This document provides details on a federal solicitation for a new vessel. The U.S. Army Corps of Engineers, Philadelphia District is seeking to procure a new diesel electric hybrid vessel through solicitation number W912BU20B0014. The vessel will be used by the New York District of the U.S. Army Corps of Engineers to support its drift collection and emergency response missions. The new vessel will replace an existing one. The Army Corps of Engineers is the contracting agency managing this project.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REV ZONE DRAWN CHKD
1 - WAJ CCW
General Notes:
1) Calculations are provided for drawing water from either the high or low seachest via the main crossover, discharging to a generator raw water pump intake (all generator circuits are nominally similar).
The engine-mounted flexible impeller pumps are rated for a maximum suction restriction of 8 ft, so the cooling pumps are designed to lift from static WL to the intake. Pumps shall be interlocked to respective generator to ensure pump operates when engine is started, stop when engine is stopped.
2) The calculations indicate a Scot 58121-4 2.5x2.5x5 centrifugal pump has significant NPSHA at rating of
130 GPM at 15 feet (6.5 PSI).
3) Calculations assume frictional losses based on commercial steel pipe for both suction and discharge.
All raw water circuits are CUNI tube which typically amounts to roughly 70% of the loss of equivalent ID steel pipe, resulting in a conservative approximation of losses.
4) Calculations are also provided for a typical raw water overboard to ensure backpressure is within
Cummins' 5 PSI limit.
5) The following are enclosed:
Cooling booster pump suction pipe and fitting equivalent lengths
Suction head calculation and NPSHa
Cooling booster pump discharge pipe and fitting equivalent lengths
Discharge and total booster system head calculation
Overboard pipe and fitting equivalent lengths
Overboard friction calculation
Pump Curve - Manufacturer's Data
Seachest shell strainer plate estimation of head loss versus flowrate
Strainer - Manufacturer Data including Cv info
NO.
SIZE REV
A 1
DATE: SCALE: SHEET 1 OF 12
revised common 6" strainer and manifold & check valve and re-route of discharge per ref 1.
REVISION HISTORY
DESCRIPTION DATE
1. Suction and discharge equivalent lengths 4-May-20
ENGINE COOLING SYSTEM DIAGRAM 740-B640-01 3
DESCRIPTION DWG NO. REV.
REFERENCES
Driftmaster
DRAWN BY: CHECKED BY:
Replacement
WAJ CCW
DATE: BHGI PROJ #:
Cooling System Piping Calculations12DEC18 17711
MARINE DESIGN CENTER
NTS
APP'D BY: PROJECT NO. DWG. NO.
2801 740-B640-03
17711 Engine Cooling - Head Loss and Pump Sizing REV BY CHK DATE
Equivalent Lengths - 15" S/C & 6" and 3" CUNI Suction 1 WAJ CCW 4-May-20
PIPE PROPERTIES AND FRICTION FACTORS:
Pump CL Elevation: 2.25 ft-ABL
Pipe sizes, nominal CUNI (in): 3 6
Pipe ID (in): 3.31 6.357 15 ID CUNI Clad Nominal Draft: 9.00 ft-ABL
Pipe ID (ft): 0.276 0.530 1.250 Maximum Lift: -6.75 ft
Pipe Flow Area (ft ): 0.06 0.22 1.23 f, friction factor, pipe: Friction Factors for Clean Commercial Steel Pipe, Crane 410 Table A-25, function of Reynold's Number, pipe diameter (assumed constant as below) ft, friction factor, turbulent flow (fittings): 0.018 0.015 0.013 Pipe Friction Data for Clean Commercial Steel Pipe (Turbulent Flow), Crane 410, Table A-26
EQUIVALENT LENGTH - ENGINE COOLING PUMP SUCTION TO PUMP
PIPE
Description
ID
(in)
Length
(ft)
3" tube 3.31 2.00 L 3" PIPE: 2.0 ft
6" tube 6.36 4.25 L 6" PIPE: 4.3 ft
15" S/C 15.00 1.25 L 15" PIPE: 1.3 ft
VALVES & FITTINGS
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
3" Entrance, square edge 3.31 1 0.5 7.66 0.5 7.7
3" Gate Valve 3.31 1 8 0.144 2.21 0.144 2.2
3" Angle Stop Check 3.31 0 200 3.6 55.17 0 0.0
3" Butterfly 3.31 0 45 0.81 12.41 0 0.0
3" Tee (through flow) 3.31 0 20 0.36 5.52 0 0.0
3" Tee (branch flow) 3.31 0 60 1.08 16.55 0 0.0
3" Elbow, 90 degree 3.31 0 14 0.252 3.86 0 0.0
3" Elbow, 45 degree 3.31 0 15 0.27 4.14 0 0.0
3"-2 1/2" Reducer 3.31 0 7 0.126 1.93 0 0.0
L EQ 3" VALVES & FITTINGS: 9.9 ft
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
6" Entrance, square edge 6.36 1 0.5 14.72 0.5 14.7
6" Gate Valve 6.36 1 8 0.12 4.24 0.12 4.2
6" Angle Stop Check 6.36 0 55 0.825 29.14 0 0.0
6" Butterfly 6.36 0 45 0.675 23.84 0 0.0
6" Tee (through flow) 6.36 0 20 0.3 10.60 0 0.0
6" Tee (branch flow) 6.36 1 60 0.9 31.79 0.9 31.8
6" Elbow, 90 degree 6.36 3 14 0.21 7.42 0.63 22.2
6" Elbow, 45 degree 6.36 0 15 0.225 7.95 0 0.0
L EQ 6" VALVES & FITTINGS: 73.0 ft
Notes: 1) Leq/D and K determined from "K" Factor table, sheets 1-4, Crane 41- ppA-26 thru A-29 for valves & fittings based on turbulent flow friction factor.
2) K calculated from tabular Leq/D and ft values where applicable; K = ft(Leq/D) or directly from tabular data, where given.
3) Valve or fitting equivalent length based on pipe ID: Leq = (Leq/D)xD or Leq = KD/ft when K taken directly from tabular data.
4) Hose friction factor assumed similar to Sch 40 clean commercial steel pipe, based on available manufacturer information.
K
K
17711 Engine Cooling System - Head Loss and Pump Sizing REV BY CHK DATE
3" Pump Suction Via Seachest & 6" crossover & 6" strainer 1 WAJ CCW 4-May-20
FRICTION LOSSES:
PIPE & FITTINGS:
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 3"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 3.00 0.06 0.00 0.00 0 2.000 9.87 11.9 0
40 0.09 3.00 0.06 1.49 0.03 0.35 2.000 9.87 11.9 0.04
80 0.18 3.00 0.06 2.98 0.14 1.2 2.000 9.87 11.9 0.14
120 0.27 3.00 0.06 4.47 0.31 2.6 2.000 9.87 11.9 0.31
130 0.29 3.00 0.06 4.85 0.37 3 2.000 9.87 11.9 0.36
140 0.31 3.00 0.06 5.22 0.42 3.4 2.000 9.87 11.9 0.40
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 6"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 6.00 0.22 0.00 0.00 0 4.25 72.99 77.2 0
110 0.25 6.00 0.22 1.12 0.02 0.0843 4.25 72.99 77.2 0.07
221 0.49 6.00 0.22 2.23 0.08 0.299 4.25 72.99 77.2 0.23
331 0.74 6.00 0.22 3.35 0.17 0.64 4.25 72.99 77.2 0.49
359 0.80 6.00 0.22 3.63 0.20 0.75 4.25 72.99 77.2 0.58
386 0.86 6.00 0.22 3.91 0.24 0.85 4.25 72.99 77.2 0.66
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 15"
(GPM) (ft /sec) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 15.00 1.23 0.00 0.00 0 1.25 1.3 0
110 0.25 15.00 1.23 0.20 0.00 0.003 1.25 1.3 0.00
221 0.49 15.00 1.23 0.40 0.00 0.006 1.25 1.3 0.00
331 0.74 15.00 1.23 0.60 0.01 0.008 1.25 1.3 0.00
359 0.80 15.00 1.23 0.65 0.01 0.009 1.25 1.3 0.00
386 0.86 15.00 1.23 0.70 0.01 0.010 1.25 1.3 0.00
NPSHA
STRAINER
PL*
STRAINER*
STATIC
HEAD
TDH NPSHr
(GPM) 3" 6" 15" (ft) (ft) (ft) (ft) (ft)
0 0.00 0.00 0.00 0.000 0.00 -6.75 -6.75 39.51 24 4.25
40 0.04 0.07 0.00 0.007 0.16 -6.75 -6.47 39.24 23 4.25
80 0.14 0.23 0.00 0.028 0.65 -6.75 -5.70 38.46 20 4.25
120 0.31 0.49 0.00 0.062 1.47 -6.75 -4.41 37.18 16 4.5
130 0.36 0.58 0.00 0.073 1.73 -6.75 -4.01 36.78 15 5
140 0.40 0.66 0.00 0.085 2.00 -6.75 -3.60 36.37 14 5.75
* flow through strainer plate, 15" S/C, 6" strainer, and 6" suction assumes two main engine circuits at rated capacity, plus hybrid cooling pump at rated capacity.
NPSHa = Ha +/- Hz - Hf + Hv - Hvp
Hvp MIN = 0.122 PSIA @ 40F Water 0.282 feet
Hvp MAX = 0.507 PSI @ 80F Water 1.170 feet
Ha = 14.696 PSIA 33.93 feet at 60F
Ha = 33.93 ft
Hz = -6.75 ft (max, negative is suction head, positive is lift)
Hf = varies ft (see above)
Hv = 0.00 ft (velocity head included in MFR NPSHR, so omitted here)
Hvp = 1.170 ft (max)
NPSHa = 39.51 feet minus ∆PFRICTION
FLOW RATE
PUMP CURVETOTAL
SUCTION
HEAD
PIPE & FITTING FRICTION
∆P (ft)
39.51 39.24 38.46
37.18 36.78
36.37
4.25 4.25 4.25 4.5
5.75
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
0 20 40 60 80 100 120 140 160
ENGINE COOLING SYSTEM
NPSH - Suction Side
NPSHA NPSHr
POSITIVE HEAD AVAILABLE AT FT130 GPM = 31.8
Equivalent Lengths - 3" Pump Discharge to Generator 1 WAJ CCW 4-May-20
PIPE PROPERTIES AND FRICTION FACTORS: Pump CL Elevation: 2.25 ft-ABL
Generator H20 Pump Elevation 17.94 ft-ABL
Pipe sizes, nominal CUNI (in): 2.5 3 Maximum Static Discharge Head: 15.69 ft
Pipe ID (in): 2.709 3.31 Desired Discharge Pressure (at entrance 0 PSI
Pipe ID (ft): 0.226 0.276 to engine mounted pump) 0.00 ft
Pipe Flow Area (ft ): 0.04 0.06 Effective Static Discharge Head: 15.69 ft f, friction factor, pipe: Friction Factors for Clean Commercial Steel Pipe, Crane 410 Table A-25, function of Reynold's Number, pipe diameter (assumed constant as below) ft, friction factor, turbulent flow (fittings): 0.018 0.018 Pipe Friction Data for Clean Commercial Steel Pipe (Turbulent Flow), Crane 410, Table A-26
EQUIVALENT LENGTH - ENGINE COOLING BOOSTER PUMP DISCHARGE
Reflecting inboard generator P or S - longest pipe run
PIPE
Description
ID
(in)
Length
(ft)
2 1/2" tube 2.71 1.75 L 2 1/2" PIPE: 1.8 ft
3" tube 3.31 21.75 L 3" PIPE: 21.8 ft
VALVES & FITTINGS
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
2 1/2" Elbow, 90 degree 2.71 1 14 0.252 3.16 0.252 3.2
L EQ 2 1/2" VALVES & FITTINGS: 3.2 ft
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
3" Entrance, square edge 3.31 0 0.5 7.66 0 0.0
3" Gate Valve 3.31 0 8 0.144 2.21 0 0.0
3" Check Valve 3.31 1 100 1.8 27.58 1.8 27.6
3" Butterfly 3.31 1 45 0.81 12.41 0.81 12.4
3" Tee (through flow) 3.31 1 20 0.36 5.52 0.36 5.5
3" Tee (branch flow) 3.31 0 60 1.08 16.55 0 0.0
3" Elbow, 90 degree 3.31 5 14 0.252 3.86 1.26 19.3
3" Elbow, 45 degree 3.31 1 7 0.126 1.93 0.126 1.9
3"-2 1/2" Reducer 3.31 2 7 0.126 1.93 0.252 3.9
L EQ 3" VALVES & FITTINGS: 70.6 ft
Notes: 1) Leq/D and K determined from "K" Factor table, sheets 1-4, Crane 41- ppA-26 thru A-29 for valves & fittings based on turbulent flow friction factor.
2) K calculated from tabular Leq/D and ft values where applicable; K = ft(Leq/D) or directly from tabular data, where given.
3) Valve or fitting equivalent length based on pipe ID: Leq = (Leq/D)xD or Leq = KD/ft when K taken directly from tabular data.
4) Hose friction factor assumed similar to Sch 40 clean commercial steel pipe, based on available manufacturer information.
K
3" Pump Discharge - Generator 1 WAJ CCW 4-May-20
FRICTION LOSSES:
PIPE & FITTINGS:
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 2 1/2"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 2.5 0.04 0.00 0.00 0 1.75 3.2 4.9 0
40 0.09 2.5 0.04 2.23 0.077 0.82 1.75 3.2 4.9 0.04
80 0.18 2.5 0.04 4.45 0.308 3.3 1.75 3.2 4.9 0.16
120 0.27 2.5 0.04 6.68 0.693 7.1 1.75 3.2 4.9 0.35
130 0.29 2.5 0.04 7.24 0.814 8.22 1.75 3.2 4.9 0.40
140 0.31 2.5 0.04 7.79 0.944 9.5 1.75 3.2 4.9 0.47
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 3"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 3.00 0.06 0.00 0.00 0 21.75 70.61 92.4 0.00
40 0.09 3.00 0.06 1.49 0.03 0.35 21.75 70.61 92.4 0.32
80 0.18 3.00 0.06 2.98 0.14 1.2 21.75 70.61 92.4 1.11
120 0.27 3.00 0.06 4.47 0.31 2.6 21.75 70.61 92.4 2.40
130 0.29 3.00 0.06 4.85 0.37 3 21.75 70.61 92.4 2.77
140 0.31 3.00 0.06 5.22 0.42 3.4 21.75 70.61 92.4 3.14
STATIC
HEAD
TDH NPSHr
(GPM) 2 1/2" 3" (ft) (ft) (ft) (ft)
0 0.00 0.00 15.69 15.69 -6.75 8.94 24 4.25
40 0.04 0.32 15.69 16.05 -6.47 9.58 23 4.25
80 0.16 1.11 15.69 16.96 -5.70 11.26 20 4.25
120 0.35 2.40 15.69 18.44 -4.41 14.02 16 4.5
130 0.40 2.77 15.69 18.86 -4.01 14.85 15 5
140 0.47 3.14 15.69 19.29 -3.60 15.69 14 5.75
Maximum permissible head from crankshaft CL (18'-2" ABL) with 15 PSI cap = 41 ft (Cummins D19-MX-1) which is 59'-2" ABL or 56'-11" above booster pump CL.
PUMP CURVE
FLOW RATE
TOTAL
DISCHARGE
HEAD
TOTAL
SYSTEM
HEAD
PIPE & FITTING FRICTION
∆P (ft) TOTAL
SUCTION
HEAD
8.94 9.58
11.26
14.02 14.85
15.69
0.00
20.00
40.00
60.00
80.00
100.00
120.00
140.00
160.00
0.00
5.00
10.00
15.00
20.00
25.00
30.00
0 20 40 60 80 100 120 140 160
ENGINE COOLING SYSTEM & PUMP CURVE
Discharge to Generator
TOTAL SYSTEM HEAD TDH NPSHA NPSHr
Equivalent Lengths - 3" Pump Discharge to Generator 0 WAJ CCW 12DEC18
PIPE PROPERTIES AND FRICTION FACTORS: Engine Outlet Elevation: 19.44 ft-ABL
OVBD Elevation: 12.44 ft-ABL
Pipe sizes, nominal CUNI (in): 2.5 3 Maximum Static Discharge Head: -7.00 ft
Pipe ID (in): 2.709 3.31
Pipe ID (ft): 0.226 0.276
Pipe Flow Area (ft ): 0.04 0.06 Effective Static Discharge Head: 0.00 ft f, friction factor, pipe: Friction Factors for Clean Commercial Steel Pipe, Crane 410 Table A-25, function of Reynold's Number, pipe diameter (assumed constant as below) ft, friction factor, turbulent flow (fittings): 0.018 0.018 Pipe Friction Data for Clean Commercial Steel Pipe (Turbulent Flow), Crane 410, Table A-26
EQUIVALENT LENGTH - ENGINE MOUNTED PUMP DISCHARGE
PIPE
Description
ID
(in)
Length
(ft)
2 1/2" tube 2.71 0.00 L 2 1/2" PIPE: 0.0 ft
3" tube 3.31 7.17 L 3" PIPE: 7.2 ft
VALVES & FITTINGS
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
2 1/2" Elbow, 90 degree 2.71 1 14 0.252 3.16 0.252 3.2
1 1/2" Hydrant Valve 2.71 0 200 3.6 45.15 0 0.0
L EQ 2 1/2" VALVES & FITTINGS: 3.2 ft
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
3" Entrance, square edge 3.31 0 0.5 7.66 0 0.0
3" Gate Valve 3.31 1 8 0.144 2.21 0.144 2.2
3" Check Valve 3.31 0 100 1.8 27.58 0 0.0
3" Butterfly 3.31 0 45 0.81 12.41 0 0.0
3" Tee (through flow) 3.31 0 20 0.36 5.52 0 0.0
3" Tee (branch flow) 3.31 0 60 1.08 16.55 0 0.0
3" Elbow, 90 degree 3.31 2 14 0.252 3.86 0.504 7.7
3" Elbow, 45 degree 3.31 2 7 0.126 1.93 0.252 3.9
3"-2 1/2" Reducer 3.31 1 7 0.126 1.93 0.126 1.9
L EQ 3" VALVES & FITTINGS: 15.7 ft
Notes: 1) Leq/D and K determined from "K" Factor table, sheets 1-4, Crane 41- ppA-26 thru A-29 for valves & fittings based on turbulent flow friction factor.
2) K calculated from tabular Leq/D and ft values where applicable; K = ft(Leq/D) or directly from tabular data, where given.
3) Valve or fitting equivalent length based on pipe ID: Leq = (Leq/D)xD or Leq = KD/ft when K taken directly from tabular data.
4) Hose friction factor assumed similar to Sch 40 clean commercial steel pipe, based on available manufacturer information.
DESCRIPTION
K
3" Pump Discharge - Generator 0 WAJ CCW 12DEC18
FRICTION LOSSES:
PIPE & FITTINGS:
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 2 1/2"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 2.5 0.04 0.00 0.00 0 0 3.2 3.2 0
40 0.09 2.5 0.04 2.23 0.077 0.82 0 3.2 3.2 0.03
80 0.18 2.5 0.04 4.45 0.308 3.3 0 3.2 3.2 0.10
120 0.27 2.5 0.04 6.68 0.693 7.1 0 3.2 3.2 0.22
130 0.29 2.5 0.04 7.24 0.814 8.22 0 3.2 3.2 0.26
140 0.31 2.5 0.04 7.79 0.944 9.5 0 3.2 3.2 0.30
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 3"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 3.00 0.06 0.00 0.00 0 7.17 15.72 22.9 0.00
40 0.09 3.00 0.06 1.49 0.03 0.35 7.17 15.72 22.9 0.08
80 0.18 3.00 0.06 2.98 0.14 1.2 7.17 15.72 22.9 0.27
120 0.27 3.00 0.06 4.47 0.31 2.6 7.17 15.72 22.9 0.60
130 0.29 3.00 0.06 4.85 0.37 3 7.17 15.72 22.9 0.69
140 0.31 3.00 0.06 5.22 0.42 3.4 7.17 15.72 22.9 0.78
(per D19-MX-1 for QSK19)
STATIC
HEAD
PSI ft
(GPM) 2 1/2" 3" (ft) (ft) (% MFR LIMIT)
0 0.00 0.00 0.00 0.00 0% 5 11.54
40 0.03 0.08 0.00 0.11 1% 5 11.54
80 0.10 0.27 0.00 0.38 3% 5 11.54
120 0.22 0.60 0.00 0.82 7% 5 11.54
130 0.26 0.69 0.00 0.95 8% 5 11.54
140 0.30 0.78 0.00 1.08 9% 5 11.54
MFR LIMIT
PIPE & FITTING FRICTION
DESCRIPTION
FLOW RATE
∆P (ft) TOTAL
DISCHARGE
HEAD
TOTAL
DISCHARGE
Marine Bronze Motorpump™ 2 1/2 Suction 2 1/2 Discharge
4 Pole 50-60 Hz 1450-1750 RPM
Group - 58000 Model - 58121-4
October 24, 2017
Impeller vs Motor HP
50 60 M 50 Hz 60 Hz 50 Hz 60 Hz Imp Hz Hz inches 220 V 230 V 380 V 230 V
562 1 1/2 1 1/2 10.50 ** 7.9 2.6 4.8 525 1 1 10.25 ** 7.1 1.9 3.8 500 1 1 10.25 ** 7.1 1.9 3.8
Single phase amps for 115 V 60 Hz is double 230 V amps Three phase amps for 460 V 60 Hz is one half 230 V amps ** = Special Order - 50 Hz motor
Motor HP Single Phase Amperes - 1450-1750 RPM TEFC
Three Phase
Pump
• Heavy-duty All Bronze marine pump Style C – for sea water. Pump has a solid cast bronze alloy 954 stub shaft.
• Pump discharge and suction have groove NPT, ANSI and Navy Flange couplings are available
• Designed to dramatically reduce galvanic action
• Hardware - External - Type 300 stainless steel Internal – Type 316 stainless steel
• Enclosed impeller for solids to 5/8 inch
• Designed for continuous 24 / 7 operation.
Shaft Seal
• Rated at 125 PSI
• Buna rubber parts, ceramic stationary element, carbon rotating element, seawater stainless steel spring and metal components Motor – 4 Pole
• Totally enclosed fan cooled IP-44 motors meet marine, European, and Coast Guard ignition protected requirements.
• Sealed ball bearings
• Single phase motors must be ordered specifically for either 50 Hz or 60 Hz.
• Single-phase motors are capacitor start 50 Hz – 110-220 Volt
60 Hz – 115-230 Volt . • Three-phase – nine lead dual voltage 50 Hz – 190/380 Volt 60 Hz – 230/460 Volt
• Three-phase motors designed for dual frequency 50 Hz or 60 Hz are available.
7.43
2 1/2 GROOVELLCC
3.50
LLCC
.44 X 1.50
2 SLOTS
5.50
4.25
4.88
4.25
3.12 8.84
2 1/2 GROOVE
2.562 F21356
M
FAN COVER FOR
TEFC ONLY
1 PHASE
ONLY
Model 58121 shown with coupling and female NPT fitting on the suction and a male NPT fitting on the discharge.
Ft. Lauderdale, FL • Cedarburg, WI • e mail: marine@scotpump.com • www.scotpump.com • 58121-4
58121-4
50 Hz
1450 RPM
60 Hz
1750 RPM
http://www.scotpump.com/documents/CN-20090.pdf
17711 - Typical Seachest Strainer Plate
Shell Strainer, 1/2" PL Monel Perforated:
5/8" holes on 7/8" centers (Detail 10-A)
193 Intact holes
0.3068 sq in/hole
Intact hole Area = 59.2 sq inches
Partial hole Area = 6.8 sq inches
Annulus:
OD 15
ID 14.5
Area = 11.6 sq in
Total open area ~ 77.61 sq in 2.74 X 6" sea inlet valve
Perforated Plate Flow:
Q = 25AKh 1/2 so h = (Q/25AK) ft
A = 77.61 in total area of holes
K = 0.68 discharge coefficient (interpolated below)
Strainer Perforated Plate: t t/d K d = 0.625 in 0.15625 0.25 0.62 t = 0.5 in 0.5 0.800 0.68
1.25 2 0.82
Strainer Loss vs Flow:
h = (Q/25AK) ft
Q (GPM) h (ft)
0 0
110 0.007
221 0.028
331 0.062
359 0.073
386 0.085
SEA STRAINER
Pressure Drop Thru Eaton Model 53BTX Strainer (up to 4") Model 50 (5-8"):
Delta P = (Q/Cv) psi (clean perforated basket, fresh water)
Q = 130 GPM (fire pump at rated flow)
∆PFW ∆PSW hf STRAINER Weight
Size CV psi psi ft (lb)
2" 53BTX 42 9.58 9.82 22.66 209
2 1/2" 53BTX 65 4.00 4.10 9.46 229
3" 53BTX 110 1.40 1.43 3.30 357
4" 53BTX 175 0.55 0.57 1.31 487
5" Model 50 300 0.19 0.19 0.44 412
6" Model 50 420 0.10 0.10 0.23 583
8" Model 50 900 0.02 0.02 0.05 1800
BRZ, flanged
Pressure Drop Thru Eaton Model 72 Simplex Strainer (up to 8"):
Delta P = (Q/Cv) psi (clean perforated basket, fresh water)
Q = 130 GPM (strainer serving bilge pump)
∆PFW ∆PSW hf STRAINER Weight
Size CV psi psi ft (lb)
2" Model 72 73 3.17 3.25 7.50 49
2 1/2" Model 72 125 1.08 1.11 2.56 64
3" Model 72 180 0.52 0.53 1.23 85
4" Model 72 350 0.14 0.14 0.33 140
6" Model 72 900 0.02 0.02 0.05 270
8" Model 72 1400 0.01 0.01 0.02 550
BRZ, flanged
Strainer
General Notes:
1) Calculations are provided for drawing water from either the high or low seachest via the main crossover, discharging to the hybrid power cooling circuit, which includes the switchboard heat exchanger/cooling cabinet, main propulsion motor cooling cabinet, and tailshaft stern tube bearing lubricating water circuit.
Tailshaft water circuit requires ~10 GPM and ~ 12.25 feet of head to provide 4 PSI overpressure (2 psi over ambient sea pressure plus 2 PSI differential for steady FCV operation).
Motor cooling circuit is low in the vessel and requires 27 GPM.
Switchboard cooling cabinet requires 60 GPM and requires the highest static and dynamic head.
If the hybrid cooling pump can accommodate the SWBD cooling circuit at it's total flow of 99 GPM and and TDH of 29.4 ft, all branches off the hybrid cooling pump can be accommodated & regulated.
2) Pumps shall be interlocked to switchgear and propulsion motors to ensure pump operates when electrical system is energized and/or propulsion system is in operation.
3) The calculations indicate a Goulds 3656 2.5x3x7 centrifugal pump with 5.69" impeller has significant NPSHA at rated flow of 99 GPM at 29 feet (13 PSI).
4) Calculations assume frictional losses based on commercial steel pipe for both suction and discharge.
All raw water circuits are CUNI tube which typically amounts to roughly 70% of the loss of equivalent ID steel pipe, resulting in a conservative approximation of losses.
5) The following are enclosed:
Hybrid cooling pump suction pipe and fitting equivalent lengths
Suction head calculation and NPSHa
Hybrid cooling pump discharge to switchboard cooling cabinet pipe and fitting equivalent lengths
Discharge and total system head to switchboard cooling cabinet calculation
Pump Curve - Manufacturer's Data
Seachest shell strainer plate estimation of head loss versus flowrate - hybrid cooling only total flow through seachest
Strainer - Manufacturer Data including Cv info
NO.
SIZE REV
A 0
DATE: SCALE: SHEET 1 OF 10NTS
APP'D BY: PROJECT NO. DWG. NO.
2801 740-B640-04
DATE: BHGI PROJ #:
Seawater Service System Calculations11JAN19 17711
MARINE DESIGN CENTER
REFERENCES
Driftmaster
DRAWN BY: CHECKED BY:
Replacement
WAJ CCW
HYBRID POWER COOLING SYSTEM DIAGRAM 740-B640-02 0
DESCRIPTION DWG NO. REV.
REVISION HISTORY
DESCRIPTION DATE
17711 Engine Cooling - Head Loss and Pump Sizing REV BY CHK DATE
Equivalent Lengths - 15" S/C & 6",4", and 3" CUNI Suction 0 WAJ CCW 11JAN19
PIPE PROPERTIES AND FRICTION FACTORS:
Pump CL Elevation: 2.25 ft-ABL
Pipe sizes, nominal CUNI (in): 3 6
Pipe ID (in): 3.31 6.357 15 ID CUNI Clad Nominal Draft: 9.00 ft-ABL
Pipe ID (ft): 0.276 0.530 1.250 Maximum Lift: -6.75 ft
Pipe Flow Area (ft ): 0.06 0.22 1.23 f, friction factor, pipe: Friction Factors for Clean Commercial Steel Pipe, Crane 410 Table A-25, function of Reynold's Number, pipe diameter (assumed constant as below) ft, friction factor, turbulent flow (fittings): 0.018 0.015 0.013 Pipe Friction Data for Clean Commercial Steel Pipe (Turbulent Flow), Crane 410, Table A-26
EQUIVALENT LENGTH - HYBRID COOLING PUMP SUCTION TO PUMP
PIPE
Description
ID
(in)
Length
(ft)
3" tube 3.31 4.50 L 3" PIPE: 4.5 ft
6" tube 6.36 5.25 L 6" PIPE: 5.3 ft
15" S/C 15.00 1.25 L 15" PIPE: 1.3 ft
VALVES & FITTINGS
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
3" Entrance, square edge 3.31 1 0.5 7.66 0.5 7.7
3" Gate Valve 3.31 1 8 0.144 2.21 0.144 2.2
3" Angle Stop Check 3.31 0 200 3.6 55.17 0 0.0
3" Butterfly 3.31 0 45 0.81 12.41 0 0.0
3" Tee (through flow) 3.31 0 20 0.36 5.52 0 0.0
3" Tee (branch flow) 3.31 0 60 1.08 16.55 0 0.0
3" Elbow, 90 degree 3.31 0 14 0.252 3.86 0 0.0
3" Elbow, 45 degree 3.31 0 15 0.27 4.14 0 0.0
3"-2 1/2" Reducer 3.31 0 7 0.126 1.93 0 0.0
L EQ 3" VALVES & FITTINGS: 9.9 ft
Description
ID
(in) Qty Leq/D = K/ft
Leq 3 Total K Total Leq
6" Entrance, square edge 6.36 1 0.5 14.72 0.5 14.7
6" Gate Valve 6.36 1 8 0.12 4.24 0.12 4.2
6" Angle Stop Check 6.36 0 55 0.825 29.14 0 0.0
6" Butterfly 6.36 0 45 0.675 23.84 0 0.0
6" Tee (through flow) 6.36 0 20 0.3 10.60 0 0.0
6" Tee (branch flow) 6.36 0 60 0.9 31.79 0 0.0
6" Elbow, 90 degree 6.36 2 14 0.21 7.42 0.42 14.8
6" Elbow, 45 degree 6.36 0 15 0.225 7.95 0 0.0
L EQ 6" VALVES & FITTINGS: 33.8 ft
Notes: 1) Leq/D and K determined from "K" Factor table, sheets 1-4, Crane 41- ppA-26 thru A-29 for valves & fittings based on turbulent flow friction factor.
2) K calculated from tabular Leq/D and ft values where applicable; K = ft(Leq/D) or directly from tabular data, where given.
3) Valve or fitting equivalent length based on pipe ID: Leq = (Leq/D)xD or Leq = KD/ft when K taken directly from tabular data.
4) Hose friction factor assumed similar to Sch 40 clean commercial steel pipe, based on available manufacturer information.
K
K
DESCRIPTION
3" Pump Suction Via Seachest & 6" crossover 0 WAJ CCW 11JAN19
FRICTION LOSSES:
PIPE & FITTINGS:
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE* FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 3"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
Hybrid 0 0 3.00 0.06 0.00 0.00 0 4.500 9.87 14.4 0
Cooling 40 0.09 3.00 0.06 1.49 0.03 0.35 4.500 9.87 14.4 0.05
60 0.13 3.00 0.06 2.24 0.08 0.75 4.500 9.87 14.4 0.11
80 0.18 3.00 0.06 2.98 0.14 1.2 4.500 9.87 14.4 0.17
99 0.22 3.00 0.06 3.69 0.21 1.8 4.500 9.87 14.4 0.26
120 0.27 3.00 0.06 4.47 0.31 2.5 4.500 9.87 14.4 0.36
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE** FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 6"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
Simultaneous 0 0 6.00 0.22 0.00 0.00 0 5.25 33.79 39.0 0
Hybrid, 160 0.36 6.00 0.22 1.62 0.041 0.17 5.25 33.79 39.0 0.07
Engine 240 0.53 6.00 0.22 2.43 0.091 0.35 5.25 33.79 39.0 0.14
Cooling 320 0.71 6.00 0.22 3.23 0.163 0.61 5.25 33.79 39.0 0.24
& 396 0.88 6.00 0.22 4.00 0.249 0.92 5.25 33.79 39.0 0.36
Fire Pump 480 1.07 6.00 0.22 4.85 0.366 1.29 5.25 33.79 39.0 0.50
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE** FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 15"
(GPM) (ft /sec) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
Simultaneous 0 0 15.00 1.23 0.00 0.00 0 1.25 1.3 0
Hybrid, 160 0.36 15.00 1.23 0.29 0.001 0.004 1.25 1.3 0.0
Engine 240 0.53 15.00 1.23 0.44 0.003 0.006 1.25 1.3 0.0
Cooling 320 0.71 15.00 1.23 0.58 0.005 0.009 1.25 1.3 0.0
& 396 0.88 15.00 1.23 0.72 0.008 0.013 1.25 1.3 0.0
Fire Pump 480 1.07 15.00 1.23 0.87 0.012 0.018 1.25 1.3 0.0
* Reflects flowrate through 3" dedicated suction to hybrid cooling pump.
** Reflects rated flowrate of 1x hybrid cooling, 2x engine cooling, and 1x fire pump suction at rated conditions.
NPSHA
STRAINER PL STRAINER
STATIC
HEAD
TDH NPSHr
(GPM) (GPM)
3"
(Hybrid)
6"
(Simultaneous
Flow)
15"
(Simultaneous
Flow)
(Simultaneous
Flow, ft) (ft) (ft) (ft) (ft)
0 0 0.00 0.00 0.00 0.000 0.00 -6.75 -6.75 39.51 32.75 3
160 40 0.05 0.07 0.00 0.015 0.31 -6.75 -6.31 39.07 33.75 3.25
240 60 0.11 0.14 0.00 0.033 0.70 -6.75 -5.77 38.53 32.75 3
320 80 0.17 0.24 0.00 0.058 1.25 -6.75 -5.03 37.79 31 2.9
396 99 0.26 0.36 0.00 0.089 1.92 -6.75 -4.13 36.89 29.4 3.1
480 120 0.36 0.50 0.00 0.131 2.82 -6.75 -2.94 35.70 27.25 3.75
NPSHa = Ha +/- Hz - Hf + Hv - Hvp
Hvp MIN = 0.122 PSIA @ 40F Water 0.282 feet
Hvp MAX = 0.507 PSI @ 80F Water 1.170 feet
Ha = 14.696 PSIA 33.93 feet at 60F
Ha = 33.93 ft
Hz = -6.75 ft (max, negative is suction head, positive is lift)
Hf = varies ft (see above)
Hv = 0.00 ft (velocity head included in MFR NPSHR, so omitted here)
Hvp = 1.170 ft (max)
NPSHa = 39.51 feet minus ∆PFRICTION
FLOW
RATE
(TOTAL)
DESCRIPTION
FLOW RATE
(HYBRID CLG)
PUMP CURVETOTAL
SUCTION
HEAD
PIPE & FITTING FRICTION
39.51 39.07 38.53
37.79 36.89
35.70
3 3.25 3 2.9 3.1
3.75
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
0 20 40 60 80 100 120 140
HYBRID COOLING SYSTEM
NPSH - Suction Side
NPSHA NPSHr
POSITIVE HEAD AVAILABLE AT FT99 GPM = 33.8
Equivalent Lengths - 3" Pump Discharge to Motor Cooling Cabinet 0 WAJ CCW 11JAN19
PIPE PROPERTIES AND FRICTION FACTORS: Pump CL Elevation: 2.25 ft-ABL
OVBD Elevation 14.00 ft-ABL
Pipe sizes, nominal CUNI (in): 2 2.5 3 Switchboard Cabinet EL 20 ft-ABL
Pipe ID (in): 2.209 2.709 3.31 Static Discharge Head, MTR cooling: 11.75 ft
Pipe ID (ft): 0.184 0.226 0.276 Static Discharge Head, SWBD cooling: 17.75 ft
Pipe Flow Area (ft ): 0.03 0.04 0.06 Effective Static Discharge Head: 17.75 ft f, friction factor, pipe: Friction Factors for Clean Commercial Steel Pipe, Crane 410 Table A-25, function of Reynold's Number, pipe diameter (assumed constant as below)Friction Factors for Clean Commercial Steel Pipe, Crane 410 Table A-25, function of Reynold's Number, pipe diameter (assumed constant as below) ft, friction factor, turbulent flow (fittings): 0.019 0.018 0.018 Pipe Friction Data for Clean Commercial Steel Pipe (Turbulent Flow), Crane 410, Table A-26
EQUIVALENT LENGTH - HYBRID COOLING DISCHARGE TO SWBD COOLING CABINET
PIPE
Description
ID
(in)
Length
(ft)
SWBD Cooling 2" tube 2.21 15.50 L 2", SWBD: 15.5 ft
SWBD Cooling 3" tube 3.31 0.50 L 3", SWBD: 0.5 ft
Common 2 1/2" tube 2.50 1.50 L 2.5" COMMON: 1.5 ft
Common 3" tube 3.31 4.33 L 3" COMMON: 4.3 ft
VALVES & FITTINGS
Switchboard Cooling Circuit
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
2" Elbow, 90 degree 2.21 8 14 0.266 2.58 2.128 20.6
2" Gate Valve 2.21 2 8 0.152 1.47 0.304 2.9
2" Globe Valve 2.21 1 340 6.46 62.59 6.46 62.6
Cooling Cabinet 2.21 Estimated in Summary
2" Measurflo FCV 2.21 Estimated in Summary
L EQ 2" VALVES & FITTINGS, SWBD: 86.2 ft
Switchboard Cooling Circuit
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
3" Elbow, 90 degree 3.31 0 14 0.252 3.86 0 0.0
3" Gate Valve 3.31 0 8 0.144 2.21 0 0.0
3" Globe Valve 3.31 0 340 6.12 93.78 0 0.0
3" Tee (branch flow) 3.31 1 60 1.08 16.55 1.08 16.6
3" Elbow, 90 degree 3.31 0 14 0.252 3.86 0 0.0
3" Elbow, 45 degree 3.31 0 7 0.126 1.93 0 0.0
3"-2" Reducer 3.31 1 7 0.126 1.93 0.126 1.9
L EQ 3" VALVES & FITTINGS, SWBD: 18.5 ft
Common
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
3" Entrance, square edge 3.31 0 0.5 7.66 0 0.0
3" Gate Valve 3.31 1 8 0.144 2.21 0.144 2.2
3" Check Valve 3.31 0 100 1.8 27.58 0 0.0
3" Butterfly 3.31 0 45 0.81 12.41 0 0.0
3" Tee (through flow) 3.31 1 20 0.36 5.52 0.36 5.5
3" Tee (branch flow) 3.31 0 60 1.08 16.55 0 0.0
3" Elbow, 90 degree 3.31 1 14 0.252 3.86 0.252 3.9
3" Elbow, 45 degree 3.31 0 7 0.126 1.93 0 0.0
3"-2 1/2" Reducer 3.31 1 7 0.126 1.93 0.126 1.9
L EQ 3" VALVES & FITTINGS: 13.5 ft
Notes: 1) Leq/D and K determined from "K" Factor table, sheets 1-4, Crane 41- ppA-26 thru A-29 for valves & fittings based on turbulent flow friction factor.
2) K calculated from tabular Leq/D and ft values where applicable; K = ft(Leq/D) or directly from tabular data, where given.
3) Valve or fitting equivalent length based on pipe ID: Leq = (Leq/D)xD or Leq = KD/ft when K taken directly from tabular data.
4) Hose friction factor assumed similar to Sch 40 clean commercial steel pipe, based on available manufacturer information.
K
DESCRIPTION
K
K
3" Pump Discharge - Motor Cooling Circuit 0 WAJ CCW 11JAN19
FRICTION LOSSES:
PIPE & FITTINGS:
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
SWBD FLOW RATE* FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 2"
Cooling (GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 2.0 0.03 0.00 0.00 0 15.50 86.15 101.7 0
24 0.05 2.0 0.03 2.01 0.06 1 15.50 86.15 101.7 1.02
36 0.08 2.0 0.03 3.01 0.14 2 15.50 86.15 101.7 2.03
48 0.11 2.0 0.03 4.02 0.25 3.4 15.50 86.15 101.7 3.46
60 0.13 2.0 0.03 5.02 0.39 5.1 15.50 86.15 101.7 5.21
72 0.16 2.0 0.03 6.03 0.56 7.2 15.50 86.15 101.7 7.32
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
SWBD FLOW RATE* FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 3"
Cooling (GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 3.0 0.06 0.00 0.00 0 0.50 18.48 19.0 0
24 0.05 3.0 0.06 0.89 0.01 0.13 0.50 18.48 19.0 0.02
36 0.08 3.0 0.06 1.34 0.03 0.28 0.50 18.48 19.0 0.05
48 0.11 3.0 0.06 1.79 0.05 0.5 0.50 18.48 19.0 0.09
60 0.13 3.0 0.06 2.24 0.08 0.72 0.50 18.48 19.0 0.14
72 0.16 3.0 0.06 2.68 0.11 0.99 0.50 18.48 19.0 0.19
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
Common
FLOW
RATE** FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 2 1/2"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 2.50 0.04 0.00 0.00 0 1.500 1.5 0.00
40 0.09 2.50 0.04 2.23 0.077 0.9 1.500 1.5 0.01
60 0.13 2.50 0.04 3.34 0.173 1.94 1.500 1.5 0.03
80 0.18 2.50 0.04 4.45 0.308 3.29 1.500 1.5 0.05
99 0.22 2.50 0.04 5.51 0.472 4.9 1.500 1.5 0.07
120 0.27 2.50 0.04 6.68 0.693 7.1 1.500 1.5 0.11
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
Common
FLOW
RATE** FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 3"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 3.00 0.06 0.00 0.00 0 4.333 13.52 17.8 0.00
40 0.09 3.00 0.06 1.49 0.035 0.347 4.333 13.52 17.8 0.06
60 0.13 3.00 0.06 2.24 0.078 0.71 4.333 13.52 17.8 0.13
80 0.18 3.00 0.06 2.98 0.138 1.2 4.333 13.52 17.8 0.21
99 0.22 3.00 0.06 3.69 0.212 1.8 4.333 13.52 17.8 0.32
120 0.27 3.00 0.06 4.47 0.311 2.5 4.333 13.52 17.8 0.45
* Flowrate through 2" branch to switchboard cooling cabinet is limited by the flow control valve to 60 GPM max. Similarly, FCVs will regulate propulsion motor cooling cabinet circuit and tailshaft lubricating circuit.
** Flowrate through 2 1/2" pump discharge and subsequent 3" common main reflects all hybrid cooling system flow and associated pressure drop.
STATIC
HEAD
TDH NPSHr
SWBD SWBD Common ∆P cabinet ∆P FCV SWBD
(GPM) (GPM) 2" 3" 3" (est) (est) (ft) (ft) (ft) (ft)
0 0 0.00 0.00 0.00 0.00 0.00 17.75 17.75 -6.75 11.00 32.75 3
40 24 1.02 0.02 0.06 0.69 0.92 17.75 20.47 -6.31 14.16 33.75 3.25
60 36 2.03 0.05 0.13 1.56 2.08 17.75 23.60 -5.77 17.83 32.75 3
80 48 3.46 0.09 0.21 2.78 3.69 17.75 27.98 -5.03 22.95 31 2.9
99 60 5.21 0.14 0.32 4.34 5.77 17.75 33.53 -4.13 29.40 29.4 3.1
120 72 7.32 0.19 0.45 6.25 8.31 17.75 40.26 -2.94 37.32 27.25 3.75
∆P cabinet and FCV are estimated at 60 GPM flow and interpolated at square of volumetric flow for other flowrates.
DESCRIPTION
FLOW RATE
(SWBD CLG)
MAX
DISCHARGE
HEAD
∆P (ft) TOTAL
SUCTION
HEAD
PUMP CURVETOTAL
SYSTEM
HEAD
FLOW
RATE
(TOTAL)
11.00
14.16
17.83
22.95
29.40
32.75
33.75
32.75
29.4
27.25
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
0 10 20 30 40 50 60 70 80
HYBRID COOLING SYSTEM & PUMP CURVE
Inspecting SWBD Cooling CKT
TOTAL SYSTEM HEAD TDH
(S W
B D co o lin g c a b in e t o n ly
4BF2F9E0
Project no.
Project
Customer Contact Phone number Email
6/26/2018Date
Head
Shaft power P2
Efficiency
NPSH-values
60%
60%
64% 66% 68% 70%
Ø 7 1/16
71.6% Eff.
71.6%
71.4%
71.1%
70%
69.4%
67.9% 66.5%
Ø 4 1/16 64%
Ø 5 11/16
70.8% 29.4 ft
1.03 hp
70.8 %
3.08 ft
98.5 US g.p.m.
Ø 7 1/16 (P2)
Ø 4 1/16 (P2)
Ø 5 11/16 (P2)
29.4 ft
1.03 hp
70.8 %
3.08 ft
98.5 US g.p.m.
Ø 7 1/16 Ø 4 1/16
Ø 5 11/16
29.4 ft
1.03 hp
70.8 %
3.08 ft
98.5 US g.p.m.
Ø 7 1/16
Ø 4 1/16
Ø 5 11/16
29.4 ft
1.03 hp
70.8 %
3.08 ft
98.5 US g.p.m.
[ft]
0.0
0.4
0.8
1.2
1.6
2.0
2.4
[hp]
0.0
1.0
2.0
3.0
4.0
5.0
[ft]
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 [US g.p.m.]
Power datas referced to:
Sea water [100%] ; 80°F; 62.2lb/ft³; 9.18E-6ft²/s
Operating Data Specification Flow Head
Hydraulic data (duty point)
Flow Head
30 f t 100 US g.p.m.
98.5 US g.p.m.
29.4 f t
Impeller R Frequency Speed
Impeller design
1800 rpm
511/16"
10 f tStatic head
Perf ormance according to ISO 9906 - Annex A
Hz
Te nd er H yd ra ul ic
Hydraulic Data
5/8" holes on 7/8" centers (Detail 10-A)
193 Intact holes
0.3068 sq in/hole
Intact hole Area = 59.2 sq inches
Partial hole Area = 6.8 sq inches
Annulus:
OD 15
ID 14.5
Area = 11.6 sq in
Total open area ~ 77.61 sq in 2.74 X 6" sea inlet valve
Perforated Plate Flow:
Q = 25AKh 1/2 so h = (Q/25AK) ft
A = 77.61 in total area of holes
K = 0.68 discharge coefficient (interpolated below)
Strainer Perforated Plate: t t/d K d = 0.625 in 0.15625 0.25 0.62 t = 0.5 in 0.5 0.800 0.68
1.25 2 0.82
Strainer Loss vs Flow:
h = (Q/25AK) ft
Hybrid Cooling Only All Systems Flow thru S/C
Q (GPM) h (ft) Q (GPM) h (ft)
0 0 0 0
40 0.001 160 0.015
60 0.002 240 0.033
80 0.004 320 0.058
99 0.006 396 0.089
120 0.008 480 0.131 (469 is total through seachest up to first branch.)
SEA STRAINER 9
psi (clean perforated basket, fresh water)
Q = 99 GPM (fire pump at rated flow)
∆PFW ∆PSW hf STRAINER Weight
Size CV psi psi ft (lb)
2" 53BTX 42 5.56 5.70 13.14 209
2 1/2" 53BTX 65 2.32 2.38 5.49 229
3" 53BTX 110 0.81 0.83 1.92 357
4" 53BTX 175 0.32 0.33 0.76 487
5" Model 50 300 0.11 0.11 0.26 412
6" Model 50 420 0.06 0.06 0.13 583
8" Model 50 900 0.01 0.01 0.03 1800
BRZ, flanged
Pressure Drop Thru Eaton Model 72 Simplex Strainer (up to 8"):
Delta P = (Q/Cv) psi (clean perforated basket, fresh water)
Q = 99 GPM (strainer serving bilge pump)
∆PFW ∆PSW hf STRAINER Weight
Size CV psi psi ft (lb)
2" Model 72 73 1.84 1.89 4.35 49
2 1/2" Model 72 125 0.63 0.64 1.48 64
3" Model 72 180 0.30 0.31 0.72 85
4" Model 72 350 0.08 0.08 0.19 140
6" Model 72 900 0.01 0.01 0.03 270
8" Model 72 1400 0.01 0.01 0.01 550
BRZ, flanged
Strainer
General Notes:
1) Calculations are provided for the exhaust routing of ref 1 for the outboard-most generators P & S, which have the longest run. The port inboard engine has the shortest overall run but incorporates two 8" 90 degree elbows. For conservatism, the calculations assume two 8" elbows in the pipe run as opposed to one 8" and one 10" as provided on the outboard-most exhaust runs.
2) The calculations indicate the silencer and routing as indicated on reference 1 develop less than 50% of the manufacturer's backpressure limit at rated conditions, using conservative assumptions. The silencer contributes 0.77 in Hg to overall backpressure, also within recommended limit of 1 in Hg, and exhaust velocity is 70% of the recommended 10,000 FPM limit.
3) Calculations reflect the following manufacturer data (see Ref 2 & 3):
Make: Cummins Silencer: Nelson 49582U, Critical Grade
Model: QSK-19 Max Exhaust Velocity: ft/min
HP: 800 Inlet Diameter: in
RPM: 1800 Inlet Area: in
Displacement: 1150 in ft
Exhaust Gas Velocity: ft/min
Exhaust Outlet: 6 in Pressure Drop Across Silencer: (in water, per MFR data)
Exhaust Flow: 4001 CFM (" Hg)
Exhaust Temp: 860 deg F (turbine outlet) (PSI)
Specific Weight of gas: 0.030 lb/ft
(39.6/(T+460))
Max allowable backpressure, ∆P MAX: 3 in Hg
1.5 PSI
4) The following are enclosed:
Typical OTBD Exhaust pipe and fitting equivalent lengths
Typical OTBD Exhaust backpressure calculation
Silencer data
NO.
SIZE REV
A 0
DATE: SCALE: SHEET 1 OF 5
REVISION HISTORY
DESCRIPTION DATE
INSTALLATION DIAGRAM 18-016_QSK19DM_HCM634G 14-Mar-17
0.38
10000
82.52
0.5730
10.25
OK
10.5
0.77
EXHAUST SYSTEM 740-B650-01 0
DESCRIPTION DWG NO. REV.
17711
MARINE DESIGN CENTER
REFERENCES
Driftmaster
DRAWN BY: CHECKED BY:
Replacement
WAJ CCW
NTS
PROP'N MARINE ENGINE PERF DATA D19-MX-1/M4714 22-Aug-16
APP'D BY: PROJECT NO. DWG. NO.
2801 740-B650-02
DATE: BHGI PROJ #:
Exhaust System Backpressure Calculation13DEC18
17711 Exhaust System Backpressure REV BY CHK DATE
Equivalent Lengths - 6", 8" & 10" Pipe and Silencer 0 WAJ CCW 13DEC18
PIPE PROPERTIES AND FRICTION FACTORS:
Pipe sizes (in): 6 SCH 40 8 SCH 20 10 SCH 20
Pipe ID (in): 6.065 8.125 10.25
Pipe ID (ft): 0.505 0.677 0.854
Pipe Flow Area (ft ): 0.20 0.36 0.57 f, friction factor, pipe: Friction Factors for Clean Commercial Steel Pipe, Crane 410 Table A-25, function of Reynold's Number, pipe diameter (assumed constant as below) ft, friction factor, turbulent flow (fittings): 0.015 0.014 0.014 Pipe Friction Data for Clean Commercial Steel Pipe (Turbulent Flow), Crane 410, Table A-26
EQUIVALENT LENGTH - OUTBOARD-MOST GENERATOR EXHAUST PIPING P/S
PIPE
Description
ID
(in)
Length
(ft)
6" Pipe 6.07 0.00 L 6" PIPE: 0.0 ft
8" Pipe 8.13 0.00 L 8" PIPE: 0.0 ft
10" Pipe 10.25 8.78 L 10" PIPE: 8.8 ft
VALVES & FITTINGS
Description
ID
(in) Qty Leq/D = K/ft
Leq 3 Total K Total Leq
6" Exp Joint - Lined 6.07 1 4 0.06 2.02 0.06 2.0
8"-6" Reducer 6.07 1 7 0.105 3.54 0.105 3.5
L EQ 6" FITTINGS: 5.6 ft
Description
ID
(in) Qty Leq/D = K/ft
Leq 3 Total K Total Leq
8" Elbow, 90 degree 8.13 2 14 0.196 9.48 0.392 19.0
10"-8" Reducer 8.13 1 7 0.105 4.74 0.105 4.7
L EQ 8" FITTINGS: 23.7 ft
Description
ID
(in) Qty Leq/D = K/ft
Leq 3 Total K Total Leq
10" Elbow, 90 degree 10.25 1 14 0.196 11.96 0.196 12.0
10" Elbow, 45 degree 10.25 2 7 0.098 5.98 0.196 12.0
10" Exp Joint - Lined 10.25 1 4 0.056 3.42 0.056 3.4
L EQ 10" FITTINGS: 27.3 ft
Notes: 1) Leq/D and K determined from "K" Factor table, sheets 1-4, Crane 41- ppA-26 thru A-29 for valves & fittings based on turbulent flow friction factor.
2) K calculated from tabular Leq/D and ft values where applicable; K = ft(Leq/D) or directly from tabular data, where given.
3) Valve or fitting equivalent length based on pipe ID: Leq = (Leq/D)xD or Leq = KD/ft when K taken directly from tabular data.
4) Hose friction factor assumed similar to Sch 40 clean commercial steel pipe, based on available manufacturer information.
DESCRIPTION
K
K
3" Pump Suction Via Seachest & 6" crossover 0 WAJ CCW 13DEC18
FRICTION LOSSES:
PIPE & FITTINGS:
LEQUIV LEQUIV LEQUIV ∆∆∆∆P *
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g PIPE FITTINGS TOTAL 6"
CFM (ft /sec) (ID, in) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (in H2O)
0 0.00 6.07 0.20 0.00 0.00 0.000 5.56 5.6 0.00
800 13.34 6.07 0.20 66.47 68.67 0.000 5.56 5.6 0.07
1600 26.67 6.07 0.20 132.95 274.69 0.000 5.56 5.6 0.28
2401 40.01 6.07 0.20 199.42 618.05 0.000 5.56 5.6 0.63
3201 53.35 6.07 0.20 265.90 1098.76 0.000 5.56 5.6 1.11
4001 66.68 6.07 0.20 332.37 1716.81 0.000 5.56 5.6 1.74
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g PIPE FITTINGS TOTAL 8"
CFM (ft /sec) (ID, in) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (in H2O)
0 0.00 8.13 0.36 0.00 0.00 0.00 23.70 23.7 0.00
800 13.34 8.13 0.36 37.04 21.32 0.00 23.70 23.7 0.07
1600 26.67 8.13 0.36 74.08 85.28 0.00 23.70 23.7 0.27
2401 40.01 8.13 0.36 111.12 191.89 0.00 23.70 23.7 0.62
3201 53.35 8.13 0.36 148.16 341.14 0.00 23.70 23.7 1.10
4001 66.68 8.13 0.36 185.20 533.03 0.00 23.70 23.7 1.72
LEQUIV LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g PIPE FITTINGS TOTAL 10"
CFM (ft /sec) (ID, in) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (in H2O)
0 0.00 10.25 0.57 0.00 0.00 8.78 27.33 36.1 0.00
800 13.34 10.25 0.57 23.27 8.42 8.78 27.33 36.1 0.03
1600 26.67 10.25 0.57 46.55 33.67 8.78 27.33 36.1 0.13
2401 40.01 10.25 0.57 69.82 75.76 8.78 27.33 36.1 0.30
3201 53.35 10.25 0.57 93.10 134.69 8.78 27.33 36.1 0.52
4001 66.68 10.25 0.57 116.37 210.45 8.78 27.33 36.1 0.82
SILENCER
CFM 6" 8" 10" (in H2O) (in H2O) (in Hg) (psi) (% MFR limit)
0 0.00 0.00 0.00 0.000 0.00 0.00 0.00 0%
800 0.07 0.07 0.03 1.000 1.17 0.09 0.04 3%
1600 0.28 0.27 0.13 2.750 3.43 0.25 0.12 8%
2401 0.63 0.62 0.30 4.750 6.29 0.46 0.23 15%
3201 1.11 1.10 0.52 7.250 9.99 0.74 0.36 25%
4001 1.74 1.72 0.82 10.500 14.78 1.09 0.53 36%
* Note: Pressure drop for compressible flow of exhaust gas ∆P ~ LSQ /187D
(in H2O with L in ft, S in lb/ft
,Q in ft
/min, and D in inches ).
TOTAL BACK PRESSURE
DESCRIPTION
FLOW RATE
Ro ta ry P os iti ve
Bl ow er S ile nc er s
2.18
En gi ne E xh au st Si le nc er s
2.18
Se e pa ge
.1 f or o rd er in g in fo rm at io n w w w .u ni ve rs al si le nc er
.c om
Spark Arresting Silencer Performance Engine Exhaust Silencers
31.5 63 125 250 500
Octave Band Center Frequency, Hz
Insertion Loss, dB
1K 2K 4K 8K
Critical
Residential
Typical Attenuation Curve
0 1 2 3 4 5 6 7 8 9 10
Exhaust Gas Velocity in Thousands (ft./min.)
Estim ated Pressure Drop
(Inches of W ater)
Pressure Drop
31.5 63 125 250 500
Octave Band Center Frequency, Hz
Insertion Loss, dB
1K 2K 4K 8K
Critical
0 1 2 3 4 5 6 7 8 9 10
Exhaust Gas Velocity in Thousands (ft./min.)
Estim ated Pressure Drop
(Inches of W ater)
31.5 63 125 250 500
Octave Band Center Frequency, Hz
Insertion Loss, dB
1K 2K 4K 8K
Residential
0 1 2 3 4 5 6 7 8 9 10
Exhaust Gas Velocity in Thousands (ft./min.)
Estim ated Pressure Drop
(Inches of W ater)
Residential
Critical
Industrial
Note: When figuring pressure drop for side or middle side inlet, add 4" H2O to back pressure shown on curve.
Note: When determining back pressure, velocity should not exceed 10,000 ft/min regardless of allowable back pressure. Specifications are subject to change without notice.
Ro ta ry P os iti ve
Bl ow er S ile nc er s
2.19
En gi ne E xh au st Si le nc er s
2.19
Se e pa ge
.1 f or o rd er in g in fo rm at io n w w w .u ni ve rs al si le nc er
.c om
49325U 49330U 49335U 49340U 49350U 49360U 49380U 49382U 49384U 49386U 49388U 49399U 49321U 49322U 49415U 49420U 49425U 49430U 49435U 49440U 49450U 49460U 49480U 49482U 49484U 49486U 49540U 49550U 49560U 49580U 49582U 49584U
2.5 3.0 3.5 4.0 5.0 6.0 8.0
10.0 12.0 14.0 16.0 18.0 20.0 22.0 1.5 2.0 2.5 3.0 3.5 4.0 5.0 6.0 8.0
10.0 12.0 14.0 4.0 5.0 6.0 8.0
10.0 12.0
9.00 9.00 9.00
10.12 12.12 14.12 18.12 22.12 26.12 36.21 36.18 42.12 48.12 54.12 7.00 8.12 9.63
10.12 11.12 12.12 14.12 16.12 18.12 22.12 26.12 36.21 14.12 16.12 18.12 22.12 26.12 30.18
21.8 24.3 23.8 23.7 28.3 31.5 48.3 52.6 67.7 72.2 80.6 92.2
103.9 115.5 16.4 20.7 25.0 31.2 33.0 35.3 41.5 45.5 62.3 74.6 86.7 90.2 41.5 47.0 52.7 66.6 72.1 86.8
25.0 29.5 29.1 31.5 35.5 38.0 56.0 60.0 74.0 77.0 90.0
100.0 109.9 123.1 20.0 25.0 30.0 36.0 38.0 42.0 48.0 55.0 72.0 82.0 93.0 95.0 48.0 54.0 62.0 76.0 86.1 92.0
1.9 2.7 2.6 3.9 3.6 2.7 3.8 3.2 3.1 2.4 4.7 3.9 3.0 3.8 1.6 2.1 2.2 2.2 2.9 3.1 3.3 4.5 4.9 3.7 3.1 2.0 3.2 3.8 5.1 3.0 3.4 2.9
1.9 2.7 2.6 3.9 3.6 2.7 3.8 3.2 3.1 2.4 4.7 3.9 3.0 3.8 1.6 2.1 2.2 2.2 2.9 3.1 3.3 4.5 4.9 3.7 3.1 2.0 3.2 3.8 5.1 3.0 3.4 2.9
Part Number
A Nominal
Inlet Diameter
B Outside
Body Diameter
C Body
Length
D Overall Length
E Inlet
Length
F Outlet Length
Male pipe thread connections through 3.5", 4", and larger are 125/150# ASA drilled flanges. Drains are standard on all silencers with a 9" body diameter or larger. Side-in end-out configuration is designed for side inlet flow only.
Unit cannot be run backward. All dimensions are in inches.
In du st ria l Re si de nt ia l Cr iti ca l Standard Spark Arresting Exhaust Silencers provide high efficiency spark arresting and exceptional sound attenuation where fire hazards must be eliminated and noise must be minimized. Three attenuation grades (industrial, residential, and critical) are available with spark arresting efficiencies
Type 1 Spark Arresting Exhaust Silencers exceeding 95%. Heavy gauge material and fully welded construction provide maximum strength and longer service life in these units. Applications include stationary and portable gen sets, oil field equipment, propulsion engines on ships, and gas compression equipment.
End-In, End-Out Design
General Notes:
1) Calculations are provided for drawing bilge water from the forepeak, the most restrictive suction branch, discharging through the bilge pump discharge circuit.
2) The calculations indicate Flowmax 8DS with impeller trim of 4.47 will provide positive NPSHA and flow for the most severe suction condition. Cavitation inception will be less likely when drawing from all remaining bilge branch suctions.
3) Bilge main, branch, and pump sizing calculations per 46CFR 56.50-50 and -55 are provided in ref 1.
4) The following are enclosed:
Forepeak suction pipe and fitting equivalent lengths
Suction head calculation and NPSHa
Bilge pump discharge pipe and fitting equivalent lengths
Discharge and total system head calculation for suction from forepeak
Pump Curve - Manufacturer's Data
Rose Box estimation of loss coefficient and head loss versus flowrate
Strainer - Manufacturer Data including Cv info
NO.
SIZE REV
A 0
DATE: SCALE: SHEET 1 OF 11
REVISION HISTORY
DESCRIPTION DATE
BILGE SYSTEM DIAGRAM 740-B660-01 0
DESCRIPTION DWG NO. REV.
REFERENCES
Driftmaster
DRAWN BY: CHECKED BY:
Replacement
WAJ CCW
DATE: BHGI PROJ #:
Bilge System Piping Calculations07DEC18 17711
MARINE DESIGN CENTER
NTS
APP'D BY: PROJECT NO. DWG. NO.
2801 740-B660-02
17711 Bilge System - Head Loss and Pump Sizing REV BY CHK DATE
Equivalent Lengths - 2" Forepeak Suction thru 4" bilge manifold 0 WAJ CCW 07DEC18
PIPE PROPERTIES AND FRICTION FACTORS:
Pump CL Elevation: 2.00 ft-ABL
Pipe sizes, nominal SCH 80(in): 2 2.5 3 4 Forepeak Suction Elevation: 2.83 ft-ABL
Pipe ID (in): 1.939 2.323 2.9 3.826 Bilge Water Level 1 ft
Pipe ID (ft): 0.162 0.194 0.242 0.319 Maximum Lift: -1.83 ft
Pipe Flow Area (ft ): 0.02 0.03 0.05 0.08 f, friction factor, pipe: Friction Factors for Clean Commercial Steel Pipe, Crane 410 Table A-25, function of Reynold's Number, pipe diameter (assumed constant as below) ft, friction factor, turbulent flow (fittings): 0.019 0.018 0.018 0.017 Pipe Friction Data for Clean Commercial Steel Pipe (Turbulent Flow), Crane 410, Table A-26
EQUIVALENT LENGTH - FOREPEAK SUCTION TO PUMP
PIPE
Description
ID
(in)
Length
(ft)
2" pipe 1.94 70.00 L 2" PIPE: 70.0 ft
2 1/2" pipe 2.32 1.00 L 2 1/2" PIPE: 1.0 ft
3" pipe 2.90 2.00 L 3" PIPE: 2.0 ft
4" pipe 3.83 4.00 L 4" PIPE: 4.0 ft
VALVES & FITTINGS
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
2" Entrance, square edge 1.94 1 0.5 4.25 0.5 4.3
2" Gate Valve 1.94 1 8 0.152 1.29 0.152 1.3
2" Angle Stop Check 1.94 1 200 3.8 32.32 3.8 32.3
2" Butterfly 1.94 0 45 0.855 7.27 0 0.0
2" Tee (through flow) 1.94 1 20 0.38 3.23 0.38 3.2
2" Tee (branch flow) 1.94 0 60 1.14 9.70 0 0.0
2" Elbow, 90 degree 1.94 2 30 0.57 4.85 1.14 9.7
2" Elbow, 45 degree 1.94 1 16 0.304 2.59 0.304 2.6
2" Sudden Enlargement 1.94 1 13 0.247 2.10 0.247 2.1
L EQ 2" VALVES & FITTINGS: 55.5 ft
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
2 1/2" Butterfly 2.32 1 45 0.81 8.71 0.81 8.7
2 1/2"-2" Reducer 2.32 1 7 0.133 1.36 0.133 1.4
L EQ 2 1/2" VALVES & FITTINGS: 10.1 ft
Description
ID
(in) Qty Leq/D = K/ft
Leq
3 Total K Total Leq
3" Entrance, square edge 2.90 1 0.5 6.36 0.5 6.4
3" Gate Valve 2.90 0 8 0.152 1.93 0 0.0
3" Angle Stop Check 2.90 0 55 1.045 13.29 0 0.0
3" Butterfly 2.90 1 45 0.855 10.88 0.855 10.9
3" Tee (through flow) 2.90 0 20 0.38 4.83 0 0.0
3" Tee (branch flow) 2.90 0 60 1.14 14.50 0 0.0
3" Elbow, 90 degree 2.90 2 14 0.266 3.38 0.532 6.8
3" Elbow, 45 degree 2.90 0 7 0.133 1.69 0 0.0
3-2 1/2" Reducer 2.90 1 7 0.133 1.69 0.133 1.7
L EQ 3" VALVES & FITTINGS: 25.7 ft
Notes: 1) Leq/D and K determined from "K" Factor table, sheets 1-4, Crane 41- ppA-26 thru A-29 for valves & fittings based on turbulent flow friction factor.
2) K calculated from tabular Leq/D and ft values where applicable; K = ft(Leq/D) or directly from tabular data, where given.
3) Valve or fitting equivalent length based on pipe ID: Leq = (Leq/D)xD or Leq = KD/ft when K taken directly from tabular data.
4) Hose friction factor assumed similar to Sch 40 clean commercial steel pipe, based on available manufacturer information.
K
K
K
DESCRIPTION
2" Forepeak Suction thru 4" bilge manifold 0 WAJ CCW 07DEC18
FRICTION LOSSES:
PIPE & FITTINGS:
IIIB-4 L LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 2"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 2 0.02 0.00 0.00 0 70 55.5 125.5 0
20 0.04 2 0.02 2.17 0.07 1.03 70 55.5 125.5 1.29
40 0.09 2 0.02 4.35 0.29 3.85 70 55.5 125.5 4.83
60 0.13 2 0.02 6.52 0.66 8.45 70 55.5 125.5 10.60
80 0.18 2 0.02 8.69 1.17 14.5 70 55.5 125.5 18.19
100 0.22 2 0.02 10.87 1.83 22.3 70 55.5 125.5 27.93
L LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 2 1/2"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 2.50 0.03 0.00 0.00 0 1 10.07 11.1 0
20 0.04 2.50 0.03 1.51 0.04 0.5 1 10.07 11.1 0.06
40 0.09 2.50 0.03 3.03 0.14 1.6 1 10.07 11.1 0.18
60 0.13 2.50 0.03 4.54 0.32 3.5 1 10.07 11.1 0.39
80 0.18 2.50 0.03 6.06 0.57 5.9 1 10.07 11.1 0.65
100 0.22 2.50 0.03 7.57 0.89 9 1 10.07 11.1 1.00
L LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 3"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 3.00 0.05 0.00 0.00 0 2 25.69 27.7 0
20 0.04 3.00 0.05 0.97 0.01 0.17 2 25.69 27.7 0.05
40 0.09 3.00 0.05 1.94 0.06 0.55 2 25.69 27.7 0.15
60 0.13 3.00 0.05 2.91 0.13 1.1 2 25.69 27.7 0.30
80 0.18 3.00 0.05 3.89 0.23 1.96 2 25.69 27.7 0.54
100 0.22 3.00 0.05 4.86 0.37 3 2 25.69 27.7 0.83
L LEQUIV LEQUIV ∆∆∆∆P
FLOW RATE FLOW RATE SIZE AREA VELOCITY V
/2g HF/100 PIPE FITTINGS TOTAL 4"
(GPM) (ft /sec) (NPS) (ft
) (ft/sec) (ft) (ft) (ft) (ft) (ft) (ft)
0 0 4.00 0.08 0.00 0.00 0 4 4.0 0
20 0.04 4.00 0.08 0.56 0.00 0.3 4 4.0 0.01
40 0.09 4.00 0.08 1.12 0.02 0.88 4 4.0 0.04
60 0.13 4.00 0.08 1.67 0.04 1.86 4 4.0 0.07
80 0.18 4.00 0.08 2.23…