2E Revised Bid Drawings Walkway 200930 1.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24424R0015
About this file
This document is a set of drawings and technical specifications related to the renovation of Building 1, Second Floor, Area 2E at the University Drive Pittsburgh VAMC campus. The project, titled "Renovate Bldg. 1, Second Floor, 2E at UD", involves constructing an enclosed rooftop walkway, replacing flooring and finishes in several exam rooms and support spaces, and making related architectural, mechanical, electrical, and fire protection upgrades.
The solicitation for this construction project, Solicitation Number 36C24424R0015, will be issued as a Request for Proposal (RFP) set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB). The North American Industry Classification System (NAICS) code is 236220 Commercial & Institutional Building & Construction, with a magnitude of construction over $10 million. A pre-bid site visit is scheduled for April 29, 2024. The period of performance is 730 calendar days from the Notice to Proceed.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
4039 423834 35 37
F
G
F.1
EXISTING
STAIRS #3
ETR
EXAM 1
2E107
EXAM 2
2E108
EXAM 3
2E109
EXAM 4
2E110
EXAM 5
2E111
EXAM 6
2E112
EXAM 7
2E113
OTBC STORAGE
2E114
OTBC
TREATMENT
AREA (EDEMA)
2E115
CORRIDOR
2E143
AREA OF WORK
1 2 1 2
EXISTING ROOF
DRAIN TYPICAL
REMOVE EXISTING ROOF
& PREPARE FOR NEW ROOF
COORIDOR PER 1/AI802
5 4
A
A
5 4
STOR
2E106
STOR
2E116C
TAKE MEASURES TO PROTECT EXISTING WINDOWS
DURING CONSTRUCTION - TYPICAL
EXISTING ITEMS TO REMAIN
DASHED LINES INDICATE
ITEMS TO BE REMOVED
DEMOLISH LIGHT
FIXTURES, ACOUSTICAL
CEILING TILE AND GIRD
DEMOLISH GYPSUM
CEILING
DEMOLITION LEGEND
TEMPORARY PARTITION 1-HOUR
SLAB-TO-SLAB BARRIERS
EXTENTS OF ANTE
ROOM
4039 423834 35 35.1 37
F
G
F.1
A.F.F.8' - 1"
AREA OF WORK
CORRIDOR
2E129
CORRIDOR
2E143
EXAM 1
2E107
EXAM 2
2E108
EXAM 3
2E109
EXAM 4
2E110
EXAM 5
2E111
EXAM 6
2E112
EXAM 7
2E113
OTBC
TREATMENT
AREA (EDEMA)
2E115
CORRIDOR
2E143
Engineers Architects
N
AREA OF WORK
2 EAST OUTLINE
KEY PLAN
# SHEET KEY NOTES:
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
SHEET NOTES:
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:2 P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
Checker Author
2ND FLOOR DEMOLITION PLAN FOR ENCLOSED
ROOF TOP WALKWAY - EAST
AD802
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
2 7
1/4" = 1'-0"1
2ND FLOOR DEMOLITION PLAN WITH ENCLOSED ROOF TOP WALKWAY - EAST
DEMOLISH EXISTING EXTERIOR
WALL. PREP FOR NEW DOOR AND
FRAME.
DEMOLISH WINDOW & FRAME
EXISTING LINTEL TO REMAIN.
DEMOLISH EXISTING ROOF DRAIN
DEMOLISH DOOR AND FRAME4
DEMOLISH WALL5
WALK OFF MAT6
1/4" = 1'-0"2
2ND FLOOR DEMOLITION REFLECTED CEILING PLAN WITH ENCLOSED ROOF WALKWAY
A. GENERAL CONTRACTOR TO MODIFY
EXISTING ROOF AS NEEDED TO DRAIN TO
NEW ROOF DRAIN LOCATIONS.
9/28/2020
DocuSign Envelope ID: 7C071EF8-284C-478E-BD63-133731E1F30A
40393834 35 37
F
F.1
EXP
PT1
RB
LIN-1
2E116
ENCLOSED
ROOF TOP
WALKWAY
AREA OF WORK
LIN-1 FIELD, TYP LIN-3 ACCENT, TYP
EXAM 4
2E110
EXAM 5
2E111
EXAM 6
2E112
EXAM 7
2E113
OTBC
TREATMENT
AREA (EDEMA)
2E115
OTBC STORAGE
2E114
EXAM 2
2E108
EXAM 3
2E109
CORRIDOR
2E143
EXAM 1
2E107
NEW
EXISTING
NEW
EXISTING
NEW
EXISTING
NEW
EXISTING
EXISTING ITEMS TO REMAIN
NEW WALL
NEW DOOR
NEW WORK LEGEND
LINOLEUM (LIN)
(STRIATO SERIES, WHITE
WASH, S230)
TRANSITION STRIP
(TS)
LIN-3 (TYPICAL)
FLOOR PATTERN LEGEND
LIN-1
(STRIATO SERIES, WHITE
WASH, S230)
TS-1
ALUMINUM
Engineers Architects
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
SHEET NOTES:
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:2 P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
KMN, KC KC, DGC
2ND FLOOR FLOORING PATTERN PLAN ROOF
WALKWAY- 2E EAST
AF802
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
7 7
1/4" = 1'-0"1
2ND FLOOR FLOORING PATTERN PLAN ROOF WALKWAY- 2E EAST
N
AREA OF WORK
2 EAST OUTLINE
KEY PLAN
A. ALIGN NEW LINOEUM PATTERN WITH AND
COUNTINUE EXISTING LINOLEUM PATTERN.
4039 423834 35 37
F
G
AI803
EXISTING
STAIRS #3
EXISTING ROOF
ETR
AI803
CLR
7' - 0"
HAND
RAIL
HAND RAIL
HAND RAIL
HAND RAIL
6" 10' - 9 1/2" 20' - 0" 20' - 0" 20' - 1 1/2" 20' - 0" 20' - 0"
FV
9' - 2"
120' - 6 1/2"
COORDINATE NUMBER AND
LOCATION OF (2) SIDEWALL
SPRINKLER HEAD WITH SHEET
FS-801. REPAIR OR REPLACE
DAMAGED BRICK VENEER
CAUSED BY THE
INSTALLATION
F V2 " F.1
2E116
ENCLOSED
ROOF TOP
WALKWAY
AI804
HSS 4" X 4" X 1/4"
HSS 4" X 4" X 1/4" HSS 4" X 4" X 1/4" HSS 4" X 4" X 1/4"
HSS 4" X 4" X 1/4"
HSS 4" X 4" X 1/4"HSS 4" X 4" X 1/4"
15' - 10 1/4" 20' - 0" 2' - 0 3/4" 18' - 0 1/2" 20' - 0" 4' - 11 1/2" 15' - 0 1/2"
FV
1' - 5 1/2" 17' - 4"
6' - 4 1/4" 10' - 0 1/4" 10' - 0 1/4" 9' - 9" 10' - 0 1/4" 10' - 2 1/2" 10' - 0 1/4" 9' - 11 3/4" 10' - 0 1/4" 10' - 0" 10' - 0 1/4" 9' - 11 3/4" 4' - 2 1/4"
NEW ROOF DRAIN
SEE DETAIL AT 7/AI803
1/2" EXPANSION
JOINT AND SEALANT W/
BACKER ROD
AI804
AI803
1/2" EXPANSIONS JOINT AND SEALANT
WITH BACKER ROD
NEW ROOF DRAIN
SEE DETAIL AT 7/AI803
NEW ROOF DRAIN
SEE DETAIL AT 7/AI803
E
E
AREA OF WORK
W1 W1 W1 W1 W1 W1 W1 W1 W1 W1 W1 W1
WINDOWS TO REMAIN U.O.N.
TYPICAL. TAKE MEAUSRES TO
PROTECT EXISTING WINDOWS
DURING CONSTRUCTION
AI803
TYP.
AI803
FV
6 1/4"
EXAM 1
2E107
EXAM 2
2E108
EXAM 3
2E109
EXAM 4
2E110
EXAM 5
2E111
EXAM 6
2E112
EXAM 7
2E113
OTBC STORAGE
2E114
OTBC
TREATMENT
AREA (EDEMA)
2E115
FV
2' - 2"
2E116C
CORRIDOR2E106
CORRIDOR
CLR
7' - 0"
EXISTING MEMBRANE ROOFING SYSTEM TO
REMAIN. SEE SHEET NOTE A ON AD801.
CONTRACTOR TO MODIFY EXITING ROOFING AS
REQUIRED TO PROVIDE PROPER WATER
DRAINAGE TO NEW ROOF DRAINS.
4039 423834 35 37
F
G
AI803
AI803
F.1
STANDING SEAM
METAL ROOF
-1
S
L O
P E
-1
S
L O
P E
AREA OF WORKEXISTING ROOF
BELOW
AI804
SIM
AI803
SIM
AI803
AI803
SIM.
EXAM 1
2E107
EXAM 2
2E108
EXAM 3
2E109
EXAM 4
2E110
EXAM 5
2E111
EXAM 6
2E112
EXAM 7
2E113
OTBC STORAGE
2E114
OTBC
TREATMENT
AREA (EDEMA)
2E115
EXISTING ROOF
BELOW
EXISTING
STAIRS #3
EXISTING MEMBRANE ROOFING SYSTEM TO REMAIN. SEE SHEET NOTE A ON
AD802. CONTRACTOR TO MODIFY EXITING ROOFING AS REQUIRED TO PROVIDE
PROPER WATER DRAINAGE TO NEW ROOF DRAINS.
EXISTING ITEMS TO REMAIN
NEW WALL
NEW DOOR
NEW WORK LEGEND
Engineers Architects
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:3 P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
KMN, KC KC, DGC
2ND FLOOR RENOVATION PLAN FOR
ENCLOSED ROOF TOP WALKWAY - EAST
AI802
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
3 7
1/4" = 1'-0"1
2ND FLOOR RENOVATION PLAN WITH ENCLOSED ROOF TOP WALKWAY - EAST
1/4" = 1'-0"2
2ND FLOOR RENOVATION PLAN WITH ENCLOSED ROOF TOP WALKWAY - ROOF PLAN
N
AREA OF WORK
2 EAST OUTLINE
KEY PLAN
CONTINOUS STRUCTURAL STEEL STUD
PURLINS @ 16" O.C. HORIZONTAL, TYP.
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP (1
PER PANEL, PER SUPPORT)
- SET CLIP IN BUTYL SEALANT
1/4"-14 HEX HEAD FASTNERS WITHOUT
WASHER
CONTINOUS BUTYL SEALANT
BASE ANGLE W/ MIN. 3" VERTICAL LEG
FRO PANEL ATTACHEMENT
FASTEN TO EXISTING 4" PRECAST SLAB
PANELS
SEALANT MARRIAGE
BEAD TO VERTICAL
PANEL JOINT
TURN UP NEW
ROOF MEMBRANE
CONTINUOUS BUTYL
SEALANT BELOW BASE
FLASHING
METAL STUD
5/8" GYPSUM BOARD
BATT INSULATION
M
IN
BASE AS SCHEDULED
EXISTING MEMBRANE ROOFING
SYSTEM TO REMAIN. SEE SHEET
NOTE A ON AD801.
CONTRACTOR TO MODIFY
EXITING ROOFING AS REQUIRED
TO PROVIDE PROPER WATER
DRAINAGE TO NEW ROOF
DRAINS.
3 1/4" 1 3/4" 3 3/4" 3/4"
CONTINOUS PURLIN @ 16" O.C.
HORIZONTAL, TYP.
- SEE STRUCTURAL DRAWINGS
MALE JOINT FEMALE
JOINT
1/4" - 14 HEX HEAD
FASTNERS WITHOUT
WASHER
12 GA STAINLESS STEEL
HIDDEN FASTENER CLIP (1
PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
PANEL MODULE
CONTINOUS BUTYL
SEALANT
CONTINOUS BUTYL
SEALANT
0"
16 GA. PAINTED SADDLE CLIP
CONTINOUS BUTYL SEALANT AT
PANEL JOINT
1/4" - 14 THROUGH FASTENERS
WITH WASHER
1 1/2 DEPTH STRUCTURAL STEEL
DECKING SYSTEM TYP.
STRUCTURAL STEEL STUD
RAFTER FRAME BEYOND
1/4" - 14 THROUGH FASTENER
WITH WASHER
16 GA. PAINTED SADDLE CLIP
INSIDE FOAM
CLOSURE
1/4" - 14 X 7/8" LOW
PROFILE TEK
SCREWS
CONTINUOUS BUTYL
TAPE
CONTINUOUS FOAM
IN PLACE SEALANT W/
BACKER
DECK BEARING
- SEE STRUCT DWG'S
LOW EAVE TRIM
SEALANT MARRIAGE
BEAD TO PANEL
JOINT
POP RIVET, TYP.
SEALANT MARRIAGE
BEAD TO PANEL
JOINT
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
CONTINUOUS BUTYL
SEALANT
INSIDE EAVE TRIM
(SET IN CONTINUOUS
BUTYL SEALANT)
CONTINUOUS BUTYL
SEALANT
STRUCTURAL STEEL
ATTACHMENT CLIP
CONTINUOUS STRUCTURAL
STEEL STUD PURLINS @ 16" O.C.
HORIZONTAL, TYP
14 GA. GALVANIZED HIDDEN CLIP (1 PER
PANEL, PER GIRT)
1/4" - 14 HEX HEAD FASTENERS
CONTINUOUS BUTYL SEALANT
AT PANEL JOINT
STRUCTURAL STEEL STUD WALL FRAME
SYSTEM
5/8" GYPSUM BOARD
BATT INSULATION
5"
1/2"
2ND FLOOR
(1193'-1 3/8")
29' - 6 3/4"
3RD FLOOR
(1204'-10 3/4")
41' - 4 1/8"
FG
STANDING SEAM METAL
ROOF ON EXTERIOR
SHEATHING ON 4" RIGID
INSULATION ON METAL
DECKING ON 6"
STRUCTURAL BEAM
3" INSULATED MTL.
PANEL ON 4"
FURRING MTL. STUD
FRAMING ON 5/8"
GYPSUM WALL
BOARD (BEYOND)
CONCRETE STOOL
WITH WATER
PROOFING ON THE
EXTERIOR ROOF SIDE
SOLID WALK SURFACE
SEE SHEET AF802 FOR
FLOOR FINISH AND
PATTERN
WELD 4" X 4"
STRUCTURAL TUBE
COLUMNS TO EXISTING
STRUCTURAL FRAMING
BELOW. PROVIDE
WATER PROOFING AT
PENETRATIONS
6'-0" (W) X 5'-0" (T)
ALUMINUM WINDOW
SYSTEM
HSS 8" X 3" X 1/4"
HSS 8" X 3"
X 1/4"
EXIST'G WALL BEYOND
Z-CHANNEL
1 1/2" DIA METAL
HANDRAIL W/ 5/8" DIA
HANDRAIL SUPPORT
F.1
1 1/2" DIA METAL
HANDRAIL W/ 5/8"
DIA HANDRAIL
SUPPORT
PATIENT LIFT
2E116
ENCLOSED
ROOF TOP
WALKWAY
AI803
AI803
HSS 6" X 2" X 1/4"
@ 5' - 0" O.C.
HSS 8" X 6" X 1/4"
AI803
AI803
ADAPTER
FRAME
EXISTING LOBBY
ROOF STRUCTURE
TO REMAIN
AI803
BASE AS
SCHEDULE
BASE AS
SCHEDULE
6' - 0 3/4"
F.V.
2"
CLEAN EXTERIOR
BRICK WHERE
CAPTURED INSIDE
NEW CORRIDOR.
CLEAN EXTERIOR
BRICK WHERE
CAPTURED INSIDE
NEW CORRIDOR.
ENCLOSURE FINISH FLOOR
SHALL ALIGN WITH FINISH
FLOOR OF 2E FINISH FLOOR
SPACE. BRING THE EXISTING
4" PRECAST SLAB PANELS
FINISH LEVEL UP OR DOWN
BASED ON FIELD CONDITIONS.
REPAIR AND LEVEL EXISTING
CONCRETE AS NEEDED TO
RECEIVE FINISH FLOOR.
W10x12
EXISTING MEMBRANE
ROOFING SYSTEM TO
REMAIN. SEE SHEET NOTE A
ON AD802. CONTRACTOR TO
MODIFY EXITING ROOFING
AS REQUIRED TO PROVIDE
PROPER WATER DRAINAGE
TO NEW ROOF DRAINS.
INSTALL METAL FLASHING
AT WINDOW HEAD
SPRINKLER - SEE FIRE
PROTECTION DWGS
RADIANT PANEL - SEE
MECH DWGS
ELEC FIXTURE - SEE
ELEC DWGS
MECH DUCT -
SEE MECH
DWGS
AI804
2ND FLOOR
(1193'-1 3/8")
29' - 6 3/4"
40 39 34
EXIST'G WALL
SLOPED
STANDING
SEAM METAL
ROOF
INSULATED
METAL
PANELS
EXIST. WALL
TO REMAIN
5' TALL BY 6'
WIDE FIXED
ALUMINUM
WINDOW
AI803
AI804
AI804
T Y
P
METAL END
CAP TRIM
W1 W1 W1 W1 W1 W1
SILL FLASHING
TYPICAL
METAL
FLASHING
G
TURN UP ROOF
MEMBRANE AT
PARAPET
EXISTING COPING
TO REMAIN
EXISTING 4" PRECAST
SLAB PANELS ROOF
DECK TO REMAIN
EXISTING BRICK
VENEER WALL TO
REMAIN
RAGGLE, LEAD WEDGE
AND SEALENT
TERMINATION BAR
FASTENED 6" O.C.
RECEIVER AND COUNTER
FLASHING. SCREW COUNTER
FLASHING TO RECEIVER WITH
GASKETED SCREW
HOT-AIR WELD
M
IN
EXISTING MEMBRANE ROOFING SYSTEM
TO REMAIN. SEE SHEET NOTE A ON
AD801. CONTRACTOR TO MODIFY
EXITING ROOFING AS REQUIRED TO
PROVIDE PROPER WATER DRAINAGE TO
NEW ROOF DRAINS.
V
IF
CAULKING & BACKER
ROD - BOTH SIDES
ALUMINIUM WINDOW
SEALANT ON
BOTH SIDES
PREFIN. INSUL.
METAL WALL
PANEL
WINDOW. SHIM
METAL FLASHING
PER MANUFACTURE
RECOMMENDATION
SEALANT ON
BOTH SIDES
METAL FLASHING PER
MANUFACTURE
RECOMMENDATION
PREFIN. INSUL.
METAL WALL
PANEL
CAULKING & BACKER
ROD - BOTH SIDES
FLASHING AT EDGE TRIM
PER MANUFACTURE
RECOMMENDATION
Engineers Architects
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
/3
/2
:0
:1 P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
KC DGC
ROOF WALKWAY DETAILS
AI803
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
5 7
3" = 1'-0"5
WALL PANEL BASE & JOINT CONDTION
3" = 1'-0"7
VERTICAL WALL PANEL PLAN VIEW
3" = 1'-0"6
INTERMEDIATE ROOF PANEL SUPPORT
3" = 1'-0"4
WALL PANEL @ ROOF PANEL LOW EAV DETAIL
3/4" = 1'-0"2
SECTION
1/4" = 1'-0"1
ENCLOSED WALK WAY ELEVATION
3" = 1'-0"3
EXISTING PARAPET DETAIL
1 1/2" = 1'-0"8
ALUMINUM WINDOW HEAD
1 1/2" = 1'-0"10
ALUMINUM WINDOW SILL
1 1/2" = 1'-0"9
AMUMINUM WINDOW JAMB
DOOR LEGEND
RAGGLE, LEAD
WEDGE AND
SEALENT
TERMINATION BAR
FASTENED 6" O.C.
RECEIVER AND
COUNTER FLASHING.
SCREW COUNTER
FLASHING TO
RECEIVER WITH
GASKETED SCREW
TERMINATION BAR
FASTENED 6" O.C.
SINGLE PLY BASE
FLASHING (ADHERED)
FOAM ROD
HOT-AIR WELD
SINGLE PLY MEMBRANE
(ADHERED)
COVER BOARD
INSULATION
M
IN
GYPSUM BOARD
EXISTING EXTERIOR
WALL TO REMAIN
F.1
1 1/2" 1 1/2"
1 1/2"
TYP.
EXISTING BUILDING
MASONRY WALL TO REMAIN
HAND RAIL
STRUCTURAL COLUMN
NOTE:
REPLACE EXISTING BRICK VENEER THAT AS
REQUIRED WHEN INSTALLING HANDRAIL.
MIN.
4"
F.I.P. INSULATION
AS REQUIRED
OUTSIDE CORNER
TRIM
POP RIVETS
EXPANISION
FASTENER
3/4" PHIL PANHEAD
INSIDER CORNER
TRIM
CONTINOUS
BUTYL SEALANT
CONTINOUS BUTYL
SEALANT
ATTACHMENT CLIP
STRUCTURAL STEEL STUD
WALL FRAME SYSTEM
CONTINOUS PURLINS
BEYOND
FIELD CUT
.0
FIELD CONDITIONWILL VARY WITH
FIELD CONDITION
WILL VARY WITH
DRAIN STRAINER
CLAMPING RING
EXISTING ROOF PRECAST SLAB
PANELS TO REMAIN
NOTE: PATCH AND REPAIR
EXISTING ROOF DRAIN HOLE TO
MATCH ROOF CONSTRUCTION
AND MEMBRANE. FOR NEW ROOF
DRAIN LOCATION - SEE PLUMBING
SHEET PP801
CONNECT TO
EXISTING ROOF
DRAIN
CORE DRILL HOLE
IN EXISTING ROOF
FOR NEW DRAIN
9. FRAME FINISH:
WTF = WOOD TRANSPARENT FINISH
WOF = WOOD OPAQUE FINISH
MGP = METAL GALVANIZED PAINTED
MP = METAL, PAINTED
AL = ANODIZED ALUMINUM
HMLL = HOLLOW METAL, LEAD LINED
10. FRAME DETAILS:
SEE FRAME DETAILS ON SHEET AE606
11. UL RATING:
20 M ; 45 M ; 1 H ; 1.5 H ; 2 H ; 3 H
12. HARDWARE SET:
SEE HARDWARE SETS SCHEDULE IN
SPECIFICATION 08 71 00.
3. DOOR SIZE:
SEE SCHEDULE FOR WIDTH, HEIGHT AND THICKNESS
4. DOOR MATERIAL:
SCV = SOLID CORE W/ WOOD VENEER FACES
SCH = SOLID CORE W/ HARDBOARD FACES
SCP = SOLID CORE PLASTIC LAMINATE FACES
SCA = SOLID CORE ACROVYN FACES
HM = HOLLOW METAL
GHM = GALVANIZED HOLLOW METAL
AL = ALUMINUM & GLASS
LL = LEAD LINED
5. DOOR FINISH:
WTF = WOOD TRANSPARENT FINISH
WOF = WOOD OPAQUE FINISH
MGP = METAL GALVANIZED PAINTED
MP = METAL PAINTED
AL = ANODIZED ALUMINUM
PL = PLASTIC LAMINATE
1. NUMBER: SEE FLOOR PLAN FOR DOOR NUMBER
2. DOOR ELEVATION: SEE TYPES BELOW
TYPE E
SEE SHEDULE
SEE SHEDULE
6. GLASS TYPE:
WG = 1/4" WIRE GLASS
CTG = 1/4" CLEAR TEMPERED GLASS
LG = 1/4" LEADED GLASS
FRG = 1/4" FIRE RATED GLASS
7. FRAME ELEVATION:
SEE HOLLOW METAL ELEVATION LEGEND
8. FRAME MATERIAL:
WD = WOOD
HM = HOLLOW METAL
GHM = GALVANIZED HOLLOW METAL
AL = ALUMINUM
KD = HOLLOW METAL KNOCK DOWN FRAME
HMLL = HOLLOW METAL, LEAD LINED
ALUMINUM FRAME
F6
S E
E S
C H
E D
U L E
2" SEE SCHEDULE 2"
9" VARIES 9"
9" 2'
-9
3' -6
SEE SCHEDULE
8"
2"
TEMPERED GLASS
TEMPERED
GLASS
KICK PLATE
W1
FIN. FLR.
AI803
TYP.
AI803
TYP.
EXTERIOR WINDOW ELEVATION
6' - 0"
TEMPERED GLASS
AI803
TYP.
WINDOW SCHEDULE
WINDOW TYPE WIDTH HEIGHT SILL HEIGHT HEAD HEIGHT
W1 6'-0" 5'-0" 4'-0" 9'-0"
DETAIL
JAMBHEAD SILL
9/AI8038/AI803 10/AI803
F.1
SIDE WALL TRIM
RAGGLE, LEAD WEDGE
AND SEALENT
TERMINATION BAR
FASTENED 6" O.C.
RECEIVER AND COUNTER
FLASHING. SCREW COUNTER
FLASHING TO RECEIVER
WITH GASKETED SCREW
HOT-AIR WELD
M
IN
EXISTING BRICK VENEER
WALL TO REMAIN
SLOPED STANDING
SEAM METAL ROOF
NEOPRENE CLOSER
MOISTURE BARRIER
Engineers Architects
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:3 P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
KMN, KC KC, DGC
ROOF, DOOR AND WINDOWS WALKWAY
DETAILS
AI804
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
6 7
3" = 1'-0"1
EXPANSION JOINT AND FLASHING DETAIL
3" = 1'-0"2
HANDRAL DETAIL AROUND COLUMN
3" = 1'-0"3
WALL PANEL OUTSIDE CORNER PLAN DETAIL
1 1/2" = 1'-0"4
ROOF DRAIN REPLACEMENT
DOOR SCHEDULE ROOF WALKWAY
MARK HEIGHT WIDTH DOOR TYPE
FRAME
MATERIAL FRAME TYPE FINISH FIRE RATING COMMENTS MARK
2E147 7' - 0" 3' - 8" E AL F6 AL - 2E147
2E148 7' - 0" 3' - 8" E AL F6 AL - 2E148
3" = 1'-0"6
ROOF DETAIL
J
LIGHTING FIXTURE SCHEDULE
A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE PART NUMBERS.
B. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.
C. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
D. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH THE LIGHT FIXTURE SHOP
DRAWINGS FOR A COMPLETE REVIEW.
GENERAL NOTES:
ELECTRICAL SYMBOL LEGEND
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
PG: PLUGMOLD
WP: WEATHERPROOF ENCLOSURE
S: SURFACE MOUNTED
SR: DUAL CHANNEL SURFACE MOUNTED RACEWAY
120V DUPLEX RECEPTACLE (EMERGENCY)
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE (EMERGENCY)
JUNCTION BOX, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH
SYMBOL
HEIGHT
AFF * DESCRIPTION
18"
18"
18"
18"
72" TOP
MAX
72" TOP
MAX
SWITCH MODIFIERS:
M: MOTOR-RATED
EQUIPMENT CONNECTIONE
120V FLOORBOX
48"
120V DUPLEX RECEPTACLE - CEILING MOUNTED
CLNG
PANELBOARD
T --- TRANSFORMER
HOMERUN---
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
18" SPECIAL RECEPTACLE
LIGHTING SYMBOL LEGEND
2' X 2' DIRECT/INDIRECT ARCHITECTURAL TROFFER -
RECESSED
2' X 4' DIRECT/INDIRECT ARCHITECTURAL TROFFER -
RECESSED
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' FLAT LENS TROFFER - RECESSED
6" DIAMETER DOWNLIGHT - RECESSED ---
EXIT SIGN - WALL MOUNTED
HATCHING AND ARROW INDICATE FACE AND CHEVRONS
EXIT SIGN - CEILING MOUNTED
HATCHING AND ARROW INDICATE FACE AND CHEVRONS
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY
LV: LOW VOLTAGE
LVD:LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
48"
CENTER
OS
OCCUPANCY SENSOR, DUAL TECHNOLOGY -
CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OS OCCUPANCY SENSOR, DUAL TECHNOLOGY -
WALL/CORNER MOUNTED
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
** - HATCHING OF ANY LIGHT FIXTURE INDICATED SERVED BY EMERGENCY CIRCUIT. PROVIDE
GENERATOR TRANSFER DEVICE FOR ALL SWITCHED EMERGENCY FIXTURES.
*** - LOWERCASE LETTER ADJACENT TO LIGHT FIXTURE AND CONTROLS INDICATES CONTROL ZONE ASSOCIATION. ALL CONTROLS AND LIGHTS WITH THE SAME LOWERCASE LETTER SHALL OPERATE
AS ONE ZONE. IF LOWERCASE LETTERS ARE NOT PROVIDED THEN ALL LIGHTS IN ROOM SHALL
OPERATE AS A SINGLE LIGHTING ZONE.
LS
LIGHT LEVEL SENSOR, SINGLE ZONE DIMMING CLOSED
LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
WITH 0-10V DIMMING
RCD
18" LINEAR - UNDERCABINET
--- 2' X 2' FLAT LENS TROFFER - RECESSED
9'-0"
BOTTOM
4' LINEAR STRIPLIGHT - SUSPENDED
--- SWITCHED / DIMMED CONTROLLED LIGHTING CIRCUIT
UNSWITCHED LIGHTING CIRCUIT
7'-5"
BOTTOM
EMERGENCY LIGHTING UNIT - WALL MOUNTED
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - 2-4 PR UTP
DATA OUTLET - 1-4 PR UTP
TELCO OUTLET - 1-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
18"
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
ELECTRONIC LOCKING MECHANISM
DOOR CONTACT
REQUEST FOR EXIT SENSOR
CARD READER
(K - KEYPAD)
48"CR
ES
DC
RX
48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)
WIRELESS ACCESS POINT - 2-4 PR UTP
WALL PHONE - 1-4 PR UTPW
DATA OUTLET - 4-4 PR UTP18"
TV OUTLET WALL MOUNTED
48"
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
FOUR POST OIT EQUIPMENT RACK
OIT EQUIPMENT CABINET
MATV EQUIPMENT CABINET
CCTV EQUIPMENT CABINET
MATV
CCTV
LADDER CABLE TARY
AS NOTED
DOOR
DOOR
ABOVE
DOOR
6' TO TOP
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
ELECTRONIC PANIC HARDWAREEP
DO DOOR OPERATOR
W WIRELESS PENDANT
L PATIENT ROAM ALERT ANTENNACEILING
GROUND BUS
CEILING
DOOR
DOOR
FLOOR
FLOOR
FLOOR
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RATED TTB8"
FLOOR TWO POST OIT EQUIPMENT RACK
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
DP DURESS PANIC ALARM PUSH BUTTON48"
PB PUSH BUTTON48"
TV OUTLET CEILING MOUNTEDCEILING
1P
1PH
2/C 2W
3PH
A
AAP
AC, A/C
ACC
ACLG
ADO
A/E
AF
AFC
AFF
AFG
AFI
AJH
AHU
AIC
AL
ALT
AMP
ANSI
APPROX
ARCH
AT
ATS
AUTO
AUX
AV
AWG
BAS
BATT
BC
BD
BFF
BISCI
BLDG
BMS
BRKR
BYP
C
CAB
CALC
CAP
CAT
CATV
CB
CCR
CCTV
cd
CD
CF
CKT
CLG
COAX
COMM
CONN
CONST
CONT
CONTR
COORD
COR
CPT
CR
CRI
CT
CTV
CTR
CU
CU FT
dB
DB
DC
DCP
DED
DEG C
DEG F
DEM
DEMO
DEPT
DIA
DISC
DIST
DN
DO
DS
DT
DVR
DWG
EC
ECB
EEB
EF
EG
EIA
ELEC
ELEV
EM
EMI
EMS
EMT
EP
EPO
EQUIP
ES
ESMT
ETC
ETR
EWC
EWH
EX
EXP
FA
FAAP
FACP
FAP
FC
FCU
FIXT
FLR
FO
FU
FVR
FVNR
GAL
GALV
GC
GEC
GEN
GFI
GND
GRS
GYP BD
HOA
HP
HT
HTR
HV
HVAC
IC
IES
IG
IMC
IR
IT
J-BOX
K
KCMIL
KV
KVA
KW
KWH
LED
LF
LM
LRA
LTS
LTG
LTNG
LV
MATV
MAX
MC
MCA
MCB
MCC
MDP
MECH
MFR
MH
MIC
MIN
MISC
MLO
MM
MSBD
MT
MTS
MTR
NA
NAC
NC
NEC
NEMA
NFPA
NIC
NL
NO
NS
NTS
NVR
OC
OD
OH
OIT
OL
OS
PA
PACS
PAMN
PB
PCB
PC
PDU
PED
PG
PF
PH
PIV
PNL
PoE
PR
PRI
PROJ
PSI
PT
PVC
PWR
QTY
RCP
RECEPT, REC
REQD
RGS
RM
RMS
RTU
RX
SC
SEC
SEP
SF
SHT
SI
SIM
SLC
SM
S/N
SPD
SPEC
SPKR
SP
SPD
SR
SS
SSBJ
S/S
STD
SURF
SW
SWBD
SYM
SYS
TBB
TC
TEL
TEL/DATA
TERM
TGB
TIA
TMGB
TP
TPS
TR
TTB
TTC
TV
TYP
UC
UE
UG
UH
UL
UPS
UT
UTP
UTIL
UV
V
VA
VAV
VERT
VFD
VOL
W W/
WAP
WH
WM
WP
XFMR
XFR
ELECTRICAL ABBREVIATIONS LIST
SINGLE MODE FIBER
SOLID NEUTRAL
SURGE PROTECTION DEVICE
SPECIFICATION
SPEAKER
SPARE
SURGE PROTECTION DEVICE
SURFACE RACEWAY
STAINLESS STEEL
SUPPLY SIDE BONDING JUMPER
STOP/START PUSHBUTTONS
STANDARD
SURFACE MOUNTED
SWITCH
SWITCHBOARD
SYMMETRICAL
SYSTEM
TELECOMMUNICATIONS BACKBONE
TIMECLOCK
TELEPHONE
TELEPHONE/DATA
TERMINAL
TELECOMM GROUND BUS BAR
TELECOMMUNICATIONS INDUSTRY
ASSOCIATION
TELECOMM MAIN GROUND BUS BAR
TWISTED PAIR
TWISTED PAIR SHIELDED
TAMPER RESISTANT OR
TELECOMM ROOM
TELEPHONE TERMINAL BOARD
TELEPHONE TERMINAL CABINET
TELEVISION
TYPICAL
UNDER COUNTER
UNDERGROUND ELECTRICAL
UNDERGROUND
UNIT HEATER
UNDERWRITER'S LABORATORY
UNINTERRUPTIBLE POWER SUPPLY
UNDERGROUND TELEPHONE
UNSHIELDED TWISTED PAIR
UTILITY
UNIT VENTILATOR OR
ULTRAVIOLET
VOLT
VOLT-AMPERES, VETERANS AFFAIRS
VARIABLE AIR VOLUME
VERTICAL
VARIABLE FREQUENCY DRIVE
VOLUME
WATT
WITH
WIRELESS ACCESS POINT
WATER HEATER
WIRE MANAGEMENT
WEATHERPROOF
TRANSFORMER
TRANSFER
MANUAL TRANSFER SWITCH
MOTOR, MOTORIZED
NOT APPLICABLE
NETWORK APPLIANCES CONTROL PANEL
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NO SCALE
NOT TO SCALE
NETWORK VIDEO RECORDER
ON CENTER
OUTSIDE DIAMETER
OVERHEAD
OFFICE OF INFORMATION AND
TECHNOLOGY
OVERLOAD
OCCUPANCY SENSOR
PUBLIC ADDRESS
PHYSICAL ACCESS CONTROL SYSTEM
PUBLIC ADDRESS AND MASS NOTIFICATION
SYSTEM
PULL BOX OR PUSHBUTTON
POLYCHLORINATED BIPHENYL
PHOTOELECTRIC CELL
POWER DISTRIBUTION UNITS
PEDESTAL
PLUGMOLD
POWER FACTOR
PHASE
POST INDICATING VALVE
PANEL
POWER-OVER-ETHERNET
PAIR
PRIMARY
PROJECTION
POUNDS PER SQUARE INCH
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE (CONDUIT)
POWER
QUANTITY
REFLECTED CEILING PLAN
RECEPTACLE
REQUIRED
RIGID GALVANIZED STEEL
ROOM
ROOT MEAN SQUARE
ROOF TOP UNIT
REQUEST TO EXIT
SURFACE CONDUIT
SECONDARY
SERVICE ENTRANCE PROTECTION
SQUARE FEET/FOOT
SHEET
INTERNATIONAL SYSTEM OF UNITS
SIMILAR
SIGNALING LINE CIRCUIT
1 POLE (2P, 3P, 4P, ETC.)
1 PHASE
TWO-CONDUCTOR (3/C, 4/C, ETC.)
TWO-WIRE (3W, 4W, ETC.)
3 PHASE
AMPERE
ALARM ANNUNCIATOR PANEL
ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACCESSIBLE
ABOVE CEILING
AUTOMATIC DOOR OPENER
ARCHITECT/ENGINEER
AMP FRAME
AVAILABLE FAULT CURRENT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ARC FAULT CIRCUIT INTERRUPTER
AUTHORITY HAVING JURISDICTION
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
ALTERNATE
AMPERE
AMERICAN NATIONAL STANDARDS INSTITUTE
APPROXIMATELY
ARCHITECT, ARCHITECTURAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AUDIO VISUAL
AMERICAN WIRE GAUGE
BUILDING AUTOMATION SYSTEM
BATTERY
BARE COPPER
BOARD
BELOW FINISHED FLOOR
BUILDING INDUSTRY CONSULTING SERVICE
INTERNATIONAL
BUILDING
BUILDING MANAGEMENT SYSTEM
BREAKER
BYPASS
CONDUIT
CABINET
CALCULATED
CAPACITY
CATALOG, CATEGORY
COMMUNITY ANTENNA TELEVISION
CIRCUIT BREAKER
CONTROL CONTRACTOR
CLOSED CIRCUIT TELEVISION
CANDELA
CONSTRUCTION DOCUMENTS
CONTRACTOR-FURNISHED
CIRCUIT
CEILING
COAXIAL CABLE
COMMUNICATION
CONNECTION
CONSTRUCTION
CONTINUATION OR CONTINUOUS
CONTRACTOR
COORDINATE
CONTRACTING OFFICER
REPRESENTATIVE
CONTROL POWER TRANSFORMER
CARD READER
COLOR RENDERING INDEX
CURRENT TRANSFORMER
CABLE TELEVISION
CENTER
COPPER
CUBIC FEET
DECIBEL
DIRECT BURIAL
DIRECT CURRENT OR
DOOR CONTACT SWITCH
DIMMER CONTROL PANEL
DEDICATED
DEGREES CELSIUS
DEGREES FAHRENHEIT
DEMAND
DEMOLISH/DEMOLITION
DEPARTMENT
DIAMETER
DISCONNECT
DISTRIBUTION
DOWN
DOOR OPERATOR
SAFETY DISCONNECT SWITCH
DOUBLE THROW
DIGITAL VIDEO RECORDER
DRAWING
ELECTRICAL CONTRACTOR
ENCLOSED CIRCUIT BREAKER
EMERGENCY EXIT BUTTON
EXHAUST FAN
EQUIPMENT GROUND
ELECTRONIC INDUSTRIES ALLIANCE
ELECTRIC, ELECTRICAL
ELEVATOR
EMERGENCY
ELECTROMAGNETIC INTERFERENCE
ENERGY MANAGEMENT SYSTEM
ELECTRICAL METALLIC TUBING
ELECTRONIC PANIC
EMERGENCY POWER OFF
EQUIPMENT
ELECTRIC STRIKE
EASEMENT
ET CETERA
EXISTING TO REMAIN
ELECTRIC WATER COOLER
ELECTRIC WALL HEATER
EXISTING
EXPLOSION PROOF
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM PANEL
FOOTCANDLE
FAN COIL UNIT
FIXTURE
FLOOR
FIBER OPTIC
FUSE
FULL VOLTAGE REVERSING
FULL VOLTAGE NON-REVERSING
GALLON
GALVANIZED
GENERAL CONTRACTOR
GROUNDING ELECTRODE CONDUCTOR
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND
GALVANIZED RIGID STEEL (CONDUIT)
GYPSUM BOARD
HAND-OFF-AUTOMATIC
HORSEPOWER
HEIGHT
HEATER
HIGH VOLTAGE
HEATING, VENTILATING AND
AIR CONDITIONING
INTERCOM
ILLUMINATION ENGINEERING SOCIETY
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
INFRARED
INTERCOMMUNICATION ROOM
JUNCTION BOX
KELVIN OR KEYPAD
THOUSAND CIRCULAR MILS
KILOVOLT
KILOVOLT-AMPERE
KILOWATT
KILOWATT HOUR
LIGHT-EMITTING DIODE
LINEAR FEET/FOOT
LUMEN
LOCKED ROTOR AMPS
LIGHTS
LIGHTING
LIGHTNING
LOW VOLTAGE
MASTER ANTENNA TELEVISION SYSTEM
MAXIMUM
MECHANICAL CONTRACTOR OR
METAL-CLAD (CONDUIT)
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MECHANICAL
MANUFACTURER
MANHOLE
MICROPHONE
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MULTI MODE FIBER
MAIN SWITCHBOARD
MOUNT
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED
PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, AND
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE
BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, AND/OR SMOKESTOP THE ANNULAR SPACE AROUND ALL PENETRATIONS
THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE
APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED
MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID
CONFLICT DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR
SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE
A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR
MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED.
ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND PARTICULAR
EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE
DEVICE'S SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT
UNLESS NOTED OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT MAY BE USED ON
VIBRATING EQUIPMENT. PVC MAY BE USED FOR UNDERGROUND OR CONCRETE-ENCASED.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN
APPROVED THIRD PARTY TESTING AGENCY.
17. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE
BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS
DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.
A1 b
E1 d
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER AND A NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE "A1" IS CONTROLLED BY SWITCH "b".
EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING.
SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES DIRECTIONAL
ARROW ON ILLUMINATED FACE(S).
EXAMPLE: THE WALL MOUNTED EXIT LIGHT TYPE "E1" WITH SINGLE FACE AND
DIRECTIONAL ARROW.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d".
KEY NOTE. SEE THE KEY NOTES ON THAT SHEET FOR THE NOTE NUMBER
INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION IS SHOWN ADJACENT TO THE HOME RUN ARROW. CIRCUIT BREAKER SIZES
(AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL SCHEDULE WITH THE
CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
EXAMPLE: HOME RUN TO PANEL 'LPN' CIRCUITS 1, 3, 5.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNIT
TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
Engineers Architects
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
/3
/2
:0
:0
P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
JKM KLC
ELECTRICAL NOTES AND LEGENDS -
ENCLOSED ROOF TOP WALKWAY
E-801
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
1 5
TYPE DESCRIPTION MOUNTING LAMPING DRIVER VOLTAGE WATTS
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN MODEL NUMBER
A1
2' X 4' ARCHITECTURAL LED TROFFER WITH CLOSED CENTER DIFFUSER;
MAXIMUM 3.6" LUMINAIRE DEPTH
RECESSED
GRID
LED; 4000 LUMENS;
80 CRI; 3500K
0-10V DIMMABLE
TO 1% DRIVER
120 V 37 W FOCAL POINT FAML-24-ACR-4000L-35K-1C-UNV-L11
E2
DIE-CAST ALUMINUM LED DOUBLE FACE EXIT SIGN WITH BRUSHED
ALUMINUM FINISH, RED LETTERS, AND CHEVRON ARROWS AS SHOWN ON
PLANS.
UNIVERSAL LED --- 120 V 5 W LITHONIA LQC 2 R
M
1.5" X 4' NARROW DIRECT/INDIRECT LINEAR PENDANT WITH DIE-CAST
ALUMINUM HOUSING, 60% DOWNLIGHT, 40% UPLIGHT; FROSTED ACRYLIC
LENS; MOUNTED AT 10'-0" AFF
CABLE
SUSPENDED
LED; 3500 LUMENS;
80 CRI; 3500K
0-10V DIMMABLE
TO 10% DRIVER
120 V 33 W FOCAL POINT
FSM1BS DCFL 500DN 375UP 35K 1C UNV LD1 C24BK
TS 4
TECHNOLOGY GENERAL NOTES
1. ALL COMMUNICATIONS DEVICES AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT
SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICAN DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI
STANDARDS AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, AND EQUIPMENT WHERE THE BUILDING CONSTRUCTION IS NOT
SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. ALL CABLING SHALL COMPLY WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION METHOD
MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
5. COMPLY WITH ANSI/TIA/EIA 758 AND 607B OR 607A - GROUNDING AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
6. COMPLY WITH ANSI/TIA/EIA 568B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING STANDARD.
7 COMPLY WITH ANSI/TIA/EIA 569B - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS PATHWAYS AND
SPACES.
8. COMPLY WITH NFPA 70 NATIONAL ELECTRICAL CODE.
9. COMPLY WITH NFPA 99 HEALTHCARE FACILITIES CODE.
10. COMPLY WITH NFPA 101 LIFE SAFETY CODE.
11. COMPLY WITH VA STANDARDS.
12. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFILCT
DURING CONSTRUCTION.
13. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN
ACT".
14. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
15. ALL CONDUITS SHALL BE RGS, OR EMT UNLESS OTHERWISE NOTED.
16. ALL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD PARTY
TESTING AGENCY.
17. ANY DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE VA COR, ARCHITECT, AND ENGINEER OF RECORD FOR CLARIFICATION. THE MORE STRINGENT OF THEM SHALL TAKE
PRECEDENCE.
18. A CORRIDOR, ROOM, OR ADJACENT SPACE WITH TWO OR MORE VISIBLE FIRE ALARM NOTIFICATION APPLIANCES
WITHIN THE FIELD OF VIEW SHALL FLASH IN SYNCHRONIZATIONS.
19. ALL COPPER OUTLETS/CONNECTORS SHALL BE TIA/EIA CAT 6.
20. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6 KEYSTONE JACK WIRED PER T568B AS DIRECTED BY THE VA COR.
21 LABELING SHALL BE ACCORDING TO LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE STANDARDS SET
FORTH BY MCGUIRE VA HOSPITAL OIT.
22 PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569B PARAGRAPH 4.5.6.2.
23 THE VA SHALL CONDUCT A WAP SURVEY AND PROVIDE SURVEY TO THE CONTRACTOR. CONTRACTOR SHALL
INSTALL CABLING AND EQUIPMENT PER THE SURVEY. COORDINATE WITH COR AND OIT.
FF
S
F
S
F
S
F
32 33 34 35 35.1 36 37 38 39 40 42
G
F
15cd
30cd
1/2 W
30cd
1/2 W 30cd
1/2 W
F.2
F.1
15cd
ENCLOSED
ROOF TOP
WALKWAY
2E116
Engineers Architects
N
AREA OF WORK
2 EAST OUTLINE
KEY PLAN
WALL RATING LEGEND
1 HOUR FIRE RATED BARRIER
2 HOUR FIRE RATED BARRIER
3 HOUR FIRE RATED WALL
SMOKE BARRIER
SMOKE RESISTANT
# SHEET KEY NOTES:
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
SHEET NOTES:
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
-0 -3
:2
:2 P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
JKM JWB
2ND FLOOR FIRE ALARM PLAN - 2E EAST
ENCLOSED ROOF TOP WALKWAY
FA802
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
2 2
0 4' 8' 16' 1/8" = 1'-0"1
2ND FLOOR FIRE ALARM PLAN - 2E EAST ENCLOSED ROOF TOP WALKWAY
SURFACE MOUNT FIRE ALARM CONDUIT ALONG
WALL AT APPROXIMATELY 11'6". FIRE ALARM
CONDUIT SHALL BE FACTORY PAINTED RED.
SURFACE MOUNT FIRE ALARM CONDUIT ALONG WALL
AT APPROXIMATELY 11'6". FIRE ALARM CONDUIT
SHALL BE FACTORY PAINTED RED.
EXIST. CONCRETE FLOOR
STEEL BEAM.
C-CLAMP.
EXPANSION ANCHOR HILTI QUIK BOLT
TZ OR APPROVED EQUAL. EXPANSION
ANCHOR SHALL BE QUALIFIED FO R
USE IN CRACKED CONCRETE PER ACI
355.2
THREADED HANGER ROD.
SURGE RESTRAINER.
ADJUSTABLE RING HANGER.
AUTO. SPRINKLER PIPE.
NOTE: HANGING DETAILS SHOWN ARE SUBJECT
TO REQUIREMENTS OF SEISMIC DESIGN.
RETAINING STRAP.
SET SCREW.
CONCRETE STEEL BEAM
INSTALL INSULATION AFTER
CAULKING SLEEVE, SEAL AS
REQUIRED.
FIRE RATED WALL AND OR SLAB.
STEEL PIPE SLEEVE TERMINATE
SLEEVE FLUSH WITH FINISHED
SURFACE.
FIRESTOPPING APPROVED
(BY LOCAL CODES)
FINISHED ESCUTCHEON PLATE
FLUSH AGAINST WALL AND OF
SIZE TO COMPLETELY COVER
OPENING.
APPROVED TYPE FIRE SAFE &
SMOKE TIGHT CAULKING SEALER
BETWEEN BARE PIPE AND SLEEVE.
NOTE: MINIMUM SIZE OF OPENINGS AROUND SPRINKLER PIPE PENETRATIONS OF
CONCRETE OR CMU WALLS SHALL BE IN ACCORDANCE WITH NFPA 13 SEISMIC
REQUIREMENTS.
1" x 1/2" REDUCER
NOTES:
1. ALL SPRINKLERS SHALL BE QUICK RESPONSE TYPE.
2. INSTALL PER MANUFACTURER'S REQUIREMENTS.
1" X 90 ELL
1" x 2" NIPPLE
BRANCH LINE
HANGERS SHALL
BE PROVIDED AS
REQUIRED BY
NFPA 13, TYPICAL
1" X RUN NIPPLE
CEILING
GUARD PROTECTOR
SIDEWALL SPRINKLER
LOCATED PER NFPA 13
Engineers Architects
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
/3
/2
:3
:0 P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
PLH SMH
FIRE PROTECTION DETAILS
FS501
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
2 3
N.T.S.2
PIPE HANGER SUPPORT DETAIL
N.T.S.3
SPRINKLER PIPE SLEEVE THRU FIRE RATED WALL
N.T.S.1
TYPICAL SIDEWALL SEMI-RECESSED PENDENT SPRINKLER
27 30 32 33 34 35 35.1 36 37 38 39 40 42 43 44
G
H
J.1
OH1
OH2
30 32 33 34 3535.1 36 37 38 39 40 42 43 44
H
G
F
F.2
F.1
J.
CONNECT TO
EXISTING
BRANCH LINE
EXISTING
BRANCH
LINE
EXISTING SPRINKLER
PIPING AND HEADS
SERVING EXAM ROOMS TO
REMAIN (TYPICAL)
SIDEWALL SPRINKLER
HEAD TO SERVE
WALKWAY (TYP.) SEE
DETAIL FS501/1.
WALKWAY WALKWAY
OTBC:
TREATMENT
AREA (EDEMA)
2E115
OTBC: STOR
2E114
EXAM 7
2E113
EXAM 6
2E112
EXAM 5
2E111
EXAM 4
2E110
EXAM 3
2E109
EXAM 2
2E108
EXAM 1
2E107
TOILET
2E106
ENCLOSED
ROOF
WALKWAY
2E116
AREA OF WORK
FOR WALL
PENETRATION SEE
DETAIL FS501/3.
Engineers Architects
N
AREA OF WORK
2 EAST OUTLINE
KEY PLAN
# SHEET KEY NOTES:
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
SHEET NOTES:
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
/3
/2
:3
:0 P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
PLH SMH
2ND FLOOR FIRE PROTECTION PLAN - 2E EAST
WITH ENCLOSED ROOF TOP WALKWAY
FS801
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
3 3
0 4' 8' 16' 1/8" = 1'-0"1
2ND FLOOR FIRE PROTECTION PLAN - 2E EAST WITH ENCLOSED ROOF TOP WALKWAY
DUST CONTROL PLAN NOTES
1. THE VAMC INFECTION CONTROL GROUP HAS CONFIRMED THE DESIGNATION FOR
THIS PROJECT IS LEVEL IV FOR THE CLASS OF PRECAUTIONS OR LEVEL OF INFECTION
CONTROL ACTIVITIES. HARD SURFACE BARRIERS SHALL BE USED EXCEPT IN THE AREA
INDICATED ON THE PHASING PLAN WITH PLASTIC BARRIERS (MINIMUM 4MIL) TO SEAL
AREA FROM NON-WORK AREA AS LONG AS THE SPRINKLER SYSTEM IS INTACT AND
ACTIVE.
1A. THIS PROJECT NEEDS AN ENTRY VESTIBULE FOR CLOTHING CHANGES (PROVIDE
AND LOCATE A STAGING AREA FOR TYVEK SUITS NEAR THE PLASTIC BARRIER
ENTRANCE SPACES - CONSTRUCTION ANTEROOM. THEY SHALL BE USED WHEN GOING
INTO CONSTRUCTION AREA AND LEAVING THE CONSTRUCTION AREA) AND TOOL
STORAGE TIGHT SEALS SHALL BE MAINTAINED AT THE FULL PERIMETER OF WALLS AND
WALL PENETRATIONS. ANY DUST SHALL BE IMMEDIATELY CLEANED IF TRACKED
OUTSIDE OF THE CONSTRUCTION BARRIER. UPON COMPLETION OF THE CONSTRUCTION
PHASE, DUST BARRIERS SHALL BE REMOVED CAREFULLY TO MINIMIZE SPREADING OF
DUST AND THE CONTRACTOR SHALL HAVE TEMPORARY DUST PROTECTION IN PLACE
BEFORE REMOVAL OF A PERMANENT BARRIER.
A DWYER GAUGE SHALL BE USED AT CONSTRUCTION ENTRY TO VALIDATE NEGATIVE
AIR FLOWS.
2. PROVIDE STICKY MATS AT THE PLASTIC BARRIER ENTRANCE SPACES
(CONSTRUCTION ANTEROOM) AND CHANGE DAILY OR MORE OFTEN AS NEEDED TO
PREVENT THE SPREAD OF DUST AND DEBRIS INTO ADJACENT CLEAN SPACE.
INTERNAL DEMOLITION AND CONSTRUCTION ACTIVITIES DUST AND DEBRIS CONTROL
3. USE CORRIDORS C2C4, C2C6 AND 2E143 AS PRIMARY CONSTRUCTION ACCESS.
3A. TRAFFIC CONTROL: DESIGNATED ENTRY AND EXIT PROCEDURES SHALL BE
DEFINED. EGRESS PATHS SHALL BE FREE OF DEBRIS; DESIGNATED ELEVATORS SHALL
BE USED DURING SCHEDULED TIMES; AND ONLY AUTHORIZED PERSONNEL SHALL
BE ALLOWED TO ENTER THE CONSTRUCTION ZONE. SIGNAGE SHALL DIRECT
PEDESTRIAN TRAFFIC AWAY FROM THE CONSTRUCTION AREA AND MATERIALS.
4. CONTRACTOR SHALL USE ISOLATION CARTS TO TRANSFER CONSTRUCTION
MATERIAL IN AND OUT OF THE PROJECT - A CLEAN CART SHALL BE USED; THE NOT-SO-
CLEAN CART SHALL BE USED BETWEEN THE MAIN ENTRY AND THE CONSTRUCTION
STAGING/PREP AREA.
4A. DEMOLITION DEBRIS: DEBRIS SHALL BE REMOVED IN CARTS WITH TIGHTLY
FITTED COVERS, DESIGNATED TRAFFIC ROUTES SHALL BE MADE TO MINIMIZE USE OF
ELEVATORS WITH AN EMPHASIS ON TRANSPORT DURING THE LOWEST PERIOD OF
ACTIVITY. DEBRIS SHALL BE REMOVED DAILY AND AT TIMES SPECIFIED BY THE VAMC. IF
CHUTES ARE USED TO DIRECT DEBRIS OUTSIDE, HIGH EFFICIENCY PARTICULATE AIR
(HEPA) FILTERED NEGATIVE AIR MACHINES SHALL BE USED, AND THE CHUTE OPENING
SHALL BE SEALED WHEN NOT IN USE. FILTERS SHALL BE BAGGED AND SEALED BEFORE
BEING TRANSPORTED OUT OF THE CONSTRUCTION AREA. THE CONTRACTOR SHALL
NOT HAUL DEBRIS THROUGH PATIENT-CARE AREAS WITHOUT PRIOR APPROVAL OF THE
COR.
4B. EXTERIOR WINDOWS: WINDOWS SHALL BE SEALED TO MINIMIZE INFILTRATION
FROM ANY ADJACENT EXCAVATION DEBRIS.
VENTILATION AND ENVIRONMENTAL CONTROLS
5. AIR SYSTEM FLOW: THE COR SHALL VERIFY AND NOTIFY CONTRACTOR WHETHER
THE CONSTRUCTION AREA USES FRESH/OUTSIDE OR RE-CIRCULATED AIR; FILTERS
SHALL BE ADDED OR RETURN VENTS COVERED AS NEEDED WITH FILTER MATERIAL OR
PLASTIC. AIR MUST FLOW FROM CLEAN TO DIRTY AREAS. CARTS NEED TO BE CLEANED,
WIPED DOWN AND COVERED BEFORE LEAVING CONSTRUCTION SITE.
5A. NEGATIVE AIR PRESSURE: THE AIR WITHIN THE CONSTRUCTION AREA SHALL BE
NEGATIVE WITH RESPECT TO SURROUNDING AREAS AND WITH NO DISRUPTION OF AIR
SYSTEMS OF ADJACENT AREAS. USE OF THE NEGATIVE AIR PRESSURE SYSTEM WITHIN
THE ENCLOSURE TO REMOVE DUST SHALL PASS AIR THROUGH AN INDUSTRIAL GRADE,
PORTABLE HEPA FILTER CAPABLE OF FILTRATION RATES OF 300-800 CUBIC FEET PER
MINUTE (FT3/MIN), OR EXHAUST AIR DIRECTLY TO THE OUTSIDE IF APPROVED BY VAMC.
IF EXHAUST SHALL BE TIED INTO A RE-CIRCULATED AIR SYSTEM, A PRE-FILTER AND
HEPA FILTER SHALL BE USED BEFORE EXHAUST TO PREVENT CONTAMINATION OF THE
DUCTS.
5B. ADJACENT AREAS: THE STATUS OF SEALED PENETRATIONS AND INTACT CEILING
SHALL BE VERIFIED DAILY.
5C. AIR EXCHANGE RATES AND PRESSURE RELATIONSHIPS: VAMC AND CONTRACTOR
SHALL VERIFY AND MAINTAIN PROPER RATES IN CRITICAL AREAS NEAR CONSTRUCTION
ACTIVITY AND ENSURE AIR IS NOT BEING RE-CIRCULATED WITHOUT FILTRATION FROM
THE CONSTRUCTION AREA ELSEWHERE. PROVIDE AIR PRESSURE TESTING
THROUGHOUT THE PROJECT IN THE FREQUENCY AS IDENTIFIED BY THE COR.
CONTAMINATION OF PATIENT ROOMS, SUPPLIES, EQUIPMENT AND RELATED AREAS
6. WORKSITE CLOTHING: CONTRACTOR PERSONNEL CLOTHING SHALL BE FREE OF
LOOSE SOIL AND DEBRIS BEFORE LEAVING THE CONSTRUCTION AREA. IF PROTECTIVE
APPAREL IS NOT WORN (E.G., COVERALLS, FOOTGEAR AND HEADGEAR) A HEPA-
FILTERED VACUUM SHALL BE USED TO REMOVE DUST FROM CLOTHING BEFORE
LEAVING THE BARRICADE. IF PROTECTIVE APPAREL IS UTILIZED, THE CONTRACTOR
SHALL CONSTRUCT A SPACE OR ANTEROOM FOR CHANGING CLOTHING AND STORING
EQUIPMENT (DESIGNATED AREA. ALL EQUIPMENT, TOOLS, TOOL CARTS, AND
MATERIALS TRANSPORTED THROUGH OCCUPIED AREAS SHALL BE MADE FREE FROM
DUST AND MOISTURE BY VACUUMING AND WET WIPING BEFORE THEIR REMOVAL FROM
THE CONSTRUCTION ZONE OR WORK AREA.
6A. POST CONSTRUCTION: DO NOT REMOVE BARRIERS AND KEEP ALL HVAC
ISOLATION UNTIL CONTRACTOR HAS CLEANED CONSTRUCTION SITE, VA EMS STAFF
HAS DONE A TERMINAL CLEANING, AND VA INFECTIOUS DISEASE CONTROL HAS
INSPECTED AND APPROVED THE CLEANING.
6B. AIR BALANCING AND AHU STARTUP ARE NOT PERMISSABLE PRIOR TO REVIEW
AND APPROVAL OF EXTENSIVE "CONSTRUCTION CLEAN" BY THE CONTRACTOR.
POLICY LETTER EC-51
7. REFER TO SPEC SECTION 01 01 10 FOR EC-51 SAFETY AND HEALTH POLICY AND
PROCEDURES DURING CONSTRUCTION ACTIVITIES.
FIRE ALARMS
8. FIRE ALARMS AND OTHER LIFE SAFETY FIXTURES WITHIN THE ICRA BARRIERS OF
THE CONSTRUCTION AREAS SHALL BE TEMPORARILY RELOCATED TO THE OUTSIDE OF
BARRIRES.
ICRA NOTES
1. SEE ICRA NOTES FROM SHEETS
GI803 FOR CONTRUCTION PHASE.
2. INSTALL ILSM EGRESS SIGNAGE
AND INDICATION OF EXIT ACCESS
ROUTE DURING CONSTRUCTION
PHASE.
ICRA
ICRA REFERENCE CODES
2018 NFPA 101 LIFE SAFETY CODE
NFPA 99 HEALTH CARE FACILITIES CODE
2018 INTERNATIONAL BUILDING CODE
2014 NEC ELECTRICAL CODE
OCCUPATIONAL SAFETY & HEALTH
ADMINISTRATION (OSHA)
UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY (USEPA)
ILSM SIGNAGE
INTERIM LIFE SAFETY MEASURES IN EFFECT
FOR RENOVATION BUILDING 1,
SECOND FLOOR ROOF WALKING TRACK, 2E AT UD
THIS EXIT IS CLOSED AND LEADS TO A
CONSTRUCTION AREA.
PLEASE USE ALL ALTERNATE EXITS AS MARKED.
1' - 5"
1/2"1/2"
/2
/2
/2
/2
/2
/2
EQ.EQ.
Engineers Architects
Drawing Title
Location
Project Title
Date
Approved: Project Director
Checked
Building Number
VA Project Number
Drawing Number
Drawn
Dwg.
CONSULTANTS: PROJECT MANAGER:
Office of Facilities
Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
E
D
C
B
A of
FULLY SPRINKLERED
3 4 5 6 7
2 3 4 5 6 7
E
D
C
B
A
Project Number Scale 15-001
Revisions: Date
AS INDICATED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:4 P
M
RENOVATE BLDG. 1, SECOND
FLOOR, 2E AT UD
KMN, KC KC, DGC
INFECTION AND DUST CONTROL PLANS AND
NOTES
GI802
AUGUST 25, 2020
100% CD
UNIVERSITY DRIVE, PITTSBURGH, PA 15240
646-14-102
2 4
3" = 1'-0"
ILSM CONSTRUCTION EGRESS SIGNAGE
"FOR REFERENCE ONLY"
SEE DIV 1 SPECIFICATIONS FOR OFFICIAL ICRA, ILSM AND ASSOCIATED FORMS AND REQUIREMENTS
UP UP
DN
1. PROVIDE TEMPORARY 1-HOUR
RATED SLAB-TO-SLAB
BARRIERS CONSIST OF 3-5/8"
METAL STUD FRAMING WITH
5/8" GYPSUM BOARD ON BOTH
SIDES. BARRIERS SHALL BE
INSPECTED BY VA LIFE
SAFETY AND ICRA STAFF
PRIOR TO START OF
CONSTRUCTION IN SPACE.
MAINTAIN NEGATIVE
PRESSURE VENITLATION IN
THE CONSTRUCTION SPACE
2. PROVIDED OUTER DOOR TO
THE CONSTRUCTION AREA
ANTEROOM SHALL BE 45 MIN.
RATED HARD DOOR IN A
RATED FRAME WITH CLOSER.
3. CONSTRUCTION ACCESS
ROUTE
4. USE ISOLATION CART FOR ALL
WORK IN THIS AREA.
5. PROVIDE TWO STICKY MATS
AT EACH CONSTRUCTION
ACCESS POINT IN ALL
PHASES.
6. PROVIDE STAGING AREA FOR
PPE (PERSONAL PROTECTIVE
EQUIPMENT) FOR HAZMAT
SUITS UNLESS NOTED
OTHERWISE.
7. TURN UP EXHAUST ON
EXTERIOR SIDE,
CONTRACTOR SHALL VERIFY
LOCATION OF AIR INTAKES AT
THE PROPER DISTANCE FROM
EXHAUST. VERIFY LOCAL
JURISDICTION CODE AND VA
REQUIREMENTS FOR
DISTAN…
This is the start of the file's text. The full file is on GovTribe.