26_05_29_-_2_Hangers_and_Supports_-_Zip_ties_and_Hangers.pdf

PDF 807 KB Posted

Attached to
LOCK 19 - UADS REPAIR and or REMOVAL
Solicitation number
140G0225R0002
Issued by

About this file

This document is a product specification for stainless steel zip ties to be used in the construction and installation of an acoustic deterrent system for the U.S. Geological Survey. The specification includes details on the part number, material, length, tensile strength, and other technical specifications for the stainless steel zip ties. It also notes that a variance is being requested to use the stainless steel zip ties instead of the aluminum zip ties originally specified. The document includes additional information on clamps and supports for rigid metal conduit and intermediate metal conduit.

The related federal contract opportunity is a solicitation from the U.S. Department of the Interior, U.S. Geological Survey, for the maintenance of a sound bar in Lock 19 with an option for removal. The solicitation is a Request for Quote (RFQ) being issued under FAR Part 12 and Part 13 procedures for simplified acquisition of commercial items. The NAICS code is 237990 - Other Heavy and Civil Engineering Construction. The solicitation requires site visits and all quotes and questions must be submitted via email to the Contracting Officer.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Hangers and Supports 26 05 29 - 2

U.S. Geological Survey Contract No. 140G0221C0001

Construct and Install Acoustic Deterrent System

Mississippi River, Lock and Dam 19 Keokuk, IA

Note: A variance is being requested to use stainless steel instead of instead of the Aluminum zip ties specified in General Electrical Note 15 on drawing E-001. We are submitting Stainless because it is stronger, more durable, and readily available

Specification Sheet Part Number: MBT14S-S

Stainless Steel Tie, 14.3" Long, 202lb Tensile Strength, SS304, Metal, 100/pkg

Article Number 111-93148

Type MBT14SS

Color Metal (ML)

Features & Benefits • 304 grade stainless steel offers excellent resistance to corrosion, weather and chemical resistance. • Self locking, ball bearing mechanism assures high tensile strength and easy insertion. • Fully enclosed head does not allow dirt or grit to interfere with locking mechanism. • High tensile strength for dependability and safety on heavy duty applications.

Quantity Per bag https://www.hellermanntyton.us/ nathan Approval nathan Typewritten Text

NAN

nathan Typewritten Text 12-29-2020 nathan Typewritten Text X

Product Description HellermannTyton’s stainless steel ties are designed with a ball bearing locking mechanism to assure high tensile strength and easy insertion when securing hoses, cables, pipes and more. Available in 304 or 316 grades of stainless steel, providing protection when used in corrosive environments, fire resistance and temperature extremes.

Short Description Stainless Steel Tie, 14.3" Long, 202lb Tensile Strength, SS304, Metal, 100/pkg

Global Part Name MBT14SS-SS304-SR

Minimum Tensile Strength (Imperial) 202.0

Minimum Tensile Strength (Metric) 900.0

Length L (Imperial) 14.3

Length L (Metric) 362.0

Identification Plate Position none

Releasable Closure No

Tie Closure ball bearing lock

Variant No Serration

Width W (Imperial) 0.18

Width W (Metric) 4.6

Bundle Diameter Min (Imperial) 0.67

Bundle Diameter Min (Metric) 17.0

Bundle Diameter Max (Imperial) 4.0

Bundle Diameter Max (Metric) 102.0

Thickness T (Imperial) 0.01

Thickness T (Metric) 0.3

Material Stainless Steel (SS304)

Material Shortcut SS304

Flammability Non-Burning

Halogen Free Yes

Operating Temperature -112°F to +1000°F (-80°C to +538°C)

Reach Compliant (Article 33) Yes

ROHS Compliant Yes

Package Quantity (Imperial) 100

Package Quantity (Metric) 100

Customs Number 7326908695

Weight (Metric) 4.3

© 2020 HellermannTyton. All Rights Reserved.

Contact Us RoHS/WEEE Compliance Disclaimer Terms and Conditions https://www.hellermanntyton.us/contactus https://www.hellermanntyton.us/rohs-weee-compliance https://www.hellermanntyton.us/disclaimer https://www.hellermanntyton.us/terms-and-conditions

Effective September, 2005 Copyright 2005

800-621-1506 www.appletonelec.com

I- 35 I

K- Clamps for RMC or IMC

Applications

• Designed to secure RMC, IMC or EMT across, parallel or perpen-dicular to channel, beam and angle supports.

Features

• Three styles meet every installation need.

• Heavy duty U-bolts, hex bolts and hex nuts.

• Capable of supporting heavy loads.

Standard Materials

• Clamps—malleable iron.

• Nuts and bolts—steel.

Standard Finishes

• Hot dipped/mechanically galvanized.

Size Range

• Right Angle type—1/2” thru 6”.

• Parallel type—1/2” thru 4”.

• Edge type—1/2” thru 3”.

Compliances

• UL listing not applicable.

• CSA Standard C22.2 No. 18

Catalog Size Number (In.)

Right Angle Type

PC-50RA 1/2

PC-75RA 3/4

PC-100RA 1

PC-125RA 1-1/4

PC-150RA 1-1/2

PC-200RA 2

PC-250RA 2-1/2

PC-300RA 3

PC-350RA 3-1/2

PC-400RA 4

PC-500RA 5

PC-600RA 6

Catalog Size Number (In.)

Parallel Type

PC-50PAR 1/2

PC-75PAR 3/4

PC-100PAR 1

PC-125PAR 1-1/4

PC-150PAR 1-1/2

PC-200PAR 2

PC-250PAR 2-1/2

PC-300PAR 3

PC-350PAR 3-1/2

PC-400PAR 4

Catalog Size Number (In.)

Edge Type

PC-50ET 1/2

PC-75ET 3/4

PC-100ET 1

PC-125ET 1-1/4

PC-150ET 1-1/2

PC-200ET 2

PC-250ET 2-1/2

PC-300ET 3

nathan Cloud nathan Approval nathan Typewritten Text x nathan Typewritten Text

NAN

nathan Typewritten Text 12-23-2020

Effective September, 2005 Copyright 2005

800-621-1506 www.appletonelec.com

I- 36

I

Clamps and Clamp Backs for RMC, IMC and EMT Malleable Iron One-Hole Clamps and Clamp Backs and Steel One-Hole Clamps.

Applications

• Used to support runs of RMC, IMC and EMT.

NOTE: 2-1/2” thru 4” sizes also suitable for EMT.

Features

• Malleable iron clamps and clamp backs are exceptionally rugged and strong.

• Steel clamps offer economy and have integrally formed gussets for ex-cellent strength.

Standard Material

• Malleable iron or steel.

Standard Finish

• Malleable iron clamps and clamp backs— hot dipped galvanized.

• Steel One-hole clamps—zinc elec-troplate.

Size Range

• Malleable iron clamps and clamp backs—1/2” thru 6”.

• Steel one-hole clamp—1/4” thru 4”.

Compliances

• UL listing not applicable

• CSA Standard C22.2 No. 18 applies to malleable iron clamps and clamp backs thru 6”.

Catalog Size Dimensions (Inches) Recommended Number (In.) A B C Bolt Dia. (In.)

One-Hole Clamps—Malleable Iron

CL-50MN 1/2 1 15/16 5/8 1/4

CL-75MN 3/4 1-3/16 1-7/32 3/4 1/4

CL-100MN 1 1-3/8 1-1/2 7/8 1/4

CL-125MN 1-1/4 1-5/8 1-15/16 7/8 3/8

CL-150MN 1-1/2 1-13/16 2-1/8 15/16 3/8

CL-200MN 2 2-5/6 2-5/8 1-1/16 1/2

CL-250MN 2-1/2 2-9/16 3 1-5/16 1/2

CL-300MN 3 3-3/16 3-13/16 1-1/2 1/2

CL-350MN 3-1/2 3-3/8 4-7/16 1-11/16 5/8

CL-400MN 4 3-3/4 5 1-15/16 5/8

CL-500MN 5 4-3/4 6-1/2 2-1/2 5/8

CL-600MN 6 5-5/8 7-1/2 2-3/4 1

Clamp Backs—Malleable Iron

CLB-50MN 1/2 2-7/16 7/16 1-1/16 —

CLB-75MN 3/4 2-1/2 1/2 1-1/8 —

CLB-100MN 1 3-3/16 9/16 1-5/16 —

CLB-125MN 1-1/4 3-11/16 3/4 1-7/16 —

CLB-150MN 1-1/2 3-15/16 13/16 1-9/16 —

CLB-200MN 2 5-1/8 3/4 2 —

CLB-250MN 2-1/2 5-3/4 3/4 2-1/2 —

CLB-300MN 3 7-1/8 13/16 2-13/16 —

CLB-350MN 3-1/2 8 1 3-1/4 —

CLB-400MN 4 8-3/4 1 3-7/16 —

CLB-500MN 5 10-1/16 1-1/4 3-3/4 —

CLB-600MN 6 11-13/16 1-1/2 3-15/16 —

One-Hole Clamps—Steel

CL-25 1/4 5/8 15/32 19/32 1/4

CL-38 3/8 13/16 5/8 11/16 9/32

CL-50 1/2 1 3/4 15/16 9/32

CL-75 3/4 1-5/32 3/4 1-1/8 9/32

CL-100 1 1-11/32 7/8 1-7/16 11/32

CL-125 1-1/4 1-11/16 1 1-25/32 13/32

CL-150 1-1/2 1-15/16 1-1/8 2 13/32

CL-200 2 2-11/32 1-3/16 2-17/32 15/32

CL-250 2-1/2 2-13/16 1-1/4 3-1/32 9/16

CL-300 3 3-5/16 1-1/4 3-21/32 9/16

CL-350 3-1/2 3-7/16 1-1/2 4-5/32 11/16

CL-400 4 3-25/32 1-1/2 4-21/32 11/16

Malleable One Hole Back

B

A

C

Steel Clamp

Malleable Clamp nathan Cloud nathan Cloud

CONTENTS

HDI SS 303

Approvals/Certificates

. Product Technical Guide Excerpt for HDI+, HDI-L+, HDI and HDI-L Drop-in Anc 1 nathan Typewritten Text Anchor to be used is Part # HDI SS 303 Internal Thread size 3/8" Anchor Length 1-9/16" nathan Cloud

Hilti, Inc.

7250 Dallas Parkway, Suite 1000 Plano, TX 75024

1-800-879-8000 www.hilti.com

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 19.

Please refer to the publication in its entirety for complete details on this product including data development, product specifications, general suitability, installation, corrosion and spacing and edge distance guidelines.

US&CA: https://submittals.us.hilti.com/PTGVol2/

To consult directly with a team member regarding our anchor fastening products, contact Hilti’s team of technical support specialists between the hours of 7:00am – 6:00pm CST.

US: 877-749-6337 or HNATechnicalServices@hilti.com CA: 1-800-363-4458, ext. 6 or CATechnicalServices@hilti.com

Page : 1 https://submittals.us.hilti.com/PTGVol2/ mailto:HNATechnicalServices@hilti.com mailto:CATechnicalServices@hilti.com

406 Anchor Fastening Technical Guide Edition 19 | 3.0 ANCHORING SYSTEMS | 3.3.12 HDI+, HDI-L+, AND HDI DROP IN ANCHORS Hilti, Inc. (U.S.) 1-800-879-8000 | en español 1-800-879-5000 | www.hilti.com | Hilti (Canada) Corporation | www.hilti.com | 1-800-363-4458

INSTALLATION PARAMETERS

Table 1 - Hilti HDI+, HDI-L+ and HDI specifications1

Setting Information Symbol Units HDI+ and HDI-L+ HDI

1/4 3/8 1/2 5/8 3/4 Insert thread d UNC 1/4-20 3/8-16 1/2-13 5/8-11 3/4-10 Nominal bit diameter dbit in . 3/8 1/2 5/8 27/32 1

Nominal embedment Anchor length Hole depth hnom in .

(mm)

(25)

1-9/16 (40)

(51)

2-9/16 (65)

3-3/16 (81)ℓ ho

Useable thread length ℓth in . 7/16 5/8 11/16 7/8 1-3/8

(mm) (11) (15) (17) (22) (34)

Installation torque Tinst ft-lb 4 11 22 37 80 (Nm) (5) (15) (30) (50) (109)

Minimum slab thickness h in . 3 3-1/8 4 5-1/8 6-3/8

(mm) (76) (79) (102) (130) (162) 1 HDI+ and HDI-L+ are available in 1/4-, 3/8- and 1/2-in . The HDI is available in 5/8- and 3/4-in .

3 .3 .12 HDI+, HDI-L+, AND HDI DROP IN ANCHORS

PRODUCT DESCRIPTION

HDI+, HDI-L+, and HDI Drop-in anchors

Anchor System Features and Benefits

HDI-L+ and HDI+ with Auto setting tools 1/4” to 1/2”

• Anchor, setting tool and Hilti drill bit form a matched tolerance system to provide reliable fastenings

• Allows shallow embedment without sacrificing performance

• Lip allows accurate flush surface setting, independent of hole depth for the HDI-L+

• Ideal for repetitive fastenings with threaded rods of equal length

• HDI+ and HDI-L+ have an innovative stepped plug that reduces number of hammer blows by up to 50%

• HDI+ and HDI-L+ can be installed with the new HDI+ Setting Tool system (stop drill bit and machine setting tool) for improved productivity

HDI and Manual setting tool 5/8” to 3/4”

Approvals/Listings

FM (Factory Mutual) Pipe hanger components for automatic sprinkler systems HDI+ 3/8, HDI-L+ 3/8, HDI+1/2, HDI-L+ 1/2, HDI 5/8 and HDI 3/4

UL and cUL (Underwriters Laboratory) Pipe hanger equipment for fire protection services HDI+ 3/8, HDI-L+ 3/8, HDI+1/2, HDI-L+ 1/2, HDI 5/8 and HDI 3/4

Uncracked concrete

MATERIAL SPECIFICATIONS

HDI+, HDI-L and HDI anchors are manufactured from mild carbon steel . Anchor bodies are zinc plated in accordance with ASTM B633, AC 1, Type III HDI stainless steel anchors are manufactured from AISI Type 303 stainless steel

Fire sprinkler listings

Page : 2

Anchor Fastening Technical Guide, Edition 19

Anchor Fastening Technical Guide Edition 19 | 3.0 ANCHORING SYSTEMS | 3.3.12 HDI+, HDI-L+, AND HDI DROP IN ANCHORS Hilti, Inc. (U.S.) 1-800-879-8000 | en español 1-800-879-5000 | www.hilti.com | Hilti (Canada) Corporation | www.hilti.com | 1-800-363-4458

3.3.12

Table 2 - Hilti HDI+, HDI-L+ and HDI carbon steel allowable loads in concrete1,2

Anchor type

Nominal anchor diameter in .

ƒ'c = 2,000 ƒ'c = 4,000 ƒ'c = 6,000

Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN)

HDI+

1/4 385 (1 .7) 450 (2 .0) 510 (2 .3) 625 (2 .8) 640 (2 .8) 700 (3 .1) 3/8 635 (2 .8) 965 (4 .3) 920 (4 .1) 1,250 (5 .6) 1,260 (5 .6) 1,500 (6 .7) 1/2 945 (4 .2) 1,500 (6 .7) 1,605 (7 .1) 2,125 (9 .5) 1,950 (8 .7) 2,500 (11 .1)

HDI+ 5/8 1,875 (8 .3) 2,500 (11 .1) 2,920 (13 .0) 3,250 (14 .5) 3,715 (16 .5) 3,750 (16 .7) 3/4 2,500 (11 .1) 3,875 (17 .2) 4,065 (18 .1) 5,000 (22 .2) 5,565 (24 .8) 5,500 (24 .5)

Table 5 - Hilti HDI stainless steel allowable loads in concrete1,2,3

Nominal anchor diameter in .

Nominal anchor ƒ'c = 4,000 ƒ'c = 6,000

Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN)

HDI+

1/4 480 (2 .1) 600 (2 .7) 740 (3 .3) 600 (2 .7) 3/8 1,040 (4 .6) 1,230 (5 .5) 1,460 (6 .5) 1,230 (5 .5) 1/2 1,840 (8 .2) 2,760 (12 .3) 2,410 (10 .7) 2,760 (12 .3)

HDI+ 5/8 2,630 (11 .7) 4,510 (20 .1) 3,770 (16 .8) 4,510 (20 .1)

3/4 3,830 (17 .0) 5,580 (24 .8) 5,030 (22 .4) 5,580 (24 .8)

Table 4 - Hilti HDI+, HDI-L+ and HDI carbon steel allowable loads in lightweight concrete and lightweight concrete poured over metal deck1,2,3,4

Anchor type

Nominal anchor diameter in .

3,000 psi lightweight concrete 3,000 psi lightweight concrete over metal deck

Upper flute Lower flute Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN)

HDI+

1/4 465 (2 .1) 340 (1 .5) 530 (2 .4) 335 (1 .5) 375 (1 .7) 250 (1 .1) 3/8 720 (3 .2) 940 (4 .2) 810 (3 .6) 1,010 (4 .5) 500 (2 .2) 500 (2 .2) 1/2 1,035 (4 .6) 1,700 (7 .6) 1,035 (4 .6) 1,755 (7 .8) 625 (2 .8) 750 (3 .3)

HDI+ 5/8 1,465 (6 .5) 2,835 (12 .6) - - 875 (3 .9) 875 (3 .9)

3/4 2,075 (9 .2) 3,680 (16 .4) - - 1,250 (5 .6) 1,000 (4 .4)

1 The shear tests were conducted with SAE Grade 5 bolts with minimum yield strength of 85 ksi and minimum tension strength of 120 ksi . Shear testing for the 1/4-in .

models were conducted with SAE Grade 8 bolts with minimum yield strength of 120 ksi and minimum tension strength of 150 ksi in 6,000 psi concrete . High-strength bolts were used to force concrete failure modes . When using steel bolts with a lower tensile strength, steel failure must be considered .

2 Minimum compressive strength of structural lightweight concrete is 3,000 psi .

3 See figure 1 for typical details.

4 Allowable loads calculated with a factor of safety of 4 .

Figure 1 - Installation of Hilti HDI+ and HDI drop-in anchor in the soffit of concrete over metal deck floor and roof assemblies W – deck

( )Nd 5/3 Vd

5/3

Nrec Vrec ( )+ ≤ 1 .0

Combined shear and tension loading

DESIGN DATA IN CONCRETE USING ALLOWABLE STRESS DESIGN

Table 6 - Hilti HDI stainless steel ultimate loads in concrete1,2

Nominal anchor diameter in .

Nominal anchor ƒ'c = 4,000 ƒ'c = 6,000

Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN)

HDI+

1/4 1,930 (8 .6) 2,400 (10 .7) 2,950 (13 .1) 2,400 (10 .7) 3/8 4,170 (18 .5) 4,920 (21 .9) 5,850 (26 .0) 4,920 (21 .9) 1/2 7,350 (32 .7) 11,040 (49 .1) 9,630 (42 .8) 11,040 (49 .1)

HDI+ 5/8 10,540 (46 .9) 18,040 (80 .2) 15,100 (67 .2) 18,040 (80 .2)

3/4 15,340 (68 .2) 22,320 (99 .3) 20,130 (89 .5) 22,320 (99 .3)

1 Stainless steel models available in HDI version only .

2 Shear testing conducted with 18-8 stainless steel bolts .

3 Allowable loads calculated with a factor of safety of 4 .

Table 3 - Hilti HDI+, HDI-L+ and HDI carbon steel ultimate loads in concrete1

Anchor type

Nominal anchor diameter in .

ƒ'c = 2,000 ƒ'c = 4,000 ƒ'c = 6,000

Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN)

HDI+

1/4 1,535 (6 .8) 1,800 (8 .0) 2,040 (9 .1) 2,500 (11 .1) 2,555 (11 .4) 2,800 (12 .5) 3/8 2,540 (11 .3) 3,850 (17 .1) 3,685 (16 .4) 5,000 (22 .2) 5,035 (22 .4) 6,000 (26 .7) 1/2 3,780 (16 .8) 6,000 (26 .7) 6,425 (28 .6) 8,500 (37 .8) 7,810 (34 .7) 10,000 (44 .5)

HDI+ 5/8 7,500 (33 .4) 10,000 (44 .5) 11,685 (52 .0) 13,000 (57 .8) 14,865 (66 .1) 15,000 (66 .7) 3/4 10,000 (44 .5) 15,500 (68 .9) 16,260 (72 .3) 20,000 (89 .0) 22,250 (99 .0) 22,000 (97 .9)

1 The shear tests were conducted with SAE Grade 5 bolts with minimum yield strength of 85 ksi and minimum tension strength of 120 ksi . Shear testing for the 1/4-in .

models were conducted with SAE Grade 8 bolts with minimum yield strength of 120 ksi and minimum tension strength of 150 ksi in 6,000 psi concrete . High-strength bolts were used to force concrete failure modes . When using steel bolts with a lower tensile strength, steel failure must be considered .

2 Allowable loads calculated with a factor of safety of 4 .

Page : 3

408 Anchor Fastening Technical Guide Edition 19 | 3.0 ANCHORING SYSTEMS | 3.3.12 HDI+, HDI-L+, AND HDI DROP IN ANCHORS Hilti, Inc. (U.S.) 1-800-879-8000 | en español 1-800-879-5000 | www.hilti.com | Hilti (Canada) Corporation | www.hilti.com | 1-800-363-4458

Table 7 - Load adjustment factors for Hilti HDI drop-in anchors in concrete Load adjustment factors for anchor spacing ƒA Load adjustment factors for edge distance ƒR

Tension/shear loads Tension ƒRN Shear ƒRV

Spacing s Anchor diameter Edge distance c Anchor diameter Anchor diameter in . (mm) 1/4 3/8 1/2 5/8 3/4 in . (mm) 1/4 3/8 1/2 5/8 3/4 1/4 3/8 1/2 5/8 3/4 2 ( 51) .50 2 ( 51) .80 .65

2-1/2 ( 64) .67 2-1/2 ( 64) .90 .83 3 ( 76) .83 .50 3 ( 76) 1 .0 .80 1 .0 .65

3-1/2 ( 89) 1 .0 .58 3-1/2 ( 89) .85 .73 4 (102) .69 .50 4 (102) .91 .80 .85 .65

4-1/2 (114) .79 .58 4-1/2 (114) .98 .85 .96 .74 5 (127) .90 .67 .50 5 (127) 1 .0 .90 .80 1 .0 .83 .65

5-1/2 (140) 1 .0 .75 .55 5-1/2 (140) .95 .83 .91 .70 6 (152) .83 .61 .50 6 (152) 1 .0 .87 1 .0 .77 7 (178) 1 .0 .74 .57 6-1/2 (165) .91 .80 .84 .65 8 (203) .87 .67 7 (178) .95 .84 .91 .72 9 (229) 1 .0 .77 8 (203) 1 .0 .90 1 .0 .83 10 (254) .88 9 (229) .96 .94 11 (279) .98 10 (254) 1 .0 1 .0 12 (305) 1 .0 smin = 2 .0 hnom scr = 3 .5 hnom ƒA = 0 .33 s – 0 .17 hnom for scr > s > smin cmin = 2 .0 hnom ccr = 3 .0 hnom ƒRN = 0 .2 c + 0 .4 hnom for ccr > c > cmin cmin = 2 .0 hnom ccr = 3 .0 hnom ƒRV = 0 .35 c – 0 .05 hnom for ccr > c > cmin

Influence of anchor spacing and edge distance ƒA and ƒR

Anchor Size hnom in . (mm) in . (mm) 1/4 (6 .4) 1 ( 25) 3/8 (9 .5) 1-9/16 (40) 1/2 (12 .7) 2 ( 51) 5/8 (15 .8) 2-9/16 ( 65) 3/4 (19 .1) 3-3/16 ( 81) hnom = nominal embedment depth

Anchor spacing and edge distance guidelines Anchor spacing adjustment factors s = Actual Spacing smin = 2 .0 hnom scr = 3 .5 hnom

Edge distance adjustment factors c = Actual edge distance cmin = 2 .0 hnom ccr = 3 .0 hnom

Anchor spacing adjustment Factor Edge distance adjustment factor

Page : 4

Anchor Fastening Technical Guide, Edition 19

Anchor Fastening Technical Guide Edition 19 | 3.0 ANCHORING SYSTEMS | 3.3.12 HDI+, HDI-L+, AND HDI DROP IN ANCHORS Hilti, Inc. (U.S.) 1-800-879-8000 | en español 1-800-879-5000 | www.hilti.com | Hilti (Canada) Corporation | www.hilti.com | 1-800-363-4458

3.3.12

ORDERING INFORMATION1

HDI+, HDI-L+ and HDI

Carbon steel

Description Description Anchor thread size Qty / box

HDI+ 1/4 HDI-L+ 1/4 1/4 100

HDI+ 3/8 HDI-L+ 3/8 3/8 50

HDI+ 1/2 HDI-L+ 1/2 1/2 50

HDI 5/8 – 5/8 25

HDI 3/4 – 3/4 25

HDI-SS anchors

Stainless steel

Description Anchor thread size Qty / box

HDI 1/4 SS303 1/4 100

HDI 3/8 SS303 3/8 50

HDI 1/2 SS303 1/2 50

HDI 5/8 SS303 5/8 25

HDI 3/4 SS303 3/4 25

Setting tools for HDI and HDI-SS anchors

Description Anchor thread size HST 5/8 Setting Tool 5/8 HST 3/4 Setting Tool 3/4

INSTALLATION INSTRUCTIONS

Manufacturer's Printed Installation Instructions (MPII) are included with each product package . They can also be viewed or downloaded at www .hilti .com . Because of the possibility of changes, always verify that downloaded MPII are current when used .

Proper installation is critical to achieve full performance . Training is available on request . Contact Hilti Technical Services for applications and conditions not addressed in the MPII .

Setting Tools for HDI+ and HDI-L+

Anchor thread size Description

1/4

HST 1/4 Setting tool

HSD-MM 1/4 (TE-C-24D6 1/4 Setting tool)

HDI+ Setting Tool includes a TE-CX 3/8x1 carbide bit

1/2

HST 1/2 Setting tool

HSD-MM 1/2 (TE-C-24SD12 1/2 Setting tool)

HDI+ Setting Tool includes a TE-CX 5/8x2 carbide bit

1 All dimensions in inches

3/8

HST 3/8 Setting tool

HSD-MM 3/8 (TE-C-24SD10 3/8 Setting tool)

HDI+ Setting Tool includes a TE-CX 1/2x1-9/16 carbide bit

Page : 5

26 05 29 Hangers and Supports.pdf
26 05 29 Hangers and Supports.pdf
cable ties.pdf
Hydrophone conduit support & anchor.pdf
K- Clamps for RMC or IMC
Clamps and Clamp Backs for RMC, IMC and EMT

File details come from the government source that posted it. Updated .