26DIX0836 DIX Required Hood Work.pdf

PDF 64 KB Posted

Attached to
Ansul Fire Suppression System Test and Repairs
Solicitation number
27-426DOC-DIXON-B-53024
Issued by
Illinois

About this file

This is a scope of work document for Dixon Correctional Center in Illinois requiring full 12-year hydrostatic testing and maintenance services on three Ansul fire suppression kitchen hood systems. The project encompasses three separate systems: a 15-gallon Ansul system serving the North Production Hood, a 6-gallon Ansul system serving the Culinary Hood, and a 3-gallon Ansul system serving the South Production Hood. All three systems are overdue for their required 12-year hydrostatic testing, with the last testing completed in 2014. The scope of work includes removal and hydrostatic testing of all system tanks with subsequent reinstallation, replacement of required cartridges, O-rings, and burst discs, replacement of eighteen aluminum link holders with stainless steel UL-listed components, replacement of four clogged duct nozzles, reconfiguration of griddle nozzle drops for proper appliance coverage, installation of bursting disc union assemblies on manifolded tank sets for the largest system, and complete system reassembly, testing, and commissioning.

Upon completion, all three systems must be returned to full operational service and verified to meet manufacturer specifications, UL 300 requirements, and applicable NFPA standards. No specific pricing terms, set-aside provisions, incumbent contractor information, response dates, or contract award timelines are detailed in this scope of work document.

View the file

Other files

File Type Posted
27DIX0007 Dixon Ansul Test-Repair B-53024 RFQ.docx DOCX document
IL Standard-Terms-and-Conditions v23.2~2.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Dixon Correctional Center Required Kitchen Hood Work

System Details:

System #1: Ansul 15-Gallon – North Production Hood

System #2: Ansul 6-Gallon – Culinary Hood

System #3: Ansul 3-Gallon – South Production Hood

Services:

Perform full 12-year hydrostatic testing and maintenance on all three (3) Ansul systems. All Ansul systems are due for their 12-year hydrostatic test & maintenance. Last hydro tested in 2014.

Scope of work includes:

- Removal, hydrostatic testing, and reinstallation of system tanks

- Replacement of required cartridges, O-rings, and burst discs

- Replacement of all eighteen (18) aluminum link holders with stainless steel UL-listed components

- Replacement of four (4) clogged duct nozzles

- Reconfiguration of griddle nozzle drops to ensure proper appliance coverage

- Installation of bursting disc union assemblies on manifolded tank sets for System #1

- Full system reassembly, testing, and commissioning upon completion

Upon completion, all systems must be returned to service and verified to be operating in accordance with manufacturer specifications, UL 300 requirements, and applicable NFPA standards.