2412-02_PCSB_Northeast_HS_Roof_Permit_Set_Structural_2025.04.16_S&S.pdf

PDF 2 MB Posted

Attached to
Reroof Buildings 3, 6, 19 and 28
Solicitation number
25-CR-054
Issued by
Pinellas County, Florida

About this file

The document is a structural engineering permit set for the Northeast High School Roof Replacement Project, prepared by Williamson Dacar Associates for the Pinellas County School District. The project involves reroofing Buildings 3, 6, 19, and 28, with detailed wind load plans and structural details for each building. The structural drawings provide comprehensive technical specifications for roof support systems, including steel joist configurations, rooftop equipment (RTU) support details, and wind load calculations. The plans are dated April 18, 2025, and are marked as a permit set, indicating they are prepared for final review and approval prior to construction.

The technical drawings specify critical structural elements such as existing steel joist configurations, new structural curbing requirements, and detailed mounting instructions for rooftop equipment. Wind load calculations are provided for multiple roof areas, with specific pressure schedules accounting for different wind speeds (154 MPH) and risk categories. The plans include precise measurements for roof heights, joist spacing, and support mechanisms, with specific notes on steel frame connections, shim placements, and welding requirements. The project appears to be funded through the school district's capital improvement or maintenance budget, with a focus on replacing and reinforcing existing roof structures to meet current building and wind resistance standards.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA A

AREA B

1'

06h = 14.0'

.6 h

.0

.2 h

.7

3 3

2 2

1'

.6 h

.7

0.6h = 8.7'

.2 h

.9

0.6h = 14.0'

.6 h

.7

A5.3

DRAWING TITLE:

SHEET NO.

WDA PROJ. NO:

OWNER PROJ. NO:

SCALE: REFER TO SHEET

ISSUE/REVISION OF DRAWINGS:

ARCHITECT: AA0002541

ENGINEER: EB 0006884

PHASE:

CHECKED:

DRAWN:

T H

IS

D

O C

U M

E N

T C

O N

T A

IN

S

C O

P Y

R

IG

H T

E D

M A

T E

R

IA

L A

N D

T R

A D

E S

E C

R E

T I N

F O

R M

A T

IO

N

B E

L O

N G

IN

G

E X

C L U

S

IV

E L Y

T O

W

IL

L

IA

M S

O N

D A

C A

R A

S S

O C

IA

T

E S

IN

C

A N

Y U

N A

U T

H O

R

IZ

E D

U S

E

D

IS

C L O

S U

R E

D

IS

S

E M

IN

A

T

IO

N O

R D

U P

L

IC

A T

IO

N

O F

A N

Y O

F T

H E

I N

F O

R M

A T

IO

N

C O

N T

A

IN

E D

H E

R E

IN

M

A Y

R E

S U

L T

I N

L

IA

B

IL

IT

Y

U N

D E

R A

P P

L

IC

A B

L E

A

W S

P R

O F

E S

S

IO

N A

L

T H

E O

D O

R E

J W

IL

L

IA

M S

O N

A R

P

E

/1

/2

:2 :3

P

M

WIND LOAD PLAN

- BUILDING 3

th

S t.

N S t.

P e te rs b u rg

F

L

S1.0

2412-02

PERMIT SET

N O

R T

H E

A S

T H

IG

H

S C

H O

O L R

O O

F R

E P

L A

C E

M E

N T

B

U

IL

D

IN

G S

Checker

Author

3/32" = 1'-0"S1.0

1 WIND LOAD PLAN - BUILDING 3

COMPONENTS AND CLADDING (ULTIMATE) UPLIFT PRESSURE SCHEDULE

1. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY.

2. ALL WIND PRESSURE VALUES INDICATED ARE IN POUNDS PER SQUARE FOOT (PSF). MULTIPLY

ULTIMATE WIND PRESSURE BY 0.60 FOR ASD PRESSURE.

3. FOR NET UPLIFT CALCULATION, THE WEIGHT OF THE STRUCTURAL MEMBER AND THE STRUCTURAL

DECK SUPPORTED ARE THE ONLY TWO (2) LOADS THAT CAN BE DEDUCTED FROM THE UPLIFT

PRESSURES INDICATED ON THE SCHEDULES.

NOTE:

BASIC WIND SPEED (3 SECOND GUST):

RISK CATEGORY

EXPOSURE:

ENCLOSED BUILDING INTERNAL PRESSURE COEFFICIENT:

P= qh (GCp) - (GCpi):

COMPONENTS AND CLADDING WIND PRESSURES:

154 MPH

III

C

+/- 0.18

RE: TABLE ABOVE

ROOF CORNERS DISTANCE: AREA A: 0.2h = 2.9' 0.6h = 8.7'

AREA B: 0.2h = 4.7' 0.6h = 14.0'

MEAN ROOF HEIGHT:

AREA A = 14' - 6"

AREA B = 23' - 2"

10 SQ. FT.

EFFECTIVE WIND AREA

+22 PSF/-83 PSF

ZONE

2 +22 PSF/-109 PSF

20 SQ. FT.

+20 PSF/-78 PSF

+20 PSF/-102 PSF

50 SQ. FT.

+18 PSF/-70 PSF

+18 PSF/-93 PSF

100 SQ. FT.

+17 PSF/-65 PSF

+17 PSF/-86 PSF

200 SQ. FT.

+17 PSF/-59 PSF

+17 PSF/-79 PSF

500 SQ. FT.

+17 PSF/-52 PSF

+17 PSF/-70 PSF

3 +22 PSF/-149 PSF +20 PSF/-135 PSF+18 PSF/-116 PSF +17 PSF/-102 PSF +17 PSF/-88 PSF +17 PSF/-70 PSF

1' +22 PSF/-48 PSF +20 PSF/-48 PSF +18 PSF/-48 PSF +17 PSF/-48 PSF +17 PSF/-41 PSF +17 PSF/-33 PSF

AREA A

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA B

1 +24 PSF/-91 PSF

2 +24 PSF/-120 PSF

+22 PSF/-85 PSF

+22 PSF/-112 PSF

+20 PSF/-77 PSF

+20 PSF/-102 PSF

+19 PSF/-71 PSF

+19 PSF/-94 PSF

+19 PSF/-65 PSF

+19 PSF/-86 PSF

+19 PSF/-57 PSF

+19 PSF/-76 PSF

3 +24 PSF/-163 PSF +22 PSF/-147 PSF +20 PSF/-127 PSF +19 PSF/-112 PSF +19 PSF/-97 PSF +19 PSF/-76 PSF

1' +24 PSF/-52 PSF +22 PSF/-52 PSF +20 PSF/-52 PSF +19 PSF/-52 PSF +19 PSF/-45 PSF +19 PSF/-36 PSF

NO. DATE DESCRIPTION

1 03/04/25 PH2 DD

2 04/01/25 PH3 100% CD

3 04/16/25 PH4 100% CD PERMIT

04/18/2025

AREA C

AREA D

AREA E

AREA F

AREA G

AREA G

AREA H

AREA I

A5.4

3 3

0.6h = 22.8'

0.2h = 7.6'

.6 h

.8

2 1

3 3

0.6h = 16.2'

.2 h

.4

0.6h = 16.2'

.6 h

.2

0.2h = 5.4'

0.6h = 9.6'

.2 h

.2

3 3

3 3

1'

1'

1'

0.6h = 9.3'

.2 h

.1

0.6h = 9.3'

0.6h = 9.3'

0.2h = 3.1'

0.6h = 9.3' 0.6h = 9.3'

DRAWING TITLE:

SHEET NO.

WDA PROJ. NO:

OWNER PROJ. NO:

SCALE: REFER TO SHEET

ISSUE/REVISION OF DRAWINGS:

ARCHITECT: AA0002541

ENGINEER: EB 0006884

PHASE:

CHECKED:

DRAWN:

T H

IS

D

O C

U M

E N

T C

O N

T A

IN

S

C O

P Y

R

IG

H T

E D

M A

T E

R

IA

L A

N D

T R

A D

E S

E C

R E

T I N

F O

R M

A T

IO

N

B E

L O

N G

IN

G

E X

C L U

S

IV

E L Y

T O

W

IL

L

IA

M S

O N

D A

C A

R A

S S

O C

IA

T

E S

IN

C

A N

Y U

N A

U T

H O

R

IZ

E D

U S

E

D

IS

C L O

S U

R E

D

IS

S

E M

IN

A

T

IO

N O

R D

U P

L

IC

A T

IO

N

O F

A N

Y O

F T

H E

I N

F O

R M

A T

IO

N

C O

N T

A

IN

E D

H E

R E

IN

M

A Y

R E

S U

L T

I N

L

IA

B

IL

IT

Y

U N

D E

R A

P P

L

IC

A B

W S

P R

O F

E S

S

IO

N A

L

T H

E O

D O

R E

J W

IL

L

IA

M S

O N

A R

P

E

/1

/2

:2 :3

P

M

WIND LOAD PLAN

- BUILDING 6

th

S t.

N S t.

P e te rs b u rg

F

L

S1.1

2412-02

PERMIT SET

N O

R T

H E

A S

T H

IG

H

S C

H O

O L R

O O

F R

E P

L A

C E

M E

N T

B

U

IL

D

IN

G S

Checker

Author

3/32" = 1'-0"S1.1

1 WIND LOAD PLAN - BUILDING 6

COMPONENTS AND CLADDING (ULTIMATE) UPLIFT PRESSURE SCHEDULE

1. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY.

2. ALL WIND PRESSURE VALUES INDICATED ARE IN POUNDS PER SQUARE FOOT (PSF). MULTIPLY

ULTIMATE WIND PRESSURE BY 0.60 FOR ASD PRESSURE.

3. FOR NET UPLIFT CALCULATION, THE WEIGHT OF THE STRUCTURAL MEMBER AND THE STRUCTURAL

DECK SUPPORTED ARE THE ONLY TWO (2) LOADS THAT CAN BE DEDUCTED FROM THE UPLIFT

PRESSURES INDICATED ON THE SCHEDULES.

NOTE:

BASIC WIND SPEED (3 SECOND GUST):

RISK CATEGORY

EXPOSURE:

ENCLOSED BUILDING INTERNAL PRESSURE COEFFICIENT:

P= qh (GCp) - (GCpi):

COMPONENTS AND CLADDING WIND PRESSURES:

154 MPH

III

C

+/- 0.18

RE: TABLE ABOVE

ROOF CORNERS DISTANCE:

AREA C: 0.2h = 7.6'

0.6h = 22.8'

AREA D: 0.2h = 5.4' 0.6h = 16.2'

AREA E: 0.2h = 5.4' 0.6h = 16.2'

AREA F: 0.2h = 3.2' 0.6h = 9.6'

AREA G: 0.2h = 4.1' 0.6h = 12.3'

AREA H: 0.2h = 3.1' 0.6h = 9.3'

AREA I: 0.2h = 3.1' 0.6h = 9.3'

MEAN ROOF HEIGHT:

AREA C = 38' - 0"

AREA D = 27' - 0"

AREA E = 27' - 0"

AREA F = 16' - 0"

AREA G = 20' - 6"

AREA H = 15' - 6"

AREA I = 15' - 6"

10 SQ. FT.

EFFECTIVE WIND AREA

+26 PSF/-100 PSF

ZONE

2 +26 PSF/-132 PSF

20 SQ. FT.

+24 PSF/-94 PSF

+24 PSF/-124 PSF

50 SQ. FT.

+22 PSF/-85 PSF

+22 PSF/-112 PSF

100 SQ. FT.

+21 PSF/-78 PSF

+21 PSF/-104 PSF

200 SQ. FT.

+21 PSF/-72 PSF

+21 PSF/-96 PSF

500 SQ. FT.

+21 PSF/-63 PSF

+21 PSF/-84 PSF

3 +26 PSF/-180 PSF +24 PSF/-163 PSF+22 PSF/-141 PSF +21 PSF/-124 PSF +21 PSF/-107 PSF +21 PSF/-84 PSF

1' +26 PSF/-58 PSF +24 PSF/-58 PSF +22 PSF/-58 PSF +21 PSF/-58 PSF +21 PSF/-50 PSF +21 PSF/-39 PSF

AREA C

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA D

1 +24 PSF/-94 PSF

2 +24 PSF/-123 PSF

+23 PSF/-87 PSF

+23 PSF/-115 PSF

+21 PSF/-79 PSF

+21 PSF/-105 PSF

+19 PSF/-73 PSF

+19 PSF/-97 PSF

+19 PSF/-67 PSF

+19 PSF/-89 PSF

+19 PSF/-59 PSF

+19 PSF/-79 PSF

3 +24 PSF/-168 PSF +23 PSF/-152 PSF +21 PSF/-131 PSF +19 PSF/-115 PSF+19 PSF/-100 PSF +19 PSF/-79 PSF

1' +24 PSF/-54 PSF +23 PSF/-54 PSF +21 PSF/-54 PSF +19 PSF/-54 PSF +19 PSF/-46 PSF +19 PSF/-37 PSF

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA E

1 +24 PSF/-94 PSF

2 +24 PSF/-123 PSF

+23 PSF/-87 PSF

+23 PSF/-115 PSF

+21 PSF/-79 PSF

+21 PSF/-105 PSF

+19 PSF/-73 PSF

+19 PSF/-97 PSF

+19 PSF/-67 PSF

+19 PSF/-89 PSF

+19 PSF/-59 PSF

+19 PSF/-79 PSF

3 +24 PSF/-168 PSF +23 PSF/-152 PSF +21 PSF/-131 PSF +19 PSF/-115 PSF+19 PSF/-100 PSF +19 PSF/-79 PSF

1' +24 PSF/-54 PSF +23 PSF/-54 PSF +21 PSF/-54 PSF +19 PSF/-54 PSF +19 PSF/-46 PSF +19 PSF/-37 PSF

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA F

1 +22 PSF/-84 PSF

2 +22 PSF/-111 PSF

+20 PSF/-79 PSF

+20 PSF/-104 PSF

+19 PSF/-71 PSF

+19 PSF/-94 PSF

+17 PSF/-66 PSF

+17 PSF/-87 PSF

+17 PSF/-60 PSF

+17 PSF/-80 PSF

+17 PSF/-53 PSF

+17 PSF/-71 PSF

3 +22 PSF/-151 PSF +20 PSF/-137 PSF +19 PSF/-118 PSF +17 PSF/-104 PSF +17 PSF/-90 PSF +17 PSF/-71 PSF

1' +22 PSF/-49 PSF +20 PSF/-49 PSF +19 PSF/-49 PSF +17 PSF/-49 PSF +17 PSF/-42 PSF +17 PSF/-33 PSF

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA G

1 +23 PSF/-88 PSF

2 +23 PSF/-117 PSF

+22 PSF/-83 PSF

+22 PSF/-109 PSF

+20 PSF/-75 PSF

+20 PSF/-99 PSF

+18 PSF/-69 PSF

+18 PSF/-92 PSF

+18 PSF/-63 PSF

+18 PSF/-84 PSF

+18 PSF/-56 PSF

+18 PSF/-74 PSF

3 +23 PSF/-159 PSF +22 PSF/-144 PSF +20 PSF/-124 PSF +18 PSF/-109 PSF +18 PSF/-94 PSF +18 PSF/-74 PSF

1' +23 PSF/-51 PSF +22 PSF/-51 PSF +20 PSF/-51 PSF +18 PSF/-51 PSF +18 PSF/-44 PSF +18 PSF/-35 PSF

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA H

1 +22 PSF/-84 PSF

2 +22 PSF/-110 PSF

+20 PSF/-78 PSF

+20 PSF/-103 PSF

+19 PSF/-71 PSF

+19 PSF/-94 PSF

+17 PSF/-65 PSF

+17 PSF/-87 PSF

+17 PSF/-60 PSF

+17 PSF/-80 PSF

+17 PSF/-53 PSF

+17 PSF/-70 PSF

3 +22 PSF/-150 PSF +20 PSF/-136 PSF +19 PSF/-117 PSF +17 PSF/-103 PSF +17 PSF/-89 PSF +17 PSF/-70 PSF

1' +22 PSF/-48 PSF +20 PSF/-48 PSF +19 PSF/-48 PSF +17 PSF/-48 PSF +17 PSF/-42 PSF +17 PSF/-33 PSF

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA I

1 +22 PSF/-84 PSF

2 +22 PSF/-110 PSF

+20 PSF/-78 PSF

+20 PSF/-103 PSF

+19 PSF/-71 PSF

+19 PSF/-94 PSF

+17 PSF/-65 PSF

+17 PSF/-87 PSF

+17 PSF/-60 PSF

+17 PSF/-80 PSF

+17 PSF/-53 PSF

+17 PSF/-70 PSF

3 +22 PSF/-150 PSF +20 PSF/-136 PSF +19 PSF/-117 PSF +17 PSF/-103 PSF +17 PSF/-89 PSF +17 PSF/-70 PSF

1' +22 PSF/-48 PSF +20 PSF/-48 PSF +19 PSF/-48 PSF +17 PSF/-48 PSF +17 PSF/-42 PSF +17 PSF/-33 PSF

NO. DATE DESCRIPTION

1 03/04/25 PH2 DD

2 04/01/25 PH3 100% CD

AREA J

AREA K

AREA L

3 3

1'

1'

0.6h = 12.0'

0.2h = 4.0'

0.6h = 12.0' 0.6h = 12.0'

0.6h = 9.0'

0.2h = 3.0'

0.6h = 9.0' 0.6h = 9.0'

0.6h = 10.5'

.2 h

.5

0.6h = 10.5'

DRAWING TITLE:

SHEET NO.

WDA PROJ. NO:

OWNER PROJ. NO:

SCALE: REFER TO SHEET

ISSUE/REVISION OF DRAWINGS:

ARCHITECT: AA0002541

ENGINEER: EB 0006884

PHASE:

CHECKED:

DRAWN:

T H

IS

D

O C

U M

E N

T C

O N

T A

IN

S

C O

P Y

R

IG

H T

E D

M A

T E

R

IA

L A

N D

T R

A D

E S

E C

R E

T I N

F O

R M

A T

IO

N

B E

L O

N G

IN

G

E X

C L U

S

IV

E L Y

T O

W

IL

L

IA

M S

O N

D A

C A

R A

S S

O C

IA

T

E S

IN

C

A N

Y U

N A

U T

H O

R

IZ

E D

U S

E

D

IS

C L O

S U

R E

D

IS

S

E M

IN

A

T

IO

N O

R D

U P

L

IC

A T

IO

N

O F

A N

Y O

F T

H E

I N

F O

R M

A T

IO

N

C O

N T

A

IN

E D

H E

R E

IN

M

A Y

R E

S U

L T

I N

L

IA

B

IL

IT

Y

U N

D E

R A

P P

L

IC

A B

W S

P R

O F

E S

S

IO

N A

L

T H

E O

D O

R E

J W

IL

L

IA

M S

O N

A R

P

E

/1

/2

:2 :3

P

M

WIND LOAD PLAN

- BUILDING 19

th

S t.

N S t.

P e te rs b u rg

F

L

S1.2

2412-02

PERMIT SET

N O

R T

H E

A S

T H

IG

H

S C

H O

O L R

O O

F R

E P

L A

C E

M E

N T

B

U

IL

D

IN

G S

Checker

Author

3/32" = 1'-0"S1.2

1 WIND LOAD PLAN - BUILDING 19

COMPONENTS AND CLADDING (ULTIMATE) UPLIFT PRESSURE SCHEDULE

1. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY.

2. ALL WIND PRESSURE VALUES INDICATED ARE IN POUNDS PER SQUARE FOOT (PSF). MULTIPLY

ULTIMATE WIND PRESSURE BY 0.60 FOR ASD PRESSURE.

3. FOR NET UPLIFT CALCULATION, THE WEIGHT OF THE STRUCTURAL MEMBER AND THE STRUCTURAL

DECK SUPPORTED ARE THE ONLY TWO (2) LOADS THAT CAN BE DEDUCTED FROM THE UPLIFT

PRESSURES INDICATED ON THE SCHEDULES.

NOTE:

BASIC WIND SPEED (3 SECOND GUST):

RISK CATEGORY

EXPOSURE:

ENCLOSED BUILDING INTERNAL PRESSURE COEFFICIENT:

P= qh (GCp) - (GCpi):

COMPONENTS AND CLADDING WIND PRESSURES:

154 MPH

III

C

+/- 0.18

RE: TABLE ABOVE

ROOF CORNERS DISTANCE:

AREA J: 0.2h = 3.0'

0.6h = 9.0'

AREA K: 0.2h = 3.5' 0.6h = 10.5'

AREA L: 0.2h = 4.0' 0.6h = 12.0'

MEAN ROOF HEIGHT:

AREA J = 15' - 0"

AREA K = 17' - 6"

AREA L = 20' - 0"

10 SQ. FT.

EFFECTIVE WIND AREA

+22 PSF/-83 PSF

ZONE

2 +22 PSF/-109 PSF

20 SQ. FT.

+20 PSF/-78 PSF

+20 PSF/-102 PSF

50 SQ. FT.

+18 PSF/-70 PSF

+18 PSF/-93 PSF

100 SQ. FT.

+17 PSF/-65 PSF

+17 PSF/-86 PSF

200 SQ. FT.

+17 PSF/-59 PSF

+17 PSF/-79 PSF

500 SQ. FT.

+17 PSF/-52 PSF

+17 PSF/-70 PSF

3 +22 PSF/-149 PSF +20 PSF/-135 PSF+18 PSF/-116 PSF +17 PSF/-102 PSF +17 PSF/-88 PSF +17 PSF/-70 PSF

1' +22 PSF/-48 PSF +20 PSF/-48 PSF +18 PSF/-48 PSF +17 PSF/-48 PSF +17 PSF/-41 PSF +17 PSF/-33 PSF

AREA J

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA K

1 +22 PSF/-86 PSF

2 +22 PSF/-113 PSF

+21 PSF/-80 PSF

+21 PSF/-106 PSF

+19 PSF/-73 PSF

+19 PSF/-96 PSF

+18 PSF/-67 PSF

+18 PSF/-89 PSF

+18 PSF/-61 PSF

+18 PSF/-82 PSF

+18 PSF/-54 PSF

+18 PSF/-72 PSF

3 +22 PSF/-154 PSF +21 PSF/-139 PSF +19 PSF/-120 PSF +18 PSF/-106 PSF +18 PSF/-91 PSF +18 PSF/-72 PSF

1' +22 PSF/-49 PSF +21 PSF/-49 PSF +19 PSF/-49 PSF +18 PSF/-49 PSF +18 PSF/-43 PSF +18 PSF/-34 PSF

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA L

1 +23 PSF/-88 PSF

2 +23 PSF/-116 PSF

+21 PSF/-82 PSF

+21 PSF/-109 PSF

+20 PSF/-75 PSF

+20 PSF/-99 PSF

+18 PSF/-69 PSF

+18 PSF/-91 PSF

+18 PSF/-63 PSF

+18 PSF/-84 PSF

+18 PSF/-55 PSF

+18 PSF/-74 PSF

3 +23 PSF/-158 PSF +21 PSF/-143 PSF +20 PSF/-123 PSF +18 PSF/-109 PSF +18 PSF/-94 PSF +18 PSF/-74 PSF

1' +23 PSF/-51 PSF +21 PSF/-51 PSF +20 PSF/-51 PSF +18 PSF/-51 PSF +18 PSF/-44 PSF +18 PSF/-34 PSF

NO. DATE DESCRIPTION

1 03/04/25 PH2 DD

2 04/01/25 PH3 100% CD

AREA M

AREA N

AREA O

3 3

DRAWING TITLE:

SHEET NO.

WDA PROJ. NO:

OWNER PROJ. NO:

SCALE: REFER TO SHEET

ISSUE/REVISION OF DRAWINGS:

ARCHITECT: AA0002541

ENGINEER: EB 0006884

PHASE:

CHECKED:

DRAWN:

T H

IS

D

O C

U M

E N

T C

O N

T A

IN

S

C O

P Y

R

IG

H T

E D

M A

T E

R

IA

L A

N D

T R

A D

E S

E C

R E

T I N

F O

R M

A T

IO

N

B E

L O

N G

IN

G

E X

C L U

S

IV

E L Y

T O

W

IL

L

IA

M S

O N

D A

C A

R A

S S

O C

IA

T

E S

IN

C

A N

Y U

N A

U T

H O

R

IZ

E D

U S

E

D

IS

C L O

S U

R E

D

IS

S

E M

IN

A

T

IO

N O

R D

U P

L

IC

A T

IO

N

O F

A N

Y O

F T

H E

I N

F O

R M

A T

IO

N

C O

N T

A

IN

E D

H E

R E

IN

M

A Y

R E

S U

L T

I N

L

IA

B

IL

IT

Y

U N

D E

R A

P P

L

IC

A B

W S

P R

O F

E S

S

IO

N A

L

T H

E O

D O

R E

J W

IL

L

IA

M S

O N

A R

P

E

/1

/2

:2 :3

P

M

WIND LOAD PLAN

- BUILDING 28

th

S t.

N S t.

P e te rs b u rg

F

L

S1.3

2412-02

PERMIT SET

N O

R T

H E

A S

T H

IG

H

S C

H O

O L R

O O

F R

E P

L A

C E

M E

N T

B

U

IL

D

IN

G S

Checker

Author

3/32" = 1'-0"S1.3

1 WIND LOAD PLAN - BUILDING 28

COMPONENTS AND CLADDING (ULTIMATE) UPLIFT PRESSURE SCHEDULE

1. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY.

2. ALL WIND PRESSURE VALUES INDICATED ARE IN POUNDS PER SQUARE FOOT (PSF). MULTIPLY

ULTIMATE WIND PRESSURE BY 0.60 FOR ASD PRESSURE.

3. FOR NET UPLIFT CALCULATION, THE WEIGHT OF THE STRUCTURAL MEMBER AND THE STRUCTURAL

DECK SUPPORTED ARE THE ONLY TWO (2) LOADS THAT CAN BE DEDUCTED FROM THE UPLIFT

PRESSURES INDICATED ON THE SCHEDULES.

NOTE:

BASIC WIND SPEED (3 SECOND GUST):

RISK CATEGORY

EXPOSURE:

ENCLOSED BUILDING INTERNAL PRESSURE COEFFICIENT:

P= qh (GCp) - (GCpi):

COMPONENTS AND CLADDING WIND PRESSURES:

154 MPH

III

C

+/- 0.18

RE: TABLE ABOVE

ROOF CORNERS DISTANCE:

AREA M: 0.2h = 5.6'

0.6h = 16.8'

AREA N: 0.2h = 3.0' 0.6h = 9.0'

AREA O: 0.2h = 2.9' 0.6h = 8.7'

MEAN ROOF HEIGHT:

AREA M = 28' - 0"

AREA N = 15' - 0"

AREA O = 14' - 6"

10 SQ. FT.

EFFECTIVE WIND AREA

+24 PSF/-94 PSF

ZONE

2 +24 PSF/-124 PSF

20 SQ. FT.

+23 PSF/-88 PSF

+23 PSF/-116 PSF

50 SQ. FT.

+21 PSF/-80 PSF

+21 PSF/-106 PSF

100 SQ. FT.

+19 PSF/-74 PSF

+19 PSF/-98 PSF

200 SQ. FT.

+19 PSF/-68 PSF

+19 PSF/-90 PSF

500 SQ. FT.

+19 PSF/-59 PSF

+19 PSF/-79 PSF

3 +24 PSF/-169 PSF +23 PSF/-153 PSF+21 PSF/-132 PSF +19 PSF/-116 PSF+19 PSF/-100 PSF +19 PSF/-79 PSF

1' +24 PSF/-54 PSF +23 PSF/-54 PSF +21 PSF/-54 PSF +19 PSF/-54 PSF +19 PSF/-47 PSF +19 PSF/-37 PSF

AREA M

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA N

1 +22 PSF/-83 PSF

2 +22 PSF/-109 PSF

+20 PSF/-78 PSF

+20 PSF/-102 PSF

+18 PSF/-70 PSF

+18 PSF/-93 PSF

+17 PSF/-65 PSF

+17 PSF/-86 PSF

+17 PSF/-59 PSF

+17 PSF/-79 PSF

+17 PSF/-52 PSF

+17 PSF/-70 PSF

3 +22 PSF/-149 PSF +20 PSF/-135 PSF +18 PSF/-116 PSF +17PSF/-102 PSF +17 PSF/-88 PSF +17 PSF/-70 PSF

1' +22 PSF/-48 PSF +20 PSF/-48 PSF +18 PSF/-48 PSF +17 PSF/-48 PSF +17 PSF/-41 PSF +17 PSF/-33 PSF

10 SQ. FT.

EFFECTIVE WIND AREA

ZONE 20 SQ. FT. 50 SQ. FT. 100 SQ. FT. 200 SQ. FT. 500 SQ. FT.

AREA O

1 +22 PSF/-83 PSF

2 +22 PSF/-109 PSF

+20 PSF/-78 PSF

+20 PSF/-102 PSF

+18 PSF/-70 PSF

+18 PSF/-93 PSF

+17 PSF/-65 PSF

+17 PSF/-86 PSF

+17 PSF/-59 PSF

+17 PSF/-79 PSF

+17 PSF/-52 PSF

+17 PSF/-70 PSF

3 +22 PSF/-149 PSF +20 PSF/-135 PSF +18 PSF/-116 PSF +17 PSF/-102 PSF +17 PSF/-88 PSF +17 PSF/-70 PSF

1' +22 PSF/-48 PSF +20 PSF/-48 PSF +18 PSF/-48 PSF +17 PSF/-48 PSF +17 PSF/-41 PSF +17 PSF/-33 PSF

NO. DATE DESCRIPTION

1 03/04/25 PH2 DD

2 04/01/25 PH3 100% CD

16' - 0"

A5.3

A5.3

A5.3

A5.3

A5.3

A5.3

A5.3

A5.3

/2

EXISING 22K6 JOISTS @ 5'-0" O.C.

/2

KSF-1

2,151 LBS

KSF-2

1,194 LBS

KSF-3

1,116 LBS

EXISING 12K1 JOISTS @ 5'-0" O.C.

EXISING 26K6 JOISTS @ 5'-0" O.C.

S5.1

S5.1

1 SIM.

S5.1

1 SIM.

S5.1

DRAWING TITLE:

SHEET NO.

WDA PROJ. NO:

OWNER PROJ. NO:

SCALE: REFER TO SHEET

ISSUE/REVISION OF DRAWINGS:

ARCHITECT: AA0002541

ENGINEER: EB 0006884

PHASE:

CHECKED:

DRAWN:

T H

IS

D

O C

U M

E N

T C

O N

T A

IN

S

C O

P Y

R

IG

H T

E D

M A

T E

R

IA

L A

N D

T R

A D

E S

E C

R E

T I N

F O

R M

A T

IO

N

B E

L O

N G

IN

G

E X

C L U

S

IV

E L Y

T O

W

IL

L

IA

M S

O N

D A

C A

R A

S S

O C

IA

T

E S

IN

C

A N

Y U

N A

U T

H O

R

IZ

E D

U S

E

D

IS

C L O

S U

R E

D

IS

S

E M

IN

A

T

IO

N O

R D

U P

L

IC

A T

IO

N

O F

A N

Y O

F T

H E

I N

F O

R M

A T

IO

N

C O

N T

A

IN

E D

H E

R E

IN

M

A Y

R E

S U

L T

I N

L

IA

B

IL

IT

Y

U N

D E

R A

P P

L

IC

A B

W S

P R

O F

E S

S

IO

N A

L

T H

E O

D O

R E

J W

IL

L

IA

M S

O N

A R

P

E

/1

/2

:2 :3

P

M

PARTIAL ROOF

FRAMING PLAN -

BUILDING 19

th

S t.

N S t.

P e te rs b u rg

F

L

S1.4

2412-02

PERMIT SET

N O

R T

H E

A S

T H

IG

H

S C

H O

O L R

O O

F R

E P

L A

C E

M E

N T

B

U

IL

D

IN

G S

Checker

Author

NO. DATE DESCRIPTION

1 04/16/25 PH4 100% CD PERMIT

3/32" = 1'-0"S1.4

1 ROOF FRAMING PLAN - BUILDING 19

EXISTING 20K6 JOISTS @ 5'-0" O.C.

HSS 6" x 4" x 1/4" SUBFRAME

NEW RTU (SEE MECH. DWGS.) REFER

TO FRAMING PLAN FOR RTU LOCATIONS

SPAN MIN. (5) JOISTS KSF-2 & 3, (6) JOISTS KSF-1

20' - 4 1/2" (V.I.F)

1/4" 3"

TYP. @ JOISTS

HSS 6" x 4" x 1/4" STEEL FRAME

EXISTING STEEL JOISTS

@ 5'-0" O.C.

RTU

NEW STRUCTURAL CURBING. VERIFY

TOP OF NEW CURBING IS MIN. 18"

ABOVE ROOF MEMBRANE (PROVIDE

SHOP DRAWINGS AND

CALCULATIONS FOR REVIEW AND

APPROVAL)

1/4" - 14 TEK SCREW @ 8" O.C. ALL ABOUT

EXISTING 1-1/2" METAL

DECK TO REMAIN

PROVIDE 7" x 3" x 1-1/2" SOLID STEEL SHIMS

BETWEEN TOP OF JOISTS AND NEW STEEL

FRAME. WELD SHIMS TO TOP OF JOISTS

(TYP. @ LOCATIONS OF STEEL FRAME

BEARING ON JOISTS)

1/4"

TYP.

1/4" 3"

TYP. @ JOISTS

NOTE: JST. STIFF. NOT

REQUIRED FOR POINT LOADS:

< 250 LBS @ TOP CHORD

<100 LBS @ BOT. CHORD

EQUIP. CURB

POINT LOAD, ETC.

STEEL JOIST

POINT

LOAD

WELD L 2 1/2" x 2 1/2" x 1/4"

FROM LOCATION OF LOAD TO

NEAREST PANEL POINT (ON

OPP. CHORD OF JOIST)

( WHERE POINT LOADS OCCUR BETWEEN JOIST PANEL POINTS )

5'-0" VERIFY IN FIELD

S5.1

EXISTING STEEL

JOIST

C8x11.5 W/ (3) 1/2"∅

A325 THRU BOLTS

BETWEEN MIDDLE OF

JOIST TOP CHORD

(TYP. @ BOTH ENDS)

C7x9.8

ALUMINUM PLATE

FOR

PIPE STANDS PER

MANUFACTURER.

1/4" 5 1/2"TYP. @

BOTH

ENDS

CUT EXISTING DECK TO

ACCOMMODATE NEW C8x11.5 x

10" LONG @ EXISTING JOIST

1"

3/4" V.I.F. IF SMALLER

V .I .F

5"

EXISTING

STEEL

JOIST TO

REMAIN

NEW C8x11.5

NOTIFY ARCH.

C8x11.5x 10" LONG W/ (3) 1/2"

A325 THRU

BOLTS BETWEEN MIDDLE OF JOIST TOP

CHORD W/ 12" x 2" x 1/4" PLATE ON

BOTTOM SIDE OF TOP CHORD (TYP. @

BOTH ENDS)

TOP OF NEW

ROOF LEVEL

NEW C7x9.8

1/4" 5 1/2"TYP. @

BOTH

ENDS

C12x20.7 x 13" LONG W/ (4) 1/2"⌀

A325 THRU BOLTS BETWEEN

MIDDLE OF JOIST TOP CHORD

GALV. STEEL PIPE

GUARDRAIL SUPPORT

C9x13.4

CUT EXIST. DECK TO

ACCOMMODATE NEW

C12x20.7 @ EXIST. JOIST

ALL STEEL CHANNELS TO

BE PAINTED WITH A

PRIMER. SEE SPEC.

EXISTING L3" x 3" x 1/4" x CONT.

PROVIDE (2) NEW 3/4"⌀

EXPANSION ANCHORS IN

EXISTING ANGLE ON EITHER

SIDE OF THE HSS STEEL.

PROVIDE MIN. 4" EMBEDMENT

PROVIDE 7" x 3" x 1-1/2" SOLID STEEL SHIMS

BETWEEN TOP OF ANGLE AND NEW STEEL

FRAME. WELD SHIMS TO TOP OF ANGLE

(TYP. @ LOCATIONS OF STEEL FRAME

BEARING ON EDGE ANGLE)

1/4" 3"

TYP. @ JOISTS

EXISTING CONCRETE TIE-

BEAM TO REMAIN

DRAWING TITLE:

SHEET NO.

WDA PROJ. NO:

OWNER PROJ. NO:

SCALE: REFER TO SHEET

ISSUE/REVISION OF DRAWINGS:

ARCHITECT: AA0002541

ENGINEER: EB 0006884

PHASE:

CHECKED:

DRAWN:

T H

IS

D

O C

U M

E N

T C

O N

T A

IN

S

C O

P Y

R

IG

H T

E D

M A

T E

R

IA

L A

N D

T R

A D

E S

E C

R E

T I N

F O

R M

A T

IO

N

B E

L O

N G

IN

G

E X

C L U

S

IV

E L Y

T O

W

IL

L

IA

M S

O N

D A

C A

R A

S S

O C

IA

T

E S

IN

C

A N

Y U

N A

U T

H O

R

IZ

E D

U S

E

D

IS

C L O

S U

R E

D

IS

S

E M

IN

A

T

IO

N O

R D

U P

L

IC

A T

IO

N

O F

A N

Y O

F T

H E

I N

F O

R M

A T

IO

N

C O

N T

A

IN

E D

H E

R E

IN

M

A Y

R E

S U

L T

I N

L

IA

B

IL

IT

Y

U N

D E

R A

P P

L

IC

A B

W S

P R

O F

E S

S

IO

N A

L

T H

E O

D O

R E

J W

IL

L

IA

M S

O N

A R

P

E

/1

/2

:2 :3

P

M

STRUCTURAL

DETAILS

th

S t.

N S t.

P e te rs b u rg

F

L

S5.1

2412-02

PERMIT SET

N O

R T

H E

A S

T H

IG

H

S C

H O

O L R

O O

F R

E P

L A

C E

M E

N T

B

U

IL

D

IN

G S

Checker

Author

NO. DATE DESCRIPTION

1 04/16/25 PH4 100% CD PERMIT

1/4" = 1'-0"S5.1

1 TYPICAL RTU SUPPORT DETAIL

1/2" = 1'-0"S5.1

2 TYPICAL RTU SUPPORT SECTION

3/4" = 1'-0"S5.1

3 JOIST STIFFENER DETAIL

1" = 1'-0"S5.1

4 TYPICAL ROOF CURB SUPPORT

3" = 1'-0"S5.1

5 ENLARGED CURB SUPPORT CONNECTION

1" = 1'-0"S5.1

6 ROOF GUARDRAIL SUPPORT

3/4" = 1'-0"S5.1

7 TYPICAL RTU STEEL SUPPORT CONNECTION @ WALL

Sheets
S1.0 - WIND LOAD PLAN - BUILDING 3
S1.1 - WIND LOAD PLAN - BUILDING 6
S1.2 - WIND LOAD PLAN - BUILDING 19
S1.3 - WIND LOAD PLAN - BUILDING 28
S1.4 - PARTIAL ROOF FRAMING PLAN - BUILDING 19
S5.1 - STRUCTURAL DETAILS
2025-04-18T14:35:50-0400
Theodore J. Williamson
2025-04-18T14:35:53-0400
Theodore J. Williamson
2025-04-18T14:35:56-0400
Theodore J. Williamson
2025-04-18T14:36:00-0400
Theodore J. Williamson
2025-04-18T14:36:03-0400
Theodore J. Williamson
2025-04-18T14:36:06-0400
Theodore J. Williamson