FY25 Chiller Rental Questions and Answers.pdf
PDF 39 KB Posted
- Attached to
- FY25 Chiller Rental
- Solicitation number
- 283525Q-ChillerRental
About this file
This document is a Questions and Answers (Q&A) file for a Fiscal Year 2025 Chiller Rental federal contract opportunity at Hanscom Air Force Base. The Q&A provides specific technical details about the chiller rental requirements, addressing three key points: (1) the power specifications require a 480V 3PH 60Hz chiller with a 150-amp breaker, (2) only a 50-ton chiller will be accepted (no substitution with a 60-ton chiller is permitted), and (3) no site visit will be allowed prior to contract award. The document is directly linked to a solicitation for a portable chiller rental for building 1607 at Hanscom AFB, Massachusetts, with the contractor expected to provide all necessary labor, equipment, and transportation for the chiller deployment within 3 business days of contract award.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FY25 Chiller Rental Questions and Answers.docx | DOCX document | |
| 1607 location Appendix A.pdf | ||
| Combo Synopsis Solicitation Chiller.pdf | ||
| 1607 Chiller Rental Bid Schedule.xlsx | XLSX spreadsheet | |
| FINAL SOW 1607 Chiller Rental.docx | DOCX document | |
| Standard Area-Wide Wage Determination 2015-4047 Rev 29.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY25 Chiller Rental Questions and Answers
Q. It shows that the chiller needed should be 480V 3PH 60Hz. Can you tell me what the breaker size is on the power side (amps available)?
A. The breaker is 150 amps
Q. Can a 60-ton chiller be substituted for the requested 50-ton chiller?
A. The chiller must be 50-ton.
Q. Will a site visit be possible?
A. No