3-Binder 3 - Drawings - CWU-0089-L BENTLEY STREET LEVEL RENOVATION CONSTRUCTION DOCUMENTS.pdf

PDF 8 MB Posted

Attached to
CWU-89-L: Bentley Street Level Renovation Lock Haven Campus
Solicitation number
Not on record
Issued by
Clearfield County, Pennsylvania

About this file

Summary: Construction Documents for Bentley Street Level Renovation

This is a comprehensive set of architectural, mechanical, and electrical construction documents for the Bentley Street Level Renovation project at Lock Haven University in Lock Haven, Pennsylvania, prepared under the Pennsylvania State System of Higher Education. The project involves the renovation of 3,810 gross square feet of interior space at street level, including selective demolition, new interior glazing and decorative walls, new ceilings and flooring, new exterior signage, and painting. The work scope encompasses general construction; HVAC work including removal and replacement of ceiling diffusers, installation of a new mini-split heat pump system, and repositioning of sprinkler heads; and electrical work including new interior lighting, additional outlets, and new information technology infrastructure. The project will be executed by separate prime contractors (General, HVAC, and Electrical), with the General Contractor serving as the lead prime contractor. A mandatory pre-bid conference with site visit is scheduled for November 12, 2026, at 11:00 AM EST at Bentley Dining Hall on the Lock Haven University campus. Electronic bids are due no later than 1:00 PM EST on December 8, 2026, through PennBid at https://pennbid.bonfirehub.com/.

The bid package is available at no cost through PennBid, which requires free registration for interested bidders to obtain solicitation documents and submit proposals. The construction documents include detailed floor plans, demolition plans, reflected ceiling plans, interior elevations and details, mechanical floor plans with equipment schedules and ductwork specifications, and comprehensive electrical plans and schedules. Key architectural features include fully accessible toilet rooms, new classroom spaces (675 square feet and 643 square feet), a podcast studio (512 square feet), a lobby (1,095 square feet), and a vestibule, with finishes specified including carpet tile, acoustic ceiling, gypsum wall board, paint, rubber base, and specialized wall systems. The mechanical system includes retention of the existing rooftop unit (RTU-3) with VAV boxes, installation of a ductless split system for supplemental heating and cooling, and new diffusers and grilles. No specific contract pricing, funding sources, or set-asides are identified in the construction documents provided.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

STATE SYSTEM OF HIGHER EDUCATION

Scale:

Date:

Project/Contract No.

Drawn By:

Checked By:

Drawing No.

Title:

Submitted:

Authorized By:

Reviewed By:

Submitted:

Description DescriptionDateDate

System Representative:

Construction Manager:

Consultant:

Professional:

AS NOTED

COMMONWEALTH UNIVERSITY

N

PROJECT LOCATION

STATE SYSTEM OF HIGHER EDUCATION

COMMONWEALTH OF PENNSYLVANIA

VICINITY MAP

PROJECT SITE

JOSH SHAPIRO, GOVERNOR

CHRIS FIORENTINO, CHANCELLOR

DR. JEFFERY OSGOOD, PRESIDENT

CPL/RMS

TLS

CS

COVER SHEET

PROJECT AREA

CWU-0089-L BENTLEY STREET LEVEL RENOVATION

CONSTRUCTION

LOCK HAVEN UNIVERSITY

LOCK HAVEN, CLINTON COUNTY, PENNSYLVANIA

CWU-ARCH-1232024-C-3 - CWU-89-L

CWU-ARCH-1232024-C-3 - CWU-89-L

LOCK HAVEN UNIVERSITY

LOCK HAVEN, CLINTON COUNTY, PENNSYLVANIA

ARCHITECTURAL

CS COVER SHEET

A0.1 SITE PLAN

A0.2 LIFE SAFETY PLANS

A0.3 CODE ANALYSIS & NOTES

AD1.0 DEMOLITION PLANS

A1.1 FLOOR PLAN

A2.0 EXTERIOR ELEVATION

A6.1 REFLECTED CEILING PLAN

A8.1 FINISH FLOOR PLAN

A8.2 INTERIOR ELEVATIONS

A8.3 INTERIOR DETAILS

MECHANICAL

M0.0 LEGEND, NOTES, AND DRAWING SCHEDULE

M1.1 STREET LEVEL FLOOR PLAN - MECHANICAL DEMOLITION

M2.1 STREET LEVEL FLOOR PLAN - MECHANICAL

ELECTRICAL

E0.0 LEGEND, NOTES AND DRAWING SCHEDULE

E1.1 FLOOR PLANS - ELECTRICAL DEMOLITION

E2.1 STREET LEVEL FLOOR PLAN - LIGHTING

E3.1 STREET LEVEL FLOOR PLAN - POWER AND SYSTEMS

FIRE PROTECTION

FP1.1 LEGEND, NOTES & STREET LEVEL FLOOR PLANS

11.03.2026

ACCESSIBLE ENTRANCE

TO STREET LEVEL

ACCESSIBLE ENTRANCE

TO GROUND FLOOR

ACCESSIBLE ENTRANCE

TO FIRST FLOOR

LO

A

D

IN

G D

O C

K

SERVICE & DUMPSTERS

THERE IS NO VISITOR PARKING

PROVIDED TO THE BUILDING

IT IS WITHIN THE GREATER

COLLEGE CAMPUS

G

LE

N N

R O

A D

FAIRVIEW STREET

AK

EL

EY

R

O

AD

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:2

P

M

CONSTRUCTION

A0.1

SITE PLAN

26-CUP-0226-CUP-02 TLS / GMBTLS / GMB

1" = 20'-0"A0.1

1 SITE PLAN

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

IO

SCOPE OF WORK:

NONE

EXIT

EXIT

EXIT

EXIT

EXIT

EXIT

EXIT

SCOPE OF WORK:

NONE

EXIT

EXIT

FULLY ACCESSIBLE

TOILET ROOMS

ELEVATOR

EXIT

SCOPE OF WORK:

INTERIOR RENOVATIONS

EXIT

EXIT

FULLY ACCESSIBLE

TOILET ROOMS

AREA OF WORK

3810 GROSS SQ FT

1320sf CLASSROOM 514sf CLASSROOM

500sf SITTING AREA

NO WORK

NO WORK

NO WORK

PHASED CONSTRUCTION BARRIER,

MUST MAINTAIN ACCESS TO ELEVATOR

& STAIR DURING SEMESTER

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:2

P

M

CONSTRUCTION

A0.2

LIFE SAFETY PLANS

26-CUP-0226-CUP-02 CPLCPL

3/32" = 1'-0"A0.2

1 GROUND FLOOR CODE PLAN

3/32" = 1'-0"A0.2

2 FIRST FLOOR CODE PLAN

3/32" = 1'-0"A0.2

3 STREET LEVEL CODE PLAN

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

PLUMBING CODE ANALYSIS:

INTERNATIONAL PLUMBING CODE - 2021

403.1.1 FIXTURE CALCULATIONS

TO DETERMINE THE OCCUPANT LOAD OF EACH SEX, THE TOTAL OCCUPANT LOAD SHALL BE

DIVIDED IN HALF. TO DETERMINE THE REQUIRED NUMBER OF FIXTURES, THE FIXTURE RATIO

OR RATIOS FOR FIXTURE TYPE SHALL BE APPLIED TO THE OCCUPANT LOAD OF EACH SEX IN

ACCORDANCE WITH TABLE 403.1

2021 EXISTING INTERNATIONAL BUILDING CODE 810.1 MINIMUM FIXTURES:

WHERE THE OCCUPANT LOAD OF THE STORY IS INCREASED BY 20 PERCENT, PLUMBING FIXTURES FOR THE STORY SHALL BE PROVIDED IN QUANTITIES SPECIFIED IN THE INTERNATIONAL PLUMBING

CODE BASED ON THE INCREASED OCCUPANT LOAD.

BUILDING REQUIREMENTS

EXISTING OCCUPANCY 2005

NEW OCCUPANCY 2005

2005 OCC/ 2 = 1003 MALE AND 1003 FEMALE

WATER CLOSETS - 1/75 = 13.3, OR 14 EACH MALE & FEMALE

PROVIDED = 9 MALE WCs + 10 URINALS & 15 FEMALE WCs

LAVATORIES - 1/200 = 5.015. 0R 6 EACH MALE & FEMALE

PROVIDED = 11 FEMALE & 10 MALE

DRINKING FOUNTAINS - WATER IS AVAILABLE TO ALL PATRONS ON GROUND & FIRST FLOORS, THERE

IS AN EXISTING, ACCESSIBLE HIGH/LOW DRINKING FOUNTAIN ON STREET LEVEL

SERVICE SINKS - 9 EXISTING

" M

IN

18" MIN

" M

IN

12" MIN

(A) FRONT APPROACH, PULL SIDE *IF BOTH CLOSER AND LATCH ARE PROVIDED

(B) FRONT APPROACH, PUSH SIDE

DOUBLE DOOR W/

(2) ACTIVE LEAVES

RIGHT SIDE

OF DOOR

NOTE: REFER TO SPECIFICATIONS FOR SIGNAGE SIZE AND LOCATION REQUIREMENTS.

9"

1'-6"

CLEAR

FLOOR AREA

ROOM

NAME

4' -0

5' -0

" M

AX

BR

AI

LL

E

H

EI

G H

T

BA

SE

LI

N

E O

F H

IG

H

ES

T

TE

XT

ROOM

NAME

ROOM

NAME

SINGLE DOOR

LATCH SIZE

9"

1'-6"

4' -0

5' -0

" M

AX

BR

AI

LL

E

H

EI

G H

T

BA

SE

LI

N

E O

F H

IG

H

ES

T

TE

XT

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:2

P

M

CONSTRUCTION

A0.3

CODE ANALYSIS &

NOTES

1/2" = 1'-0"A0.3

1 ADA DOOR SWING APPROACH

1/2" = 1'-0"A0.3

2 TACTILE SIGNAGE

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

9.1

9.4

9.2 9.2

9.1

9.3

9.5

9.2

9.6

9.3

9.3

9.6

9.6

9.5 9.5

9.7

9.8 9.8

9.8

9.8

9.8

9.8

9.8

1.

2.

3.

A.

B.

A.

B.

PRIOR TO COMMENCEMENT OF WORK:

G.C. SHALL REVIEW AND VERIFY ACTUAL FIELD CONDITIONS AND

NOTIFY THE ARCHITECT IN WRITING OF ALL INCONSISTENCIES OR

CONFLICTS. EXIST. CONSTRUCTION MAY VARY FROM THE

DRAWINGS.

G.C. SHALL REVIEW AND VERIFY ALL DEMOLITION WORK AGAINST

ALL NEW CONSTRUCTION WORK AND NOTIFY THE ARCHITECT IN

WRITING OF ALL INCONSISTENCIES OR CONFLICTS. REFER TO

FINISH PLANS AND SCHEDULES FOR COORDINATION OF

DEMOLITION WORK WITH NEW FINISHES AND CONSTRUCTION.

PROTECTION, INTERIOR :

G.C. TO PROTECT ALL EXIST. CONSTRUCTION, FINISHES,

FURNITURE, FIXTURES AND EQUIPMENT TO REMAIN DURING ALL

PHASES OF DEMOLITION AND CONSTRUCTION. U.N.O. G.C. SHALL

DETERMINE APPROPRIATE MEANS OF PROTECTION.

FLOOR AND WALL BASE: PROVIDE LAPPED AND TAPED

SHEET GOOD TO PROTECT ALL FLOOR FINISHES AND

WALL BASES.

WALL: PROVIDE PARTIAL HEIGHT LAPPED AND TAPED

SHEET GOOD AT AREAS OF INTENSIVE USE,

PARTICULARLY OUTSIDE CORNERS.

4. STRUCTURE AND TEMPORARY SHORING :

G.C. SHALL PROTECT AND ENSURE THAT ALL EXIST. STRUCTURE

REMAINS UNDISTURBED U.N.O.

A. G.C. SHALL PROVIDE ALL TEMPORARY SHORING AND

SUPPORT DURING ALL DEMOLITION AND CONSTRUCTION

ACTIVITIES.

5. REMOVAL:

G.C. SHALL REMOVE ALL CONSTRUCTION INDICATED UNLESS

REQUESTED BY THE OWNER TO BE SALVAGED.

A. ALL MATERIALS TO BE REMOVED SHALL BE PROPERLY

REMOVED IN STRICT COMPLIANCE WITH ALL LAWS, PROJECT

SPECIFICATIONS AND IN A MANNER WHICH DOES NOT IMPEDE

THE PROJECT SCHEDULE; DOES NOT OPEN THE BUILDING TO

DETRIMENT; AND DOES NOT ADVERSELY IMPACT CAMPUS OR

BUILDING OPERATION.

B. G.C. SHALL REMOVE ALL ITEMS INCIDENTALLY

NECESSARY FOR REMOVAL OF ITEMS INDICATED FOR REMOVAL,

STORE, AND REINSTALL AT APPROPRIATE STAGE OF

CONSTRUCTION.

C. REFER TO OTHER DISCIPLINE DRAWINGS FOR RELEVANT

DEMOLITION SCOPE.

6. SALVAGE:

ALL SALVAGE RIGHTS REMAIN WITH THE OWNER. G.C. SHALL

COORDINATE WITH OWNER PRIOR TO COMMENCEMENT OF

WORK AND AS REQ'D DURING DEMOLITION AND CONSTRUCTION

ACTIVITIES. ANY ITEMS NOT REQUESTED BY THE OWNER SHALL

BE PROPERLY BY THE G.C.

ANY ITEMS INDICATED FOR SALVAGE OR REINSTALLATION SHALL:

BE TAGGED FOR IDENTIFICATION AS TO WHERE THE ITEM

WAS REMOVED AND PLANNED TO BE RELOCATED.

BE STORED IN A SAFE DRY LOCATION AWAY FROM ANY

CONSTRUCTION ACTIVITIES. COORDINATE LOCATION

WITH OWNER.

7. REPAIR:

G.C. TO REPAIR OR REPLACE IN KIND AT NO COST TO OWNER ALL

DAMAGE TO EXIST. BUILDING AND F.F.E., TEMPORARY

PROTECTION, AND PARTIAL OR COMPLETED CONSTRUCTION AND

F.F.E. RELATED TO ANY DEMOLITION OR CONSTRUCTION

ACTIVITY. WHERE AN ITEM OR ASSEMBLY CANNOT BE REPAIRED,

IT SHALL BE REPLACED IN KIND.

WHERE CONCEALED, EXIST. DAMAGE IS DISCOVERED, SUCH AS

PATCHING REQ'D TO EXIST. CONC. FLOOR, G.C. SHALL PATCH

AND OR REPAIR AS REQ'D FOR SOUND, LEVEL AND PLUMB

SUBSTRATES TO TOLERANCES REQ'D BY MFR. OR IDENTIFIED IN

THE SPECIFICATIONS.

BASE SCOPE DEMOLITION GENERAL NOTES

BASE SCOPE DEMOLITION LEGEND

EXIST. ELEMENTS TO REMAIN

EXIST. ELEMENTS TO BE REMOVED

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:3

P

M

CONSTRUCTION

AD1.0

DEMOLITION PLANS

1/8" = 1'-0"AD1.0

1 STREET LEVEL DEMO PLAN

1/8" = 1'-0"AD1.0

2 STREET LEVEL DEMO RCP

DEMOLITION SPECIFIC NOTES - SHEET AD1.0

9.1 REMOVE TILE

9.2 REMOVE CARPET

9.3 REMOVE WALL & ASSOCIATED FRAMING

9.4 REMOVE WALL SEGMENTS FOR GLAZING

9.5 REMOVE WALL COVERINGS & FINISHES

9.6 REMOVE CHAIR RAIL FROM WALL

9.7 TO REPLACE WITH SIMILAR PRODUCT WHILE PRESERVING SURROUNDING

TILE

9.8 REMOVE 24x24 CEILING & ASSOCIATED FRAMING

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

IO

N

0 16' 24' 32'8'

0 16' 24' 32'8'

A8.2

A8.2

A8.2

DD1.5

1095 SF

LOBBY

S02

512 SF

PODCAST

SPACE

S05

57 SF

IT

CLOSET

614 SF

CORRIDOR

S-C1

675 SF

CLASSROOM

G53

643 SF

CLASSROOM

G54

A8.2

A8.2

DD1.5

1 / 2

A2.0

A2.0

A2.0

A8.3

A8.3

P1

P2

P2

P2

P1P1

P1

P2

11' - 6 1/2"

5'

1/

2"

12' - 4" 2' - 0 1/2" 30' - 11 1/2" 2' - 0 1/2" 31' - 0" 2' - 0 1/2" 13' - 2 1/4"

P2

P2

P2

P2

7' - 9 3/4"

6' - 0 1/4"

7' - 10"

P2

P2

P2

P2

P2

P2

P2

P2

5' - 9"

A2.0

A2.0

STUD PARTITIONS

P1 3 5/8" METAL STUD W/ 5/8" GYP. BOARD

EACH SIDE w/ SOUND BATT INSULATION

INTERIOR PARTITIONS

PARTITION TYPE SCHEDULE & NOTES

P2 3 5/8" STUD W/ 5/8" GYP. BOARD ONE

SIDE.

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:2

P

M

CONSTRUCTION

A1.1

FLOOR PLAN

1/4" = 1'-0"A1.1

1 STREET LEVEL PLAN

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

IO

N

N

S

E

W

PLAN

NORTH

0 8' 12' 16'4'

STREET LEVEL

-14' - 0"

1'

2'

5" 3'

5"

3'

7"

7' - 0"

5'

1/

2"

STREET LEVEL

-14' - 0"

A2.0

RELOCATE EXISITNG "BENTLEY"

SIGN

DONOR SIGNAGE;

FONT TYPE: FRANKLIN GOTHIC

FINISH:

BRUSHED ALUMINUM

ACRYLIC PANEL - BLACK

BRUSHED ALUMINUM FRAME

ALUMINUM PANELS

WRAPPED OVER

EXISTING FINISH

EXISTING BRUSHED

ALUMINUM CAP

STREET LEVEL

-14' - 0"

A2.0

1/2" 1"

2 1/4"

DONOR SIGNAGE;

FONT TYPE: FRANKLIN GOTHIC

FINISH:

BRUSHED ALUMINUM

SIZE: 10 & 6"

ACRYLIC PANEL - BLACK

BRUSHED ALUMINUM FRAME

BRUSHED ALUMINUM FRAME (MATCH

KAWNEER TRIFAB 451 SYSTEM)

2" 2"

5'

1/

2"

5' - 1 1/2"

3' - 10 3/4"

10' - 4 3/4"

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:2

P

M

CONSTRUCTION

A2.0

EXTERIOR ELEVATION

1/4" = 1'-0"A2.0

1 STREET LEVEL ELEVATION

1/2" = 1'-0"A2.0

2 SIGNAGE ELEVATION

1/2" = 1'-0"A2.0

3 SIGNAGE ELEVATION - SIDE

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

IO

N

1" = 1'-0"A2.0

4 SIGNAGE DETAIL

1/4" = 1'-0"5 SIGN PLAN

S

S

S

S

S

S

S

S

WA

P

S

S

S

S

WA

P

S

RC

OS

DS

OS

OS

RC

RC

RC

RC

OS

OS

OS

RC

OS

OS

RC

RC

OS

DS

OS

RC

RC

OS

OS

OS

DS

WA

P WA

P

WA

P

8' - 11"

9' - 4"

9' - 4"

9' - 5 3/4"

9' - 5 3/4"

10' - 0"

9' - 0 3/4"

A6.1

A6.1

A6.1

A8.3

A8.3

CLASSROOM

G54

CLASSROOM

G53

CORRIDOR

S-C1

IT

CLOSET

S12

PODCAST

SPACE

S05

VESTIBULE

S01

LOBBY

S02

INFILL GAP AROUND

PARTITION OPERATOR

A2.0

PROVIDE HOLD DOWN CLIPS

FOR CEILING TILES WITHIN

VESTIBULE

EXISTING CEILING - GWB, PREP &

PAINT,

PARTITION TRACK TO REMAIN

INFILL GWB WHERE

DAMAGED/MISSING

ACOUSTICAL CAULK

AROUND ALL

PENETRATIONS

NEW CEILING TILE

IN EXISTING GRID

NEW CEILING TILE

IN EXISTING GRID

INFILL GWB WHERE

DAMAGED/MISSING

ACOUSTICAL CAULK

AROUND ALL

PENETRATIONS

INFILL ACOUSTICAL

SEALANT IN ANY

GAPS BETWEEN TOP

OF EXISTING WALL

& METAL DECK

5"

PERIMETER TRIM

OF LINEAR METAL

SUSPENSION SYSTEM

2X2 ACT CEILING

PLANX PANEL

PLANX CARRIER GRID

SYSTEM

NOTE: REFER TO MFG. DETAIL

AND SPECIFICATION

GENERAL REFLECTED CEILING PLAN

LEGEND AND NOTES:

ACOUSTICAL CEILING INSTALLATION

1. THE CONTRACTOR SHALL FIELD CHECK THE PREMISES AND VERIFY THAT THE

CEILING LAYOUT SHOWN ON THE DRAWINGS CAN BE ACCOMMODATED AND VERIFY

ALL CLEARANCES AS REQUIRED FOR ALL LIGHTING FIXTURES, DUCT WORK, AND

SPRINKLERS BEFORE PROCEEDING WITH ANY INSTALLATION. REPORT ANY

DISCREPANCIES TO THE ARCHITECT PRIOR TO PROCEEDING.

2. REVIEW CEILING LAYOUT WITH MEP COORDINATION DRAWINGS.

3.

4.

CEILING SHALL BE TRUE, FLAT, STRAIGHT AND REGULAR. PROVIDE STABILIZER BARS AS

REQUIRE TO DISTRIBUTE LOAD EQUALLY OVER TWO OR MORE RUNNERS.

5.

LEVEL CEILING TO BE WITHIN 1/8" IN 12 FEET IN ANY DIRECTION. LEVEL WITH HANGER WIRE

TAUT AND PLUMB, WITHOUT KINKING OR BENDING HANGER WIRES. CEILING HEIGHT SHALL

MATCH EXISTING UNLESS OTHERWISE NOTED.

6.

INSTALL MAX. LENGTHS OF EDGE MOLDING AT INTERSECTION OF CEILING AND VERTICAL

SURFACE. MITER ALL CORNERS.

7.

COORDINATE INSTALLATION WITH ELECTRICAL, MECHANICAL AND SPRINKLER REQUIREMENTS.

8.

INSTALL CEILING TILE HOLD DOWN CLIPS IN ALL VESTIBULES & AIR LOCKS.

9.

LAY DIRECTIONAL PATTERN UNITS IN SINGLE DIRECTION.

10.

INSTALL CEILING TILE HOLD DOWN CLIPS AT PARTITIONS WITH CUT CEILING TILES.

11. REGULAR CEILING TILE TO BE CUT AND FITTED SNUG AGAINST PARTITIONS. DO NOT SHIM

THE GRID TO ALLOW CEILING TILE TO PASS OVER TOP OF PARTITION.

ALL FIXTURE TRIM (LIGHTING, SPEAKER,, HVAC GRILLES, ETC.) SHALL BE METAL AND

PAINTED TO MATCH ADJACENT CEILING FINISH. PLASTIC TRIM IS NOT ACCEPTABLE UNLESS

APPROVED BY THE ARCHITECT.

- INDICATES 2X4 A.C.T. CEILING, REFER TO FINISH SCHEDULE.

- INDICATES G.W.B. CEILING, REFER TO FINISH SCHEDULE.

NOTES:

1.) REFER TO SPECIFICATIONS FOR CEILING MATERIALS.

FINAL CEILING HEIGHTS TO BE CONFIRMED FOLLOWING FIRE PROTECTION, PLUMBING,

MECHANICAL, AND ELECTRICAL COORDINATION

12.

2.) EXISTING GRIDS ARE NOT SHOWN FOR CLARITY, VERIFY IN FIELD.

- INDICATES 2X2 A.C.T. CEILING, REFER TO FINISH SCHEDULE.

- INDICATES AREA IN WHICH CONTRACTOR SHALL INSPECT EXISTING CEILING SYSTEMS

AND REPLACE DAMAGED ACT AND DEFECTIVE GWB CEILING AREAS ONLY.

CONTRACTOR SHALL RETAIN ALL EXISTING UNDAMAGED CEILING FINISHES.

- PAINT EXPOSED CEILING, INCLUDING ALL STRUCTURAL AND MEP COMPONENTSEXPOSED

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:2

P

M

CONSTRUCTION

A6.1

REFLECTED CEILING

PLAN

1/4" = 1'-0"A6.1

1 STREET LEVEL REFLECTED CEILING PLAN

1 1/2" = 1'-0"A6.1

2 CEILING DETAIL - CLASSROOM

1 1/2" = 1'-0"A6.1

3 CEILING DETAIL - PODCAST

1 1/2" = 1'-0"A6.1

4 CEILING DETAIL - LOBBY

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

IO

N

N

S

E

W

PLAN

NORTH

0 8' 12' 16'4'

675 SF

CLASSROOM

G53

643 SF

CLASSROOM

G54

512 SF

PODCAST

SPACE

S05

57 SF

IT

CLOSET

S12

614 SF

CORRIDOR

S-C1

1095 SF

LOBBY

S02

138 SF

VESTIBULE

S01

A8.3

A8.3

CPT-2 RF-1

CPT-2

EXIST

CPT-2 RF-1

RF-1

RF-1

EXIST

EXIST

R F-1

RF-1

EXIST

RF-1

EXIST

ACCENT WALL

(PNT-2/PNT-3)

REF. ELEVATION

R F-1

EXIST

R F-1

C

PT-2

R F-1

C

PT-2

ACCENT WALL

(PNT-2)

ACCENT WALL

(PNT-2)

W G

-1

PAINT FACE AND

SIDES OF BUMP OUT

(PNT-2)

PAINT FACE AND

SIDES OF BUMP OUT

(PNT-2)

PAINT FACE AND

SIDES OF BUMP OUT

(PNT-2)

R F-

R

F-

R F-

R

F-

W C

P-

W C

P-

R F-

R F-

R F-

RF-1 EXIST

EX

IS

T

W C

P-

W C

P-

WG-1 WS-1WS-1

W S-1

W S-1

W S-1

RF-1

RF-2

AC

C

EN

T

(PN

T-2)

AC

C

EN

T

(PN

T-2)

PAINT EXIST DOOR

FRAME (PNT-4)

PAINT EXIST DOOR

FRAME (PNT-4)

PAINT EXIST DOOR

FRAME (PNT-4)

PAINT EXIST DOOR

FRAME (PNT-4)

PAINT EXIST DOOR

FRAME (PNT-4)

PAINT EXIST DOOR

FRAME (PNT-4)

PAINT EXIST DOOR

FRAME (PNT-4)

PAINT EXIST DOOR

FRAME (PNT-4)

A2.0

MANUFACTURER: MOHAWK CARPET TILE; COLLECTION: LEARN & LIVE; STYLE: SIDE

STRIPE GT419; COLOR: 963 HERITAGE; SIZE: 24"X24"

CPT-2

MANUFACTURER: MOHAWK CARPET TILE; COLLECTION:FRACTAL FLUENCY; STYLE:

SQUARED GT478; COLOR: 949 MINERAL; SIZE: 12"X36"

CPT-2

BASE FINISHES

FINISH LEGEND

FLOOR FINISHES

RB

JOHNSONITE/ TARKETT, RUBBER COVE BASE, SIZE: 4" COLOR: TBD, INCLUDE 1-3 COLORS IN

ADDITION TO (TBD), TO BE DETERMINED FROM MANUFACTURER'S FULL RANGE.

PAINT

PNT-1:

FIELD PAINT: BENJAMIN MOORE, COLOR: OC-17 WHITE DOVE, FINISH: SCUFF-X EGGSHELL

PNT-2:

ACCENT PAINT (LOCK HAVEN PANTONE): BENJAMIN MOORE, COLOR TO MATCH: PANTONE PMS 1955

FINISH: SCUFF-X EGGSHELL

CEILING FINISHES

ACT:

ACOUSTIC CEILING TILE: REFER TO SPECIFICATIONS FOR PRODUCT TYPES AND SPECIFIC

LOCATIONS.

GWB:

GYPSUM WALL BOARD, PAINTED FINISH, AS REQUIRED

WALL FINISHES

MANUFACTURER: MOHAWK GROUP, SERIES: CREATIVE TERRAIN II C2117, SIZE:

36"X36"; COLOR: 733 RED BLUFFS W/ INTEGRAL COVE BASE

RF-1

MISCELLANEOUS

PNT-3:

ACCENT PAINT (LOCK HAVEN PANTONE): BENJAMIN MOORE, COLOR TO MATCH: PANTONE PMS 425, FINISH: SCUFF-X EGGSHELL

PNT-4:

DOOR FRAME PAINT: BENJAMIN MOORE, COLOR TO MATCH: PANTONE PMS 425, FINISH: SCUFF-X

SEMI-GLOSS, REFER TO FINISH PLAN FOR LOCATIONS

WS-1: USG WOOD WALL SLAT SYSTEM, REFER TO SPECIFICATIONS FOR PRODUCT TYPES

AND DRAWINGS FOR SPECIFIC LOCATIONS AND DETAILS, COLOR: S32 CP MAPLE

WG-1: VINYL WALL GRAPHICS, OWNER PROVIDED IMAGE FILES

MANUFACTURER: MOHAWK GROUP, SERIES: CREATIVE TERRAIN II C2117, SIZE:

36"X36"; COLOR: 937 ALPINE MIST W/ INTEGRAL COVE BASE

RF-2

CONSTRUCTION SPECIALTIES WALK-OFF MAT SYSTEM; STYLE: PEDITRED G4;

COLOR: AS SELECTED FROM MANUFACTURER'S FULL STANDARD LINE.

WCP-1

WCS-1:

WOOD CEILING SLAT SYSTEM: REFER TO SPECIFICATIONS FOR PRODUCT TYPES AND

SPECIFIC LOCATIONS, COLOR: S32 CP MAPLE

MB (BASIS OF DESIGN)

ELITE EXPRESSIONS, ANODIZED BLACK ALUMINUM18GA WALL BASE, SIZE: 8" STYLE: COVE BASE

INTEGRAL FLASH COVE

MOHAWK GROUP, CREATIVE TERRAIN II, SIZE: 4"HT COLOR: 937 ALPINE MIST & 733 RED

BLUFFS, TRIM: ELEMENTAL EDGES COVE STICK;

REFERENCE FINISH PLAN FOR FLOORING TRANSITIONS

1. CONTRACTORS SHALL FIELD VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO FABRICATION AND/OR COMMENCEMENT

OF WORK AND SHALL IMMEDIATELY REPORT ANY DISCREPANCIES TO THE ARCHITECT.

2. ALL FINISHES, COLORS AND FINAL PRODUCT SELECTIONS TO BE VERIFIED WITH OWNER.

3. PATCH AND REPAIR ANY FINISHES DISTURBED DURING CONSTRUCTION.

4. PAINT COLOR SELECTIONS WILL BE CONFIRMED DURING THE SUBMITTALS PROCESS WITH DRAWDOWNS.

5. ALL COLORS TO BE CONFIRMED DURING THE SUBMITTAL PROCESS.

GENERAL

1. REFER TO CODE REVIEW DRAWING A0.1 FOR FLAME SPREAD RATINGS FOR INTERIOR FINISHES.

2. STARTING OF FINISH WORK SHALL INDICATE APPLICATORS ACCEPTANCE OF SUBSTRATE.

3. ENSURE ALL SURFACES TO RECEIVE FINISH ARE CLEAN, TRUE AND FREE OF IRREGULARITIES. DO NOT PROCEED WITH WORK

UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED.

4. UPON RECEIPT FROM MANUFACTURER, THE INSTALLER SHALL INSPECT ALL MATERIALS FOR DEFECTS, SHIPPING DAMAGE, FLAWS, CORRECT COLOR, AND PATTERN. DAMAGED OR INCORRECT MATERIALS SHALL BE SENT BACK TO THE MANUFACTURER

FOR IMMEDIATE REPLACEMENT.

5. WHERE TWO FLOOR FINISHES MEET AT A DOORWAY, THE TRANSITION MUST OCCUR ON THE CENTER LINE OF THE DOOR IN ITS

CLOSED POSITION.

6. EXTEND FLOOR FINISH UNDER OPEN-BOTTOM AND RAISED BOTTOM OBSTRUCTIONS. EXTEND FINISH INTO CLOSETS AND

ALCOVE AREAS INDICATED UNLESS ANOTHER FINISH IS INDICATED FOR THAT AREA.

7. APPLY RUBBER BASE WHERE SCHEDULED TO WALLS, COLUMNS AND OTHER PERMANENT FIXTURES IN ROOMS OR AREAS WHERE SPECIFIED. INSTALL BASE IN AS LONG LENGTHS AS PRACTICABLE. TIGHTLY BOND BASE TO BACKING THROUGHOUT THE LENGTH AND HEIGHT OF EACH PIECE, WITH CONTINUOUS CONTACT AT VERTICAL AND HORIZONTAL SURFACES. ALL RUBBER

CORNERS TO BE PRE-MOLDED.

8. AFTER COMPLETION OF WORK AND JUST PRIOR TO THE FINAL INSPECTION OF WORK, THOROUGHLY CLEAN FLOORS AND

ACCESSORIES.

9. PRIOR TO OCCUPANCY, THE CONTRACTOR SHALL CLEAN ALL MATERIALS OF DUST, DEBRIS, LOOSE CONSTRUCTION MATERIALS

AND EQUIPMENT.

FINISH

PAINT NOTES

1. ALL PAINT TO BE APPLIED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. SAND LIGHTLY BETWEEN COATS TO ACHIEVE REQUIRED FINISH. ALLOW EACH COAT OF FINISH TO DRY BEFORE THE FOLLOWING COAT IS APPLIED, UNLESS DIRECTED OTHERWISE BY MANUFACTURER. FILL KNICKS, GOUGES AND OTHER IMPERFECTIONS OF SURFACES WITH LATEX FILLER AND SAND SMOOTH UNTIL FLUSH WITH SURFACE.

2. MATERIALS TO ARRIVE AT JOBSITE IN ORIGINAL, NEW, UNOPENED CONTAINERS BEARING THE MANUFACTURER'S NAME, TRADE NAME AND LABEL ANALYSIS. STORE ON SITE IN STRICT ACCORDANCE WITH

MANUFACTURER'S INSTRUCTIONS.

3. ALL PAINTING TO BE DONE UNDER FINAL LIGHTING CONDITIONS.

4. FINISHED PAINTED SURFACES SHALL BE OF UNIFORM COLOR, APPEARANCE AND FINISH WITHOUT DRIPS, RUNS OR SMUDGES.

5. WHERE GRILLES OR DIFFUSERS OCCUR IN CEILING OR WALL, CONFIRM WITH PROFESSIONAL PRIOR TO

PAINTING TO MATCH EXISTING ADJACENT SURFACES.

6. REMOVE OR OTHERWISE PROTECT FINISH HARDWARE, ACCESSORIES, PLATES, LIGHTING FIXTURES AND

SIMILAR ITEMS BEFORE PAINTING.

7. DO NOT PAINT ANY MOVING PARTS OR OPERATION UNITS, CODE-REQUIRED LABELS AND EQUIPMENT

IDENTIFICATIONS.

8. PAINT AREAS BEHIND MOVEABLE SURFACE (E.G. INSIDE CABINETS AND BACKS OF ACCESS PANELS).

COORDINATE WITH ARCHITECT PRIOR TO START OF WORK.

9. REPAINT OR REFINISH PAINTED SURFACES DAMAGED BY SUBSEQUENT WORK.

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:2

P

M

CONSTRUCTION

A8.1

FINISH FLOOR PLAN

1/4" = 1'-0"A8.1

1 FINISH FLOOR PLAN

ROOM FINISH SCHEDULE

NUMBER NAME

FLOOR

FINISH BASE

WALL FINISH

Ceiling Finish COMMENTSN E S W

G53 CLASSROOM 01 CPT-1 RB PNT-1 PNT-1/PNT-2 PNT-1 PNT-1 ACT

G54 CLASSROOM 02 CPT-1 RB PNT-1 PNT-1/PNT-2 PNT-1 PNT-1 ACT

S01 VESTIBULE WCP-1 RB EXIST EXIST EXIST EXIST ACT

S02 LOBBY RF-1/RF-2 INTEGRAL/MB PNT-1/PNT-2 PNT-1/WS-1 PNT-1/PNT-2 PNT-1 ACT/WCS-1

S05 PODCAST SPACE CPT-2 RB-1 PNT-2 PNT-1/WS-1 PNT-1 PNT-1 ACT

S12 IT CLOSET CPT-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT

S-C1 CORRIDOR RF-1 INTEGRAL PNT-1 PNT-1 PNT-1/PNT-2/PNT-3 PNT-1 ACT

0 8' 12' 16'4' N

S

E

W

PLAN

NORTH

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

11'-5 1/4" 5'-11 3/4"7'-10 1/8"

GLASS

STOREFRONT

SYSTEM

USG WOOD

SLAT WALL

SYSTEM (WS-1),

REFER TO FINISH

LEGEND

DONOR SIGNAGE;

FONT TYPE:

FRANKLIN GOTHIC

FINISH:

BRUSHED ALUMINUM

LOBBYS02

A8.3

A8.3

3' - 9 3/4"3' - 9 3/4"3' - 9 3/4" 1'

8" 5'

3/ 4"

1'

6"

3' - 0"3' - 0"

1'

6" 5'

3/ 4"

8" 8"

8" HT. METAL BASE

TO MATCH STOREFRONT

FINISH

4" 6"

2"

1'

8" 2"

4"

1/ 4"

1/

2"

VINYL WALL

GRAPHIC WRAP, OWNER

TO PROVIDE IMAGE;

WALL GRAPHIC TO CONCEAL

ELEC.

PANEL DOOR,

CUT THE VINYL

AT ALL DOOR SEAMS

TO KEEP OPERABLE

ELEC. PANEL;

VERIFY EXACT

LOCATION IN

FIELD

INTEGRAL BASE

LOBBYS02

ETR

75" DISPLAYS.

FINAL PLACEMENT

W/ OWNER, TYP.

INTEGRAL BASE

LASER CUT

LOGO; OWNER

TO PROVIDE

ARTWORK AND

FINAL SIZE

PAINT FACE AND SIDES

OF PILASTER (PNT-2)

LOBBYS02

WS-1

7' - 0 3/4"

8'

1/

2"

WS-1

7' - 0 3/4"

+/- 3' - 8"

- 3

PNT-1

PAINT FACE

AND SIDES

OF PILASTER

(PNT-2)

PNT-1 PNT-1PNT-1

75" DISPLAY. FINAL PLACEMENT W/ OWNER, TYP.

TALL PLAM CABINET 27"X90"X18", ADJUSTABLE SHELVING

PODCAST SPACES05

2"

A8.3

A8.3

RUBBER BASE

75" DISPLAY. FINAL PLACEMENT

W/ OWNER, TYP.

WS-1

8'-2 1/4"

WS-1

8'-2 1/4"

RUBBER BASE

PODCAST SPACES05

A6.1PNT-1

E.T.R

GLASS

STOREFRONT

SYSTEM

RUBBER BASE

PODCAST SPACES05

2"

3' - 0" 3' - 0"1'

6" 5'

3/ 4"

1'

6"

(34) 16"X20"

PLAQUES

INTEGRAL BASEPN

T-

2'

-6

PN

T-

2'

-0

PN

T-

PN

T-

1' -0

COORDINATE SIGNAGE W/ OWNER

PAINT FACE AND SIDES

OF PILASTER (PNT-2)

CORRIDORS-C1

PAINT FACE AND SIDES

OF PILASTER (PNT-2)

INSTALL PICTURE RAIL,

(2) 6'-6" STD. LENGTH AND CUT

(3) 4'10" LENGTHS AS SHOWN, TWO

CLIPS PER CABLE;

REF. DETAIL (7)

TO

P

O F

PI

C

TU

R

E R

AI

L

A.

F.

F.

7'

3"

1/

4"

ORIGINAL GALLERY SYSTEM

TRACK

FINISH: PRE-PAINTED WHITE

INCLUDE END CAPS, FINISH:

WHITE

STEEL CABLE HANGERS

PUSHBUTTON SECURITY

HOOK; PROVIDE (2) PER

STEEL CABLE, REF.

ELEVATION 4

GWB

3/4"

STEEL CABLE

CLASSROOM 02G54

75" DISPLAYS. FINAL PLACEMENT

W/ OWNER, TYP.

E.T.R E.T.R

RUBBER BASE

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:2

P

M

CONSTRUCTION

A8.2

INTERIOR

ELEVATIONS

1/2" = 1'-0"A8.2

2 INTERIOR ELEVATION

1/2" = 1'-0"A8.2

3 INTERIOR ELEVATION

1/2" = 1'-0"A8.2

1 INTERIOR ELEVATION OF SEATING AREA

1/2" = 1'-0"A8.2

5 INTERIOR ELEVATION

1/2" = 1'-0"A8.2

6 INTERIOR ELEVATION

1/2" = 1'-0"A8.2

8 INTERIOR ELEVATION

1/2" = 1'-0"A8.2

4 INTERIOR ELEVATION OF PLAQUE WALL

1/2" = 1'-0"A8.2

9 INTERIOR ELEVATION

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

IO

N

12" = 1'-0"A8.2

7 PICTURE RAIL DETAIL

STREET LEVEL

-14' - 0"

ACOUSTICAL INSULATION

TO METAL DECK

SHIM AS REQ'D

8", 20 GA DBL. HEADER STUDS

5/8" GWB

ALUMINUM GLASS

STOREFRONT WALL

1/

2"

SOUND INSULATION

3 5/8" MTL. STUD

5/8 GWB

LOBBY

S02

PODCAST

SPACE

S05

8" MTL BASE,

SEE FINISH

LEGEND

8"

8" MTL BASE,

SEE FINISH

LEGEND

1095 SF

LOBBY

S02

ACOUSTICAL INSULATION

TO METAL DECK

5/8" GWB

SOUND INSULATION

3 5/8" MTL. STUD

USG PLANX UNIVERSAL

CARRIER COMPONENT

SECURED TO FRAMING

W/ FASTENER

USG PLANX UNIVERSAL

INTEGRAL REVEAL

PANEL FIELD CUT TO

FIT

FASTENER TO BE

INSTALLED EVERY 9"

O.C. TYP.

DONOR SIGNAGE. SEE

INT ELEVATIONS FOR

DETAILS

A

SHEET TITLE:

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

5:

:3

P

M

CONSTRUCTION

A8.3

INTERIOR DETAILS

1 1/2" = 1'-0"A8.3

1 CURTAIN WALL DETAIL

1 1/2" = 1'-0"A8.3

2 WOOD WALL PANEL DETAIL

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

N

.0

3.

C

O N

S T

R U

C T

GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

27.

28.

29.

30.

31.

32.

33.

34.

35.

36.

37.

38.

39.

40.

41.

COORDINATE ALL EQUIPMENT AND DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS.

COORDINATE ALL PENETRATIONS THROUGH EXTERIOR WALLS WITH ARCHITECTURAL DRAWINGS.

THE CONTRACTOR SHALL CHECK AND VERIFY ALL CONDITIONS AND DIMENSIONS AT THE SITE BEFORE PROCEEDING WITH THE WORK. THEY SHALL REPORT ANY DISCREPANCIES TO THE ARCHITECT/ENGINEER FOR CORRECTION PRIOR TO BEGINNING ANY WORK. DISCOVERY OF ANY DISCREPANCIES AFTER WORK

HAS COMMENCED SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

DO NOT SCALE THESE DRAWING FOR EXACT DIMENSIONS, VERIFY ALL FIGURES, CONDITIONS,

DIMENSIONS, ETC. AT THE JOB SITE.

THE HVAC CONTRACTOR SHALL CENTER AND/OR ALIGN REGISTERS, DIFFUSERS, AND EQUIPMENT WITH

ADJACENT ARCHITECTURAL FEATURES. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS.

DUCT DIMENSIONS INDICATED ARE CLEAR INSIDE DIMENSIONS.

ALL ROOF CURBS FOR MECHANICAL EQUIPMENT SHALL BE FURNISHED, INSTALLED AND FLASHED BY THE HVAC CONTRACTOR. THE HVAC CONTRACTOR IS RESPONSIBLE FOR ALL HVAC RELATED ROOF WORK, INCLUDING CUTTING AND PATCHING. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR

MAINTAINING THE ROOF WARRANTY.

HVAC CONTRACTOR SHALL REVIEW THE EQUIPMENT SCHEDULES, SPECIFICATIONS, AND DRAWINGS IN ALL CONTRACT DOCUMENTS AND SUBSEQUENT SHOP DRAWINGS AND PROVIDE ALL LABOR AND MATERIAL FOR A COMPLETE AND OPERABLE SYSTEM. FAILURE TO REVIEW THESE DOCUMENTS DOES NOT RELIEVE

THE CONTRACTOR OF FULFILLING THEIR CONTRACTUAL OBLIGATIONS.

REFER TO ARCHITECTURAL DRAWINGS AND SHOP DRAWINGS FOR FINAL CONNECTIONS AND EXACT

LOCATIONS FOR ALL WORK REQUIRED FOR EQUIPMENT NOT FURNISHED UNDER THIS CONTRACT.

COORDINATE INSTALLATION OF NEW WORK WITH ARCHITECTURAL, STRUCTURAL, PLUMBING, POWER AND LIGHTING PLANS. CONTRACTOR SHALL TAKE ALL INTERFERENCE INTO CONSIDERATION. PROVIDE ALL NECESSARY OFFSETS OR TRANSITIONS WITH EQUIVALENT AREAS TO MATCH DUCT SIZES AS INDICATED

ON DRAWINGS.

DO NOT INSTALL ANY MECHANICAL WORK ABOVE OR THROUGH ELECTRICAL ROOMS UNLESS

SPECIFICALLY SERVING THE ELECTRICAL ROOM. DO NOT INSTALL ANY MECHANICAL WORK ABOVE

ELECTRICAL PANELS.

DO NOT INSTALL ANY MECHANICAL WORK ABOVE OR THROUGH ELEVATOR EQUIPMENT ROOMS UNLESS

SPECIFICALLY SERVING EQUIPMENT ROOM.

DO NOT INSTALL ANY MECHANICAL WORK ABOVE OR THROUGH TELECOMMUNICATIONS EQUIPMENT

ROOMS UNLESS SPECIFICALLY SERVING THE TELECOMMUNICATIONS ROOM.

LOCATE ALL EQUIPMENT THAT MUST BE SERVICED, OPERATED, OR MAINTAINED IN FULLY ACCESSIBLE POSITIONS. EQUIPMENT SHALL INCLUDE, VAV BOXES, COILS, VALVES, MOTORS, FANS, CONTROLLERS, DRAIN POINTS, TRAPS, STRAINERS, ETC. THE CONTRACTOR WILL BE REQUIRED TO RE-WORK, AT THEIR

EXPENSE, ANY EQUIPMENT THAT IS DEEMED INACCESSIBLE BY THE OWNER.

THE MOUNTING HEIGHT OF ALL THERMOSTATS, ROOM TEMPERATURE SENSORS, AND/OR HUMIDITY SENSORS, SHALL MATCH THE MOUNTING HEIGHT OF ELECTRICAL LIGHT SWITCHES OR, IN THE ABSENCE

OF NEARBY SWITCHES, BE MOUNTED 44" ABOVE FINISHED FLOOR.

FOR ALL BRANCH DUCT CONNECTIONS TO MAIN TRUNK, PROVIDE 45° TRANSITION FITTING OR CONICAL TAP FOR ROUND DUCT. BUTT FITTINGS ARE NOT PERMITTED. PROVIDE MANUAL VOLUME DAMPER WITH

LOCKING QUADRANT AN ALL BRANCH RUNOUTS TO GRILLES AND DIFFUSERS.

PROVIDE TURNING VANES IN ALL MITERED ELBOWS OR PROVIDE ELBOWS WITH CENTERLINE RADIUS

EQUAL TO 1.5 TIMES DUCT WIDTH.

INSTALL ALL FIRE DAMPERS AND CEILING RADIATION DAMPERS IN STRICT ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATION. PROVIDE UL FIRE DAMPERS WITH BLADES OUT OF AIR STREAM AND ACCESS DOORS. FIRE DAMPERS IN TRANSFER DUCTS ONLY MAY HAVE BLADES IN AIR STREAM.

SLEEVE AND SEAL ALL PIPE OR DUCT PENETRATIONS OF WALL AND FLOORS. PACK VOID BETWEEN PIPE OR DUCT AND SLEEVE WITH INSULATION IN NON-RATED WALLS AND FLOORS. PACK VOID BETWEEN PIPE OR DUCT AND SLEEVE WITH INSULATION IN FIRE-RATED WALLS AND FLOORS, APPLY INTUMESCENT FIRE SAFING COMPOUND AT PENETRATION, MAINTAINING INTEGRITY AND RATING OF FIRE SEPARATION.

SLEEVES THROUGH FLOORS SHALL EXTEND 2" ABOVE FLOOR AND BE GROUTED INTO PLACE AND

WATERPROOFED. PIPING THROUGH EXTERIOR WALLS SHALL BE SLEEVED AND SEALED WEATHER TIGHT.

THE OWNER SHALL HAVE THE OPTION TO RETAIN ANY EQUIPMENT, CONTROLS, PIPING, DUCTWORK, AND

ACCESSORIES SCHEDULED TO BE REMOVED.

SHUTDOWN OF SERVICES SHALL BE COORDINATED AND SCHEDULED WITH THE OWNER.

DUCTWORK AND PIPING THAT REMAIN AFTER DEMOLITION IS COMPLETE, SHALL BE CAPPED AT THE MAIN (IF THEY ARE TO BE TAKEN OUT OF SERVICE), OR PREPARED FOR RECONNECTION (IF THEY ARE

TO BE REUSED).

ALL ABANDONED SYSTEMS AND EQUIPMENT WITHIN THE PROJECT AREA SHALL BE REMOVED.

COORDINATE REMOVAL WITH THE OWNER AND OTHER TRADES.

CEILINGS THAT NEED TO BE TEMPORARILY REMOVED TO ALLOW FOR THE INSTALLATION OF DUCTWORK, PIPING, OR EQUIPMENT SHALL BE REMOVED AND REPLACED BY HVAC CONTRACTOR. ALL FIRE

PROTECTION, ELECTRICAL, MEDICAL GAS, AND SERVICES SHALL ALSO BE INCLUDED.

THE HVAC CONTRACTOR SHALL DISCONNECT AND CAP ALL SUPPLY, RETURN, AND EXHAUST AIR OUTLETS

THAT ARE STILL ACTIVE IN THE PROJECT AREA DURING CONSTRUCTION.

THE HVAC CONTRACTOR SHALL REFER TO THE PHASING PLAN TO DETERMINE THE EXTENT OF WORK AND

TEMPORARY SYSTEM CONNECTIONS NECESSARY FOR EACH PHASE.

ALL DUCT AND UNIT MOUNTED SMOKE DETECTORS FOR MECHANICAL EQUIPMENT AND DAMPERS SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR, WIRED TO FIRE

ALARM SYSTEM BY ELECTRICAL CONTRACTOR, WITH UNIT SHUTDOWN CONTROL WIRING BY THE

MECHANICAL CONTRACTOR.

HVAC CONTRACTOR SHALL PROVIDE ALL TRANSFORMERS AS REQUIRED FOR DUCT-MOUNTED DAMPER

ACTUATORS OR THE DDC CONTROLS SYSTEM.

ALL WORK SHALL BE SCHEDULED AND COORDINATED WITH THE OWNER SO THAT DISRUPTION OF AREAS

INVOLVED IS KEPT TO A MINIMUM. ANY ACCIDENTAL INTERRUPTIONS TO SERVICES SHALL BE

REPAIRED IMMEDIATELY BY THE CONTRACTOR WITH OUT ANY ADDITIONAL COST TO THE OWNER.

PRIOR TO SUBMITTING BIDS AND DURING CONSTRUCTION, THE CONTRACTOR SHALL EXAMINE THE DRAWINGS OF ALL TRADES AND COORDINATE THE INSTALLATION WITH ALL TRADES AND EXISTING CONDITIONS. COORDINATION OF WORK IF NECESSARY SHALL BE PROVIDED AT NO ADDITIONAL COST

TO THE OWNER.

THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT INDICATE ALL OFFSETS, BENDS, ACCESS PANELS, AND SIMILAR PARTS WHICH MAY BE REQUIRED. THE CONTRACTOR SHALL INVESTIGATE THE STRUCTURAL AND FINISH CONDITIONS AFFECTING HIS WORK AND PROVIDE ALL FITTINGS, ACCESS PANELS, AND SIMILAR ACCESSORIES THAT MAYBE REQUIRED TO PROVIDE A COMPLETE AND OPERATING INSTALLATION AT NO

ADDITIONAL COST TO THE OWNER.

INSTALL ROOFTOP EQUIPMENT NOT LESS THAN 10 FEET FROM THE ROOF EDGE OR ANY CHANGE IN ROOF HEIGHT GREATER THAN 2 FEET. WHERE EQUIPMENT MUST BE PLACED WITHIN PARAMETERS LISTED, ARCHITECT MUST PROVIDE A RAIL OR PARAPET ALONG ROOF EDGE IN QUESTION.

PROVIDE 4" THICK CONCRETE PADS FOR EQUIPMENT INSTALLED ON FLOORS OR ON GRADE, 6" LARGER

THAN THE EQUIPMENT ON ALL SIDES.

INSTALL FLEXIBLE DUCTWORK IN A FULLY EXTENDED CONDITION WITHOUT SAGS AND KINKS.

PROVIDE ALL DAMPERS, SHEAVES, AND BELTS AS REQUIRED FOR BALANCING.

THIS CONTRACTOR IS RESPONSIBLE FOR THE CUTTING AND PATCHING OF ALL OPENINGS RELATED TO THEIR WORK. PATCHES SHALL MATCH SURROUNDING WALL AND CEILING SURFACES AND SHALL BE SEALED

AND FIRESTOPPED AS REQUIRED.

INSTALL FIRE DAMPERS AS REQUIRED PER NFPA 101 AND NFPA 90A, (2012 EDITION).

ALL HVAC INSTALLATIONS SHALL COMPLY WITH NFPA 101.

PER NFPA25, SPRINKLER PIPING SHALL NOT BE SUBJECTED TO EXTERNAL LOADS BY MATERIALS EITHER RESTING ON THE PIPE OR HUNG FROM THE PIPE. NO CABLING, SYSTEMS, EQUIPMENT OR ACCESSORIES SHALL BE IN CONTACT WITH SPRINKLER SYSTEM. RELOCATE AND/OR RESUPPORT SYSTEM AS REQUIRED

SO THEY ARE NOT IN CONTACT WITH SPRINKLER PIPING.

10' MINIMUM CLEARANCE BETWEEN ALL OUTSIDE AIR INTAKES, EXHAUSTS AND PLUMBING VENTS. 25'

MINIMUM FOR HEALTHCARE UNLESS NOTED OTHERWISE.

M.C. SHALL PROVIDE CEILING IDENTIFICATION LABELS AT ALL LOCATIONS WHERE SERVICEABLE MECHANICAL EQUIPMENT, DEVICES, VALVES, DAMPERS, CONTROLS, AND SIMILAR COMPONENTS ARE LOCATED ABOVE ACCESSIBLE CEILINGS. LABELS SHALL BE INSTALLED ON THE CEILING GRID OR ACCESS PANEL DIRECTLY BELOW THE ASSOCIATED EQUIPMENT AND SHALL BE IN ACCORDANCE WITH

OWNER LABELING STANDARDS.

ABBREVIATIONS

BALL

BUTTERFLY

GATE

GATE, ANGLE

GLOBE

GLOBE, ANGLE

PLUG

THREE WAY

LEVER

NON-RISING STEM

OUTSIDE STEM & YOKE

GEAR

ELECTRIC, SOLENOID

PNEUMATIC, MOTORM

S

CHECK

NEEDLE

PRESSURE REDUCING

QUICK OPENING

QUICK CLOSING, FUSIBLE LINK

RELIEF (R) OR SAFETY (S)

VALVES FOR SELECTIVE ACTUATORS

VALVE ACTUATORS

SPECIAL DUTY VALVES

HOSE END DRAIN VALVE

R

PIPING SYMBOLS

FLOWMETER, ORIFICE

OFM-1

FLOWMETER, VENTURI

VFM-1

FLOW SWITCHFS

PRESSURE GAUGE, WITH COCKPI

PRESSURE SWITCHPS

PRESSURE GAUGE, COMPOUND

PI

STEAM TRAP, FLOAT AND THERMOSTATIC

THERMOMETER

STRAINER

STRAINER, BLOW OFF

THERMOMETER WELL

TEST PLUG

BALANCING VALVE

G

TRIPLE DUTY

FLOWMETER, ULTRASONIC STRAP-ON

UFM-1

SPECIALTIES (CONT)

TAGS

HEATING COIL

ROOFTOP UNIT

AIR HANDLING UNIT

FAN COIL UNIT

RADIANT CEILING PANEL

ENERGY RECOVERY UNIT

EXHAUST FAN

CONDENSING UNIT

BOILER

PUMP

EXPANSION TANK

NOTE: THIS IS A GENERAL MECHANICAL

LEGEND. ALL SYMBOLS MAY NOT APPEAR

ON THE PLANS. SEE PLANS FOR ACTUAL

SYMBOLS USED.

AUTOMATIC TEMPERATURE CONTROL PANEL

EXISTING PIPINGNAME(EX)

12x20(EX) 12x20(EX)

EXISTING CEILING SUPPLY DIFFUSER/

GRILLE/REGISTER

EXISTING CEILING RETURN

GRILLE/REGISTER

VAV TERMINAL BOX

FIRE DAMPER

TEMPERATURE SENSOR

VOLUME DAMPER

DETAIL #/DRAWING NUMBER

DIFFUSER/GRILLE/REGISTER DESIGNATION AND

FLOW RATE IN CFM

ROOM THERMOSTAT

ACOUSTICALLY LINED DUCT

FLEXIBLE DUCT (INSULATED)

DUCT SYMBOLS

M1

GENERAL

POINT OF CONNECTION TO EXISTING

POINT OF DISCONNECTION

EQUIPMENT IDENTIFICATION TAG

BACKDRAFT DAMPER

DUCT, FIRST FIGURE IS

PLAN DIMENSION

CARBON DIOXIDE SENSOR

(ROOM & DUCT MOUNTED)

ROOM PRESSURE SENSOR/

TRANSMITTER

PIPING SYMBOLS

HIGH-PRESSURE STEAM

MEDIUM-PRESSURE STEAM

LOW-PRESSURE STEAM

HEATING

HIGH-PRESSURE CONDENSATE

MEDIUM-PRESSURE CONDENSATE

LOW-PRESSURE CONDENSATE

BOILER BLOWDOWN

PUMPED CONDENSATE

VACUUM PUMP DISCHARGE

MAKEUP WATER

ATMOSPHERIC VENT

HOT WATER SUPPLY

HOT WATER RETURN

COMPRESSED AIR

PIPE TO BE REMOVED

HPS

MPS

LPS

HPC

MPC

LPC

BBD

PC

VPD

MU

ATV

HWS

HWR

A

NAME

AIR CONDITIONING AND REFRIGERATION

REFRIGERANT SUCTIONRS

REFRIGERANT LIQUIDRL

CONDENSER WATER SUPPLYCWS

CONDENSER WATER RETURNCWR

CHWS CHILLED WATER SUPPLY

CHWR CHILLED WATER RETURN

FILL FILL

HUMIDIFICATION LINEH

DRAIND

HEAT PUMP WATER SUPPLYHPWS

HEAT PUMP WATER RETURNHPWR

GENERAL

FITTINGS

PIPE ELBOW UP

PIPE ELBOW DOWN

PIPE TEE DOWN

PIPE TEE UP

UNION

FLANGE

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC

STRAIGHT INVERT

REDUCER, ECCENTRIC

STRAIGHT CROWN

SPECIALTIES

AIR VENT, AUTOMATICAV

AIR VENT, MANUAL

MV

ALIGNMENT GUIDE

ANCHOR

EXPANSION JOINT

EXPANSION LOOP

FLEXIBLE CONNECTOR

EJ-1

EL-1

CAP

COMBINATION FIRE

AND SMOKE DAMPER

SMOKE DAMPER

BDDBDD

12x20 12x20

AD

AD

FLEXIBLE CONNECTION

CEILING SUPPLY DIFFUSER/GRILLE/REGISTER

LINEAR WALL SUPPLY DIFFUSER/

GRILLE/REGISTER WITH PLENUM

LINEAR CEILING SUPPLY DIFFUSER/

GRILLE/REGISTER WITH PLENUM

CEILING RETURN

GRILLE/REGISTER

WALL SUPPLY DIFFUSER/

GRILLE/REGISTER

LINEAR WALL RETURN/EXHAUST

GRILLE/REGISTER WITH PLENUM

LINEAR CEILING RETURN/EXHAUST

GRILLE/REGISTER WITH PLENUM

WALL RETURN/EXHAUST

GRILLE/REGISTER

OUTDOOR AIR LOUVER

EXHAUST AIR LOUVER

WALL TRANSFER GRILLE

ARROW INDICATING FLUID

FLOW DIRECTION

GENERAL

DAMPERS

DIFFUSERS/GRILLES/REGISTERS

EQUIPMENT

EXISTING DUCT

DUCT TO BE REMOVED12x20 12x20

SENSORS

DEMOLITION KEY NOTE

AIRFLOW MEASURING STATION

DUCT SYMBOLS

DUCT SMOKE DETECTOR

PIPE RISER, UP & DN

RECTANGULAR DUCT RISER, UP & DN,

SUPPLY OR OUTDOOR AIR

RECTANGULAR DUCT RISER, UP & DN,

RETURN OR EXHAUST AIR

RECTANGULAR DUCT ELBOW UP,

SUPPLY OR OUTDOOR AIR

RECTANGULAR DUCT ELBOW UP,

RETURN OR EXHAUST AIR

RECTANGULAR DUCT ELBOW DN,

SUPPLY OR OUTDOOR AIR

RECTANGULAR DUCT ELBOW DN,

RETURN OR EXHAUST AIR

RECTANGULAR DUCT TEE UP,

SUPPLY OR OUTDOOR AIR

RECTANGULAR DUCT TEE UP,

RETURN AIR

RECTANGULAR DUCT TEE DN,

SUPPLY OR OUTDOOR AIR

RECTANGULAR DUCT TEE DN,

RETURN AIR

ROUND DUCT RISER, UP & DN

ROUND DUCT ELBOW UP

ROUND DUCT ELBOW DN

ROUND DUCT TEE UP

ROUND DUCT TEE DN

REVISION TAG

AD - ACCESS DOOR

AP - ACCESS PANEL

AD

MOTORIZED DAMPER

BLANKOFF INDICATING NO AIR THROW

TO THIS SIDE

CONDENSATE DRAINCD

M M

(A)240

ROOM HUMIDISTAT

EXISTING DIFFUSER/GRILLE/REGISTER

DESIGNATION AND FLOW RATE IN CFM

(EX)240

D

R

INCLINED RISE, IN DIRECTION

OF AIR FLOW

INCLINED DROP, IN DIRECTION

OF AIR FLOW

D

R

HUMIDITY SENSOR

C02 C02

AFS

S

FD

FSD

SD

HC

HC

RTU

AHU

FC

RCP

ERU

EF

CU

B

P

ET

ATC

VAV

VAV BOX

AIR CONDITIONER

AC

DEDICATED OUTDOOR AIR SYSTEM

DOAS

CABINET UNIT HEATER

CUH

DUCT HEATER

DH

HUMIDIFIER

H

LOUVER

L

VRF

VARIABLE REFRIGERANT FLOW

FD

FSD

SD

RECTANGULAR DUCT TEE UP,

EXHAUST AIR

RECTANGULAR DUCT TEE DN,

EXHAUST AIR

KEY NOTE1

EXISTING CEILING EXHAUST

GRILLE/REGISTER

CEILING EXHAUST

GRILLE/REGISTER

T

H

P

T

H

A COMPRESSED AIR

AC AIR CONDITIONING

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

ADP APPARATUS DEW POINT

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AIR COND AIR CONDITION(-ING, -ED)

AMP AMPS AMPERE(S)

APPROX APPROXIMATE

ATC AUTOMATIC TEMPERATURE CONTROL

ATM ATMOSPHERE

ATV ATMOSPHERIC VENT DUCT DIMENSIONS

(INDICATED ARE CLEAR INSIDE

DIMENSIONS)

AVG AVERAGE

B BOILER

BBD BOILER BLOWDOWN

BDD BACKDRAFT DAMPER

BHP BRAKE HORSEPOWER

BMS BUILDING MANAGEMENT SYSTEM

BTU BRITISH THERMAL UNIT

BTUH BTU PER HOUR

CAV CONSTANT AIR VOLUME

CC COOLING COIL

CCW COUNTERCLOCKWISE

CFM CUBIC FEET PER MINUTE

CH CHILLER

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CLG CEILING

CMPR COMPRESSOR

CMU CONCRETE MASONRY UNIT

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

COND CONDENS(-ER, -ING, -ATION)

CONT. CONTINU(-ED, -ATION)

CORR CORRIDOR

CP CONDENSATE PUMP

CT COOLING TOWER

CU CONDENSING UNIT

CU FT CUBIC FEET

CU IN CUBIC INCH

CUH CABINET UNIT HEATER

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

D DRAIN

dB DECIBEL

DB DRY-BULB TEMPERATURE

DEG OR ° DEGREE FAHRENHEIT (°F)

DIA OR ∅ DIAMETER DIM DIMENSION

DN DOWN

DPT DEW-POINT TEMPERATURE

DWG DRAWING

DX DIRECT EXPANSION

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE (°F)

E.C. ELECTRICAL CONTRACTOR

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

EL ELEVATION

ENT ENTERING

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EVAP EVAPORAT(-E, -ING, -ED, -OR)

EWT ENTERING WATER TEMPERATURE (°F)

EX OR EXIST EXISTING

F FAHRENHEIT

FA FACE AREA

FCU FAN COIL UNIT

FD FIRE DAMPER

FP FIRE PROTECTION

FPM FEET PER MINUTE

FPS FEET PER SECOND

FR FINNED RADIATION

FT FEET

FVEL FACE VELOCITY

G GRAINS

GA GAUGE OR GAGE

GAL GALLON

G.C. GENERAL CONTRACTOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GRD GRILLES, REGISTERS, DIFFUSERS

H HUMIDIFICATION

HC HEATING COIL

HD HEAD

HG MERCURY

HGT HEIGHT

HP HORSEPOWER

HPC HIGH PERSSURE CONDENSATE

HPS HIGH PRESSURE STEAM

HPWR HEAT PUMP WATER RETURN

HPWS HEAT PUMP WATER SUPPLY

HR HOUR (S)

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

HX HEAT EXCHANGER

HZ HERTZ

ID INSIDE DIAMETER

IN INCH(ES)

KW KILOWATTS

L LOUVER

LAT LEAVING AIR TEMPERATURE (°F)

LBS POUNDS

LF LINEAR FEET

LG LENGTH

LPC LOW-PRESSURE CONDENSATE

LPS LOW-PRESSURE STEAM

LWT LEAVING WATER TEMPERATURE (°F)

MAU MAKEUP AIR UNIT

MAX MAXIMUM

MBH 1000 BTUH

M.C. MECHANICAL CONTRACTOR

MIN MINIMUM

MPC MEDIUM-PRESSURE CONDENSATE

MPS MEDIUM-PRESSURE STEAM

MU MAKEUP WATER

N C NORMALLY CLOSED

N I C NOT IN CONTRACT

N O NORMALLY OPEN

N/A NOT APPLICABLE

NC NOISE CRITERIA

NO NUMBER

NTS NOT TO SCALE

OA OUTSIDE AIR

OAT OUTSIDE AIR TEMPERATURE

OD OUTSIDE DIAMETER

OZ OUNCE

P PUMP

P.C. PLUMBING CONTRACTOR

PC PUMPED CONDENSATE

PD PRESSURE DROP

PH PHASE

PPM PARTS PER MILLION

PRESS PRESSURE

PSI POUNDS PER SQUARE INCH

RA RETURN AIR

RAD RADIAT(-E, -OR)

RB RETURN BEND

RD ROOF DRAIN

RECIRC RECIRCULATE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHP RADIANT HEATING PANEL

RL REFRIGERANT LIQUID

RO ROOF OPENING

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RTU ROOFTOP UNIT

S SECOND

SA SUPPLY AIR

SAN SANITARY

SEER SEASONAL ENERGY EFFICIENCY RATIO

SH SENSIBLE HEAT

SHG SENSIBLE HEAT GAIN

SHR SENSIBLE HEAT RATIO

SP STATIC PRESSURE (IN. WG.)

SPEC SPECIFICATION

SQ SQUARE

STD STANDARD

SUCT SUCTION

T THERMOSTAT

TD TEMPERATURE DIFFERENCE

TEMP TEMPERATURE (°F)

TH TOTAL HEAT

THKNS THICKNESS

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TV TURNING VANES

TYP TYPICAL

UC UNDERCUT

UH UNIT HEATER

V VOLT

VAC VACUUM, VACUUM AIR

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VENT VENTILATION, VENT

VFD VARIABLE FREQUENCY DRIVE

VFV VAV, WITH FAN

VOL VOLUME

VPD VACUUM PUMP DISCHARGE

W WATT

W/ WITH

WB WET BULB TEMPERATURE (°F)

WC WALL CAP

WD WIDTH

WG WATER GAGE

WMS WIRE MESH SCREEN

WT WEIGHT

W ilk es -B ar re

, P A t:

.8

.1 f:

.8

.0

N . P en ns yl va ni a

A ve w : w w w

.m ra pc .c om

A

SHEET TITLE: 11.03.2026

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

4:

:3

P

M

CONSTRUCTION

M0.0

LEGEND, NOTES AND

DRAWING SCHEDULE

26-CUP-0226-CUP-02 TPTP

MECHANICAL DRAWING LIST

Sheet Number Sheet Name

Sheet Issue Date

M0.0 LEGEND, NOTES AND DRAWING SCHEDULE 11/03/26

M1.1 STREET LEVEL FLOOR PLAN - MECHANICAL DEMOLITION 11/03/26

M2.1 STREET LEVEL FLOOR PLAN - MECHANICAL 11/03/26

IS

S

U E

D A

T E

S

IS

S U

E D

A T

E S

D A

T E

D

A T

E

D E

S C

R

IP

T

IO

N

D E

S C

R

IP

T

IO

V 3-1

VF

3-4

VF

3-5

VF

3-2

VF

3-3

VF

3-1

T

T

T

T

T

44"x14" SA W/FD UP TO RTU-3 ON ROOF 44"x12" RA W/FD UP

TO RTU-3 ON ROOF

10"x10" EA W/FD UP

TO EF-3 ON ROOF

1 1 1

5 5

EUH

EUH

8 8

KEYED MECHANICAL DEMOLITION NOTES:

REMOVE EXISTING SUPPLY AIR DIFFUSER.

REMOVE EXISTING RETURN AIR GRILLE.

EXISTING SERIES FAN-POWERED VAV BOX SHALL REMAIN. TEST, BALANCE, AND ADJUST

PRIMARY MINIMUM, PRIMARY MAXIMUM, AND FAN AIRFLOWS TO VALUES INDICATED IN

THE SCHEDULE. VERIFY FAN, DAMPER, ELECTRIC HEATER, AIRFLOW SENSOR, FILTER, AND

CONTROLS OPERATE PROPERLY.

EXISTING BYPASS VAV BOX SHALL REMAIN. TEST, BALANCE, AND ADJUST MINIMUM AND

MAXIMUM AIRFLOWS TO VALUES INDICATED IN THE SCHEDULE. VERIFY DAMPER,

AIRFLOW SENSOR, STATIC-PRESSURE CONTROL, AND ASSOCIATED CONTROLS OPERATE

PROPERLY.

REMOVE EXISTING WIRE SCREEN AND PREPARE EXISTING DUCTWORK FOR CONNECTION

TO DUCT EXTENSION WITH SOUND ATTENUATION ELBOW.

FIELD VERIFY EXACT LOCATION OF EXISTING VF-3-3. IF LOCATED ABOVE NEW IT

CLOSET, DISCONNECT UNIT AND REMOVE ASSOCIATED DUCTWORK, SUPPORTS, AND

CONNECTIONS AS REQUIRED FOR RELOCATION. PROTECT AND RETAIN UNIT FOR

REINSTALLATION.

REMOVE EXISTING DUCTWORK AND BALANCING DAMPER BACK TO POINT OF

CONNECTION AS REQUIRED TO RELOCATE BALANCING DAMPER OUTSIDE THE AREA

ABOVE THE NEW SLAT CEILING. COORDINATE WITH NEW WORK AND PROVIDE ACCESS TO

THE RELOCATED DAMPER FOR ADJUSTMENT AND MAINTENANCE.

REMOVE EXISTING CEILING-MOUNTED ELECTRIC CABINET HEATER AND ASSOCIATED

MOUNTING HARDWARE. COORDINATE ELECTRICAL DISCONNECTION WITH ELECTRICAL

CONTRACTOR. PREPARE EXISTING CEILING OPENING AND SUPPORTS FOR

INSTALLATION OF NEW HEATER; MODIFY AS REQUIRED TO SUIT NEW UNIT.

EXISTING BYPASS VAV BOX SCHEDULE (FOR REFERENCE ONLY)

TAG SERVICE MANUFACTURER MODEL / UNIT SIZE

INLET DIA.

(IN.)

MAX

CFM

MIN CFM

INLET PD IN.

WG

NOTES

V-3-1

RTU-3 SUPPLY-TO-

RETURN BYPASS

CARRIER MODEL 35K / SIZE 12 12 2,000 420 0.03

1-5

NOTES:

1. EXISTING V-3-1 BYPASS VAV BOX SHALL REMAIN. VERIFY MODEL, INLET SIZE, DAMPER OPERATION, AIRFLOW SENSOR, AND ACCESSIBILITY IN FIELD.

2. V-3-1 SHALL MODULATE BETWEEN 420 CFM MINIMUM AND 2,000 CFM MAXIMUM TO MAINTAIN THE EXISTING RTU-3 SUPPLY-DUCT STATIC-PRESSURE SETPOINT.

3. CONTROLS CONTRACTOR SHALL VERIFY THE EXISTING STATIC-PRESSURE SENSOR LOCATION AND SETPOINT. BYPASS AIRFLOW SHALL DECREASE AS ZONE

PRIMARY-AIR DAMPERS OPEN.

4. CALCULATED BYPASS AIRFLOW AT THE REVISED VF MINIMUMS EQUALS RTU-3 SUPPLY AIRFLOW LESS THE TOTAL REVISED OCCUPIED PRIMARY-AIR MINIMUM.

INDIVIDUAL VF MAXIMUMS ARE NONCOINCIDENT. VERIFY FINAL VALUES AFTER TAB OF RTU-3 AND ALL VF BOXES.

5. TEST AND BALANCE CONTRACTOR SHALL RECORD BYPASS AIRFLOW AT FULL OPEN, DAMPER POSITION, INLET STATIC PRESSURE, AND SYSTEM STATIC PRESSURE.

SUBMIT RESULTS WITH THE FINAL TAB REPORT.

EXISTING SERIES FAN POWER VAV BOX SCHEDULE (FOR REFERENCE ONLY)

TAG SERVED SPACE MANUFACTURER MODEL / UNIT SIZE

INLET DIA.

(IN.)

EXIST.

PRIMARY MAX

CFM

REVISED REVISED

PRIMARY MAX PRIMARY MAX

CFMCFM

EXIST.

PRIMARY

MIN CFM

REVISED REVISED

PRIMARY PRIMARY

MIN CFMMIN CFM

OA AT OA AT

REVISED REVISED

MIN CFMMIN CFM

EXIST.

FAN CFM

REVISED REVISED

FAN CFMFAN CFM

FAN HP HEAT kW

HEAT

MBH

EXIST. EAT

°F

EXIST. LAT

°F

CALC. MIXED

EAT °F

CALC. LAT CALC. LAT

°F°F

POWER

NOTES

VF-3-1 MAIN ENTRY LOBBY CARRIER 45J-DDC / SIZE 06 12 1,860 1,6701,670 370 900900 301301 1,860 1,7501,750 3/4 13.0 44.37 67.0 89.0 63.8 86.786.7 208V / 3PH / 60HZ 1-6 VF-3-2 CORRIDOR CARRIER 45JN / SIZE 02 6 480 400400 205 400400 134134 480 425425 1/10 4.5 15.00 63.0 93.0 57.8 89.589.5 208V / 3PH / 60HZ 1-6 VF-3-3 PODCAST STUDIO CARRIER 45JN / SIZE 04 8 610 700700 265 380380 127127 785 735735 1/4 5.5 18.00 66.0 88.0 63.8 86.886.8 208V / 3PH / 60HZ 1-6 VF-3-4 CLASSROOM 01 CARRIER 45JN / SIZE 04 8 810 915915 350 520520 174174 810 950950 1/4 7.0 24.00 63.0 90.0 64.9 86.086.0 208V / 3PH / 60HZ 1-6 VF-3-5 CLASSROOM 02 CARRIER 45JN / SIZE 04 8 840 915915 360 520520 174174 840 950950 1/4 7.5 25.00 63.0 91.0 65.2 87.687.6 208V / 3PH / 60HZ 1-6

1. EXISTING SERIES FAN-POWERED VAV BOXES SHALL REMAIN. SCHEDULE DATA IS BASED ON EXISTING DOCUMENTS. VERIFY MODEL, INLET SIZE, ELECTRICAL DATA, HEATER CAPACITY, AND ACCESSIBILITY IN FIELD BEFORE WORK.

2. TEST AND BALANCE CONTRACTOR SHALL INSPECT EACH BOX, CLEAN OR REPLACE FILTERS, VERIFY FAN ROTATION AND OPERATION, CALIBRATE THE PRIMARY AIRFLOW SENSOR, AND SET THE REVISED PRIMARY MAXIMUM, PRIMARY MINIMUM, AND FAN AIRFLOWS SHOWN.

3. SERIES FAN SHALL OPERATE CONTINUOUSLY DURING OCCUPIED MODE. PRIMARY-AIR DAMPER SHALL MODULATE BETWEEN THE SCHEDULED MINIMUM AND MAXIMUM AIRFLOWS IN RESPONSE TO ZONE COOLING DEMAND. EXISTING ELECTRIC HEAT SHALL OPERATE IN SEQUENCE WITH THE PRIMARY DAMPER AT

MINIMUM AIRFLOW.

4. REVISED PRIMARY MINIMUMS ARE BASED ON THE 2021 IMC MULTIPLE-ZONE RECIRCULATING SYSTEM METHOD, 0.85 OCCUPANT DIVERSITY, MAXIMUM ZP NOT GREATER THAN 0.55, EV OF 0.60, AND RTU-3 MINIMUM OUTDOOR AIRFLOW OF 1,540 CFM. BALANCE AND VERIFY ACTUAL OUTDOOR AIRFLOW.

5. CALCULATED MIXED EAT IS BASED ON 55°F PRIMARY AIR AT THE REVISED PRIMARY MINIMUM MIXED WITH 72°F PLENUM RETURN AIR FOR THE BALANCE OF THE FAN AIRFLOW. CALCULATED LAT USES THE MIXED EAT, EXISTING HEATER kW, AND REVISED FAN AIRFLOW. VERIFY ACTUAL TEMPERATURES AND HEATER

STAGING DURING TAB.

6. SUBMIT A FINAL TAB REPORT LISTING MEASURED PRIMARY MINIMUM, PRIMARY MAXIMUM, FAN DISCHARGE AIRFLOW, INLET STATIC PRESSURE, AND HEATING DISCHARGE TEMPERATURE FOR EACH BOX.

EXISTING GAS FIRED ROOFTOP UNIT SCHEDULE (FOR REFERENCE ONLY)

TAG

BASIS OF DESIGN SUPPLY FAN COOLING GAS HEATING FILTRATION ELECTRICAL DATA

NOTES

MANUFACTURER MODEL

TOTAL

CFM

O/A

CFM

E.S.P.

(IN. WG)

T.S.P.

(IN. WG)

RPM HP

DRIVE

TYPE

TOTAL

MBH

SENS.

MBH

EAT

DB (°F)

EAT

WB (°F)

LAT

DB (°F)

LAT

WB (°F)

INPUT

MBH

OUTPUT

MBH

EAT

DB (°F)

LAT

DB (°F)

FUEL

EFF.

STAGES PRE FINAL VOLTAGE FLA MCA MOCP STAGES

WEIGHT

(LBS)

RTU-3 CARRIER 48HJD012 4,600 1,540 2.0 — 1,282 5 — 131.4 99.9 81.9 68.5 61.8 — 180.0 147.5 — EAT + 29.7 NATURAL GAS 81.9 2 30% — 208/3/60 — 63.4 70.0 2 — 1-9

NOTES:

1. EXISTING RTU-3 SHALL REMAIN. VERIFY MANUFACTURER, MODEL, NAMEPLATE DATA, ELECTRICAL CHARACTERISTICS, SERVICE CLEARANCES, AND CONDITION IN FIELD.

2. TEST AND BALANCE RTU-3 TO 4,600 CFM SUPPLY AIR AND NOT LESS THAN 1,540 CFM OUTDOOR AIR DURING OCCUPIED OPERATION. VERIFY AIRFLOW AT THE OUTDOOR-AIR INTAKE.

3. VERIFY OUTDOOR-AIR DAMPER AND ECONOMIZER OPERATION. MINIMUM OUTDOOR AIR SHALL BE MAINTAINED DURING OCCUPIED MODE; OUTDOOR AIR MAY INCREASE TO 4,600 CFM WHEN ECONOMIZER CONDITIONS PERMIT.

4. VERIFY EXISTING POWER EXHAUST FAN OPERATION AND BALANCE TO 3,850 CFM AT FULL OPERATION. COORDINATE POWER EXHAUST WITH ECONOMIZER AND BUILDING PRESSURE CONTROL.

5. COORDINATE RTU-3 OPERATION WITH THE SERIES FAN-POWERED VAV BOXES AND V-3-1 BYPASS VAV. BYPASS VAV SHALL MODULATE BETWEEN 420 AND 2,000 CFM TO MAINTAIN THE EXISTING SUPPLY-DUCT STATIC-PRESSURE SETPOINT.

6. INSPECT AND CLEAN EXISTING COILS, DRAIN PAN, FILTER SECTION, DAMPERS, FANS, BELTS, AND ASSOCIATED CONTROLS. REPLACE DAMAGED OR DETERIORATED COMPONENTS AS REQUIRED.

7. COOLING LAT DB OF 61.8°F AND HEATING OUTPUT OF 147.5 MBH ARE CALCULATED FROM THE SCHEDULED AIRFLOW, SENSIBLE CAPACITY, AND 29.7°F TEMPERATURE RISE. VERIFY ACTUAL OPERATING TEMPERATURES AND NAMEPLATE PERFORMANCE IN FIELD.

8. SUBMIT A FINAL TAB REPORT LISTING SUPPLY, OUTDOOR, RETURN, RELIEF/EXHAUST, AND BYPASS AIRFLOWS; FAN SPEED; EXTERNAL STATIC PRESSURE; DAMPER POSITIONS; AND OPERATING TEMPERATURES.

9. FOR REFERENCE ONLY

W ilk es -B ar re

, P A t:

.8

.1 f:

.8

.0

N . P en ns yl va ni a

A ve w : w w w

.m ra pc .c om

A

SHEET TITLE: 11.03.2026

SHEET NUMBER:

B C D E F G H I J

A B C D E F G H I J

S E

A L:

PROJ # : DRAWN BY :

C O

N S

U

LT

A N

T

T H

IS

D

R A

W

IN

G I

S T

H E

P R

O P

E R

T Y

O F

T H

E A

R C

H

IT

E C

T A

N D

M A

Y N

O T

B E

P R

O D

U C

E D

I N

A N

Y F

O R

M W

IT

H

O U

T W

R

IT

T E

N P

E R

M

IS

S

IO

N

/2

/2

4:

:3

P

M

CONSTRUCTION

M1.1

STREET LEVEL FLOOR

PLAN - MECHANICAL

DEMOLITION

SCALE:M1.1 3/16" = 1'-0"

1 STREET LEVEL PLAN - MECHANICAL DEMOLITION

THE FOLLOWING SUMMARIZES THE EXISTING CONTROL DOCUMENTATION. VERIFY ACTUAL

EQUIPMENT, CONTROLS, SETPOINTS, AND OPERATION IN THE FIELD PRIOR TO PERFORMING

WORK.

OCCUPIED OPERATION

1. RTU-3 SHALL OPERATE CONTINUOUSLY IN “HAND,” REMAIN OFF IN “OFF,” AND BE

CONTROLLED BY THE DDC SYSTEM IN “AUTO.”

2. FAN F-3 SHALL BE INTERLOCKED WITH RTU-3 AND SHALL START UPON PROOF OF

OUTDOOR-AIR DAMPER D-1 END SWITCH.

3. UPON A CALL FOR OPERATION, THE ASSOCIATED SMOKE DAMPER SHALL OPEN. THE SUPPLY

FAN SHALL START UPON PROOF OF THE DAMPER END SWITCH. THE DAMPER SHALL CLOSE

UPON FAN SHUTDOWN.

4. DISCHARGE-AIR SENSOR T-1 SHALL MAINTAIN A 55°F SUPPLY-AIR TEMPERATURE

SETPOINT. THE SETPOINT SHALL RESET BASED ON FAN-POWERED BOX PRIMARY-AIR

DAMPER POSITIONS.

5. A CURRENT SENSOR SHALL MONITOR SUPPLY-FAN OPERATING STATUS.

6. WHEN MIXED-AIR TEMPERATURE RISES ABOVE THE ADJUSTABLE 55°F SETPOINT OF

SENSOR T-3, OUTDOOR-AIR AND RETURN-AIR DAMPERS D-1 AND D-2 SHALL MODULATE TO

PROVIDE ECONOMIZER COOLING.

7. WHEN MIXED-AIR TEMPERATURE FALLS BELOW SETPOINT, THE GAS-FIRED HEATING

SECTION SHALL STAGE AS REQUIRED.

8. MIXED-AIR LOW-LIMIT SENSOR T-3 SHALL OVERRIDE ECONOMIZER OPERATION TO

MAINTAIN A MINIMUM MIXED-AIR TEMPERATURE OF 50°F.

9. WHEN ECONOMIZER CONDITIONS ARE NOT AVAILABLE, DAMPERS D-1 AND D-2…