This document comprises architectural and engineering drawings and specifications for the Building Technologies Center HVAC and Plumbing Lab Improvements renovation project at Pennsylvania College of Technology in Williamsport, Pennsylvania. The construction documents include structural, mechanical, electrical, and fire protection design details prepared by BRIX Design Group, LLC, with project number 4000-005 and EDA number 01-79-15372. The scope encompasses renovation of an existing plumbing laboratory with selective demolition of existing equipment, installation of new HVAC systems including four rooftop units (RTU-7 through RTU-10) and two air handling units (AHU-1 and AHU-2), replacement lighting systems with LED fixtures and occupancy controls, electrical service upgrades including new panelboard BTC-115-A, plumbing modifications, and fire protection system installation. The project documents indicate a mandatory pre-bid meeting scheduled for 10:00 AM on Wednesday, April 1, 2026, at the Kenneth Carl Building Technologies Center's north entrance, with bids due by 2:30 PM on Wednesday, April 15, 2026, via the PennBid Program. The project is subject to Pennsylvania Prevailing Wage Act requirements, and bidders must submit a bid bond or certified check equal to ten percent of the proposal amount.
The construction documents detail extensive mechanical specifications including four TRANE rooftop units (25-30 tons cooling capacity), two TRANE air handling units with hydronic heating options, chilled water units, and associated ductwork, piping, and controls. Electrical work includes installation of multiple LED lighting fixtures with occupancy sensors, a new 60-ampere electrical loadcenter, motor disconnects, and fire alarm system integration. Structural modifications include joist reinforcement, roof framing modifications for equipment support, and stair framing with wood components. The fire protection system design specifies a wet sprinkler system for laboratory areas with 0.40 density coverage per NFPA-13 Extra Hazard Group 2 criteria. Estimated water flow data indicates 493 gallons per minute available at 54 pounds per square inch static pressure. The documents note this is a qualifications-based selection process with the top four firms to be shortlisted for further consideration, and the overall project is estimated at a construction budget between $10-20 million for the Diesel Technology Instructional Building at the Schneebeli Earth Science Center, though these specific drawings pertain to the Plumbing Lab renovation component.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JOIST TOP CHORD REINFORCING -
SEE DETAIL /E S201
6" MIN.
17'-0" +/-
6" MIN.
ROOFTOP UNIT - SEE
MECHANICAL DWGS.
40'-0" +/- (V.I.F.)
REINFORCE WEB -
SEE DETAIL /D S201
NOTE:
FOR JOIST REINFORCING AT ALL POINT
LOADS - SEE DETAIL /B S201
ROOFTOP UNIT - SEE
MECHANICAL DWGS.
40'-0" +/- (V.I.F.)
JOIST TOP CHORD REINFORCING -
SEE DETAIL /E S201
REINFORCE WEB -
SEE DETAIL /D S201
21'-0" +/-
NOTE:
FOR JOIST REINFORCING AT ALL POINT
LOADS - SEE DETAIL /B S201
6" MIN. 6" MIN.
ROOFTOP UNIT - SEE
MECHANICAL DWGS.
40'-0" +/- (V.I.F.)
REINFORCE WEB -
SEE DETAIL /D S201
NOTE:
FOR JOIST REINFORCING AT ALL POINT
LOADS - SEE DETAIL /B S201
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
3 2 1456
A
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX
Design Group, LLC whether the project for which they are made is executed or not. All rights reserved.
Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
50% CONSTRUCTION DOCUMENTS 05/21/25
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
EDA # 01-79-15372
215 EAST 3RD STREET, WILLIAMSPORT, PA 17701
570 215 5660 | WWW.BRIXDG.COM
250334
PERMIT SET 06/27/25
S001
BUILDING TECHNOLOGIES CENTER
HVAC & PLUMBING LAB
IMPROVEMENTS
GENERAL STRUCTURAL NOTES AND
DETAILS
4000-005
06-27-25
ONE COLLEGE AVENUE
WILLIAMSPORT, PA 17701
PERMIT SET
NO SCALE
(E) JOIST REINFORCING ELEVATION R1
NO SCALE
(E) JOIST REINFORCING ELEVATION R2
NO SCALE
(E) JOIST REINFORCING ELEVATION R3
# DESCRIPTION DATE
brt10 Image brt10 Rectangle
25'-0" +/- 25'-0" +/- 25'-0" +/- 25'-0" +/-e13e12e11e10e9 eB eB.5 eC eD eE eF eC.5 eD.5 eE.5
'-0
'-0
'-0
'-0
'-0
'-0
'-8
'-4
'-0
'-0
'-0
'-0
(E )W x3
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )W x4
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )W x3
(E
)W x3
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H 8(E
)W x4
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H 8(E
)2 4H
(E )W x3
(E)W16x31 (E)W16x31 (E)W16x31 (E)W16x31
(E)W16x40(E)W16x36(E)W16x40
(E)W16x40(E)W16x36(E)W16x40
(E)W16x40 (E)W16x36 (E)W16x40
(E )W x3
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )W x4
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )W x3
(E
)W x3
(E )2
4H
(E )2
4H
(E )2
4H
(E)W16x40 (E)W16x36 (E)W16x40
(E )W x3
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H
(E )2
4H 8(E
)W x4
(E )2
4H
(E )2
4H
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E) BEAM REINFORCEMENT B1
(E) BEAM REINFORCEMENT B1
(E) BEAM REINFORCEMENT B1
(E) BEAM REINFORCEMENT B1
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
6,000+/- LB. MECHANICAL
ROOFTOP UNIT (TYP. 4)
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
(E
JO
IS
T R
E
IN
F O
R C
E M
E N
T R
PLAN NOTES
1. BMD EL. = (+x'-x") INDICATES BOTTOM OF METAL DECK ELEVATION ABOVE REFERENCE ELEVATION (0'-0")
UNLESS NOTED.
2. SEE S001 FOR GENERAL STRUCTURAL NOTES.
3. COORDINATE SIZE AND LOCATION OF ALL OPENINGS AND SLEEVES WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS. PROVIDE ROOF FRAMES FOR ALL OPENINGS > 10" DIAMETER.
SEE DETAIL . COORDINATE WITH OTHER TRADES.
4. REINFORCE (E) JOISTS AT CONCENTRATED LOADS APPLIED BETWEEN PANEL POINTS. SEE DETAIL
COORDINATE WITH OTHER TRADES.
5. SEE S001 FOR (E) JOIST REINFORCEMENT DIAGRAMS.
6. FOR (E) BEAM REINFORCEMENT NOTED ON PLAN, SEE DETAIL
/C S201
/B S201
/F S201
CENTERLINE OF
(E) STEEL JOIST
(TYPICAL)
ANGLE BRACKET
(TYPICAL)
OPENING
CHANNEL HEADERS EACH SIDE
WITH HANGER CLIPS EACH END
(E) METAL ROOF DECK 1/2" DIA. RODS AT 8" O.C. - REMOVE
AFTER EQUIPMENT, ETC. IS INSTALLED
REINFORCE (E) JOISTS
IN ACCORDANCE WITH
DETAIL
(E) STEEL JOIST
L6x4x3/8 (LLH) x 0'-4" LONG
(4 REQUIRED PER OPENING).
COORDINATE LOCATIONS TO
ALIGN WITH HIGH FLUTES.
C5x6.7 FRAME
TYP.
TYP.
C1
SECTION
C1
MAX. (TYP.)
1/2" GAP
PLAN VIEW
/B S201
NOTES:
1. REFER TO ARCHITECTURAL, MECHANICAL AND ELECTRICAL
DRAWINGS FOR EXACT NUMBER, SIZE AND LOCATION. PROVIDE
FRAMES FOR ALL OPENINGS GREATER THAN 10" DIAMETER.
2. PROVIDE RADIUSED CORNERS IN ACCORDANCE WITH AISC.
9"
3" 3"
3"
NOTE 2
NOTES:
1. EQUIPMENT CONNECTIONS TO SUPPORTING STRUCTURE SHALL
BE PROVIDED BY THE CONTRACTOR AND IN ACCORDANCE WITH
MANUFACTURER'S SPECIFICATIONS.
SECTION
A1
PLAN VIEW
ROOF PENETRATION, PROVIDE FRAME
FOR SUPPORT OF ROOF DECK AND
PROVIDE TEMPORARY INFILL RODS.
SEE DETAIL .
C5x6.7 CHANNELS
(TYPICAL AT PERIMETER
OF EQUIPMENT/CURB)
(E) ROOF FRAMING (TYPICAL)
(E) ROOF FRAMING
(TYPICAL)
L6x4x3/8 (LLH) x 0'-4" LONG
(TYPICAL)
TOP OF CHANNEL TO MATCH
TOP OF (E) STEEL JOIST
CLIP HORIZONTAL LEGS OF HANGER ANGLES SO
VERTICAL LEG FITS TIGHT AGAINST ROOF FRAMING.
FOR LOCATIONS WHERE DECK IS EXISTING AND TO
REMAIN, PROVIDE (1) L7x4x3/8 (LLH) OVERLAPPED ON TOP OF (1) L6x4x3/8 (LLH).
FIT TIGHT OR CLIP L3x3x1/4
(CONTRACTOR OPTION)ROOFTOP
EQUIPMENT / CURB
PROVIDE FRT WOOD BLOCKING
IN HIGH FLUTES OF DECK AT
PERIMETER OF UNIT CURB
ANGLE TO
JOIST, TYP.A1
/C S201
EXISTING JOIST TOP
CHORD ANGLES
(2) 1 1/8" DIA. RODS
2-12
6" AT EACH END
NEW ANGLE REINFORCING
EXISTING ROD WEB
SECTION
D1
D1
L1 1/2 x 1 1/2 x 3/16 EACH SIDE
1/8 1 1/2
1/8 1 1/2
(E) JOIST
(2) L1 1/2x 1 1/2x 3/16 STIFFENERS
FROM LOAD TO JOIST PANEL POINT
(1 NEAR SIDE AND 1 FAR SIDE)
THRU-BOLT JOIST CHORD AND
PROVIDE 3"x3"x1/4" PLATE
WASHER AND NUT BOTH
SIDES OF CHORD ANGLES
STIFFENER ANGLES REQUIRED
WHERE CONCENTRATED LOAD IS
MORE THAN 3" AWAY FROM JOIST
TOP OR BOTTOM CHORD PANEL
POINT AND LOAD EXCEEDS 100 LBS.
PIPE HANGER
ROOFTOP EQUIPMENT / CURB
(E) METAL ROOF DECK
SEE TYPICAL SUPPLEMENTAL
SUPPORT FRAMING FOR ROOFTOP
EQUIPMENT DETAIL
(E) STEEL JOIST
(2) L1 1/2x1 1/2x3/16 STIFFENERS
FROM LOAD TO JOIST PANEL POINT
(1 NEAR SIDE AND 1 FAR SIDE)
SUPPORT ANGLE
BY OTHERS
HANGER FOR MECHANICAL
UNIT, CONVEYOR OR SIMILAR
POINT LOADING
1/8
TYP.
STIFFENER ANGLES REQUIRED
WHERE LOADS DO NOT OCCUR
AT PANEL POINTS
STIFFENER ANGLES
REQUIRED WHERE LOADS
DO NOT OCCUR AT PANEL
POINTS
/A S201
1/4 2-12
10" AT
EACH END
(TYPICAL)
(E) STEEL BEAM
L2 1/2x2 1/2x3/8 FULL
LENGTH EACH SIDE
RENOVATION
AREA
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
3 2 1456
A
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX
Design Group, LLC whether the project for which they are made is executed or not. All rights reserved.
Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
50% CONSTRUCTION DOCUMENTS 05/21/25
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
EDA # 01-79-15372
215 EAST 3RD STREET, WILLIAMSPORT, PA 17701
570 215 5660 | WWW.BRIXDG.COM
250334
PERMIT SET 06/27/25
S201
BUILDING TECHNOLOGIES CENTER
HVAC & PLUMBING LAB
IMPROVEMENTS
ROOF FRAMING PLAN AND DETAILS
4000-005
06-27-25
ONE COLLEGE AVENUE
WILLIAMSPORT, PA 17701
PERMIT SET
PLAN
NORTH
SCALE: 1/8" = 1'-0"
ROOF FRAMING PLAN
NO SCALES201
C TYPICAL DECK OPENING IN (E) FRAMING
NO SCALES201
A
TYPICAL SUPPLEMENTAL SUPPORT FRAMING FOR ROOFTOP
EQUIPMENT
NO SCALES201
E (E) JOIST TOP CHORD REINFORCING
NO SCALES201
D (E) JOIST DIAGONAL WEB REINFORCING
NO SCALES201
B TYPICAL (E) JOIST REINFORCING AT POINT LOADINGS
NO SCALES201
F (E) BEAM REINFORCING B1
NORTH
NO SCALE
KEY PLAN
# DESCRIPTION DATE
brt10 Image e13e12e11e10e9 eB eB.5 eC eC.5
6x 66x6
6x 66x6
4x4 4x
4x44x
6x 66x6
6x6 6x
4x4
4x 44x4
4x 4 4x4
6x66x
6x 6 6x6
6x66x
6x 6 6x6
4x4
S202
5' -1
/8
6'
-0
6' -1
0"
4'-0"
5' -1
/8
6'
-0
6' -1
0"
4'-0"
2x8
(2) 2x10
(2) 2x10
(2
2x
(2
2x
4' -0
5'
-6
4' -0
6'-5" 4'-0" 6'-5"
6'-5" 4'-6" 6'-5"
4' -6
5'
-6
4' -6
2x
(2) 2x10
(2) 2x10
(2
2x
(2
2x
(2
2x
2x
2x
(2) 2x12
2x12
2x12
(2) 2x12
2x12
2x12
2x
(2) 2x10
(2) 2x10
(2
2x
(2
2x
(2
2x
2x
2x
(2) 2x10
(2) 2x10
(2
2x
(2
2x 10 2x8 (2) 2x12
2x12
2x12
(2) 2x12
2x12
2x12
2x
(2) 2x10
(2) 2x10
(2
2x
(2
2x
(2
2x
2x
2x
(2
2x
2x
2x
2x
(2) 2x10
(2) 2x10
(2
2x
(2
2x
S202
S202
S202
S202
SIM
SIM
SIM
S202
S202
S202
SIM
SIM
SIM
FINISH FLOOR EL.
EL. = (0'-0")
TOP OF LOWER MEZZ. SLAB
EL. = (8'-2")
SIMPSON RPBZ POST
BASE CLIP TO SLAB (TYP.)
(E) CONCRETE SLAB
WOOD POST - SEE PLAN
(TYPICAL)
WOOD FRAMING -
SEE PLAN
SIMPSON HGMA10 CLIP EACH
SIDE AT STRINGER TO SLAB -
(2) EACH SIDE AT DOUBLE
STRINGERS
SIMPSON LSCZ STRINGER TO BEAM
CONNECTOR AT SINGLE STRINGERS,
SIMPSON LSSR210-2Z JOIST HANGER
AT DOUBLE STRINGERS - SEE PLAN
(TYPICAL)
POSTS, GUARD AND
RAILING - SEE
ARCHITECTURAL DWGS.
TREADS AND RISERS -
SEE ARCHITECTURAL
DWGS.
SIMPSON LU28
HANGER AT JOIST
(TYPICAL)
SIMPSON
BEAM HANGER
(TYPICAL)
STAIR STRINGERS -
SEE PLAN (TYPICAL).
CENTER STRINGERS AND
STRINGERS AGAINST WALLS
TO BE NOTCHED - SEE
ARCHITECTURAL DWGS.
(FIELD VERIFY)
PLYWOOD SHEATHING -
SEE GENERAL
STRUCTURAL NOTES
2" M
IN
3" M
IN
2" M
IN
(2) 1/2" DIA.
THRU-BOLTS
STUD WALL BEYOND - SEE
ARCHITECTURAL DWGS. FASTEN SILL
PLATE TO (E) CONCRETE SLAB WITH
3/8" DIA. SIMPSON TITEN HD SCREWS
WITH 3" EMBEDMENT INTO (E) SLAB.
NOTE:
STAIR STRINGERS AGAINST WALLS TO
BE FASTENED TO EACH WALL STUD WITH
(2) 10d NAILS - SEE ARCHITECTURAL
DWGS. FOR WALL INFORMATION
PLAN NOTES
1. SEE S001 FOR GENERAL STRUCTURAL NOTES.
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
3 2 1456
A
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX
Design Group, LLC whether the project for which they are made is executed or not. All rights reserved.
Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
50% CONSTRUCTION DOCUMENTS 05/21/25
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
EDA # 01-79-15372
215 EAST 3RD STREET, WILLIAMSPORT, PA 17701
570 215 5660 | WWW.BRIXDG.COM
250334
PERMIT SET 06/27/25
S202
BUILDING TECHNOLOGIES CENTER
HVAC & PLUMBING LAB
IMPROVEMENTS
STAIR FRAMING PLANS AND DETAILS
4000-005
06-27-25
ONE COLLEGE AVENUE
WILLIAMSPORT, PA 17701
PERMIT SET
NORTH
NO SCALE
STAIR FRAMING PLANS
SECTION
S202 SCALE: 1/2" = 1'-0"
# DESCRIPTION DATE
brt10 Image
AB ABOVE
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AHJ AUTHORITY HAVING JURISDICTION
ARCH ARCHITECTURAL
BDD BACK DRAFT DAMPER
BEL BELOW
BFF BELOW FINISH FLOOR
BFG BELOW FINISH GRADE
BFP BACKFLOW PREVENTER
BJ BETWEEN JOISTS
BOD BOTTOM OF DUCT
BTM BOTTOM
BTU BRITISH THERMAL UNIT
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEANOUT
CONN CONNECT / CONNECTION
CONT CONTINUED / CONTINUATION
COORD COORDINATE
CW DOMESTIC COLD WATER
DB DRY BULB
DEG,° DEGREE
DIA, ∅ DIAMETER
DISC DISCONNECT
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
ER EXHAUST REGISTER
ESP EXTERNAL STATIC PRESSURE
EWB ENTERING WET BULB TEMPERATURE
EWT ENTERING WATER TEMPERATURE
EX, (E) EXISTING
FD FIRE DAMPER / FLOOR DRAIN
FLA FULL LOAD AMPERES
FLEX FLEXIBLE
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT / FEET / FIN TUBE
FT HD FEET OF HEAD
GA GAUGE / GAGE
GAL GALLON
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HC HVAC CONTRACTOR
HD HUB DRAIN
HORZ HORIZONTAL
HP HORSE POWER
HSTAT HUMIDISTAT
ID INSIDE DIAMETER
IN, " INCHES
INS INSULATION
INV INVERT
ISP INTERNAL STATIC PRESSURE
IWG INCHES WATER GAUGE
LAT LEAVING AIR TEMPERATURE
LF LINEAR FEET
LB, # POUNDS
LDB LEAVING DRY BULB TEMPERATURE
LWB LEAVING WET BULB TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MOCP MAXIMUM OVERCURRENT PROTECTION
MOD MOTOR OPERATED DAMPER
MFR MANUFACTURER
MIN MINIMUM
MTD, MTG MOUNTED, MOUNTING
NC NOISE CRITERIA
NIC NOT IN CONTRACT
OA OUTSIDE AIR
OAC OPEN ABOVE CEILING
OAI OUTSIDE AIR INTAKE
OC ON CENTER
ORD OVERFLOW ROOF DRAIN
OSW OVERFLOW STORM WATER
PC PLUMBING CONTRACTOR
PH PHASE
PRV PRESSURE REDUCING VALVE /
PRESSURE RELIEF VENT
PSI POUNDS PER SQUARE INCH
RA RETURN AIR
RD ROOF DRAIN
RG RETURN GRILLE
RPM REVOLUTIONS PER MINUTE
RWC RAINWATER CONDUCTOR
RX REMOVE EXISTING
S&C STUB AND CAP
SA SUPPLY AIR
SAN SANITARY
SD SMOKE DETECTOR
SF SQUARE FEET
SG SUPPLY GRILLE
SPEC SPECIFICATIONS
SR SUPPLY REGISTER
SW STORMWATER
TD TRANSFER DUCT
TEMP TEMPERATURE
TG TRANSFER GRILLE
THRU THROUGH
TJ THROUGH JOISTS
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL)
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
W WATTS / WASTE
W/ WITH
W/O WITHOUT
WB WET BULB
WL WALL / WEATHER LOUVER
WPD WATER PRESSURE DROP
WTD WATER TEMPERATURE DROP
WTR WATER TEMPERATURE RISE
XFMR TRANSFORMER
MECHANICAL ABBREVIATIONS HVAC SYMBOL LEGEND
CO
NO
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
12x20
UP
T
S B
H
M
S
D
DL
DU
S R
NEW WORK
DEMOLITION WORK
EXISTING WORK
DOOR UNDERCUT, SEE ARCH. DWGS.
DOOR LOUVER, SEE ARCH. DWGS.
FIRE DAMPER (FD)
MANUAL VOLUME DAMPER
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
DUCT SMOKE DETECTOR
CONTROL SWITCH
MOTOR OPERATED DAMPER
HUMIDISTAT
EMERGENCY BURNER SHUT-OFF SWITCH
THERMOSTAT
FLEXIBLE CONNECTION
MITERED ELBOW W/O TURNING VANES
(USE ONLY WHERE SHOWN)
MITERED ELBOW W/ TURNING VANES
INCLINED RISE (UP) OR DROP (DN) ARROW
IN DIRECTION OF AIR FLOW
STANDARD BRANCH FOR SUPPLY &
RETURN (NO SPLITTER)
DUCT (1ST FIGURE, SIDE SHOWN;
2ND FIGURE, SIDE NOT SHOWN)
3-WAY CEILING DIFFUSER
2-WAY CORNER CEILING DIFFUSER
2-WAY CEILING DIFFUSER
4-WAY CEILING DIFFUSER OR REGISTER
RETURN GRILLE OR REGISTER
EXHAUST GRILLE OR REGISTER
ROOFTOP RELIEF HOOD
ROOFTOP INTAKE HOOD
ROOFTOP EXHAUSTER
RETURN AIR DUCT RISER
SUPPLY AIR DUCT RISER
EXHAUST OR RELIEF AIR DUCT RISER
FIRE SMOKE DAMPER (FSD)
SMOKE DAMPER (SD)
CD
CHS
CHR
HS
HR
CS
CR
MPS
MPR
LPS
PCR
RS
RL
s
LPR
MECHANICAL PIPING SYMBOL LEGEND
COIL CONDENSATE DRAIN (CD)
CHILLED WATER SUPPLY (CHS)
CHILLED WATER RETURN (CHR)
CONDENSER WATER SUPPLY (CS)
CONDENSER WATER RETURN (CR)
HOT WATER HEATING SUPPLY (HS)
HOT WATER HEATING RETURN (HR)
MEDIUM PRESSURE STEAM SUPPLY (MPS)
MEDIUM PRESSURE CONDENSATE RETURN (MPR)
LOW PRESSURE STEAM SUPPLY (LPS)
LOW PRESSURE CONDENSATE RETURN (LPR)
PUMPED CONDENSATE RETURN
REFRIGERANT SUCTION (RS)
REFRIGERANT LIQUID (RL)
EXISTING WORK
DEMOLITION WORK
NEW WORK
FLOOR CLEANOUT (FCO)
WALL CLEANOUT (WCO)
OVERHEAD CLEANOUT (CO)
PIPE DROP
BRANCH (TOP CONNECTION)
PIPE RISE
BRANCH (BOTTOM CONNECTION)
CONTINUATION
STUB AND CAP
FLEXIBLE CONNECTOR
EXPANSION LOOP
THERMOSTATIC MIXING VALVE
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
FLOW ARROW
AUTOMATIC AIR VENT
PUMP
SHUTOFF VALVE
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
GLOBE VALVE
STRAINER
PRESSURE REDUCING VALVE
SOLENOID VALVE
RELIEF VALVE
PLUG COCK VALVE
THERMOMETER
UNION
PRESSURE GAUGE
PIPE ANCHOR
PIPE GUIDE
STEAM TRAP
MECHANICAL AND PLUMBING GENERAL NOTES
- ALL WORK SHOWN IS TO BE CONSIDERED NEW AND PROVIDED UNDER THIS CONTRACT UNLESS SPECIFICALLY
INDICATED AS EXISTING.
- CONNECT ALL DUCTS TO MECHANICAL EQUIPMENT BY FLEXIBLE DUCT CONNECTORS WITH NOT LESS THAN 3"
SPACING BETWEEN DUCT AND EQUIPMENT.
- CONSTRUCT AND INSTALL ALL DUCTWORK IN ACCORDANCE WITH SMACNA.
- ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS.
- INSTALL DUCT MOUNTED SMOKE DETECTOR(S) IN THE RETURN AIR STREAM OF AIR SYSTEMS OVER 2000 CFM, PER MANUFACTURER'S RECOMMENDATIONS, DOWNSTREAM OF ALL BRANCH CONNECTIONS, UPSTREAM OF ANY OUTSIDE AIR CONNECTIONS OR FILTERS, AND PROVIDE WIRING FOR FAN SHUTDOWN. DETECTOR IS TO BE FURNISHED AND CONNECTED TO THE FIRE ALARM SYSTEM BY OTHERS. IN OCCUPANCIES WHERE A FIRE ALARM SYSTEM IS NOT PRESENT AND/OR REQUIRED, THE DUCT SMOKE DETECTOR SHALL BE FURNISHED AND WIRED BY THE MECHANICAL
CONTRACTOR TO A REMOTE TEST STATION MANUFACTURED BY SIMPLEX, MODEL 4098-9842.
- INSTALL DUCTWORK, EQUIPMENT, AND PIPING CONCEALED IN CHASES OR ABOVE CEILINGS WHERE CEILINGS ARE INDICATED, UNLESS NOTED OTHERWISE. WHERE DUCTWORK OR PIPING IS INDICATED TO BE EXPOSED, INSTALL AS HIGH AS POSSIBLE. ELEVATIONS SHOWN ARE TO THE LOWEST POINT, UNLESS NOTED OTHERWISE.
- ANY PIPING SHOWN TO BE INSTALLED WITHIN AN EXTERIOR WALL MUST BE INSTALLED ON THE INTERIOR SIDE OF THE
WALL INSULATION.
- WALL MOUNTED THERMOSTATS SHALL BE INSTALLED 44" ABOVE THE FLOOR AND HANDICAPPED ACCESSIBLE.
- INSTALL ROOFTOP EQUIPMENT NOT LESS THAN 10 FT FROM THE ROOF EDGE OR ANY CHANGE IN ROOF HEIGHT
GREATER THAN 2 FT.
- SEAL OR CAP OPENINGS IN PIPES OR DUCTS UNTIL FINAL CONNECTIONS ARE MADE.
- INSTALL SUFFICIENT UNIONS IN PIPING SYSTEMS TO ALLOW SERVICE OF ANY CONNECTED EQUIPMENT WITHOUT
BREAKING FITTINGS OR CUTTING PIPING CONNECTIONS.
- DIMENSIONS AND PIPE SIZES ARE IN INCHES UNLESS NOTED OTHERWISE.
- RUNOUTS TO EQUIPMENT SHALL BE RUN IN SIZES INDICATED ON PLANS OR SCHEDULES AND INCREASED OR REDUCED
AT POINT OF FINAL CONNECTION.
- DO NOT RUN PIPING OR DUCTWORK OVER ELECTRICAL EQUIPMENT.
- PROVIDE SUFFICIENT CLEARANCE FOR OPERATION AND MAINTENANCE OF MECHANICAL EQUIPMENT ACCORDING TO
THE MANUFACTURER'S RECOMMENDATIONS.
- PROVIDE SERVICE CLEARANCE FOR ELECTRICAL EQUIPMENT AS REQUIRED BY THE NATIONAL ELECTRICAL CODE (NEC).
- PIPING INSTALLED ABOVE CEILINGS SHALL BE BELOW THE ROOF INSULATION.
- FOR ANY COOLING EQUIPMENT ABOVE CEILING, PROVIDE CONDENSATE OVERFLOW PROTECTION WITH LIQUID
DETECTOR AT TOP OF DRAIN PAN, WIRED TO SHUT DOWN THE SYSTEM.
- FOR INDICATED DEMOLITION WORK: REMOVE EQUIPMENT, DUCTWORK, PIPING, AND RELATED DIFFUSERS, SUPPORTS, WIRING, CONTROLS IN THEIR ENTIRETY UNLESS NOTED OTHERWISE. REMOVE BRANCH PIPING TO THE CONNECTION AT
THE MAIN AND BEYOND THE SURFACE OF WALLS AND FLOORS.
- PATCH OPENINGS CREATED OR UNCOVERED DURING DEMOLITION WORK IN PORTIONS OF WALLS, ROOF, OR FLOORS THAT WILL REMAIN. REPAIR SURFACES TO MATCH ADJACENT OR ORIGINAL CONSTRUCTION. SEE ARCHITECTURAL
DRAWINGS AND SPECIFICATION FOR FINAL FINISH MATERIALS AND METHODS.
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
Certificate Number: 3869
3 2 1456
A
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX
Design Group, LLC whether the project for which they are made is executed or not. All rights reserved.
Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
50% + CONSTRUCTION DOCUMENTS 05/21/25
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
EDA # 01-79-15372
215 EAST 3RD STREET, WILLIAMSPORT, PA 17701
570 215 5660 | WWW.BRIXDG.COM
250334
95% CONSTRUCTION DOCUMENTS 06/04/25
PERMIT SET 06/27/25
M001
BUILDING TECHNOLOGIES CENTER
HVAC & PLUMBING LAB
IMPROVEMENTS
MECHANICAL LEGENDS,
SCHEDULES AND
ABBREVIATIONS
4000-005
06-27-25
O N E C O L L E G E A V E N U E
W I L L I A M S P O R T , P A 1 7 7 0 1
PERMIT SET
# DESCRIPTION DATE
AIR HANDLING UNIT SCHEDULE
TAG
SUPPLY FAN COOLING COIL / DX HOT WATER HEATING COIL
WEIGHT
(LB)
ELECTRICAL BASIS OF DESIGN
NOTES
OA
(CFM)
TOTAL SA
(CFM)
TOTAL
(BTU)
SENSIBLE
(BTU)
EDB
(F)
EWB
(F)
LDB
(F)
LWB
(F) EER
TOTAL
(BTU)
EAT
(F)
LAT
(F)
FLOW
RATE
(GPM)
WPD
(FT)
EWT
(F)
LWT
(F) WATTS HP VOLTAGE PHASE FLA MCA MOCP
DISC.
SWITCH MANUFACTURER MODEL
AHU-1 290 1125 44.89 32.35 80.2 66.4 53.9 53.3 - 46.36 52.0 - - - 200 160.3 164 - - 200-208 1 3.9 - 15 EC TRANE 5TAMXD05AV41DA PROVIDE HYDRONIC HEATER
OPTION, BAYWACC08SC1AA
AHU-2 255 900 39.36 27.52 80.6 66.6 52.7 52.2 - 38.65 50.4 - - - 200 157.1 153 - - 200-208 1 3.9 - 15 EC TRANE 5TAMXD04AV31DA PROVIDE HYDRONIC HEATER
OPTION, BAYWACC08SC1AA
CU-1 - - 48,000 - - - - - - 48,000 - - - - - - 257 - 1.2 208 3 0.93 16.2 25 EC TRANE 5TTA4048A300A -
CU-2 - - 42,000 - - - - - - 42,000 - - - - - - 212 - 1.2 208 3 1.05 16.3 25 EC TRANE 5TTA4042A300A -
ROOFTOP UNIT SCHEDULE
TAG
OA
(CFM)
SA
(CFM)
COOLING COIL / DX HOT WATER HEATING COIL
WEIGHT
(LB)
ELECTRICAL BASIS OF DESIGN
NOTES
NOMINAL
TONS
TOTAL
MBh
SENSIBLE
MBh
COMPRESSOR
STAGES (%)
EDB
(F)
EWB
(F)
LDB
(F)
LWB
(F) EER
TOTAL
MBh
EAT
(F)
LAT
(F)
EWT
(F)
LWT
(F)
FLOW RATE
(GPM)
SUPPLY FAN
VOLTAGE PHASE FLA MCA MOCP
DISC.
SWITCH MANUFACTURER MODELHP
RTU-7 1,400 7,300 25 283.95 216.23 100/75/63/37/25 79.2 65.6 50.7 50.6 10.1 337.7 55.0 99.5 200 156.3 20.0 5441.5 7.5 200 3 - 160.0 200.0 EC TRANE SLHPF25EB ROOF CURB, ECONOMIZER
RTU-8 1,400 7,300 25 283.95 216.23 100/75/63/37/25 79.2 65.6 50.7 50.6 10.1 337.7 55.0 99.5 200 156.3 20.0 5441.5 7.5 200 3 - 160.0 200.0 EC TRANE SLHPF25EB ROOF CURB, ECONOMIZER
RTU-9 1,600 7,400 25 283.95 216.23 100/75/63/37/25 79.2 65.6 50.7 50.6 10.1 337.7 55.0 99.5 200 156.3 20.0 5441.5 7.5 200 3 - 160.0 200.0 EC TRANE SLHPF25EB ROOF CURB, ECONOMIZER
RTU-10 2,000 10,000 30 323.1 243.09 100/76/62/38/24 79.2 65.6 57.3 55.1 9.9 431.5 55.0 94.8 200 161.3 30.0 5905.1 15.0 200 3 - 189.0 225.0 EC TRANE SLHPF30EB ROOF CURB, ECONOMIZER
ESTIMATED HYDRAULIC WATERFLOW INFORMATION
STATIC
PRESSURE
(PSI)
RESIDUAL
PRESSURE
(PSIG)
FLOW (GPM)
EST. FLOW
AT 20 PSI
(GPM)
TEST DATE LOCATION OF
FIRE HYDRANT REMARKS
54 52 493 11/5/24
NOTES:
THIS IS ESTIMATED FLOW DATA. THE DELEGATED DESIGNER SHALL SECURE FINAL FLOW TEST DATA FROM THE WATER UTILITY COMPANY.
FIRE PROTECTION SYSTEM DESIGN CRITERIA
ZONE SYSTEM TYPE
MINIMUM
NUMBER OF
SYSTEMS
SPRINKLER CRITERIA
REFERENCES REMARKS
LABS
B WET 1
CEILING SYSTEMS: EXTRA HAZARD (GROUP 2)
DENSITY: 0.40
AREA OF OPERATION: 2,500 SF
NFPA-13
TABLE A.4.3.5 (LABS)
FIGURE 19.2.3.1.2
NOTES:
1. FLOW DURATION: 2 HOURS, MINIMUM.
2. INSTALLATION SHALL BE IN ACCORDANCE TO THE REQUIREMENTS OF NFPA-13 AND FACTORY MUTUAL DATA SHEETS INCLUDING BUT NOT LIMITED TO
FM DS 8-3, DS 2-0, DS 8-2, DS 8-9.
3. PROVIDE HOSE RACKS WITH 100 LINEAR FEET OF HOSE TO COVER ALL AREAS.
brt10 Rectangle
Image
A. DESCRIPTION
1. THE WORK OF THIS SECTION INCLUDES, BUT IS NOT LIMITED TO, THE HVAC SYSTEM.
B. QUALITY ASSURANCE
1. COMPLY WITH THE CURRENT ADOPTED: INTERNATIONAL MECHANICAL (IMC), BUILDING CODE (IBC), ENERGY CODE (IECC);
LOCAL CODES AND AMENDMENTS; NFPA 70, UL LISTING, NFPA 90A & 90.
C. SUBMITTALS
1. PRODUCT DATA FOR HEATING AND COOLING UNITS AND FANS ONLY.
2. WARRANTIES AND GUARANTEES.
3. OWNERS OPERATIONAL AND MAINTENANCE MANUALS.
4. BALANCING REPORTS.
5. RECORD DRAWINGS: DELIVER TO OWNER AT THE COMPLETION OF THE PROJECT A SET OF PRINTS OF THE DRAWINGS MARKED IN RED SHOWING CHANGES IN LOCATIONS, MODELS, AND CAPACITIES OF THE SYSTEM.
D. PIPING AND INSULATION
1. GENERAL: PROVIDE STEEL PIPE SLEEVES FOR MASONRY WALL PENETRATIONS, TIGHT FITTING SHEET METAL SLEEVES IN WOOD PENETRATIONS AND 3M FIRE STOPPING IN RATED WALL OR FLOOR PENETRATIONS. PROVIDE DIELECTRIC
FITTINGS OR UNIONS IN ALL PIPE CONNECTIONS OF DISSIMILAR METALS.
2. COOLING COIL CONDENSATE: RUN IN PVC PIPING AND SOLVENT WELDED JOINTS EXCEPT PLENUM AREAS RUN IN TYPE L RIGID COPPER TUBING WITH SOLDERED WROUGHT COPPER FITTINGS. INSULATE WITH 1/2” CLOSED CELL FOAM
(ARMAFLEX).
3. HOT WATER: TYPE L RIGID COPPER WITH WROUGHT COPPER LEAD FREE SOLDERED FITTINGS OR SCH 40 STEEL WITH THREADED OR WELDED CAST IRON FITTINGS OR FLEXIBLE GASKETED GROOVED FITTINGS (FULL VACUUM GASKET).
INSULATE WITH PREFORMED FIBERGLASS PIPE INSULATION (K=0.27 @150°F, R=3.7 /IN) AND INTEGRAL JACKET, 1-1/2” THICK FOR PIPE SIZES 1-1/4” AND SMALLER, 2” THICK FOR LARGER PIPES. PROVIDE PVC JACKET FOR EXPOSED PIPES
AND FITTINGS.
4. REFRIGERANT PIPING SHALL BE DRAWN AND ANNEALED (MAX. O.D. 0.625") ACR COPPER TUBE WITH WROUGHT COPPER FITTINGS. INSULATE WITH CLOSED CELL FOAM (AP ARMAFLEX FS OR EQUAL), 1” THICK FOR 1.5” AND LARGER PIPES, 0.5” THICK FOR SMALLER PIPES. SEAL INSULATION JOINTS WITH MASTIC VAPOR TIGHT. BRAZE WITH INERT GAS PROTECTION, CHARGE WITH NITROGEN & EVACUATE TO 200 MICRONS OR LESS IN MULTIPLE CYCLES AS RECOMMENDED BY
EQUIPMENT MANUFACTURER.
E. HANGERS AND SUPPORTS
1. PROVIDE CLEVIS HANGERS SIZED TO INCLUDE INSULATION WITH INSULATION SHIELDS.
2. PROVIDE JOIST HANGERS AND ALL-THREAD RODS.
3. PROVIDE PIPE CLAMPS TO SUPPORT VERTICAL PIPING THROUGH FLOOR.
4. INSTALL SUPPORTS FOR VERTICAL PVC PIPING EVERY 48 INCHES AND INSTALL HANGERS FOR HORIZONTAL
PIPING WITH THE FOLLOWING MAXIMUM SPACING AND MINIMUM ROD DIAMETERS:
a. NPS 1” AND SMALLER: 36” SPAN & 3/8” ROD, NPS 1-1/4” TO 2”: 48” SPAN & 3/8” ROD, NPS 2-1/2” TO 3-1/2”: 48” SPAN & 1/2”
ROD, NPS 4” TO 5”: 48” SPAN & 5/8” ROD, NPS 6” & 8”: 48” SPAN & 3/4" ROD.
5. INSTALL SUPPORTS FOR VERTICAL COPPER TUBING EVERY 10 FEET AND INSTALL HANGERS FOR HORIZONTAL TUBING
WITH THE FOLLOWING MAXIMUM SPACING AND MINIMUM ROD DIAMETERS:
a. NPS 3/4” & SMALLER: 60” SPAN & 3/8” ROD, NPS 1” & 1.25”: 72” SPAN & 3/4” ROD, NPS 1.5” & 2”: 96” SPAN & 3/8” ROD, NPS
2-1/2”: 108” SPAN & 1/2” ROD, NPS 3” TO 5”: 120” SPAN 1/2” ROD.
6. INSTALL SUPPORTS FOR VERTICAL STEEL PIPING EVERY 10 FEET AND INSTALL HANGERS FOR HORIZONTAL
PIPING WITH THE FOLLOWING MAXIMUM SPACING AND MINIMUM ROD DIAMETERS:
a. NPS 1” & SMALLER: 96” SPAN & 3/8” ROD, NPS 1-1/4” TO 2”: 108” SPAN & 3/8” ROD, NPS 2-1/2” TO 3-1/2”: 120” SPAN & 1/2”
ROD, NPS 4” & LARGER: 120” SPAN & 5/8” ROD.
F. IDENTIFICATION
1. GENERAL: PROVIDE PERMANENT LABELS ON ALL EQUIPMENT WITH DRAWING TAG, CAPACITY, AND ELECTRICAL
CHARACTERISTICS.
2. OUTDOOR EQUIPMENT: PROVIDE STAMPED METAL NAMEPLATES.
3. PROVIDE PIPE LABELS SHOWING TYPE OF DUTY (I.E. “HOT WATER SUPPLY” AND DIRECTION OF FLOW) AT 15 FOOT
INTERVALS.
G. ELECTRICAL REQUIREMENTS
1. GENERAL: PROVIDE STARTERS, VARIABLE SPEED DRIVES, TRANSFORMERS, RELAYS, 120V POWER FOR ACTUATORS, SWITCHES, DISCONNECTS, AND CONTROLS AS LISTED BELOW FOR A COMPLETE SYSTEM. FOLLOW THE REQUIREMENTS
OF THE ELECTRICAL SECTION OF THE SPECIFICATION.
2. UNIT MOUNTED RECEPTACLES: PROVIDE RECEPTACLES ON ROOFTOP EQUIPMENT WITH 120V TRANSFORMER AND
DISCONNECT FROM UNIT POWER FEED AHEAD OF UNIT DISCONNECT.
3. MOTORS: PROVIDE MOTORS FOR MECHANICAL EQUIPMENT SUPPLIED BY THE EQUIPMENT MANUFACTURER WHEN POSSIBLE. PROVIDE MOTORS OF PHASE AND VOLTAGE INDICATED ON DRAWINGS AND SUITABLE FOR THE LOADING AND ENVIRONMENT. PROVIDE OPEN DRIP PROOF (ODP) MOTOR ENCLOSURES FOR NORMAL USE OR TOTALLY ENCLOSED FAN COOLED (TEFC) ENCLOSURES FOR OUTDOOR USE, HAZARDOUS OR DIRTY ENVIRONMENTS. PROVIDE MOTORS WITH 1.15 SERVICE FACTOR, INSULATION CLASS F, AND PRE-LUBRICATED BALL BEARINGS RATED FOR CONTINUOUS DUTY UP TO 105°F AMBIENT TEMPERATURE AND 3300FT ALTITUDE. POLY-PHASE MOTORS SHALL BE PREMIUM EFFICIENCY AND WHEN USED WITH VARIABLE SPEED DRIVES, SHALL BE RATED FOR INVERTER DUTY. SINGLE PHASE MOTORS LARGER THAN 1/6HP SHALL BE OPEN-CAPACITOR START, CAPACITOR RUN TYPE UNLESS OTHERWISE INDICATED. SINGLE PHASE MOTORS 1/6HP AND SMALLER MAY BE SPLIT PHASE START, CAPACITOR RUN TYPE OR PERMANENT-SPLIT CAPACITOR
TYPE.
4. STARTERS: PROVIDE EACH MOTOR WITH A MOTOR STARTER OF PROPER DESIGN TO MEET THE REQUIREMENTS OF THE MOTOR AND DRIVE. STARTER TYPES SHALL INCLUDE MAGNETIC, MANUAL, SOLID-STATE REDUCED VOLTAGE, OR VARIABLE SPEED DRIVE. COORDINATE STARTER REQUIREMENTS WITH THE EQUIPMENT AND CONTROL SEQUENCE.
PROVIDE ACCESSORIES SUCH AS CONTACTS, OVERLOADS, EXTERNAL RESETS, CONTROL CIRCUIT TRANSFORMERS, PILOT LIGHTS, PUSH BUTTONS, HOA AND OTHER SELECTOR SWITCHES AS NEEDED FOR THE SPECIFIED OPERATION.
H. PACKAGED HEATING AND COOLING ROOFTOP UNIT
1. FURNISH AND INSTALL HYDRONIC HEATING/DX COOLING SYSTEMS, SELF CONTAINED, FULLY CHARGED, FACTORY ASSEMBLED, DDC BASED CONTROLS, WIRED AND TESTED UNITS WITH VERTICAL DISCHARGE AIRFLOW AND 12” ROOF CURB.
2. PROVIDE 100% MODULATING OUTSIDE AIR ECONOMIZER DAMPERS.
3. PROVIDE CAPACITY, PERFORMANCE, STAGES, AND OPTIONS LISTED ON THE DRAWING SCHEDULE.
4. ALL UNITS SHALL BE FACTORY ASSEMBLED, PIPED, INTERNALLY WIRED AND FULLY CHARGED WITH R-454B.
5. COOLING AND HEATING CAPACITIES SHALL BE RATED IN ACCORDANCE WITH A.R.I. STANDARDS.
6. THE UNIT DESIGN SHALL BE CERTIFIED BY THE AGA OR CSA, SPECIFICALLY FOR OUTDOOR APPLICATIONS USING
PROPANE OR NATURAL GAS.
7. UNITS SHALL BE WEATHERPROOFED AND DESIGNED FOR OUTDOOR ROOFTOP INSTALLATION.
8. PROVIDE HAIL GUARDS ON CONDENSER COILS.
9. EXTERIOR SURFACES OF ALL UNITS SHALL BE PHOSPHATIZED, ZINC-COATED STEEL WITH EPOXY RESIN PRIMER AND
BAKED ENAMEL FINISH.
10. ACCESS TO FILTERS, BLOWER, HEATING SECTION, AND OTHER ITEMS NEEDING PERIODIC CHECKING OR MAINTENANCE SHALL BE THROUGH HINGED ACCESS DOORS WITH QUARTER-TURN LATCHES. DOOR FASTENING SCREWS ARE NOT
ACCEPTABLE.
11. ACCESS DOORS SHALL HAVE STAINLESS STEEL HINGES AND FULL PERIMETER GASKETS.
12. ALL OPENINGS THROUGH THE BASE PAN OF THE UNIT SHALL HAVE UPTURNED FLANGES OF AT LEAST ½” IN HEIGHT
AROUND THE OPENING THROUGH THE BASE PAN.
13. ALL ACCESS DOORS SHALL HAVE AN INTERNAL METAL LINER TO PROTECT THE DOOR AND 2 THICK, 1 1/2 LB DENSITY
FIBERGLASS INSULATION.
14. THE INTERIOR AIR SIDE OF THE CABINET SHALL BE ENTIRELY INSULATED ON ALL EXTERIOR PANELS WITH 1" THICK, 1 1/2
LB. DENSITY FIBERGLASS INSULATION.
15. BLOWER(S) SHALL BE ENTIRELY SELF CONTAINED ON A SLIDE DECK FOR SERVICE AND REMOVAL FROM THE CABINET.
16. ALL DIRECT DRIVE BLOWER(S) SHALL HAVE FORWARD CURVED BLADES.
17. COORDINATE ROOF OPENINGS AND LOCATIONS WITH STRUCTURAL OPENINGS AND REINFORCEMENT.
HVAC SPECIFICATION
I. DUCTWORK, ACCESSORIES AND INSULATION
1. DUCTWORK: GALVANIZED G90 SHEET METAL FABRICATED AND SEALED WITH MASTIC IN ACCORDANCE WITH SMACNA STANDARDS AND LEAKAGE TESTED FOR THE PRESSURE CLASS OF THE SYSTEM TO MEET OR EXCEED THE SPECIFIED FAN PRESSURE. RETURN AIR SYSTEMS SHALL BE CONSTRUCTED AND TESTED TO -2.0” WC PRESSURE CLASS UNLESS OTHERWISE NOTED. PROVIDE DOUBLE-WALL SPIRAL LOCKSEAM CONSTRUCTION FOR EXPOSED ROUND DUCTS.
PROVIDE PVC COATED ROUND DUCTS BELOW GRADE.
2. DUCT LINER: GLASS FIBER DUCT LINER (K=0.24, R=4.2 /IN) WITH EROSION AND MICROBIAL RESISTANT COATING.
THOROUGHLY COAT ALL PENETRATIONS AND EXPOSED EDGES WITH MASTIC. SOUND ABSORPTION COEFFICIENTS (125 Hz) 0.08, (250 Hz) 0.31, (500 Hz) 0.64, (1000 Hz) 0.84, (2000 Hz) 0.97, (4000 Hz) 1.03, NRC=0.70.
3. BLANKET INSULATION (FIBERGLASS): 3/4 LB/CF GLASS FIBERS BONDED WITH A THERMOSETTING RESIN (UNCOMPRESSED K=0.24, R=4.1 /IN), ASTM C 1290 TYPE III WITH ASTM C 1136 TYPE II FOIL REINFORCED KRAFT (FRK) LOW
PERMEANCE VAPOR RETARDER FACING.
4. BOARD INSULATION: 3 LB/CF GLASS FIBERS BONDED WITH A THERMOSETTING RESIN (MIN R-4.1 /IN), ASTM C 612 WITH ASTM C 1136 TYPE II FOIL REINFORCED KRAFT (FRK) LOW PERMEANCE VAPOR RETARDER FACING.
5. INSULATION APPLICATION: APPLY INSULATION AS FOLLOWS:
a. INDOOR EXPOSED SUPPLY: 1” THICK FIBERGLASS LINER OR 1” BOARD WITH VAPOR BARRIER.
6. BALANCING DAMPERS: PROVIDE GALVANIZED STEEL MANUAL BALANCING DAMPERS WITH GALVANIZED STEEL SHAFTS
AND STEEL BEARINGS.
7. TURNING VANES: PROVIDE GALVANIZED STEEL AIRFOIL TYPE TURNING VANES IN DUCT ELBOWS AS INDICATED.
8. CONTROL DAMPERS: PROVIDE ULTRA-LOW LEAK GALVANIZED STEEL DAMPERS GALVANIZED STEEL SHAFTS AND STEEL
BEARINGS, NEOPRENE BLADE AND EDGE SEALS.
9. FLEXIBLE DUCTWORK: VINYL LINER, 1-1/2” FIBERGLASS INSULATION (MIN R-5) WITH STEEL WIRE REINFORCEMENT AND
VINYL JACKET, MEETING FLAME SPREAD AND SMOKE DEVELOPED REQUIREMENTS OF UL 181.
J. AIR DEVICES
1. GRILLES & REGISTERS: HORIZONTAL FACE BARS WITH 45° DEFLECTION ON ½” CENTERS, OPPOSED BLADE DAMPER FOR
REGISTERS. PRICE MODEL 70D FOR RETURN, PRICE MODEL 32 FOR SUPPLY, OR EQUAL.
K. CONTROLS
1. PROVIDE DIGITAL CONTROLLERS, SENSORS AND CONTROL DEVICES, SWITCHES, RELAYS, ACTUATORS, ENGINEERING
AND COMMISSIONING FOR COMPLETE SYSTEM AND SEQUENCES OF OPERATION LISTED BELOW.
2. PROVIDE POWER FOR CONTROLLERS WITH TRANSFORMER AND DISCONNECT FED FROM HVAC UNIT POWER OR UNIT
MOUNTED RECEPTACLE AHEAD OF THE MAIN DISCONNECT.
3. PROVIDE 120V POWER FOR CONTROL PANELS, DAMPER ACTUATORS AND VALVE ACTUATORS FROM THE NEAREST 120V OR 120-208V ELECTRICAL DISTRIBUTION PANEL INCLUDING BREAKER, DISCONNECTS, WIRE AND CONDUIT.
4. PROVIDE CONTROL RELAYS FOR INTERLOCKING FANS, AND DAMPERS WITH LOW VOLTAGE SWITCHES AND
THERMOSTATS.
5. ATC SYSTEM: PROVIDE BROWSER WEB ACCESSIBLE JOHNSON CONTROLS BACNET SYSTEM WITH GRAPHIC INTERFACE AND FULLY EDITABLE SEQUENCES FOR CONTROL AND MONITORING OF ALL HVAC EQUIPMENT. EQUIPMENT SUCH AS PACKAGED ROOFTOP UNITS WILL OPERATE FROM MANUFACTURERS CONTROLS WITH INTEGRATION TO THE ATC SYSTEM FOR SETPOINT ADJUSTMENT, MONITORING OF CRITICAL DATA POINTS, AND ALARMS. FULLY COORDINATE INSTALLATION AND PROGRAMMING OF ALL CONTROLS
WITH PCT AND JOHNSON CONTROLS (CHRISTOPHER BARLOW 717-418-3878).
6. PROGRAMMABLE THERMOSTATS: 7 DAY, 24 HOUR PROGRAM, AUTOMATIC HEATING/COOLING CHANGEOVER AND 5 DEGREE DEADBAND, WITH FAN OFF-AUTO-SUB-BASE, AUXILIARY CONTACTS, AND BATTERY BACKUP.
L. SEQUENCE OF OPERATION (ALL SETPOINTS SHALL BE ADJUSTABLE)
1. PACKAGEED ROOF TOP UNIT: REFER TO SHEET M003.
2. AIR HANDLER UNIT: REFER TO SHEET M003.
M. BALANCING
1. VERIFY ALL NECESSARY BALANCING COMPONENTS ARE INSTALLED SUCH AS BALANCING VALVES AND DAMPERS.
2. BALANCE AIR SYSTEMS TO WITHIN 0 TO + 10% OF INDICATED VALUES.
3. BALANCE HYDRONIC SYSTEMS TO WITHIN ± 5% OF INDICATED VALUES.
4. SUBMIT REPORTS SPECIFIED UNDER SUBMITTALS.
1. PROVIDE CHROME PLATED FINISH FOR CEILING MOUNTED SPRINKLER HEADS AND ROUGH BRASS FINISH
SPRINKLER HEADS FOR AREAS WITHOUT CEILINGS.
2. PROVIDE DRAIN VALVES AND INSPECTOR'S TEST WITH SIGHT GLASS FOR TESTING.
3. PROVIDE FIRE ALARM VALVES FOR EACH ZONE WITH A MAXIMUM COVERAGE AREA OF 52,000 SQUARE FEET
AS REQUIRED BY NFPA 13 AND IBC.
4. OBTAIN HYDRANT FLOW TEST DATA AND PERFORM HYDRAULIC CALCULATIONS. THE FIRE PROTECTION CONTRACTOR SHALL CONFIRM THE ADEQUACY OF THE WATER SUPPLY TO MEET THE DEMANNDS OF THE
SPRINKLER SYSTEM PRIOR TO BIDDING.
5. PROVIDE SEALED DRAWINGS AND ISSUE TO AUTHORITY TO OBTAIN PERMIT, INCLUDING PERMIT FEES.
6. PROVIDE WET PIPE SPRINKLER SYSTEM FOR ALL AREAS OF THE BUILDING ACCORDING TO NFPA 13 REQUIREMENTS AS SCHEDULED ON DRAWING M002. ALL PRODUCTS SHALL BE UL/FM APPROVED FOR THEIR
INTENDED USE.
7. THE AUTOMATIC SPRINKLER SYSTEM DESIGN WILL BE PROVIDED ON A DELEGATED DESIGN BASIS. THE SUCCESSFUL DELEGATED DESIGNER SHALL DESIGN AND PREPARE THE DOCUMENTS FOR THE AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA-13, LOCAL CODE, AND THE AHJ, UTILITY COMPANY REQUIREMENT, AND THE OWNER'S INSURANCE CARRIER, SIGN AND SEAL THE DOCUMENTS BY A LICENSED PROFESSIONAL ENGINEER CURRENTLY LICENSED IN THE COMMONWEALTH OF PENNSYLVANIA, APPLY FOR, SECURE APPROVAL FROM THE LOCAL AHJ AND THE OWNER'S INSURANCE COMPANY REPRESENTATIVE, AND PAY FOR ALL PERMITS REQUIRED FOR INSTALLATION OF THE AUTOMATIC SPRINKLER SYSTEM, INSTALL AUTOMATIC SPRINKLER SYSTEM, START UP ALL AUTOMATIC SPRINKLER SYSTEMS AND PLACE ALL WORK IN OPERATION, PROVIDE O & M MANUALS AND AS-BUILT DRAWINGS, AND WARRANT ALL WORK FOR A MINIMUM OF 1 YEAR AFTER FINAL ACCEPTANCE OF THE AUTOMATIC SPRINKLER SYSTEM WORK. THE FIRE PROTECTION CONTRACTOR SHALL INFORM THE GENERAL CONTRACTOR OF THE MINIMUM WATER SERVICE PIPE SIZE REQUIRED BY THE FIRE PROTECTION CONTRACTOR'S HYDRAULIC CALCULATIONS TO SUPPLY THE FIRE
PROTECTION SYSTEM PRIOR TO BIDDING.
8. HOSE RACKS SHALL BE SUPPLIED FROM ALTERNATIVE LOCATIONS NOT WITHIN THE SPECIFIED AREA OF WORK.
FIRE PROTECTION SPECIFICATION
TO WATER MOTOR GONG
FLOW SWITCH
OS&Y GATE VALVE WITH
SUPERVISORY SWITCH -
(TYPICAL)
RETARD CHAMBER
TO DRAIN
ALARM
VALVE
WET
SEALANT JOINT 1/4" MIN.
WIDE x 3/8" DEEP - BOTH
SIDES
FIRESTOPPING MATERIAL
IN ACCORDANCE WITH UL
723 OR 1479 - BOTH SIDES
DUCT
1/2" HARDWARE CLOTH
METAL DUCT
TYPICAL DUCTMATE FLANGE
METAL SCREEN FRAME
1/2" HARDWARE CLOTH
BOLT (TYPICAL)
UNION - (TYPICAL)
AUTOMATIC AIR VENT
CONTROL VALVE (3 WAY,
MODULATING)
CALIBRATED
BALANCING VALVE
RETURN
SUPPLY
STRAINER WITH HOSE END
BALL VALVE WITH MEMORY
STOP - (TYPICAL)
HOT WATER
HEATING COIL
1 FLOOR PENETRATION
(E) PIPING IS ELECTRICALLY
HEAT TRACED
1 1 1 12
NOTES:
1. EXISTING ISOLATION VALVES WITH TAMPER SWITCH.
2. EXISTING BACKFLOW PREVENTER.
3. REMOVE EXISTING CAP AND INSTALL NEW ISOLATION
VALVE WITH TAMPER SWITCH AND NEW RISER
ASSEMBLY, MATCH EXISTING.
PREFABRICATED
GALVANIZED STEEL
INSULATED ROOF CURB
WOOD BLOCKING
FRAMING ANGLE - SEE
STRUCTURAL DRAWINGS
METAL ROOF DECK -
SEE STRUCTURAL DRAWINGS
RIGID INSULATION -
SEE ARCH.
ROOF MEMBRANE -
SEE ROOF PLAN
FLASHING
COUNTERSUNK
MACHINE BOLT
COUNTERFLASHING
HOLD-DOWN BRACKET WITH
TEK SCREWS (TYPICAL)
NAILER
NOTES:
1. FOR REFERENCE ONLY.
2. PROVIDE PITCHED CURB FOR EQUIPMENT TO SET LEVEL ON ROOF.
3. INSTAL HOLD-DOWN BRACKETS IN ACCORDANCE TO ROOF TOP
EQUIPMENT MANUFACTURER'S RECOMMENDATIONS AND
REQUIREMENTS.
ROOFTOP EQUIPMENT
WASHER, LOCK
WASHER, HEX NUT
26 GA GALVANIZED STEEL
SHEET METAL LINER
SEALANT JOINT 1/4" MIN.
WIDE x 3/8" DEEP
FIRESTOPPING MATERIAL
IN ACCORDANCE WITH UL
723 OR 1479
PIPE
ESCUTCHEON (TYPICAL FOR
FINISHED INTERIOR WALLS)
PIPE SLEEVE
DISCHARGE AT NEAREST EQUIPMENT DRAIN.
REFER TO THE PLANS FOR LOCATIONS. THE
PIPING SO AS NOT TO OBSTRUCT WALKING
ROUTE PATHWAYS. PROVIDE THE CODE
REQUIRED AIR GAP WHERE THE PIPING
TERMINATES AT THE EQUIPMENT DRAIN.
SLOPE PIPE AT 2%
CLEANOUT PLUG
DRAIN PAN
H_: BLOW-THRU = 1" (25MM)
H_: DRAW-THRU = FAN INLET PRESSURE (IN WC) + 1"
H_: BLOW-THRU = FAN OUTLET PRESSURE (IN WC) + 1"
H_: DRAW-THRU = 1/2 OF THE FAN INLET PRESSURE (IN WC) + 1/2"
NOTES:
1. INCREASE UNIT PAD/STRUCTURE/CURB HEIGHT FOR FLOOR MOUNTED EQUIPMENT TO ACHIEVE THE HEIGHT REQUIRED TO INSTALL THE TRAP DEPTH. THE PRESSURES SHALL BE BASED ON 1.25 TIMES THE SCHEDULED AHU
STATIC PRESSURE.
2. IF THE TRAP IS LOCATED IN AN UN-HEATED SPACE, PROVIDE A DRAIN WITH BALL VALVE IN THE LOW POINT
OF THE TRAP WITH A CAP. THIS WILL ALLOW THE TAP TO BE DRAINED IF REQUIRED.
3. REFER TO THE CONTRACT DOCUMENTS FOR PIPE MATERIAL AND INSULATION REQUIREMENTS.
4. THE TRAP PIPE SIZE SHALL BE A MINIMUM OF 1 1/2". REFER TO THE CHART ABOVE FOR THE CONDENSATE DRAIN SIZE (UNLESS NOTED ELSEWHERE IN TEH CONTRACT DOCUMENTS THAT THE PIPE SIZE SHOULD BE LARGER
THAN NOTED IN THE CHART). THE DRAIN LINE SHALL NEVER BE SMALLER THAN THE DRAIN PAN CONNECTION.
PIPE SIZE
(INCHES)
TONNAGE
0-50
51-150
151-300
301-430
1 1/2
H
H
DISCHARGE TO ROOF. REFER TO THE PLANS
FOR ROOFTOP UNIT LOCATIONS. ROUTE THE
PIPING SO AS NOT TO OBSTRUCT WALKING
PATHWAYS. PROVIDE THE CODE REQUIRED AIR
GAP WHERE THE PIPING TERMINATES AT THE
EQUIPMENT DRAIN.
SLOPE PIPE AT 2%
CLEANOUT PLUG
DRAIN PAN
H_: BLOW-THRU = 1"
H_: DRAW-THRU = FAN INLET PRESSURE (IN WC) + 1"
H_: BLOW-THRU = FAN OUTLET PRESSURE (IN WC) + 1"
H_: DRAW-THRU = 1/2 OF THE FAN INLET PRESSURE (IN WC) + 1/2"
PIPE SIZE
(INCHES)
TONNAGE
0-50
51-150
151-300
301-430
1 1/2
LOW POINT DRAIN WITH
BALL VALVE AND CAP
NOTES:
1. INCREASE UNIT PAD/STRUCTURE/CURB HEIGHT FOR FLOOR MOUNTED EQUIPMENT TO ACHIEVE THE HEIGHT REQUIRED TO INSTALL THE TRAP DEPTH. THE PRESSURES SHALL BE BASED ON 1.25 TIMES THE SCHEDULED AHU
STATIC PRESSURE.
2. PROVIDE A DRAIN WITH BALL VALVE IN THE LOW POINT OF THE TRAP WITH A CAP. THIS WILL ALLOW THE TAP
TO BE DRAINED TO PREVENT FREEZING.
3. REFER TO THE CONTRACT DOCUMENTS FOR PIPE MATERIAL AND INSULATION REQUIREMENTS.
4. THE TRAP PIPE SIZE SHALL BE A MINIMUM OF 1 1/2". REFER TO THE CHART ABOVE FOR THE CONDENSATE DRAIN SIZE (UNLESS NOTED ELSEWHERE IN TEH CONTRACT DOCUMENTS THAT THE PIPE SIZE SHOULD BE LARGER
THAN NOTED IN THE CHART). THE DRAIN LINE SHALL NEVER BE SMALLER THAN THE DRAIN PAN CONNECTION.
H
H
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
Certificate Number: 3869
3 2 1456
A
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX
Design Group, LLC whether the project for which they are made is executed or not. All rights reserved.
Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
50% + CONSTRUCTION DOCUMENTS 05/21/25
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
EDA # 01-79-15372
215 EAST 3RD STREET, WILLIAMSPORT, PA 17701
570 215 5660 | WWW.BRIXDG.COM
250334
95% CONSTRUCTION DOCUMENTS 06/04/25
PERMIT SET 06/27/25
M002
BUILDING TECHNOLOGIES CENTER
HVAC & PLUMBING LAB
IMPROVEMENTS
MECHANICAL SPECIFICATIONS
AND DETAILS
4000-005
06-27-25
O N E C O L L E G E A V E N U E
W I L L I A M S P O R T , P A 1 7 7 0 1
PERMIT SET
NO SCALEM002
A WALL OR FLOOR PENETRATION
NO SCALEM002
B OPEN END DUCT TERMINATION
NO SCALEM002
C AHU HW COIL PIPING
NO SCALEM002
E ALARM CHECK VALVE
NO SCALEM002
F RISER A
NO SCALEM002
D ROOF CURB
NO SCALEM002
G WALL OR FLOOR PIPE PENETRATION
NO SCALEM002
H CONDENSATE TRAP DETAIL - INTERIOR
NO SCALEM002
J DEEP SEAL CONDENSATE TRAP DETAIL - EXTERIOR # DESCRIPTION DATE
brt10 Rectangle
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
Certificate Number: 3869
3 2 1456
A
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX
Design Group, LLC whether the project for which they are made is executed or not. All rights reserved.
Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
50% + CONSTRUCTION DOCUMENTS 05/21/25
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
EDA # 01-79-15372
215 EAST 3RD STREET, WILLIAMSPORT, PA 17701
570 215 5660 | WWW.BRIXDG.COM
250334
95% CONSTRUCTION DOCUMENTS 06/04/25
PERMIT SET 06/27/25
M003
BUILDING TECHNOLOGIES CENTER
HVAC & PLUMBING LAB
IMPROVEMENTS
MECHANICAL AUTOMATIC
TEMPERATURE CONTROLS
4000-005
06-27-25
O N E C O L L E G E A V E N U E
W I L L I A M S P O R T , P A 1 7 7 0 1
PERMIT SET
# DESCRIPTION DATE
brt10 Rectangle
(e)F.1(e)F.1
(e)9
(e)9
(e)10
(e)10
(e)11
(e)11
(e)12
(e)12
(e)13
(e)13
(e)C(e)C
(e)B(e)B
(e)D(e)D
(e)E(e)E
(e)F(e)F
HV-B12
HV-B13
HV-B14
HV-B28
HV-B10
HV-B15
HV-B09
HV-B11
(E) 42"x16" (E) 35"x16" (E) 29"x16" (E) 24"x12"
(E)
"x9
(E)
"x9
(E)
"x1 6"
(E)
"x1 8"
(E)
"x8
(E)
"x1 2"
(E) 8" x6
(E)
"x8
(E)
"x1 0"
(E)
"x8
(E) 27"x12" (E) 19"x12" (E) 14"x12"(E) 27"x14"(E) 31"x14"
(E) 16"x17"
(E) 42"x16" (E) 35"x16" (E) 32"x14" (E) 27"x14" (E) 24"x14"
(E) 17"x12"
(E) 28"x16" (E) 28"x14" (E) 23"x14" (E) 20"x12" (E) 14"x12"
(E) 36"x16" (E) 30"x14" (E) 23"x12"
(E) 14"x12" (E) 10"x6"
(E) 14"x12"
(E) 10"x6"
(E) 10"x8"
(E) 16"x12"
(E) 16"x16"
7 8
1 7
8 5
2 7
2 7
HS
HR
HS
H
SH
R
HR
HS
HR
(E) 1 1/4"
(E) 3/4"
H R
H S
(E) OA
(E) 18"x12"
(E)
"x1 2"
(E) 14"x8"
(E) OA
(E) 14"x14"
(E) 14"x12"
HS
HR
H
SH
R
H S
H R
H
SH
R
HS
H S
H S
H R
TO BOILER
HR
5 6 9
DEMOLITION KEYED NOTES
1. REMOVE EXISTING HEAT AND VENTILATION UNIT, DUCTWORK, PIPING, HANGERS, HARDWARE, AND ACCESSORIES
TO EXTENT INDICATED.
2. REMOVE EXISTING CHILLED WATER PIPING, HARDWARE, AND ACCESSORIES TO EXTENT INDICATED.
3. REMOVE EXISTING HEAT AND VENTILATION UNIT, DUCTWORK, PIPING, HANGERS, HARDWARE, AND ACCESSORIES
TO EXTENT INDICATED. AIR HANDLING UNIT TO BE REPLACED IN SEPARATE PROJECT.
4. REMOVE EXISTING OUTSIDE AIR UNIT, DUCTWORK, PIPING, HANGERS, HARDWARE, AND ACCESSORIES TO
EXTENT INDICATED.
5. REMOVE EXISTING SUPPLY DUCTWORK AND ALL ASSOCIATED FITTINGS, AIR DEVICES, HANGERS, SUPPORTS, PIPING, AND CONTROLS.
6. REMOVE EXISTING RETURN DUCTWORK AND ALL ASSOCIATED FITTINGS, AIR DEVICES, HANGERS, SUPPORTS, PIPING, AND CONTROLS.
7. REMOVE EXISTING OUTSIDE AIR DUCTWORK AND ALL ASSOCIATED FITTINGS, AIR DEVICES, HANGERS, SUPPORTS, PIPING, AND CONTROLS.
8. REMOVE EXISTING HOT WATER PIPING, HANGERS, HARDWARE, AND ACCESSORIES TO EXTENT INDICATED.
9. REMOVE EXISTING RTU, CURB, AND ASSOCIATED DUCT DROPS TO THE EXTENT INDICATED. RELOCATE RTU AS
SHOWN ON M101.
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
Certificate Number: 3869
3 2 1456
A
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX
Design Group, LLC whether the project for which they are made is executed or not. All rights reserved.
Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
50% + CONSTRUCTION DOCUMENTS 05/21/25
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
EDA # 01-79-15372
215 EAST 3RD STREET, WILLIAMSPORT, PA 17701
570 215 5660 | WWW.BRIXDG.COM
250334
95% CONSTRUCTION DOCUMENTS 06/04/25
PERMIT SET 06/27/25
MD101
BUILDING TECHNOLOGIES CENTER
HVAC & PLUMBING LAB
IMPROVEMENTS
DEMOLITION PLANS -
MECHANICAL
4000-005
06-27-25
O N E C O L L E G E A V E N U E
W I L L I A M S P O R T , P A 1 7 7 0 1
PERMIT SET
P
LA
N
O
R
THSCALE: 1/8" = 1'-0"
MEZZANINE DEMOLITION PLAN - MECHANICAL
# DESCRIPTION DATE
brt10 Rectangle
F
D
D
D
D
T T
T T
F
T T
T
T
(e)F.1(e)F.1
(e)8
(e)8
(e)9
(e)9
(e)10
(e)10
(e)11
(e)11
(e)12
(e)12
(e)13
(e)13
(e)C(e)C
(e)B(e)B
(e)D(e)D
(e)E(e)E
(e)F(e)F
(e)G(e)G
32"x24"
"x
AHU-1
AHU-2
(E) 14"x12"
(E)SR-18x18-480 (E)SR-18x18-480 (E)SR-22x10-555 (E)SR-22x10-555 (E)SR-22x10-555 (E)SR-22x10-555 (E)SR-22x10-555
(E)SR-12x18-670
(E) 42"x16" (E) 35"x16" (E) 29"x16" (E) 24"x12"
(E)
"x1 6"
(E)
"x1 8"
(E)
"x8
(E)
"x1 2"
(E) 8" x6
(E)
"x8
(E)
"x1 0"
(E)
"x8
(E) 27"x12" (E) 19"x12"(E) 27"x14"(E) 31"x14"
(E) 16"x17"
(E) 42"x16" (E) 35"x16" (E) 32"x14" (E) 27"x14" (E) 24"x14"
(E) 17"x12"
(E) 28"x16" (E) 28"x14" (E) 23"x14"
(E) 20"x12" (E) 14"x12"
(E) 36"x16" (E) 30"x14" (E) 23"x12"
(E) 14"x12" (E) 10"x6"
(E) 14"x12"
(E) 10"x6"
(E) 10"x8"
(E) 16"x12"
(E) 16"x16"
(E) 18"x12"
(E)
"x1 2"
(E) 14"x8"
(E) 14"x14"
(E) 14"x12"
(E)SR-12x18-665 (E)SR-12x18-665
(E) 10x8 DN
(E) OA
(E) OA
(E) 10x8 DN
(E)SR-18x10-635(E)SR-18x10-635(E)SR-18x10-635(E)SR-18x10-635(E)SR-18x10-635(E)SR-18x10-635 (E)SR-12x18-670 (E)SR-12x18-665 (E)SR-12x18-665
(E)SR-18x8-400
(E)SR-18x8-405 (E)SR-18x8-405
SR-18x10-635
(E)SR-30x10-800
(E)SR-30x10-340 (E)SR-30x10-340
(E)SR-30x10-800
(E)SR-18x10-340
(E)SR-30x10-800
(E)SR-18x10-340
(E)SR-30x10-800
(E)SR-18x10-340
(E)SR-18x8-30(E)SR-18x8-35 (E)SR-18x8-35
(E)SR-24x10-575(E)SR-24x10-575 (E)SR-24x10-505 (E)SR-24x10-505 (E)SR-24x10-505 (E)SR-24x10-505
(E)SR-18x8-390 (E)SR-18x8-325 (E)SR-18x8-325 (E)SR-18x8-325 (E)SR-18x8-325
(E)SR-18x8-180 (E)SR-18x8-180 (E)SR-18x8-180
(E)SR-10x6-135 (E)SR-22x10-635(E)SR-22x10-635(E)SR-22x10-635(E)SR-22x10-635
(E)SR-18x8-180(E)SR-18x8-180(E)SR-18x8-180(E)SR-18x8-180(E)SR-18x8-180
(E)SR-22x10-635(E)SR-22x10-635 (E)SR-18x8-345(E)SR-18x8-345
2" 1 1/2"
3/4" SR-30x10-1150
SR-30x10-1150
2"
1 1/2"
RTU-7
RTU-8
RTU-9
(E)SR-18x8-540
RTU-10
(E)SR-10x6-140
3/4" 1 1/2"
2"
RTU-7
RTU-8
RTU-9
RTU-10
HS
HR
HS
HR
HS
HR
H R
H S
H R
H S
H S
H R
H R
H S
TO BOILERHS
HR
H S
H R
H S
H R
H S
H R
H S H
R
HR
2 1/2"
(E) 5"
(E) 2 1/2"
888888
8 8 8 8 8
88888
8 8 8 8 8
888 8 8 8
8 8
(E) 5"
8 8
8 8
8 8 8
C H
R C
H S
CHS
CHR
C H
S C
H R
C H
S C
H R
C H
S C
H R
CU-1
CU-2
RS/RL
RS/RL
8"x8"
C D
C D
CD
CD
(e)9
(e)9
(e)10
(e)10
(e)D(e)D
(e)E(e)E
RTU-8
RTU-7
(E) 16x10 RA UP
(E) 12x16 RA UP
KEYED NOTES #
1. PROVIDE OPEN-END DUCT TERMINATION ON RETURN PER DETAIL. SIZE PER RETURN OPENING ON RTU.
2. NEW DUCTWORK TO BE MECHANICALLY FASTENED TO THE EXTERIOR OF EXISTING DUCTWORK. TAPING WILL
NOT BE ACCEPTABLE.
3. RTU HW PIPING UP THROUGH CURB INTO UNIT. COORDINATE EXACT ROOF/UNIT PENETRATION LOCATION WITH
EQUIPMENT SELECTIONS AND GC. SEE DETAIL C/M002.
4. AIR HANDLING UNIT ONE FOR ONE REPLACEMENT. SEE AHU SCHEUDLE ON M001.
5. NEW PIPE SIZE TO CONNECT TO MAIN IN HALLWAY AT CLOSET LOCATION.
6. EXISTING THERMOSTAT TO SERVE NEW AHU.
7. NEW DUCTWORK TO BE INSTALLED WITHIN JOIST SPACE TO ALLOW MAXIMUM HEADROOM FOR WALKWAY
BELOW.
8. REBALANCE EXISTING DIFFUSER TO INDICATED AIRFLOW.
9. CAP EXISTING DUCTWORK. DUCTWORK TO BE REUSED IN FUTURE PROJECT.
10. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.
11. RELOCATED RTU AS SHOWN. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. RECONNECT SUPPLY AND RETURN DUCT TO EXISTING DUCT RUNS, RECONNECT ALL PIPING. MAINTAIN ALL ACCESSORIES. MAINTAIN ALL SERVICE CLEARANCES PER MANUFACTURER'S RECOMMENDATIONS. INSTALL GUARDS PER IMC 304.11.
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
Certificate Number: 3869
3 2 1456
A
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX
Design Group, LLC whether the project for which they are made is executed or not. All rights reserved.
Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
50% + CONSTRUCTION DOCUMENTS 05/21/25
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
EDA # 01-79-15372
215 EAST 3RD STREET, WILLIAMSPORT, PA 17701
570 215 5660 | WWW.BRIXDG.COM
250334
95% CONSTRUCTION DOCUMENTS 06/04/25
PERMIT SET 06/27/25
M101
BUILDING TECHNOLOGIES CENTER
HVAC & PLUMBING LAB
IMPROVEMENTS
FLOOR PLANS - MECHANICAL
4000-005
06-27-25
O N E C O L L E G E A V E N U E
W I L L I A M S P O R T , P A 1 7 7 0 1
PERMIT SET
P
R
THSCALE: 1/8" = 1'-0"
MEZZANINE PLAN - MECHANICAL
P
R
THSCALE: 1/8" = 1'-0"
FIRST FLOOR - UNDER MEZZANINE
# DESCRIPTION DATE
brt10 Rectangle
S 120-277 SINGLE POLE LINE VOLTAGE TOGGLE SWITCH
S3
S4
SOC
SLV
SD
SD3
OC OC
24VDC
120-277
120-277
24VDC
12-24VAC/VDC
12-24VAC/VDC
120-277 sPODMA 3X (SENSORSWITCH)
WSXA PDT SA (SENSORSWITCH)
sPODMA (SENSORSWITCH) sPODMA D (SENSORSWITCH) sPODMA D 3X (SENSORSWITCH)
PP20 (SENSORSWITCH)
CM PDT 10
LOW VOLTAGE 3-WAY ON/OFF PUSH BUTTON SWITCH
4-WAY LINE VOLTAGE TOGGLE SWITCH
LOW VOLTAGE OCCUPANCY SENSOR WALL SWITCH
LOW VOLTAGE ON/OFF PUSH BUTTON SWITCH
LOW VOLTAGE PUSH BUTTON DIMMER
LOW VOLTAGE PUSH BUTTON DIMMER, MULTI-WAY OPERATION
LINE VOLTAGE POWER PACK, INTEGRAL RELAY
LOW VOLTAGE CEILING OR WALL MOUNT OCCUPANCY
SENSOR, DUAL TECHNOLOGY (PIR/MICROPHONICS), LARGE
MOTION 360 DEGREES
NOTES:
1. COORDINATE DEVICE COLORS WITH ARCHITECT.
2. NOT ALL SYMBOLS UTILIZED ON PROJECTS.
LIGHTING CONTROL SCHEDULE
SYMBOL VOLTAGE
CATALOG NUMBER DISCRIPTION
P
24VDC
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
Certificate Number: 3869
3 2 1456
A
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX
Design Group, LLC whether the project for which they are made is executed or not. All rights reserved.
Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
50% + CONSTRUCTION DOCUMENTS 05/21/25
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
EDA # 01-79-15372
215 EAST 3RD STREET, WILLIAMSPORT, PA 17701
570 215 5660 | WWW.BRIXDG.COM
250334
95% CONSTRUCTION DOCUMENTS 06/04/25
PERMIT SET 06/27/25
E001
BUILDING TECHNOLOGIES CENTER
HVAC & PLUMBING LAB
IMPROVEMENTS
LEGENDS, SCHEDULES AND
ABBREVIATIONS
4000-005
06-27-25
O N E C O L L E G E A V E N U E
W I L L I A M S P O R T , P A 1 7 7 0 1
PERMIT SET
ELECTRICAL ABBREVIATIONS
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MH MANHOLE
MOD MOTOR OPERATED DAMPER
MFR MANUFACTURER
MIN MINIMUM
MTD, MTG MOUNTED, MOUNTING
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NUMBER
OC ON CENTER
P POLE
PC PLUMBING CONTRACTOR
PH PHASE
PWR POWER
SCH SCHEDULE
SEC SECONDARY
SHLD SHIELDED
S&C STUB AND CAP
SF SQUARE FEET
SPEC SPECIFICATIONS
SN SOLID NEUTRAL
SS STAINLESS STEEL
SW SWITCH
T TOE SPACE MOUNTED
TEMP TEMPERATURE
THRU THROUGH
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W WATTS, WIRE
WL WET LOCATION
WP WEATHERPROOF
XFMR TRANSFORMER
A AMPERES
AC ALTERNATING CURRENT
AB ABOVE
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AHJ AUTHORITY HAVING JURISDICTION
AL ALUMINUM
ARCH ARCHITECTURAL
BEL BELOW
BFF BELOW FINISH FLOOR
BFG BELOW FINISH GRADE
BLDG BUILDING
C CONDUIT
CLG CEILING
DC DIRECT CURRENT
DEG, ° DEGREE
DIA., ⌀ DIAMETER
DISC DISCONNECT
DN DOWN
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ETR EXISTING TO REMAIN
EX, (E) EXISTING
F FUSE
FLA FULL LOAD AMPERES
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GRD GROUND
H HIGH
HP HORSEPOWER
IN, " INCHES
INS INSULATION
KW KILOWATTS
LB, # POUNDS
MAX MAXIMUM
ELECTRICAL SYMBOL LEGEND
FACP
W
CS
PA
HT
VFD
DC
K
F
FF
FF
S S
S S
H
PP
J
P
L
CR
C
WP
GFCI
GFCI
USB
TR
C
GFCI
2X2 LAY-IN FIXTURE WITH
NORMAL/EMERGENCY
NOT ALL SYMBOLS UTILIZED ON PROJECT
2x4 LED LAY-IN FIXTURE
WITH NORMAL/EMERGENCY
LINEAR INDUSTRIAL LED FIXTURE
WITH NORMAL/EMERGENCY
LINEAR INDUSTRIAL LED
STRIP FIXTURE
WITH NORMAL/EMERGENCY
EXTERIOR LED WALL PACK
EXTERIOR LED AREA FIXTURE
DOWNL…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .