25189_PCC GO ZONE RENO_SPECS_06-24-2026.pdf

PDF 313 KB Posted

Attached to
PCC SW GoZone Remodel
Solicitation number
IFB1 GJKA 2027000015 1
Issued by
Morgan County, Manzanola Town, Colorado

About this file

This is a Project Manual and Construction/Bid Set for Project #26-0022 GO-ZONE REMODEL at Pueblo Community College's Southwest Campus in Mancos, Colorado, prepared by the Pueblo Community College Purchasing Department. The project involves renovation work at 33057 Highway 160, Mancos, CO 81321, with a bid set dated June 24, 2026. The scope of work includes multiple construction divisions covering general requirements, demolition of existing conditions, thermal and moisture protection, openings, finishes, and furnishings. Specific work includes selective demolition of flooring, casework, paneling, and light fixtures; installation of metal wall panels with exterior finishes; sheet metal flashing and trim work; door hardware for hollow metal and fire-rated doors; acoustical ceiling systems with suspended metal grid and mineral fiber tiles; resilient vinyl composition tile flooring with rubber base; and solid surfacing countertops. The manual establishes detailed specifications and procedures for construction contractor performance, including requirements for price and payment procedures, quality assurance, testing and inspection, mock-ups, and tolerances.

The project manual specifies that all work must comply with referenced standards including ASTM, BHMA, NFPA, and other industry standards current as of the contract documents date. Payment procedures require contractors to submit schedules of values using AIA G703 forms within 15 days of the Owner-Contractor Agreement, with progress payments submitted at intervals stipulated in the agreement using AIA G702 and G703 forms in electronic and hard-copy formats. Quality assurance requirements mandate compliance with manufacturers' instructions, submission of design data and test reports, and engagement of qualified testing agencies at the contractor's expense for work beyond specified requirements. The contractor is responsible for all demolition, protection of existing structures to remain, proper handling and storage of materials, mock-up construction with architect approval before final installation, and achievement of specified tolerances. Manufacturer warranties are required, including 15-year coverage on metal wall panel finishes, 2-year water-tightness warranties on seals, three-year coverage on locksets and cylinders, and two-year coverage on other hardware. The project employs a Construction Manager/General Contractor (CMGC) agreement structure for contract administration.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT MANUAL FOR:

#26-0022

GO-ZONE REMODEL

PUEBLO COMMUNITY COLLEGE- SOUTHWEST CAMPUS

33057 HIGHWAY 160- MANCOS, CO 81321

CONSTRUCTION/ BID SET

FOR:

Pueblo Community College Purchasing Department, CA 109

900 W. Orman Avenue Pueblo, CO 81004

JUNE 24, 2026

Pueblo Community College Go Zone Renovation TABLE OF CONTENTS 06-24-2026

TABLE OF CONTENTS

DIVISION 01 - GENERAL REQUIREMENTS

01 20 00 PRICE AND PAYMENT PROCEDURES

01 40 00 QUALITY REQUIREMENTS

DIVISION 02 - EXISTING CONDITIONS

02 41 00 DEMOLITION

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 42 13 METAL WALL PANELS

07 62 00 SHEET METAL FLASHING AND TRIM

DIVISION 08 - OPENINGS

08 71 00 DOOR HARDWARE

DIVISION 09 - FINISHES

09 51 00 ACOUSTICAL CEILINGS

09 65 00 RESILIENT FLOORING

DIVISION 12 - FURNISHINGS

12 36 00 COUNTERTOPS

June 24, 2026 100% CD Set

Pueblo Community College Go Zone Renovation

Price And Payment Procedures 01 20 00 - 1

SECTION 01 20 00

PRICE AND PAYMENT PROCEDURES

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Procedures for preparation and submittal of applications for progress payments.

B. Documentation of changes in Contract Sum and Contract Time.

C. Change procedures.

D. Correlation of Contractor submittals based on changes.

E. Procedures for preparation and submittal of application for final payment.

1.02 RELATED REQUIREMENTS

A. Document: Project will be constructed under a Construction Manager/ General Contractor

(CMGC) agreement.

B. Section 01 21 00 - Allowances: Payment procedures relating to allowances.

C. Section 01 22 00 - Unit Prices: Monetary values of unit prices; Payment and modification procedures relating to unit prices.

D. Section 01 78 00 - Closeout Submittals: Project record documents.

1.03 SCHEDULE OF VALUES

A. Use Schedule of Values Form: AIA G703, edition stipulated in the Agreement or approved equal by owner.

B. Electronic media printout including equivalent information will be considered in lieu of standard form specified; submit draft to Architect for approval.

C. Forms filled out by hand will not be accepted.

D. Submit Schedule of Values in duplicate within 15 days after date of Owner-Contractor

Agreement.

E. Format: Utilize the Table of Contents of this Project Manual. Identify each line item with number and title of the specification section. Identify site mobilization.

F. Include in each line item, the amount of Allowances specified in this section. For unit cost

Allowances, identify quantities taken from Contract Documents multiplied by the unit cost to achieve the total for the item.

G. Revise schedule to list approved Change Orders, with each Application For Payment.

1.04 APPLICATIONS FOR PROGRESS PAYMENTS

A. Payment Period: Submit at intervals stipulated in the Agreement.

B. Use Form AIA G702 and Form AIA G703, edition stipulated in the Agreement or approved equal by owner.

C. Electronic media printout including equivalent information will be considered in lieu of standard form specified; submit sample to Architect for approval.

D. Forms filled out by hand will not be accepted.

E. For each item, provide a column for listing each of the following:

1. Item Number.

2. Description of work.

3. Scheduled Values.

4. Previous Applications.

5. Work in Place and Stored Materials under this Application.

6. Authorized Change Orders.

7. Total Completed and Stored to Date of Application.

Pueblo Community College Go Zone Renovation

01 20 00 - 2

8. Percentage of Completion.

9. Balance to Finish.

10. Retainage.

F. Execute certification by signature of authorized officer.

G. Use data from approved Schedule of Values. Provide dollar value in each column for each line item for portion of work performed and for stored products.

H. List each authorized Change Order as a separate line item, listing Change Order number and dollar amount as for an original item of work.

I. Submit one electronic and three hard-copies of each Application for Payment.

J. Include the following with the application:

1. Transmittal letter as specified for submittals in Section 01 30 00.

2. Construction progress schedule, revised and current as specified in Section 01 30 00.

3. Partial release of liens from major subcontractors and vendors.

4. Affidavits attesting to off-site stored products.

K. When Architect requires substantiating information, submit data justifying dollar amounts in question. Provide one copy of data with cover letter for each copy of submittal. Show application number and date, and line item by number and description.

1.05 MODIFICATION PROCEDURES

A. Submit name of the individual authorized to receive change documents and who will be responsible for informing others in Contractor's employ or subcontractors of changes to Contract Documents.

B. For minor changes not involving an adjustment to the Contract Sum or Contract Time, Architect will issue instructions directly to Contractor.

C. For other required changes, Architect will issue a document signed by Owner instructing Contractor to proceed with the change, for subsequent inclusion in a Change Order.

1. The document will describe the required changes and will designate method of determining any change in Contract Sum or Contract Time.

2. Promptly execute the change.

D. For changes for which advance pricing is desired, Architect will issue a document that includes a detailed description of a proposed change with supplementary or revised drawings and specifications, a change in Contract Time for executing the change with a stipulation of any overtime work required and the period of time during which the requested price will be considered valid. Contractor shall prepare and submit a fixed price quotation within ____ days.

E. Contractor may propose a change by submitting a request for change to Architect, describing the proposed change and its full effect on the work, with a statement describing the reason for the change, and the effect on the Contract Sum and Contract Time with full documentation.

Document any requested substitutions in accordance with Section 01 60 00.

F. Computation of Change in Contract Amount: As specified in the Agreement and Conditions of the Contract.

1. For change requested by Architect for work falling under a fixed price contract, the amount will be based on Contractor's price quotation.

2. For change requested by Contractor, the amount will be based on the Contractor's request for a Change Order as approved by Architect.

3. For pre-determined unit prices and quantities, the amount will be based on the fixed unit prices.

4. For change ordered by Architect without a quotation from Contractor, the amount will be determined by Architect based on the Contractor's substantiation of costs as specified for Time and Material work.

G. Substantiation of Costs: Provide full information required for evaluation.

Pueblo Community College Go Zone Renovation

01 20 00 - 3

1. On request, provide the following data:

a. Quantities of products, labor, and equipment.

b. Taxes, insurance, and bonds.

c. Overhead and profit.

d. Justification for any change in Contract Time.

e. Credit for deletions from Contract, similarly documented.

2. Support each claim for additional costs with additional information:

a. Origin and date of claim.

b. Dates and times work was performed, and by whom.

c. Time records and wage rates paid.

d. Invoices and receipts for products, equipment, and subcontracts, similarly documented.

3. For Time and Material work, submit itemized account and supporting data after completion of change, within time limits indicated in the Conditions of the Contract.

H. Execution of Change Orders: Architect will issue Change Orders for signatures of parties as provided in the Conditions of the Contract.

I. After execution of Change Order, promptly revise Schedule of Values and Application for

Payment forms to record each authorized Change Order as a separate line item and adjust the Contract Sum.

J. Promptly revise progress schedules to reflect any change in Contract Time, revise sub-schedules to adjust times for other items of work affected by the change, and resubmit.

K. Promptly enter changes in Project Record Documents.

1.06 APPLICATION FOR FINAL PAYMENT

A. Prepare Application for Final Payment as specified for progress payments, identifying total adjusted Contract Sum, previous payments, and sum remaining due.

B. Application for Final Payment will not be considered until the following have been accomplished:

1. All closeout procedures specified in Section 01 70 00.

PART 2 PRODUCTS - NOT USED

PART 3 EXECUTION - NOT USED

END OF SECTION

Pueblo Community College Go Zone Renovation

Quality Requirements 01 40 00 - 1

SECTION 01 40 00

QUALITY REQUIREMENTS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Submittals.

B. Quality assurance.

C. References and standards.

D. Testing and inspection agencies and services.

E. Control of installation.

F. Mock-ups.

G. Tolerances.

H. Manufacturers' field services.

I. Defect Assessment.

1.02 RELATED REQUIREMENTS

A. Section 01 30 00 - Administrative Requirements: Submittal procedures.

B. Section 01 60 00 - Product Requirements: Requirements for material and product quality.

1.03 REFERENCE STANDARDS

1.04 DEFINITIONS

A. Design Data: Design-related, signed and sealed drawings, calculations, specifications, certifications, shop drawings and other submittals provided by Contractor, and prepared directly by, or under direct supervision of, appropriately licensed design professional.

1.05 SUBMITTALS

A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.

B. Design Data: Submit for Architect's knowledge as contract administrator for the limited purpose of assessing compliance with information given and the design concept expressed in the Contract Documents, or for Owner's information.

C. Test Reports: After each test/inspection, promptly submit two copies of report to Architect and to Contractor.

1. Include:

a. Date issued.

b. Project title and number.

c. Name of inspector.

d. Date and time of sampling or inspection.

e. Identification of product and specifications section.

f. Location in the Project.

g. Type of test/inspection.

h. Date of test/inspection.

i. Results of test/inspection.

j. Compliance with Contract Documents.

k. When requested by Architect, provide interpretation of results.

2. Test report submittals are for Architect's knowledge as contract administrator for the limited purpose of assessing compliance with information given and the design concept expressed in the Contract Documents, or for Owner's information.

D. Certificates: When specified in individual specification sections, submit certification by the manufacturer and Contractor or installation/application subcontractor to Architect, in quantities specified for Product Data.

Pueblo Community College Go Zone Renovation

01 40 00 - 2

1. Indicate material or product complies with or exceeds specified requirements. Submit supporting reference data, affidavits, and certifications as appropriate.

2. Certificates may be recent or previous test results on material or product, but must be acceptable to Architect.

E. Manufacturer's Instructions: When specified in individual specification sections, submit printed instructions for delivery, storage, assembly, installation, start-up, adjusting, and finishing, for the Owner's information. Indicate special procedures, perimeter conditions requiring special attention, and special environmental criteria required for application or installation.

F. Manufacturer's Field Reports: Submit reports for Architect's benefit as contract administrator or for Owner.

1. Submit report in duplicate within 30 days of observation to Architect for information.

2. Submit for information for the limited purpose of assessing compliance with information given and the design concept expressed in the Contract Documents.

1.06 QUALITY ASSURANCE

A. Testing Agency Qualifications:

1. Prior to start of work, submit agency name, address, and telephone number, and names of full time registered Engineer and responsible officer.

1.07 REFERENCES AND STANDARDS

A. For products and workmanship specified by reference to a document or documents not included in the Project Manual, also referred to as reference standards, comply with requirements of the standard, except when more rigid requirements are specified or are required by applicable codes.

B. Comply with reference standard of date of issue current on date of Contract Documents, except where a specific date is established by applicable code.

C. Obtain copies of standards where required by product specification sections.

D. Maintain copy at project site during submittals, planning, and progress of the specific work, until

Substantial Completion.

E. Should specified reference standards conflict with Contract Documents, request clarification from Architect before proceeding.

F. Neither the contractual relationships, duties, or responsibilities of the parties in Contract nor those of Architect shall be altered from Contract Documents by mention or inference otherwise in any reference document.

1.08 TESTING AND INSPECTION AGENCIES AND SERVICES

A. Owner will employ and pay for services of an independent testing agency to perform other specified testing.

B. Employment of agency in no way relieves Contractor of obligation to perform Work in accordance with requirements of Contract Documents.

PART 3 EXECUTION

2.01 CONTROL OF INSTALLATION

A. Monitor quality control over suppliers, manufacturers, products, services, site conditions, and workmanship, to produce work of specified quality.

B. Comply with manufacturers' instructions, including each step in sequence.

C. Should manufacturers' instructions conflict with Contract Documents, request clarification from

Architect before proceeding.

D. Comply with specified standards as minimum quality for the work except where more stringent tolerances, codes, or specified requirements indicate higher standards or more precise workmanship.

Pueblo Community College Go Zone Renovation

01 40 00 - 3

E. Have work performed by persons qualified to produce required and specified quality.

F. Verify that field measurements are as indicated on shop drawings or as instructed by the manufacturer.

G. Secure products in place with positive anchorage devices designed and sized to withstand stresses, vibration, physical distortion, and disfigurement.

2.02 MOCK-UPS

A. Before installing portions of the Work where mock-ups are required, construct mock-ups in location and size indicated for each form of construction and finish required to comply with the following requirements, using materials indicated for the completed Work. The purpose of mock-up is to demonstrate the proposed range of aesthetic effects and workmanship.

B. Accepted mock-ups establish the standard of quality the Architect will use to judge the Work.

C. Notify Architect and 15 Consultant fifteen (15) working days in advance of dates and times when mock-ups will be constructed.

D. Provide supervisory personnel who will oversee mock-up construction. Provide workers that will be employed during the construction at Project.

E. Tests shall be performed under provisions identified in this section and identified in the respective product specification sections.

F. Assemble and erect specified items with specified attachment and anchorage devices, flashings, seals, and finishes.

G. Obtain Architect's approval of mock-ups before starting work, fabrication, or construction.

1. Architect will issue written comments within seven (7) working days of initial review and each subsequent follow up review of each mock-up.

H. Architect will use accepted mock-ups as a comparison standard for the remaining Work.

I. Where mock-up has been accepted by Architect and is specified in product specification sections to be removed, protect mock-up throughout construction, remove mock-up and clear area when directed to do so by Architect.

2.03 TOLERANCES

A. Monitor fabrication and installation tolerance control of products to produce acceptable Work.

Do not permit tolerances to accumulate.

B. Comply with manufacturers' tolerances. Should manufacturers' tolerances conflict with

Contract Documents, request clarification from Architect before proceeding.

C. Adjust products to appropriate dimensions; position before securing products in place.

2.04 TESTING AND INSPECTION

A. Testing Agency Duties:

1. Provide qualified personnel at site. Cooperate with Architect and Contractor in performance of services.

2. Perform specified sampling and testing of products in accordance with specified standards.

3. Ascertain compliance of materials and mixes with requirements of Contract Documents.

4. Promptly notify Architect and Contractor of observed irregularities or non-compliance of

Work or products.

5. Perform additional tests and inspections required by Architect.

6. Submit reports of all tests/inspections specified.

B. Limits on Testing/Inspection Agency Authority:

1. Agency may not release, revoke, alter, or enlarge on requirements of Contract

Documents.

2. Agency may not approve or accept any portion of the Work.

3. Agency may not assume any duties of Contractor.

Pueblo Community College Go Zone Renovation

01 40 00 - 4

4. Agency has no authority to stop the Work.

C. Contractor Responsibilities:

1. Deliver to agency at designated location, adequate samples of materials proposed to be used that require testing, along with proposed mix designs.

2. Cooperate with laboratory personnel, and provide access to the Work and to manufacturers' facilities.

3. Provide incidental labor and facilities:

a. To provide access to Work to be tested/inspected.

b. To obtain and handle samples at the site or at source of Products to be tested/inspected.

c. To facilitate tests/inspections.

d. To provide storage and curing of test samples.

4. Notify Architect and laboratory 24 hours prior to expected time for operations requiring testing/inspection services.

5. Employ services of an independent qualified testing laboratory and pay for additional samples, tests, and inspections required by Contractor beyond specified requirements.

6. Arrange with Owner's agency and pay for additional samples, tests, and inspections required by Contractor beyond specified requirements.

D. Re-testing required because of non-compliance with specified requirements shall be performed by the same agency on instructions by Architect.

E. Re-testing required because of non-compliance with specified requirements shall be paid for by Contractor.

2.05 MANUFACTURERS' FIELD SERVICES

A. When specified in individual specification sections, require material or product suppliers or manufacturers to provide qualified staff personnel to observe site conditions, conditions of surfaces and installation, quality of workmanship, start-up of equipment, test, adjust, and balance equipment as applicable, and to initiate instructions when necessary.

B. Report observations and site decisions or instructions given to applicators or installers that are supplemental or contrary to manufacturers' written instructions.

2.06 DEFECT ASSESSMENT

A. Replace Work or portions of the Work not complying with specified requirements.

B. If, in the opinion of Owner, it is not practical to remove and replace the work, Owner will direct an appropriate remedy or adjust payment.

Pueblo Community College Go Zone Renovation

Demolition 02 41 00 - 1

SECTION 02 41 00

DEMOLITION

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Selective demolition of built site elements.

B. Selective demolition of building elements for alteration purposes.

1.02 RELATED REQUIREMENTS

A. Section 01 10 00 - Summary: Limitations on Contractor's use of site and premises.

B. Section 01 10 00 - Summary: Sequencing and staging requirements.

C. Section 01 10 00 - Summary: Description of items to be salvaged or removed for re-use by

Contractor.

D. Section 01 50 00 - Temporary Facilities and Controls: Site fences, security, protective barriers, and waste removal.

E. Section 01 60 00 - Product Requirements: Handling and storage of items removed for salvage and relocation.

F. Section 01 70 00 - Execution and Closeout Requirements: Project conditions; protection of bench marks, survey control points, and existing construction to remain; reinstallation of removed products; temporary bracing and shoring.

G. Section 31 22 00 - Grading: Rough and fine grading.

H. Section 31 23 23 - Fill: Fill material for filling holes, pits, and excavations generated as a result of removal operations.

PART 3 EXECUTION

2.01 DEMOLITION

A. Remove portions of existing buildings as shown in the demolition plans. Demolition includes:

1. Flooring.

2. Existing casework and panelling on the walls..

3. Light fixtures.

B. Remove other items indicated, for salvage, relocation, recycling, and ______.

C. Fill excavations, open pits, and holes in ground areas generated as result of removals, using specified fill; compact fill as specified in Section 31 22 00.

2.02 GENERAL PROCEDURES AND PROJECT CONDITIONS

A. Comply with applicable codes and regulations for demolition operations and safety of adjacent structures and the public.

1. Obtain required permits.

2. Take precautions to prevent catastrophic or uncontrolled collapse of structures to be removed; do not allow worker or public access within range of potential collapse of unstable structures.

3. Provide, erect, and maintain temporary barriers and security devices.

4. Conduct operations to minimize effects on and interference with adjacent structures and occupants.

5. Do not close or obstruct roadways or sidewalks without permits from authority having jurisdiction.

6. Conduct operations to minimize obstruction of public and private entrances and exits. Do not obstruct required exits at any time. Protect persons using entrances and exits from removal operations.

7. Obtain written permission from owners of adjacent properties when demolition equipment will traverse, infringe upon, or limit access to their property.

Pueblo Community College Go Zone Renovation

Demolition 02 41 00 - 2

B. Do not begin removal until receipt of notification to proceed from Owner.

C. Protect existing structures and other elements to remain in place and not removed.

1. Provide bracing and shoring.

2. Prevent movement or settlement of adjacent structures.

3. Stop work immediately if adjacent structures appear to be in danger.

2.03 SELECTIVE DEMOLITION FOR ALTERATIONS

A. Existing construction and utilities indicated on drawings are based on casual field observation and existing record documents only.

1. Verify construction and utility arrangements are as indicated.

2. Report discrepancies to Architect before disturbing existing installation.

3. Beginning of demolition work constitutes acceptance of existing conditions that would be apparent upon examination prior to starting demolition.

B. Remove existing work as indicated and required to accomplish new work.

1. Remove items indicated on drawings.

C. Services including, but not limited to, HVAC, Plumbing, Fire Protection, Electrical, and

Telecommunications: Remove existing systems and equipment as indicated.

1. Maintain existing active systems to remain in operation, and maintain access to equipment and operational components.

2. Where existing active systems serve occupied facilities but are to be replaced with new services, maintain existing systems in service until new systems are complete and ready for service.

3. Verify that abandoned services serve only abandoned facilities before removal.

4. Remove abandoned pipe, ducts, conduits, and equipment, including those above accessible ceilings. Remove back to source of supply where possible, otherwise cap stub and tag with identification.

D. Protect existing work to remain.

1. Prevent movement of structure. Provide shoring and bracing as required.

2. Perform cutting to accomplish removal work neatly and as specified for cutting new work.

3. Repair adjacent construction and finishes damaged during removal work.

4. Patch to match new work.

2.04 DEBRIS AND WASTE REMOVAL

A. Remove debris, junk, and trash from site.

B. Leave site in clean condition, ready for subsequent work.

C. Clean up spillage and wind-blown debris from public and private lands.

Pueblo Community College Go Zone Renovation

Metal Wall Panels 07 42 13 - 1

SECTION 07 42 13

METAL WALL PANELS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Manufactured metal panels for exterior wall panels, with related flashings and accessory components.

1.02 RELATED REQUIREMENTS

A. Section 06 10 00 - Rough Carpentry: Wall panel substrate.

B. Section 07 21 00 - Thermal Insulation.

C. Section 07 25 00 - Weather Barriers: Weather barrier under wall panels.

D. Section 07 92 00 - Joint Sealants: Sealing joints between metal wall panel system and adjacent construction.

1.03 DELIVERY, STORAGE, AND HANDLING

A. Protect panels from accelerated weathering by removing or venting sheet plastic shipping wrap.

B. Store prefinished material off the ground and protected from weather; prevent twisting, bending, or abrasion; provide ventilation; slope metal sheets to ensure proper drainage.

C. Prevent contact with materials that may cause discoloration or staining of products.

1.04 FIELD CONDITIONS

A. Do not install wall panels when air temperature or relative humidity are outside manufacturer's limits.

1.05 WARRANTY

A. See Section 01 78 00 - Closeout Submittals for additional warranty requirements.

B. Finish Warranty: Provide 15-year manufacturer warranty against excessive degradation of exterior finish. Include provision for replacement of units with excessive fading, chalking, or flaking. Complete forms in Owner's name and register with warrantor.

C. Special Warranty: Provide 2-year warranty covering water tightness and integrity of seals of metal wall panels. Complete forms in Owner's name and register with warrantor.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Metal Wall Panels - Exposed Fasteners:

1. Metal Sales.

2.02 METAL WALL PANEL SYSTEM

A. Wall Panel System: Factory fabricated prefinished metal panel system, site assembled.

1. Provide exterior wall panels, interior liner panels, soffit panels, retrofit wall panels, and subgirt framing assembly.

2. Design and size components to support assembly dead loads, and to withstand live loads caused by positive and negative wind pressure acting normal to plane of wall.

3. Maximum Allowable Deflection of Panel: L/180 for length(L) of span.

4. Movement: Accommodate movement within system without damage to components or deterioration of seals, movement between system and perimeter components when subject to seasonal temperature cycling; dynamic loading and release of loads; and deflection of structural support framing.

5. Drainage: Provide positive drainage to exterior for moisture entering or condensation occurring within panel system.

6. Fabrication: Formed true to shape, accurate in size, square, and free from distortion or defects; pieces of longest practical lengths.

Pueblo Community College Go Zone Renovation

Metal Wall Panels 07 42 13 - 2

7. Corners: Factory-fabricated in one continuous piece with minimum 2-inch returns.

8. Provide continuity of weather barrier seal at building enclosure elements in accordance with requirements; see Section 07 25 00.

B. Exterior Wall Panels:

1. Profile: Vertical; style as indicated.

2. Side Seams: Double-interlocked, tight-fitting, sealed with continuous gaskets.

3. Material: Precoated steel sheet, 20 gauge, 0.0359 inch minimum thickness.

4. Panel Width: 12 inches.

5. Color: As selected by Architect from manufacturer's standard line.

C. Internal and External Corners: Same material, thickness, and finish as exterior sheets; profile to suit system; shop cut and factory mitered to required angles.

D. Expansion Joints: Same material, thickness and finish as exterior sheets; 22 gauge, 0.029 inch thick; manufacturer's standard brake formed type, of profile to suit system.

E. Trim: Same material, thickness and finish as exterior sheets; brake formed to required profiles.

F. Anchors: Galvanized steel.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that building framing members are ready to receive panels.

B. Verify weather barrier, see Section 07 25 00, has been installed over wall panel substrate; see

Section 06 10 00.

3.02 PREPARATION

A. Protect surrounding areas and adjacent surfaces from damage during execution of this work.

3.03 INSTALLATION

A. Install panels on walls in accordance with manufacturer's instructions.

B. Fasten panels to structural supports; aligned, level, and plumb.

C. Lap panel ends 2 inches, minimum.

D. Use concealed fasteners unless otherwise indicated by Architect.

E. Seal and place gaskets to prevent weather penetration. Maintain neat appearance.

3.04 TOLERANCES

A. Offset From True Alignment Between Adjacent Members Abutting or In Line: 1/16 inch, maximum.

B. Variation from Plane or Location As Indicated on Drawings: 1/4 inch, maximum.

3.05 CLEANING

A. See Section 01 70 00 - Execution and Closeout Requirements for additional requirements.

B. Remove site cuttings from finish surfaces.

C. Remove protective material from wall panel surfaces.

D. Clean and wash prefinished surfaces with mild soap and water; rinse with clean water.

3.06 PROTECTION

A. Protect metal wall panels until completion of project.

B. Touch-up, repair, or replace damaged wall panels or accessories before Date of Substantial

Completion.

Pueblo Community College Go Zone Renovation

Sheet Metal Flashing And Trim 07 62 00 - 1

SECTION 07 62 00

SHEET METAL FLASHING AND TRIM

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Fabricated sheet metal items, including flashings, counterflashings, gutters, downspouts, exterior penetrations, and other items indicated in Schedule.

B. Sealants for joints within sheet metal fabrications.

1.02 RELATED REQUIREMENTS

A. Section 07 71 23 - Manufactured Gutters and Downspouts.

1.03 REFERENCE STANDARDS

A. AAMA 2605 - Voluntary Specification, Performance Requirements and Test Procedures for Superior Performing Organic Coatings on Aluminum Extrusions and Panels (with Coil Coating Appendix); 2022.

B. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc- Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process; 2023.

C. ASTM C920 - Standard Specification for Elastomeric Joint Sealants; 2018.

D. ASTM D4586/D4586M - Standard Specification for Asphalt Roof Cement, Asbestos-Free; 2007

(Reapproved 2018).

E. CDA A4050 - Copper in Architecture - Handbook; Current Edition.

F. SMACNA (ASMM) - Architectural Sheet Metal Manual; 2012.

1.04 ADMINISTRATIVE REQUIREMENTS

A. Preinstallation Meeting: Convene one week before starting work of this section.

1.05 SUBMITTALS

A. See Section 01 30 00 - Administrative Requirements for submittal procedures.

B. Shop Drawings: Indicate material profile, jointing pattern, jointing details, fastening methods, flashings, terminations, and installation details.

C. Samples: Submit two samples, 2 by 4 inches in size, illustrating metal finish color.

1.06 QUALITY ASSURANCE

A. Perform work in accordance with SMACNA (ASMM) and CDA A4050 requirements and standard details, except as otherwise indicated.

B. Fabricator and Installer Qualifications: Company specializing in sheet metal work with five years of documented experience.

1.07 DELIVERY, STORAGE, AND HANDLING

A. Stack material to prevent twisting, bending, and abrasion, and to provide ventilation. Slope metal sheets to ensure drainage.

B. Prevent contact with materials that could cause discoloration or staining.

PART 2 PRODUCTS

2.01 SHEET MATERIALS

A. Galvanized Steel: ASTM A653/A653M, with G90/Z275 zinc coating; minimum 24-gauge, 0.0239-inch thick base metal.

B. Pre-Finished Galvanized Steel: ASTM A653/A653M, with G90/Z275 zinc coating; minimum 24-gauge, 0.0239-inch thick base metal, shop pre-coated with PVDF coating.

1. Polyvinylidene Fluoride (PVDF) Coating: Superior performing organic powder coating, AAMA 2605; multiple coat, thermally cured fluoropolymer finish system.

Pueblo Community College Go Zone Renovation

07 62 00 - 2

2. Color: As selected by Architect from manufacturer's standard colors.

2.02 FABRICATION

A. Form sections true to shape, accurate in size, square, and free from distortion or defects.

B. Form pieces in longest possible lengths.

C. Hem exposed edges on underside 1/2 inch; miter and seam corners.

D. Form material with flat lock seams, except where otherwise indicated; at moving joints, use sealed lapped, bayonet-type or interlocking hooked seams.

E. Fabricate corners from one piece with minimum 18-inch long legs; seam for rigidity, seal with sealant.

F. Fabricate flashings to allow toe to extend 2 inches over roofing gravel. Return and brake edges.

2.03 GUTTERS AND DOWNSPOUTS

A. See Section 07 71 23 for manufactured gutters and downspouts.

B. Seal metal joints.

2.04 FLASHING

A. Flashing Panels for Exterior Wall Penetrations: Premanufactured components and accessories as required to preserve integrity of building envelope; suitable for conduits and facade materials to be installed.

2.05 ACCESSORIES

A. Fasteners: Galvanized steel, with soft neoprene washers.

B. Primer Type: Zinc chromate.

C. Concealed Sealants: Non-curing butyl sealant.

D. Exposed Sealants: ASTM C920; elastomeric sealant, with minimum movement capability as recommended by manufacturer for substrates to be sealed; color to match adjacent material.

E. Asphalt Roof Cement: ASTM D4586/D4586M, Type I, asbestos-free.

F. Reglets: Surface-mounted type, galvanized steel; face and ends covered with plastic tape.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify roof openings, curbs, pipes, sleeves, ducts, and vents through roof are solidly set, reglets in place, and nailing strips located.

B. Verify roofing termination and base flashings are in place, sealed, and secure.

3.02 PREPARATION

A. Install starter and edge strips, and cleats before starting installation.

B. Install surface mounted reglets true to lines and levels, and seal top of reglets with sealant.

C. Back paint concealed metal surfaces with protective backing paint to a minimum dry film thickness of 15 mil, 0.015 inch.

3.03 INSTALLATION

A. Secure flashings in place using concealed fasteners, and use exposed fasteners only where permitted..

B. Apply plastic cement compound between metal flashings and felt flashings.

C. Fit flashings tight in place; make corners square, surfaces true and straight in planes, and lines accurate to profiles.

D. Seal metal joints watertight.

Pueblo Community College Go Zone Renovation

07 62 00 - 3

E. Secure gutters and downspouts in place with concealed fasteners.

3.04 FIELD QUALITY CONTROL

A. See Section 01 40 00 - Quality Requirements for field inspection requirements.

B. Inspection will involve surveillance of work during installation to ascertain compliance with specified requirements.

Pueblo Community College Go Zone Renovation

Door Hardware 08 71 00 - 1

SECTION 08 71 00

DOOR HARDWARE

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Hardware for hollow metal doors.

B. Hardware for fire-rated doors.

1.02 RELATED REQUIREMENTS

A. Section 07 92 00 - Joint Sealants: Sealants for setting exterior door thresholds.

B. Section 08 11 13 - Hollow Metal Doors and Frames.

1.03 REFERENCE STANDARDS

A. ADA Standards - 2010 ADA Standards for Accessible Design; 2010.

B. BHMA (CPD) - Certified Products Directory; Current Edition.

C. BHMA A156.1 - Standard for Butts and Hinges; 2021.

D. BHMA A156.2 - Bored and Preassembled Locks and Latches; 2022.

E. BHMA A156.5 - Cylinders and Input Devices for Locks; 2020.

F. BHMA A156.6 - Standard for Architectural Door Trim; 2021.

G. BHMA A156.16 - Standard for Auxiliary Hardware; 2023.

H. BHMA A156.18 - Standard for Materials and Finishes; 2020.

I. BHMA A156.115 - Hardware Preparation in Steel Doors and Frames; 2016.

J. BHMA A156.115W - Hardware Preparation in Wood Doors with Wood or Steel Frames; 2006.

K. ICC A117.1 - Accessible and Usable Buildings and Facilities; 2017.

L. NFPA 80 - Standard for Fire Doors and Other Opening Protectives; 2025.

M. NFPA 101 - Life Safety Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.

N. UL (DIR) - Online Certifications Directory; Current Edition.

1.04 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing products specified in this section with minimum three years of documented experience.

B. Installer Qualifications: Company specializing in performing work of the type specified for commercial door hardware with at least three years of documented experience.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Package hardware items individually; label and identify each package with door opening code to match door hardware schedule.

1.06 WARRANTY

A. See Section 01 78 00 - Closeout Submittals for additional warranty requirements.

B. Manufacturer's Warranty: Provide warranty against defects in material and workmanship for period indicated. Complete forms in Owner's name and register with manufacturer.

1. Locksets and Cylinders: Three years, minimum.

2. Other Hardware: Two years, minimum.

PART 2 PRODUCTS

2.01 DESIGN AND PERFORMANCE CRITERIA

A. Provide specified door hardware as required to make doors fully functional, compliant with applicable codes, and secure to extent indicated.

Pueblo Community College Go Zone Renovation

08 71 00 - 2

B. Provide individual items of single type, of same model, and by same manufacturer.

C. Provide door hardware products that comply with the following requirements:

1. Applicable provisions of federal, state, and local codes.

2. Accessibility: ADA Standards and ICC A117.1.

3. Applicable provisions of NFPA 101.

4. Listed and certified compliant with specified standards by BHMA (CPD).

5. Hardware Preparation for Steel Doors and Steel Frames: BHMA A156.115.

6. Hardware Preparation for Wood Doors with Wood or Steel Frames: BHMA A156.115W.

7. Products Requiring Electrical Connection: Listed and classified by UL (DIR) as suitable for the purpose specified.

D. Lock Function: Provide lock and latch function numbers and descriptions of manufacturer's series. See Door Hardware Schedule.

E. Fasteners:

1. Provide fasteners of proper type, size, quantity, and finish that comply with commercially recognized standards for proposed applications.

a. Aluminum fasteners are not permitted.

b. Provide phillips flat-head screws with heads finished to match door surface hardware unless otherwise indicated.

2. Provide machine screws for attachment to reinforced hollow metal and aluminum frames.

a. Self-drilling (Tek) type screws are not permitted.

3. Provide stainless steel machine screws and lead expansion shields for concrete and masonry substrates.

4. Provide wall grip inserts for hollow wall construction.

5. Fire-Rated Applications: Comply with NFPA 80.

a. Provide wood or machine screws for hinges mortised to doors or frames, strike plates to frames, and closers to doors and frames.

b. Provide steel through bolts for attachment of surface mounted closers, hinges, or exit devices to door panels unless proper door blocking is provided.

6. Concealed Fasteners: Do not use through or sex bolt type fasteners on door panel sides indicated as concealed fastener locations, unless otherwise indicated.

2.02 HINGES

A. Manufacturers:

1. McKinney; an Assa Abloy Group company: www.assaabloydss.com/#sle.

2. Hager Companies: www.hagerco.com/#sle.

3. BEST, dormakaba Group; _____: www.bestaccess.com/#sle.

4. Ives, an Allegion brand: www.allegion.com.

5. Substitutions: See Section 01 60 00 - Product Requirements.

B. Hinges: Comply with BHMA A156.1, Grade 1.

1. Provide hinges on every swinging door.

2. Provide five-knuckle full mortise butt hinges unless otherwise indicated.

3. Provide ball-bearing hinges at each door with closer.

4. Provide non-removable pins on exterior outswinging doors.

5. Provide non-removable pins on interior outswinging doors at locations as indicated.

6. Provide power transfer hinges where electrified hardware is mounted in door leaf.

7. Provide following quantity of butt hinges for each door:

a. Doors From 60 inches High up to 90 inches High: Three hinges.

b. Doors 90 inches High up to 120 inches High: Four hinges.

2.03 LOCK CYLINDERS

A. Manufacturers:

1. Schlage, and Allegion brand: www.allegion.com

Pueblo Community College Go Zone Renovation

08 71 00 - 3

2. Substitutions: See Section 01 60 00 - Product Requirements.

B. Lock Cylinders: Provide key access on outside of each lock, unless otherwise indicated.

1. Provide standard, electronic, conventional, full size interchangeable core (FSIC), and small format interchangeable core (SFIC) type cylinders, Grade 1, with six-pin core in compliance with BHMA A156.5 at locations indicated.

2. Provide cylinders from same manufacturer as locking device.

3. Provide cams and/or tailpieces as required for locking devices.

4. Within specific Door Sections, when provisions for lock cylinder are being referenced to this Section, provide specified lock cylinder and keyed to building keying system, unless otherwise indicated.

2.04 CYLINDRICAL LOCKS

A. Manufacturers:

1. Schlage, an Allegion brand; ND Series: www.allegion.com/us/#sle.

2. Substitutions: See Section 01 60 00 - Product Requirements.

B. Cylindrical Locks (Bored): Comply with BHMA A156.2, Grade 1, 4000 Series.

1. Bored Hole: 2-1/8 inch diameter.

2. Latchbolt Throw: 1/2 inch, minimum.

3. Backset: 2-3/4 inch unless otherwise indicated.

4. Strikes: Provide manufacturer's standard strike for each latchset or lockset with strike box and curved lip extending to protect frame in compliance with indicated requirements.

a. Finish: To match lock or latch.

2.05 DOOR PULLS AND PUSH PLATES

A. Manufacturers:

1. Hager Companies: www.hagerco.com/#sle.

2. Trimco: www.trimcohardware.com/#sle.

3. Ives, an Allegion brand: www.allegion.com/us/#sle.

4. Substitutions: See Section 01 60 00 - Product Requirements.

B. Door Pulls and Push Plates: Comply with BHMA A156.6.

1. Pull Type: Straight, unless otherwise indicated.

2. Push Plate Type: Flat, with square corners, unless otherwise indicated.

a. Edges: Beveled, unless otherwise indicated.

3. Material: Aluminum, unless otherwise indicated.

4. Provide door pulls and push plates on doors without a lockset, latchset, exit device, or auxiliary lock unless otherwise indicated.

2.06 KICK PLATES

A. Manufacturers:

1. Hiawatha, Inc, an Activar Construction Products Group company:

www.activarcpg.com/hiawatha/#sle.

2. Ives, an Allegion brand: www.allegion.com/us/#sle.

3. Standard Metal Hardware Manufacturing Ltd; Door Plates: www.smhardware.com/#sle.

4. Trimco: www.trimcohardware.com/#sle.

5. Substitutions: See Section 01 60 00 - Product Requirements.

B. Kick Plates: Provide along bottom edge of push side of every door with closer, except aluminum storefront and glass entry doors, unless otherwise indicated.

1. Size: 8 inch high by 2 inch less door width (LDW) on push side of door.

2.07 DOOR HOLDERS

A. Manufacturers:

1. McKinney or Rockwood; an Assa Abloy Group company; _____:

www.assaabloydss.com/#sle.

Pueblo Community College Go Zone Renovation

08 71 00 - 4

B. Door Holders: Comply with BHMA A156.16, Grade 1.

1. Type: Lever, or kick down stop, with rubber bumper at bottom end.

2. Material: Aluminum.

2.08 WALL STOPS

A. Manufacturers:

1. Rockwood; an Assa Abloy Group company: www.assaabloydss.com/#sle.

2. Hager Companies: www.hagerco.com/#sle.

3. Hiawatha, Inc, division of Activar Construction Products Group, Inc:

www.activarcpg.com/hiawatha/#sle.

4. Trimco: www.trimcohardware.com/#sle.

5. Substitutions: See Section 01 60 00 - Product Requirements.

B. Wall Stops: Comply with BHMA A156.16, Grade 1 and Resilient Material Retention Test as described in this standard.

1. Type: Bumper, concave, wall stop.

2. Material: Aluminum housing with rubber insert.

2.09 FINISHES

A. Finishes: Provide door hardware of same finish, unless otherwise indicated.

1. Primary Finish: 625; bright chromium plated over nickel, with brass or bronze base material (former US equivalent US26); BHMA A156.18.

2. Secondary Finish: 626; satin chromium plated over nickel, with brass or bronze base material (former US equivalent US26D); BHMA A156.18.

a. Use secondary finish in kitchens, bathrooms, and other spaces containing chrome or stainless steel finished appliances, fittings, and equipment; provide primary finish on one side of door and secondary finish on other side if necessary.

3. Exceptions:

a. Where base material metal is specified to be different, provide finish that is an equivalent appearance in accordance with BHMA A156.18.

Pueblo Community College Go Zone Renovation

Acoustical Ceilings 09 51 00 - 1

SECTION 09 51 00

ACOUSTICAL CEILINGS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Suspended metal grid ceiling system.

B. Acoustical units.

1.02 RELATED REQUIREMENTS

A. Section 07 21 00 - Thermal Insulation: Acoustical insulation.

1.03 REFERENCE STANDARDS

A. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-

Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process; 2023.

B. ASTM C635/C635M - Standard Specification for Manufacture, Performance, and Testing of

Metal Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings; 2022.

C. ASTM E1264 - Standard Classification for Acoustical Ceiling Products; 2023.

1.04 ADMINISTRATIVE REQUIREMENTS

A. Sequence work to ensure acoustical ceilings are not installed until building is enclosed, sufficient heat is provided, dust generating activities have terminated, and overhead work is completed, tested, and approved.

B. Do not install acoustical units until after interior wet work is dry.

1.05 SUBMITTALS

A. See Section 01 30 00 - Administrative Requirements for submittal procedures.

B. Product Data: Provide data on suspension system components and acoustical units.

C. Samples: Submit two samples 6 by 6 inch in size illustrating material and finish of acoustical units.

D. Manufacturer's Installation Instructions: Indicate special procedures and perimeter conditions requiring special attention.

E. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.

1. See Section 01 60 00 - Product Requirements, for additional provisions.

2. Extra Acoustical Units: Quantity equal to 5 percent of total installed.

1.06 QUALITY ASSURANCE

A. Suspension System Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience.

B. Acoustical Unit Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience.

1.07 FIELD CONDITIONS

A. Maintain uniform temperature of minimum 60 degrees F, and maximum humidity of 40 percent prior to, during, and after acoustical unit installation.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Acoustic Tiles/Panels:

1. Armstrong World Industries, Inc; ____: www.armstrongceilings.com/#sle.

2. Certainteed Architectural; ____: www.certainteed.com/ceilings-and-walls/#sle.

3. Rockfon; _____: www.rockfon.com/#sle.

4. USG Corporation; ____: www.usg.com/ceilings/#sle.

5. Substitutions: See Section 01 60 00 - Product Requirements.

Pueblo Community College Go Zone Renovation

09 51 00 - 2

B. Suspension Systems:

1. Same as for acoustical units. Basis of design is Decoustics by Certainteed.

2.02 ACOUSTICAL UNITS

A. Acoustical Units - General: ASTM E1264, Class A.

B. Acoustical Panels: Painted mineral fiber, with the following characteristics:

1. Classification: ASTM E1264 Type III.

2. Size: 24 by 48 inches.

3. Thickness: 5/8 inch.

4. Panel Edge: Reveal.

5. Color: White.

6. Suspension System: Exposed grid.

7. Products:

a. Armstrong World Industries, Inc; Cortega Tegular 704:

www.armstrongceilings.com/#sle.

b. Certainteed Architectural; Boroque BET-154: www.certainteed.com/ceilings-and-walls/#sle.

c. USG Corporation: www.usg.com/ceilings/#sle.

d. Substitutions: See Section 01 60 00 - Product Requirements.

2.03 SUSPENSION SYSTEM(S)

A. Metal Suspension Systems - General: Complying with ASTM C635/C635M; die cut and interlocking components, with perimeter moldings, hold down clips, stabilizer bars, clips, and splices as required.

1. Materials:

a. Steel Grid: ASTM A653/A653M, G30 coating, unless otherwise indicated.

B. Exposed Suspension System: Hot-dipped galvanized steel grid with steel cap.

1. Structural Classification: Intermediate-duty, when tested in accordance with ASTM C635/C635M.

2. Profile: Tee; 15/16 inch face width.

3. Finish: Baked enamel.

4. Color: White.

5. Products:

a. Certainteed Architectural; 15/16" EZ Stab Classic System:

www.certainteed.com/ceilings-and-walls/#sle.

b. USG Corporation; Donn Brand ZXLA 15/16 inch Acoustical Suspension System:

www.usg.com/ceilings/#sle.

c. Armstrong World Industries, Inc.; Prelude XL 15/16":

www.armstrongceilings.com/#sle.

d. Substitutions: See Section 01 60 00 - Product Requirements.

2.04 ACCESSORIES

A. Support Channels and Hangers: Galvanized steel; size and type to suit application, seismic requirements, and ceiling system flatness requirement specified.

B. Hanger Wire: 12 gauge, 0.08 inch galvanized steel wire.

C. Perimeter Moldings: Same metal and finish as grid.

1. Angle Molding: L-shaped, for mounting at same elevation as face of grid.

2. Acoustical Sealant For Perimeter Moldings: Non-hardening, non-skinning, for use in conjunction with suspended ceiling system.

D. Touch-up Paint: Type and color to match acoustical and grid units.

Pueblo Community College Go Zone Renovation

09 51 00 - 3

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify existing conditions before starting work.

B. Verify that layout of hangers will not interfere with other work.

3.02 PREPARATION

A. Install after major above-ceiling work is complete.

B. Coordinate the location of hangers with other work.

3.03 INSTALLATION - SUSPENSION SYSTEM

A. Install suspension system in accordance with ASTM C636/C636M, ASTM E580/E580M, and manufacturer's instructions and as supplemented in this section.

B. Rigidly secure system, including integral mechanical and electrical components, for maximum deflection of 1:360.

C. Locate system on room axis according to reflected plan.

D. Perimeter Molding: Install at intersection of ceiling and vertical surfaces and at junctions with other interruptions.

1. Use longest practical lengths.

E. Suspension System, Non-Seismic: Hang suspension system independent of walls, columns, ducts, pipes and conduit. Where carrying members are spliced, avoid visible displacement of face plane of adjacent members.

F. Where ducts or other equipment prevent the regular spacing of hangers, reinforce the nearest affected hangers and related carrying channels to span the extra…

This is the start of the file's text. The full file is on GovTribe.