Checked: KGW
Drawn : FNM
BATIMENT PROJECT
NAIROBI
PO BOX 23751-00100
CONSULTING LTD.
EMAIL- info@batimentprojects.co.ke
BLUE VIOLETS PLAZA KINDARUMA RD.
CELL + 254 715392396
SUITE 307 3rd FLOOR
WEB - www.batimentprojects.co.ke
PROPOSED LOCHAB PERIMETER WALL UPGRADE
Lateral Stress Major σ3 = (ƴ h + q) ke - 2c√ka
Minor σ1 = q + ƴ h
At ground level σ3 = qke -2c√ka
Red Soil k = 0.333
C = 20 kN / m2 ƴ = 16 kN / m3 σ3 = (ƴ h + q ) ke - 2c√ka crack develops where σha = 0 (0.333 x 7.5) + ( 1.35 x 16 x ht x 0.333) - 31.18 ht = 3.983 m
Max depth (Hc)
Hc = 2ht = 2 x 3.983 = 7.97 m
Mechanics for Lateral Stresses due to soil and surcharge
2.0
5.0
Ground Level
Backfill q
Y
X c = 20 kPa ø = 30° ƴ = 16 kN / m3 q - imposed load for garages and vehicle traffic areas q = 5.0 kN / m2 applying ULS partial factors of safety q = 1.5 x 5 q= 7.5 kN / m2 σha live = 7.5 x 13 = 2.5 kN / m2 σha dead = 0 - 2 x 20 x 0.333 = - 23.094 kN / m2 applying ULS partial factors of safety σhadead = 1.35 x 23.094
=-31.18 kN / m2 σha 0m = 2.5 - 31.18 =-28.68 kN / m2
Mechanics for Lateral Stresses due to Surcharge at the top of the cut σha live = 2.5 kN / m2 σha dead = 16 x 4.3 x 13 - 23.094 = - 0.161 kN / m2 applying ULS partial factors of safety σha dead = 1.35 x - 0.161
= - 0.2169 kN / m2 σha 4.3m = 2.5 - 0.2169 =2.2831 kN / m2
Mechanics for Lateral Stresses due to Surcharge at the bottom of the cut
Unsupported excavated face cracking analysis
1.0
Figure 1: Excavation for lochab perimeter wall
3.0
4.0
Existing ground level
Backfill
Y
X
Tension crack
Maximum depth of excavation
6.0
Figure 2: Depth of crack for lochab retaining wall
Figure 3: Lateral earth pressure diagram due to symmetry w = 15.24 kN / m 2 load = 12 bh
= 1 2 x 15.24 x 2.117
= 10.92 kN
R
10.92 Cos 45 = 10.92 / R
R = 15.44 kN fy = 500 N/mm2
Asreq = 15.44 x 10 3 / 0.87 x 500 = 35.49 mm2
Provide 1 row of D12 @ 1000 mm As prov = 113.098 mm2
7.0
Soil Nails Analysis
,0
8.0
FACILITY MANAGEMENT
U.S. EMBASSY NAIROBI
P.O. BOX 606-00621
NAIROBI, KENYA
qkA - 2c√ka ƴ hka
-28.68 kN/m2 30.96 kN/m2
-28.68 kN/m2
2.28 kN/m2
Shotcrete Concrete/
Plaster on BS MESH
File details come from the government source that posted it. Updated .