25Z4AF6 - Statement of Objectives - Transformer Only.docx

DOCX document 43 KB Posted

Attached to
FCI Waseca - Transformer Replacement Federal contract opportunity
Solicitation number
15BFA026Q00000001
Issued by
Department of Justice Bureau of Prisons Field Acquisition Office

About this file

This document is a Statement of Objectives (SOO) from the U.S. Department of Justice Federal Bureau of Prisons for a transformer replacement project at FCI Waseca in Minnesota. The detailed specifications call for a 225 Kva 3-Phase padmount transformer with specific technical requirements, including high voltage at 4160 D with 60 kV BIL, low voltage at 208Y 120 with 30 kV BIL, and multiple tap configurations. The transformer must include features such as mineral oil fluid, 60 Hz frequency, AI/AI conductor, bayonet fusing with ISO links, and accessories like a drain and sample valve, dial-type thermometer, liquid level gauge, pressure vacuum gauge, and pressure relief valve.

The related federal contract opportunity (Solicitation Number 15BFA026Q00000001) is seeking quotes for this transformer replacement, with quotes to be submitted electronically via email to lbonner@bop.gov in PDF format. Potential quoters must be registered in the System for Award Management (SAM) database with NAICS code 221122 and include their Unique Entity Identifier (UEI). The solicitation is issued by the Department of Justice Bureau of Prisons Field Acquisition Office, with specific instructions for quote submission and emphasizing the importance of following all provided guidelines.

View the file

Other files for this federal contract opportunity

Other files attached to FCI Waseca - Transformer Replacement, newest first.
File Type Posted
MOD 0002.pdf PDF
15BFA026Q00000001.pdf PDF
25Z4AF6 - Statement of Objectives - Transformer Only.docx DOCX document
15BFA026Q00000001.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. Department of Justice Federal Bureau of Prisons

FCI Waseca

Facilities Department

Waseca, MN 56093

July 16, 2025

MEMORANDUM FOR LUCAS BONNER, CONTRACTING OFFICER, FIELD ACQUISITIONS OFFICE

FROM:J. Lincycomb,
Facility Manager
SUBJECT:Project Material Specifications - Transformer
B&F Project 25Z4AF6 – Transformer Replacement

This memorandum provides the material specifications for the project referenced in the subject above and as approved by North Central Regional Office.

225 Kva 3-Phase padmount transformer

· High Voltage: 4160 D, 60 kV BIL

· Low Voltage: 208Y 120, 30 kV BIL

· Taps: 4368, 4264, 4160, 4056, 3952

· HV Bushings: (6) 200A Wells & Inserts (dead front, loop feed)

· LV Bushings: (4) 4-Hole Spades

· Fluid: Mineral Oil

· Frequency: 60 Hz

· Temperature Rise: 65°

· Cooling Class: ONAN

· Conductor: AI/AI

· Fusing: Bayonet w/ISO Links

· Switch: 3-2 pos. LBOR