260-B6260-003 MTS Replace Rooftop Unit_DRAWINGS.pdf
PDF 3 MB Posted
- Attached to
- 260-B6260-003 MTS Replace Rooftop Unit
- Solicitation number
- IFB-129404
- Issued by
- Prince William County, Virginia
About this file
These are architectural and engineering drawings for the replacement of rooftop air conditioning unit RTU-1 at Northern Virginia Community College's Manassas campus, located at 10500 Battleview Parkway, Manassas, Virginia 20109. The project involves the complete removal and replacement of an existing two-story building's rooftop unit with a new 40-ton Carrier model 50K unit utilizing R-454B refrigerant that meets current federal regulatory requirements. The new equipment will be installed on the existing roof curb with a compatible curb adapter and will maintain equivalent performance capacity and functional compatibility with existing systems. The project is under the Virginia Community College System (VCCS) A/E Term Contract #VCCS-04132023-E, with project number 260-B6260-003. The scope includes supply air delivery at 13,000 CFM, provision of a 0-100% enthalpy economizer, 4-inch MERV 13 filters, stainless steel drip pan and cooling coil casing, hinged access doors, BACnet communication interface, and compliance with ASHRAE 90.1-2022 minimum efficiency requirements. The replacement unit will serve the second floor east spaces of the college building through an existing distribution system.
The project is designed to comply with Virginia Uniform Statewide Building Code 2021, Virginia Energy Conservation Code 2021, and applicable mechanical, plumbing, fire, and electrical codes. The replacement unit is rated at an operating weight of 5,680 pounds, with maximum combined weight with curb adapter not to exceed 6,800 pounds. The contractor is responsible for all permits, crane rigging coordination, electrical work, roof warranty compliance, and coordination with the college's existing Tridium Niagara BAC building automation control system managed by Chesapeake Controls Inc. Electrical service requires a 480/277V, three-phase, 131-150 ampere fused disconnect switch mounted independently on unistrut framing. The contractor must provide pre-functional checklists, start-up reports, Building Automation System integration, seven-day notice prior to RTU start-up and functional testing, and coordinate noisy work or crane lifts one week in advance to avoid disrupting college classes. No specific pricing information, set-asides, funding amounts, response dates, or award dates are contained within these technical drawings.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NORTHERN VIRGINIA COMMUNITY COLLEGE
MTS REPLACE ROOF TOP UNIT
10500 BATTLEVIEW PKWY, MANASSAS, VA 20109
A/E TERM CONTRACT #: VCCS-04132023-E
PROJECT #: 260-B6260-003
DESCRIPTION OF WORK
THE SCOPE OF WORK INCLUDES THE REMOVAL AND REPLACEMENT OF ROOFTOP UNIT RTU-1 SERVING AN EXISTING TWO STORY COMMUNITY COLLEGE BUILDING. THE REPLACEMENT UNIT IS PROVIDED WITH A CURB ADAPTER DESIGNED TO INTERFACE WITH THE EXISTING ROOF CURB, MAINTAINING COMPATIBILITY WITH THE EXISTING CURB DIMENSIONS AND ACCOMMODATING COMPARABLE EQUIPMENT WEIGHT. THE RTU-1 IS REMOVED IN ITS ENTIRETY AND REPLACED WITH A NEW UNIT OF EQUIVALENT PERFORMANCE CAPACITY, COMPLETE AND TURNKEY. THE REPLACEMENT UNIT UTILIZES A REFRIGERANT THAT COMPLIES WITH CURRENT FEDERAL REGULATORY REQUIREMENTS AND CORRESPONDING ELECTRICAL MANUFACTURER'S RECOMMENDATIONS , WHILE MAINTAINING FUNCTIONAL EQUIVALENCY TO THE EXISTING SYSTEM.
GENERAL INFORMATION
PRIMARY CONTACTS
VCCS - NORTHERN VIRGINIA COMMUNITY
COLLEGE
FACILITIES PLANNING AND SUPPORT SERVICES
8333 LITTLE RIVER TURNPIKE, ROOM #311
ANNADALE, VA 22003-3796
PHONE: 571-888-4456
ENGINEER
WSP USA, INC
MICHAEL HATHORNE
1300 N 17TH ST, SUITE 1000
ARLINGTON, VA 22209
PHONE: 703-209-9379
ASBESTOS DISCLOSURE STATEMENT
AN ASBESTOS INSPECTION WAS NOT PERFORMED BECAUSE ALL PORTIONS OF THE EXISTING BUILDING THAT MAY BE AFFECTED
BY THE WORK WERE ORIGINALLY CONSTRUCTED AFTER JANUARY 1, 1985.
USE OF NEW ASBESTOS-CONTAINING MATERIALS WITHIN THE PROJECT SCOPE IS PROHIBITED.
LEAD DISCLOSURE STATEMENT
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS NOT BEEN CONDUCTED BECAUSE THE BECAUSE THE BUILDING WAS CONSTRUCTED AFTER JANUARY 1, 1985 AND THE OWNER HAS NO KNOWLEDGE OF LEAD CONTAINING OR COATED BUILDING COMPONENTS IN THE BUILDING. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND
LEAD-COATED BUILDING COMPONENTS SHALL BE RECYCLED TO THE EXTENT POSSIBLE.
NEW WORK NOTES
HPBA COMPLIANCE STATEMENT
IN ACCORD WITH THE HIGH PERFORMANCE BUILDINGS ACT, THE BUILDING IS EXEMPT FROM COMPLIANCE BECAUSE THE COST OF
RENOVATIONS DOES NOT EXCEED 50% OF THE VALUE OF THE BUILDING.
VECC COMPLIANCE STATEMENT
IN ACCORD WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING SHALL COMPLY WITH VECC SECTIONS C402
THROUGH C405 AND C408. THE FOLLOWING SECTIONS ARE NOT APPLICABLE: C402 AND C404.
PROJECT DATA
GENERAL INFORMATION
NAME OF PROJECT - NVCC MTS REPLACE ROOF TOP UNIT
ADDRESS - 10500 BATTLEVIEW PKWY
MANASSAS, VA 20109
OWNER OR AUTHORIZED AGENT - VIRGINIA COMMUNITY COLLEGE SYSTEM
CONSTRUCTION TYPE - IIB NONCOMBUSTIBLE, UNPROTECTED
USE GROUP - MIXED USE, NON-SEPARATED, B, BUSINESS
OCCUPANCY - BUSINESS
NUMBER OF STORIES - 2 STORIES
BUILDING AREA - 21,294 GSF
WORK AREA - 660 GSF
BUILDING HEIGHT - 24' - 0" (APPROXIMATE)
CODES LISTED BELOW SHOW CODES APPLICABLE TO BASIS-OF-DESIGN. CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE
CODES, INCLUDING LOCAL AMMENDMENTS.
APPLICABLE CODES
BUILDING CODE - VIRGINIA UNIFORM STATEWIDE BUILDING CODE 2021
- VIRGINIA CONSTRUCTION CODE 2021 (VCC)
- VIRGINIA EXISTING BUILDING CODE 2021 (VEBC) - LEVEL 01
ENERGY CODE - VIRGINIA ENERGY CONSERVATION CODE 2021
MECHANICAL CODE - VIRGINIA MECHANICAL CODE 2021
PLUMBING CODE - VIRGINIA PLUMBING CODE 2021
FIRE CODE - VIRGINIA STATEWIDE FIRE PREVENTION CODE 2021 (VSFPC)
- INTERNATIONAL FIRE CODE 2021 (IFC)
ELECTRICAL CODE - NFPA 70/NATIONAL ELECTRICAL CODE, 2020 EDITION
FIRE ALARM CODE - NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE 2021
ADDITIONAL CODES - NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVE 2021
- VIRGINIA CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL 2026. REV 0 - 7/31/2026
ACCESSIBILITY CODE - ADA 90-Title II: 2010 ASAD Chapter 2 (Scoping) & ICC A117.1-2017 Chapters 1, 3-11 (Technical)
DESIGN CRITERIA
COORDINATES
LATITUDE/LONGITUDE - 38°80'63.7"N , 77°51'77.3."W
ELEVATION
FEET ABOVE SEA LEVEL - 230'
ASHRAE SUMMER DESIGN CONSIDERATIONS
0.4% DB MWB - 93.0°/74.8°
ASHRAE WINTER DESIGN CONSIDERATIONS
99.6% DB - 11.1°
BUILDING SPACE DESIGN TEMPERATURES
SUMMER DB - 75°
WINTER DB - 70°
ABBREVIATIONS
ATTN ATTENTION
B BUSINESS
CPSM CONSTRUCTION & PROFESSION SERVICES
MANUAL
DWGS DRAWINGS
FT FEET
GC GENERAL CONTRACTOR
MAX MAXIMUM
MIN MINIMUM
NEC NATIONAL ELECTRICAL CODE
SF SQUARE FEET
VEBC VIRGINIA EXISTING BUILDING CODE
VCC VIRGINIA CONSTRUCTION CODE
VCCS VIRGINIA COMMUNITY COLLEGE SYSTEM
ADA COMPLIANCE STATEMENT
IN ACCORD WITH ADA STANDARDS FOR ACCESSIBLE DESIGN, THE BUILDING SHALL COMPLY WITH SECTION 203.9 FOR FULLY
ACCESSIBLE EMPLOYEE WORK AREAS.
LOCATION MAP
VICINITY MAP
1.
2.
3.
4.
5.
6.
7.
8.
9.
A.
REVIEW THE DRAWINGS FOR NOTES, DIMENSIONS, ETC., AND COORDINATE WITH OTHER TRADES INVOLVED.
CONTRACTORS SHALL VERIFY LAYOUT AND BE RESPONSIBLE FOR ALL MEASUREMENTS OF ALL EXISTING CONDITIONS BEFORE COMMENCING WORK AND SHALL NOTIFY OWNER AND/OR ENGINEER IF A CONDITION EXISTS THAT PREVENTS THE CONTRACTOR FROM ACCOMPLISHING THE
INTENT OF THE DRAWINGS.
CONTRACTOR TO PROVIDE A FIRE WATCH ANY TIME THE FIRE ALARM SYSTEM IS IMPAIRED. HOURLY BUILDING INSPECTIONS AND ANY ADDITIONAL REQUIREMENTS MADE BY THE STATE FIRE MARSHAL SHALL BE REQUIRED. COORDINATE WITH NVCC PROJECT MANAGER.
COORDINATE IMPAIRMENTS TWO WORK DAYS IN ADVANCE, MINIMUM.
HOT WORKS PERMIT SHALL COORDINATED TWO WORK DAYS IN ADVANCE, MINIMUM. COORDINATE WITH NVCC PROJECT MANAGER.
SUBMIT 1 ELECTRONIC COPY OF PRODUCT AND CAPACITY DATA FOR EQUIPMENT TO THE ENGINEER AS DIRECTED BEFORE ORDERING
EQUIPMENT. COPIES SHALL BE DELIVERED TO THE FOLLOWING: OWNER AND ENGINEER.
THOUGH SOME OFFSETS AND TRANSITIONS ARE SHOWN IN PIPING AND SHEET METAL TO HELP INDICATE THE PHYSICAL RELATIONSHIP BETWEEN THEM, IT IS NOT THE INTENT OF THE DRAWING TO SHOW ALL PIPING AND SHEET METAL OFFSETS AND TRANSITIONS REQUIRED. THE CONTRACTOR SHALL FULLY COORDINATE THE MECHANICAL WORK INTERNALLY AND WITH ALL TRADES TO PROVIDE COMPLETE & OPERABLE
SYSTEMS WITHOUT INTERFERENCES.
CONTRACTOR SHALL START-UP AND DEMONSTRATE ALL NEW EQUIPMENT FOR OWNER/ENGINEER AND/OR OWNER'S OPERATING PERSONNEL.
CONTRACTOR SHALL DEMONSTRATE SATISFACTORY PERFORMANCE, ADJUST AND CORRECT OPERATIONS AS REQUIRED FOR PROPER
PERFORMANCE, CLEAN AND LUBRICATE EACH SYSTEM.
INSTALL, TEST AND START-UP IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
FURNISH AND INSTALL ALL EQUIPMENT WITH THE FOLLOWING:
ALL LOW VOLTAGE CONTROL DEVICES AND THEIR RELATED WIRING. LOW VOLTAGE IS DEFINED AS ANY VOLTAGE SYSTEM THAT IS AT OR LOWER THAN THE 120-VOLT, SINGLE PHASE, 60 HERTZ SYSTEM, EXCLUDING FIRE ALARM, SECURITY, AND OTHER
COMMUNICATIONS TYPE SYSTEMS.
MT
AGENCY REPRESENTATIVES
NAME: MIKE JONES, MBA
TITLE: CAPITAL OUTLAY PROGRAM MANAGER
DEPARTMENT: VIRGINIA'S COMMUNITY
COLLEGES - SYSTEM OFFICE
ADDRESS: 300 ARBORETUM PLACE, SUITE 200
RICHMOND, VA 23236
PHONE: 832-428-4678
EMAIL: MJONES@VCCS.EDU
FOR VIRGINIA COMMUNITY COLLEGE SYSTEM (VCCS)
NVCC INTERSECTION
SUDLEY RD & CAMPUS DR
WSP USA Buildings Inc wsp.com
1300 N 17TH ST, SUITE 1000
ARLINGTON VA, 22209
(202) 362-2800
NO. REVISION DATE
SCALE:
DWN. BY:
VCCS PROJECT NO.:
WSP PROJECT NO.:
CKD. BY:
OWNER NAME:
PROJECT TITLE:
TITLE
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL TAKE PRECEDENCE OVER
SCALED DIMENSIONS. THESE DRAWING SHALL BE COPIED FROM THE ORIGINAL
BLUEPRINTS AND ARE APPROXIMATELY TO SCALE. IT IS THE CONTRACTORS
RESPONSIBILITY TO VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND
CONDITIONS ON THE PROJECT AND SHALL NOTIFY THE ENGINEER OF ANY
VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THESE
DRAWINGS.
N.T.S.
MEP Engineer:
PROJECT CODE:
Commissioning Agent:
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
US0027294.0531
260-B6260-003
APT MLH
VCCS - NORTHERN
VIRGINIA COMMUNITY
COLLEGE
MTS REPLACE ROOF
TOP UNIT
COVER SHEET
G-001
PROJECT ADDRESS:
10500 BATTLEVIEW PKWY
MANASSAS, VIRGINIA 20109
260-B6260-003
DRAWING SHEET LIST
Sheet Number Sheet Name
G-001 COVER SHEET
G-002 SITE PLAN
ME-001 LEGENDS AND ABBREVIATIONS
ME-002 SCHEDULES AND CALCULATIONS
ME-003 SCHEDULES
ME-101 OVERALL PLAN
ME-201 ROOF PLANS
ME-301 PARTIAL FLOOR PLANS
ME-501 RISERS
ME-801 CONTROLS AND DETAILS
Grand total: 10
LOCATION MAP
VICINITY MAP
MT NVCC INTERSECTION
SUDLEY RD & CAMPUS DR
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
MICHAEL L.
HATHORNE
Lic. No. 0402066441
09.04.2026
ISSUE FOR BID 09/04/2026
M CONTRACT #: V
ROJECT #: 260-B6
ISSUE FOR BID
C
L
P
L
P
L
P
L
P
L
P
L
P
L
P
TV
CONCRETE SIDEWALK
CONC.
WALK
CONCRETE
SIDEWALK
B R
ID
G E
P
ED
ES
TR
IAN
C O N C
RE
TE
SI
DE
W
AL
K
C O N C
W
AL
K
CONCRETE
SIDEWALK
CONCRETE
SIDEWALK
CO
NC
RE
TE
S
ID
EW
AL
K
CONCRETE
SIDEWALK
BATTLEVIEW PARKWAY - ROUTE 2740
CHAIN LINK FENCE CHAIN LINK FENCE
IPF
LOT 2
144,130 SQ. FT. OR
3.30876 ACRES
N67°38'48"E
LINDEN-BATTLEFIELD LLC
D .B
P G
LOT 3
BATTLEFIELD BUSINESS PARK
D .B
P G
G P
IN
7697-
38-
COMMONWEALTH OF VIRGINIA
STATE BOARD OF COMMUNITY COLLEGES
D.B. 428 PG. 481
GPIN: 7697-39-2308
MAN
AS
SA
S H
OSP
ITA
LIT
Y, INC.
IN
ST
R.
GP
IN
10 SPACES
12 SPACES
WSP USA Buildings Inc wsp.com
1300 N 17TH ST, SUITE 1000
ARLINGTON VA, 22209
(202) 362-2800
NO. REVISION DATE
SCALE:
DWN. BY:
VCCS PROJECT NO.:
WSP PROJECT NO.:
CKD. BY:
OWNER NAME:
PROJECT TITLE:
TITLE
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL TAKE PRECEDENCE OVER
SCALED DIMENSIONS. THESE DRAWING SHALL BE COPIED FROM THE ORIGINAL
BLUEPRINTS AND ARE APPROXIMATELY TO SCALE. IT IS THE CONTRACTORS
RESPONSIBILITY TO VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND
CONDITIONS ON THE PROJECT AND SHALL NOTIFY THE ENGINEER OF ANY
VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THESE
DRAWINGS.
N.T.S.
MEP Engineer:
PROJECT CODE:
Commissioning Agent:
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
US0027294.0531
260-B6260-003
APT MLH
VCCS - NORTHERN
VIRGINIA COMMUNITY
COLLEGE
MTS REPLACE ROOF
TOP UNIT
SITE PLAN
G-002
PROJECT ADDRESS:
10500 BATTLEVIEW PKWY
MANASSAS, VIRGINIA 20109
260-B6260-003
1/16" = 1'-0"
SITE PLAN
1/16" = 1'0"
016' 8'
SCALE: 1/16" = 1' - 0"
GRAPHIC SCALE
16' 32' 48'
N
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
MICHAEL L.
HATHORNE
Lic. No. 0402066441
09.04.2026
ISSUE FOR BID 09/04/2026
ABBREVIATIONS - MECHANICAL
AHU AIR HANDLING UNIT
BHP BRAKE HORSE POWER
BTU BRITISH THERMAL UNIT
CFM CUBIC FEET PER MINUTE
DB DRY BULB
DN DOWN
(E) EXISTING TO REMAIN
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB
EF EXHAUST FAN
EHC ELECTRIC HEATING COIL
EWB ENTERING WET BULB
EWT ENTERING WATER TEMPERATURE
°F DEGREES FAHRENHEIT
FLA FULL LOAD AMPS
FT FEET
GPM GALLONS PER MINUTE
HC HEATING COIL
HP HORSE POWER
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
MAT MIXED AIR TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MECHANICAL LEGEND & ABBREVIATIONS
DUCTWORK LEGEND
RECTANGULAR SUPPLY DUCT UP
RECTANGULAR SUPPLY DUCT DOWN
RECTANGULAR RETURN OR EXHAUST
DUCT UP
RECTANGULAR RETURN OR EXHAUST
DUCT DOWN
S DUCT SMOKE DETECTOR
CONTROLS LEGEND
PIPING LEGEND
ELBOW TURNED UP
ELBOW TURNED DOWN
CONDENSATE DRAIN
D D
18x12 DUCT SIZE (CLEAR INSIDE DIMENSION)
FIRST FIGURE INDICATES PLAN SIZE
MFS MAXIMUM FUSE SIZE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
(N) NEW
NIC NOT IN THIS CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OBD OPPOSED BLADE DAMPER
PD PRESSURE DROP
PSI POUNDS PER SQUARE INCH (GAUGE)
PSIA POUNDS PER SQUARE INCH ABSOLUTE
RA RETURN AIR
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
RTU ROOFTOP UNIT
SA SUPPLY AIR
SF SUPPLY FAN
SP STATIC PRESSURE
SQFT SQUARE FEET
RD ROOF DRAIN
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
W/ WITH
WB WET BULB
(X) EXISTING TO BE DEMOLISHED
(300) CUBIC FEET OF AIR PER MINUTE OR GALLONS PER MINUTE
RACEWAY LEGEND
CONDUIT CONCEALED ABOVE CEILING OR WITHIN WALL
CONDUIT BELOW GRADE OR EMBEDDED WITHIN SLAB
CONDUIT UP
CONDUIT DOWN
CONDUIT STUBBED OUT WITH BUSHING
NOTE: PROVIDE PULLSTRING IN EACH EMPTY RACEWAY
CONDUIT STUBBED OUT AND CAPPED
NOTE: PROVIDE PULLSTRING IN EACH EMPTY RACEWAY
GROUNDING CONDUCTOR
PHASE CONDUCTOR(S)
ISOLATED GROUNDING CONDUCTOR
NEUTRAL CONDUCTOR
WIRING DEVICE LEGEND
DUPLEX RECEPTACLE OUTLET: 125V; WALL MOUNTED
DOUBLE DUPLEX RECEPTACLE OUTLET: 125V; WALL MOUNTED
POWER LEGEND
ATS, CPC, DPH, DPL, DSH, DSL, MCC OR
MS: SIZE APPROXIMATELY AS SHOWN.
DOUBLE LINE INDICATES FRONT.
SURFACE MOUNTED LPH, LRC, MP OR TC:
SIZE APPROXIMATELY AS SHOWN
RECESSED MOUNTED LPH, LRC, MP OR TC:
SIZE APPROXIMATELY AS SHOWN
SURFACE MOUNTED LP:
SIZE APPROXIMATELY AS SHOWN
RECESSED MOUNTED LP:
SIZE APPROXIMATELY AS SHOWN
STEP DOWN TRANSFORMER
GENERATOR
T F
G
AUTOMATIC TRANSFER SWITCH
HEAVY DUTY DISCONNECT SWITCH, FUSED TYPE
VFD WITHOUT DISCONNECTVFD
MOTOR CONNECTION
JUNCTION BOX, CEILING MOUNTEDJ
M
JUNCTION BOX, WALL MOUNTED
PULL BOX
CIRCUIT BREAKER
SWITCH AND FUSE
P B
J
CIRCUIT BREAKER IN ENCLOSURE
CURRENT TRANSFORMER COMPARTMENT AND KWH
METERM
TRANSFORMER
WR = WEATHER RESISTANTWR
GENERATOR IN WP ENCLOSURE
VFD WITH DISCONNECT, NOT PROVIDED UNDER
ELECTRICAL SCOPE
WIRING DEVICE SUBSCRIPT LEGEND
GFCI = GROUND FAULT CIRCUIT INTERRUPTER
WP = WEATHERPROOF
GFCI
WP
VFD
G
EQUIPMENT NAMING LEGEND
BUS
U
E
DPL
DSH
DSL
LP
A 1,3,5
CIRCUIT NUMBER(S)
FIRST OF THIS TYPE ON FLOOR
FLOOR LEVEL
ATS 2
MS
MP
MCC
LRC
TB
TC
- /N
NORTH, EAST, SOUTH OR WEST
DPH
LPH
T
PDU
O S
ATS AUTOMATIC TRANSFER SWITCH
BUS BUSWAY
DPH DISTRIBUTION PANEL 277/480V
DPL DISTRIBUTION PANEL 120/208V
DSH DISTRIBUTION SWITCHBOARD 277/480V
DSL DISTRIBUTION SWITCHBOARD 120/208V
LP BRANCH CIRCUIT PANELBOARD 120/208V
LPH BRANCH CIRCUIT PANELBOARD 277/480V
LRC LIGHTING RELAY CABINET
MCC MOTOR CONTROL CENTER
MP MECHANICAL EQUIPMENT PANELBOARD 120/208V
MS MAIN SWITCHBOARD
PDU POWER DISTRIBUTION UNIT
T TRANSFORMER
TB TELECOM BACKBOARD
TC TELECOM CABINET
E EMERGENCY LIFE SAFETY
O OPTIONAL STANDBY POWER
S LEGALLY REQUIRED STANDBY POWER
U UNINTERRUPTIBLE POWER SUPPLY
MPH MECHANICAL EQUIPMENT PANELBOARD 277/480V
ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
AIC AMPERES INTERRUPTING CAPACITY
AF/AS AMPERE RATING OF FUSE/SWITCH
AT/AF AMPERE RATING OF CIRCUIT, BREAKER TRIP/FRAME
CKT CIRCUIT
EC EMPTY CONDUIT / ELECTRICAL CONTRACTOR
GND GROUND
IG ISOLATED GROUND
WP WEATHERPROOF
A AMPERES
AL ALUMINUM
C CONDUIT (GENERIC TERM FOR RACEWAY - PROVIDE AS SPECIFIED)
CB CIRCUIT BREAKER
CU COPPER
DWG DRAWING
GC GENERAL CONTRACTOR
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILS
KVA KILO-VOLT AMPERE
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
P POLE
PWR POWER
PH PHASE
ATS AUTOMATIC TRANSFER SWITCH
GFCI GROUND FAULT CIRCUIT INTERRUPTOR
MCC MOTOR CONTROL CENTER
MS MANUAL SWITCH
DPH-B1/1,3,5
EF-1-1
POWER SOURCE
MECHANICAL EQUIPMENT TAG
ELECTRICAL LEGEND & ABBREVIATIONS
LINEWEIGHTS LEGEND
EXISTING TO REMAIN
NEW WORK
REMOVED / DEMOLISHED
ABBREVIATIONS - MECHANICAL
(E) EXISTING TO REMAIN
HP HORSE POWER
KW KILOWATT
GENERAL LEGEND & ABBREVIATIONS
CT
1-1
EQUIPMENT
DESIGNATION
EQUIPMENT TYPE
EQUIPMENT
AND NUMBER
MISCELLANEOUS
NEW WORK
EXISTING WORK
EXISTING WORK TO BE REMOVED
(N) NEW
NTS NOT TO SCALE
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
(X) EXISTING TO BE DEMOLISHED
(R) EXISTING TO BE RELOCATED
SHEET NOTE1 1
WSP USA Buildings Inc wsp.com
1300 N 17TH ST, SUITE 1000
ARLINGTON VA, 22209
(202) 362-2800
NO. REVISION DATE
SCALE:
DWN. BY:
VCCS PROJECT NO.:
WSP PROJECT NO.:
CKD. BY:
OWNER NAME:
PROJECT TITLE:
TITLE
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL TAKE PRECEDENCE OVER
SCALED DIMENSIONS. THESE DRAWING SHALL BE COPIED FROM THE ORIGINAL
BLUEPRINTS AND ARE APPROXIMATELY TO SCALE. IT IS THE CONTRACTORS
RESPONSIBILITY TO VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND
CONDITIONS ON THE PROJECT AND SHALL NOTIFY THE ENGINEER OF ANY
VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THESE
DRAWINGS.
N.T.S.
MEP Engineer:
PROJECT CODE:
Commissioning Agent:
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
US0027294.0531
260-B6260-003
MT MLH
VCCS - NORTHERN
VIRGINIA COMMUNITY
COLLEGE
MTS REPLACE ROOF
TOP UNIT
LEGENDS AND
ABBREVIATIONS
ME-001
PROJECT ADDRESS:
10500 BATTLEVIEW PKWY
MANASSAS, VIRGINIA 20109
260-B6260-003
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
MICHAEL L.
HATHORNE
Lic. No. 0402066441
09.04.202609.04.2026
Multiple zone
RTU1
System name and number RTU1
Condition analyzed (impacts Ez, Vdz, Vpz and Vps) Heating
All zones are included in the VRP calculation Yes
Zone Name and Number
Occupancy Category
Zone Floor Area Are you using default value for zone population?
Zone Population
Zone Air Distribution
Effectiveness
Zone Outdoor Airflow
Zone Discharge
Airflow
Zone Primary Airflow
Zone Secondary Recirculation
Fraction Zone Primary Air
Fraction
Az Pz Ez Voz Vdz Vpz Er Ep (sq ft) (people) (cfm) (cfm) (cfm)
01-060 281 OPEN SPACE / CORRIDORS Corridors 700 Yes 0.00 0.80 52.50 1,100 330 0.50 0.30 01-070 281 TRAINING SUITE Classrooms (age 9 plus) 531 No 5.00 0.80 142.15 676 203 0.50 0.30 01-070 278 CORRIDOR Corridors 180 Yes 0.00 0.80 13.50 75 23 0.50 0.30 01-070 208 CORRIDOR Corridors 212 Yes 0.00 0.80 15.90 100 30 0.50 0.30 01-050 213-MENS RESTROOM 146 Yes 0.00 0.80 0.00 75 23 0.50 0.30 01-030 214-WOMENS RESTROOM 151 Yes 0.00 0.80 0.00 75 23 0.50 0.30 01-050 203-SECURITY ADMIN Office space 106 No 1.00 0.80 14.20 100 30 0.50 0.30 01-090 204-SKILL SOURCE Office space 842 No 12.00 0.80 138.15 1,350 405 0.50 0.30 01-080 206-WORKFORCE Office space 473 No 7.00 0.80 79.23 1,100 330 0.50 0.30 01-070 209-STORAGE CLOSET Storage rooms 60 Yes 0.00 0.80 9.00 50 15 0.50 0.30 01-110 215,218-SYSTEMIC SOLUTIONS Office space 450 No 5.00 0.80 65.00 500 150 0.50 0.30 01-110 216-STORAGE CLOSET Storage rooms 33 Yes 0.00 0.80 4.95 50 15 0.50 0.30 01-100 217-OFFICE Office space 126 No 1.00 0.80 15.70 200 60 0.50 0.30 01-050, 110 219 CORRIDOR Corridors 856 Yes 0.00 0.80 64.20 250 75 0.50 0.30 01-110 221-ROBOTIC STORAGE Storage rooms 277 Yes 0.00 0.80 41.55 150 45 0.50 0.30 01-100 222-ROBOTIC CLASSROOM Classrooms (age 9 plus) 535 No 18.00 0.80 305.25 1,200 360 0.50 0.30 01-010 229-CLASSROOM Classrooms (age 9 plus) 543 No 28.00 0.80 431.45 1,500 450 0.50 0.30 01-020 230-CLASSROOM Classrooms (age 9 plus) 543 No 25.00 0.80 393.95 1,500 450 0.50 0.30 01-030 231-CLASSROOM Classrooms (age 9 plus) 612 No 28.00 0.80 441.80 1,500 450 0.50 0.30 01-040 232-CLASSROOM Classrooms (age 9 plus) 614 No 28.00 0.80 442.10 1,600 480 0.50 0.30 01-050 234-STUDENT LOUNGE Break rooms (general) 403 Yes 10.08 0.80 93.19 1,200 360 0.50 0.30 01-090 282 WORK COPY Office space 63 No 1.00 0.80 10.98 250 75 0.50 0.30
System area As (sq ft) 8,456 Net occupiable floor area served by the ventilation system
System population Ps (people) 151.00
Sum of zone population sum of Pz (people) 169.07 ∑Pz
Occupant diversity D 0.89 Ps / ∑Pz
Uncorrected outdoor air intake Vou (cfm) 2,054.19 D ∑ (Rp Pz) + ∑(Ra Az)
System primary airflow (at condition analyzed) Vps (cfm) 4,380
Average outdoor air fraction Xs 0.46 Vou / Vps
Which method from ASHRAE 62.1 is being used to determine system ventilation efficiency (Ev)? Appendix A
Ventilation efficiency Ev 0.79 Ventilation efficiency from critical zone
Outdoor air intake flow (required by 62.1) Vot (cfm) 2,600 Vou / Ev
Outdoor air intake flow provided (measured or design) (cfm) 3,100
Multiple zone
RTU1 (DEMAND CONTROL VENTILATION MINIMUM)
Show simple view
System name and number RTU1
Condition analyzed (impacts Ez, Vdz, Vpz and Vps) Heating
All zones are included in the VRP calculation Yes
Zone Name and Number
Occupancy Category
Zone Floor Area Are you using default value for zone population?
Zone Population
Zone Air Distribution
Effectiveness
Zone Outdoor Airflow
Zone Discharge
Airflow
Zone Primary Airflow
Zone Secondary Recirculation
Fraction Zone Primary Air
Fraction
Az Pz Ez Voz Vdz Vpz Er Ep (sq ft) (people) (cfm) (cfm) (cfm)
01-060 281 OPEN SPACE / CORRIDORS **** Corridors 700 Yes 0.00 0.80 52.50 1,100 330 0.50 0.30 01-070 281 TRAINING SUITE Classrooms (age 9 plus) 531 No 0.00 0.80 79.65 676 203 0.50 0.30 01-070 278 CORRIDOR Corridors 180 Yes 0.00 0.80 13.50 75 23 0.50 0.30 01-070 208 CORRIDOR Corridors 212 Yes 0.00 0.80 15.90 100 30 0.50 0.30 01-050 213-MENS RESTROOM 146 Yes 0.00 0.80 0.00 75 23 0.50 0.30 01-030 214-WOMENS RESTROOM 151 Yes 0.00 0.80 0.00 75 23 0.50 0.30 01-050 203-SECURITY ADMIN Office space 106 No 0.00 0.80 7.95 100 30 0.50 0.30 01-090 204-SKILL SOURCE Office space 842 No 0.00 0.80 63.15 1,350 405 0.50 0.30 01-080 206-WORKFORCE Office space 473 No 0.00 0.80 35.48 1,100 330 0.50 0.30 01-070 209-STORAGE CLOSET Storage rooms 60 Yes 0.00 0.80 9.00 50 15 0.50 0.30 01-110 215,218-SYSTEMIC SOLUTIONS Office space 450 No 0.00 0.80 33.75 500 150 0.50 0.30 01-110 216-STORAGE CLOSET Storage rooms 33 Yes 0.00 0.80 4.95 50 15 0.50 0.30 01-100 217-OFFICE Office space 126 No 0.00 0.80 9.45 200 60 0.50 0.30 01-050, 110 219 CORRIDOR *** Corridors 856 Yes 0.00 0.80 64.20 250 75 0.50 0.30 01-110 221-ROBOTIC STORAGE Storage rooms 277 Yes 0.00 0.80 41.55 150 45 0.50 0.30 01-100 222-ROBOTIC CLASSROOM Classrooms (age 9 plus) 535 No 0.00 0.80 80.25 1,200 360 0.50 0.30 01-010 229-CLASSROOM Classrooms (age 9 plus) 543 No 0.00 0.80 81.45 1,500 450 0.50 0.30 01-020 230-CLASSROOM Classrooms (age 9 plus) 543 No 0.00 0.80 81.45 1,500 450 0.50 0.30 01-030 231-CLASSROOM Classrooms (age 9 plus) 612 No 0.00 0.80 91.80 1,500 450 0.50 0.30 01-040 232-CLASSROOM Classrooms (age 9 plus) 614 No 0.00 0.80 92.10 1,600 480 0.50 0.30 01-050 234-STUDENT LOUNGE Break rooms (general) 403 No 0.00 0.80 30.23 1,200 360 0.50 0.30 01-090 282 WORK COPY Office space 63 No 0.00 0.80 4.73 250 75 0.50 0.30
System area As (sq ft) 8,456 Net occupiable floor area served by the ventilation system
System population Ps (people) 151.00
Sum of zone population sum of Pz (people) 0.00 ∑Pz
Occupant diversity D 0.00 Ps / ∑Pz
Uncorrected outdoor air intake Vou (cfm) 714.42 D ∑ (Rp Pz) + ∑(Ra Az)
System primary airflow (at condition analyzed) Vps (cfm) 4,380
Average outdoor air fraction Xs 0.16 Vou / Vps
Which method from ASHRAE 62.1 is being used to determine system ventilation efficiency (Ev)? Appendix A
Ventilation efficiency Ev 0.67 Ventilation efficiency from critical zone
Outdoor air intake flow (required by 62.1) Vot (cfm) 1,066 Vou / Ev
Outdoor air intake flow provided (measured or design) (cfm) 1,100
ROOFTOP AIR CONDITIONING UNIT SCHEDULE
DESIGNATION
MANUFACTURER
MODEL
NUMBER
LOCATION /
SERVICE
NOMINAL
COOLING
CAPACITY
(TON)
REFRIGERANT
SUPPLY
AIR
CFM
OUTSIDE
AIR CFM
OUTSIDE AIR DATA SUPPLY FAN EXHAUST FAN COOLING COIL ELECTRIC HEATING COIL ELECTRICAL DATA
GEN.
POWER
(Y/N)
VFD
(Y/N)
OPER.
WEIGHT
(LB)
NOTES
SUMMER WINTER
C
FM ES
P
(IN
W G
R
PM
BR
AK
E H
P
M O
TO
R
H P
ES
P
Q
TY
M O
TO
R
H P
FL
A
/ M O
C (E
AC
H
EAT LAT CAPACITY
EA
T
(º F)
LA
T
(º F)
C
AP
AC
IT
Y (K
W
C O
N
TR
O L
VO
LT
AG
E/
PH
AS
E
M C
A/ M
O P
U N
IT
FL
A
D B
(º F)
W B
(º F)
D B
(º F)
D B
(º F)
W B
(º F)
D B
(º F)
W B
(º F)
TO
TA
L (M
BH
SE
N
SI
BL
E (M
BH
RTU-1 CARRIER 50K ROOF / SECOND FLOOR EAST 40 R-454B 13,000 3,100 93.0 74.8 11.7 13,000 2.10 980 13.4 15 0.11 4 1 3.1 80.0 67.0 56.5 55.4 469 329 70.0 87.5 72.0 SCR 460 / 3 131 / 150 86.6 N Y 5,680 ALL
GENERAL NOTES:
A) PROVIDE DOWNFLOW SUPPLY / UPFLOW RETURN AIRFLOW CONFIGURATION WITH POWER EXHAUST FAN.
B) PROVIDE UNIT WITH 0-100% ENTHALPY ECONOMIZER.
C) PROVIDE 4" MERV 13 FILTERS.
D) PROVIDE STAINLESS STEEL DRIP PAN AND COOLING COIL CASING.
E) PROVIDE HINGED AND LATCHED ACCESS DOORS THAT DO NOT REQUIRE TOOLS FOR ACCESS.
F) COMMUNICATION INTERFACE SHALL BE BACNET.
G) EQUIPMENT SHALL MEET OR EXCEED MINIMUM EFFICIENCY REQUIREMENTS OF IEER 13.2 (ASHRAE 90.1-2022).
H) PROVIDE NEMA 3R DISCONNECT SWITCH MOUNTED ON UNISTRUT FRAMING, INSTALLED INDEPENDENTLY OF THE AHU CABINET AND ROOF CURB.
I) PROVIDE UNIT-MOUNTED WEATHERPROOF GFCI 120V DUPLEX CONVENIENCE RECEPTACLE.
J) PROVIDE CURB ADAPTER.
K) OPERATING WEIGHT REPRESENTS RTU ONLY AND DOES NOT INCLUDE CURB ADAPTER.
L) MAXIMUM COMBINED WEIGHT OF ROOFTOP UNIT AND CURB ADAPTER SHALL NOT EXCEED 6,800 LB. WHERE THE COMBINED INSTALLED WEIGHT EXCEEDS THIS LIMIT, THE CONTRACTOR SHALL PROVIDE STRUCTURAL ANALYSIS AND DESIGN, AND SHALL FURNISH AND INSTALL ALL REQUIRED SUPPLEMENTAL STRUCTURAL REINFORCEMENT TO SAFELY SUPPORT THE IMPOSED LOADS.
M) PROVIDE UNIT EXHAUST FAN WITH MULTI-STAGE POWER EXHAUST WITH BUILDING PRESSURE CONTROL.
N) PROVIDE FACTORY FURNISHED RETURN AIR HUMIDITY SENSOR TO FACILITATE COOLING-ONLY DEHUMIDIFICATION MODE. COOLING-ONLY DEHUMIDIFICATION MODE SHALL BE IMPLEMENTED USING THE UNIT MANUFACTURER'S NATIVE CONTROLLER LOGIC.
O) PROVIDE ECONOMIZER FAULT DETECTION AND DIAGNOSTIC SYSTEM (FDDS) AS STANDARD FEATURE.
P) MINIMUM SYSTEM OUTSIDE AIRFLOW WITH ALL TERMINAL UNITS IN DEMAND CONTROL VENTILATION MODE SHALL BE 1,100 CFM AS CALCULATED IN MECHANICAL VENTILATION CALCULATIONS, DEMAND CONTROL VENTILATION - ASHRAE 62.1 TABLE BELOW.
WSP USA Buildings Inc wsp.com
1300 N 17TH ST, SUITE 1000
ARLINGTON VA, 22209
(202) 362-2800
NO. REVISION DATE
SCALE:
DWN. BY:
VCCS PROJECT NO.:
WSP PROJECT NO.:
CKD. BY:
OWNER NAME:
PROJECT TITLE:
TITLE
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL TAKE PRECEDENCE OVER
SCALED DIMENSIONS. THESE DRAWING SHALL BE COPIED FROM THE ORIGINAL
BLUEPRINTS AND ARE APPROXIMATELY TO SCALE. IT IS THE CONTRACTORS
RESPONSIBILITY TO VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND
CONDITIONS ON THE PROJECT AND SHALL NOTIFY THE ENGINEER OF ANY
VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THESE
DRAWINGS.
N.T.S.
MEP Engineer:
PROJECT CODE:
Commissioning Agent:
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
US0027294.0531
260-B6260-003
MT MLH
VCCS - NORTHERN
VIRGINIA COMMUNITY
COLLEGE
MTS REPLACE ROOF
TOP UNIT
SCHEDULES AND
CALCULATIONS
ME-002
PROJECT ADDRESS:
10500 BATTLEVIEW PKWY
MANASSAS, VIRGINIA 20109
260-B6260-003
MECHANICAL VENTILATION CALCULATIONS - ASHRAE 62.1
1.
NOTES:
ZONE POPULATION IS BASED ON THE LARGEST OF THE DESIGN OCCUPANCY AND THE OCCUPANCY
CALCULATED USING DESIGNATED IMC / ASHRAE DEFAULT OCCUPANCY RATE UNLESS OTHERWISE
NOTED.
MECHANICAL VENTILATION CALCULATIONS, DEMAND CONTROL
VENTILATION - ASHRAE 62.13
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
MICHAEL L.
HATHORNE
Lic. No. 0402066441
TYPICAL RUNS FOR BRANCH CIRCUIT
MAXIMUM VOLTAGE DROP OF 3% BASED
ON COPPER:
CONDUCTOR SIZE
#12
#10
#8
#4
#3
#2
#12
#10
#8
#6
#4
#3
#2
#6
VOLTAGE PHASE CURRENT IN AMPS
MAXIMUM
DISTANCE IN
FEET
3 PHASE CONDUCTORS
WIRING SCHEDULE - COPPER CONDUCTORS (0-600V)
CIRCUIT
RATING
CONDUIT SIZE (INCHES) CONDUCTOR SIZE
G NG NGI NNG NNGI PHASE/
NEUTRAL
GND/*
IG
20 0.75 0.75 0.75 0.75 0.75 12 12
30 0.75 0.75 0.75 0.75 0.75 10 10
40 0.75 0.75 0.75 1 1 8 10
50 0.75 0.75 0.75 1 1 8 10
60 0.75 1 1 1 1.25 6 10
70 1 1.25 1.25 1.25 1.5 4 8
80 1 1.25 1.25 1.25 1.5 4 8
90 1.25 1.25 1.25 1.5 1.5 3 8
100 1.25 1.25 1.25 1.5 1.5 3 8
110 1.25 1.25 1.5 1.5 2 2 6
125 1.25 1.5 2 2 2 1 6
150 1.5 2 2 2 2.5 1/0 6
175 2 2 2 2.5 2.5 2/0 6
200 2 2.5 2.5 2.5 2.5 3/0 6
225 2 2.5 2.5 2.5 3 4/0 4
250 2.5 2.5 2.5 3 3 250 4
300 2.5 2.5 3 3 3 350 4
350 3 3 3.5 4 4 500 3
45 0.75 0.75 0.75 1 1 8 10
225NG
SUBSCRIPT KEY
SUBSCRIPT CONDUCTORS PER CONDUIT
G 3 PHASE CONDUCTORS, 1 GROUNDING CONDUCTOR
NG 3 PHASE CONDUCTORS, 1 NEUTRAL CONDUCTOR,
1 GROUNDING CONDUCTOR
NGI 3 PHASE CONDUCTORS, 1 NEUTRAL CONDUCTOR, 1 GROUNDING
CONDUCTOR, 1 ISOLATED GROUNDING CONDUCTOR
NNG 3 PHASE CONDUCTORS, 2 NEUTRAL CONDUCTORS*,
1 GROUNDING CONDUCTOR
NNGI 3 PHASE CONDUCTORS, 2 NEUTRAL CONDUCTORS*,
1 GROUNDING CONDUCTOR, 1 ISOLATED GROUNDING CONDUCTOR
EXAMPLES
SOURCE LOAD CIRCUIT RATING SUBSCRIPT
225 NG
TYPICAL COPPER SCHEDULES NOTES:
1. SCHEDULE IS BASED ON 2020 EDITION OF THE NATIONAL ELECTRICAL CODE.
2. CURRENT CARRYING CONDUCTOR AMPACITY IS BASED ON TABLE 310.15(B)(16) 3 CURRENT CARRYING CONDUCTORS IN RACE WAY, CABLE OR EARTH AT AMBIENT AIR TEMPERATURE OF 30 DEGREES C (86 DEGREE D).
3. CURRENT CARRYING CONDUCTOR AMPACITY IS BASED ON TABLE 310.15(B)(16), COPPER WITH INSULATION VALUE OF 75 DEGREES C (167 DEGREES F) TYPES RHW, THHW, THW, THWN, XHHW, USE, ZW.
4. RACEWAY FILL SCHEDULE IS BASED ON USING COPPER CONDUCTORS WITH THHN, THWN OR THWN-2.
5. MAXIMUM FILL FOR RACEWAY IS BASED ON TABLE 1 CHAPTER 9 AND TABLE C.1 FOR ELECTRIC METAL TUBING (EMT). ADJUST FILL FOR DIFFERENT RACEWAY TYPES INCLUDING TABLE C.4 INTERMEDIATE METAL CONDUIT, (IMC), TABLE C.8 RIGID METAL CONDUIT (RMC), TABLE C.10 RIGID PVC CONDUIT -SCHEDULE 40 AS REQUIRED FOR APPLICATION AND IN ACCORDANCE WITH THE SPECIFICATION.
6. IN ACCORDANCE WITH CHAPTER 9 TABLES, NOTE 3, THE GROUND CONDUCTOR IS INCLUDED IN THE FILL CALCULATION. FOR THE PURPOSE OF THE FILL CALCULATION, THE GROUND CONDUCTOR IS ASSUMED THE SAME
TYPICAL RUNS FOR FEEDER
MAXIMUM VOLTAGE DROP OF 2% BASED
ON COPPER:
CONDUCTOR SIZE
#3
#2
#1
#2/0
#3/0
#4/0
#3
#2
#1
#1/0
#2/0
#3/0
#1/0
VOLTAGE PHASE CURRENT IN AMPS
MAXIMUM
DISTANCE IN
FEET
805#4/0
11. BRANCH CIRCUITS ARE SIZED FOR A MAXIMUM VOLTAGE DROP OF 3%. FEEDERS ARE SIZED FOR A MAXIMUM VOLTAGE DROP OF 2%.
SIZE AS THE CURRENT CARRYING CONDUCTOR.
7. FOR THE PURPOSE OF FILL CALCULATION AND CONDUCTOR RATING, THE NEUTRAL CONDUCTOR IS NOT CONSIDERED A CURRENT CARRYING CONDUCTOR AS REFERENCED IN 310.15(B)(5).
8. CONDUCTORS RUN IN PARALLEL ARE PERMITTED IN SIZE 1/0 AND LARGER AND ONLY IF RUN IN SEPARATE RACEWAYS. PARALLELED CONDUCTORS SHALL NOT BE PERMITTED TO BE RUN IN THE SAME RACEWAY EVEN IF
ALLOWED BY THE CONDUIT FILL TABLES.
9. EQUIPMENT GROUNDING CONDUCTOR RATING IS BASED ON TABLE 250.122. REFER TO NEC TABLE 250.66 FOR SERVICE ENTRANCE GROUNDING ELECTRODE CONDUCTOR RATING.
10. THE MAXIMUM ALLOWABLE CONDUCTOR SIZE SHALL BE 500KCMIL.
WSP USA Buildings Inc wsp.com
1300 N 17TH ST, SUITE 1000
ARLINGTON VA, 22209
(202) 362-2800
NO. REVISION DATE
SCALE:
DWN. BY:
VCCS PROJECT NO.:
WSP PROJECT NO.:
CKD. BY:
OWNER NAME:
PROJECT TITLE:
TITLE
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL TAKE PRECEDENCE OVER
SCALED DIMENSIONS. THESE DRAWING SHALL BE COPIED FROM THE ORIGINAL
BLUEPRINTS AND ARE APPROXIMATELY TO SCALE. IT IS THE CONTRACTORS
RESPONSIBILITY TO VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND
CONDITIONS ON THE PROJECT AND SHALL NOTIFY THE ENGINEER OF ANY
VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THESE
DRAWINGS.
N.T.S.
MEP Engineer:
PROJECT CODE:
Commissioning Agent:
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
US0027294.0531
260-B6260-003
MT Checker
VCCS - NORTHERN
VIRGINIA COMMUNITY
COLLEGE
MTS REPLACE ROOF
TOP UNIT
SCHEDULES
ME-003
PROJECT ADDRESS:
10500 BATTLEVIEW PKWY
MANASSAS, VIRGINIA 20109
260-B6260-003
EQUIPMENT SCHEDULE - MECHANICAL
NOTES: ELECTRICAL CONTRACTOR SHALL PROVIDE WIRING BETWEEN THE ELECTRICAL DISCONNECT AND THE MECHANICAL EQUIPMENT POWER CONNECTION. ELECTRICAL CONTRACTOR SHALL COORDINATE FINAL ELECTRICAL CONNECTION WITH MECHANICAL SHOP DRAWINGS
AND/OR SUBMITTALS. ALL WIRE SIZES BASED ON "NG" TYPE AS OUTLINED IN WIRING SCHEDULE. *= DESIGNATES NOT APPLICABLE
EQUIPMENT
DESIGNATION ELECTRICAL DATA
S =Motor Rated Switch*, TO = Thermal
Overload Switch
SWITCH SIZE
(AS)*
FUSE SIZE
(AF)* WIRE SIZE PANEL NAME CIRCUIT
NUMBER NOTES
TYPE NUMBER FLA VA VOLTAGE PHASE
FD = Fused Disconnect, NFD = Non-Fused Disconnect
VFD = Variable Frequency Drive, MS = Motor Starter
MSD = Motor Starter Disconnect, SP = Single Point Connection*
VFDD = Variable Frequency Drive with Disconnect
DISCONNECT TYPE
RTU 1 131 108861 VA 480 V 3 FD 200 150 150 (E) L2E Sec 2 38,40,42
SPARE LOADS CLASSIFICATION INDICATED EXISTING LOAD VALUES.
TOTAL EXISTING LOAD TO BE DEMOLISHED IN THE PANEL: 100 A.
TOTAL NEW LOAD TO BE ADDED TO THIS PANEL: 31 A.
NET LOAD: 31 A.
Notes:
Total Est. Demand Current: 305 A Total Conn. Current: 305 A
Total Est. Demand: 253872 VA Spare 145011 VA 100.00% 145011 VA Total Conn. Load: 253872 VA
HVAC 108861 VA 100.00% 108861 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 298 A 311 A 311 A Total Load: 82408 VA 85732 VA 85732 VA
41 (E) SPACE -- 1 -- 36287 VA -- -- -- 42
39 (E) SPACE -- 1 -- 36287 VA -- -- -- 40
37 (E) SPACE -- 1 -- 36287 VA 3 150 A RTU-1 38
35 -- -- -- 3833 VA 3833 VA -- -- -- 36
33 -- -- -- 3833 VA 3833 VA -- -- -- 34
31 (E) VAV 20 A 3 3833 VA 3833 VA 3 15 A (E) VAV 32
29 -- -- -- 3066 VA 2700 VA -- -- -- 30
27 -- -- -- 3066 VA 2700 VA -- -- -- 28
25 (E) VAV 20 A 3 3066 VA 2700 VA 3 15 A (E) VAV 26
23 -- -- -- 14965 VA 0 VA -- -- -- 24
21 -- -- -- 14965 VA 0 VA 2 30 A (E) SPARE 22
19 (E) PANEL P2E SEC 1, 2, 3 90 A 3 14965 VA 0 VA -- -- -- 20
17 -- -- -- 0 VA 0 VA 2 30 A (E) SPARE 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 (E) SPARE 20 A 3 0 VA 0 VA -- -- -- 14
11 (E) FLOOD LIGHTS / WALL PACKS 20 A 1 3324 VA 0 VA 3 25 A (E) SPARE 12
9 (E) SPACE -- 1 -- 3324 VA 1 20 A (E) WATER HEATER BATHROOM 10
7 (E) EAST LIGHTING 20 A 1 3324 VA 14400 VA -- -- -- 8
5 (E) EAST LIGHTING 20 A 1 3324 VA 14400 VA -- -- -- 6
3 (E) EAST LIGHTING 20 A 1 3324 VA 14400 VA 3 70 A (E) RTU-5 4
1 (E) SPACE -- 1 -- -- 1 -- (E) SPACE 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
EXISTING PANELBOARD: SIEMENS - CDP-7
Notes:
Enclosure: Type 1 MCB Rating: -- Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Main SWBD Phases: 3 Mains Type: MLO Location: East Elec Rm, 2nd Floor Volts: 480/277 WYE A.I.C. Rating: 14 kAIC
Branch Panel: (E) L2E Sec 2
EXISTING SPARE CIRCUIT BREAKER PROVIDED FROM EXISTING CONDITION
EXISTING SPACE PROVIDED FROM EXISTING CONDITION
PROVIDE NEW CIRCUIT BREAKER PER RATINGS INDICATED TO REPLACE EXISTING SPARE CIRCUIT BREAKER OR SPACE UNDER CURRENT PROJECT SCOPE OF WORK
EXISTING CIRCUIT TO BE REMOVED UNDER THIS PACKAGE
PANELBOARD NOTES
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
MICHAEL L.
HATHORNE
Lic. No. 0402066441
A
B
C
D
11 12 13 14 15 16 17 18
WSP USA Buildings Inc wsp.com
1300 N 17TH ST, SUITE 1000
ARLINGTON VA, 22209
(202) 362-2800
SHEET NOTES GENERAL NOTES
NO. REVISION DATE
SCALE:
DWN. BY:
VCCS PROJECT NO.:
WSP PROJECT NO.:
CKD. BY:
OWNER NAME:
PROJECT TITLE:
TITLE
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL TAKE PRECEDENCE OVER
SCALED DIMENSIONS. THESE DRAWING SHALL BE COPIED FROM THE ORIGINAL
BLUEPRINTS AND ARE APPROXIMATELY TO SCALE. IT IS THE CONTRACTORS
RESPONSIBILITY TO VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND
CONDITIONS ON THE PROJECT AND SHALL NOTIFY THE ENGINEER OF ANY
VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THESE
DRAWINGS.
MEP Engineer:
PROJECT CODE:
Commissioning Agent:
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
3/32" = 1'-0"
US0027294.0531
260-B6260-003
MT MLH
VCCS - NORTHERN
VIRGINIA COMMUNITY
COLLEGE
MTS REPLACE ROOF
TOP UNIT
OVERALL PLAN
ME-101
PROJECT ADDRESS:
10500 BATTLEVIEW PKWY
MANASSAS, VIRGINIA 20109
260-B6260-003
3/32" = 1'-0"
OVERALL PLAN
A.
B.
C.
D.
E.
THE NEW ROOFTOP EQUIPMENT MAY BE MOUNTED ON THE EXISTING ROOF CURB
OR CURB ADAPTER, IF COMPATIBLE. OTHERWISE, DEMOLISH CURB ADAPTER AND
PROVIDE NEW CURB ADAPTER DESIGNED FOR PROPOSED NEW EQUIPMENT.
COORDINATE INSTALLATION TIMING WITH THE OWNER.
COORDINATE THE OWNER'S REQUIREMENTS FOR POSITIONING OF THE MAIN CAB
AND PROTECTION OF THE OWNER'S GROUNDS.
CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS FOR CRANE RIGGING, ROAD
CLOSURES, ELECTRICAL WORK, AND THE REPLACEMENT OF EQUIPMENT.
CONTRACTOR SHALL NOT VOID ANY ROOF WARRANTIES. ROOFING SERVICE
COMPANY SHALL INSPECT THE ROOF PRIOR TO AND AFTER CONSTRUCTION FOR
DAMAGES CAUSED BY THE PROJECT. ROOFING WILL BE REPAIRED / RESTORED
AT CONTRACTOR'S EXPENSE.
F. REFER TO THE TABLE ON SHEET ME-301 FOR THE LIST OF SPACES SERVED BY
THE EXISTING RTU AND THE CORRESPONDING AIRFLOW QUANTITIES. THE
INFORMATION PRESENTED IN THE SHEET ME-301 TABLE IS BASED ON 2015
CONSTRUCTION DOCUMENTS AND IT IS PROVIDED FOR REFERENCE ONLY.
G. BALANCE ASSOCIATED SYSTEM ACCORDING TO PREVIOUSLY PERMITTED
AIRFLOWS AS INDICATED IN NOTE F.
H. CONTRACTOR SHALL PROVIDE A MINIMUM 7-DAY NOTICE TO THE CxA AND A/E
PRIOR TO THE RTU START-UP AND FUNCTIONAL TESTING.
I. BEFORE CxA SITE VISIT, ALL PRE-FUNCTIONAL CHECKLISTS, START-UP REPORTS, AND BAS INTEGRATION MUST BE VERIFIED BY THE CONTRACTOR AS 'COMPLETE'.
N
J. CONTRACTOR MUST PROVIDE WALKWAY PADS OR PLYWOOD
PROTECTION FROM THE ROOF HATCH OR ROOF ACCESS TO THE UNIT
TO PREVENT DAMAGE TO THE EXISTING MEMBRANE DURING THE
"TURNKEY" INSTALLATION.
K. COORDINATE NOISY WORK OR CRANE LIFTS A WEEK IN ADVANCE TO
AVOID DISRUPTING CLASSES
08' 4'
SCALE: 3/32" = 1' - 0"
GRAPHIC SCALE
8' 16' 32'24'
G. BALANCE ASSOCIATED SYSTEM ACCORDING TO PREVIOUSLY PERMITTED
AIRFLOWS AS INDICATED IN NOTE F.
H. CONTRACTOR SHALL PROVIDE A MINIMUM 7-DAY NOTICE TO THE CxA AND A/E
PRIOR TO THE RTU START-UP AND FUNCTIONAL TESTING.
I. BEFORE CxA SITE VISIT, ALL PRE-FUNCTIONAL CHECKLISTS, START-UP REPORTS, AND BAS INTEGRATION MUST BE VERIFIED BY THE CONTRACTOR AS 'COMPLETE'.
ANY RE-TESTING REQUIRED DUE TO INCOMPLETE INSTALLATION WILL BE AT THE
CONTRACTOR'S EXPENSE.
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
MICHAEL L.
HATHORNE
Lic. No. 0402066441
A
B
C
D
11 12 13 14 15 16 17 18
(X)RTU
(E)RTU
(E)RTU
(E)RD
(E)RD
(E) L2E Sec 2/ 38,40,42
(X) RTU-1
S
S
(E)ROOF HATCH
A
B
C
D
11 12 13 14 15 16 17 18
RTU
2 3
(E)RTU
(E)RTU
2 4
(E)RD (E)RD
1 1/4" D
S
S
(E) L2E Sec 2/ 38,40,42
RTU-1
5 GFCI
WP (E)
(E)ROOF HATCH
(E)
(E)
WSP USA Buildings Inc wsp.com
1300 N 17TH ST, SUITE 1000
ARLINGTON VA, 22209
(202) 362-2800
NO. REVISION DATE
SCALE:
DWN. BY:
VCCS PROJECT NO.:
WSP PROJECT NO.:
CKD. BY:
OWNER NAME:
PROJECT TITLE:
TITLE
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL TAKE PRECEDENCE OVER
SCALED DIMENSIONS. THESE DRAWING SHALL BE COPIED FROM THE ORIGINAL
BLUEPRINTS AND ARE APPROXIMATELY TO SCALE. IT IS THE CONTRACTORS
RESPONSIBILITY TO VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND
CONDITIONS ON THE PROJECT AND SHALL NOTIFY THE ENGINEER OF ANY
VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THESE
DRAWINGS.
MEP Engineer:
GENERAL NOTES
KEYNOTES
PROJECT CODE:
Commissioning Agent:
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
1/8" = 1'-0"
US0027294.0531
260-B6260-003
MT MLH
VCCS - NORTHERN
VIRGINIA COMMUNITY
COLLEGE
MTS REPLACE ROOF
TOP UNIT
ROOF PLANS
ME-201
PROJECT ADDRESS:
10500 BATTLEVIEW PKWY
MANASSAS, VIRGINIA 20109
260-B6260-003
1 REMOVE EXISTING RTU AND ASSOCIATED ACCESSORIES. EXISTING SMOKE
DETECTOR TO REMAIN.
2 PROVIDE NEW ROOF TOP UNIT RTU-1 AS SCHEDULED. PROVIDE NEW ADAPTER
CURB TO ACCOMMODATE NEW RTU-1. THE NEW UNIT AND CURB ADAPTER WILL
SIT ON AN EXISTING CURB WITH GASKETING AND SHALL BE INSTALLED PER
MANUFACTURER'S RECOMMENDATIONS.
3 THIS UNIT SERVES THE SECOND FLOOR EAST SPACES.
4 ROUTE PIPING DOWN TO ROOF AND DISCHARGE AT ROOF DRAIN. PROVIDE ROOF
PIPING SUPPORT PER SPECIFICATION 232113.
5 EXISTING VERTICAL SUPPLY AND RETURN AIR DUCTWORK AND SMOKE
DETECTORS SHOWN FOR REFERENCE ONLY. FIELD VERIFY EXACT DUCTWORK
LOCATION AND ADJUST CURB ADAPTER REQUIREMENTS AS NEEDED.
6 PROVIDE NEW EPDM PRESSURE-SENSITIVE MOLDED WALKWAY PADS AS SHOWN.
7 REFER TO ROOM 200-J ELECTRICAL FOR PANEL L2E ON SHEET ME-301.
1/8" = 1'-0"
ROOF DEMOLITION PLAN - EAST
1/8" = 1'-0"
ROOF NEW WORK PLAN - EAST
1 A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
THE NEW ROOFTOP EQUIPMENT MAY BE MOUNTED ON THE EXISTING ROOF
CURB OR CURB ADAPTER, IF COMPATIBLE. OTHERWISE, DEMOLISH CURB
ADAPTER AND PROVIDE NEW CURB ADAPTER DESIGNED FOR PROPOSED NEW
EQUIPMENT.
COORDINATE INSTALLATION TIMING WITH THE OWNER.
COORDINATE THE OWNER'S REQUIREMENTS FOR POSITIONING OF THE MAIN
CAB AND PROTECTION OF THE OWNER'S GROUNDS.
CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS FOR CRANE RIGGING, ROAD
CLOSURES, ELECTRICAL WORK, AND THE REPLACEMENT OF EQUIPMENT.
CONTRACTOR SHALL NOT VOID ANY ROOF WARRANTIES. ROOFING SERVICE
COMPANY SHALL INSPECT THE ROOF PRIOR TO AND AFTER CONSTRUCTION
FOR DAMAGES CAUSED BY THE PROJECT. ROOFING WILL BE REPAIRED /
RESTORED AT CONTRACTOR'S EXPENSE.
REFER TO THE TABLE ON SHEET ME-301 FOR THE LIST OF SPACES SERVED BY
THE EXISTING RTU AND THE CORRESPONDING AIRFLOW QUANTITIES. THE
INFORMATION PRESENTED IN THE SHEET ME-301 TABLE IS BASED ON 2015
CONSTRUCTION DOCUMENTS AND IT IS PROVIDED FOR REFERENCE ONLY.
BALANCE ASSOCIATED SYSTEM ACCORDING TO PREVIOUSLY PERMITTED
AIRFLOWS AS INDICATED IN NOTE F.
CONTRACTOR SHALL PROVIDE A MINIMUM 7-DAY NOTICE TO THE CxA AND A/E
PRIOR TO THE RTU START-UP AND FUNCTIONAL TESTING.
BEFORE CxA SITE VISIT, ALL PRE-FUNCTIONAL CHECKLISTS, START-UP
REPORTS, AND BAS INTEGRATION MUST BE VERIFIED BY THE CONTRACTOR AS
'COMPLETE'. ANY RE-TESTING REQUIRED DUE TO INCOMPLETE INSTALLATION
WILL BE AT THE CONTRACTOR'S EXPENSE.
CONTRACTOR MUST PROVIDE WALKWAY PADS OR PLYWOOD PROTECTION
FROM THE ROOF HATCH OR ROOF ACCESS TO THE UNIT TO PREVENT DAMAGE
TO THE EXISTING MEMBRANE DURING THE "TURNKEY" INSTALLATION.
COORDINATE NOISY WORK OR CRANE LIFTS A WEEK IN ADVANCE TO AVOID
DISRUPTING CLASSES.
GFCI
WP (E)
N
N
08' 4'
SCALE: 1/8" = 1' - 0"
GRAPHIC SCALE
8' 16' 24'
08' 4'
SCALE: 1/8" = 1' - 0"
GRAPHIC SCALE
8' 16' 24'
(E)
(E)
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
MICHAEL L.
HATHORNE
Lic. No. 0402066441
WZPE24
WZPE24
WZPE24
WZPE24
6 7 8 9 10
16 17 18 19 20
A2
A1 A2
DN
DN
A
B
C
D
161514131211
MICRO
T
F
A
B
C
D
11 12 13 14 15 16 17
(E) L2E Sec 1
(E) L2E Sec 2
(E) P2E Sec 1
(E) P2E Sec 2
(E) P2E Sec 3
206 - WORKFORCE
SUITE
205 - WORK/COPY
203 -
SECURITY/ADMIN
OFFICE
213 - MENS
RESTROOM
214 - WOMENS
RESTROOM
217 - OFFICE218 - WORK/COPY
215 - SYSTEMIC
SOLUTION SUITE
216 - STORAGE
CLOSET
222 - ROBOTIC
CLASSROOM
221 - ROBOTICS
STORAGE 220 - STUDY NOOK
230 - TRAINING
CLASSROOM
231 - TRAINING
CLASSROOM
232 - TRAINING
CLASSROOM
234 - STUDENT
LOUNGE
200-J - EXISTING
ELECTRICAL
210 - NETWORK
CLOSET
209 - STORAGE
CLOSET
211 - CORRIDOR 219 - CORRIDOR
208 - CORRIDOR
204 - SKILL SOURCE
SUITE
200 - ATRIUM
281 - TRAINING SUITE
233 - STUDY NOOK
223 - ROBOTIC
CLASSROOM
229 - WORKFORCE
CLASSROOM
278 - CORRIDOR
TABLE 1.1 - LIST OF ROOMS AND CORRESPONDING AIRFLOWS SERVED BY EXISTING RTU
VAV
DESIGNATION
ROOM
NUMBER ROOM NAME
OUTLET AIRFLOW DATA
TOTAL CFM NUMBER OF SUPPLY
AIR DIFFUSERS COMMENT
VAV 200 ATRIUM 1100 3 3x375 CFM DIFFUSERS AT ATRIUM WALL
VAV
203 SECURITY ADMIN 100 1 1X100 CFM DIFFUSER
211 CORRIDOR 100 1 1X100 CFM DIFFUSER BY ATRIUM
213 MENS RESTROOM 75 1 1X75 CFM DIFFUSER AT DOOR
234 STUDENT LOUNGE 1200 4 4X300 CFM DIFFUSERS
VAV 204, 205 SKILL SOURCE 1350 6
3X250 CFM DIFFUSERS AT WINDOWS
3X200 CFM DIFFUSERS CENTER OF ROOM
218 WORK/COPY 250 1 1X250 CFM DIFFUSER AT WINDOWS
VAV 206 WORKFORCE 1100 4 4X275 CFM DIFFUSERS AT WINDOWS
VAV
208 CORRIDOR 100 1 1X100 CFM DIFFUSER
209 STORAGE CLOSET 50 1 1X50 CFM DIFFUSER
273 CORRIDOR 75 1 1X75 CFM DIFFUSER
281 TRAINING SUITE 675 3 3X225 CFM DIFFUSERS
VAV
215 SYSTEMIC SOLUTIONS 250 2 2X250 CFM DIFFUSERS BY CORRIDORS
216 STORAGE CLOSET 50 1 1X50 CFM DIFFUSER
219 CORRIDOR 250 1 1X150 CFM DIFFUSER AT ROOM 231 DOOR
220 STUDY NOOK 200 1 1X200 CFM DIFFUSER IN CORRIDOR
221 ROBOTIC STORAGE 150 1 1X150 CFM DIFFUSER
VAV
217 OFFICE 200 1 1X200 CFM DIFFUSER
222 ROBOTIC CLASSROOM 1200 4 4X300 CFM DIFFUSERS
VAV 229 CLASSROOM 1500 4 4X375 CFM DIFFUSERS
VAV 230 CLASSROOM 1500 4 4X375 CFM DIFFUSERS
VAV
214 WOMENS RESTROOM 75 1 1X75 CFM DIFFUSER AT DOOR
231 CLASSROOM 1500 4 4X375 CFM DIFFUSERS
VAV 232 CLASSROOM 1600 4 4X400 CFM DIFFUSERS
GENERAL:
A. THE INFORMATION PRESENTED IN THIS TABLE WAS DERIVED FROM THE EXISTING CONSTRUCTION DOCUMENTS DATED JULY 6, 2015 AND IS PROVIDED FOR REFERENCE PURPOSES ONLY. FIELD VERIFICATION OF ALL EXISTING CONDITIONS IS REQUIRED PRIOR TO CONSTRUCTION.
B. RETURN AIR GRILLES ASSOCIATED WITH THE SPACES IDENTIFIED IN THIS TABLE ARE CONNECTED TO THE EXISTING RETURN AIR PLENUM SYSTEM. AS PART OF A PLENUM RETURN CONFIGURATION, THESE RETURN AIR DEVICES ARE NOT INDIVIDUALLY BALANCED AND NO RETURN
AIRFLOW QUANTITIES ARE ASSOCIATED WITH THE GRILLES.
C. REFER TO EXISTING BUILDING AUTOMATION SYSTEM FOR VAV BOX DESIGNATION.
WSP USA Buildings Inc wsp.com
1300 N 17TH ST, SUITE 1000
ARLINGTON VA, 22209
(202) 362-2800
NO. REVISION DATE
SCALE:
DWN. BY:
VCCS PROJECT NO.:
WSP PROJECT NO.:
CKD. BY:
OWNER NAME:
PROJECT TITLE:
TITLE
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL TAKE PRECEDENCE OVER
SCALED DIMENSIONS. THESE DRAWING SHALL BE COPIED FROM THE ORIGINAL
BLUEPRINTS AND ARE APPROXIMATELY TO SCALE. IT IS THE CONTRACTORS
RESPONSIBILITY TO VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND
CONDITIONS ON THE PROJECT AND SHALL NOTIFY THE ENGINEER OF ANY
VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THESE
DRAWINGS.
MEP Engineer:
GENERAL NOTES
KEYNOTES
PROJECT CODE:
Commissioning Agent:
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
As indicated
US0027294.0531
260-B6260-003
MT MLH
VCCS - NORTHERN
VIRGINIA COMMUNITY
COLLEGE
MTS REPLACE ROOF
TOP UNIT
PARTIAL FLOOR
PLANS
ME-301
PROJECT ADDRESS:
10500 BATTLEVIEW PKWY
MANASSAS, VIRGINIA 20109
260-B6260-003
A.
B.
REFER TO THE TABLE ON SHEET ME-301 FOR THE LIST OF SPACES
SERVED BY THE EXISTING RTU AND THE CORRESPONDING
AIRFLOW QUANTITIES. THE INFORMATION PRESENTED IN THE
SHEET ME-301 TABLE IS BASED ON 2015 CONSTRUCTION
DOCUMENTS AND IT IS PROVIDED FOR REFERENCE ONLY.
BALANCE ASSOCIATED SYSTEM ACCORDING TO PREVIOUSLY
PERMITTED AIRFLOWS AS INDICATED IN NOTE A.
1/8" = 1'-0"
SECOND FLOOR NEW WORK PLAN
N
1 PROVIDE A SPARE FUSE CABINET IN THE ELECTRICAL CLOSET. PROVIDE 1
COMPLETE SET OF FUSES FOR EACH TYPE OF FUSES USED FOR THIS PROJECT.
08' 4'
SCALE: 1/8" = 1' - 0"
GRAPHIC SCALE
8' 16' 24'
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
MICHAEL L.
HATHORNE
Lic. No. 0402066441
SUSPENDED CEILINGS CAVITY.
SUSPENDED CEILINGS.
OCCUPIED SPACE.
SUSPENDED CEILINGS CAVITY.
SUSPENDED CEILINGS.
OCCUPIED SPACE.
150G
3 5
150AF
200AS
(E) 1600A MAIN
SWITCHBOARD
480/277V 3ɸ-4W
480/277V 3ɸ-4W 400A
DEMO RISER NEW WORK RISER
(E) 1600A MAIN
SWITCHBOARD
480/277V 3ɸ-4W
480/277V 3ɸ-4W 400A
EAST ELEC RM EAST ELEC RM
MAIN ELEC RMMAIN ELEC RM
RTU-1
WP
M M
T F
XFMR
75kVA
M M
(E) (E) (E) (E) (E)
(E) (E)
(E)
(E)
(E) (E) (E) (E) (E)
(E) (E)(E) (E)
(E)(E)
(E) (E) (E) (E)
125AF
200AS
ELEVATION:
LEVEL 2
ELEVATION:
ROOF
ELEVATION:
ROOF
ELEVATION:
LEVEL 2
ELEVATION:
LEVEL 1
ELEVATION:
LEVEL 1
T F
XFMR
75kVA
PNL
L2E
SEC 1
L2E
ELEVATION:
LEVEL 2
ELEVATION:
ROOF
ELEVATION:
ROOF
ELEVATION:
LEVEL 2
ELEVATION:
LEVEL 1
ELEVATION:
LEVEL 1
PNL
L2E
SEC 2
PNL
P2E
SEC 1
PNL
P2E
SEC 2
PNL
P2E
SEC 3
(E) (E)
(E)
(E)
PNL
L2E
SEC 1
PNL
L2E
SEC 2
PNL
P2E
SEC 1
PNL
P2E
SEC 2
PNL
P2E
SEC 3
L2E
RTU-1
WP
WSP USA Buildings Inc wsp.com
1300 N 17TH ST, SUITE 1000
ARLINGTON VA, 22209
(202) 362-2800
SHEET NOTES GENERAL NOTES
NO. REVISION DATE
SCALE:
DWN. BY:
VCCS PROJECT NO.:
WSP PROJECT NO.:
CKD. BY:
OWNER NAME:
PROJECT TITLE:
TITLE
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL TAKE PRECEDENCE OVER
SCALED DIMENSIONS. THESE DRAWING SHALL BE COPIED FROM THE ORIGINAL
BLUEPRINTS AND ARE APPROXIMATELY TO SCALE. IT IS THE CONTRACTORS
RESPONSIBILITY TO VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND
CONDITIONS ON THE PROJECT AND SHALL NOTIFY THE ENGINEER OF ANY
VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THESE
DRAWINGS.
MEP Engineer:
PROJECT CODE:
Commissioning Agent:
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
As indicated
US0027294.0531
260-B6260-003
MT MLH
VCCS - NORTHERN
VIRGINIA COMMUNITY
COLLEGE
MTS REPLACE ROOF
TOP UNIT
RISERS
ME-501
PROJECT ADDRESS:
10500 BATTLEVIEW PKWY
MANASSAS, VIRGINIA 20109
260-B6260-003
N.T.S.
RISER
1 REMOVE EXISTING FUSED DISCONNECT.
2 EXISTING FEEDER FROM PANEL L2E SEC 2. DEMO EXISTING CONDUCTORS AND
CONDUIT.
3 REMOVE THE CONDUIT FROM THE PITCH POCKET. SEAL AD MAKE WATER TIGHT.
4 REMOVE THE ASSOCIATED CIRCUIT BREAKER IN PANEL L2E.
5 ROUTE NEW FEEDER WITHIN THE CURB CONFINES. SEAL THE CURB PENETRATION
WATER TIGHT.
6 PROVIDE FIELD MARKING INDICATING THE UNIT HAS 10KAIC SCCR RATING.
7 AREA FOR DEMOLITION OF THE 3-1/0 CU. CONDUCTOR IN 2" ELECTRIC METAL TUBING
INCLUDES SPACES WITH SUSPENDED CEILINGS.
8 AREA FOR INSTALLING NEW FEEDER INCLUDES SPACES WITH SUSPENDED CEILINGS.
A.
B.
C.
INFORMATION SHOWN IN GRAY ON THE ONE-LINE DIAGRAM REPRESENTS EXISTING
CONDITIONS THAT ARE TO REMAIN AND IS PROVIDED FOR REFERENCE ONLY.
INFORMATION SHOWN IN DASHED ON THE ONE-LINE DIAGRAM REPRESENTS
EXISTING EQUIPMENT THAT IS TO BE DEMOLISHED.
INFORMATION SHOWN IN DARK ON THE ONE-LINE DIAGRAM REPRESENTS NEW
WORK.
10030 WINDY HOLLOW RD
GREAT FALLS, VA 22066
703.731.1509
MICHAEL L.
HATHORNE
Lic. No. 0402066441
SEQUENCE OF OPERATIONS
ROOFTOP AIR CONDITIONING UNIT WITH ELECTRIC HEAT
BUILDING AUTOMATION SYSTEM INTERFACE:
THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE CONTROLLER OCCUPIED BYPASS,
MORNING WARM-UP / PRE-COOL, OCCUPIED / UNOCCUPIED AND HEAT / COOL MODES.
IF A BAS IS NOT PRESENT, OR COMMUNICATION IS LOST WITH THE BAS THE CONTROLLER SHALL
OPERATE USING DEFAULT MODES AND SETPOINTS.
THE BAS SHALL ALSO SEND THE CONTROLLER A DUCT STATIC PRESSURE SETPOINT, DISCHARGE AIR
TEMPERATURE SETPOINT, AND VENTILATION AIRFLOW SETPOINT, EACH CALCULATED BY
OPTIMIZATION ROUTINES IN THE BAS.
EXISTING BAS PROGRAMMING SHALL BE UPDATED TO ACCOMMODATE NEW EQUIPMENT WITH
CONTROLS POINTS AND GRAPHICS.
OCCUPIED MODE:
DURING OCCUPIED PERIODS, THE SUPPLY FAN SHALL RUN CONTINUOUSLY AND THE OUTSIDE AIR DAMPER SHALL OPEN TO MAINTAIN THE CURRENT AIRFLOW SETPOINT. THE UNIT CONTROLLER SHALL CONTROL THE SUPPLY FAN SPEED TO MAINTAIN THE CURRENT DUCT STATIC PRESSURE SETPOINT (ADJ.).THE DX COOLING AND ELECTRIC HEAT SHALL STAGE TO MAINTAIN THE CURRENT DISCHARGE
AIR TEMPERATURE SETPOINT. IF ECONOMIZING IS ENABLED THE OUTSIDE AIR DAMPER SHALL
MODULATE TO MAINTAIN THE CURRENT DISCHARGE AIR TEMPERATURE SETPOINT.
UNOCCUPIED MODE (VERIFY SEQUENCES ACCEPTABLE WITH EXISTING PROGRAMMING):
WHEN THE SPACE TEMPERATURE IS BELOW THE UNOCCUPIED HEATING SETPOINT OF 55.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL START, THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND THE
ELECTRIC HEAT SHALL BE ENABLED. WHEN THE SPACE TEMPERATURE RISES ABOVE THE
UNOCCUPIED HEATING SETPOINT OF 55.0 DEG. F (ADJ.) PLUS THE UNOCCUPIED DIFFERENTIAL OF 4.0
DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP AND THE ELECTRIC HEAT SHALL BE DISABLED.
WHEN THE SPACE TEMPERATURE IS ABOVE THE UNOCCUPIED COOLING SETPOINT OF 85.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL START, THE OUTSIDE AIR DAMPER SHALL OPEN IF ECONOMIZING IS
ENABLED AND REMAIN CLOSED IF ECONOMIZING IS DISABLED AND THE DX COOLING SHALL BE
ENABLED. WHEN THE SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED COOLING SETPOINT OF
85.0 DEG. F (ADJ.) MINUS THE UNOCCUPIED DIFFERENTIAL OF 4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP, THE DX COOLING SHALL BE DISABLED AND THE OUTSIDE AIR DAMPER SHALL CLOSE.
OPTIMAL START:
THE BAS SHALL MONITOR THE SCHEDULED OCCUPIED TIME, OCCUPIED SPACE SETPOINTS AND SPACE
TEMPERATURE TO CALCULATE WHEN THE OPTIMAL START OCCURS.
MORNING WARM-UP MODE (VERIFY SEQUENCES ACCEPTABLE WITH EXISTING PROGRAMMING):
DURING OPTIMAL START, IF THE AVERAGE SPACE TEMPERATURE IS BELOW THE OCCUPIED HEATING
SETPOINT A MORNING WARM-UP MODE SHALL BE ACTIVATED.
WHEN MORNING WARM-UP IS INITIATED, THE UNIT SHALL ENABLE THE HEATING AND SUPPLY FAN. THE
OUTSIDE AIR DAMPER SHALL REMAIN CLOSED.
WHEN THE AVERAGE SPACE TEMPERATURE REACHES THE OCCUPIED HEATING SETPOINT (ADJ.), THE
UNIT SHALL TRANSITION TO THE OCCUPIED MODE.
PRE-COOL MODE:
DURING OPTIMAL START, IF THE AVERAGE SPACE TEMPERATURE IS ABOVE THE OCCUPIED COOLING SETPOINT, PRE-COOL MODE SHALL BE ACTIVATED. WHEN PRE-COOL IS INITIATED, THE UNIT SHALL ENABLE THE FAN AND COOLING OR ECONOMIZER. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED, UNLESS ECONOMIZING. WHEN THE AVERAGE SPACE TEMPERATURE REACHES OCCUPIED COOLING
SETPOINT (ADJ.), THE UNIT SHALL TRANSITION TO THE OCCUPIED MODE.
OPTIMAL STOP:
THE BAS SHALL MONITOR THE SCHEDULED UNOCCUPIED TIME, OCCUPIED SETPOINTS AND SPACE TEMPERATURE TO CALCULATE WHEN THE OPTIMAL STOP OCCURS. WHEN THE OPTIMAL STOP MODE IS ACTIVE THE UNIT CONTROLLER SHALL MAINTAIN THE SPACE TEMPERATURE USING AN ADJUSTED SPACE TEMPERATURE SETPOINT BASED ON THE CURRENT MODE OF OPERATION. IN COOLING MODE, THE ACTIVE SPACE TEMPERATURE SETPOINT SHALL BE EQUAL TO THE OCCUPIED COOLING SETPOINT
PLUS THE SPACE TEMPERATURE…
This is the start of the file's text. The full file is on GovTribe.