25Z4AF6 - Statement of Objectives - Transformer Only.docx
DOCX document 44 KB Posted
- Attached to
- FCI Waseca - Transformer Replacement Federal contract opportunity
- Solicitation number
- 15BFA026Q00000001
About this file
This document is a Statement of Objectives (SOO) from the U.S. Department of Justice Federal Bureau of Prisons for a transformer replacement project at FCI Waseca in Minnesota. The project requires a 225 Kva 3-Phase padmount transformer with specific technical specifications, including high voltage of 4160 D, 60 kV BIL, low voltage of 208Y 120, and 30 kV BIL. Additional required components include 480 linear feet of 2" Schedule 80 carbon steel condensate pipe, polyurethane foam insulation, high-density polyethylene insulation jacket, prefabricated elbows, end seals, and anchors.
The solicitation (Solicitation Number: 15BFA026Q00000001) is being managed by the Department of Justice Bureau of Prisons Field Acquisition Office. Potential vendors must be registered in the System for Award Management (SAM) database with NAICS code 221122 and submit their quotes electronically via email to lbonner@bop.gov in PDF format. Modification 0001 added a line item for 15 KV cable, expanding the original scope of the transformer replacement project.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| MOD 0002.pdf | ||
| 15BFA026Q00000001.pdf | ||
| 25Z4AF6 - Statement of Objectives - Transformer Only.docx | DOCX document | |
| 15BFA026Q00000001.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. Department of Justice Federal Bureau of Prisons
FCI Waseca
Facilities Department
Waseca, MN 56093
October 8, 2025
MEMORANDUM FOR LUCAS BONNER, CONTRACTING OFFICER, FIELD ACQUISITIONS OFFICE
| FROM: | J. Lincycomb, |
| Facility Manager |
| SUBJECT: | Project Material Specifications - Transformer |
| B&F Project 25Z4AF6 – Transformer Replacement |
This memorandum provides the material specifications for the project referenced in the subject above and as approved by North Central Regional Office.
225 Kva 3-Phase padmount transformer
· High Voltage: 4160 D, 60 kV BIL
· Low Voltage: 208Y 120, 30 kV BIL
· Taps: 4368, 4264, 4160, 4056, 3952
· HV Bushings: (6) 200A Wells & Inserts (dead front, loop feed)
· LV Bushings: (4) 4-Hole Spades
· Fluid: Mineral Oil
· Frequency: 60 Hz
· Temperature Rise: 65°
· Cooling Class: ONAN
· Conductor: AI/AI
· Fusing: Bayonet w/ISO Links
· Switch: 3-2 pos. LBOR
REQUIRED FEATURES AND ACCESSORIES
· Drain and Sample Valve
· Dial-Type Thermometer
· Liquid Level Guage
· Pressure Vacuum Guage
· Pressure Relief Valve
· Gas Sampler
· UL Listed
15 KV Cable
1. 480 linear feet of 2” Schedule 80 A53, GR B, ERW carbon steel condensate pipe
· Service Pressure: 15 PSIG
· Temperature: 250℉
2. Service pipe fittings shall be ASME B16.11 ASTM A105
3. Polyurethan foam insulation surrounding condensate pipe shall have a minimum of 2.0lb/cu ft density with a minimum .92” thickness
4. High Density Polyethylene (HDPE) Insulation jacket shall have an outer diameter of 4.5” with no less than .138” thickness of ASTM D3350, grade PE345444C or grade PE4710 high density polyethylene
5. 2 prefabricated ASTM A36 2” elbows (45°) with 34’ tangent
6. 2 wall/floor ASTM A36 end seals
7. 3 prefabricated ASTM A36 anchors with field joint kits (32 total) image1.png
File details come from the government source that posted it. Updated .