3-Binder 3 - Drawings - CWU-0089-L BENTLEY STREET LEVEL RENOVATION CONSTRUCTION DOCUMENTS.pdf
PDF 8 MB Posted
- Solicitation number
- Not on record
- Issued by
- Clearfield County, Pennsylvania
About this file
Summary: Construction Documents for Bentley Street Level Renovation
This is a comprehensive set of architectural, mechanical, and electrical construction documents for the Bentley Street Level Renovation project at Lock Haven University in Lock Haven, Pennsylvania, prepared under the Pennsylvania State System of Higher Education. The project involves the renovation of 3,810 gross square feet of interior space at street level, including selective demolition, new interior glazing and decorative walls, new ceilings and flooring, new exterior signage, and painting. The work scope encompasses general construction; HVAC work including removal and replacement of ceiling diffusers, installation of a new mini-split heat pump system, and repositioning of sprinkler heads; and electrical work including new interior lighting, additional outlets, and new information technology infrastructure. The project will be executed by separate prime contractors (General, HVAC, and Electrical), with the General Contractor serving as the lead prime contractor. A mandatory pre-bid conference with site visit is scheduled for November 12, 2026, at 11:00 AM EST at Bentley Dining Hall on the Lock Haven University campus. Electronic bids are due no later than 1:00 PM EST on December 8, 2026, through PennBid at https://pennbid.bonfirehub.com/.
The bid package is available at no cost through PennBid, which requires free registration for interested bidders to obtain solicitation documents and submit proposals. The construction documents include detailed floor plans, demolition plans, reflected ceiling plans, interior elevations and details, mechanical floor plans with equipment schedules and ductwork specifications, and comprehensive electrical plans and schedules. Key architectural features include fully accessible toilet rooms, new classroom spaces (675 square feet and 643 square feet), a podcast studio (512 square feet), a lobby (1,095 square feet), and a vestibule, with finishes specified including carpet tile, acoustic ceiling, gypsum wall board, paint, rubber base, and specialized wall systems. The mechanical system includes retention of the existing rooftop unit (RTU-3) with VAV boxes, installation of a ductless split system for supplemental heating and cooling, and new diffusers and grilles. No specific contract pricing, funding sources, or set-asides are identified in the construction documents provided.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 6-SDB Form, 71-FA-8.2 Dec 2023.docx | DOCX document | |
| 5-Bid Form, 71-FA-8.2 Dec 2023.docx | DOCX document | |
| 1-Binder1 - Solicitation and Contract Documents.pdf | ||
| 2-Binder 2 - Specifications - CWU-0089-L Lock Haven Bentley Hall.pdf | ||
| 4-Spec Instr to Bidders 71-FA-8.2 Dec 2023.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
STATE SYSTEM OF HIGHER EDUCATION
Scale:
Date:
Project/Contract No.
Drawn By:
Checked By:
Drawing No.
Title:
Submitted:
Authorized By:
Reviewed By:
Submitted:
Description DescriptionDateDate
System Representative:
Construction Manager:
Consultant:
Professional:
AS NOTED
COMMONWEALTH UNIVERSITY
N
PROJECT LOCATION
STATE SYSTEM OF HIGHER EDUCATION
COMMONWEALTH OF PENNSYLVANIA
VICINITY MAP
PROJECT SITE
JOSH SHAPIRO, GOVERNOR
CHRIS FIORENTINO, CHANCELLOR
DR. JEFFERY OSGOOD, PRESIDENT
CPL/RMS
TLS
CS
COVER SHEET
PROJECT AREA
CWU-0089-L BENTLEY STREET LEVEL RENOVATION
CONSTRUCTION
LOCK HAVEN UNIVERSITY
LOCK HAVEN, CLINTON COUNTY, PENNSYLVANIA
CWU-ARCH-1232024-C-3 - CWU-89-L
CWU-ARCH-1232024-C-3 - CWU-89-L
LOCK HAVEN UNIVERSITY
LOCK HAVEN, CLINTON COUNTY, PENNSYLVANIA
ARCHITECTURAL
CS COVER SHEET
A0.1 SITE PLAN
A0.2 LIFE SAFETY PLANS
A0.3 CODE ANALYSIS & NOTES
AD1.0 DEMOLITION PLANS
A1.1 FLOOR PLAN
A2.0 EXTERIOR ELEVATION
A6.1 REFLECTED CEILING PLAN
A8.1 FINISH FLOOR PLAN
A8.2 INTERIOR ELEVATIONS
A8.3 INTERIOR DETAILS
MECHANICAL
M0.0 LEGEND, NOTES, AND DRAWING SCHEDULE
M1.1 STREET LEVEL FLOOR PLAN - MECHANICAL DEMOLITION
M2.1 STREET LEVEL FLOOR PLAN - MECHANICAL
ELECTRICAL
E0.0 LEGEND, NOTES AND DRAWING SCHEDULE
E1.1 FLOOR PLANS - ELECTRICAL DEMOLITION
E2.1 STREET LEVEL FLOOR PLAN - LIGHTING
E3.1 STREET LEVEL FLOOR PLAN - POWER AND SYSTEMS
FIRE PROTECTION
FP1.1 LEGEND, NOTES & STREET LEVEL FLOOR PLANS
11.03.2026
ACCESSIBLE ENTRANCE
TO STREET LEVEL
ACCESSIBLE ENTRANCE
TO GROUND FLOOR
ACCESSIBLE ENTRANCE
TO FIRST FLOOR
LO
A
D
IN
G D
O C
K
SERVICE & DUMPSTERS
THERE IS NO VISITOR PARKING
PROVIDED TO THE BUILDING
IT IS WITHIN THE GREATER
COLLEGE CAMPUS
G
LE
N N
R O
A D
FAIRVIEW STREET
AK
EL
EY
R
O
AD
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:2
P
M
CONSTRUCTION
A0.1
SITE PLAN
26-CUP-0226-CUP-02 TLS / GMBTLS / GMB
1" = 20'-0"A0.1
1 SITE PLAN
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
IO
SCOPE OF WORK:
NONE
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
SCOPE OF WORK:
NONE
EXIT
EXIT
FULLY ACCESSIBLE
TOILET ROOMS
ELEVATOR
EXIT
SCOPE OF WORK:
INTERIOR RENOVATIONS
EXIT
EXIT
FULLY ACCESSIBLE
TOILET ROOMS
AREA OF WORK
3810 GROSS SQ FT
1320sf CLASSROOM 514sf CLASSROOM
500sf SITTING AREA
NO WORK
NO WORK
NO WORK
PHASED CONSTRUCTION BARRIER,
MUST MAINTAIN ACCESS TO ELEVATOR
& STAIR DURING SEMESTER
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:2
P
M
CONSTRUCTION
A0.2
LIFE SAFETY PLANS
26-CUP-0226-CUP-02 CPLCPL
3/32" = 1'-0"A0.2
1 GROUND FLOOR CODE PLAN
3/32" = 1'-0"A0.2
2 FIRST FLOOR CODE PLAN
3/32" = 1'-0"A0.2
3 STREET LEVEL CODE PLAN
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
PLUMBING CODE ANALYSIS:
INTERNATIONAL PLUMBING CODE - 2021
403.1.1 FIXTURE CALCULATIONS
TO DETERMINE THE OCCUPANT LOAD OF EACH SEX, THE TOTAL OCCUPANT LOAD SHALL BE
DIVIDED IN HALF. TO DETERMINE THE REQUIRED NUMBER OF FIXTURES, THE FIXTURE RATIO
OR RATIOS FOR FIXTURE TYPE SHALL BE APPLIED TO THE OCCUPANT LOAD OF EACH SEX IN
ACCORDANCE WITH TABLE 403.1
2021 EXISTING INTERNATIONAL BUILDING CODE 810.1 MINIMUM FIXTURES:
WHERE THE OCCUPANT LOAD OF THE STORY IS INCREASED BY 20 PERCENT, PLUMBING FIXTURES FOR THE STORY SHALL BE PROVIDED IN QUANTITIES SPECIFIED IN THE INTERNATIONAL PLUMBING
CODE BASED ON THE INCREASED OCCUPANT LOAD.
BUILDING REQUIREMENTS
EXISTING OCCUPANCY 2005
NEW OCCUPANCY 2005
2005 OCC/ 2 = 1003 MALE AND 1003 FEMALE
WATER CLOSETS - 1/75 = 13.3, OR 14 EACH MALE & FEMALE
PROVIDED = 9 MALE WCs + 10 URINALS & 15 FEMALE WCs
LAVATORIES - 1/200 = 5.015. 0R 6 EACH MALE & FEMALE
PROVIDED = 11 FEMALE & 10 MALE
DRINKING FOUNTAINS - WATER IS AVAILABLE TO ALL PATRONS ON GROUND & FIRST FLOORS, THERE
IS AN EXISTING, ACCESSIBLE HIGH/LOW DRINKING FOUNTAIN ON STREET LEVEL
SERVICE SINKS - 9 EXISTING
" M
IN
18" MIN
" M
IN
12" MIN
(A) FRONT APPROACH, PULL SIDE *IF BOTH CLOSER AND LATCH ARE PROVIDED
(B) FRONT APPROACH, PUSH SIDE
DOUBLE DOOR W/
(2) ACTIVE LEAVES
RIGHT SIDE
OF DOOR
NOTE: REFER TO SPECIFICATIONS FOR SIGNAGE SIZE AND LOCATION REQUIREMENTS.
9"
1'-6"
CLEAR
FLOOR AREA
ROOM
NAME
4' -0
5' -0
" M
AX
BR
AI
LL
E
H
EI
G H
T
BA
SE
LI
N
E O
F H
IG
H
ES
T
TE
XT
ROOM
NAME
ROOM
NAME
SINGLE DOOR
LATCH SIZE
9"
1'-6"
4' -0
5' -0
" M
AX
BR
AI
LL
E
H
EI
G H
T
BA
SE
LI
N
E O
F H
IG
H
ES
T
TE
XT
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:2
P
M
CONSTRUCTION
A0.3
CODE ANALYSIS &
NOTES
1/2" = 1'-0"A0.3
1 ADA DOOR SWING APPROACH
1/2" = 1'-0"A0.3
2 TACTILE SIGNAGE
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
9.1
9.4
9.2 9.2
9.1
9.3
9.5
9.2
9.6
9.3
9.3
9.6
9.6
9.5 9.5
9.7
9.8 9.8
9.8
9.8
9.8
9.8
9.8
1.
2.
3.
A.
B.
A.
B.
PRIOR TO COMMENCEMENT OF WORK:
G.C. SHALL REVIEW AND VERIFY ACTUAL FIELD CONDITIONS AND
NOTIFY THE ARCHITECT IN WRITING OF ALL INCONSISTENCIES OR
CONFLICTS. EXIST. CONSTRUCTION MAY VARY FROM THE
DRAWINGS.
G.C. SHALL REVIEW AND VERIFY ALL DEMOLITION WORK AGAINST
ALL NEW CONSTRUCTION WORK AND NOTIFY THE ARCHITECT IN
WRITING OF ALL INCONSISTENCIES OR CONFLICTS. REFER TO
FINISH PLANS AND SCHEDULES FOR COORDINATION OF
DEMOLITION WORK WITH NEW FINISHES AND CONSTRUCTION.
PROTECTION, INTERIOR :
G.C. TO PROTECT ALL EXIST. CONSTRUCTION, FINISHES,
FURNITURE, FIXTURES AND EQUIPMENT TO REMAIN DURING ALL
PHASES OF DEMOLITION AND CONSTRUCTION. U.N.O. G.C. SHALL
DETERMINE APPROPRIATE MEANS OF PROTECTION.
FLOOR AND WALL BASE: PROVIDE LAPPED AND TAPED
SHEET GOOD TO PROTECT ALL FLOOR FINISHES AND
WALL BASES.
WALL: PROVIDE PARTIAL HEIGHT LAPPED AND TAPED
SHEET GOOD AT AREAS OF INTENSIVE USE,
PARTICULARLY OUTSIDE CORNERS.
4. STRUCTURE AND TEMPORARY SHORING :
G.C. SHALL PROTECT AND ENSURE THAT ALL EXIST. STRUCTURE
REMAINS UNDISTURBED U.N.O.
A. G.C. SHALL PROVIDE ALL TEMPORARY SHORING AND
SUPPORT DURING ALL DEMOLITION AND CONSTRUCTION
ACTIVITIES.
5. REMOVAL:
G.C. SHALL REMOVE ALL CONSTRUCTION INDICATED UNLESS
REQUESTED BY THE OWNER TO BE SALVAGED.
A. ALL MATERIALS TO BE REMOVED SHALL BE PROPERLY
REMOVED IN STRICT COMPLIANCE WITH ALL LAWS, PROJECT
SPECIFICATIONS AND IN A MANNER WHICH DOES NOT IMPEDE
THE PROJECT SCHEDULE; DOES NOT OPEN THE BUILDING TO
DETRIMENT; AND DOES NOT ADVERSELY IMPACT CAMPUS OR
BUILDING OPERATION.
B. G.C. SHALL REMOVE ALL ITEMS INCIDENTALLY
NECESSARY FOR REMOVAL OF ITEMS INDICATED FOR REMOVAL,
STORE, AND REINSTALL AT APPROPRIATE STAGE OF
CONSTRUCTION.
C. REFER TO OTHER DISCIPLINE DRAWINGS FOR RELEVANT
DEMOLITION SCOPE.
6. SALVAGE:
ALL SALVAGE RIGHTS REMAIN WITH THE OWNER. G.C. SHALL
COORDINATE WITH OWNER PRIOR TO COMMENCEMENT OF
WORK AND AS REQ'D DURING DEMOLITION AND CONSTRUCTION
ACTIVITIES. ANY ITEMS NOT REQUESTED BY THE OWNER SHALL
BE PROPERLY BY THE G.C.
ANY ITEMS INDICATED FOR SALVAGE OR REINSTALLATION SHALL:
BE TAGGED FOR IDENTIFICATION AS TO WHERE THE ITEM
WAS REMOVED AND PLANNED TO BE RELOCATED.
BE STORED IN A SAFE DRY LOCATION AWAY FROM ANY
CONSTRUCTION ACTIVITIES. COORDINATE LOCATION
WITH OWNER.
7. REPAIR:
G.C. TO REPAIR OR REPLACE IN KIND AT NO COST TO OWNER ALL
DAMAGE TO EXIST. BUILDING AND F.F.E., TEMPORARY
PROTECTION, AND PARTIAL OR COMPLETED CONSTRUCTION AND
F.F.E. RELATED TO ANY DEMOLITION OR CONSTRUCTION
ACTIVITY. WHERE AN ITEM OR ASSEMBLY CANNOT BE REPAIRED,
IT SHALL BE REPLACED IN KIND.
WHERE CONCEALED, EXIST. DAMAGE IS DISCOVERED, SUCH AS
PATCHING REQ'D TO EXIST. CONC. FLOOR, G.C. SHALL PATCH
AND OR REPAIR AS REQ'D FOR SOUND, LEVEL AND PLUMB
SUBSTRATES TO TOLERANCES REQ'D BY MFR. OR IDENTIFIED IN
THE SPECIFICATIONS.
BASE SCOPE DEMOLITION GENERAL NOTES
BASE SCOPE DEMOLITION LEGEND
EXIST. ELEMENTS TO REMAIN
EXIST. ELEMENTS TO BE REMOVED
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:3
P
M
CONSTRUCTION
AD1.0
DEMOLITION PLANS
1/8" = 1'-0"AD1.0
1 STREET LEVEL DEMO PLAN
1/8" = 1'-0"AD1.0
2 STREET LEVEL DEMO RCP
DEMOLITION SPECIFIC NOTES - SHEET AD1.0
9.1 REMOVE TILE
9.2 REMOVE CARPET
9.3 REMOVE WALL & ASSOCIATED FRAMING
9.4 REMOVE WALL SEGMENTS FOR GLAZING
9.5 REMOVE WALL COVERINGS & FINISHES
9.6 REMOVE CHAIR RAIL FROM WALL
9.7 TO REPLACE WITH SIMILAR PRODUCT WHILE PRESERVING SURROUNDING
TILE
9.8 REMOVE 24x24 CEILING & ASSOCIATED FRAMING
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
IO
N
0 16' 24' 32'8'
0 16' 24' 32'8'
A8.2
A8.2
A8.2
DD1.5
1095 SF
LOBBY
S02
512 SF
PODCAST
SPACE
S05
57 SF
IT
CLOSET
614 SF
CORRIDOR
S-C1
675 SF
CLASSROOM
G53
643 SF
CLASSROOM
G54
A8.2
A8.2
DD1.5
1 / 2
A2.0
A2.0
A2.0
A8.3
A8.3
P1
P2
P2
P2
P1P1
P1
P2
11' - 6 1/2"
5'
1/
2"
12' - 4" 2' - 0 1/2" 30' - 11 1/2" 2' - 0 1/2" 31' - 0" 2' - 0 1/2" 13' - 2 1/4"
P2
P2
P2
P2
7' - 9 3/4"
6' - 0 1/4"
7' - 10"
P2
P2
P2
P2
P2
P2
P2
P2
5' - 9"
A2.0
A2.0
STUD PARTITIONS
P1 3 5/8" METAL STUD W/ 5/8" GYP. BOARD
EACH SIDE w/ SOUND BATT INSULATION
INTERIOR PARTITIONS
PARTITION TYPE SCHEDULE & NOTES
P2 3 5/8" STUD W/ 5/8" GYP. BOARD ONE
SIDE.
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:2
P
M
CONSTRUCTION
A1.1
FLOOR PLAN
1/4" = 1'-0"A1.1
1 STREET LEVEL PLAN
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
IO
N
N
S
E
W
PLAN
NORTH
0 8' 12' 16'4'
STREET LEVEL
-14' - 0"
1'
2'
5" 3'
5"
3'
7"
7' - 0"
5'
1/
2"
STREET LEVEL
-14' - 0"
A2.0
RELOCATE EXISITNG "BENTLEY"
SIGN
DONOR SIGNAGE;
FONT TYPE: FRANKLIN GOTHIC
FINISH:
BRUSHED ALUMINUM
ACRYLIC PANEL - BLACK
BRUSHED ALUMINUM FRAME
ALUMINUM PANELS
WRAPPED OVER
EXISTING FINISH
EXISTING BRUSHED
ALUMINUM CAP
STREET LEVEL
-14' - 0"
A2.0
1/2" 1"
2 1/4"
DONOR SIGNAGE;
FONT TYPE: FRANKLIN GOTHIC
FINISH:
BRUSHED ALUMINUM
SIZE: 10 & 6"
ACRYLIC PANEL - BLACK
BRUSHED ALUMINUM FRAME
BRUSHED ALUMINUM FRAME (MATCH
KAWNEER TRIFAB 451 SYSTEM)
2" 2"
5'
1/
2"
5' - 1 1/2"
3' - 10 3/4"
10' - 4 3/4"
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:2
P
M
CONSTRUCTION
A2.0
EXTERIOR ELEVATION
1/4" = 1'-0"A2.0
1 STREET LEVEL ELEVATION
1/2" = 1'-0"A2.0
2 SIGNAGE ELEVATION
1/2" = 1'-0"A2.0
3 SIGNAGE ELEVATION - SIDE
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
IO
N
1" = 1'-0"A2.0
4 SIGNAGE DETAIL
1/4" = 1'-0"5 SIGN PLAN
S
S
S
S
S
S
S
S
WA
P
S
S
S
S
WA
P
S
RC
OS
DS
OS
OS
RC
RC
RC
RC
OS
OS
OS
RC
OS
OS
RC
RC
OS
DS
OS
RC
RC
OS
OS
OS
DS
WA
P WA
P
WA
P
8' - 11"
9' - 4"
9' - 4"
9' - 5 3/4"
9' - 5 3/4"
10' - 0"
9' - 0 3/4"
A6.1
A6.1
A6.1
A8.3
A8.3
CLASSROOM
G54
CLASSROOM
G53
CORRIDOR
S-C1
IT
CLOSET
S12
PODCAST
SPACE
S05
VESTIBULE
S01
LOBBY
S02
INFILL GAP AROUND
PARTITION OPERATOR
A2.0
PROVIDE HOLD DOWN CLIPS
FOR CEILING TILES WITHIN
VESTIBULE
EXISTING CEILING - GWB, PREP &
PAINT,
PARTITION TRACK TO REMAIN
INFILL GWB WHERE
DAMAGED/MISSING
ACOUSTICAL CAULK
AROUND ALL
PENETRATIONS
NEW CEILING TILE
IN EXISTING GRID
NEW CEILING TILE
IN EXISTING GRID
INFILL GWB WHERE
DAMAGED/MISSING
ACOUSTICAL CAULK
AROUND ALL
PENETRATIONS
INFILL ACOUSTICAL
SEALANT IN ANY
GAPS BETWEEN TOP
OF EXISTING WALL
& METAL DECK
5"
PERIMETER TRIM
OF LINEAR METAL
SUSPENSION SYSTEM
2X2 ACT CEILING
PLANX PANEL
PLANX CARRIER GRID
SYSTEM
NOTE: REFER TO MFG. DETAIL
AND SPECIFICATION
GENERAL REFLECTED CEILING PLAN
LEGEND AND NOTES:
ACOUSTICAL CEILING INSTALLATION
1. THE CONTRACTOR SHALL FIELD CHECK THE PREMISES AND VERIFY THAT THE
CEILING LAYOUT SHOWN ON THE DRAWINGS CAN BE ACCOMMODATED AND VERIFY
ALL CLEARANCES AS REQUIRED FOR ALL LIGHTING FIXTURES, DUCT WORK, AND
SPRINKLERS BEFORE PROCEEDING WITH ANY INSTALLATION. REPORT ANY
DISCREPANCIES TO THE ARCHITECT PRIOR TO PROCEEDING.
2. REVIEW CEILING LAYOUT WITH MEP COORDINATION DRAWINGS.
3.
4.
CEILING SHALL BE TRUE, FLAT, STRAIGHT AND REGULAR. PROVIDE STABILIZER BARS AS
REQUIRE TO DISTRIBUTE LOAD EQUALLY OVER TWO OR MORE RUNNERS.
5.
LEVEL CEILING TO BE WITHIN 1/8" IN 12 FEET IN ANY DIRECTION. LEVEL WITH HANGER WIRE
TAUT AND PLUMB, WITHOUT KINKING OR BENDING HANGER WIRES. CEILING HEIGHT SHALL
MATCH EXISTING UNLESS OTHERWISE NOTED.
6.
INSTALL MAX. LENGTHS OF EDGE MOLDING AT INTERSECTION OF CEILING AND VERTICAL
SURFACE. MITER ALL CORNERS.
7.
COORDINATE INSTALLATION WITH ELECTRICAL, MECHANICAL AND SPRINKLER REQUIREMENTS.
8.
INSTALL CEILING TILE HOLD DOWN CLIPS IN ALL VESTIBULES & AIR LOCKS.
9.
LAY DIRECTIONAL PATTERN UNITS IN SINGLE DIRECTION.
10.
INSTALL CEILING TILE HOLD DOWN CLIPS AT PARTITIONS WITH CUT CEILING TILES.
11. REGULAR CEILING TILE TO BE CUT AND FITTED SNUG AGAINST PARTITIONS. DO NOT SHIM
THE GRID TO ALLOW CEILING TILE TO PASS OVER TOP OF PARTITION.
ALL FIXTURE TRIM (LIGHTING, SPEAKER,, HVAC GRILLES, ETC.) SHALL BE METAL AND
PAINTED TO MATCH ADJACENT CEILING FINISH. PLASTIC TRIM IS NOT ACCEPTABLE UNLESS
APPROVED BY THE ARCHITECT.
- INDICATES 2X4 A.C.T. CEILING, REFER TO FINISH SCHEDULE.
- INDICATES G.W.B. CEILING, REFER TO FINISH SCHEDULE.
NOTES:
1.) REFER TO SPECIFICATIONS FOR CEILING MATERIALS.
FINAL CEILING HEIGHTS TO BE CONFIRMED FOLLOWING FIRE PROTECTION, PLUMBING,
MECHANICAL, AND ELECTRICAL COORDINATION
12.
2.) EXISTING GRIDS ARE NOT SHOWN FOR CLARITY, VERIFY IN FIELD.
- INDICATES 2X2 A.C.T. CEILING, REFER TO FINISH SCHEDULE.
- INDICATES AREA IN WHICH CONTRACTOR SHALL INSPECT EXISTING CEILING SYSTEMS
AND REPLACE DAMAGED ACT AND DEFECTIVE GWB CEILING AREAS ONLY.
CONTRACTOR SHALL RETAIN ALL EXISTING UNDAMAGED CEILING FINISHES.
- PAINT EXPOSED CEILING, INCLUDING ALL STRUCTURAL AND MEP COMPONENTSEXPOSED
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:2
P
M
CONSTRUCTION
A6.1
REFLECTED CEILING
PLAN
1/4" = 1'-0"A6.1
1 STREET LEVEL REFLECTED CEILING PLAN
1 1/2" = 1'-0"A6.1
2 CEILING DETAIL - CLASSROOM
1 1/2" = 1'-0"A6.1
3 CEILING DETAIL - PODCAST
1 1/2" = 1'-0"A6.1
4 CEILING DETAIL - LOBBY
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
IO
N
N
S
E
W
PLAN
NORTH
0 8' 12' 16'4'
675 SF
CLASSROOM
G53
643 SF
CLASSROOM
G54
512 SF
PODCAST
SPACE
S05
57 SF
IT
CLOSET
S12
614 SF
CORRIDOR
S-C1
1095 SF
LOBBY
S02
138 SF
VESTIBULE
S01
A8.3
A8.3
CPT-2 RF-1
CPT-2
EXIST
CPT-2 RF-1
RF-1
RF-1
EXIST
EXIST
R F-1
RF-1
EXIST
RF-1
EXIST
ACCENT WALL
(PNT-2/PNT-3)
REF. ELEVATION
R F-1
EXIST
R F-1
C
PT-2
R F-1
C
PT-2
ACCENT WALL
(PNT-2)
ACCENT WALL
(PNT-2)
W G
-1
PAINT FACE AND
SIDES OF BUMP OUT
(PNT-2)
PAINT FACE AND
SIDES OF BUMP OUT
(PNT-2)
PAINT FACE AND
SIDES OF BUMP OUT
(PNT-2)
R F-
R
F-
R F-
R
F-
W C
P-
W C
P-
R F-
R F-
R F-
RF-1 EXIST
EX
IS
T
W C
P-
W C
P-
WG-1 WS-1WS-1
W S-1
W S-1
W S-1
RF-1
RF-2
AC
C
EN
T
(PN
T-2)
AC
C
EN
T
(PN
T-2)
PAINT EXIST DOOR
FRAME (PNT-4)
PAINT EXIST DOOR
FRAME (PNT-4)
PAINT EXIST DOOR
FRAME (PNT-4)
PAINT EXIST DOOR
FRAME (PNT-4)
PAINT EXIST DOOR
FRAME (PNT-4)
PAINT EXIST DOOR
FRAME (PNT-4)
PAINT EXIST DOOR
FRAME (PNT-4)
PAINT EXIST DOOR
FRAME (PNT-4)
A2.0
MANUFACTURER: MOHAWK CARPET TILE; COLLECTION: LEARN & LIVE; STYLE: SIDE
STRIPE GT419; COLOR: 963 HERITAGE; SIZE: 24"X24"
CPT-2
MANUFACTURER: MOHAWK CARPET TILE; COLLECTION:FRACTAL FLUENCY; STYLE:
SQUARED GT478; COLOR: 949 MINERAL; SIZE: 12"X36"
CPT-2
BASE FINISHES
FINISH LEGEND
FLOOR FINISHES
RB
JOHNSONITE/ TARKETT, RUBBER COVE BASE, SIZE: 4" COLOR: TBD, INCLUDE 1-3 COLORS IN
ADDITION TO (TBD), TO BE DETERMINED FROM MANUFACTURER'S FULL RANGE.
PAINT
PNT-1:
FIELD PAINT: BENJAMIN MOORE, COLOR: OC-17 WHITE DOVE, FINISH: SCUFF-X EGGSHELL
PNT-2:
ACCENT PAINT (LOCK HAVEN PANTONE): BENJAMIN MOORE, COLOR TO MATCH: PANTONE PMS 1955
FINISH: SCUFF-X EGGSHELL
CEILING FINISHES
ACT:
ACOUSTIC CEILING TILE: REFER TO SPECIFICATIONS FOR PRODUCT TYPES AND SPECIFIC
LOCATIONS.
GWB:
GYPSUM WALL BOARD, PAINTED FINISH, AS REQUIRED
WALL FINISHES
MANUFACTURER: MOHAWK GROUP, SERIES: CREATIVE TERRAIN II C2117, SIZE:
36"X36"; COLOR: 733 RED BLUFFS W/ INTEGRAL COVE BASE
RF-1
MISCELLANEOUS
PNT-3:
ACCENT PAINT (LOCK HAVEN PANTONE): BENJAMIN MOORE, COLOR TO MATCH: PANTONE PMS 425, FINISH: SCUFF-X EGGSHELL
PNT-4:
DOOR FRAME PAINT: BENJAMIN MOORE, COLOR TO MATCH: PANTONE PMS 425, FINISH: SCUFF-X
SEMI-GLOSS, REFER TO FINISH PLAN FOR LOCATIONS
WS-1: USG WOOD WALL SLAT SYSTEM, REFER TO SPECIFICATIONS FOR PRODUCT TYPES
AND DRAWINGS FOR SPECIFIC LOCATIONS AND DETAILS, COLOR: S32 CP MAPLE
WG-1: VINYL WALL GRAPHICS, OWNER PROVIDED IMAGE FILES
MANUFACTURER: MOHAWK GROUP, SERIES: CREATIVE TERRAIN II C2117, SIZE:
36"X36"; COLOR: 937 ALPINE MIST W/ INTEGRAL COVE BASE
RF-2
CONSTRUCTION SPECIALTIES WALK-OFF MAT SYSTEM; STYLE: PEDITRED G4;
COLOR: AS SELECTED FROM MANUFACTURER'S FULL STANDARD LINE.
WCP-1
WCS-1:
WOOD CEILING SLAT SYSTEM: REFER TO SPECIFICATIONS FOR PRODUCT TYPES AND
SPECIFIC LOCATIONS, COLOR: S32 CP MAPLE
MB (BASIS OF DESIGN)
ELITE EXPRESSIONS, ANODIZED BLACK ALUMINUM18GA WALL BASE, SIZE: 8" STYLE: COVE BASE
INTEGRAL FLASH COVE
MOHAWK GROUP, CREATIVE TERRAIN II, SIZE: 4"HT COLOR: 937 ALPINE MIST & 733 RED
BLUFFS, TRIM: ELEMENTAL EDGES COVE STICK;
REFERENCE FINISH PLAN FOR FLOORING TRANSITIONS
1. CONTRACTORS SHALL FIELD VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO FABRICATION AND/OR COMMENCEMENT
OF WORK AND SHALL IMMEDIATELY REPORT ANY DISCREPANCIES TO THE ARCHITECT.
2. ALL FINISHES, COLORS AND FINAL PRODUCT SELECTIONS TO BE VERIFIED WITH OWNER.
3. PATCH AND REPAIR ANY FINISHES DISTURBED DURING CONSTRUCTION.
4. PAINT COLOR SELECTIONS WILL BE CONFIRMED DURING THE SUBMITTALS PROCESS WITH DRAWDOWNS.
5. ALL COLORS TO BE CONFIRMED DURING THE SUBMITTAL PROCESS.
GENERAL
1. REFER TO CODE REVIEW DRAWING A0.1 FOR FLAME SPREAD RATINGS FOR INTERIOR FINISHES.
2. STARTING OF FINISH WORK SHALL INDICATE APPLICATORS ACCEPTANCE OF SUBSTRATE.
3. ENSURE ALL SURFACES TO RECEIVE FINISH ARE CLEAN, TRUE AND FREE OF IRREGULARITIES. DO NOT PROCEED WITH WORK
UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED.
4. UPON RECEIPT FROM MANUFACTURER, THE INSTALLER SHALL INSPECT ALL MATERIALS FOR DEFECTS, SHIPPING DAMAGE, FLAWS, CORRECT COLOR, AND PATTERN. DAMAGED OR INCORRECT MATERIALS SHALL BE SENT BACK TO THE MANUFACTURER
FOR IMMEDIATE REPLACEMENT.
5. WHERE TWO FLOOR FINISHES MEET AT A DOORWAY, THE TRANSITION MUST OCCUR ON THE CENTER LINE OF THE DOOR IN ITS
CLOSED POSITION.
6. EXTEND FLOOR FINISH UNDER OPEN-BOTTOM AND RAISED BOTTOM OBSTRUCTIONS. EXTEND FINISH INTO CLOSETS AND
ALCOVE AREAS INDICATED UNLESS ANOTHER FINISH IS INDICATED FOR THAT AREA.
7. APPLY RUBBER BASE WHERE SCHEDULED TO WALLS, COLUMNS AND OTHER PERMANENT FIXTURES IN ROOMS OR AREAS WHERE SPECIFIED. INSTALL BASE IN AS LONG LENGTHS AS PRACTICABLE. TIGHTLY BOND BASE TO BACKING THROUGHOUT THE LENGTH AND HEIGHT OF EACH PIECE, WITH CONTINUOUS CONTACT AT VERTICAL AND HORIZONTAL SURFACES. ALL RUBBER
CORNERS TO BE PRE-MOLDED.
8. AFTER COMPLETION OF WORK AND JUST PRIOR TO THE FINAL INSPECTION OF WORK, THOROUGHLY CLEAN FLOORS AND
ACCESSORIES.
9. PRIOR TO OCCUPANCY, THE CONTRACTOR SHALL CLEAN ALL MATERIALS OF DUST, DEBRIS, LOOSE CONSTRUCTION MATERIALS
AND EQUIPMENT.
FINISH
PAINT NOTES
1. ALL PAINT TO BE APPLIED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. SAND LIGHTLY BETWEEN COATS TO ACHIEVE REQUIRED FINISH. ALLOW EACH COAT OF FINISH TO DRY BEFORE THE FOLLOWING COAT IS APPLIED, UNLESS DIRECTED OTHERWISE BY MANUFACTURER. FILL KNICKS, GOUGES AND OTHER IMPERFECTIONS OF SURFACES WITH LATEX FILLER AND SAND SMOOTH UNTIL FLUSH WITH SURFACE.
2. MATERIALS TO ARRIVE AT JOBSITE IN ORIGINAL, NEW, UNOPENED CONTAINERS BEARING THE MANUFACTURER'S NAME, TRADE NAME AND LABEL ANALYSIS. STORE ON SITE IN STRICT ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
3. ALL PAINTING TO BE DONE UNDER FINAL LIGHTING CONDITIONS.
4. FINISHED PAINTED SURFACES SHALL BE OF UNIFORM COLOR, APPEARANCE AND FINISH WITHOUT DRIPS, RUNS OR SMUDGES.
5. WHERE GRILLES OR DIFFUSERS OCCUR IN CEILING OR WALL, CONFIRM WITH PROFESSIONAL PRIOR TO
PAINTING TO MATCH EXISTING ADJACENT SURFACES.
6. REMOVE OR OTHERWISE PROTECT FINISH HARDWARE, ACCESSORIES, PLATES, LIGHTING FIXTURES AND
SIMILAR ITEMS BEFORE PAINTING.
7. DO NOT PAINT ANY MOVING PARTS OR OPERATION UNITS, CODE-REQUIRED LABELS AND EQUIPMENT
IDENTIFICATIONS.
8. PAINT AREAS BEHIND MOVEABLE SURFACE (E.G. INSIDE CABINETS AND BACKS OF ACCESS PANELS).
COORDINATE WITH ARCHITECT PRIOR TO START OF WORK.
9. REPAINT OR REFINISH PAINTED SURFACES DAMAGED BY SUBSEQUENT WORK.
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:2
P
M
CONSTRUCTION
A8.1
FINISH FLOOR PLAN
1/4" = 1'-0"A8.1
1 FINISH FLOOR PLAN
ROOM FINISH SCHEDULE
NUMBER NAME
FLOOR
FINISH BASE
WALL FINISH
Ceiling Finish COMMENTSN E S W
G53 CLASSROOM 01 CPT-1 RB PNT-1 PNT-1/PNT-2 PNT-1 PNT-1 ACT
G54 CLASSROOM 02 CPT-1 RB PNT-1 PNT-1/PNT-2 PNT-1 PNT-1 ACT
S01 VESTIBULE WCP-1 RB EXIST EXIST EXIST EXIST ACT
S02 LOBBY RF-1/RF-2 INTEGRAL/MB PNT-1/PNT-2 PNT-1/WS-1 PNT-1/PNT-2 PNT-1 ACT/WCS-1
S05 PODCAST SPACE CPT-2 RB-1 PNT-2 PNT-1/WS-1 PNT-1 PNT-1 ACT
S12 IT CLOSET CPT-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT
S-C1 CORRIDOR RF-1 INTEGRAL PNT-1 PNT-1 PNT-1/PNT-2/PNT-3 PNT-1 ACT
0 8' 12' 16'4' N
S
E
W
PLAN
NORTH
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
11'-5 1/4" 5'-11 3/4"7'-10 1/8"
GLASS
STOREFRONT
SYSTEM
USG WOOD
SLAT WALL
SYSTEM (WS-1),
REFER TO FINISH
LEGEND
DONOR SIGNAGE;
FONT TYPE:
FRANKLIN GOTHIC
FINISH:
BRUSHED ALUMINUM
LOBBYS02
A8.3
A8.3
3' - 9 3/4"3' - 9 3/4"3' - 9 3/4" 1'
8" 5'
3/ 4"
1'
6"
3' - 0"3' - 0"
1'
6" 5'
3/ 4"
8" 8"
8" HT. METAL BASE
TO MATCH STOREFRONT
FINISH
4" 6"
2"
1'
8" 2"
4"
1/ 4"
1/
2"
VINYL WALL
GRAPHIC WRAP, OWNER
TO PROVIDE IMAGE;
WALL GRAPHIC TO CONCEAL
ELEC.
PANEL DOOR,
CUT THE VINYL
AT ALL DOOR SEAMS
TO KEEP OPERABLE
ELEC. PANEL;
VERIFY EXACT
LOCATION IN
FIELD
INTEGRAL BASE
LOBBYS02
ETR
75" DISPLAYS.
FINAL PLACEMENT
W/ OWNER, TYP.
INTEGRAL BASE
LASER CUT
LOGO; OWNER
TO PROVIDE
ARTWORK AND
FINAL SIZE
PAINT FACE AND SIDES
OF PILASTER (PNT-2)
LOBBYS02
WS-1
7' - 0 3/4"
8'
1/
2"
WS-1
7' - 0 3/4"
+/- 3' - 8"
- 3
PNT-1
PAINT FACE
AND SIDES
OF PILASTER
(PNT-2)
PNT-1 PNT-1PNT-1
75" DISPLAY. FINAL PLACEMENT W/ OWNER, TYP.
TALL PLAM CABINET 27"X90"X18", ADJUSTABLE SHELVING
PODCAST SPACES05
2"
A8.3
A8.3
RUBBER BASE
75" DISPLAY. FINAL PLACEMENT
W/ OWNER, TYP.
WS-1
8'-2 1/4"
WS-1
8'-2 1/4"
RUBBER BASE
PODCAST SPACES05
A6.1PNT-1
E.T.R
GLASS
STOREFRONT
SYSTEM
RUBBER BASE
PODCAST SPACES05
2"
3' - 0" 3' - 0"1'
6" 5'
3/ 4"
1'
6"
(34) 16"X20"
PLAQUES
INTEGRAL BASEPN
T-
2'
-6
PN
T-
2'
-0
PN
T-
PN
T-
1' -0
COORDINATE SIGNAGE W/ OWNER
PAINT FACE AND SIDES
OF PILASTER (PNT-2)
CORRIDORS-C1
PAINT FACE AND SIDES
OF PILASTER (PNT-2)
INSTALL PICTURE RAIL,
(2) 6'-6" STD. LENGTH AND CUT
(3) 4'10" LENGTHS AS SHOWN, TWO
CLIPS PER CABLE;
REF. DETAIL (7)
TO
P
O F
PI
C
TU
R
E R
AI
L
A.
F.
F.
7'
3"
1/
4"
ORIGINAL GALLERY SYSTEM
TRACK
FINISH: PRE-PAINTED WHITE
INCLUDE END CAPS, FINISH:
WHITE
STEEL CABLE HANGERS
PUSHBUTTON SECURITY
HOOK; PROVIDE (2) PER
STEEL CABLE, REF.
ELEVATION 4
GWB
3/4"
STEEL CABLE
CLASSROOM 02G54
75" DISPLAYS. FINAL PLACEMENT
W/ OWNER, TYP.
E.T.R E.T.R
RUBBER BASE
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:2
P
M
CONSTRUCTION
A8.2
INTERIOR
ELEVATIONS
1/2" = 1'-0"A8.2
2 INTERIOR ELEVATION
1/2" = 1'-0"A8.2
3 INTERIOR ELEVATION
1/2" = 1'-0"A8.2
1 INTERIOR ELEVATION OF SEATING AREA
1/2" = 1'-0"A8.2
5 INTERIOR ELEVATION
1/2" = 1'-0"A8.2
6 INTERIOR ELEVATION
1/2" = 1'-0"A8.2
8 INTERIOR ELEVATION
1/2" = 1'-0"A8.2
4 INTERIOR ELEVATION OF PLAQUE WALL
1/2" = 1'-0"A8.2
9 INTERIOR ELEVATION
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
IO
N
12" = 1'-0"A8.2
7 PICTURE RAIL DETAIL
STREET LEVEL
-14' - 0"
ACOUSTICAL INSULATION
TO METAL DECK
SHIM AS REQ'D
8", 20 GA DBL. HEADER STUDS
5/8" GWB
ALUMINUM GLASS
STOREFRONT WALL
1/
2"
SOUND INSULATION
3 5/8" MTL. STUD
5/8 GWB
LOBBY
S02
PODCAST
SPACE
S05
8" MTL BASE,
SEE FINISH
LEGEND
8"
8" MTL BASE,
SEE FINISH
LEGEND
1095 SF
LOBBY
S02
ACOUSTICAL INSULATION
TO METAL DECK
5/8" GWB
SOUND INSULATION
3 5/8" MTL. STUD
USG PLANX UNIVERSAL
CARRIER COMPONENT
SECURED TO FRAMING
W/ FASTENER
USG PLANX UNIVERSAL
INTEGRAL REVEAL
PANEL FIELD CUT TO
FIT
FASTENER TO BE
INSTALLED EVERY 9"
O.C. TYP.
DONOR SIGNAGE. SEE
INT ELEVATIONS FOR
DETAILS
A
SHEET TITLE:
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
5:
:3
P
M
CONSTRUCTION
A8.3
INTERIOR DETAILS
1 1/2" = 1'-0"A8.3
1 CURTAIN WALL DETAIL
1 1/2" = 1'-0"A8.3
2 WOOD WALL PANEL DETAIL
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
N
.0
3.
C
O N
S T
R U
C T
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
COORDINATE ALL EQUIPMENT AND DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS.
COORDINATE ALL PENETRATIONS THROUGH EXTERIOR WALLS WITH ARCHITECTURAL DRAWINGS.
THE CONTRACTOR SHALL CHECK AND VERIFY ALL CONDITIONS AND DIMENSIONS AT THE SITE BEFORE PROCEEDING WITH THE WORK. THEY SHALL REPORT ANY DISCREPANCIES TO THE ARCHITECT/ENGINEER FOR CORRECTION PRIOR TO BEGINNING ANY WORK. DISCOVERY OF ANY DISCREPANCIES AFTER WORK
HAS COMMENCED SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
DO NOT SCALE THESE DRAWING FOR EXACT DIMENSIONS, VERIFY ALL FIGURES, CONDITIONS,
DIMENSIONS, ETC. AT THE JOB SITE.
THE HVAC CONTRACTOR SHALL CENTER AND/OR ALIGN REGISTERS, DIFFUSERS, AND EQUIPMENT WITH
ADJACENT ARCHITECTURAL FEATURES. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS.
DUCT DIMENSIONS INDICATED ARE CLEAR INSIDE DIMENSIONS.
ALL ROOF CURBS FOR MECHANICAL EQUIPMENT SHALL BE FURNISHED, INSTALLED AND FLASHED BY THE HVAC CONTRACTOR. THE HVAC CONTRACTOR IS RESPONSIBLE FOR ALL HVAC RELATED ROOF WORK, INCLUDING CUTTING AND PATCHING. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR
MAINTAINING THE ROOF WARRANTY.
HVAC CONTRACTOR SHALL REVIEW THE EQUIPMENT SCHEDULES, SPECIFICATIONS, AND DRAWINGS IN ALL CONTRACT DOCUMENTS AND SUBSEQUENT SHOP DRAWINGS AND PROVIDE ALL LABOR AND MATERIAL FOR A COMPLETE AND OPERABLE SYSTEM. FAILURE TO REVIEW THESE DOCUMENTS DOES NOT RELIEVE
THE CONTRACTOR OF FULFILLING THEIR CONTRACTUAL OBLIGATIONS.
REFER TO ARCHITECTURAL DRAWINGS AND SHOP DRAWINGS FOR FINAL CONNECTIONS AND EXACT
LOCATIONS FOR ALL WORK REQUIRED FOR EQUIPMENT NOT FURNISHED UNDER THIS CONTRACT.
COORDINATE INSTALLATION OF NEW WORK WITH ARCHITECTURAL, STRUCTURAL, PLUMBING, POWER AND LIGHTING PLANS. CONTRACTOR SHALL TAKE ALL INTERFERENCE INTO CONSIDERATION. PROVIDE ALL NECESSARY OFFSETS OR TRANSITIONS WITH EQUIVALENT AREAS TO MATCH DUCT SIZES AS INDICATED
ON DRAWINGS.
DO NOT INSTALL ANY MECHANICAL WORK ABOVE OR THROUGH ELECTRICAL ROOMS UNLESS
SPECIFICALLY SERVING THE ELECTRICAL ROOM. DO NOT INSTALL ANY MECHANICAL WORK ABOVE
ELECTRICAL PANELS.
DO NOT INSTALL ANY MECHANICAL WORK ABOVE OR THROUGH ELEVATOR EQUIPMENT ROOMS UNLESS
SPECIFICALLY SERVING EQUIPMENT ROOM.
DO NOT INSTALL ANY MECHANICAL WORK ABOVE OR THROUGH TELECOMMUNICATIONS EQUIPMENT
ROOMS UNLESS SPECIFICALLY SERVING THE TELECOMMUNICATIONS ROOM.
LOCATE ALL EQUIPMENT THAT MUST BE SERVICED, OPERATED, OR MAINTAINED IN FULLY ACCESSIBLE POSITIONS. EQUIPMENT SHALL INCLUDE, VAV BOXES, COILS, VALVES, MOTORS, FANS, CONTROLLERS, DRAIN POINTS, TRAPS, STRAINERS, ETC. THE CONTRACTOR WILL BE REQUIRED TO RE-WORK, AT THEIR
EXPENSE, ANY EQUIPMENT THAT IS DEEMED INACCESSIBLE BY THE OWNER.
THE MOUNTING HEIGHT OF ALL THERMOSTATS, ROOM TEMPERATURE SENSORS, AND/OR HUMIDITY SENSORS, SHALL MATCH THE MOUNTING HEIGHT OF ELECTRICAL LIGHT SWITCHES OR, IN THE ABSENCE
OF NEARBY SWITCHES, BE MOUNTED 44" ABOVE FINISHED FLOOR.
FOR ALL BRANCH DUCT CONNECTIONS TO MAIN TRUNK, PROVIDE 45° TRANSITION FITTING OR CONICAL TAP FOR ROUND DUCT. BUTT FITTINGS ARE NOT PERMITTED. PROVIDE MANUAL VOLUME DAMPER WITH
LOCKING QUADRANT AN ALL BRANCH RUNOUTS TO GRILLES AND DIFFUSERS.
PROVIDE TURNING VANES IN ALL MITERED ELBOWS OR PROVIDE ELBOWS WITH CENTERLINE RADIUS
EQUAL TO 1.5 TIMES DUCT WIDTH.
INSTALL ALL FIRE DAMPERS AND CEILING RADIATION DAMPERS IN STRICT ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATION. PROVIDE UL FIRE DAMPERS WITH BLADES OUT OF AIR STREAM AND ACCESS DOORS. FIRE DAMPERS IN TRANSFER DUCTS ONLY MAY HAVE BLADES IN AIR STREAM.
SLEEVE AND SEAL ALL PIPE OR DUCT PENETRATIONS OF WALL AND FLOORS. PACK VOID BETWEEN PIPE OR DUCT AND SLEEVE WITH INSULATION IN NON-RATED WALLS AND FLOORS. PACK VOID BETWEEN PIPE OR DUCT AND SLEEVE WITH INSULATION IN FIRE-RATED WALLS AND FLOORS, APPLY INTUMESCENT FIRE SAFING COMPOUND AT PENETRATION, MAINTAINING INTEGRITY AND RATING OF FIRE SEPARATION.
SLEEVES THROUGH FLOORS SHALL EXTEND 2" ABOVE FLOOR AND BE GROUTED INTO PLACE AND
WATERPROOFED. PIPING THROUGH EXTERIOR WALLS SHALL BE SLEEVED AND SEALED WEATHER TIGHT.
THE OWNER SHALL HAVE THE OPTION TO RETAIN ANY EQUIPMENT, CONTROLS, PIPING, DUCTWORK, AND
ACCESSORIES SCHEDULED TO BE REMOVED.
SHUTDOWN OF SERVICES SHALL BE COORDINATED AND SCHEDULED WITH THE OWNER.
DUCTWORK AND PIPING THAT REMAIN AFTER DEMOLITION IS COMPLETE, SHALL BE CAPPED AT THE MAIN (IF THEY ARE TO BE TAKEN OUT OF SERVICE), OR PREPARED FOR RECONNECTION (IF THEY ARE
TO BE REUSED).
ALL ABANDONED SYSTEMS AND EQUIPMENT WITHIN THE PROJECT AREA SHALL BE REMOVED.
COORDINATE REMOVAL WITH THE OWNER AND OTHER TRADES.
CEILINGS THAT NEED TO BE TEMPORARILY REMOVED TO ALLOW FOR THE INSTALLATION OF DUCTWORK, PIPING, OR EQUIPMENT SHALL BE REMOVED AND REPLACED BY HVAC CONTRACTOR. ALL FIRE
PROTECTION, ELECTRICAL, MEDICAL GAS, AND SERVICES SHALL ALSO BE INCLUDED.
THE HVAC CONTRACTOR SHALL DISCONNECT AND CAP ALL SUPPLY, RETURN, AND EXHAUST AIR OUTLETS
THAT ARE STILL ACTIVE IN THE PROJECT AREA DURING CONSTRUCTION.
THE HVAC CONTRACTOR SHALL REFER TO THE PHASING PLAN TO DETERMINE THE EXTENT OF WORK AND
TEMPORARY SYSTEM CONNECTIONS NECESSARY FOR EACH PHASE.
ALL DUCT AND UNIT MOUNTED SMOKE DETECTORS FOR MECHANICAL EQUIPMENT AND DAMPERS SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR, WIRED TO FIRE
ALARM SYSTEM BY ELECTRICAL CONTRACTOR, WITH UNIT SHUTDOWN CONTROL WIRING BY THE
MECHANICAL CONTRACTOR.
HVAC CONTRACTOR SHALL PROVIDE ALL TRANSFORMERS AS REQUIRED FOR DUCT-MOUNTED DAMPER
ACTUATORS OR THE DDC CONTROLS SYSTEM.
ALL WORK SHALL BE SCHEDULED AND COORDINATED WITH THE OWNER SO THAT DISRUPTION OF AREAS
INVOLVED IS KEPT TO A MINIMUM. ANY ACCIDENTAL INTERRUPTIONS TO SERVICES SHALL BE
REPAIRED IMMEDIATELY BY THE CONTRACTOR WITH OUT ANY ADDITIONAL COST TO THE OWNER.
PRIOR TO SUBMITTING BIDS AND DURING CONSTRUCTION, THE CONTRACTOR SHALL EXAMINE THE DRAWINGS OF ALL TRADES AND COORDINATE THE INSTALLATION WITH ALL TRADES AND EXISTING CONDITIONS. COORDINATION OF WORK IF NECESSARY SHALL BE PROVIDED AT NO ADDITIONAL COST
TO THE OWNER.
THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT INDICATE ALL OFFSETS, BENDS, ACCESS PANELS, AND SIMILAR PARTS WHICH MAY BE REQUIRED. THE CONTRACTOR SHALL INVESTIGATE THE STRUCTURAL AND FINISH CONDITIONS AFFECTING HIS WORK AND PROVIDE ALL FITTINGS, ACCESS PANELS, AND SIMILAR ACCESSORIES THAT MAYBE REQUIRED TO PROVIDE A COMPLETE AND OPERATING INSTALLATION AT NO
ADDITIONAL COST TO THE OWNER.
INSTALL ROOFTOP EQUIPMENT NOT LESS THAN 10 FEET FROM THE ROOF EDGE OR ANY CHANGE IN ROOF HEIGHT GREATER THAN 2 FEET. WHERE EQUIPMENT MUST BE PLACED WITHIN PARAMETERS LISTED, ARCHITECT MUST PROVIDE A RAIL OR PARAPET ALONG ROOF EDGE IN QUESTION.
PROVIDE 4" THICK CONCRETE PADS FOR EQUIPMENT INSTALLED ON FLOORS OR ON GRADE, 6" LARGER
THAN THE EQUIPMENT ON ALL SIDES.
INSTALL FLEXIBLE DUCTWORK IN A FULLY EXTENDED CONDITION WITHOUT SAGS AND KINKS.
PROVIDE ALL DAMPERS, SHEAVES, AND BELTS AS REQUIRED FOR BALANCING.
THIS CONTRACTOR IS RESPONSIBLE FOR THE CUTTING AND PATCHING OF ALL OPENINGS RELATED TO THEIR WORK. PATCHES SHALL MATCH SURROUNDING WALL AND CEILING SURFACES AND SHALL BE SEALED
AND FIRESTOPPED AS REQUIRED.
INSTALL FIRE DAMPERS AS REQUIRED PER NFPA 101 AND NFPA 90A, (2012 EDITION).
ALL HVAC INSTALLATIONS SHALL COMPLY WITH NFPA 101.
PER NFPA25, SPRINKLER PIPING SHALL NOT BE SUBJECTED TO EXTERNAL LOADS BY MATERIALS EITHER RESTING ON THE PIPE OR HUNG FROM THE PIPE. NO CABLING, SYSTEMS, EQUIPMENT OR ACCESSORIES SHALL BE IN CONTACT WITH SPRINKLER SYSTEM. RELOCATE AND/OR RESUPPORT SYSTEM AS REQUIRED
SO THEY ARE NOT IN CONTACT WITH SPRINKLER PIPING.
10' MINIMUM CLEARANCE BETWEEN ALL OUTSIDE AIR INTAKES, EXHAUSTS AND PLUMBING VENTS. 25'
MINIMUM FOR HEALTHCARE UNLESS NOTED OTHERWISE.
M.C. SHALL PROVIDE CEILING IDENTIFICATION LABELS AT ALL LOCATIONS WHERE SERVICEABLE MECHANICAL EQUIPMENT, DEVICES, VALVES, DAMPERS, CONTROLS, AND SIMILAR COMPONENTS ARE LOCATED ABOVE ACCESSIBLE CEILINGS. LABELS SHALL BE INSTALLED ON THE CEILING GRID OR ACCESS PANEL DIRECTLY BELOW THE ASSOCIATED EQUIPMENT AND SHALL BE IN ACCORDANCE WITH
OWNER LABELING STANDARDS.
ABBREVIATIONS
BALL
BUTTERFLY
GATE
GATE, ANGLE
GLOBE
GLOBE, ANGLE
PLUG
THREE WAY
LEVER
NON-RISING STEM
OUTSIDE STEM & YOKE
GEAR
ELECTRIC, SOLENOID
PNEUMATIC, MOTORM
S
CHECK
NEEDLE
PRESSURE REDUCING
QUICK OPENING
QUICK CLOSING, FUSIBLE LINK
RELIEF (R) OR SAFETY (S)
VALVES FOR SELECTIVE ACTUATORS
VALVE ACTUATORS
SPECIAL DUTY VALVES
HOSE END DRAIN VALVE
R
PIPING SYMBOLS
FLOWMETER, ORIFICE
OFM-1
FLOWMETER, VENTURI
VFM-1
FLOW SWITCHFS
PRESSURE GAUGE, WITH COCKPI
PRESSURE SWITCHPS
PRESSURE GAUGE, COMPOUND
PI
STEAM TRAP, FLOAT AND THERMOSTATIC
THERMOMETER
STRAINER
STRAINER, BLOW OFF
THERMOMETER WELL
TEST PLUG
BALANCING VALVE
G
TRIPLE DUTY
FLOWMETER, ULTRASONIC STRAP-ON
UFM-1
SPECIALTIES (CONT)
TAGS
HEATING COIL
ROOFTOP UNIT
AIR HANDLING UNIT
FAN COIL UNIT
RADIANT CEILING PANEL
ENERGY RECOVERY UNIT
EXHAUST FAN
CONDENSING UNIT
BOILER
PUMP
EXPANSION TANK
NOTE: THIS IS A GENERAL MECHANICAL
LEGEND. ALL SYMBOLS MAY NOT APPEAR
ON THE PLANS. SEE PLANS FOR ACTUAL
SYMBOLS USED.
AUTOMATIC TEMPERATURE CONTROL PANEL
EXISTING PIPINGNAME(EX)
12x20(EX) 12x20(EX)
EXISTING CEILING SUPPLY DIFFUSER/
GRILLE/REGISTER
EXISTING CEILING RETURN
GRILLE/REGISTER
VAV TERMINAL BOX
FIRE DAMPER
TEMPERATURE SENSOR
VOLUME DAMPER
DETAIL #/DRAWING NUMBER
DIFFUSER/GRILLE/REGISTER DESIGNATION AND
FLOW RATE IN CFM
ROOM THERMOSTAT
ACOUSTICALLY LINED DUCT
FLEXIBLE DUCT (INSULATED)
DUCT SYMBOLS
M1
GENERAL
POINT OF CONNECTION TO EXISTING
POINT OF DISCONNECTION
EQUIPMENT IDENTIFICATION TAG
BACKDRAFT DAMPER
DUCT, FIRST FIGURE IS
PLAN DIMENSION
CARBON DIOXIDE SENSOR
(ROOM & DUCT MOUNTED)
ROOM PRESSURE SENSOR/
TRANSMITTER
PIPING SYMBOLS
HIGH-PRESSURE STEAM
MEDIUM-PRESSURE STEAM
LOW-PRESSURE STEAM
HEATING
HIGH-PRESSURE CONDENSATE
MEDIUM-PRESSURE CONDENSATE
LOW-PRESSURE CONDENSATE
BOILER BLOWDOWN
PUMPED CONDENSATE
VACUUM PUMP DISCHARGE
MAKEUP WATER
ATMOSPHERIC VENT
HOT WATER SUPPLY
HOT WATER RETURN
COMPRESSED AIR
PIPE TO BE REMOVED
HPS
MPS
LPS
HPC
MPC
LPC
BBD
PC
VPD
MU
ATV
HWS
HWR
A
NAME
AIR CONDITIONING AND REFRIGERATION
REFRIGERANT SUCTIONRS
REFRIGERANT LIQUIDRL
CONDENSER WATER SUPPLYCWS
CONDENSER WATER RETURNCWR
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
FILL FILL
HUMIDIFICATION LINEH
DRAIND
HEAT PUMP WATER SUPPLYHPWS
HEAT PUMP WATER RETURNHPWR
GENERAL
FITTINGS
PIPE ELBOW UP
PIPE ELBOW DOWN
PIPE TEE DOWN
PIPE TEE UP
UNION
FLANGE
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC
STRAIGHT INVERT
REDUCER, ECCENTRIC
STRAIGHT CROWN
SPECIALTIES
AIR VENT, AUTOMATICAV
AIR VENT, MANUAL
MV
ALIGNMENT GUIDE
ANCHOR
EXPANSION JOINT
EXPANSION LOOP
FLEXIBLE CONNECTOR
EJ-1
EL-1
CAP
COMBINATION FIRE
AND SMOKE DAMPER
SMOKE DAMPER
BDDBDD
12x20 12x20
AD
AD
FLEXIBLE CONNECTION
CEILING SUPPLY DIFFUSER/GRILLE/REGISTER
LINEAR WALL SUPPLY DIFFUSER/
GRILLE/REGISTER WITH PLENUM
LINEAR CEILING SUPPLY DIFFUSER/
GRILLE/REGISTER WITH PLENUM
CEILING RETURN
GRILLE/REGISTER
WALL SUPPLY DIFFUSER/
GRILLE/REGISTER
LINEAR WALL RETURN/EXHAUST
GRILLE/REGISTER WITH PLENUM
LINEAR CEILING RETURN/EXHAUST
GRILLE/REGISTER WITH PLENUM
WALL RETURN/EXHAUST
GRILLE/REGISTER
OUTDOOR AIR LOUVER
EXHAUST AIR LOUVER
WALL TRANSFER GRILLE
ARROW INDICATING FLUID
FLOW DIRECTION
GENERAL
DAMPERS
DIFFUSERS/GRILLES/REGISTERS
EQUIPMENT
EXISTING DUCT
DUCT TO BE REMOVED12x20 12x20
SENSORS
DEMOLITION KEY NOTE
AIRFLOW MEASURING STATION
DUCT SYMBOLS
DUCT SMOKE DETECTOR
PIPE RISER, UP & DN
RECTANGULAR DUCT RISER, UP & DN,
SUPPLY OR OUTDOOR AIR
RECTANGULAR DUCT RISER, UP & DN,
RETURN OR EXHAUST AIR
RECTANGULAR DUCT ELBOW UP,
SUPPLY OR OUTDOOR AIR
RECTANGULAR DUCT ELBOW UP,
RETURN OR EXHAUST AIR
RECTANGULAR DUCT ELBOW DN,
SUPPLY OR OUTDOOR AIR
RECTANGULAR DUCT ELBOW DN,
RETURN OR EXHAUST AIR
RECTANGULAR DUCT TEE UP,
SUPPLY OR OUTDOOR AIR
RECTANGULAR DUCT TEE UP,
RETURN AIR
RECTANGULAR DUCT TEE DN,
SUPPLY OR OUTDOOR AIR
RECTANGULAR DUCT TEE DN,
RETURN AIR
ROUND DUCT RISER, UP & DN
ROUND DUCT ELBOW UP
ROUND DUCT ELBOW DN
ROUND DUCT TEE UP
ROUND DUCT TEE DN
REVISION TAG
AD - ACCESS DOOR
AP - ACCESS PANEL
AD
MOTORIZED DAMPER
BLANKOFF INDICATING NO AIR THROW
TO THIS SIDE
CONDENSATE DRAINCD
M M
(A)240
ROOM HUMIDISTAT
EXISTING DIFFUSER/GRILLE/REGISTER
DESIGNATION AND FLOW RATE IN CFM
(EX)240
D
R
INCLINED RISE, IN DIRECTION
OF AIR FLOW
INCLINED DROP, IN DIRECTION
OF AIR FLOW
D
R
HUMIDITY SENSOR
C02 C02
AFS
S
FD
FSD
SD
HC
HC
RTU
AHU
FC
RCP
ERU
EF
CU
B
P
ET
ATC
VAV
VAV BOX
AIR CONDITIONER
AC
DEDICATED OUTDOOR AIR SYSTEM
DOAS
CABINET UNIT HEATER
CUH
DUCT HEATER
DH
HUMIDIFIER
H
LOUVER
L
VRF
VARIABLE REFRIGERANT FLOW
FD
FSD
SD
RECTANGULAR DUCT TEE UP,
EXHAUST AIR
RECTANGULAR DUCT TEE DN,
EXHAUST AIR
KEY NOTE1
EXISTING CEILING EXHAUST
GRILLE/REGISTER
CEILING EXHAUST
GRILLE/REGISTER
T
H
P
T
H
A COMPRESSED AIR
AC AIR CONDITIONING
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
ADP APPARATUS DEW POINT
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AIR COND AIR CONDITION(-ING, -ED)
AMP AMPS AMPERE(S)
APPROX APPROXIMATE
ATC AUTOMATIC TEMPERATURE CONTROL
ATM ATMOSPHERE
ATV ATMOSPHERIC VENT DUCT DIMENSIONS
(INDICATED ARE CLEAR INSIDE
DIMENSIONS)
AVG AVERAGE
B BOILER
BBD BOILER BLOWDOWN
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BMS BUILDING MANAGEMENT SYSTEM
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
CAV CONSTANT AIR VOLUME
CC COOLING COIL
CCW COUNTERCLOCKWISE
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG CEILING
CMPR COMPRESSOR
CMU CONCRETE MASONRY UNIT
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COND CONDENS(-ER, -ING, -ATION)
CONT. CONTINU(-ED, -ATION)
CORR CORRIDOR
CP CONDENSATE PUMP
CT COOLING TOWER
CU CONDENSING UNIT
CU FT CUBIC FEET
CU IN CUBIC INCH
CUH CABINET UNIT HEATER
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DRAIN
dB DECIBEL
DB DRY-BULB TEMPERATURE
DEG OR ° DEGREE FAHRENHEIT (°F)
DIA OR ∅ DIAMETER DIM DIMENSION
DN DOWN
DPT DEW-POINT TEMPERATURE
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE (°F)
E.C. ELECTRICAL CONTRACTOR
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
EL ELEVATION
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EVAP EVAPORAT(-E, -ING, -ED, -OR)
EWT ENTERING WATER TEMPERATURE (°F)
EX OR EXIST EXISTING
F FAHRENHEIT
FA FACE AREA
FCU FAN COIL UNIT
FD FIRE DAMPER
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPS FEET PER SECOND
FR FINNED RADIATION
FT FEET
FVEL FACE VELOCITY
G GRAINS
GA GAUGE OR GAGE
GAL GALLON
G.C. GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRD GRILLES, REGISTERS, DIFFUSERS
H HUMIDIFICATION
HC HEATING COIL
HD HEAD
HG MERCURY
HGT HEIGHT
HP HORSEPOWER
HPC HIGH PERSSURE CONDENSATE
HPS HIGH PRESSURE STEAM
HPWR HEAT PUMP WATER RETURN
HPWS HEAT PUMP WATER SUPPLY
HR HOUR (S)
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HX HEAT EXCHANGER
HZ HERTZ
ID INSIDE DIAMETER
IN INCH(ES)
KW KILOWATTS
L LOUVER
LAT LEAVING AIR TEMPERATURE (°F)
LBS POUNDS
LF LINEAR FEET
LG LENGTH
LPC LOW-PRESSURE CONDENSATE
LPS LOW-PRESSURE STEAM
LWT LEAVING WATER TEMPERATURE (°F)
MAU MAKEUP AIR UNIT
MAX MAXIMUM
MBH 1000 BTUH
M.C. MECHANICAL CONTRACTOR
MIN MINIMUM
MPC MEDIUM-PRESSURE CONDENSATE
MPS MEDIUM-PRESSURE STEAM
MU MAKEUP WATER
N C NORMALLY CLOSED
N I C NOT IN CONTRACT
N O NORMALLY OPEN
N/A NOT APPLICABLE
NC NOISE CRITERIA
NO NUMBER
NTS NOT TO SCALE
OA OUTSIDE AIR
OAT OUTSIDE AIR TEMPERATURE
OD OUTSIDE DIAMETER
OZ OUNCE
P PUMP
P.C. PLUMBING CONTRACTOR
PC PUMPED CONDENSATE
PD PRESSURE DROP
PH PHASE
PPM PARTS PER MILLION
PRESS PRESSURE
PSI POUNDS PER SQUARE INCH
RA RETURN AIR
RAD RADIAT(-E, -OR)
RB RETURN BEND
RD ROOF DRAIN
RECIRC RECIRCULATE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHP RADIANT HEATING PANEL
RL REFRIGERANT LIQUID
RO ROOF OPENING
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOFTOP UNIT
S SECOND
SA SUPPLY AIR
SAN SANITARY
SEER SEASONAL ENERGY EFFICIENCY RATIO
SH SENSIBLE HEAT
SHG SENSIBLE HEAT GAIN
SHR SENSIBLE HEAT RATIO
SP STATIC PRESSURE (IN. WG.)
SPEC SPECIFICATION
SQ SQUARE
STD STANDARD
SUCT SUCTION
T THERMOSTAT
TD TEMPERATURE DIFFERENCE
TEMP TEMPERATURE (°F)
TH TOTAL HEAT
THKNS THICKNESS
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TV TURNING VANES
TYP TYPICAL
UC UNDERCUT
UH UNIT HEATER
V VOLT
VAC VACUUM, VACUUM AIR
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VENT VENTILATION, VENT
VFD VARIABLE FREQUENCY DRIVE
VFV VAV, WITH FAN
VOL VOLUME
VPD VACUUM PUMP DISCHARGE
W WATT
W/ WITH
WB WET BULB TEMPERATURE (°F)
WC WALL CAP
WD WIDTH
WG WATER GAGE
WMS WIRE MESH SCREEN
WT WEIGHT
W ilk es -B ar re
, P A t:
.8
.1 f:
.8
.0
N . P en ns yl va ni a
A ve w : w w w
.m ra pc .c om
A
SHEET TITLE: 11.03.2026
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
4:
:3
P
M
CONSTRUCTION
M0.0
LEGEND, NOTES AND
DRAWING SCHEDULE
26-CUP-0226-CUP-02 TPTP
MECHANICAL DRAWING LIST
Sheet Number Sheet Name
Sheet Issue Date
M0.0 LEGEND, NOTES AND DRAWING SCHEDULE 11/03/26
M1.1 STREET LEVEL FLOOR PLAN - MECHANICAL DEMOLITION 11/03/26
M2.1 STREET LEVEL FLOOR PLAN - MECHANICAL 11/03/26
IS
S
U E
D A
T E
S
IS
S U
E D
A T
E S
D A
T E
D
A T
E
D E
S C
R
IP
T
IO
N
D E
S C
R
IP
T
IO
V 3-1
VF
3-4
VF
3-5
VF
3-2
VF
3-3
VF
3-1
T
T
T
T
T
44"x14" SA W/FD UP TO RTU-3 ON ROOF 44"x12" RA W/FD UP
TO RTU-3 ON ROOF
10"x10" EA W/FD UP
TO EF-3 ON ROOF
1 1 1
5 5
EUH
EUH
8 8
KEYED MECHANICAL DEMOLITION NOTES:
REMOVE EXISTING SUPPLY AIR DIFFUSER.
REMOVE EXISTING RETURN AIR GRILLE.
EXISTING SERIES FAN-POWERED VAV BOX SHALL REMAIN. TEST, BALANCE, AND ADJUST
PRIMARY MINIMUM, PRIMARY MAXIMUM, AND FAN AIRFLOWS TO VALUES INDICATED IN
THE SCHEDULE. VERIFY FAN, DAMPER, ELECTRIC HEATER, AIRFLOW SENSOR, FILTER, AND
CONTROLS OPERATE PROPERLY.
EXISTING BYPASS VAV BOX SHALL REMAIN. TEST, BALANCE, AND ADJUST MINIMUM AND
MAXIMUM AIRFLOWS TO VALUES INDICATED IN THE SCHEDULE. VERIFY DAMPER,
AIRFLOW SENSOR, STATIC-PRESSURE CONTROL, AND ASSOCIATED CONTROLS OPERATE
PROPERLY.
REMOVE EXISTING WIRE SCREEN AND PREPARE EXISTING DUCTWORK FOR CONNECTION
TO DUCT EXTENSION WITH SOUND ATTENUATION ELBOW.
FIELD VERIFY EXACT LOCATION OF EXISTING VF-3-3. IF LOCATED ABOVE NEW IT
CLOSET, DISCONNECT UNIT AND REMOVE ASSOCIATED DUCTWORK, SUPPORTS, AND
CONNECTIONS AS REQUIRED FOR RELOCATION. PROTECT AND RETAIN UNIT FOR
REINSTALLATION.
REMOVE EXISTING DUCTWORK AND BALANCING DAMPER BACK TO POINT OF
CONNECTION AS REQUIRED TO RELOCATE BALANCING DAMPER OUTSIDE THE AREA
ABOVE THE NEW SLAT CEILING. COORDINATE WITH NEW WORK AND PROVIDE ACCESS TO
THE RELOCATED DAMPER FOR ADJUSTMENT AND MAINTENANCE.
REMOVE EXISTING CEILING-MOUNTED ELECTRIC CABINET HEATER AND ASSOCIATED
MOUNTING HARDWARE. COORDINATE ELECTRICAL DISCONNECTION WITH ELECTRICAL
CONTRACTOR. PREPARE EXISTING CEILING OPENING AND SUPPORTS FOR
INSTALLATION OF NEW HEATER; MODIFY AS REQUIRED TO SUIT NEW UNIT.
EXISTING BYPASS VAV BOX SCHEDULE (FOR REFERENCE ONLY)
TAG SERVICE MANUFACTURER MODEL / UNIT SIZE
INLET DIA.
(IN.)
MAX
CFM
MIN CFM
INLET PD IN.
WG
NOTES
V-3-1
RTU-3 SUPPLY-TO-
RETURN BYPASS
CARRIER MODEL 35K / SIZE 12 12 2,000 420 0.03
1-5
NOTES:
1. EXISTING V-3-1 BYPASS VAV BOX SHALL REMAIN. VERIFY MODEL, INLET SIZE, DAMPER OPERATION, AIRFLOW SENSOR, AND ACCESSIBILITY IN FIELD.
2. V-3-1 SHALL MODULATE BETWEEN 420 CFM MINIMUM AND 2,000 CFM MAXIMUM TO MAINTAIN THE EXISTING RTU-3 SUPPLY-DUCT STATIC-PRESSURE SETPOINT.
3. CONTROLS CONTRACTOR SHALL VERIFY THE EXISTING STATIC-PRESSURE SENSOR LOCATION AND SETPOINT. BYPASS AIRFLOW SHALL DECREASE AS ZONE
PRIMARY-AIR DAMPERS OPEN.
4. CALCULATED BYPASS AIRFLOW AT THE REVISED VF MINIMUMS EQUALS RTU-3 SUPPLY AIRFLOW LESS THE TOTAL REVISED OCCUPIED PRIMARY-AIR MINIMUM.
INDIVIDUAL VF MAXIMUMS ARE NONCOINCIDENT. VERIFY FINAL VALUES AFTER TAB OF RTU-3 AND ALL VF BOXES.
5. TEST AND BALANCE CONTRACTOR SHALL RECORD BYPASS AIRFLOW AT FULL OPEN, DAMPER POSITION, INLET STATIC PRESSURE, AND SYSTEM STATIC PRESSURE.
SUBMIT RESULTS WITH THE FINAL TAB REPORT.
EXISTING SERIES FAN POWER VAV BOX SCHEDULE (FOR REFERENCE ONLY)
TAG SERVED SPACE MANUFACTURER MODEL / UNIT SIZE
INLET DIA.
(IN.)
EXIST.
PRIMARY MAX
CFM
REVISED REVISED
PRIMARY MAX PRIMARY MAX
CFMCFM
EXIST.
PRIMARY
MIN CFM
REVISED REVISED
PRIMARY PRIMARY
MIN CFMMIN CFM
OA AT OA AT
REVISED REVISED
MIN CFMMIN CFM
EXIST.
FAN CFM
REVISED REVISED
FAN CFMFAN CFM
FAN HP HEAT kW
HEAT
MBH
EXIST. EAT
°F
EXIST. LAT
°F
CALC. MIXED
EAT °F
CALC. LAT CALC. LAT
°F°F
POWER
NOTES
VF-3-1 MAIN ENTRY LOBBY CARRIER 45J-DDC / SIZE 06 12 1,860 1,6701,670 370 900900 301301 1,860 1,7501,750 3/4 13.0 44.37 67.0 89.0 63.8 86.786.7 208V / 3PH / 60HZ 1-6 VF-3-2 CORRIDOR CARRIER 45JN / SIZE 02 6 480 400400 205 400400 134134 480 425425 1/10 4.5 15.00 63.0 93.0 57.8 89.589.5 208V / 3PH / 60HZ 1-6 VF-3-3 PODCAST STUDIO CARRIER 45JN / SIZE 04 8 610 700700 265 380380 127127 785 735735 1/4 5.5 18.00 66.0 88.0 63.8 86.886.8 208V / 3PH / 60HZ 1-6 VF-3-4 CLASSROOM 01 CARRIER 45JN / SIZE 04 8 810 915915 350 520520 174174 810 950950 1/4 7.0 24.00 63.0 90.0 64.9 86.086.0 208V / 3PH / 60HZ 1-6 VF-3-5 CLASSROOM 02 CARRIER 45JN / SIZE 04 8 840 915915 360 520520 174174 840 950950 1/4 7.5 25.00 63.0 91.0 65.2 87.687.6 208V / 3PH / 60HZ 1-6
1. EXISTING SERIES FAN-POWERED VAV BOXES SHALL REMAIN. SCHEDULE DATA IS BASED ON EXISTING DOCUMENTS. VERIFY MODEL, INLET SIZE, ELECTRICAL DATA, HEATER CAPACITY, AND ACCESSIBILITY IN FIELD BEFORE WORK.
2. TEST AND BALANCE CONTRACTOR SHALL INSPECT EACH BOX, CLEAN OR REPLACE FILTERS, VERIFY FAN ROTATION AND OPERATION, CALIBRATE THE PRIMARY AIRFLOW SENSOR, AND SET THE REVISED PRIMARY MAXIMUM, PRIMARY MINIMUM, AND FAN AIRFLOWS SHOWN.
3. SERIES FAN SHALL OPERATE CONTINUOUSLY DURING OCCUPIED MODE. PRIMARY-AIR DAMPER SHALL MODULATE BETWEEN THE SCHEDULED MINIMUM AND MAXIMUM AIRFLOWS IN RESPONSE TO ZONE COOLING DEMAND. EXISTING ELECTRIC HEAT SHALL OPERATE IN SEQUENCE WITH THE PRIMARY DAMPER AT
MINIMUM AIRFLOW.
4. REVISED PRIMARY MINIMUMS ARE BASED ON THE 2021 IMC MULTIPLE-ZONE RECIRCULATING SYSTEM METHOD, 0.85 OCCUPANT DIVERSITY, MAXIMUM ZP NOT GREATER THAN 0.55, EV OF 0.60, AND RTU-3 MINIMUM OUTDOOR AIRFLOW OF 1,540 CFM. BALANCE AND VERIFY ACTUAL OUTDOOR AIRFLOW.
5. CALCULATED MIXED EAT IS BASED ON 55°F PRIMARY AIR AT THE REVISED PRIMARY MINIMUM MIXED WITH 72°F PLENUM RETURN AIR FOR THE BALANCE OF THE FAN AIRFLOW. CALCULATED LAT USES THE MIXED EAT, EXISTING HEATER kW, AND REVISED FAN AIRFLOW. VERIFY ACTUAL TEMPERATURES AND HEATER
STAGING DURING TAB.
6. SUBMIT A FINAL TAB REPORT LISTING MEASURED PRIMARY MINIMUM, PRIMARY MAXIMUM, FAN DISCHARGE AIRFLOW, INLET STATIC PRESSURE, AND HEATING DISCHARGE TEMPERATURE FOR EACH BOX.
EXISTING GAS FIRED ROOFTOP UNIT SCHEDULE (FOR REFERENCE ONLY)
TAG
BASIS OF DESIGN SUPPLY FAN COOLING GAS HEATING FILTRATION ELECTRICAL DATA
NOTES
MANUFACTURER MODEL
TOTAL
CFM
O/A
CFM
E.S.P.
(IN. WG)
T.S.P.
(IN. WG)
RPM HP
DRIVE
TYPE
TOTAL
MBH
SENS.
MBH
EAT
DB (°F)
EAT
WB (°F)
LAT
DB (°F)
LAT
WB (°F)
INPUT
MBH
OUTPUT
MBH
EAT
DB (°F)
LAT
DB (°F)
FUEL
EFF.
STAGES PRE FINAL VOLTAGE FLA MCA MOCP STAGES
WEIGHT
(LBS)
RTU-3 CARRIER 48HJD012 4,600 1,540 2.0 — 1,282 5 — 131.4 99.9 81.9 68.5 61.8 — 180.0 147.5 — EAT + 29.7 NATURAL GAS 81.9 2 30% — 208/3/60 — 63.4 70.0 2 — 1-9
NOTES:
1. EXISTING RTU-3 SHALL REMAIN. VERIFY MANUFACTURER, MODEL, NAMEPLATE DATA, ELECTRICAL CHARACTERISTICS, SERVICE CLEARANCES, AND CONDITION IN FIELD.
2. TEST AND BALANCE RTU-3 TO 4,600 CFM SUPPLY AIR AND NOT LESS THAN 1,540 CFM OUTDOOR AIR DURING OCCUPIED OPERATION. VERIFY AIRFLOW AT THE OUTDOOR-AIR INTAKE.
3. VERIFY OUTDOOR-AIR DAMPER AND ECONOMIZER OPERATION. MINIMUM OUTDOOR AIR SHALL BE MAINTAINED DURING OCCUPIED MODE; OUTDOOR AIR MAY INCREASE TO 4,600 CFM WHEN ECONOMIZER CONDITIONS PERMIT.
4. VERIFY EXISTING POWER EXHAUST FAN OPERATION AND BALANCE TO 3,850 CFM AT FULL OPERATION. COORDINATE POWER EXHAUST WITH ECONOMIZER AND BUILDING PRESSURE CONTROL.
5. COORDINATE RTU-3 OPERATION WITH THE SERIES FAN-POWERED VAV BOXES AND V-3-1 BYPASS VAV. BYPASS VAV SHALL MODULATE BETWEEN 420 AND 2,000 CFM TO MAINTAIN THE EXISTING SUPPLY-DUCT STATIC-PRESSURE SETPOINT.
6. INSPECT AND CLEAN EXISTING COILS, DRAIN PAN, FILTER SECTION, DAMPERS, FANS, BELTS, AND ASSOCIATED CONTROLS. REPLACE DAMAGED OR DETERIORATED COMPONENTS AS REQUIRED.
7. COOLING LAT DB OF 61.8°F AND HEATING OUTPUT OF 147.5 MBH ARE CALCULATED FROM THE SCHEDULED AIRFLOW, SENSIBLE CAPACITY, AND 29.7°F TEMPERATURE RISE. VERIFY ACTUAL OPERATING TEMPERATURES AND NAMEPLATE PERFORMANCE IN FIELD.
8. SUBMIT A FINAL TAB REPORT LISTING SUPPLY, OUTDOOR, RETURN, RELIEF/EXHAUST, AND BYPASS AIRFLOWS; FAN SPEED; EXTERNAL STATIC PRESSURE; DAMPER POSITIONS; AND OPERATING TEMPERATURES.
9. FOR REFERENCE ONLY
W ilk es -B ar re
, P A t:
.8
.1 f:
.8
.0
N . P en ns yl va ni a
A ve w : w w w
.m ra pc .c om
A
SHEET TITLE: 11.03.2026
SHEET NUMBER:
B C D E F G H I J
A B C D E F G H I J
S E
A L:
PROJ # : DRAWN BY :
C O
N S
U
LT
A N
T
T H
IS
D
R A
W
IN
G I
S T
H E
P R
O P
E R
T Y
O F
T H
E A
R C
H
IT
E C
T A
N D
M A
Y N
O T
B E
P R
O D
U C
E D
I N
A N
Y F
O R
M W
IT
H
O U
T W
R
IT
T E
N P
E R
M
IS
S
IO
N
/2
/2
4:
:3
P
M
CONSTRUCTION
M1.1
STREET LEVEL FLOOR
PLAN - MECHANICAL
DEMOLITION
SCALE:M1.1 3/16" = 1'-0"
1 STREET LEVEL PLAN - MECHANICAL DEMOLITION
THE FOLLOWING SUMMARIZES THE EXISTING CONTROL DOCUMENTATION. VERIFY ACTUAL
EQUIPMENT, CONTROLS, SETPOINTS, AND OPERATION IN THE FIELD PRIOR TO PERFORMING
WORK.
OCCUPIED OPERATION
1. RTU-3 SHALL OPERATE CONTINUOUSLY IN “HAND,” REMAIN OFF IN “OFF,” AND BE
CONTROLLED BY THE DDC SYSTEM IN “AUTO.”
2. FAN F-3 SHALL BE INTERLOCKED WITH RTU-3 AND SHALL START UPON PROOF OF
OUTDOOR-AIR DAMPER D-1 END SWITCH.
3. UPON A CALL FOR OPERATION, THE ASSOCIATED SMOKE DAMPER SHALL OPEN. THE SUPPLY
FAN SHALL START UPON PROOF OF THE DAMPER END SWITCH. THE DAMPER SHALL CLOSE
UPON FAN SHUTDOWN.
4. DISCHARGE-AIR SENSOR T-1 SHALL MAINTAIN A 55°F SUPPLY-AIR TEMPERATURE
SETPOINT. THE SETPOINT SHALL RESET BASED ON FAN-POWERED BOX PRIMARY-AIR
DAMPER POSITIONS.
5. A CURRENT SENSOR SHALL MONITOR SUPPLY-FAN OPERATING STATUS.
6. WHEN MIXED-AIR TEMPERATURE RISES ABOVE THE ADJUSTABLE 55°F SETPOINT OF
SENSOR T-3, OUTDOOR-AIR AND RETURN-AIR DAMPERS D-1 AND D-2 SHALL MODULATE TO
PROVIDE ECONOMIZER COOLING.
7. WHEN MIXED-AIR TEMPERATURE FALLS BELOW SETPOINT, THE GAS-FIRED HEATING
SECTION SHALL STAGE AS REQUIRED.
8. MIXED-AIR LOW-LIMIT SENSOR T-3 SHALL OVERRIDE ECONOMIZER OPERATION TO
MAINTAIN A MINIMUM MIXED-AIR TEMPERATURE OF 50°F.
9. WHEN ECONOMIZER CONDITIONS ARE NOT AVAILABLE, DAMPERS D-1 AND D-2…
This is the start of the file's text. The full file is on GovTribe.