3-26-31 Part 3 BEYER EARLY CHILDHOOD CENTER FULL SET.pdf
PDF 9 MB Posted
- Solicitation number
- IFB No. 26-31
- Issued by
- Washington County, Illinois
About this file
This document comprises detailed architectural, mechanical, plumbing, and electrical construction drawings for toilet room renovations at Beyer Early Childhood Center, a facility operated by Rockford Public School District 205 in Rockford, Illinois. The project, identified as RPS Project Number 2607 and IFB #26-31, involves comprehensive renovation of seven toilet rooms (Rooms 108, 110, 122, 127, 140, 141, 169, and 171) totaling approximately 1,375 square feet of work, representing 2.8 percent of the building's 49,352.75 square foot total area. The project scope includes demolition and renovation of floors, walls, ceiling finishes, light fixtures, toilet fixtures, and toilet accessories. The work is classified as an Alteration Level 2 project in a Type II non-sprinklered building under Use Group E (Education). The project was issued for bidding on January 23, 2026, and must comply with the 2024 International Building Code, 2024 Illinois Energy Conservation Code, 2024 International Fire Code, 2024 International Mechanical Code, 2020 National Electrical Code, 2014 Illinois Plumbing Code, 2018 Illinois Accessibility Code, and 2010 ADA Standards for Accessible Design.
The project includes installation of new plumbing fixtures, including water closets (both standard and children's heights), lavatories (accessible and standard heights), urinals, floor drains, and associated piping; new HVAC supply and exhaust diffusers with flex duct connections and balance dampers; new electrical lighting fixtures with emergency battery backup options and occupancy sensors; and fire alarm notification appliances. Specific plumbing fixture quantities include multiple water closets, lavatories, and accessories distributed across the eight toilet rooms to meet code requirements for the facility's 603-person occupancy (520 students and 83 staff members). The design incorporates ceramic tile wall finishes, porcelain tile flooring, acoustic ceiling panels, grab bars, mirrors, soap dispensers, and toilet partitions throughout the renovated spaces. All work must maintain continuous utility service to unaffected building areas, coordinate with existing mechanical and electrical systems, and be performed in phases to minimize disruption to occupied facilities. Electrical work includes day and weekend premium labor, and the mechanical contractor must coordinate extensively with other trades regarding ductwork, piping, and equipment locations to avoid conflicts.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-26-31 Part1 Bid Specs.pdf | ||
| 2-26-31 Part 2 Project Manual 2026-01-23.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Larson & Darby Group
COPYRIGHT 2025
S H
E E T N
U M
B E R
P R
O
JE
C T N
U M
B E R
D A
T E
All drawn and written information appearing herein shall not be duplicated, disclosed, or otherwise used without the written consent of
IS
S U
E D
F O
R
D A
T E
-1
G .0
B E Y E R E
A R
LY
C H
IL
D
H O
O D
C E N
T E R T
O
IL
E T R
O O
M R
E N
O V
A T
IO
N S
R O
C K F O
R D
P U
B
LI
C S
C H
O O
L D
IS
T
T H
A V
E R O
C K
F O
R D
IL
-2
-2
ROCKFORD PUBLIC
SCHOOL DIST. 205
BEYER EARLY CHILDHOOD CENTER TOILET ROOM
RENOVATIONS
333 15TH AVE. ROCKFORD, IL 61104
01-23-2026
ISSUE FOR BIDDING
RPS PROJECT NUMBER: 2607
IFB#: 26-31
PROJECT LOCATION
IFB#: 26-31
Larson & Darby Group
COPYRIGHT 2025
S H
E E T N
U M
B E R
P R
O
JE
C T N
U M
B E R
D A
T E
All drawn and written information appearing herein shall not be duplicated, disclosed, or otherwise used without the written consent of
IS
S U
E D
F O
R
D A
T E
SHEET INDEX
PROJECT TEAM
-1
G .1
B E Y E R E
A R
LY
C H
IL
D
H O
O D
C E N
T E R T
O
IL
E T R
O O
M R
E N
O V
A T
IO
N S
R O
C K F O
R D
P U
B
LI
C S
C H
O O
L D
IS
T
T H
A V
E R O
C K
F O
R D
IL
-2
-2
GENERAL
G0.0 COVER SHEET
G0.1 PROJECT TEAM AND SHEET INDEX
G0.2 ABBREVIATIONS AND SYMBOLS
G0.3 CODE SUMMARY
G0.4 INTERIOR PARTITION STANDARDS
ARCHITECTURAL
A1.1 OVERALL FLOOR PLAN
A1.2 FLOOR PLAN - CHILDREN'S TOILET ROOM 169
A1.3 FLOOR PLAN - CHILDREN'S TOILET ROOM 171
A1.4 FLOOR PLAN - STAFF TOILET ROOM 140 & 141
A1.5 FLOOR PLAN - ACCESSIBLE TOILET ROOM 122 & 127
A1.6 FLOOR PLAN - CHILDREN'S TOILET ROOM 108
A1.7 FLOOR PLAN - CHILDREN'S TOILET ROOM 110
A1.8 ELEVATION REFERENCE PLAN & STANDARD MOUNTING HEIGHTS
A1.9 INTERIOR ELEVATIONS
A1.10 SECTION DETAILS
A2.1 FINISH & DOOR SCHEDULE & DETAILS
INTERIORS
I1.1 INTERIOR WALL FINISH PLAN
PLUMBING
P000 PLUMBING TITLE SHEET
P001 PLUMBING UNDERFLOOR DEMOLITION
P002 PLUMBING DEMOLITION
P003 PLUMBING UNDERFLOOR NEW WORK
P004 PLUMBING NEW WORK
P005 PLUMBING NEW WORK AREA A
P006 PLUMBING SCHEDULES
MECHANICAL
M000 MECHANICAL TITLE SHEET
MD100 MECHANICAL DEMOLITION - FIRST FLOOR
M100 MECHANICAL NEW WORK - FIRST FLOOR
ELECTRICAL
E000 ELECTRICAL TITLE SHEET
E001 ELECTRICAL DEMOLITION
E002 ELECTRICAL NEW WORK
E003 ELECTRICAL SCHEDULES
T C
ETIHCRADESN
C E
I L
SI
ONILLIFOETATS
LICENSED ARCHITECT
EXPIRES: _______________
DATE
ARCHITECTURAL
LARSON & DARBY GROUP
4949 HARRISON AVENUE, SUITE 100
IL. DESIGN FIRM NO. 184.000280-0007
815.484.0739
ROCKFORD, ILLINOIS 61108
DOCUMENTS ARE UNDER A SEPARATE
COVER
PLUMBING
KEDbluestone
707 NE JEFFERSON AVE
FIRM LICENSE NUMBER: 184-004470
(309) 938-4005
PEORIA, IL 61603
DOCUMENTS ARE UNDER A SEPARATE
COVER
HEATING, VENTING AND AIR CONDITIONING
KEDbluestone
707 NE JEFFERSON AVE
FIRM LICENSE NUMBER: 184-004470
(309) 938-4005
PEORIA, IL 61603
DOCUMENTS ARE UNDER A SEPARATE
COVER
ELECTRICAL
KEDbluestone
707 NE JEFFERSON AVE
FIRM LICENSE NUMBER: 184-004470
(309) 938-4005
PEORIA, IL 61603
INTERIORS
LARSON & DARBY GROUP
4949 HARRISON AVENUE, SUITE 100
IL. DESIGN FIRM NO. 184.000280-0007
815.484.0739
ROCKFORD, ILLINOIS 61108
UNDER SEPERATE SEAL
NORTH
PROJECT
NORTH
TRUE
Larson & Darby Group
COPYRIGHT 2025
S H
E E T N
U M
B E R
P R
O
JE
C T N
U M
B E R
D A
T E
All drawn and written information appearing herein shall not be duplicated, disclosed, or otherwise used without the written consent of
IS
S U
E D
F O
R
D A
T E
ACP-1
9'-0"
G3B-2
W S -2
A
.2
WS-1
2A3.2
3A4.1
101.2
.1
1059 S.F.
(30)
OFFICE
A
B
C E G K P S
V
D
F
H
I
J
L
M
N
O
R
Q
T
U
SYMBOLS
Y
X
W
STEEL
WOOD BLOCKING
FINISHED WOOD TRIM
PLYWOOD
GYP. WALLBOARDBATT INSULATION
(HORIZONTAL)
AB ANCHOR BOLT
ACCU AIR COOLED CONDENSING UNIT
ACP ACOUSTICAL CEILING PANEL
ACT ACOUSTICAL CEILING TILE
ADJ ADJUSTABLE, ADJACENT
A/E ARCHITECT/ENGINEER
AFF ABOVE FINISHED FLOOR
AGGR AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AL, ALUM ALUMINUM
ALR ARCHITECTURAL LOUVER
ALT ALTERNATE
AMP AMPERE
ANOD ANODIZE, ANODIZED
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE, APPROXIMATELY
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AUTO AUTOMATIC
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
AWI ARCHITECTURAL WOODWORKING INSTITUTE
AWP ACOUSTIC WALL PANEL
AWS AMERICAN WELDING SOCIETY
B&B BALLED & BURLAPPED
BB BALL BEARING
BFF BELOW FINISHED FLOOR
BIT BITUMINOUS
BLDG BUILDING
BM BEAM, BENCHMARK
BP BASE PLATE, BEARING PLATE
BRG BEARING
BSMT BASEMENT
BTR BETTER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
BTWN BETWEEN
CB CATCH BASIN, CERAMIC BASE, CHALKBOARD
CBB CEMENTITIOUS BACKER BOARD
CC CUBICLE CURTAIN
CD COILING DOOR
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD
CI CAST IRON, CURB INLET
CIP CAST IRON PIPE, CAST-IN-PLACE
CJ CONSTRUCTION JOINT, CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLG HT CEILING HEIGHT
CLL CONTRACT LIMIT LINE
CLR CLEAR
COMP COMPOSITE, COMPUTER
CM CASEWORK/MILLWORK
CMU CONCRETE MASONRY UNIT
CO CLEANOUT, CARBON MONOXIDE, CASED OPENING
COL COLUMN
CONC CONCRETE
COND CONDENSER, CONDITION
CONF CONFERENCE
CONN CONNECT, CONNECTION
CONT CONTINUE, CONTINUOUS
COORD COORDINATE
CORR CORRIDOR
CP CONCRETE PIPE, CONTROL PANEL
CPT CARPET
CPTT CARPET TILE
CPVC CHLORINATED POLYVINYL CHLORIDE
CSI CONSTRUCTION SPECIFICATIONS INSTITUTE
CSR CLOSET SHELF & ROD
CT CERAMIC TILE, CURRENT TRANSFORMER
CTR CENTER
CTRL CONTROL
CU FT CUBIC FEET
CU IN CUBIC INCH
CU YD CUBIC YARD
CUH CABINET UNIT HEATER
CUV CABINET UNIT VENTILATOR
CW COLD WATER, CLOCKWISE
CYL CYLINDER
D DEEP, DEPTH, PENNY (NAIL)
DAT DATUM
dB DECIBEL
D-B DESIGN-BUILD
DBL DOUBLE
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DEG DEGREE
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH, DEMOLITION, DEMONSTRATION
DET DETAIL
DFT DRY FILM THICKNESS
DHI DOOR HARDWARE INSTITUTE
DIA DIAMETER
DIM DIMENSION
DIP DUCTILE IRON PIPE
DL DEAD LOAD
DR DOOR, DRAIN
DS DOWNSPOUT
DT DRAIN TILE
DW DOMESTIC WATER, DISHWASHER
DWG DRAWING
DWV DRAIN, WASTE, & VENT
E EAST
EA EACH
EB EXPANSION BOLT
EF EACH FACE, EXHAUST FAN
EHD ELECTRIC HAND DRYER
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELAST ELASTOMER, ELASTOMERIC
ELEC ELECTRIC, ELECTRICAL
EM ENTRANCE MAT
EMER EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENAM ENAMEL
EP EPOXY
EPL ELECTRICAL PANEL
EPDM ETHYLENE PROPYLENE DIENE MONOMER
EPS EPANDED POLYSTYRENE BOARD (INSULATION)
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWH EXHAUST
EXIST EXISTING
EXP EXPAND, EXPANSION, EXPOSED
EXT EXTERIOR
EXV EXHAUST VENT
F FAHRENHEIT
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FiD FIRE DAMPER
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER & BRACKET
FEC FIRE EXTINGUISHER & CABINET
FF&E FURNITURE, FURNISHINGS, & EQUIPMENT
FFA FROM FLOOR ABOVE
FFB FROM FLOOR BELOW
FIN FINISH, FINISHED
FIN FLR FINISHED FLOOR
FL FLUSH
FLA FULL LOAD AMPS
FLR FLOOR
FLUOR FLUORESCENT
FM FACTORY MUTUAL
FR FRAME
FRP FIBERGLASS REINFORCED PLASTIC
FRG FIBER REINFORCED GYPSUM
FRTW FIRE RETARDANT TREATED WOOD
FT FOOT, FEET
FTG FOOTING
FTR FIN TUBE REGISTER
FURN FURNISH, FURNITURE
FV FLUSH VALVE
FWC FABRIC WALLCOVERING
G GUTTER, NATURAL GAS
GA GAGE
GAL GALLON
GALV GALVANIC, GALVANIZE, GALVANIZED
GALV STL GALVANIZED STEEL
GB## GRAB BAR (LENGTH IN INCHES)
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFRC GLASS FIBER-REINFORCED CONCRETE
GFRG GLASS FIBER-REINFORCED GYPSUM
G/DS GUTTER / DOWNSPOUT
GI GALVANIZED IRON
GL GLASS, GLAZING
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GUT GUTTER
GWH GAS-FIRED WATER HEATER
GWB GYPSUM WALLBOARD
GYP GYPSUM
H HIGH
HB HOSE BIBB
HC HANDICAP, HANDICAPPED
HD JT HEAD JOINT
HDWR HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSEPOWER
HR HOUR, HANDRAIL
HS HIGH STRENGTH, HEAT-STRENGTHENED (GLASS)
HT HEIGHT
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HW HOT WATER
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER, INSIDE DIMENSION
INCAND INCANDESCENT
INFO INFORMATION
INSUL INSULATE, INSULATION
INT INTERIOR
INV INVERT
INV EL INVERT ELEVATION
JAN JANITOR
JAN CLO JANITOR CLOSET
J-BOX JUNCTION BOX
KD KILN DRIED, KNOCKED DOWN
KIP THOUSAND POUNDS
KIP FT THOUSAND POUND - FEET
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
kV KILOVOLT kVA KILOVOLT AMPERE kW KILOWATT kWh KILOWATT HOUR
L ANGLE
LAM LAMINATE
LAV LAVATORY
LBS POUNDS
LED LIGHT EMITTING DIODE
LF LINEAL FEET (FOOT)
LKR/# LOCKER/QUANTITY
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LAUNDRY TRAY
LTG LIGHTING
LVT LUXURY VINYL TILE
M MINUTE, MINUTES
MATL MATERIAL
MAU MAKE UP AIR UNIT
MAX MAXIMUM
MB MOP BASIN
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLR MECHANICAL LOUVER
MO MASONRY OPENING, MECHANICAL OPENING
MR MOISTURE RESISTANT
MTD MOUNTED
MTL METAL
MULL MULLION
MWP METAL WALL PANEL
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NM NON METALLIC
NO NUMBER
NOM NOMINAL
NRP NON-REMOVABLE PIN (HINGES)
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER, OUTSIDE DIMENSION
OH DR OVERHEAD DOOR
OPNG OPENING
OPH OPPOSITE HAND
OPP OPPOSITE
OS OVERFLOW SCUPPER
P PAINT
PC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCI PRECAST/PRESTRESSED CONCRETE INSTITUTE
PCP PORTLAND CEMENT PLASTER
PE PROFESSIONAL ENGINEER
PL PROPERTY LINE, PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER, PLASTIC
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PLY PLYWOOD
PNL PANEL
POLY POLYETHYLENE
PORC PORCELAIN
POS POSITIVE
PP PUSH/PULL
PP PL PUSH/PULL PLATE
PPM PARTS PER MILLION
PPT PRESERVATIVE PRESSURE TREATED
PR PAIR
PRE POWER ROOF EXHAUSTER, PREFINISHED
PREFAB PREFABICATE, PREFABRICATED
PREP PREPARE, PREPARATION
PREV PREVIOUS
PROD PRODUCT, PRODUCTION
PROJ PROJECT
PRV POWER ROOF VENTILATOR, PRESSURE REDUCING VALVE,
PRESSURE REGULATOR VALVE, PRESSURE RELIEF VALVE
PS PULL STATION
PSC PROJECTION SCREEN, CEILING MOUNTED
PSW PROJECTION SCREEN, WALL MOUNTED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
PTD PAPER TOWEL DISPENSER
PTD/W PAPER TOWEL DISPENSER WITH WASTE RECEPTACLE
PTN PARTITION
PV PLUMBING VENT
PVC POLYVINYL CHLORIDE
PWR POWER
QRTZ QUARTZ
QRY QUARRY
QT QUARRY TILE
R RADIUS, RISER, THERMAL RESISTANCE
RA RETURN AIR
RB RUBBER BASE
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REBAR REINFORCING STEEL BARS
RECPT RECEPTACLE
REF REFERENCE, REFRIGERATOR
REFL REFLECT, REFLECTED
REINF REINFORCE, REINFORCED, REINFORCING
REM REMOVABLE
REQD REQUIRED
REV REVISE, REVISED, REVISION
RFM RECESSED FLOOR MAT
RM ROOM
RO ROUGH OPENING
RT RUBBER TILE
RTG RATING
RTU ROOFTOP UNIT
RWP ROOF WALKWAY PADS/PAVERS
S SOUTH
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
SALV SALVAGE
SAN SANITARY
SC SOLID CORE
SCONC SEALED CONCRETE
SCHED SCHEDULE
SCMU SOLID CONCRETE MASONRY UNIT
SD SOAP DISPENSER
SDI STEEL DECK INSTITUTE
SE STRUCTURAL ENGINEER
SECT SECTION
SF SQUARE FOOT (FEET)
SHT SHEET
SJI STEEL JOIST INSTITUTE
SKY SKYLIGHT
SND SANITARY NAPKIN DISPENSER
SNDL SANITARY NAPKIN DISPOSAL
SPEC SPECIFICATION
SPF SPRUCE-PINE-FIR
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SRD SECONDARY ROOF DRAIN
SS SOLID SURFACE MATERIAL
SSTL STAINLESS STEEL
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STL PL STEEL PLATE
STRUCT STRUCTURAL
SUH SUSPENDED UNIT HEATER
SUSP SUSPENDED
SV SHEET VINYL
SWS SHELVING WITH STANDARDS
SYM SYMBOL
SYMM SYMMETRICAL
T TREAD
TB TACK BOARD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TD TRENCH DRAIN
TEMP TEMPERATURE
TERR TERRAZZO
TFA TO FLOOR ABOVE
TFB TO FLOOR BELOW
THK THICK, THICKNESS
THRES THRESHOLD
THRU THROUGH
TI TAPERED INSULATION
TLP TOILET PARTITION
TLT TOILET
TOB TOP OF BEAM
TOC TOP OF CONCRETE, TOP OF CURB
TOF TOP OF FLOOR
TOJ TOP OF JOIST
TOS TOP OF SLAB
TOW TOP OF WALL
TS TUBE STEEL
TSTAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTD TOILET TISSUE DISPENSER
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UC UNDERCUT
UNO UNLESS NOTED OTHERWISE
UR URINAL
UV ULTRAVIOLET
V VOLT
VA VOLT AMPERE
VAV VARIABLE AIR VOLUME
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VET VINYL ENHANCED TILE
VFD VARIABLE FREQUENCY DRIVE
VG VERTICAL GRAIN
VIF VERIFY IN FIELD
VOC VOLATILE ORGANIC COMPOUND
VOL VOLUME
VR VAPOR RETARDER
VS VENT STACK
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
COLUMN CENTER LINES
WALL SECTION
BUILDING SECTION ROOM AREA & OCCUPANT LOAD
ROOM NAME & NUMBER
PARTITION TYPE
ELEVATION TARGET
DOOR/OPENING NUMBERS
PLAN OR SECTION DETAIL
ELEVATION MARK
W WEST, WASTE, WATT, WIDE
W/ WITH
W/O WITHOUT
WB WHITEBOARD
WC WATER CLOSET, WATER COLUMN
WCO WALL CLEANOUT
WD WOOD
WG WALL GUARD
WH WALL HUNG, WALL HYDRANT, WATER HEATER
WI WROUGHT IRON
WM WATER METER
WO WALK OFF CARPET TILE
WP WATERPROOFING, WEATHERPROOF, WORKING POINT
WR WATER REPELLANT, WEATHER RESISTANT
WV WOOD VENEER
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
WWR WELDED WIRE REINFORCING
XFER TRANSFER
XFMR TRANSFORMER
XPS EXTRUDED POLYSTYRENE BOARD (INSULATION)
YCO YARD CLEANOUT
YD YARD
YR YEAR
PLUS OR MINUS
ROUND, DIAMETER
SQUARE
CENTERLINEC
PLATE
L
PL
COURSE GRAVEL
EARTH
CONCRETE
ASPHALT PAVING
CONCRETE MASONRY
BRICK
(DIMENSION LUMBER, FULL SIZE)
WOOD BLOCKING
(DIMENSION LUMBER, CUT TO SIZE)
GLASS
NORTH ARROW (TRUE NORTH)
NORTH ARROW (PROJECT NORTH)
REVISION CLOUD
REVISION NUMBER
REVISION COMMENT
CEILING SYMBOL
CEILING MATERIAL
CEILING HEIGHT
KEYED NOTE SYMBOL
BREAK SYMBOL
RIGID INSULATION
SHEET SYMBOLS
ACCESSIBILITY CLEARANCES MATERIAL SYMBOLS
ABBREVIATIONS
FD FLOOR DRAIN
-1
G .2
B E Y E R E
A R
LY
C H
IL
D
H O
O D
C E N
T E R T
O
IL
E T R
O O
M R
E N
O V
A T
IO
N S
R O
C K F O
R D
P U
B
LI
C S
C H
O O
L D
IS
T
T H
A V
E R O
C K
F O
R D
IL
-2
-2
PROJECT DATA:
BUILDING CODES:
(WITH LOCAL AMENDMENTS)
BUILDING:
2024 INTERNATIONAL BUILDING CODE
ENERGY:
2024 ILLINOIS ENERGY CONSERVATION CODE
FIRE PREVENTION:
2024 INTERNATIONAL FIRE CODE
PROJECT TYPE:
ALTERATION LEVEL 2
USE GROUP:
E - EDUCATION
MECHANICAL, ELECTRICAL AND PLUMBING:
2024 INTERNATIONAL MECHANICAL CODE
2020 NATIONAL ELECTRICAL CODE
2014 ILLINOIS PLUMBING CODE
ACCESSIBILITY:
2018 ILLINOIS ACCESSIBILITY CODE
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
ANSI A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
BUILDING CONSTRUCTION TYPE:
TYPE II
SPRINKLER SYSTEM:
NON-SPRINKLERED
BUILDING AREA:
49,352.75 SF
AREA OF WORK:
1,375 SF
PROJECT NARRATIVE:
PROJECT CONSISTS OF THE ALTERATION OF THE TOILET
FACILITIES WITHIN THE BUILDING, INCLUDING FLOORS,
WALLS, CEILING FINISHES, LIGHT FIXTURES, TOILET FIXTURES,
AND TOILET ACCESSORIES.
THERE IS NO INCREASE IN THE BUILDING AREA AND NO
CHANGES ARE PROPOSED TO THE EXISTING EGRESS
MINIMUM NUMBER OF PLUMBING FIXTURES BY ILLINOIS PLUMBING CODE SECTION 890.810
DAY CARE CENTER (890.810 -2a)
FLOOR AREA PER PERSON (SQ. FT) 70 SF/PERSON
MINIMUM NUMBER OF PLUMBING FIXTURES BY ILLINOIS PLUMBING CODE 890 APPENDIX A, TABLE B
TYPE OF BUILDING DAY CARE, NURSERY AND PRESCHOOL CENTER TODDLERS
AT CAPACITY:
STUDENT COUNT: 520
BOY: 260
GIRLS: 260
STAFF COUNT: 83
MEN: 41
WOMEN: 42
TOTAL OCCUPANCY: 603
CODE PROVISION REQUIRED QUANTITY EXISTING PROPOSED
TOTAL OCCUPANCY (603) MALE FEMALE MALE FEMALE MALE FEMALE MALE FEMALE
WATER CLOSET 1: 1-10 1: 1-10 11 11 11 21 8 18
2: 11-25 2: 11-25 3: 26-50 3: 26-50 4: 51-75 4: 51-75 5: 76-100 5: 76-100 6: 101-125 6: 101-125 7: 126-150 7: 126-150 8: 151-175 8: 151-175
OVER 175: ADD 1 FIXTURE
PER RESTROOM FOR EACH
ADDITIONAL 50 PERSONS
URINALS URINALS MAY BE SUBSTITUTED X - 14 - 8 -
FOR WATER CLOSETS FOR
MALES, NOT TO EXCEED HALF
OF REQUIRED TOTAL NUMBER
OF WATER CLOSETS.
COMPARABLE FIXTURES FOR
FEMALES MAY BE SUBSTITUTED
FOR WATER CLOSETS FOR
FEMALES, NOT TO EXCEED
HALF OF THE REQUIRED TOTAL
NUMBER OF WATER CLOSETS.
LAVATORIES 1: 1-25 1: 1-25 11 11 9 11 10 +1 11
2: 11-25 2: 11-25 3: 26-50 3: 26-50 4: 51-75 4: 51-75 5: 76-100 5: 76-100 6: 101-125 6: 101-125 7: 126-150 7: 126-150 8: 151-175 8: 151-175
OVER 175: ADD 1 FIXTURE
PER RESTROOM FOR EACH
ADDITIONAL 50 PERSONS
WATER FOUNTAINS 1 PER 75 9 10 0
PERCENTAGE OF WORK:
1,375 / 49,352.75 = 2.8%
CHILDREN'S TOILET ROOM (GIRLS)
CHILDREN'S TOILET ROOM (BOYS)
CHILDREN'S TOILET ROOM (BOYS)
CHILDREN'S TOILET
ROOM (GIRLS)
FACULTY TOILET
ROOM (MALE)
FACULTY TOILET
ROOM (FEMALE)
DESIGNATED-USER
TOILET ROOM
DESIGNATED-USER
TOILET ROOM
ADA
AMBULATORY
ADA
ADA
ACCESSIBLE
ACCESSIBLE ACCESSIBLE
ADA
ADA
Larson & Darby Group
COPYRIGHT 2025
S H
E E T N
U M
B E R
P R
O
JE
C T N
U M
B E R
D A
T E
All drawn and written information appearing herein shall not be duplicated, disclosed, or otherwise used without the written consent of
IS
S U
E D
F O
R
D A
T E
CODE SUMMARY
-1
G .3
B E Y E R E
A R
LY
C H
IL
D
H O
O D
C E N
T E R T
O
IL
E T R
O O
M R
E N
O V
A T
IO
N S
R O
C K F O
R D
P U
B
LI
C S
C H
O O
L D
IS
T
T H
A V
E R O
C K
F O
R D
IL
-2
-2
SCALE: 1/16" = 1'-0"
1ST FLOOR CODE PLAN
LEGEND - MASONRY PARTITION BRACING
1. SPAN LIMITS BETWEEN CORNERS AND/OR NON-LOAD BEARING
INTERIOR MASONRY WALLS:
2. WALLS EXCEEDING SPAN LIMITS ABOVE REQUIRE STEEL BRACKETS
4'-0" O.C. ANCHORED TO STRUCTURE ABOVE ( WELDED OR SCREWED
AS REQUIRED AND APPROVED)
3. REFER TO DETAILS FOR VARIOUS CONDITIONS & BRACKET TYPES
WALL THICKNESS
(NOMINAL)
6" 8" 10" 12"
SPAN LIMIT
(HORIZONTAL)
14'-0" 18'-0" 23'-0" 28'-0"
WALL THICKNESS
PLUS 1/4" MAX
WALL THICKNESS
PLUS 1/4" MAX
WALL THICKNESS
PLUS 1/4" MAX
VERIFY
VERIFY VERIFY
TYPE A TYPE B TYPE C
" 2
PLATE
ANGLE
BENT PLATE
ANGLE
1. TYPICAL PLATE: 10 GAUGE 10" LONG. WIDTH VARIES W/ WALL TYPE
2. TYPICAL ANGLE: 3"X5"X1/4"X6" LONG (5" LEG VERTICAL)
3. TYPICAL SPACING: 4'-0" ON CENTER
4. FASTEN BRACKET TO DECK OR STRUCTURE ABOVE. DO NOT FASTEN TO CMU
METAL DECK
BRACKET TO METAL DECK IF
STEEL SPACING IS 6'-0" OR
GREATER
STEEL JOIST OR BEAM
PROVIDE 1/2" EXPANSION/FIRESTOPPING
MATERIAL AROUND STRUCTURAL STEEL AT
WALL PENETRATION
CMU WALL PERPENDICULAR TO JOIST
OR BEAM
BRACKET @ EACH JOIST
PERPENDICULAR TO STEEL JOIST
OR BEAM
TOP OF CMU
PROVIDE TYP. 2" GAP FOR
VERTICAL MOVEMENT OF
STRUCTURE & STRUCTURE
SUPPORTED MATERIALS
GENERAL NOTES - INTERIOR PARTITIONS
1. PLAN DIMENSIONS ARE TO THE FACE OF GWB OR CMU UNLESS NOTED OTHERWISE.
2. "HOLD" DIMENSIONS INDICATE THAT THE GIVEN DIMENSION IS TO BE MAINTAINED BETWEEN FINISHED SURFACES.
3. SUBSTITUTE TILE BACKER BOARD (TBB) FOR GWB AT AREAS INDICATED TO RECEIVE TILE.
4. REFER TO PROJECT MANUAL FOR FIRE-RESISTIVE JOINT SYSTEMS AND THROUGH-PENETRATION FIRESTOP SYSTEM IN FIRE-
RATED ASSEMBLIES.
5. SEE PROJECT MANUAL FOR FRAMING MATERIAL THICKNESS. STATED THICKNESS ARE THE MINIMUM REQUIRED. INCREASE
THE THICKNESS AS REQUIRED BY THE MANUFACTURER'S LIMITING HEIGHT TABLES.
6. PROVIDE BLOCKING FOR WALL MOUNTED EQUIPMENT. SEE PROJECT MANUAL FOR ALLOWABLE BLOCKING TYPES.
1/2" BOLT, TYP.
SECTION
PARTITION PARALLEL
TO DECK FLUTES
USE L4x3x1/4x0'-8"
FASTENED TO DECK
PARTITION PERPENDICULAR
TO DECK FLUTES
USE L4x3x1/8x8" FASTENED TO 8"x1'-0"x3/16" PLATE
FASTENED TO DECK
1/2" BOLT, TYP.
WT4x5x4" W/ 2-1/2"x3-1/8" STUDS
CEILING
BOND BEAM W/ (2) #
5 BARS CONT.
L3x3x3/16 BRACE AT 4'-0"
O.C. MAX, ALTERNATE
DIRECTION OF BRACE
SECTION
#5 BAR x 12" LONG @ 48"
O.C. IN GROUTED CELL, DRILL
BAR 4" INTO CONCRETE SLAB,
TYPICAL ALL CONDITIONS
ENTIRE PARTITION EXTENDS
TO JUST ABOVE THE FINISHED
CEILING
FLOOR
ENTIRE PARTITION EXTENDS
TO STRUCTURAL DECK, BRACE
TOP OF WALL AS INDICATED
WHERE 1-HOUR AND 2-HOUR
FIRE RATED WALL ASSEMBLY IS
REQUIRED, SEE SHEET A8.2 FOR
FIRE RATED HEAD CONDITION
TYPE "A" BRACKET
SHOWN, SEE DETAIL
THIS SHEET
METAL DECK
EXPANSION MATERIAL
(OR FIRE STOPPING)
PARTITION TERMINATES AT
BOTTOM CHORD OF JOIST, BRACE
TOP OF WALL AS INDICATED
METAL DECK
SLIP CONNECTION
STEEL JOIST
GWB/METAL STUDS
(RATED AS REQUIRED)
VERTICAL CONTROL
JOINTS AT 4'-0" O.C.
(MAX)
TYPE B BRACKET, SEE
DETAIL THIS SHEET
EXPANSION MATERIAL
(OR FIRE STOPPING
AT BRACKETS)
PARTITION TERMINATES AT
BOTTOM CHORD OF JOIST, BRACE
TOP OF WALL AS INDICATED
CEILING
METAL DECK
TYPE C BRACKET, SEE
DETAIL THIS SHEET
WELD
BOND BEAM W/ (2) #
5 BARS CONT
#5 BAR IN GROUTED
CELL AT 48" O.C.
LEGEND - MASONRY PARTITION HEAD CONDITIONS
LOW HEIGHT MASONRY PARTITION,
SEE INTERIOR ELEVATIONS FOR
HEIGHT AND DETAILS FOR
ADDITIONAL REQUIREMENTS
LOW HEIGHT MASONRY PARTITION,
SEE INTERIOR ELEVATIONS FOR
HEIGHT AND DETAILS FOR
ADDITIONAL REQUIREMENTS
SOLID CMU
BOND BEAM W/ (2)
#5 BARS CONT.
#5 BAR IN GROUT
CELL AT 48" O.C.
SE
E
IN
TE
RI
O
R
EL
EV
A
TI
O
N S
FO
R
H
EI
G H
T
SE
E
IN
TE
RI
O
R
EL
EV
A
TI
O
N S
FO
R
H
EI
G H
T
STUD BRACE AT 4'-0" O.C. MAX,
ALTERNATE DIRECTION OF BRACE
CEILING
ENTIRE PARTITION EXTENDS
TO 6" ABOVE CEILING
SYSTEM., BRACE TOP OF
WALL AS REQUIRED
FLOOR
LEGEND - STEEL STUD PARTITION HEAD CONDITIONS
STRUCTURAL DECK
STUD EXTENDS TO STRUCTURAL
DECK, GWB EXTENDS TO 6"
ABOVE CEILING SYSTEM BOTH
SIDES OF STUD
SLIP DETAIL
STUD FLANGE
BRACING1
'-0
M A
X
'-0
M
A X
STUD EXTENDS TO STRUCTURAL
DECK, GWB EXTENDS TO 6" ABOVE
CEILING SYSTEM ONE SIDE AND TO
STRUCTURAL DECK ONE SIDE
SLIP DETAIL
STUD FLANGE
BRACING1
'-0
M A
X
'-0
M
A X
ENTIRE PARTITION EXTENDS TO
STRUCTURAL DECK
SLIP DETAIL
WHERE 1-HOUR AND 2-HOUR
FIRE RATED WALL ASSEMBLY IS
REQUIRED, SEE SHEET A8.2 FOR
FIRE RATED HEAD CONDITION
CEILING
LOW HEIGHT PARTITION, SEE
INTERIOR ELEVATIONS FOR HEIGHT
AND DETAILS FOR ADDITIONAL
REQUIREMENTS
CANTILEVERED WALL
POST, WHERE SHOWN
ON PLAN
SE
E
IN
TE
RI
O
R
EL
EV
A
TI
O
N S
FO
R
H
EI
G H
T
LEGEND - MASONRY PARTITION NAMING
MASONRY PARTITION SERIES DESIGNATION
M MASONRY/CMU
MASONRY SIZE
4 4" NOMINAL
6 6" NOMINAL
8 8" NOMINAL
FIRE RATING
2 2 HOUR FIRE-RATED CONSTRUCTION, UL DESIGN NO. U905
3 3 HOUR FIRE-RATED CONSTRUCTION, UL DESIGN NO. U904
4 4 HOUR FIRE-RATED CONSTRUCTION, UL DESIGN NO. U901
M41-2
PARTITION SERIES
MASONRY UNIT SIZE, NOM.
FIRE RATING, IF INDICATED
PARTITION HEAD CONDITION
LEGEND - STEEL PARTITION NAMING
STEEL PARTITION SERIES DESIGNATION
H HAT SHAPED FURRING CHANNEL
S SHAFTWALL FRAMING
F STEEL STUD FURRING
Z Z-FURRING
G STEEL STUD FRAMING
STUD FURRING/FRAMING MEMBER SIZE
1 1-5/8" STEEL STUD
2.5 2-1/2" STEEL STUD
3 3-5/8" STEEL STUD
3.5 3-1/2" STEEL STUD
4 4" STEEL STUD
5.5 5-1/2" STEEL STUD
6 6" STEEL STUD
8 8" STEEL STUD
FURRING CHANNEL SIZE
7 7/8" HAT CHANNEL
1 1-1/2" HAT CHANNEL
G3B1-2s
PARTITION SERIES
FRAMING MEMBER SIZE, NOM.
FIRE RATING, IF INDICATED
PARTITION HEAD CONDITION
SOUND BATT INSULATION, IF INDICATED
GWB CONFIGURATION
GWB CONFIGURATION
A GWB ONE SIDE ONLY
B GWB BOTH SIDES
C GWB BOTH SIDES, TWO LAYERS
FIRE RATING
4 3/4 HOUR FIRE-RATED CONSTRUCTION
1 1 HOUR FIRE-RATED CONSTRUCTION
2 2 HOUR FIRE-RATED CONSTRUCTION
3 3 HOUR FIRE-RATED CONSTRUCTION
LEGEND - DIMENSIONING OF PARTITIONS ON THE FLOOR PLANS
G3B-2 M8-2 H7-1 M4-2 G3B-1
2"
6'-0" 12'-0" 6'-0" 6'-0" 3'-0" 9'-5 1/2" 8'-0" 8'-0"
5"
1. DIMENSION MARKS ARE TO THE FINISH FACE OF THE PARTITION, ONE SIDE ONLY.
2. REFER TO PARTITION TYPE DETAILS ON THIS SHEET FOR PARTITION THICKNESS.
LEGEND - STEEL STUD SLIP DETAILS
TYPICAL FOR ALL SLIP DETAIL OPTIONS: WHERE
TRACK IS PARALLEL TO DECK FLUTES AND DOES
NOT FALL ON BOTTOM OF DECK RIB, PROVIDE 4"
WIDE x 8" LONG x 18GA FLAT STRAPPING AT 32"
O.C. TO SPAN VOID IN DECK. FASTEN TRACK TO
STRAPPING
" 3" SLOTTED DEFLECTION TRACK (2" SLOTS)
INSTALL FASTENER AT MID-HEIGHT OF
SLOT
SEE STEEL PARTITION HEAD CONDITIONS
FOR GWB
DO NOT FASTEN GWB TO SLOTTED
TRACKSLIP DETAIL - OPTION 1
SLIP DETAIL - OPTION 2
SLIP DETAIL - OPTION 3
METAL DECK OR STRUCTURE
2" MIN. DEEP LEG TRACK FASTENED TO
METAL DECK
PARTITION TOP TRACK FASTENED TO
STUDS
SEE STEEL PARTITION HEAD CONDITIONS
FOR GWB
METAL DECK OR STRUCTURE
2" MIN. DEEP LEG TRACK FASTENED TO
METAL DECK. DO NOT FASTEN STUD TO
TRACK
SEE STEEL PARTITION HEAD CONDITIONS
FOR GWB
COLD-ROLLED CHANNEL BRIDGING
CLIP ATTACHMENT TO STUD
M A
X
H7
5/8" GWB
7/8" HAT CHANNEL
AT 24" O.C.
1 1/2"
S U
B S
TR
A
TE
S U
B S
TR
A
TE
H1
2 1/8"
5/8" GWB
1-1/2" HAT
CHANNEL AT 24"
O.C.
S4A
1 LAYER 5/8" GWB
4" I-STUD AT 24" O.C.
1" GWB SHAFTLINER
4 5/8"
S6A
1 LAYER 5/8" GWB
6" I-STUD AT 24" O.C.
1" GWB SHAFTLINER
6 5/8"
S U
B S
TR
A
TE
5/8" GWB
1 5/8" METAL STUD
AT 16" O.C.
1/4" NOMINAL GAP
BETWEEN SUBSTRATE
AND STUD
CLIP STUD TO
SUBSTRATE AT 4'-0"
O.C. MAX
F1
2 1/2"
F2 F3
S U
B S
TR
A
TE
S U
B S
TR
A
TE
5/8" GWB
2 1/2" METAL STUD
AT 16" O.C.
1/4" NOMINAL GAP
BETWEEN SUBSTRATE
AND STUD
CLIP STUD TO
SUBSTRATE AT 4'-0"
O.C. MAX
3 3/8"
5/8" GWB
3 5/8" METAL STUD
AT 16" O.C.
1/4" NOMINAL GAP
BETWEEN SUBSTRATE
AND STUD
CLIP STUD TO
SUBSTRATE AT 4'-0"
O.C. MAX
4 1/2"
S U
B S
TR
A
TE
Z15
5/8" GWB
1 1/2" Z-FURRING
AT 24" O.C.
2 1/8"
S U
B S
TR
A
TE
Z2
5/8" GWB
1 1/2" Z-FURRING
AT 24" O.C.
S U
B S
TR
A
TE
Z25
5/8" GWB
2 1/2" Z-FURRING
AT 24" O.C.
S U
B S
TR
A
TE
5/8" GWB
3" Z-FURRING AT
24" O.C.
Z3
G2A G3A G6A
G2B G3B G6B
B3B1 G6B1
G3C2 G6C2
2 5/8" 3 1/8" 3 5/8"
5/8" GWB
2 1/2" METAL STUD
AT 16" O.C.
5/8" GWB
3 5/8" METAL STUD
AT 16" O.C.
5/8" GWB
6" METAL STUD
AT 16" O.C.
3 1/8" 4 1/4" 6 5/8"
5/8" GWB
2 1/2" METAL STUD
AT 16" O.C.
3 3/4"
6 1/8"
4 7/8" 7 1/4"
8 1/2"
1 HOUR FIRE RATED
UL DESIGN U465
2 HOUR FIRE RATED
UL DESIGN U419
1 HOUR FIRE RATED
UL DESIGN U465
2 HOUR FIRE RATED
UL DESIGN U419
LEGEND - PARTITION TYPES
5/8" GWB
3 5/8" METAL STUD
AT 16" O.C.
5/8" GWB
6" METAL STUD AT
16" O.C.
2ND LAYER OF
GWB, IF INDICATED
2ND LAYER OF
GWB, IF INDICATED
5/8" GWB
3/4" HAT CHANNEL
AT 18" O.C.
H3
1 3/8"
C3A
C3B
5/8" CEMENT
BACKER BOARD
3 5/8" METAL STUD
AT 16" O.C.
4 1/4"
4 7/8"
3 5/8" METAL STUD
AT 16" O.C.
5/8" CEMENT
BACKER BOARD
3'-0"
FIRE/SMOKE BARRIER
PROTECT PENETRATIONS
FIRE BARRIER SIGNAGE:
1. LOCATE WITHIN 15 FEET OF THE END OF EACH WALL AND AT
INTERVALS NOT EXCEEDING 30 FEET MEASURED HORIZONTALLY
ALONG THE WALL OR PARTITION.
2. LETTERING NOT LESS THAN 3 INCHES IN HEIGHT WITH A MINIMUM
3/8-INCH STROKE. RED LETTERS ON WHITE BACKGROUND
LEGEND - FIRE/SMOKE BARRIER SIGNAGE
Larson & Darby Group
COPYRIGHT 2025
S H
E E T N
U M
B E R
P R
O
JE
C T N
U M
B E R
D A
T E
All drawn and written information appearing herein shall not be duplicated, disclosed, or otherwise used without the written consent of
IS
S U
E D
F O
R
D A
T E
-1
G .4
B E Y E R E
A R
LY
C H
IL
D
H O
O D
C E N
T E R T
O
IL
E T R
O O
M R
E N
O V
A T
IO
N S
R O
C K F O
R D
P U
B
LI
C S
C H
O O
L D
IS
T
T H
A V
E R O
C K
F O
R D
IL
-2
-2
981 829
916 960
5,163
1,066
930914
829981
961 956
3,197
1,616
189 920
13,394
174 140
468406
1,465
33 35
6,956
Jan.
Early Childhood
Early Childhood Early Childhood
Early Childhood
Early Childhood
Early Childhood Early Childhood
Early Childhood Early Childhood
Early Childhood Early Childhood
Resource
Gym/Multi-Purpose
Early Childhood
Early Childhood
Early Childhood
Early Childhood
Team
Early Childhood
Early ChildhoodEarly Childhood
Early Childhood Early Childhood
Resource Center
Early Childhood
Corridor
Vestibule J
Corridor
Vestibule I
Corridor
Corridor
Lobby
Corridor
Vestibule H Corridor
Corridor
Men
OT/PT
Stor
Girls
Boys
Jan.
Stor
Water Meter
Stor
Kitchen
Stor
Nurse
Wellness
Vest Vest
AP Off Princ
Waiting
Recept
Coats
HallwayWomen
Faculty/Work
RR
Faculty/Work
Hall
RR
Stor
Corridor
EntranceStorage
Corridor
Elec. Meter
Coats
OT/PT
RR RR
Girls
Janitor
Boys
Hallway
Hallway
HS Admin
Speech
Hallway
Hallway
Office/I.T.
Corridor
157 158
160 161
163 164
147148
149151
126 123
B102
143 129
B106 B107
B114 B111
B108
B109
B103
B110
B113
B112
117.1 116
127 122
Entrance_Arrow_Green
Entrance_Arrow_Green
Entrance_Arrow_Green
H
Entrance_Arrow_Green
Entrance_Arrow_Green
Entrance_Arrow_Green
5 A1.5 1 A1.5
1 A1.4
1 A1.2
1 A1.6
1 A1.3
1 A1.7
Larson & Darby Group
COPYRIGHT 2025
S H
E E T N
U M
B E R
P R
O
JE
C T N
U M
B E R
D A
T E
All drawn and written information appearing herein shall not be duplicated, disclosed, or otherwise used without the written consent of
IS
S U
E D
F O
R
D A
T E
-1
A .1
B E Y E R E
A R
LY
C H
IL
D
H O
O D
C E N
T E R T
O
IL
E T R
O O
M R
E N
O V
A T
IO
N S
R O
C K F O
R D
P U
B
LI
C S
C H
O O
L D
IS
T
T H
A V
E R O
C K
F O
R D
IL
-2
-2
OVERALL FLOOR PLAN
SCALE: 3/32" = 1'-0"
FIRST FLOOR - EXISTING
NORTH
PROJECT
TRUE
BOYS
D03
D03
D01
D03.2
D05
D07
D03
D03
D03
D03
D01
D01.1V .I.
F
'-0
V .I.F
10'-8"
V .I.
F
'-8
V .I.
F
'-0
4'-3" V.I.F
V.I.F
4'-11"
2'-8 " V
.I.F
BOYS
'-6
'-6
'-8
'-4
'-8
V .I.
F
'-0
2'-6"
2'-6"
2'-7"
1'-3"
'-6
'-6
'-6
'-7
/8
R02
A
.1
ALIGN TOILET TO
EXISTING OPENING
18B
18B
7B 9B
8B
1B
1B
37B
G3B-1
G3A-1
G A
-1
G A
-1
HOLD 32" M
IN.
15B
15B
G 3A
-1
'-3
2'-3"
R04
R05
G3B-1
-A
2'-1" 2'-6"
10'-8"
3'-7" 1'-6" 1'-0"
5'-1" 4'-0" 5'-1" 1'-0"
10B
10B
10B
5B
5B
5B
5B
ACP1
8'-0"
STORAGE
CABINET BELOW
D02
EXISTING HARD CEILING
GYPSUM OR PLASTER CEILING
1. BEFORE BEGINNING WORK AT THE SITE AND THROUGHOUT THE COURSE OF WORK, INSPECT AND VERIFY THE LOCATION AND CONDITION OF EVERY ITEM AFFECTED BY THE WORK UNDER THIS CONTRACT AND REPORT DISCREPANCIES TO THE ARCHITECT BEFORE BEGINNING WORK
RELATED TO THAT BEING INSPECTED.
2. BEFORE BEGINNING WORK AT THE SITE, INSPECT THE EXISTING BUILDING AND DETERMINE THE EXTENT OF EXISTING FINISHES, SPECIALTIES, EQUIPMENT, AND OTHER ITEMS WHICH MUST BE REMOVED AND REINSTALLED IN ORDER TO PERFORM THE WORK UNDER THIS CONTRACT.
3. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPLE AREAS WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT. INCIDENTAL WORK MAY ALSO BE NECESSARY IN AREAS NOT SHOWN ON THE ARCHITECTURAL DRAWINGS DUE TO CHANGES AFFECTING EXISTING MECHANICAL, ELECTRICAL, PLUMBING, AND OTHER SYSTEMS. SUCH INCIDENTAL WORK IS ALSO PART OF THIS CONTRACT. INSPECT THOSE AREAS AND ASCERTAIN WORK NEEDED AND DO THAT WORK IN ACCORDANCE WITH THE CONTRACT REQUIREMENTS AT NO ADDITIONAL
COST.
4. PROTECT EXISTING FINISHES TO REMAIN FROM DAMAGE.
5. REPAIR, PATCH, OR REFINISH AS APPLICABLE TO MATCH ADJACENT EXISTING FINISHES, THOSE FINISHES DAMAGED OR NEWLY EXPOSED
DURING PERFORMANCE OF THE WORK UNDER THIS CONTRACT.
6. WHERE MATCH EXISTING IS INDICATED, NEW CONSTRUCTION OR FINISHES, SHALL MATCH THE EXISTING IN EVERY PARTICULAR.
7. WHERE PERMANENT REMOVAL OF EXISTING CASEWORK, DOORS AND FRAMES, EQUIPMENT, OR FURNISHINGS IS REQUIRED AND PREVIOUSLY CONCEALED SURFACES ARE TO REMAIN EXPOSED, PATCH PREVIOUSLY CONCEALED SURFACES TO MATCH ADJACENT EXPOSED SURFACES.
WHERE SUCH SURFACES ARE SCHEDULED TO RECEIVE NEW FINISHES, PREPARE THE SURFACES TO RECEIVE THE NEW FINISHES.
8. WHERE CUTTING OF EXISTING SURFACES OR REMOVAL OF EXISTING SURFACES IS REQUIRED TO PERFORM THE WORK UNDER THIS CONTRACT, AND NEW FINISH IS NOT INDICATED, FILL RESULTING OPENINGS AND PATCH THE SURFACE AFTER DOING THE WORK AND FINISH
TO MATCH ADJACENT EXISTING SURFACES.
9. REFER TO NEW WORK PLANS TO COORDINATE EXTENT OF DEMOLITION REQUIRED.
10. REFER TO MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS FOR ADDITIONAL DEMOLITION REQUIRED. CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY UPON DISCOVERY OF CONFLICT OR DISCREPANCY WITH ITEMS INDICATED TO BE REMOVED.
11. WHERE NOT SPECIFICALLY NOTED, CONTRACTOR SHALL MODIFY EXISTING FLOORING AND CEILING CONSTRUCTION TO REMAIN AS
REQUIRED TO ABUT NEW CONSTRUCTION AND MATCH ADJACENT EXISTING CONDITIONS.
12. COORDINATE SLAB REMOVAL AND REPLACEMENT WITH PLUMBING AND ELECTRICAL UNDERGROUND AND IN-SLAB WORK.
13. WHERE AN ITEM IS SHOWN TO BE REMOVED OR DEMO'ED ALL MECHANICAL, ELECTRICAL, AND PLUMBING COMPONENTS SHALL BE REMOVED WITH IT U.N.O. PIPING SHALL BE REMOVED TO WITHIN NEAREST WALL TO REMAIN AND CAPPED. ELECTRICAL WIRING AND CONDUIT SHALL BE REMOVED BACK TO NEAREST JUNCTION BOX TO REMAIN. DUCTS AND TERMINALS SHOULD BE REMOVED AS FAR AS NECESSARY FOR NEW
DISTRIBUTION SYSTEM OR COMPONENTS TO TIE INTO, OR CAP WITHIN CONCEALED SPACE.
GENERAL NOTES - DEMOLITION
1. COORDINATE LIGHTING LAYOUT WITH ELECTRICAL DRAWINGS AND
SPECIFICATIONS.
2. COORDINATE DIFFUSERS, GRILLES, AND DUCTWORK WITH MECHANICAL
DRAWINGS AND SPECIFICATIONS.
3. CEILING HEIGHT SHOWN ON REFLECTED CEILING PLANS ARE AN
APPROXIMATION. NEW CEILING SHOULD BE INSTALLED AT THE SAME
ELEVATION AS THE PREVIOUS CEILING.
GENERAL NOTES - REFLECTED CEILING
2' X 2' LAY-IN ACOUSTICAL
CEILING PANEL SYSTEM
LEGEND - REFLECTED CEILING
EXISTING 2' X 2' LAY-IN ACOUSTICAL
CEILING PANEL SYSTEM
2'x4' RECESSED TROFFER
LIGHT FIXTURE
RECESSED WALL WASHER
RECESSED LIGHT FIXTURE
SUPPLY AIR DIFFUSER
EXHAUST AIR REGISTER
RETURN AIR REGISTER / TRANSFER GRILLE
EXISTING 1'x4' SURFACE
MOUNTED LIGHT FIXTURE
EXISTING 12" DIA. SURFACE MOUNTED
DECORATIVE LIGHT FIXTURE
2'x2' RECESSED TROFFER
LIGHT FIXTURE
1. DIMENSIONS ON FLOOR PLAN ARE BASED ON FACE OF FINISHED WALL TO FACE OF FINISHED WALL (NOMINAL).
2. VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE. PORTIONS OF EXISTING CONSTRUCTION MAY HAVE BEEN
REMOVED BY OWNER.
3. MAINTAIN CONTINUOUS UTILITY SERVICE TO ALL SPACES IN THE BUILDING NOT AFFECTED BY THIS WORK. COORDINATE WITH OWNER ANY DISRUPTION IN SERVICES REQUIRED TO PERFORM WORK OR TO MODIFY EXISTING PIPING, DUCTWORK
OR ANY ASSOCIATED EQUIPMENT.
4. REFER TO SHEETS A1.8 AND A1.9 FOR ELEVATIONS.
5. REFER TO SHEET A2.1 FOR ROOM FINISH AND DOOR SCHEDULES.
6. REFER TO SHEETS A2.1 AND I1.1 FOR MATERIAL DESIGNATIONS.
GENERAL NOTES - FLOOR PLAN
Larson & Darby Group
COPYRIGHT 2025
S H
E E T N
U M
B E R
P R
O
JE
C T N
U M
B E R
D A
T E
All drawn and written information appearing herein shall not be duplicated, disclosed, or otherwise used without the written consent of
IS
S U
E D
F O
R
D A
T E
-1
A .2
B E Y E R E
A R
LY
C H
IL
D
H O
O D
C E N
T E R T
O
IL
E T R
O O
M R
E N
O V
A T
IO
N S
R O
C K F O
R D
P U
B
LI
C S
C H
O O
L D
IS
T
T H
A V
E R O
C K
F O
R D
IL
-2
-2
FLOOR PLAN - CHILDREN'S TOILET ROOM 169NORTH
PROJECT
NORTH
TRUE
SCALE: 3/8" = 1'-0"
TOILET ROOM 169 - DEMOLITION
1 SCALE: 3/8" = 1'-0"
TOILET ROOM 169 - RENOVATION
2 SCALE: 3/8" = 1'-0"
REFLECTED CEILING PLAN 169 - RENOVATION
4SCALE: 3/8" = 1'-0"
REFLECTED CEILING PLAN 169 - DEMOLITION
LEGEND - KEYNOTE
KEY VALUE KEYNOTE TEXT
D01 REMOVE CONCRETE FLOOR AS REQUIRED FOR NEW PLUMBING. COORDINATE CONCRETE REMOVAL WITH
PLUMBING DRAWINGS.
D01.1 REMOVE EXISTING FLOOR FINISHES DOWN TO CLEAN AND BARE SUBSTRATE. PREPARE FLOOR TO RECEIVE NEW
FINISHES.
D02 REMOVE EXISTING CEILING SYSTEM INCLUDING ALL LIGHTS, HANGARS, HVAC COMPONENTS, ELECTRICAL FIXTURES, AND ANY OTHER MISCELLANEOUS ACCESSORIES. COORDINATE EXTENT OF DEMO WITH MECHANICAL AND ELECTRICAL DRAWINGS. REMOVE MISCELLANEOUS SUSPENDED EQUIPMENT AND COMPONENTS AS
REQUIRED FOR NEW CONSTRUCTION. PREPARE AREA FOR NEW CEILING OR FINISH
D03 REMOVE EXISTING WALL OR PORTION OF EXISTING WALL AS INDICATED. REMOVE ALL ASSOCIATED FINISHES (WALL TILE, ETC.), MECHANICAL, ELECTRICAL, AND PLUMBING COMPONENTS ON/IN/ OR ASSOCIATED WITH WALL TO BE REMOVED. PATCH AND REPAIR AS NECESSARY TO PREPARE AREA TO RECEIVE NEW CONSTRUCTION
D03.2 REMOVE ALL WALL FIXTURES AND ACCESSORIES AND PREPARE WALLS TO RECEIVE NEW FINISHES. COORDINATE
WITH FINISH SCHEDULE.
D05 COORDINATE THE REMOVAL AND ALTERATION OF MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION
WORK WITH MEP&FP DRAWINGS IN THIS SET.
D07 TOTAL ROOM DEMOLITION OF FIXTURES AND FINISHES DOWN TO USABLE SUBSTRATE. REMOVE EXISTING PLUMBING FIXTURES, LIGHT FIXTURES, FLOOR AND CEILING FINISHES, WALL BASE, AND TOILET PARTITIONS AND
ACCESSORIES IN THEIR ENTIRETY. PREPARE SPACE FOR NEW CONSTRUCTION.
R02 WRAP EXPOSED PLUMBING PIPES, DRAINS AND WATER SUPPLY LINES UNDER SINKS TO PROTECT AGAINST
BURNS, CUTS AND ABRASIONS.
R04 NEW STORAGE CABINET. REFER TO DETAILS 1 AND 2 ON A1.10 FOR ELEVATION AND SECTION DETAIL. WIDTH
AND DEPTH MAY VARY, REFER TO FLOOR PLANS FOR STORAGE CABINET SIZE.
R05 BABY CHANGING COUNTERTOP MEASURING 41" WIDE x 27" DEEP x 30" HIGH - ABOVE FINISHED FLOOR.
INCLUDE BACK SPLASH AND SIDE SPLASH AS REQUIRED. COUNTERTOP TO BE SUPPORTED BY (3) IRON SUPPORTS' 20"H x 12"V HD FRONT MOUNT COUNTERTOP L BRACKET. ONE NEAR EACH END AND ONE IN THE CENTER TO ENSURE EVEN WEIGHT DISTRIBUTION. BRACKETS SHOULD BE SPACED 16-24 INCHES APART. WHENEVER POSSIBLE ALIGN EACH BRACKET WITH WALL STUDS FOR MAXIMUM SUPPORT. MODEL NUMBER 0647213497441.
SCHEDULE - TOILET ACCESSORIES
ACCESSORY NUMBER DESCRIPTION MANUFACTURER MODEL COMMENTS
1 SOAP DISPENSER BRADLEY 6A00-11 FURNISHED BY OWNER, INSTALLED BY GC
1B SOAP DISPENSER BRADLEY 6A00-11 FURNISHED BY OWNER, INSTALLED BY GC
5 24"x36" MIRROR BOBRICK B-290 2436
5B 24"x36" MIRROR BOBRICK B-290 2436
7B 42" GRAB BAR BRADLEY 8122-001420
8B 36" GRAB BAR BRADLEY 8122-001360
9B 18" GRAB BAR BRADLEY 8122-001180
10B TOILET PAPER DISPENSER BRADLEY 5234-52 FURNISHED BY OWNER, INSTALLED BY GC
15B PAPER TOWEL DISPENSER SEE SPECS SEE SPECS FURNISHED BY OWNER, INSTALLED BY GC
18 OVERHEAD BRACED TOILET PARTITION SEE SPECS SEE SPECS
18B OVERHEAD BRACED TOILET PARTITION SEE SPECS SEE SPECS
20 URINAL SCREEN SEE SPECS SEE SPECS
37 WASTE RECEPTACLE ASI 0826 FURNISHED BY OWNER, INSTALLED BY GC
38 WASTE DISPOSAL ASI 0815 FURNISHED BY OWNER, INSTALLED BY GC
GIRLS
D01
D05
D07
D03
D03
D03
D01.1
D03
D03
V .I.
F
'-2
4'-0" V.I.F
'-1
V .I.
F
'-6
V .I.
F
3'-6" V.I.F
A
1.
GIRLS
'-1
'-9
'-9
'-4
'-5
'-1
'-6
'-6
'-9
'-9
'-9
'-9
'-7
'-5
1' -3
2' -6
2' -6
2' -6
2' -6
2' -6
5'-1" 4'-1" 5'-0"
R02
ALIGN AMBULATORY
TOILET TO EXISTING
OPENING
1B
1B
37B
7B
7B
8B
9B7B
18B
18B
18B
18B
18B
18B
18B 38 G3A-1
G3A-1
G3A-1
ALIGN TOILET TO
EXISTING OPENING
R05
R04
R04
G3B-1
G3B-1
1'-3"
3'-6"
'-6
'-5
4'-0"
15B
15B
10B
10B
10B
10B
10B
10B
10B
10B
10B
5B
5B
H3
D02
EXISTING HARD CEILING
GYPSUM OR PLASTER CEILING
ACP1
8'-0"
STORAGE
CABINETS BELOW
1. BEFORE BEGINNING WORK AT THE SITE AND THROUGHOUT THE COURSE OF WORK, INSPECT AND VERIFY THE LOCATION AND CONDITION OF EVERY ITEM AFFECTED BY THE WORK UNDER THIS CONTRACT AND REPORT DISCREPANCIES TO THE ARCHITECT BEFORE BEGINNING WORK
RELATED TO THAT BEING INSPECTED.
2. BEFORE BEGINNING WORK AT THE SITE, INSPECT THE EXISTING BUILDING AND DETERMINE THE EXTENT OF EXISTING FINISHES, SPECIALTIES, EQUIPMENT, AND OTHER ITEMS WHICH MUST BE REMOVED AND REINSTALLED IN ORDER TO PERFORM THE WORK UNDER THIS CONTRACT.
3. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPLE AREAS WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT. INCIDENTAL WORK MAY ALSO BE NECESSARY IN AREAS NOT SHOWN ON THE ARCHITECTURAL DRAWINGS DUE TO CHANGES AFFECTING EXISTING MECHANICAL, ELECTRICAL, PLUMBING, AND OTHER SYSTEMS. SUCH INCIDENTAL WORK IS ALSO PART OF THIS CONTRACT. INSPECT THOSE AREAS AND ASCERTAIN WORK NEEDED AND DO THAT WORK IN ACCORDANCE WITH THE CONTRACT REQUIREMENTS AT NO ADDITIONAL
COST.
4. PROTECT EXISTING FINISHES TO REMAIN FROM DAMAGE.
5. REPAIR, PATCH, OR REFINISH AS APPLICABLE TO MATCH ADJACENT EXISTING FINISHES, THOSE FINISHES DAMAGED OR NEWLY EXPOSED
DURING PERFORMANCE OF THE WORK UNDER THIS CONTRACT.
6. WHERE MATCH EXISTING IS INDICATED, NEW CONSTRUCTION OR FINISHES, SHALL MATCH THE EXISTING IN EVERY PARTICULAR.
7. WHERE PERMANENT REMOVAL OF EXISTING CASEWORK, DOORS AND FRAMES, EQUIPMENT, OR FURNISHINGS IS REQUIRED AND PREVIOUSLY CONCEALED SURFACES ARE TO REMAIN EXPOSED, PATCH PREVIOUSLY CONCEALED SURFACES TO MATCH ADJACENT EXPOSED SURFACES.
WHERE SUCH SURFACES ARE SCHEDULED TO RECEIVE NEW FINISHES, PREPARE THE SURFACES TO RECEIVE THE NEW FINISHES.
8. WHERE CUTTING OF EXISTING SURFACES OR REMOVAL OF EXISTING SURFACES IS REQUIRED TO PERFORM THE WORK UNDER THIS CONTRACT, AND NEW FINISH IS NOT INDICATED, FILL RESULTING OPENINGS AND PATCH THE SURFACE AFTER DOING THE WORK AND FINISH
TO MATCH ADJACENT EXISTING SURFACES.
9. REFER TO NEW WORK PLANS TO COORDINATE EXTENT OF DEMOLITION REQUIRED.
10. REFER TO MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS FOR ADDITIONAL DEMOLITION REQUIRED. CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY UPON DISCOVERY OF CONFLICT OR DISCREPANCY WITH ITEMS INDICATED TO BE REMOVED.
11. WHERE NOT SPECIFICALLY NOTED, CONTRACTOR SHALL MODIFY EXISTING FLOORING AND CEILING CONSTRUCTION TO REMAIN AS
REQUIRED TO ABUT NEW CONSTRUCTION AND MATCH ADJACENT EXISTING CONDITIONS.
12. COORDINATE SLAB REMOVAL AND REPLACEMENT WITH PLUMBING AND ELECTRICAL UNDERGROUND AND IN-SLAB WORK.
13. WHERE AN ITEM IS SHOWN TO BE REMOVED OR DEMO'ED ALL MECHANICAL, ELECTRICAL, AND PLUMBING COMPONENTS SHALL BE REMOVED WITH IT U.N.O. PIPING SHALL BE REMOVED TO WITHIN NEAREST WALL TO REMAIN AND CAPPED. ELECTRICAL WIRING AND CONDUIT SHALL BE REMOVED BACK TO NEAREST JUNCTION BOX TO REMAIN. DUCTS AND TERMINALS SHOULD BE REMOVED AS FAR AS NECESSARY FOR NEW
DISTRIBUTION SYSTEM OR COMPONENTS TO TIE INTO, OR CAP WITHIN CONCEALED SPACE.
GENERAL NOTES - DEMOLITION
1. COORDINATE LIGHTING LAYOUT WITH ELECTRICAL DRAWINGS AND
SPECIFICATIONS.
2. COORDINATE DIFFUSERS, GRILLES, AND DUCTWORK WITH MECHANICAL
DRAWINGS AND SPECIFICATIONS.
3. CEILING HEIGHT SHOWN ON REFLECTED CEILING PLANS ARE AN
APPROXIMATION. NEW CEILING SHOULD BE INSTALLED AT THE SAME
ELEVATION AS THE PREVIOUS CEILING.
GENERAL NOTES - REFLECTED CEILING
2' X 2' LAY-IN ACOUSTICAL
CEILING PANEL SYSTEM
LEGEND - REFLECTED CEILING
EXISTING 2' X 2' LAY-IN ACOUSTICAL
CEILING PANEL SYSTEM
2'x4' RECESSED TROFFER
LIGHT FIXTURE
RECESSED WALL WASHER
RECESSED LIGHT FIXTURE
SUPPLY AIR DIFFUSER
EXHAUST AIR REGISTER
RETURN AIR REGISTER / TRANSFER GRILLE
EXISTING 1'x4' SURFACE
MOUNTED LIGHT FIXTURE
EXISTING 12" DIA. SURFACE MOUNTED
DECORATIVE LIGHT FIXTURE
2'x2' RECESSED TROFFER
LIGHT FIXTURE
1. DIMENSIONS ON FLOOR PLAN ARE BASED ON FACE OF FINISHED WALL TO FACE OF FINISHED WALL (NOMINAL).
2. VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE. PORTIONS OF EXISTING CONSTRUCTION MAY HAVE BEEN
REMOVED BY OWNER.
3. MAINTAIN CONTINUOUS UTILITY SERVICE TO ALL SPACES IN THE BUILDING NOT AFFECTED BY THIS WORK. COORDINATE WITH OWNER ANY DISRUPTION IN SERVICES REQUIRED TO PERFORM WORK OR TO MODIFY EXISTING PIPING, DUCTWORK
OR ANY ASSOCIATED EQUIPMENT.
4. REFER TO SHEETS A1.8 AND A1.9 FOR ELEVATIONS.
5. REFER TO SHEET A2.1 FOR ROOM FINISH AND DOOR SCHEDULES.
6. REFER TO SHEETS A2.1 AND I1.1 FOR MATERIAL DESIGNATIONS.
GENERAL NOTES - FLOOR PLAN
Larson & Darby Group
COPYRIGHT 2025
S H
E E T N
U M
B E R
P R
O
JE
C T N
U M
B E R
D A
T E
All drawn and written information appearing herein shall not be duplicated, disclosed, or otherwise used without the written consent of
IS
S U
E D
F O
R
D A
T E
-1
A .3
B E Y E R E
A R
LY
C H
IL
D
H O
O D
C E N
T E R T
O
IL
E T R
O O
M R
E N
O V
A T
IO
N S
R O
C K F O
R D
P U
B
LI
C S
C H
O O
L D
IS
T
T H
A V
E R O
C K
F O
R D
IL
-2
-2
FLOOR PLAN - CHILDREN'S TOILET ROOM 171
SCALE: 3/8" = 1'-0"
TOILET ROOM 171 - DEMOLITION
1 SCALE: 3/8" = 1'-0"
TOILET ROOM 171 - RENOVATION
2 SCALE: 3/8" = 1'-0"
REFLECTED CEILING PLAN 171 - DEMOLITION
3 SCALE: 3/8" = 1'-0"
REFLECTED CEILING PLAN 171 - RENOVATION
LEGEND - KEYNOTE
KEY VALUE KEYNOTE TEXT
D01 REMOVE CONCRETE FLOOR AS REQUIRED FOR NEW PLUMBING. COORDINATE CONCRETE REMOVAL WITH
PLUMBING DRAWINGS.
D01.1 REMOVE EXISTING FLOOR FINISHES DOWN TO CLEAN AND BARE SUBSTRATE. PREPARE FLOOR TO RECEIVE NEW
FINISHES.
D02 REMOVE EXISTING CEILING SYSTEM INCLUDING ALL LIGHTS, HANGARS, HVAC COMPONENTS, ELECTRICAL FIXTURES, AND ANY OTHER MISCELLANEOUS ACCESSORIES. COORDINATE EXTENT OF DEMO WITH MECHANICAL AND ELECTRICAL DRAWINGS. REMOVE MISCELLANEOUS SUSPENDED EQUIPMENT AND COMPONENTS AS
REQUIRED FOR NEW CONSTRUCTION. PREPARE AREA FOR NEW CEILING OR FINISH
D03 REMOVE EXISTING WALL OR PORTION OF EXISTING WALL AS INDICATED. REMOVE ALL ASSOCIATED FINISHES (WALL TILE, ETC.), MECHANICAL, ELECTRICAL, AND PLUMBING COMPONENTS ON/IN/ OR ASSOCIATED WITH WALL TO BE REMOVED. PATCH AND REPAIR AS NECESSARY TO PREPARE AREA TO RECEIVE NEW CONSTRUCTION
D05 COORDINATE THE REMOVAL AND ALTERATION OF MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION
WORK WITH MEP&FP DRAWINGS IN THIS SET.
D07 TOTAL ROOM DEMOLITION OF FIXTURES AND FINISHES DOWN TO USABLE SUBSTRATE. REMOVE EXISTING PLUMBING FIXTURES, LIGHT FIXTURES, FLOOR AND CEILING FINISHES, WALL BASE, AND TOILET PARTITIONS AND
ACCESSORIES IN THEIR ENTIRETY. PREPARE SPACE FOR NEW CONSTRUCTION.
R02 WRAP EXPOSED PLUMBING PIPES, DRAINS AND WATER SUPPLY LINES UNDER SINKS TO PROTECT AGAINST BURNS, CUTS AND ABRASIONS.
R04 NEW STORAGE CABINET. REFER TO DETAILS 1 AND 2 ON A1.10 FOR ELEVATION AND SECTION DETAIL. WIDTH AND
DEPTH MAY VARY, REFER TO FLOOR PLANS FOR STORAGE CABINET SIZE.
R05 BABY CHANGING COUNTERTOP MEASURING 41" WIDE x 27" DEEP x 30" HIGH - ABOVE FINISHED FLOOR. INCLUDE BACK SPLASH AND SIDE SPLASH AS REQUIRED. COUNTERTOP TO BE SUPPORTED BY (3) IRON SUPPORTS' 20"H x 12"V HD FRONT MOUNT COUNTERTOP L BRACKET. ONE NEAR EACH END AND ONE IN THE CENTER TO ENSURE EVEN WEIGHT DISTRIBUTION. BRACKETS SHOULD BE SPACED 16-24 INCHES APART. WHENEVER POSSIBLE ALIGN
EACH BRACKET WITH WALL STUDS FOR MAXIMUM SUPPORT. MODEL NUMBER 0647213497441.
SCHEDULE - TOILET ACCESSORIES
ACCESSORY NUMBER DESCRIPTION MANUFACTURER MODEL COMMENTS
1 SOAP DISPENSER BRADLEY 6A00-11 FURNISHED BY OWNER, INSTALLED BY GC
1B SOAP DISPENSER BRADLEY 6A00-11 FURNISHED BY OWNER, INSTALLED BY GC
5 24"x36" MIRROR BOBRICK B-290 2436
5B 24"x36" MIRROR BOBRICK B-290 2436
7B 42" GRAB BAR BRADLEY 8122-001420
8B 36" GRAB BAR BRADLEY 8122-001360
9B 18" GRAB BAR BRADLEY 8122-001180
10 TOILET PAPER DISPENSER BRADLEY 5234-52 FURNISHED BY OWNER, INSTALLED BY GC
10B TOILET PAPER DISPENSER BRADLEY 5234-52 FURNISHED BY OWNER, INSTALLED BY GC
15B PAPER TOWEL DISPENSER SEE SPECS SEE SPECS FURNISHED BY OWNER, INSTALLED BY GC
18 OVERHEAD BRACED TOILET PARTITION SEE SPECS SEE SPECS
18B OVERHEAD BRACED TOILET PARTITION SEE SPECS SEE SPECS
37 WASTE RECEPTACLE ASI 0826 FURNISHED BY OWNER, INSTALLED BY GC
38 WASTE DISPOSAL ASI 0815 FURNISHED BY OWNER, INSTALLED BY GC
NORTH
PROJECT
WOMEN
MEN
D03
D06D03.1
D03
D03
D01
D03.2 D06.1
D01
D07
D07
D04.2
D05
D03.2
D05
3'-8" 3'-4" 1'-10 1/2" 2'-9"
V .I.
F
'-7
D03
D01.1
D01.1
/4
V .I.
F
/8
V .I.
F
/8
V .I.
F
5'-0" V.I.F
V .I.
F
WOMEN
MEN
2'-0" 1'-8" 10'-10"
3'-6" 1'-8" 8'-7" 2'-0" 7'-0"
'-6
'-6
'-8
G A
-1
-A
140-A
G3A-1 7 /A1.10
R02
R02
R06
1'-6" 5'-6"
A
.1
G B
-1 18
37B
'-1
'-7
R04
R04
'-2
'-4
'-4
V .I.
F
'-4
/4
V.I.F
26'-0"
WOMEN 141 SIDE TO BE GLAZED
BLOCK TO MATCH EXISTING; CORRIDOR
SIDE TO BE BRICK TO MATCH EXISTING
5 5 10
6" CIRCULAR COUNTER TOP
WASTE CHUTE WITH RECEPTICAL
DIRECTLY UNDERNEATH
1'-10"
ACP1
8'-0"
ACP1
8'-0"
STORAGE
CABINET BELOW
MEN
WOMEN
D02.1
D02 D02
EXISTING HARD CEILING
GYPSUM OR PLASTER CEILING
EXISTING HARD CEILING
GYPSUM CEILING
1. BEFORE BEGINNING WORK AT THE SITE AND THROUGHOUT THE COURSE OF WORK, INSPECT AND VERIFY THE LOCATION AND CONDITION OF EVERY ITEM AFFECTED BY THE WORK UNDER THIS CONTRACT AND REPORT DISCREPANCIES TO THE ARCHITECT BEFORE BEGINNING WORK
RELATED TO THAT BEING INSPECTED.
2. BEFORE BEGINNING WORK AT THE SITE, INSPECT THE EXISTING BUILDING AND DETERMINE THE EXTENT OF EXISTING FINISHES, SPECIALTIES, EQUIPMENT, AND OTHER ITEMS WHICH MUST BE REMOVED AND REINSTALLED IN ORDER TO PERFORM THE WORK UNDER THIS CONTRACT.
3. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPLE AREAS WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT. INCIDENTAL WORK MAY ALSO BE NECESSARY IN AREAS NOT SHOWN ON THE ARCHITECTURAL DRAWINGS DUE TO CHANGES AFFECTING EXISTING MECHANICAL, ELECTRICAL, PLUMBING, AND OTHER SYSTEMS. SUCH INCIDENTAL WORK IS ALSO PART OF THIS CONTRACT. INSPECT THOSE AREAS AND ASCERTAIN WORK NEEDED AND DO THAT WORK IN ACCORDANCE WITH THE CONTRACT REQUIREMENTS AT NO ADDITIONAL
COST.
4. PROTECT EXISTING FINISHES TO REMAIN FROM DAMAGE.
5. REPAIR, PATCH, OR REFINISH AS APPLICABLE TO MATCH ADJACENT EXISTING FINISHES, THOSE FINISHES DAMAGED OR NEWLY EXPOSED
DURING PERFORMANCE OF THE WORK UNDER THIS CONTRACT.
6. WHERE MATCH EXISTING IS INDICATED, NEW CONSTRUCTION OR FINISHES, SHALL MATCH THE EXISTING IN EVERY PARTICULAR.
7. WHERE PERMANENT REMOVAL OF EXISTING CASEWORK, DOORS AND FRAMES, EQUIPMENT, OR FURNISHINGS IS REQUIRED AND PREVIOUSLY CONCEALED SURFACES ARE TO REMAIN EXPOSED, PATCH PREVIOUSLY CONCEALED SURFACES TO MATCH ADJACENT EXPOSED SURFACES.
WHERE SUCH SURFACES ARE SCHEDULED TO RECEIVE NEW FINISHES, PREPARE THE SURFACES TO RECEIVE THE NEW FINISHES.
8. WHERE CUTTING OF EXISTING SURFACES OR REMOVAL OF EXISTING SURFACES IS REQUIRED TO PERFORM THE WORK UNDER THIS CONTRACT, AND NEW FINISH IS NOT INDICATED, FILL RESULTING OPENINGS AND PATCH THE SURFACE AFTER DOING THE WORK AND FINISH
TO MATCH ADJACENT EXISTING SURFACES.
9. REFER TO NEW WORK PLANS TO COORDINATE EXTENT OF DEMOLITION REQUIRED.
10. REFER TO MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS FOR ADDITIONAL DEMOLITION REQUIRED. CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY UPON DISCOVERY OF CONFLICT OR DISCREPANCY WITH ITEMS INDICATED TO BE REMOVED.
11. WHERE NOT SPECIFICALLY NOTED, CONTRACTOR SHALL MODIFY EXISTING FLOORING AND CEILING CONSTRUCTION TO REMAIN AS
REQUIRED TO ABUT NEW CONSTRUCTION AND MATCH ADJACENT EXISTING CONDITIONS.
12. COORDINATE SLAB REMOVAL AND REPLACEMENT WITH PLUMBING AND ELECTRICAL UNDERGROUND AND IN-SLAB WORK.
13. WHERE AN ITEM IS SHOWN TO BE REMOVED OR DEMO'ED ALL MECHANICAL, ELECTRICAL, AND PLUMBING COMPONENTS SHALL BE REMOVED WITH IT U.N.O. PIPING SHALL BE REMOVED TO WITHIN NEAREST WALL TO REMAIN AND CAPPED. ELECTRICAL WIRING AND CONDUIT SHALL BE REMOVED BACK TO NEAREST JUNCTION BOX TO REMAIN. DUCTS AND TERMINALS SHOULD BE REMOVED AS FAR AS NECESSARY FOR NEW
DISTRIBUTION SYSTEM OR COMPONENTS TO TIE INTO, OR CAP WITHIN CONCEALED SPACE.
GENERAL NOTES - DEMOLITION
1. COORDINATE LIGHTING LAYOUT WITH ELECTRICAL DRAWINGS AND
SPECIFICATIONS.
2. COORDINATE DIFFUSERS, GRILLES, AND DUCTWORK WITH MECHANICAL
DRAWINGS AND SPECIFICATIONS.
3. CEILING HEIGHT SHOWN ON REFLECTED CEILING PLANS ARE AN
APPROXIMATION. NEW CEILING SHOULD BE INSTALLED AT THE SAME
ELEVATION AS THE PREVIOUS CEILING.
GENERAL NOTES - REFLECTED CEILING
2' X 2' LAY-IN ACOUSTICAL
CEILING PANEL SYSTEM
LEGEND - REFLECTED CEILING
EXISTING 2' X 2' LAY-IN ACOUSTICAL
CEILING PANEL SYSTEM
2'x4' RECESSED TROFFER
LIGHT FIXTURE
RECESSED WALL WASHER
RECESSED LIGHT FIXTURE
SUPPLY AIR DIFFUSER
EXHAUST AIR REGISTER
RETURN AIR REGISTER / TRANSFER GRILLE
EXISTING 1'x4' SURFACE
MOUNTED LIGHT FIXTURE
EXISTING 12" DIA. SURFACE MOUNTED
DECORATIVE LIGHT FIXTURE
2'x2' RECESSED TROFFER
LIGHT FIXTURE
1. DIMENSIONS ON FLOOR PLAN ARE BASED ON FACE OF FINISHED WALL TO FACE OF FINISHED WALL (NOMINAL).
2. VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE. PORTIONS OF EXISTING CONSTRUCTION MAY HAVE BEEN
REMOVED BY OWNER.
3. MAINTAIN CONTINUOUS UTILITY SERVICE TO ALL SPACES IN THE BUILDING NOT AFFECTED BY THIS WORK. COORDINATE WITH OWNER ANY DISRUPTION IN SERVICES REQUIRED TO PERFORM WORK OR TO MODIFY EXISTING PIPING, DUCTWORK
OR ANY ASSOCIATED EQUIPMENT.
4. REFER TO SHEETS A1.8 AND A1.9 FOR ELEVATIONS.
5. REFER TO SHEET A2.1 FOR ROOM FINISH AND DOOR SCHEDULES.
6. REFER TO SHEETS A2.1 AND I1.1 FOR MATERIAL DESIGNATIONS.
GENERAL NOTES - FLOOR PLAN
Larson & Darby Group
COPYRIGHT 2025
S H
E E T N
U M
B E R
P R
O
JE
C T N
U M
B E R
D A
T E
All drawn and written information appearing herein shall not be duplicated, disclosed, or otherwise used without the written consent of
IS
S U
E D
F O
R
D A
T E
-1
A .4
B E Y E R E
A R
LY
C H
IL
D
H O
O D
C E N
T E R T
O
IL
E T R
O O
M R
E N
O V
A T
IO
N S
R O
C K F O
R D
P U
B
LI
C S
C H
O O
L D
IS
T
T H
A V
E R O
C K
F O
R D
IL
-2
-2
FLOOR PLAN - STAFF TOILET ROOM 140 & 141NORTH
PROJECT
NORTH
TRUE
SCALE: 3/8" = 1'-0"
TOILET ROOM 140 & 141 - DEMOLITION
1 SCALE: 3/8" = 1'-0"
TOILET ROOM 140 & 141 - RENOVATION
SCALE: 3/8" = 1'-0"
REFELECTED CEILING PLAN 140 & 141 - RENOVATION
4SCALE: 3/8" = 1'-0"
REFELECTED CEILING PLAN 140 & 141 - DEMOLITION
LEGEND - KEYNOTE
KEY VALUE KEYNOTE TEXT
D01 REMOVE CONCRETE FLOOR AS REQUIRED FOR NEW PLUMBING. COORDINATE CONCRETE REMOVAL
WITH PLUMBING DRAWINGS.
D01.1 REMOVE EXISTING FLOOR FINISHES DOWN TO CLEAN AND BARE SUBSTRATE. PREPARE FLOOR TO
RECEIVE NEW FINISHES.
D02 REMOVE EXISTING CEILING SYSTEM INCLUDING ALL LIGHTS, HANGARS, HVAC COMPONENTS, ELECTRICAL FIXTURES, AND ANY OTHER MISCELLANEOUS ACCESSORIES. COORDINATE EXTENT OF DEMO WITH
MECHANICAL AND ELECTRICAL DRAWINGS. REMOVE MISCELLANEOUS SUSPENDED EQUIPMENT AND
COMPONENTS AS REQUIRED FOR NEW CONSTRUCTION. PREPARE AREA FOR NEW CEILING OR FINISH
D02.1 REMOVE EXISTING GYPSUM BOARD SOFFIT ASSEMBLY IN ITS ENTIRETY AS INDICATED.
D03 REMOVE EXISTING WALL OR PORTION OF EXISTING WALL AS INDICATED. REMOVE ALL ASSOCIATED FINISHES (WALL TILE, ETC.), MECHANICAL, ELECTRICAL, AND PLUMBING COMPONENTS ON/IN/ OR ASSOCIATED WITH WALL TO BE REMOVED. PATCH AND REPAIR AS NECESSARY TO PREPARE AREA TO
RECEIVE NEW CONSTRUCTION
D03.1 SAW CUT OPENING IN EXISTING GLAZED BLOCK AND BRICK VENEER WALL. REMOVE AND SALVAGE PORTIONS OF SAWCUT WALL FOR REINSTALLATION AS INDICATED IN ADJACENT DOOR OPENING. IF OPENING IS FOR DOOR, COORDINATE OPENING SIZE WITH DOOR SCHEDULE. FOR DUCT COORDINATE
SIZE AND LOCATION WITH MECHANICAL DRAWINGS.
D03.2 REMOVE ALL WALL FIXTURES AND ACCESSORIES AND PREPARE WALLS TO RECEIVE NEW FINISHES.
COORDINATE WITH FINISH SCHEDULE.
D04.2 DISCARD EXISTING STEEL LOCKERS.
D05 COORDINATE THE REMOVAL AND ALTERATION OF MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION WORK WITH MEP&FP DRAWINGS IN THIS SET.
D06 REMOVE EXISTING DOOR, FRAME, AND…