25021 RCC Fire Alarm Addendum 1.pdf
PDF 258 KB Posted
- Attached to
- Fire Alarm Panel Upgrade Main Campus
- Solicitation number
- 116-10022025
- Issued by
- Richmond County, North Carolina
About this file
This is an addendum to the bid documents for the Randolph Community College Fire Alarm Replacement project, issued by Progressive Design Collaborative, Ltd on October 31, 2025. The addendum clarifies that all fire alarm detection and notification devices in the Kinley Center building, as shown on drawing FA1.41, require replacement to ensure compatibility with the new system upgrade. The work involves modifications to fire alarm drawings, specifically drawing FA1.51, which includes revisions to keynotes and cross-references identifying which fire alarm control panels are to be disconnected and removed versus retained.
The addendum specifies three key modifications to drawing FA1.51: revising Keynote #1 to clarify the disconnection and removal of the EST-3 fire alarm control panel; adding Keynote #3 to indicate that the existing Pyrotronics System 3 fire alarm control panel and all existing connections shall remain; and adding a cross-reference to Keynote #3 in Mechanical Room MECH 281 on the drawing. These clarifications became necessary following a project walk-through and serve as binding changes to the original bid documents that contractors must incorporate into their proposals and subsequent contract performance.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Adendum #2.pdf | ||
| RPF Main Campus Fire Panel Upgrade Package.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Progressive Design Collaborative, Ltd
3101 Poplarwood Court, Suite 300
Raleigh, North Carolina 27604
919 -790 -9989 pdcengineers.com
ADDENDUM 01 – FIRE ALARM REPLACEMENT
DATE: October 31, 2025
PROJECT: Randolph Community College Fire Alarm Replacement PDC Project No. 25021
This Addendum, applicable to the work designed below, shall be understood to be and is a change to the bid documents and shall be part of and included in the contract for the above referenced project. All General, Supplementary and Special Conditions, etc., as originally specified or as modified below shall apply to these items.
General Clarification:
During walk-through it was determined that all fire alarm detection and notification devices in the Kinley Center building as shown on drawing FA1.41 will need to be replaced to be compatible with the new system upgrade.
Clarifications to Fire Alarm Drawings:
1. Drawing FA1.51
a. REVISE KEYNOTE #1 to read: “DISCONNECT AND REMOVE EST-3 FIRE ALARM CONTROL
PANEL…”.
b. ADD KEYNOTE #3 to read: “EXISTING PYROTRONICS SYSTEM 3 FIRE ALARM CONTROL PANEL
AND ALL EXISTING CONNECTIONS TO REMAIN.
c. ADD KEYNOTE Cross reference #3 into Mechanical Room MECH 281 on drawing.
END OF ADDENDUM 01 – FIRE ALARM REPLACEMENT