26_018 Addendum 4.pdf
PDF 128 KB Posted
- Attached to
- Bid Ref. #26-018 Pad Mount Transformers
- Solicitation number
- PE-64750-NONST-2026-000000158
- Issued by
- Douglas County, Georgia
About this file
This is an Addendum 4 to an Invitation to Bid issued by a state or local utility jurisdiction for Pad Mount Transformers (Bid Reference #26-018). The addendum clarifies specifications and requirements through a question-and-answer format, addressing nine specific technical questions submitted by potential bidders. The bid opening is scheduled for October 27, 2025, at 2:30 p.m. Bidders are required to acknowledge receipt of this addendum on their bid forms at submission. The addendum specifies that load break or sectionalizing switches, parking stands, and arresters are not required; however, temperature gauges, pressure relief valves, drain/sample valves, bayonet fuses, secondary bonds, and penta-head bolts on doors are required. Additionally, the specification clarifies that 1-inch studs only are required for secondary pads, rather than 4-hole NEMA secondary pads.
No pricing information, set-asides, incumbent vendor details, funding sources, or other financial terms are included in this addendum. The document serves solely to clarify technical specifications and requirements for the pad mount transformer procurement based on bidder inquiries. Bidders who have already submitted bids prior to the release of this addendum may email their acknowledgment form directly to the buyer, Takeshia Martin, to ensure bid acceptability.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 26_018 Pad Mount Transformers.pdf | ||
| 26_018 Addendum 3.pdf | ||
| 26_018 Addendum 1 .pdf | ||
| 26_018 Addendum 2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
October 17, 2025
TO: All Potential Bidders
SUBJECT: Pad Mount Transformers
Bid Ref. #26-018
Bid Opening Date & Time: October 27, 2025, at 2:30 p.m.
ADDENDUM NO. 4
The items contained in this addendum are added to and/or deleted from and become part of the specifications and proposal documents for the above-referenced Invitation to Bid. Bidders must acknowledge receipt of the Addendum on the Bid Form, located in the invitation to bid, when the bids are submitted.
QUESTIONS:
Question 1: Do you require a load break or sectionalizing switch? Answer: No.
Question 2: Do you require parking stands, if so, how many? No? Answer: Not required.
Question 3: Do you require arresters? Answer: No.
Question 4: Do you require a temp gauge, pressure relief valve? Answer: Yes.
Question 5: Do you require a drain/sample valve? Answer: Yes.
Question 6: Do you require bayonet fuses? Answer: Yes.
Question 7: Do you require 4-hole NEMA secondary pads or 1" studs only? Answer: 1” studs only.
Question 8: Do you require a secondary bond? Answer: Yes.
Question 9: Do you a require penta-head bolt or hex bolt on the door? Answer: Penta-head bolt.
End of Addendum 4 (You must acknowledge this Addendum for your bid to be acceptable. If you have already submitted your bid to the Procurement office at the time of the release of this Addendum, you can email your Acknowledgment form ONLY to the Buyer for this
Addendum.)
Takeshia Martin Takeshia Martin, Buyer
Cc: Jesse Barnes, Warehouse Manager, Finance Kendall Hodge, Director, Utility Operations Kurt Anthony, Deputy Director, Utility Operations
ADDENDUM NO. 4