25-0058 ACM REPORT.pdf

PDF 66 KB Posted

Attached to
Repair Exhaust Fans, Bldg FC420
Solicitation number
N4008525R9025
Issued by

About this file

This is an Asbestos Inspection Report for Building FC420 at MCB Camp Lejeune, dated August 11, 2025. The report details the presence of asbestos-containing materials (ACM) in the French Creek Dining Hall, a building constructed in 1975. Key findings include non-friable ACMs such as cloth lagging material in the southwest mechanical room HVAC ducts (8 SF) and interior caulking in kitchen areas and concrete wall joints (6 LF), identified during inspections from 2000 to 2023.

The report emphasizes that intact and undisturbed ACM is not considered a significant health hazard. Multiple sampling efforts have been conducted, with some materials like 9" tan floor tiles and adhesive testing positive for asbestos in various locations. The document provides detailed guidance on handling ACMs, including avoiding disturbance, reporting any damage, and contacting the Asbestos Program Manager at 910-451-5837 for further information. The building has a hazard ranking of 3/Green as of April 2023, with ongoing monitoring and periodic inspections of the identified asbestos-containing materials.

View the file

Other files

File Type Posted
Amend 0002.pdf PDF
Amend 0001.pdf PDF
25-0058 SOW.pdf PDF
N4008525B0058 Specs.pdf PDF
N4008525B0058 Dwgs.pdf PDF
RFP 250058.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASBESTOS INSPECTION REPORT of:

Building # FC420

MCB CAMP LEJEUNE

Monday, August 11, 2025

Print Date

Monday, August 11, 2025 Page 1 of 9Print Date:

INSPECTION SUMMARY

BLDG #:

OCCUPANT:

YEAR BUILT:

BUILDING COMMENTS:

FC420

FRENCH CREEK DINING HALL

HAZ RANK 3/GREEN [APR2023]

SEALANT ON WALL AT STAIRS

APR2023

ACM REMAINS

JUN2016

ACM REMAINS, ADDL SAMPLING, ACM INCLUDES:

MISC. SEALANT, BLACK

NOV2013

ACM GASKET, CAULK, AND SEALANT ON LAGGING REMAIN

AUG2011

TILE MASTIC AND CAULKING REMAIN, TILES VERIFIED NON ACM VIA TEM, ACM GASKET AND DUCTS REMOVED, ROOFING IS NEW

2009-2010 UNDER RENOVATION

NOV08

ADDL SAMPLING, ACM INCLUDES:

MASTIC UNDER 9" TILE

INTERIOR CAULKING, WHITE

GASKET MATERIAL

SEALANT ON CLOTH LAGGING MATERIAL, HVAC

JUL02 AES

NO ASBESTOS CONTAINING MATERIALS IDENTIFIED

DEC2000 (LTD.)

TANK INSULATION NON ACM

ASBESTOS MANAGER: 910-451-5837

Friable ACM(s) identified

Non-friable ACM(s) identified

NOTICE: The following asbestos-containing materials have been identified in this structure. Refer to survey findings for additional information or contact the Asbestos Program Manager. Please note ACM that is intact and undisturbed is not considered a significant health hazard to building occupants.

DESCRIPTION LOCATION Date Quantity

DESCRIPTION LOCATION Date Quantity

No friable ACM records found in database

NOTIFICATION OF ACM IN BUILDING

CLOTH LAGGING MATERIAL 8 SFSOUTHWEST MECHANICAL ROOM

HVAC DUCTS

11/18/2008

INTERIOR CAULKING, 6 LFKITCHEN AREAS, TILE WALLS TO FIXED

CEILINGS; SOUTHWEST MECHANICAL

AREA CONCRETE WALL JOINTS

11/18/2008

Monday, August 11, 2025 Page 2 of 9Print Date:

Tested Non ACM or REMOVED Materials

DESCRIPTION LOCATION Date

9" TAN FLOOR TILE AND ADHESIVE 110 SFEAST CENTER OFFICE AREA HALLWAY

(UNDER HM13)

11/18/2008

MISCELLANEOUS SEALANT 12 SFRESIDUAL MATERIAL ON WALL,

SOUTHEAST STAIRWELL

6/29/2016

9" TAN FLOOR TILE AND ADHESIVE 110 SFEAST CENTER OFFICE AREA HALLWAY

(UNDER HM13)

8/16/2011

CLOTH LAGGING MATERIAL 8 SFSOUTHWEST MECHANICAL ROOM

HVAC DUCTS

8/16/2011

INTERIOR CAULKING, 6 LFSOUTHWEST MECHANICAL AREA

CONCRETE WALL JOINTS

8/16/2011

9" TAN FLOOR TILE AND ADHESIVE 110 SFEAST CENTER OFFICE AREA HALLWAY

(UNDER HM13)

11/12/2013

INTERIOR CAULKING, 6 LFSOUTHWEST MECHANICAL AREA

CONCRETE WALL JOINTS

11/12/2013

CLOTH LAGGING MATERIAL 8 SFSOUTHWEST MECHANICAL ROOM

HVAC DUCTS

11/12/2013

9" TAN FLOOR TILE AND ADHESIVE 110 SFEAST CENTER OFFICE AREA HALLWAY

(UNDER HM13)

6/29/2016

INTERIOR CAULKING, 6 LFSOUTHWEST MECHANICAL AREA

CONCRETE WALL JOINTS

6/29/2016

CLOTH LAGGING MATERIAL 8 SFSOUTHWEST MECHANICAL ROOM

HVAC DUCTS

6/29/2016

9" TAN FLOOR TILE AND ADHESIVE 110 SFEAST CENTER OFFICE AREA HALLWAY

(UNDER HM13)

9/17/2019

INTERIOR CAULKING, 6 LFSOUTHWEST MECHANICAL AREA

CONCRETE WALL JOINTS

9/17/2019

MISCELLANEOUS SEALANT 12 SFRESIDUAL MATERIAL ON WALL,

SOUTHEAST STAIRWELL

9/17/2019

9" TAN FLOOR TILE AND ADHESIVE 110 SFEAST CENTER OFFICE AREA HALLWAY

(UNDER HM13)

4/12/2023

INTERIOR CAULKING, 6 LFSOUTHWEST MECHANICAL AREA

CONCRETE WALL JOINTS

4/12/2023

CLOTH LAGGING MATERIAL 8 SFSOUTHWEST MECHANICAL ROOM

HVAC DUCTS

4/12/2023

MISCELLANEOUS SEALANT 12 SFRESIDUAL MATERIAL ON WALL,

SOUTHEAST STAIRWELL

4/12/2023

ROOFING MATERIAL, EXTERIOR GROUND DEBRIS (SEE ALSO

HM10)

11/18/2008

Monday, August 11, 2025 Page 3 of 9Print Date:

BROWN VINYL BASE AND ADHESIVE, 4" OFFICES AND PUBLIC AREAS OF THE

BUILDING

7/18/2002

DEBRIS, WEST CENTER EXTERIOR GROUND

DEBRIS

11/18/2008

12" Off WHITE w/ BEIGE FLOOR TILE AND

ADHESIVE

EAST CENTRAL OFFICE AREA (OVER

HM15 TILE IN CENTER OFFICE)

11/18/2008

DUCT SEALANT, TAN OVERHEAD HVAC DUCT SYSTEMS ON

FIBERGLASS ROUND DUCTS

11/18/2008

GASKET MATERIAL SOUTHWEST MECHANICAL ROOM

WATER STORAGE TANK FLANGE (SEE

ALSO HM26)

11/18/2008

GASKET MATERIAL SOUTHWEST MECHANICAL ROOM

WATER STORAGE TANK FLANGE (SEE

ALSO HM25)

11/18/2008

DRYWALL AND JOINT MATERIAL OFFICES AND PUBLIC AREAS OF THE

BUILDING (SEE ALSO HM17)

7/18/2002

MISCELLANEOUS SEALANT OVERHEAD METAL VENTILATION

DUCT SEAMS

11/18/2008

CLOTH LAGGING MATERIAL SOUTH CENTRAL KITCHEN AREA,

WALL PENETRATION

11/18/2008

TEXTURED CEILING MATERIAL NORTH CENTER PRIVATE DINING 11/18/2008

SUSPECT TSI WITHIN WALLS SOUTH CENTRAL KITCHEN AREA,

WALL PENETRATION

11/18/2008

EXTERIOR CAULKING, NORTHHALF PICTURE WINDOWS AT

PERIMETER AND BASE ON BRICK

11/18/2008

JOINT MATERIAL EAST CENTER OFFICE AREA WALLS,

SKIM COAT

11/18/2008

DUCT SEALANT, GRAY OVERHEAD METAL VENTILATION

DUCT SEAMS

11/18/2008

INSULATION, LOOSE FILL ABOVE FIXED CEILINGS 11/18/2008

2'x2' CEILING TILE, OFFICES AND PUBLIC AREAS OF THE

BUILDING

7/18/2002

TANK INSULATION SOUTHWEST MECHANICAL ROOM,

WATER STORAGE TANK

12/21/2000

FIBROUS DEBRIS SOUTHWEST MECHANICAL ROOM AT

SUMP PIT AND FLOOR

11/18/2008

DUCT SEALANT, RED OVERHEAD DUCT SYSTEMS ON HVAC

AND VENTILATION DUCTS; CAN OF

MATERIAL

11/18/2008

ROOFING SEALANT, BLACK ROOF AT VENT BASE FLASHINGS 11/18/2008

ROOFING SEALANT, GRAY RESIDUAL MATERIALS ON ROOF AT

VENT BASE FLASHINGS AND

PENETRATIONS

11/18/2008

PITCH POCKET TAR ROOFING PENETRATIONS (PACKINGS

MATERIAL)

11/18/2008

PIPE INSULATION SOUTHWEST EXTERIOR STEAM PIT

PIPING

11/18/2008

HVAC DUCT INSULATION SOUTHWEST MECHANICAL ROOM

MAIN HVAC DUCTS

7/18/2002

Monday, August 11, 2025 Page 4 of 9Print Date:

ACM only presents a health hazard when asbestos fibers are airborne and inhaled.

Avoid disturbance which will release fibers. The presence of asbestos does not constitute a health hazard.

HEALTH ASPECTS:

Do not disturb or cause damage to ACM. Do not sand, grind or abrade materials or cause damage with any type of equipment.

CONDITIONS TO AVOID:

Report any damage, dust or debris that may come from ACM or suspect ACM, or any change in the condition of materials, or accidental disturbance to the Asbestos

Program Manager.

REPORTS OF DAMAGE:

Corrective action initiated to minimize fiber release and protect personnel. RESPONSE ACTION:

ACM will be inspected periodically to evaluate any changes in condition.INSPECTION:

The Camp Lejeune Asbestos Program Manager maintains a copy of the survey for the building.

RECORDKEEPING:

CAMP LEJEUNE Asbestos Program Manager: Phone: (910) 451-5837

BLACK VINYL BASE AND ADHESIVE, 4" EAST CENTER OFFICE AREAS AND

HALLWAY

11/18/2008

ROOFING MATERIAL, DEBRIS, ABOVE FIXED PLASTER

CEILINGS (SEE ALSO HM29)

11/18/2008

EXTERIOR CAULKING, EXTERIOR WALL BRICK EXPANSION

JOINTS; STEEL DOORS

8/16/2011

MISCELLANEOUS FLOOR COVERINGS, SOUTHSIDE KITCHEN AREA, UNDER

HARD TILE FLOORING

8/16/2011

GASKET MATERIAL SOUTHWEST MECHANICAL ROOM

WATER STORAGE TANK FLANGE (SEE

ALSO HM25)

8/16/2011

TANK INSULATION SOUTHWEST MECHANICAL ROOM,

WATER STORAGE TANK

7/18/2002

DRYWALL AND JOINT MATERIAL EAST CENTER OFFICE AREA WALLS

AND SKIM COAT ON BLOCK

8/16/2011

DUCT SEALANT, RED OVERHEAD DUCT SYSTEMS ON HVAC

AND VENTILATION DUCTS; CAN OF

MATERIAL

8/16/2011

GASKET MATERIAL SOUTHWEST MECHANICAL ROOM

WATER STORAGE TANK FLANGE (SEE

ALSO HM26)

8/16/2011

12" Off WHITE w/ BEIGE FLOOR TILE AND

ADHESIVE

EAST CENTRAL OFFICE AREA (OVER

HM15 TILE IN CENTER OFFICE)

8/16/2011

Monday, August 11, 2025 Page 5 of 9Print Date:

SAMPLES COLLECTED

Sample Sample

Date

HA Sample Location Chr

Amo

Oth

Description

FC420-01-01 7/18/200201 EAST CNTR OFFICES 0 0 02'x2' CEILING TILE, FC420-01-01 7/18/200201 OFFICES 0 0 02'x2' CEILING TILE, FC420-01-02 7/18/200201 DINING AREA 0 0 02'x2' CEILING TILE, FC420-01-02 7/18/200201 DINING AREA 0 0 02'x2' CEILING TILE, FC420-02-03 7/18/200202 EAST CNTR OFFICE AREA 0 0 0DRYWALL AND JOINT

MATERIAL

FC420-03-04 7/18/200203 EAST CNTR OFFICE AREA

HALL

0 0 0BROWN VINYL BASE

AND ADHESIVE, 4"

FC420-04-05 7/18/200204 SW MECH RM, SW 0 0 0HVAC DUCT

INSULATION

FC420-04-06 7/18/200204 SW MECH RM, NW 0 0 0HVAC DUCT

INSULATION

FC420-05-07 7/18/200205 SW MECH RM, CNTR TANK 0 0 0TANK INSULATION

FC420-05-08 7/18/200205 SW MECH RM, CNTR TANK 0 0 0TANK INSULATION

FC420-05-369B1 12/21/200005 DHW TANK 0 0 0TANK INSULATION

FC420-05-370B1 12/21/200005 DHW TANK 0 0 0TANK INSULATION

FC420-10-10 11/18/200810 CNTR NORTH OVHD 0 0 0ROOFING MATERIAL,

FC420-10-11 11/18/200810 SE OVHD 0 0 0ROOFING MATERIAL,

FC420-11-10 11/18/200811 CNTR NORTH OVHD 0 0 0DUCT SEALANT, RED

FC420-11-11 11/18/200811 EAST CNTR HEADS OVHD 0 0 0DUCT SEALANT, RED

FC420-11-20 8/16/201111 EAST CNTR OFFICE OVHD 0 0 0DUCT SEALANT, RED

FC420-12-10 11/18/200812 NORTH CNTR DINING 0 0 0TEXTURED CEILING

MATERIAL

FC420-13-10 11/18/200813 EAST CNTR OFFICE 0 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC420-13-11 11/18/200813 EAST CNTR OFFICE 0 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

Monday, August 11, 2025 Page 6 of 9Print Date:

HA Sample Location Chr

Amo

Oth

Description

FC420-13-20 8/16/201113 EAST CNTR OFFICE 0 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC420-13-20tem 8/16/201113 EAST CNTR OFFICE 0 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC420-14-10 11/18/200814 EAST CNTR OFFICE OVHD 0 0 0DUCT SEALANT, TAN

FC420-14-11 11/18/200814 SOUTH CNTR STRGE OVHD 0 0 0DUCT SEALANT, TAN

FC420-15-00ri13 11/12/201315 N/A 9 9 99" TAN FLOOR TILE AND

ADHESIVE

FC420-15-00ri16 6/29/201615 N/A 9 9 99" TAN FLOOR TILE AND

ADHESIVE

FC420-15-00ri23 4/12/202315 N/A 9 9 99" TAN FLOOR TILE AND

ADHESIVE

FC420-15-10 11/18/200815 EAST CNTR OFFICE HALL 4 0 09" TAN FLOOR TILE AND

ADHESIVE

FC420-15-20 8/16/201115 EAST CNTR OFFICE 2 0 09" TAN FLOOR TILE AND

ADHESIVE

FC420-15-20tem 8/16/201115 EAST CNTR OFFICE .1 .1 .19" TAN FLOOR TILE AND

ADHESIVE

FC420-15-50 9/17/201915 EAST CNTR OFFICE, SW 3 0 09" TAN FLOOR TILE AND

ADHESIVE

FC420-15-50tem 9/17/201915 EAST CNTR OFFICE, SW 0 0 09" TAN FLOOR TILE AND

ADHESIVE

FC420-16-10 11/18/200816 EAST CNTR OFFICE AREA

HALL

0 0 0BLACK VINYL BASE

AND ADHESIVE, 4"

FC420-17-10 11/18/200817 EAST CNTR OFFICE HALL

WALL

0 0 0JOINT MATERIAL

FC420-17-20 8/16/201117 EAST CNTR OFFICE WALL 0 0 0JOINT MATERIAL

FC420-17-21 8/16/201117 EAST CNTR OFFICE WALL 0 0 0JOINT MATERIAL

FC420-18-10 11/18/200818 SE KITCHEN AREA VENT

DUCT

0 0 0DUCT SEALANT, GRAY

FC420-19-10 11/18/200819 SE KITCHEN AREA (AT DUCT

HOLE)

0 0 0INSULATION, LOOSE

FILL

FC420-20-10 11/18/200820 SE KITCHEN AREA DUCT 0 0 0MISCELLANEOUS

SEALANT

WHITE

Monday, August 11, 2025 Page 7 of 9Print Date:

HA Sample Location Chr

Amo

Oth

Description

FC420-21-10 11/18/200821 SOUTH CNTR KITCHEN AREA 0 0 0CLOTH LAGGING

MATERIAL

FC420-22-10 11/18/200822 SOUTH CNTR KITCHEN AREA 0 0 0SUSPECT TSI WITHIN

WALLS

FC420-23-00ri11 8/16/201123 N/A 9 9 9INTERIOR CAULKING, WHITE

FC420-23-00ri13 11/12/201323 N/A 9 9 9INTERIOR CAULKING, WHITE

FC420-23-00ri16 6/29/201623 N/A 9 9 9INTERIOR CAULKING, WHITE

FC420-23-00ri19 9/17/201923 N/A 9 9 9INTERIOR CAULKING, WHITE

FC420-23-00ri23 4/12/202323 N/A 9 9 9INTERIOR CAULKING, WHITE

FC420-23-10 11/18/200823 SOUTH CNTR KITCHEN AREA

CEILING

0 0 0INTERIOR CAULKING, WHITE

FC420-23-11 11/18/200823 SW MECHANICAL AREA

WALL JOINT

2 0 0INTERIOR CAULKING, WHITE

FC420-23-50 9/17/201923 WEST MR OVERHEAD VENT 0 0 0INTERIOR CAULKING, WHITE

FC420-24-10 11/18/200824 SW MECH RM, WEST CNTR 0 0 0FIBROUS DEBRIS

FC420-24-11 11/18/200824 SW MECH RM, SW 0 0 0FIBROUS DEBRIS

FC420-24-12 11/18/200824 SW MECH RM, SE 0 0 0FIBROUS DEBRIS

FC420-25-10 11/18/200825 SW MECH RM, CNTR TANK

FLANGE

65 0 0GASKET MATERIAL THICK

FC420-26-10 11/18/200826 SW MECH RM, CNTR TANK

FLANGE

65 0 0GASKET MATERIAL THIN

FC420-27-00ri11 8/16/201127 N/A 9 9 9CLOTH LAGGING

MATERIAL

w/YELLOW SEALANT

FC420-27-00ri13 11/12/201327 N/A 9 9 9CLOTH LAGGING

MATERIAL

w/YELLOW SEALANT

FC420-27-00ri16 6/29/201627 N/A 9 9 9CLOTH LAGGING

MATERIAL

w/YELLOW SEALANT

FC420-27-00ri23 4/12/202327 Not Available 9 9 9CLOTH LAGGING

MATERIAL

w/YELLOW SEALANT

FC420-27-10 11/18/200827 SW MECH RM, WEST 3 0 0CLOTH LAGGING

MATERIAL

w/YELLOW SEALANT

FC420-28-10 11/18/200828 SW EXT. STEAM PIT 0 0 0PIPE INSULATION

FC420-29-10 11/18/200829 SW EXT. GROUND 0 0 0ROOFING MATERIAL, BLACK

Monday, August 11, 2025 Page 8 of 9Print Date:

HA Sample Location Chr

Amo

Oth

Description

FC420-29-11 11/18/200829 WEST CNTR EXT. GROUND 0 0 0ROOFING MATERIAL, BLACK

FC420-30-10 11/18/200830 WEST CNTR EXT. GROUND 0 0 0DEBRIS, BEIGE

FC420-31-10 11/18/200831 NORTHSIDE, WEST CNTR

WINDOW

0 0 0EXTERIOR CAULKING, GRAY

FC420-31-11 11/18/200831 NORTHSIDE, EAST CNTR

WINDOW

0 0 0EXTERIOR CAULKING, GRAY

FC420-32-10 11/18/200832 ROOF, SW VENT 0 0 0ROOFING SEALANT,

BLACK

FC420-32-11 11/18/200832 ROOF, EAST CNTR VENT 0 0 0ROOFING SEALANT,

BLACK

FC420-32-12 11/18/200832 ROOF, NORTH CNTR HVAC 0 0 0ROOFING SEALANT,

BLACK

FC420-33-10 11/18/200833 ROOF, SW HVAC 0 0 0ROOFING SEALANT,

GRAY

FC420-33-11 11/18/200833 ROOF, NORTH CNTR

PENETRATION

0 0 0ROOFING SEALANT,

GRAY

FC420-34-10 11/18/200834 ROOF, SW PIPE 0 0 0PITCH POCKET TAR BLACK

FC420-34-11 11/18/200834 ROOF, NORTH CNTR

PENETRATION

0 0 0PITCH POCKET TAR BLACK

FC420-40-20 8/16/201140 NORTH CNTR BRICK JOINT 0 0 0EXTERIOR CAULKING, WHITE

FC420-40-21 8/16/201140 WEST CNTR MECH RM DOOR 0 0 0EXTERIOR CAULKING, WHITE

FC420-41-20 8/16/201141 SOUTH CNTR KITCHEN, CNTR 0 0 0MISCELLANEOUS

FLOOR COVERINGS,

BLACK

FC420-45-00ri19 9/17/201945 N/A 9 9 9MISCELLANEOUS

SEALANT

BLACK

FC420-45-00ri23 4/12/202345 N/A 9 9 9MISCELLANEOUS

SEALANT

BLACK

FC420-45-40 6/29/201645 SOUTH EXT., EAST 2 0 0MISCELLANEOUS

SEALANT

BLACK

Monday, August 11, 2025 Page 9 of 9Print Date: