2D RLP 36C10F23R0075 Appendix A_3 Room Data Matrix RDM Nashville TN OPC - 8-10-2023.pdf

PDF 692 KB Posted

Attached to
X1DA--Nashville, TN OPC Amendment #3 FSL 2 188, 712 ANSI/BOMA
Solicitation number
36C10F23R0075
Issued by

About this file

This document contains a Room Data Matrix and related notes for the Nashville, TN VA Outpatient Clinic project. The matrix lists over 100 room types with specifications for interior construction, mechanical, electrical, lighting, and IT requirements. Key room types include exam rooms, procedure rooms, imaging rooms, dental treatment rooms, physical therapy spaces, pharmacy, sterile processing, and office/workstation areas. Specifications cover flooring, wall, and ceiling finishes; doors, hardware, and glazing; HVAC, plumbing, and electrical systems; and lighting controls. Accompanying notes provide definitions and additional requirements. The related federal contract opportunity is for design-build construction services for the Nashville OPC project under solicitation number 36C10F23R0075. The project involves renovating and expanding the existing facility to 188,712 ANSI/BOMA square feet.

View the file

Other files

File Type Posted
36C10F23R0075 0003.docx DOCX document
36C10F23R0075 - Nashville TN OPC - RLP Amendment 3 - 9.27.2023 - Executed.pdf PDF
36C10F23R0075 - Nashville TN OPC - RLP Amendment 2 - Pre-bid Presentation - 8.24.2023.pdf PDF
36C10F23R0075 - Nashville TN OPC - RLP Amendment 2 - Pre-Bid Presentation - Attendance Sheets - 8.24.2023.pdf PDF
36C10F23R0075 - Nashville TN OPC - RLP Amendment 2 - 9.14.2023.pdf PDF
36C10F23R0075 - Nashville TN OPC - RLP Amendment 2 - Pre-Bid Presentation - Transcript - 8.24.2023.pdf PDF
2B RLP 36C10F23R0075 Appendix A_1 Project Contents List PRC Nashville TN OPC - 8-10-2023.pdf PDF
36C10F23R0075 0002.docx DOCX document
2C RLP 36C10F23R0075 Appendix A.2 Lease Design Narrative LDN Nashville TN OPC - 9.14.2023 REVISION.pdf PDF
36C10F23R0075 - Nashville TN OPC - RLP Amendment 2 - VA Q_A Matrix - 9.14.2023.pdf PDF
36C10F23R0075 0001.docx DOCX document
36C10F23R0075 - Nashville TN OPC RLP Amendment No 1 - 16 August 2023.pdf PDF
2G RLP 36C10F23R0075 Appendix A_4_5 Facility Level Security FSL III Nashville TN OPC - 8-10-2023.pdf PDF
2B RLP 36C10F23R0075 Appendix A_1 Project Contents List PRC Nashville TN OPC - 8-10-2023.xlsx XLSX spreadsheet
3 RLP 36C10F23R0075 Appendix A_6 Conceptual Floor Plan Nashville TN OPC -8-10-2023.pdf PDF
5 RLP 36C10F23R0075 Offering Entity Acknowledgement Form Nashville TN OPC - 8-10-2023.pdf PDF
22 RLP 36C10F23R0075 Pre Bid Conference Registration Form Nashville TN OPC - 8-10-2023.pdf PDF
8 RLP 36C10F23R0075 Attachment No_1 to GSA Form 1364 Nashville TN OPC -8-10-2023.xlsx XLSX spreadsheet
23 RLP 36C10F233R0074 GSAR 552_270-33 Foreign Ow Fin Rep for High Sec Leased Sp Clarksville TN OPC - 8-10-2023.pdf PDF
11 RLP 36C10F23R0075 Past Performance Questionnaire Nashville TN OPC - 8-10-2023.pdf PDF
13 RLP 36C10F23R0075 GSA Form 527 Contractors Quals and Financial Info Nashville TN OPC -8-10-2023.pdf PDF
9 RLP 36C10F23R0075 GSA Form 1217 Lessor s Annual Cost Statement Nashville TN OPC - 8-10-2023.pdf PDF
20 RLP 36C10F23R0075 Covered Telecommunications Equip or Services Representation Nashville TN OPC - 8-10-2023.pdf PDF
1 RLP 36C10F23R0075 Lease Nashville TN OPC - 8-10-2023.pdf PDF
7 RLP 36C10F23R0075 Proposal to Lease Space GSA Form 1364 Nashville TN OPC -8-10-2023.pdf PDF
0 RLP 36C10F23R0075 RLP Nashville TN OPC - 8-10-2023.pdf PDF
18 RLP 36C10F23R0075 Certification of Building Energy Performance Nashville TN OPC - 8-10-2023.pdf PDF
17 RLP 36C10F23R0075 GSA Form 12000 for Prelease Fire Protection and Life Safety Eval Nashville TN OPC - 8-10-2023.pdf PDF
6 RLP 36C10F23R0075 Offeror Proposal Compliance Matrix Nashville TN OPC - 8-10-2023.pdf PDF
4 RLP 36C10F23R0075 Appendix B Janitorial Services and Site Maintenance Nashville TN OPC - 8-10-2023.pdf PDF
10 RLP 36C10F23R0075 Form VA 10091 VA FSC Vendor File Request Form Nashville TN OPC - 8-10-2023.pdf PDF
2C_1 RLP 36C10F23R0075 Appendix A_2_1 Interior Finish Standards Nashville TN OPC - 8-10-2023.pdf PDF
14 RLP 36C10F23R0075 VA Handbook 6500_6 (Appendix D) VA Rules of Behavior Nashville TN OPC - 8-10-2023.pdf PDF
2C RLP 36C10F23R0075 Appendix A_2 Lease Design Narrative LDN Nashville TN OPC - 8-10-2023.pdf PDF
36C10F23R0075.docx DOCX document
2 RLP 36C10F23R0075 Cover Page for Agency Specific Requirements (ASR) Nashville TN OPC -8-10-2023.pdf PDF
2F RLP 36C10F23R0075 Appendix A_4_1 OIT Extra Small Campus Spt Ctr Dsgn Nashville TN OPC - 8-10-2023.pdf PDF
19 RLP 36C10F23R0075 Davidson County Wage Determination Nashville TN OPC - 8-10-2023.pdf PDF
21 RLP 36C10F23R0074 Seismic Forms Nashville TN OPC - 8-10-2023.pdf PDF
15 RLP 36C10F23R0075 GSA Form 3516 Solicitation Provisions Nashville TN OPC - 8-10-2023.pdf PDF
2E RLP 36C10F23R0075 Appendix A_4 OIT Design Template Nashville TN OPC - 8-10-2023.pdf PDF
12 RLP 36C10F23R0075 SF 330 Architect Engineer Qualifications Nashville TN OPC - 8-10-2023.pdf PDF
2A RLP 36C10F23R0075 Appendix A Program for Design PFD Nashville TN OPC - 8-10-2023.pdf PDF
16 RLP 36C10F23R0075 GSA Form 3517B General Clauses Modified General Clauses Nashville TN OPC - 8-10-2023.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROOM IDENTIFICATION NOTES

Functional Area

DEPARTMENT ROOM NAME ROOM NAMES (VA) FGI EQUIVALENT FOR

ASHRAE 170

FGI EQUIVALENT FOR

TABLE 1.2-5 Minimum

Sound Isolation

F lo o r

F in is h

B as e

W al l F in is h

W ai n sc o t

M at er ia l

W ai n sc o t

H ei g h t

S T

C

C ei li n g F in is h

H ei g h t

N o te s

S iz e (W id th

T yp e

M at er ia l

G la zi n g

R at in g

H ar d w ar e

G ro u p

H ar d w ar e

N o te s

In d o o r T em p er at u re

C o o li n g

F

In d o o r T em p er at

H ea ti n g

F

In d o o r R el at iv e

H u m id it y

R

H M ax

In d o o r R el at iv e

H u m id it y

R

H M in

M in im u m T o ta l A

C H

M in im u m O

A A

C H

R o o m

A ir

R et rn

G en

E xh

G S p ec

E xh S

M ax im u m N o is e L ev el

N C

R o o m

A ir

B al an ce

V

A C

N o te s

D u p le x

R ec ep ta cl es

Q ad

R ep ta cl es

P o w er

N o te s

F ix tu re

T yp e

C o n tr o ls

L ig h ti n g

S p ec ia l

R eq u ir em en ts

L ig h ti n g

N o te s

D at a

O u tl et s (s ta n d ar d d en si ty

W A

O

IT

S ec ia l

R eq u ir em en ts

0 General Rooms/Spaces

Exam Room PACT Exam EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" 10 3'-0"

3'-6"

Flush Wood _ _ 12 SE 3 8 1 Multilevel Switching, Dimming & Occupancy

Multi-level switching or manual dimming

N/A 3

0 General Rooms/Spaces

Exam Room

Exam Room - Multi-Specialty, Exam / Treatment, Exam -

Consult, Consult Room - PACT, Exam/Consult Room (Mental

Health/Social Work), Exam Room EMG/EEG, Exam Room-

Cardiology, Exam/Consult, Nurse Practitioner, Women's Health

Exam, Tele-Health Exam, Optometry Exam Treatment

Room, Eye Lane, Tele-Retinal, TECHS, Applicance Fitting Room, Fitting Room, Physical Therapy Room, Occupational Treatment

Room

EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" 10 3'-6" Flush Wood _ _ 12 S 8 1 Multilevel Switching, Dimming & Occupancy

Multi-level switching or manual dimming

N/A 3

0 General Rooms/Spaces

Consult Room Consult Room, Audiology

Rehabilitation Counceling Room, Dental Consult Room

CONSULTATION CPT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 - 4 2 Return 40 NR 6 Multilevel Switching, Dimming & Occupancy

Multi-level switching or manual dimming

N/A 1

0 General Rooms/Spaces

Procedure Room

Procedure Room, General, Urology, Gynecology, Specialty Care, Multi-Specialty Care, Cast

Room

PROCEDURE TREATMENT WSF WSF EP RWC 4'-0" SEE FGI AT 9'-0" 3

3'-0"

3'-6"

Flush Wood -- -- 12 SE 3 7 P13 Multilevel Switching, Dimming & Occupancy

Wall mounted exam light N/A 2

0 General Rooms/Spaces

Laboratory Laboratory (Typical)

LABORATORY

WORKROOM

__ WSF WSF EP -- -- 40 AT-SP 9'-0" 3 3'-0" Flush Wood _ _ 15 AG 4 6 P3, P4 Multilevel Switching, Dimming & Occupancy

N/A N/A 5

0 General Rooms/Spaces

Conference Room

Conference Room, Multi-Purpose Room, Group Room, Shared Medical Appointment Room, Education Room, Staff Training Room, Classroom

__ CPT RB P RWC 4'-0" 40 AT 9'-0" 17 3'-6" Flush Wood _ _ 15 S _ M2 8 P14 Multilevel Switching, Dimming & Occupancy

Provide 4 scene preset dimmable lighting for a variety of tasks. Consider placement and optics to mitigate glare and ceiling reflections.

N/A 4 Floor data for table

0 General Rooms/Spaces

TOILET

General Toilet, Patient - Toilet, Toilet - Police, Toilet - Family, Toilet - Female Staff, Toilet - Male Staff, Toilet - Procedure Room, Toilet - Public, Toilet - RF Patient, Toilet - Women's Health, Toilet - Female, Toilet - Family Assist, Specimen Collection Toilet

TOILET ROOM TOILET ROOM PT PT P CT 7'-0" SEE FGI AT 9'-0" 1,2 3'-6" Flush Wood _ _ 11 _ 1 Downlights/Mirror or vanity Occupancy Sensor N/A N/A

0 General Rooms/Spaces

OFFICE Any Office -- CONSULTATION CPT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS 4 1 Multilevel Switching, Dimming & Occupancy

N/A N/A 2

0 General Rooms/Spaces

WAITING

Waiting - Family - PACT, Waiting - PACT 3, Waiting - General - 20 People, Waiting - General - 10 People, Waiting - General - 6

People, Waiting-General

EXAM - PUBLIC SPACE CPT RB P -- -- SEE FGI AT 9'-0" 10, 17 M4 -- --

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

0 General Rooms/Spaces

RECEPTION

Reception, Information Desk, Travel Window, Reception -

Accessible

-- -- RFT RB P -- -- -- AT 9'-0" -- 3'-0"

Flush w/ narrow vision

Wood _ _ 12 CG 3 M4 1 1 Downlights, pendants, decorative, and accent

Multilevel Switching, Dimming & Occupancy

N/A N/A 10 Data/phone feeds to systems furniture

0 General Rooms/Spaces

COPY ALCOVE

Copy Alcove, Copier - Workroom, Copy / Office Supply Room, Copy Room

-- -- RFT RB P -- -- -- AT 9'-0" 6 _ _ _ _ _ _ 6 3

Multilevel Switching, Dimming & Occupancy

N/A N/A 3

0 General Rooms/Spaces

CLEAN UTILITY

Clean Utility, Clean Supply, Clean Workroom, Clean Linen, Sterile Storage, CBOC Steril Supply Storage Room, Clean Scope, Dental Clean Cart, Central Sterile

-- -- RFT RB P RWC 4'-0" -- AT 9'-0" -- 3'-0" Flush Wood -- 45 MIN 121 AG _ 66 75 55 30 4 (+) 1 Occupancy Sensor N/A N/A

0 General Rooms/Spaces

SOILED UTILITY

Soiled Utility Room, Recycled Material, Soiled Holding, Soiled Linen, Soiled Workroom, Soiled

Supply, Soiled Cart

SOILED HOLDING /

SOILED WORK ROOM

-- WSF WSF P RWC 4'-0" -- AT 9'-0" 3 3'-0" Flush Wood -- 45 MIN 121 AG _ 2 -- Occupancy Sensor N/A N/A --

0 General Rooms/Spaces

STORAGE

Storage - Medical Equipment, Storage - Shared Medical

Appointments, DME - Prosthetics Storage, Storage - Homeless, EMS Storage, Storage - Bistro/Coffee Bar, Storage -

Patient Clothing and Luggage, Laundry / Storage, Tray Cart Storage Area, Buld Storage, General Storage, Secure Storage, CLEAN

WORKROOM/CLEAN

SUPPLY

RFT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG 1 per wall, not to exceed

12' spacing -- Surface or chain mounted 1' x 4' Occupancy Sensor N/A N/A

0 General Rooms/Spaces

JANITOR'S CLOSET

Housekeeping Aides Closet

(HAC)

ENVIRONMENTAL

SERVICES ROOM

-- CS RB P FRP 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 34 A _ 1 -- Occupancy Sensor N/A N/A --

0 General Rooms/Spaces

KITCHENETTE Social Activities Space/ Kitchen -- -- RFT RB P -- -- -- AT 9'-0" 17 3'-0" Flush Wood -- -- 15 A _ 4 -- Multilevel switching/dimming/occ upancy

N/A N/A --

0 General Rooms/Spaces

EQUIPMENT ALCOVE

AED Alcove, Height and Weight Alcove, Scale Alcove, Stretcher Alcove, Med Alcove, Portable Patient Lift Alcove, Wheelchair Alcove, My Health eVet, Kiosk, Match

Adjacent Match Adjacent Match Adjacent RWC 4'-0" -- AT

Match Adjacent

3 -- -- -- -- -- 6 1 -- Multilevel Switching, Dimming & Occupancy

N/A N/A --

0 General Rooms/Spaces

STAFF LOUNGE Staff Lounge -- -- RSF RB P -- -- 40 AT 9'-0" 4 3'-0" Flush w/ narrow vision Wood -- -- 13 _ Exh. (G) (-) 8 --

P7 Multilevel Switching, Dimming & Occupancy

N/A N/A 2

0 General Rooms/Spaces

MEDICATION ROOM Medication Room MEDICATION ROOM -- RFT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 34 5 1 Multilevel Switching, Dimming & Occupancy

N/A N/A 1

0 General Rooms/Spaces

LACTATION ROOM

Employee Wellness, Lactation

Room, Quiet Room -- -- RFT RB P -- -- 50 AT 9'-0" 10 3'-0" Flush Wood -- -- 12 CS 4 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

0 General Rooms/Spaces

LOCKER ROOM

Locker Room, Locker Room (Male/ Female) Locker - Staff

Personal Property, Locker Room - Staff

-- -- RFT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- Push/Pull Exh. (G) (-) 4 -- Multilevel Switching, Dimming & Occupancy

N/A N/A --

0 General Rooms/Spaces

OFFICE, CUBICLE, Open Office

Cubicle - Administrative, Data Processing, Workstation -

Extended Team, Homeless, Workstation - MICHM, Workstation - Suicide Prevention, Workstation - VOC Rehab, Workstation - Rad Tech, Workstation - Shipping / Receiving, Workstation, Administration (MSA MH; Rad, LPN), Workstation-Sleep Tech, Work Station, Call Center (MSA), Workstation-Cart Case Dispatch, Workstation-Clerical, -- -- CPT RB P -- -- -- AT 9'-0" 2 per workstation -- Multilevel Switching, Dimming & Occupancy

N/A N/A 1

0 General Rooms/Spaces

SUB-WAITING

Sub-Waiting, MRI Sub-Waiting, CT Sub-Waiting, Mammo Sub-

Waiting, Sub-Waiting - Diagnostic Patient, Sub-Waiting - Dilation Patient, CT Vestibule, Waiting, Waiting-Zone 1, Sub-Waiting-

Zone 2

-- -- CPT RB P -- -- -- AT 9'-0" 10, 17 -- -- -- -- -- - 6 M4 4 --

Multilevel Switching, Dimming & Occupancy

N/A N/A --

0 General Rooms/Spaces

VENDING Vending Machine Area RFT RB P -- -- -- AT 9'-0" -- -- -- -- -- -- 6 M4 8 -- Multilevel Switching, Dimming & Occupancy

N/A N/A 4

0 General Rooms/Spaces

TOILET/SHOWER ROOM

Toilet/Shower-Staff, Toilet/Shower-Patient, Toilet/Shower-Female Staff, Toilet/Shower-Male Staff

TOILET ROOM TOILET ROOM PT PT CT -- -- SEE FGI GWB/P 9'-0" 2, 19 3'-6" Flush Wood -- -- 11 G 2 -- Multilevel Switching, Dimming & Occupancy

N/A N/A

0 General Rooms/Spaces

CHANGING ROOM Dressing room RFT RB P -- -- 40 AT 9'-0" 3'-6" Flush Wood -- -- 11 K 75 70 60 - 4 2 Return NR NR 1 -- Multilevel Switching, Dimming & Occupancy

N/A N/A

2 Primary Care, Specialty Care, PACT

PACT TEAM WORK

SPACE

PACT Team Work Space, Team Work Area- Home Based Primary

Care -- CPT RB P -- AT 9'-0" -- _ _ _ _ _ 14 MP 6 M3 2 per workstation --

Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.

N/A 1 per workstation

2 Primary Care, Specialty Care, PACT

EXAM ROOM, AIRBORNE

INFECTION ISOLATION

Exam, Isolation, Negative Pressure

AII Room EXAMINATION WSF WSF P -- -- SEE FGI GWB:P 9'-0" 3,7 3'-6" Flush Wood -- -- 12 S 6 -- Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 1

5 Audiology and SLP

AUDIOLOGY HEARING

AID TESTING

Hearing Aid Lab, Hearing Aid

Processing, Hearing Aid Repair -- RFT RB P -- -- 40 AT 9'-0" -- 3'-0" Flush Wood _ _ 15 S _ 75 70 60 - Exh. (G) (-) 7 0 P4

Multilevel Switching, Dimming & Occupancy

N/A N/A 2

5 Audiology and SLP

AUDIOLOGY HEARING

AID FITTING

Audiology Programming / Fitting, Hearing Aid Fitting Room, Cerumen Management Room, Speech Language Pathology Assistive Technology Romm, Speech Language Pathology

Voice Treatment Room

EXAM -- CPT RB P -- -- 60 AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 Multilevel Switching, Dimming & Occupancy N/A N/A 2

5 Audiology and SLP

AUDIOMETRIC EXAM

BOOTH

Audiometric Exam Suite, Exam - Audiometric Booth, Aud: Suite -

Audiometric Exam, Hearing/Diagnostics, Booth, 1-

Person

EXAM -- Pre-Fab Pre-Fab Pre-Fab -- -- SEE EQUIP LIST Pre-Fab 8'-0" -- 3'-0"

3'-6"

Pre-Fab Pre-Fab _ _ 1 2,4 9 P1 Typically pre-packaged unit including lighting and switching

N/A L1 5

5 Audiology and SLP ELECTROPHYSIOLOGY Electrophysiology, Posturography, Vestibulography EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 P2, P3, P14

Multilevel Switching, Dimming & Occupancy

N/A N/A 3

6 Dental Service

SPECIALTY EQUIPMENT

MECHANICAL ROOM

Dental Equipment Mech. Room, Mechanical Rooms - Electrical

-- -- CS -- P -- -- 60 EXP 9'-0" 3'-6" Flush Wood -- -- 14 S Exh. (G) (-) 2 -- P3 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 1

6 Dental Service

DENTAL PROSTHETICS

LABORATORY

Laboratory, Dental Prosthetics -- WSF WSF P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 15 AG 75 70 60 20 6 2

Return Exh. (G) 45 (-) M13 7 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 5

6 Dental Service

DENTAL TREATMENT

ROOM

Dental Treatment Room (DTR), Multi-Functional (4/Hygiene), Special Needs Patient, Bariatric EXAM TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS (+) 7 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

6 Dental Service DENTAL X-RAY ROOM X-Ray Room, Panoramic /

Cephalometric (Cone Beam) CLASS 1 IMAGING ROOM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 17 AGL 8 7 -- P3

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

7 Optometry

FITTING & DISPENSING,

EYEGLASSES

Fitting & Dispensing, Eyeglasses -- RFT RB P -- -- -- AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S 6 75 70 60 - 4 2 Return 40 NR 2 Downlights and accent/display

Multilevel Switching, Dimming & Occupancy

N/A N/A 2

7 Optometry

LOW VISION EXAM/

THERAPY/ TRAINING

Low Vision Exam/ Therapy/

Training EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6

Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.

N/A 3

7 Optometry PRE-TESTING/ INTAKE Pre-Testing/ Intake EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 1 Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.

N/A 2

7 Optometry VISUAL FIELDS ROOM

Visual Fields Room, Photography Room, Ultrasound Room, Tomography Room, Imaging Room, OCT Laser

EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 7 Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.

N/A 2

8 Mental Health QUIET ROOM Quiet Room for Patients EXAM TREATMENT CPT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 1

8 Mental Health

BIOFEEDBACK

TREATMENT ROOM

Biofeedback Treatment Room EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 15 S 4 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 2

ROOM DATA MATRIX

FLOOR WALLS CEILING

IT

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING

INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

ROOM IDENTIFICATION NOTES

Functional Area

DEPARTMENT ROOM NAME ROOM NAMES (VA) FGI EQUIVALENT FOR

ASHRAE 170

FGI EQUIVALENT FOR

TABLE 1.2-5 Minimum

Sound Isolation

F lo o r

F in is h

B as e

W al l F in is h

W ai n sc o t

M at er ia l

W ai n sc o t

H ei g h t

S T

C

C ei li n g F in is h

H ei g h t

N o te s

S iz e (W id th

T yp e

M at er ia l

G la zi n g

R at in g

H ar d w ar e

G ro u p

H ar d w ar e

N o te s

In d o o r T em p er at

C o o li n g

F

In d o o r T em p er at ea ti n g

F

In d o o r R el at iv e

H u m id it y

R

H M ax

In d o o r R el at iv e

H u m id it y

R

H M in

M in im u m T o ta l A

C H

M in im u m O

A A

C H

R o o m

A ir

R et rn

G en

E xh

G S

E xh S

M ax im u m N o is e L ev el

N C

R o o m

A ir

B al an ce

V

A C

N o te s

D u p le x

R ec ep ta cl es

Q ad

R ep ta cl es

P o w er

N o te s

F ix tu re

T yp e

C o n tr o ls

L ig h ti n g

S p ec ia l

R eq u ir em en ts

L ig h ti n g

N o te s

D at a

O u tl et s (s ta n d ar d d en si ty

W A

O

IT

S ec ia l

R eq u ir em en ts

ROOM DATA MATRIX

FLOOR WALLS CEILING

IT

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING

INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

9 Specialty Care Services

PULMONARY FUNCTION

ROOM

Pulmonary Function - Analysis EXAM TREATMENT WSF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 G 6 -- Multilevel Switching, Dimming & Occupancy N/A N/A 2

9 Specialty Care Services

TREADMILL ROOM Treadmill Room EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 MS 6 -- P9 Multilevel Switching, Dimming & Occupancy N/A N/A 2

9 Specialty Care Services

EKG TESTING ROOM EKG Testing Room EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 12 S One per wall -- Multilevel Switching, Dimming & Occupancy

N/A N/A 2

9 Recreation Therapy

GROUP THERAPY

ROOM, MUSIC

Creative Arts - Group Therapy

Room - Music -- TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

9 Recreation Therapy

GROUP THERAPY

ROOM, ART

Creative Arts - Group Therapy

Room - Large -- TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

9 Recreation Therapy WEIGHT ROOM, SMALL Recreation Therapy Exercise /

Weight Room - Small -- TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 34 AG 12 --

Multilevel Switching, Dimming & Occupancy

N/A N/A --

10 PHYSICAL THERAPY

PHYSICAL THERAPY

GYM

Treatment Exercise Area (includes workstations therapists) EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 14 S 14 -- P14

Multilevel Switching, Dimming & Occupancy

N/A N/A 4

10 PHYSICAL THERAPY

Activities Daily Living (ADL)

Training

ADL Evaluation and Training Center, Toilet, Tub, Bed, Kitchen, Laundry EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 15 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A

13 Imaging Services RADIOLOGY Radiology, ES: General Purpose

Radiology Room CLASS 1 IMAGING ROOM TREATMENT WSF RB P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 LS 8 5 P3, P13

Fully dimmable, occupancy sensor

N/A L2 2

13 Imaging Services C.T. CONTROL ROOM CT Control Area, X-Ray -

Computed Tomography - Control TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 3'-0" Flush Wood -- LEAD LINED 12 LS 45 M14 6 -- P3

Multilevel Switching, Dimming & Occupancy

N/A N/A 4

13 Imaging Services C.T. EQUIPMENT ROOM CT Equipment Room, X-Ray - Computed Tomography - Indep

View Console -- WSF WSF P -- -- -- AT 9'-0" 5 6'-0" Flush Wood -- -- 45 AG 7 50 M14 7 -- P3, P13

Multilevel Switching, Dimming & Occupancy

N/A N/A 2

13 Imaging Services C.T. SCAN ROOM CT Scanning Room (Ceiling Lift), X-Ray - Computed Tomography -

Scanner CLASS 1 IMAGING ROOM TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 ALG 7 -- P3, P13

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

13 Imaging Services

MAMMOGRAPHY SCAN

ROOM

Mammo - X-ray, Mammography

Room CLASS 1 IMAGING ROOM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 12 LS 7 -- P3

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

13 Imaging Services

RADIOGRAPHIC /

FLOURO SCAN ROOM

Radiographic / Fluoroscopic (R/F)

Room CLASS 1 IMAGING ROOM TREATMENT WSF WSF P - - SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 15 AGL 7 -- P3, P13

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

13 Imaging Services

ULTRASOUND SCAN

ROOM

Ultrasound Room CLASS 1 IMAGING ROOM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- --

12 S 7 -- P3, P13

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

13 Imaging Services PACS SERVER ROOM

X-Ray - Storage - Digital Files, Viewing Room - Picture Archiving and Communication System

(PACS)

-- RFT RB P - - - AT 9'-0" 3'-0" Flush Wood -- -- 15 GK 50 4 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4

13 Imaging Services MRI CONTROL ROOM MRI Control Room, X-Ray -

Magnetic Resonance - Control, MRI Zone 3

CLASS 1 IMAGING ROOM EXAM - MRI RFT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 45 M14 6 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4

13 Imaging Services MRI EQUIPMENT ROOM MRI System Component Room, X-Ray - Magnetic Resonance -

System Component TREATMENT RFT RB P RWC 4'-0" AT 9'-0" 11 4'-0" Flush Wood -- -- 35 AG 40 50 M14 7 -- P3

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

13 Imaging Services

MRI FERROMAGNETIC

DETECTION

X-Ray - Magnetic Resonance - Ferromagnetic Detection, MRI Zone 2, MRI Viewing Room

EXAM - MRI RFT RB P -- -- SEE FGI AT 9'-0" 11, 16 4'-0" Flush Wood -- -- 15 G 75 70 60 40 12 2 Return 40 NR 1 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 1

13 Imaging Services MRI SCAN ROOM MRI Scanning, X-Ray - Magnetic

Resonance - Scanner, EXAM - MRI WSF RB P -- -- SEE FGI AT VARIES 11,13,16 4'-0" Flush Wood -- R/F Shielded 1 75 70 60 40 12 2

Return Exh. (S)

50 NR M17 2 -- P3

Multilevel Switching, Dimming & Occupancy MRI rated fixtures N/A 1

13 Imaging Services READING ROOM MRI Viewing Room, X-Ray -

Magnetic Resonance - Viewing -- CPT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 40 6 -- P3

Multilevel Switching, Dimming & Occupancy

N/A N/A 6

13 Imaging Services BONE DENSITOMETRY Bone Densitometer EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 7 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 2

14 Pathology and Laboratory Medicine

SPECIMEN COLLECTION

Blood Specimen Collection, Alcove - Specimen Collection

Point of Care (also for Substance Abuse plus Coumadin), Blood Draw Alcove, Support Area, Laboratory-Satellite, Laboratory- Venipuncture, Blood Draw

EXAM __ WSF WSF EP -- -- -- AT 9'-0" 3 -- _ _ _ _ _ 6 4

Multilevel Switching, Dimming & Occupancy Multi-level switching or manual dimming N/A 2

14 Pathology and Laboratory Medicine

SPECIMEN

ACCESSIONING,

PROCESSING &

DISTRIBUTION ROOM

Specimen Accessioning, Processing & Distribution Room

LABORATORY WORK

ROOM

-- WSF WSF EP -- -- -- GYP/EP or

AT-SP

9'-0 3, 7 3'-6" Flush w/ Narrow Vision

Wood Narrow Vision -- 15 AG One per wall, 6' spacing, one adjacent to sink One at each workstation

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted

N/A One at each workstation

15 Pharmacy Service PHARMACY Pharmacy, Pharmacy, PACT 3

(Controlled Substance) (w/3 AutoDispensing)

PHARMACY -- RF RB P -- -- -- AT 9'-0" -- 6'-0" Flush Metal - - 200 AS 7 15 P5 Multilevel Switching, Dimming & Occupancy N/A N/A 9

15 Pharmacy Service

PHARMACY

DISPENSING WINDOW

Dispense/Consult Window, Workroom, Pharmacist

PHARMACY -- RF RB P -- -- -- AT 9'-0" -- - - - - - - OPEN 12

Multilevel Switching, Dimming & Occupancy

N/A N/A 5

15 Pharmacy Service

CLEAN ROOM,

COMPOUNDING

Pharmacy - Clean Room -

Chemotherapy Compounding

-- -- RF RF P -- -- -- GWB:P 9'-0" 3 7'-0"

Single Slide Auto Sliding

Door

Aluminum/ Glass

Yes -- 850 68 68 60 20 30 2 Exh. (S) 55 (-) M12 14 -- P10 Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 5

15 Pharmacy Service IV ADMIXTURE Pharmacy - IV Admixture - Low

Volume

-- -- RF RF P -- -- -- GWB:P 9'-0" 3 7'-0"

Single Slide Auto Sliding

Door

Aluminum/ Glass

Yes -- 850 68 68 60 20 30 2 Return 55 (++) M12 14 -- P10 Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 5

15 Pharmacy Service

PRESCRIPTION

DISPENSING AREA

Prescription Dispensing Area -

OmniCell Station

-- -- RF RF P -- -- -- AT 9'-0" 3 -- -- -- -- -- - 6 8 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 2

15 Pharmacy Service

SECURE STORAGE

VAULT

Secure Storage, Vault

CLEAN WORK ROOM/

CLEAN SUPPLY

-- RFT RB P RWC 4'-0" -- GWB:P 9'-0" 3'-0" Flush Hollow Metal -- -- 1 1 -- Multilevel Switching, Dimming & Occupancy N/A N/A --

15 Pharmacy Service ANTEROOM Anteroom, Compound Sterile

Preparation

-- WSF WSF EP -- -- -- GWB:SP 9'-0" 3 7'-0"

Single Slide Auto Sliding

Door

Aluminum/ Glass

Yes -- 850 68 68 60 20 30 2 Return 55 (+) M12 2 -- Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A --

17 Business Office SECURE CASH ROOM Secure Money Handling Room -- RFT RB P -- -- -- AT 9'-0 3'-0" Flush w/ 1- Way Viewer

Steel -- -- 200 GV 4 -- Multilevel switching/dimming/occ upancy

N/A N/A 1

18 Engineering BIOMED. REPAIR SHOP Repair Shop, Biomedical Eng. -- -- RF RB P -- -- -- AT 9'-0" 3'-6" Flush Wood -- -- 35 AG Exh. (G) (-) M7 10 -- P4, P6 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 2 19 Logistics LOADING DOCK Receiving/ Shipping Dock -- -- CS RB EP -- -- -- EXP. -- 8 6'-0" Flush Wood -- -- 44 APW 7 - 60 - - Exh. (G) (+) M5 2 -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 2

19 Logistics MAIL ROOM Support: Mail Room and Dist.

Center, Mailing Room - Prosthetic Appliances

-- -- RF RB P RWC 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 15 G 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

19 Logistics

GAS CYLINDER

STORAGE

Storage - Gas Cylinders - MRI, Storage - Gas Cylinders - Interior -- -- WSF RB P RWC 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- 45 MIN 34 G

Exh. (S) (-) 1 --

Multilevel Switching, Dimming & Occupancy

N/A N/A --

19 Logistics BIO-HAZARD STORAGE Storage - Bio Hazardous Material, Storage - Hazardous Material, Infectious / Hazardous Waste

REGULATED WASTE -- WSF WSF EP RWC 4'-0" -- GWB:SP 9'-0" 3 3'-6" Flush Hollow Metal -- -- 34 G 1 -- Multilevel Switching, Dimming & Occupancy N/A N/A --

19 Logistics STORAGE WAREHOUSE Bulk Storage, General Storage, Warehouse

CLEAN

WORKROOM/CLEAN

SUPPLY

CS RB P -- -- -- Exp 10'-0" 6'-0" Flush Wood -- -- 45 AG minimum, 1 per wall, not to exceed 12' spacing -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A

19 Logistics BREAK DOWN Break Down

CLEAN

WORKROOM/CLEAN

SUPPLY

RPT RB EP -- -- -- AT 9'-0" 8 4'-0" Flush Wood -- -- 34 AG 1 -- Multilevel Switching, Dimming & Occupancy

N/A N/A

20 Police Service POLICE HOLDING ROOM Holding Room -- -- CS RB P -- -- -- GWB-PT 9'-0" 3,15 3'-6" Flush Hollow Metal Half Glass w/

Laminated Glass

18 P 0 -- Multilevel Switching, Dimming & Occupancy Tamperproof fixture design N/A --

20 Police Service OPERATIONS ROOM Operations Room RFT RB P -- -- 40 AT 9'-0" 3'-6" Flush Hollow Metal -- -- 200 APS M15 0 8 Multilevel Switching, Dimming & Occupancy

N/A N/A 4

20 Police Service SECURE STORAGE Small Arms Armory, Storage -

Secure RFT RB P -- -- -- AT 9'-0" 3'-0" Flush Hollow Metal -- -- 200 P 75 70 60 - 4 2 Return NR NR 1 -- Multilevel Switching, Dimming & Occupancy N/A N/A 1

21 VCS RETAIL AREA Retail Area EXAM - PUBLIC SPACE RFT RB P -- -- SEE FGI AT 9'-0 17 6'-0" Flush w/ Full Vision

Wood Full Vision 47 KM 7, 9 M4 One per wall, 6' spacing -- Multilevel Switching, Dimming & Occupancy Track or adjustable accent lighting for retail displays.

L5 3

23 OI&T TELECOMM.

Telecommunications Room/

Closet, IT Telecommunications Room

-- -- RFT RB P -- -- -- EXP. 12'-0" 3'-6" Flush Wood -- -- 34 AS 64 75 55 30 - - - - NR 6 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A --

23 OI&T SERVER ROOM Central Server Room -- -- RFT RB P -- -- -- EXP. 12'-0" 3'-6" Flush Wood -- -- 34 AS 72 81 60 6 M8 10 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A --

23 OI&T I.T. WORKROOM

IT Workroom, Equip.

Configuration/ Repair

-- -- RFT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG 10 -- P4, P6

Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 8

24 SPS

ANTEROOM, SOILED

TRANSITION

Anteroom, Soiled Transition/Drop-

Off

DECONTAM

ROOM

-- RES RES EP -- -- -- GYP-EP 9'-0 3, 7 3'-6" Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 10 10 Exhaust (G) 40 (-) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted

N/A 2

24 SPS

DECONTAMINATION

ROOM

Decontamination Work Room, Scope Decontamination Room

DECONTAM

ROOM

-- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6" Flush w/ Narrow Vision

Steel Narrow Vision -- 15 AG 66 72 60 30 6 6 Exhaust (G) 40 (--) One per wall -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy Gyp ceiling - lights to be sealed type/flange mounted N/A 4

24 SPS Cart Wash Cart Wash -- RES RES CT -- GYP-EP 9'-0 3, 7 3'-6" Flush w/ Narrow Vision

Steel Narrow Vision -- 15 AG 70 75 10 10 Exhaust (S) 40 (-) M18, M19 One per wall -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy Gyp ceiling - lights to be sealed type/flange mounted N/A

24 SPS

Water Treatment Storage

Room Water Treatment Storage Room -- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6" Flush Steel -- 15 AG 70 75 10 10 Exhaust (G) 40 (-) M18, M19 One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted

N/A 1

24 SPS

REPROCESSING ROOM,

SCOPE

Reprocessing Room, Scope -- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6" Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 6 6 Exhaust (G) 40 (-) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted

N/A 2

24 SPS Instrument Assembly Instrument Assembly -- WSF WSF EP -- GYP-EP 9'-0 3, 7 3'-6" Flush w/ Narrow Vision

Steel Narrow Vision -- 15 AG 66 72 60 30 4 4 Exhaust (G) 40 (++) One per wall -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy Gyp ceiling - lights to be sealed type/flange mounted N/A 4

24 SPS Sterilization Area Steam Sterilization Area, Low

Temp Sterilization Area -- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6" Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 66 75 60 30 10 10 Exhaust (G) 40 (++) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted

N/A 2

24 SPS Cooling Area Cooling Area -- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6" Flush w/ Narrow Vision

Steel Narrow Vision -- 15 AG 66 75 60 30 10 10 Exhaust (G) 40 (++) One per wall -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy Gyp ceiling - lights to be sealed type/flange mounted N/A 1

24 SPS

Equipment Room, Steam

Generator Equipment Room, Steam

Generator -- RFT RB EP -- ACT-SP 9'-0 3, 7 3'-6" Flush Steel -- 15 AG 85 10 10 Exhaust (G) 45 (-) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted

N/A --

24 SPS Clean Dispatch Clean Dispatch -- RFT RB EP -- ACT-SP 9'-0 3, 7 70 75 60 30 4 4 Exhaust (G) 40 One per wall -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy Gyp ceiling - lights to be sealed type/flange mounted N/A 1

24 SPS

STORAGE, CLEAN

SCOPE

Storage, Clean Scope CLEAN SUPPLY -- RES RES EP RWC 4'-0" -- GYP-EP 9'-0 3, 7 3'-6" Flush w/

Narrow Vision Wood Narrow Vision -- 15 AG 66 75 55 30 4 (+) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted

N/A --

Interior Finishes Notes

General Notes A. Hollow metal frames and doors to be painted.

B. Window sills to be solid surface fabrication.

C. Resilient base to be 4", unless otherwise noted.

D. Provide painted finishes only on inside of exterior walls (no wall covering).

E. Floor material transitions to occur at centerline of door, unless otherwise noted.

F. Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color.

G. Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety.

H. Coordinate height of wall protection with wall-mounted devices.

I. Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks, reception desks and lobby/waiting areas.

J. Soffit above upper cabinets to be gypsum board.

K. Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials.

L. Solid surface countertops to have sides and backsplash at walls.

Schedule Notes

1. CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling.

2. Tile base to be coved.

3. Integral coved base 6" high tightly sealed to walls.

4. If sink is present, use hard suface flooring as noted.

5. Lead lined walls and control area view window.

6. Flooring and base to match adjacent area flooring material and base.

7. Use gasketed, clip down ACT/grid system

8. Use slip-retardant finish on floor material

9. Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads. Stair nosings to be a contrasting color for safety.

10. Note that if wall saver designed chairs are used, no wall protection is required.

11. Extend all room partitions to structural deck.

12. CT above countertop on wall.

13. Ceiling height as required to acommodate equipment.

14. Cove QT base, 6" high.

15. No separate trim at top of base, use alternate method to seal to wall.

16. Ceiling suspension system should be fabricated from nonferromagnetic material.

17. Aesthetic specialty materials may be used as accents where the design and budget permits.

18. Ceiling tile to meet USDA regulations.

19. Floors to be slip-resistant and meet ANSI 326.3 for measuring dynamic coefficient of friction for hard surfaces

20. Wall base on gyp board but not needed on any exterior materials such as brick, metal, or stone walls.

21. Wall CT and ceiling to meet building code light reflectancy standards.

22. Space may be room or area within a room. Coordinate finishes with adjacent spaces.

23. Provide 3/4" painted plywood where required by Telecommunications.

AT Acoustical Ceiling Tile AT-SP Acoustical Scrubbable Ceiling Tile (with sprayed plastic finish) CPT Carpet Tile CS Concrete, Sealed CT Ceramic Tile (Wall) EP Epoxy Paint EXP Exposed Ceiling MAT Modular Carpet Walk Off Mat P Paint PT Porcelain Tile QT Quarry Tile RB Resilient Base RES Resinous Flooring and Base RF Rubber Flooring RFT Resilient Floor Tile RSF Resilient Sheet Flooring - Heterogeneous RWC Rigid Wall Covering (Wall Protection) SD Static Dissipative Tile S Solid Surface Fabrication WSF Welded Seam Sheet Flooring - Homogeneous

Finish Codes

Doors and Hardware Notes

General Notes

A.

Refer to Lease Design Narrative (LDN) Appendix for Hardware Groups and Modifiers which are added to numeric hardware group assignments to indicate a variation to the group.

B. All doors to be 7'-0" high, unless otherwise noted.

C.

Coordinate acoustical requirements for doors with required wall acoustical ratings as shown in Room Data Matrix - Interior Finishes in Appendix.

Schedule Notes

1. Hollow metal frame cased opening

2. Two door (in swing and swing out) acoustical door and frame assembly.

3. Two doors required at this room/space.

4. Narrow lite optional. Use insulated or laminated glass to meet acoustical criteria.

5. Provide STC 50 rated acoustical door.

6. No door in this room/space.

7. Equal leaf pair of doors.

8. Lead lined door and hardware.

9. Space may be a room or area within another room. Omit door if space is not a separate room.

ELECTRICAL NOTES

POWER NOTES LIGHTING NOTES

P1. Multiple receptacles above and below desk for device charging, receptacles provided with Pre-Fab system.

L1. EMI/RFI emissions to be controlled

P2. Receptacles on all walls L2. Dimmable to 5 fc

P3. Coordinate electrical connections with equipment to be installed.

Receptacles on all walls.

L3. May not have ceiling - then use industrial fixture type

P4. Plug strip at 44" above counters L4. May not have ceiling. If no ceiling, use industrial fixture type

P5. Multiple receptacles above and below desk for device charging L5. Treat like a store. Adjustable lighting, General lighting.

P6. Cord reel(s) for freestanding workbenches L6. No ceiling in these rooms. No prescription for lighting.

P7. All outlets on dedicated circuits.

P8. Cord reel(s) for freestanding workbenches

P9. Treadmill on dedicated circuit

P10. Each hood on dedicated circuit

P11. Provide receptacles per equipment plan

P12. Electrical to review redundancy requirements with OIT guidelines.

P13. Receptacle above ceiling for overhead lift P14. Recessed power quad floor box P15. L21-20R receptical above each rack P16.

MECHANICAL HVAC NOTES

M1. Intentioanlly Left Blank M2. Per ASHRAE 62 for ventilation, and FGI Guidelines for NC M3. General Open Office area M4. General Open/Public area M5. Per ASHRAE 62 for ventilation if interior enclosed space.

M6. Comply with ASHRAE 15 if Special Refrigeration Systems are used M7. If chemicals are used, provide specialized exhaust M8. Data Center M9. Transfer air to Food Prep Kitchen M10. Intentioanlly Left Blank M11. MEP Room M12. See USP-797 and -800 M13. Counter-height specialized exhaust system required M14. Provide air conditioning and ventilation per imaging manufacturer recommendations

M15. General Office Area M16. Verify specific vendor/manufacturer requirements.

M17. Non-ferrous construction M18. Provide cooling only air terminal unit to serve the manual equipment wash room.M19. Provide a dedicated wet exhaust system