1-8281 Mechanical - Drawings.pdf
PDF 3 MB Posted
- Attached to
- #8281 Dust Collection System Install
- Solicitation number
- Not on record
- Issued by
- Schuylkill County, Pennsylvania
About this file
This is a mechanical drawing set for the Building Technologies Center Addition & Interior Renovations project located at 1201 West 3rd Street, Williamsport, Pennsylvania, prepared by BRIX Design Group, LLC for Pennsylvania College of Technology. The project scope includes the installation of a new dust collection system with associated ductwork, as well as demolition of existing dust collection infrastructure. The drawings contain mechanical legends, schedules, abbreviations, specifications, automatic temperature controls, and first-floor demolition and installation plans for the dust collection system. Key specifications require 10 feet of straight ductwork per non-return valve requirements and 20 feet of unobstructed straight ductwork per spark detection system requirements. All duct branches must be side connections, and dust cleanout must be air and light tight. The drawings indicate work is to be installed per manufacturer's recommendations, with the dust collector shop drawings to be provided by others. The permit set was issued on November 22, 2024, with revisions dated May 22, 2026 for RTU duct modifications and May 29, 2026 for dust collection work. The project number is 231641 with a certificate number of 3869.
The mechanical drawing set serves as the technical documentation for contractors bidding on the dust collection system installation contract. The specifications emphasize compliance with SMACNA standards for ductwork construction, proper sizing and slope for piping systems, and coordination with other trades to avoid conflicts. Installation requirements include flexible duct connectors with minimum 3-inch spacing from equipment, concealment of ductwork and piping in chases or above ceilings where indicated, and provision of adequate clearance for equipment operation and maintenance. All work shown is to be considered new unless specifically indicated as existing. The drawings establish the technical baseline for the solicitation and would guide contractors in preparing accurate bids and ensuring compliant installations of the new dust collection system.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AB ABOVE
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AHJ AUTHORITY HAVING JURISDICTION
ARCH ARCHITECTURAL
BDD BACK DRAFT DAMPER
BEL BELOW
BFF BELOW FINISH FLOOR
BFG BELOW FINISH GRADE
BJ BETWEEN JOISTS
BOD BOTTOM OF DUCT
BTM BOTTOM
BTU BRITISH THERMAL UNIT
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEANOUT
CONN CONNECT / CONNECTION
CONT CONTINUED / CONTINUATION
COORD COORDINATE
CW DOMESTIC COLD WATER
DB DRY BULB
DCO DUCT CLEANOUT
DEG,° DEGREE
DIA, ∅ DIAMETER
DISC DISCONNECT
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
ER EXHAUST REGISTER
ESP EXTERNAL STATIC PRESSURE
EWB ENTERING WET BULB TEMPERATURE
EWT ENTERING WATER TEMPERATURE
EX, (E) EXISTING
FD FIRE DAMPER / FLOOR DRAIN
FLA FULL LOAD AMPERES
FLEX FLEXIBLE
FLS FLOOR SWEEP
FPM FEET PER MINUTE
FT FOOT / FEET / FIN TUBE
FT HD FEET OF HEAD
GA GAUGE / GAGE
GAL GALLON
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HC HVAC CONTRACTOR
HD HUB DRAIN
HORZ HORIZONTAL
HP HORSE POWER
HSTAT HUMIDISTAT
ID INSIDE DIAMETER
IN, " INCHES
INS INSULATION
INV INVERT
ISP INTERNAL STATIC PRESSURE
IWG INCHES WATER GAUGE
LAT LEAVING AIR TEMPERATURE
LF LINEAR FEET
LB, # POUNDS
LDB LEAVING DRY BULB TEMPERATURE
LWB LEAVING WET BULB TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MOD MOTOR OPERATED DAMPER
MFR MANUFACTURER
MIN MINIMUM
MTD, MTG MOUNTED, MOUNTING
NC NOISE CRITERIA
NIC NOT IN CONTRACT
OA OUTSIDE AIR
OAC OPEN ABOVE CEILING
OAI OUTSIDE AIR INTAKE
OC ON CENTER
ORD OVERFLOW ROOF DRAIN
PC PLUMBING CONTRACTOR
PH PHASE
PRV PRESSURE REDUCING VALVE /
PRESSURE RELIEF VENT
PSI POUNDS PER SQUARE INCH
RA RETURN AIR
RD ROOF DRAIN
RG RETURN GRILLE
RPM REVOLUTIONS PER MINUTE
RWC RAINWATER CONDUCTOR
RX REMOVE EXISTING
SW STORMWATER
S&C STUB AND CAP
SA SUPPLY AIR
SAN SANITARY
SF SQUARE FEET
SG SUPPLY GRILLE
SPEC SPECIFICATIONS
SR SUPPLY REGISTER
TD TRANSFER DUCT
TEMP TEMPERATURE
TG TRANSFER GRILLE
THRU THROUGH
TJ THROUGH JOISTS
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL)
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
W WATTS / WASTE
W/ WITH
W/O WITHOUT
WB WET BULB
WL WALL / WEATHER LOUVER
WPD WATER PRESSURE DROP
WTD WATER TEMPERATURE DROP
WTR WATER TEMPERATURE RISE
XFMR TRANSFORMER
CO
NO
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
12x20
UP
T
S B
H
M
S
D
DL
DU
S R
NEW WORK
DEMOLITION WORK
EXISTING WORK
DOOR UNDERCUT, SEE ARCH. DWGS.
DOOR LOUVER, SEE ARCH. DWGS.
VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
MANUAL VOLUME DAMPER
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
DUCT SMOKE DETECTOR
CONTROL SWITCH
MOTOR OPERATED DAMPER
HUMIDISTAT
EMERGENCY BURNER SHUT-OFF SWITCH
THERMOSTAT
FLEXIBLE CONNECTION
MITERED ELBOW W/O TURNING VANES
(USE ONLY WHERE SHOWN)
MITERED ELBOW W/ TURNING VANES
INCLINED RISE (UP) OR DROP (DN) ARROW
IN DIRECTION OF AIR FLOW
STANDARD BRANCH FOR SUPPLY &
RETURN (NO SPLITTER)
DUCT (1ST FIGURE, SIDE SHOWN;
2ND FIGURE, SIDE NOT SHOWN)
3-WAY CEILING DIFFUSER
2-WAY CORNER CEILING DIFFUSER
2-WAY CEILING DIFFUSER
4-WAY CEILING DIFFUSER OR REGISTER
RETURN GRILLE OR REGISTER
EXHAUST GRILLE OR REGISTER
ROOFTOP RELIEF HOOD
ROOFTOP INTAKE HOOD
ROOFTOP EXHAUSTER
RETURN AIR DUCT RISER
SUPPLY AIR DUCT RISER
EXHAUST OR RELIEF AIR DUCT RISER
SW
PS
G
LP
CA
CD
140R
F
CHS
CHR
HS
HR
CS
CR
MPS
MPR
LPS
PCR
RS
RL
s
A
LPR
COLD WATER (CW)
HOT WATER (HW)
HOT WATER RECIRCULATION (HWR)
SOIL / WATER (SAN)
STORM WATER (SW)
PUMPED SEWAGE
VENT (V)
NATURAL GAS (G)
LIQUID PROPANE (LP)
COMPRESSED AIR (CA)
COIL CONDENSATE DRAIN (CD)
140°F HOT WATER (140)
140°F HOT WATER RECIRCULATION (140R)
FIRE (F)
CHILLED WATER SUPPLY (CHS)
CHILLED WATER RETURN (CHR)
CONDENSER WATER SUPPLY (CS)
CONDENSER WATER RETURN (CR)
HOT WATER HEATING SUPPLY (HS)
HOT WATER HEATING RETURN (HR)
MEDIUM PRESSURE STEAM SUPPLY (MPS)
MEDIUM PRESSURE CONDENSATE RETURN (MPR)
LOW PRESSURE STEAM SUPPLY (LPS)
LOW PRESSURE CONDENSATE RETURN (LPR)
PUMPED CONDENSATE RETURN
REFRIGERANT SUCTION (RS)
REFRIGERANT LIQUID (RL)
EXISTING WORK
DEMOLITION WORK
NEW WORK
FLOOR CLEANOUT (CO)
WALL CLEANOUT (CO)
OVERHEAD CLEANOUT (CO)
HOSE BIBB (HB)
WALL HYDRANT (WH)
ROOF DRAIN (RD)
FLOOR DRAIN (FD)
PIPE DROP
BRANCH (TOP CONNECTION)
PIPE RISE
BRANCH (BOTTOM CONNECTION)
CONTINUATION
STUB AND CAP
FLEXIBLE CONNECTOR
EXPANSION LOOP
THERMOSTATIC MIXING VALVE
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
FLOW ARROW
STEAM TRAP
AUTOMATIC AIR VENT
PUMP
SHUTOFF VALVE
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
GLOBE VALVE
STRAINER
PRESSURE REDUCING VALVE
SOLENOID VALVE
RELIEF VALVE
PLUG COCK VALVE
THERMOMETER
UNION
PRESSURE GAUGE
PIPE ANCHOR
PIPE GUIDE
WATER HAMMER ARRESTER
(SIZE A-F, SEE SCHEDULE)
• ALL WORK SHOWN IS TO BE CONSIDERED NEW AND PROVIDED UNDER THIS CONTRACT UNLESS SPECIFICALLY
INDICATED AS EXISTING.
• CONNECT ALL DUCTS TO MECHANICAL EQUIPMENT BY FLEXIBLE DUCT CONNECTORS WITH NOT LESS THAN 3"
SPACING BETWEEN DUCT AND EQUIPMENT.
• CONSTRUCT AND INSTALL ALL DUCTWORK IN ACCORDANCE WITH SMACNA.
• ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS.
• INSTALL DUCT MOUNTED SMOKE DETECTOR(S) IN THE RETURN AIR STREAM OF AIR SYSTEM OVER 2000 CFM, PER MANUFACTURER'S RECOMMENDATIONS, DOWNSTREAM OF ALL BRANCH CONNECTIONS, UPSTREAM OF ANY OUTSIDE AIR CONNECTIONS OR FILTERS, AND PROVIDE WIRING FOR FAN SHUTDOWN. DETECTOR IS TO BE FURNISHED AND CONNECTED TOP THE FIRE ALARM SYSTEM BY OTHERS. IN OCCUPANCIES WHERE A FIRE ALARM SYSTEM IS NOT PRESENT AND/OR REQUIRED, THE DUCT SMOKE DETECTOR SHALL BE FURNISHED AND WIRED BY THE MECHANICAL CONTRACTOR TO A REMOTE TEST STATION MANUFACTURED BY SIMPLEX, MODEL 4098-9842.
• INSTALL DUCTWORK, EQUIPMENT, AND PIPING CONCEALED IN CHASES OR ABOVE CEILINGS WHERE CEILINGS ARE INDICATED, UNLESS NOTED OTHERWISE. WHERE DUCTWORK OR PIPING IS INDICATED TO BE EXPOSED, INSTALL AS HIGH AS POSSIBLE. ELEVATIONS SHOWN ARE TO THE LOWEST POINT, UNLESS NOTED OTHERWISE.
• ANY PIPING SHOWN TO BE INSTALLED WITHIN AN EXTERIOR WALL MUST BE INSTALLED ON THE INTERIOR SIDE
OF THE WALL INSULATION.
• WALL MOUNTED THERMOSTATS SHALL BE INSTALLED 44" ABOVE THE FLOOR AND HANDICAPPED ACCESSIBLE.
• INSTALL ROOFTOP EQUIPMENT NOT LESS THAN 10 FT FROM THE ROOF EDGE OR ANY CHANGE IN ROOF HEIGHT
GREATER THAN 2 FT.
• SEAL OR CAP OPENINGS IN PIPES OR DUCTS UNTIL FINAL CONNECTIONS ARE MADE.
• INSTALL SUFFICIENT UNIONS IN PIPING SYSTEMS TO ALLOW SERVICE OF ANY CONNECTED EQUIPMENT WITHOUT
BREAKING FITTINGS OR CUTTING PIPING CONNECTIONS.
• DIMENSIONS AND PIPE SIZES ARE IN INCHES UNLESS NOTED OTHERWISE.
• RUNOUTS TO EQUIPMENT SHALL BE RUN IN SIZES INDICATED ON PLANS OR SCHEDULES AND INCREASED OR
REDUCED AT POINT OF FINAL CONNECTION.
• DO NOT RUN PIPING OR DUCTWORK OVER ELECTRICAL EQUIPMENT.
• PROVIDE SUFFICIENT CLEARANCE FOR OPERATION AND MAINTENANCE OF MECHANICAL EQUIPMENT
ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.
• PROVIDE SERVICE CLEARANCE FOR ELECTRICAL EQUIPMENT AS REQUIRED BY THE NATIONAL ELECTRICAL CODE
(NEC).
• CONNECT HW, CW, VENT, AND SAN LINES TO FIXTURES IN ACCORDANCE WITH SIZES INDICATED ON THE PLUMBING FIXTURE SCHEDULE WITH A 2" MINIMUM SIZE FOR SANITARY PIPING BELOW FLOOR.
• PIPING INSTALLED ABOVE CEILINGS SHALL BE BELOW THE ROOF INSULATION.
• SLOPE SANITARY PIPING SIZES 3" AND LARGER 1/8" PER FOOT, AND SMALLER PIPES 1/4" PER FOOT, UNLESS
NOTED OTHERWISE.
• ALL EXPOSED PLUMBING PIPING AND ACCESSORIES (VALVES, TRAPS, STRAINERS, ETC.) SHALL BE CHROME
PLATED.
• PROVIDE BACKFLOW PREVENTER OR AIR GAP FOR ALL DOMESTIC HOT AND COLD WATER CONNECTIONS TO
FIXTURES AND EQUIPMENT THAT DO NOT HAVE INTEGRAL AIR GAPS.
• PROVIDE SHUTOFF VALVES FOR ALL DOMESTIC WATER CONNECTIONS TO FIXTURES AND EQUIPMENT.
• COORDINATE LOCATIONS OF ALL PIPING, DUCTWORK, EQUIPMENT, AND DEVICES BEFORE INSTALLATION, WITH THE WORK OF OTHER TRADES. WHERE A CONFLICT IN CLEARANCES OCCURS, OBTAIN CLARIFICATION FROM THE ENGINEER, ARCHITECT, OR OWNER. INSTALL ALL NECESSARY PIPING, DUCTWORK, FITTINGS, ETC. THAT ARE
REQUIRED FOR A COMPLETE SYSTEM WITHOUT ADDITIONAL COST TO THE CONTRACT.
• TEST INSTALLATIONS IN ACCORDANCE WITH THE APPROPRIATE CODE REQUIREMENTS AS EACH PORTION IS INSTALLED. FLUSH NEW DOMESTIC WATER PIPING UNTIL IT RUNS CLEAR, FILL WITH 50 PPM CHLORINE FOR 24 HOURS, PURGE WITH FRESH WATER, TEST FOR BACTERIAL CONTENT, AND REPEAT IF NECESSARY.
• PROVIDE P-TRAPS FOR ALL SANITARY FIXTURE CONNECTIONS TO FIXTURES WITHOUT INTEGRAL P-TRAPS.
• PROVIDE CONDENSATE DRAINS WITH P-TRAPS FOR AIR HANDLING UNITS WITH COOLING COILS. DISCHARGE
CONDENSATE TO ROOF, GRADE, OR INDIRECT WASTE.
• FOR ANY COOLING EQIUPMENT ABOVE CEILING, PROVIDE CONDENSATE OVERFLOW PROTECTION WITH LIQUID
DETECTOR AT TOP OF DRAIN PAN, WIRED TO SHUT DOWN THE SYSTEM.
• VERIFY MOUNTING HEIGHTS OF EQUIPMENT AND FIXTURES WITH ARCHITECTURAL DRAWINGS, AUTHORITY
HAVING JURISDICTION, AND THE OWNER.
• FOR INDICATED DEMOLITION WORK: REMOVE EQUIPMENT, DUCTWORK, PIPING, AND RELATED DIFFUSERS, SUPPORTS, WIRING, CONTROLS IN THEIR ENTIRETY UNLESS NOTED OTHERWISE. REMOVE BRANCH PIPING TO
THE CONNECTION AT THE MAIN AND BEYOND THE SURFACE OF WALLS AND FLOORS.
• PATCH OPENINGS CREATED OR UNCOVERED DURING DEMOLITION WORK IN PORTIONS OF WALLS, ROOF, OR FLOORS THAT WILL REMAIN. REPAIR SURFACES TO MATCH ADJACENT OR ORIGINAL CONSTRUCTION. SEE
ARCHITECTURAL DRAWINGS AND SPECIFICATION FOR FINAL FINISH MATERICAL AND METHODS.
MECHANICAL ABBREVIATIONS HVAC SYMBOL LEGEND PIPING SYMBOL LEGEND MECHANICAL AND PLUMBING GENERAL NOTES
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
3 2 1456
A
215 East 3rd Street
Williamsport PA 17701
570 215 5660 www.BRIXDG.com
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX Design Group, LLC whether the project for which they are made is executed or not. All rights reserved. Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
231641 Certificate Number: 3869
PERMIT SET 11.22.24
M001
BUILDING TECHNOLOGIES CENTER ADDITION & INTERIOR
RENOVATIONS
MECHANICAL LEGENDS, SCHEDULES, &
ABBREVIATIONS
231641
11.22.24
1201 WEST 3RD STREET
WILLIAMSPORT, PA 17701
PERMIT SET
# DESCRIPTION DATE
3 DUST COLLECTION 05/29/26
brt10 Rectangle
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
3 2 1456
A
215 East 3rd Street
Williamsport PA 17701
570 215 5660 www.BRIXDG.com
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX Design Group, LLC whether the project for which they are made is executed or not. All rights reserved. Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
231641 Certificate Number: 3869
PERMIT SET 11.22.24
M003
BUILDING TECHNOLOGIES CENTER ADDITION & INTERIOR
RENOVATIONS
MECHANICAL SPECIFICATIONS
231641
11.22.24
1201 WEST 3RD STREET
WILLIAMSPORT, PA 17701
PERMIT SET
# DESCRIPTION DATE
2 RTU DUCT MODIFICATIONS 05/22/26
3 DUST COLLECTION 05/29/26
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
3 2 1456
A
215 East 3rd Street
Williamsport PA 17701
570 215 5660 www.BRIXDG.com
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX Design Group, LLC whether the project for which they are made is executed or not. All rights reserved. Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
231641 Certificate Number: 3869
PERMIT SET 11.22.24
M005
BUILDING TECHNOLOGIES CENTER ADDITION & INTERIOR
RENOVATIONS
MECHANICAL AUTOMATIC TEMPERATURE
CONTROLS
231641
11.22.24
1201 WEST 3RD STREET
WILLIAMSPORT, PA 17701
PERMIT SET
# DESCRIPTION DATE
2 RTU DUCT MODIFICATIONS 05/22/26
3 DUST COLLECTION 05/29/26
DEMOLITION KEYED NOTES
1. REMOVE EXISTING DUST COLLECTOR AND ALL ASSOCIATED FITTINGS, DEVICES, HANGERS, AND SUPPORTS.
2. REMOVE EXISTING FLOOR SWEEP AND ALL ASSOCIATED FITTINGS, HANGERS, AND SUPPORTS, TO THE EXTENT INDICATED.
3. REMOVE EXISTING DUST COLLECTION DUCTWORK AND ALL ASSOCIATED FITTINGS, HANGERS, AND SUPPORTS TO THE EXTENT INDICATED IN THIS AREA.
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
3 2 1456
A
215 East 3rd Street
Williamsport PA 17701
570 215 5660 www.BRIXDG.com
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX Design Group, LLC whether the project for which they are made is executed or not. All rights reserved. Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
231641 Certificate Number: 3869
PERMIT SET 11.22.24
MD201
BUILDING TECHNOLOGIES CENTER ADDITION & INTERIOR
RENOVATIONS
FIRST FLOOR DEMOLITION PLAN - DUST
COLLECTION SYSTEM
231641
11.22.24
1201 WEST 3RD STREET
WILLIAMSPORT, PA 17701
PERMIT SET
# DESCRIPTION DATE
3 DUST COLLECTION 05/29/26
3/4" = 1'-0"1
FIRST FLOOR DEMOLITION PLAN - DUST COLLECTION SYSTEM
KEYED NOTES
1. REFER TO DUST COLLECTOR SHOP DRAWINGS FOR EQUIPMENT DETAILS. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. 10'-0" OF STRAIGHT DUCTWORK PER NON-RETURN VALVE REQUIREMENTS. NON-RETURN VALVE SELECTED BY OTHERS.
3. 20'-0" UNOBSTRUCTED STRAIGHT DUCTWORK PER SPARK DETECTION SYSTEM REQUIREMENTS. SPARK DETECTION SYSTEM DESIGN BY OTHERS.
4. DUST CLEAN OUT TO BE AIR AND LIGHT TIGHT.
PLAN NOTES
1. ALL DUCT BRANCHES MUST BE SIDE CONNECTIONS. BOTTOM CONNECTIONS ARE NOT ACCEPTABLE.
PEC Job Number:
Phone: 717-793-3997 York, PA 17403
1071 Edgar Street, Suite A
3 2 1456
A
215 East 3rd Street
Williamsport PA 17701
570 215 5660 www.BRIXDG.com
These Drawings and Specifications as instruments of service are, and shall remain, the property of BRIX Design Group, LLC whether the project for which they are made is executed or not. All rights reserved. Any other use requires the express written authorization of the Architect.
PROJECT NUMBER:
STAMP
REVISIONS
ISSUE DATE
DESCRIPTION DATE
3 2 1456
B
C
D
E
A
B
C
D
E
231641 Certificate Number: 3869
PERMIT SET 11.22.24
M201
BUILDING TECHNOLOGIES CENTER ADDITION & INTERIOR
RENOVATIONS
FIRST FLOOR PLAN - DUST COLLECTION SYSTEM
231641
11.22.24
1201 WEST 3RD STREET
WILLIAMSPORT, PA 17701
PERMIT SET
# DESCRIPTION DATE
3 DUST COLLECTION 05/29/26
3/4" = 1'-0"1
FIRST FLOOR PLAN - DUST COLLECTION SYSTEM
File details come from the government source that posted it. Updated .