24_FAC_003_AMS_Construction_Drawings.pdf
PDF 14 MB Posted
- Attached to
- ALBANY MIDDLE SCHOOL HVAC UPGRADES
- Solicitation number
- PE-64710-NONST-2024-000000006
- Issued by
- Dekalb County, Georgia
About this file
This document appears to be a set of construction drawings for a project titled "24_FAC_003_AMS" for the state and local government. The drawings provide detailed plans and specifications for the construction of this project. The project overview indicates that the government is seeking a contractor to perform construction services for this project. The drawings contain details on the site, floor plans, elevations, and other construction-related information. The response due date, site visit requirements, and other key dates are not explicitly provided in this document. However, this document is likely part of a larger solicitation package for this construction project.
The pricing terms, set-asides, incumbent contractor information, funding requirements, and other financial details are not contained within these construction drawings. Those details would likely be found in other attachments or documents related to this solicitation. This document focuses solely on providing the technical specifications and drawings for the proposed construction work.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D A
D E
BLECKLEY LAURENS
CHATHAM
EFFINGHAM
IRWIN
BERRIEN
LOWNDESGRADY
SE
MI
NO
LE
DECATUR
EARLY
MILLER
BAKER
THOMAS
BROOKS
COLQUITT
MITCHELL
COOK
TIFT
SCHLEY
TERRELL
DOUGHERTY
WEBSTER
RANDOLPH
QUITMAN
CLAY
CALHOUN
CHATTAHOOCHEE
STEWART
MARION
WILCOX
CRISP
WORTH
LEE
TURNER
DOOLY
MACON
SUMTER
HOUSTON
PULASKI
McINTOSH
PIERCE
CHARLTON
LA
NIE
R
CLINCH
ECHOLS
ATKINSON
WARE
CAMDEN
BRANTLEY
GLYNN
TOOMBS
APPLING
COFFEE
BEN HILL
TELFAIR
DAVIS
JEFF
WHEELER
DODGE
TREUTLEN
M
ON
TG
OM
ER
Y
LONG
WAYNE
LIBERTY
BULLOCH
EVANS
CANDLER
TATTNALL
BRYAN
DAWSON FRANKLIN
CLARKE
OCONEE
PUTNAM
BALDWIN
TWIGGS
HENRY
FA
YE
TT
E
PIKE
UPSON
SPALDING
M
ER
IW
ET
HER
HARRIS
MUSCOGEE
TALBOT
COWETA
HEARD
TROUP
PEACH
CRAWFORD
TAYLOR
BIBB
MONROE
LAMAR
BUTTS
JASPER
JONES
CHEROKEE
FULTON
PAULDING
HARALSON
CARROLL
DOUGLAS
BARTOWFLOYD
POLK
COBB
NEWTON
DEKALB
CL
AY
TO
N
ROCKD
AL
E
WALTON
MORGAN
GWINNETT
FORSYTH
JACKSON
HALL BANKS
BARROW
M cD
U F
FI
E
JEFFERSON
EMANUEL
WASHINGTON
WILKINSON
JOHNSON
HANCOCK
WARREN
GLASCOCK
JENKINS
SCREVEN
RICHMOND
BURKE
COLUMBIA
OGLETHORPE
WILKES
TALIAFERROGREENE
LINCOLN
ELBERT
HART
MADISON
RABUN
STEPHENS
FANNIN
PICKENS
GILMER
WHITF
IELD
GORDON
C H
AT
TO
O G
A
WALKER M
U
R R
AY
CATOOSA
UNION
LUMPKIN
WHITE
HABERSHAM
TOWNS
BACON
DOUGHERTY
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
T100
TITLE SHEET
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
T100 TITLE SHEET
C100 SITE PLAN
A100 ARCHITECTURAL CEILING PLAN - OVERALL
MD100 MECHANICAL DEMOLITION FLOOR PLAN - OVERALL
MD101 MECHANICAL DEMOLITION FLOOR PLAN - SECTOR A
MD102 MECHANICAL DEMOLITION FLOOR PLAN - SECTOR B
MD103 MECHANICAL DEMOLITION FLOOR PLAN - SECTOR C & D
MD104 MECHANICAL DEMOLITION FLOOR PLAN - SECTOR E
M100 MECHANICAL NEW WORK FLOOR PLAN - OVERALL
M101 MECHANICAL NEW WORK FLOOR PLAN - SECTOR A
M102 MECHANICAL NEW WORK FLOOR PLAN - SECTOR B
M103 MECHANICAL NEW WORK FLOOR PLAN - SECTOR C & D
M104 MECHANICAL NEW WORK FLOOR PLAN - SECTOR E
M201 MECHANICAL NEW WORK PIPING PLAN - SECTOR A
M202 MECHANICAL NEW WORK PIPING PLAN - SECTOR B
M401 MECHANICAL EQUIPMENT PIPING DIAGRAMS
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M503 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
M602 MECHANICAL SCHEDULES, LEGEND & GENERAL NOTES
ED101 ELECTRICAL OVERALL DEMO PLAN
E100 ELECTRICAL SITE PLAN
E101 ELECTRICAL NEW WORK PLAN - OVERALL
E801 ELECTRICAL SCHEDULES AND LEGEND
INDEX OF DRAWINGS GEORGIA/COUNTY MAP PROJECT LOCATION
ALBANY MIDDLE SCHOOL - HVAC
UPGRADES
1700 CORDELL AVE. ALBANY, GA 31705
GA DOE ID#: 0101
No. Description Date
CONTRACTOR SHALL COORDINATE WITH
OWNER FOR TEMPORARY CONNECTION
OF 2" DOMESTIC COLD WATER PIPING TO
EXISTING IN THIS APPROXIMATE
LOCATION.
TEMPORARY PORTABLE
CLASSROOMS - 8 CLASSROOM
MODULE
GENERAL NOTE: LOCATIONS OF CLASSROOM TRAILERS IS
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF
EXISTING STORM DRAINS, FENCING, SIDEWALKS, PLAYGROUNDS,
DRIVES, ETC. AND CAREFULLY COORDINATE PLACEMENT OF
CLASSROOMS TO AVOID CONFLICT AND MAINTAIN REQUIRED
CLEARANCES.
E X
IS
T
IN
G
W A
T E
R L
IN
E
EXISTING 8" WATER LINE
ROUTE NEW 2" CW PIPE
THROUGH EXISTING 6" SLEEVE
UNDER DRIVEWAY
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
C100
SITE PLAN
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
1" = 50'-0"
SITE PLAN
No. Description Date
CORDELL AVE
BASEBALL FIELD
BASEBALL FIELD
FOOTBALL/SOCCER FIELD
W O
O D
L
IN
E
W O
O D
L
IN
E
WOODLINE
WOODLINE
W
OODLINE
W O
O D
L
IN
E
PARKING LOT
PARKING LOT
PARKING
LO
T
EXISTING CLEAN OUT
NEW 4" SANITARY LINE ROUTED
FROM EXISTING CLEAN OUT TO
PORTABLE CLASSROOM.
DEMO HATCH LEGEND
DEMO EXISTING CEILING TILE
DEMO EXISTING CEILING TILE & GRID
(NO HATCH) EXISTING CEILING TILE AND
GRID TO REMAIN
GENERAL NOTE: REMOVAL OF CEILINGS REQUIRED
FOR REMOVAL OF EXISTING EXHAUST FANS
LOCATED ABOVE RESTROOMS NOT SHOWN. SEE
MECHANICAL DRAWINGS FOR LOCATIONS OF
ITEMS LOCATED ABOVE CEILINGS THAT MAY
REQUIRE REMOVAL OF CEILING TILES.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
A100
ARCHITECTURAL CEILING
PLAN - OVERALL
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
1" = 20'-0"
ARCHITECTURAL CEILING PLAN - OVERALL
MD101
MD102
MD103
MD103
MD104
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
MD100
MECHANICAL DEMOLITION
FLOOR PLAN - OVERALL
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
No. Description Date
1" = 20'-0"
MECHANICAL DEMOLITION PLAN - OVERALL
CHORUS
EXIT
OFFICE
174 PRACTICE
STORAGE
INSTR. REPAIR
MAT'L. PROC.
BAND
INST. STO.
TECH LAB
CONTROL ROOM
VIDEO
LECTURE
OFFICE
STO.
STO.
TOILET
JAN.
MAIN LOBBY
CORRIDOR
CORRIDOR
RECEPTION
STUDENT WAITING
PARENT WAITING
CAREER CENTER
STO.
STO.
ELECT.
Room
COUNS.
COUNS.
STORAGE
ISS
SRO
Room
MEN
WOMEN
STORAGE
TEST
VAULT
TOILET
CLINIC
WORK ROOM
BOOK KEEPER
213 STORAGE
ASST. PRINCIPAL
TOILET
216 PRINCIPAL
HALL
C
D
E
B
A
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
MD101
MECHANICAL DEMOLITION
FLOOR PLAN - SECTOR A
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
1/8" = 1'-0"
DEMOLITION FLOOR PLAN - SECTOR A
NOTES: (THIS SHEET ONLY)
1/4" = 1'-0"
DEMOLITION FLOOR PLAN - MECHANICAL MEZZANINE
1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE
EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW WALL HUNG HEAT
PUMP SAME LOCATION.
2 . EXISTING CEILING HEATER TO BE DEMOED. DEMO EXISTIN CIRCUIT BACK TO SOURCE.
3 . EXISTING ROOF MOUNTED EXHAUST FAN TO BE REMOVED AND REPLACED.
4 . EXISTING FAN COIL UNIT TO BE REPLACED. REMOVE EXISTING REFIGERANT AND
CONDENSATE LINES. EXISTING RETURN AIR PLENUM TO REMAIN FOR REUSE. REMOVE
SUPPLY DUCT AS NEEDED TO CONNECT NEW FAN COIL UNIT.
5 . EXISTING INLINE EXHASUT FAN TO BE REMOVED. EXISTING DUCTWORK TO REMAIN FOR
REUSE.
6 . EXISTING AIR HANDLER AND ASSPCOATED HEAT PUMP ARE TO REMAIN. CONRTACTOR
SHALL SERVICE THIS SYSTEM DURING CONSTRUCTION.
No. Description Date
GENERAL NOTE: ALL EXISTING SUPPLY AND RETURN GRILLES AND ASSOCIATED FLEX
DUCTS ARE TO BE DEMOLISHED AND REPLACED WITH NEW UNDER THIS CONTRACTOR
UNLESS NOTED OTHERWISE. SEE DRAWINGS FOR EXCEPTIONS.
CORRIDOR
CORRIDOR
VESTIBULE
VESTIBULE
GYMNASIUM
TOILET
ELECT.
MEDIA PROD.
WORK ROOM
OFFICE
MEDIA
COMP.
AV STORAGE
DISPLAY
BOYS
MEZZ.
GIRLS
CONFERENCE
STORAGE
HEALTH/PLATFORM
CAFETORIUM
DISH WASH
KITCHEN
DRY STORAGE
OFFICE
TOILET
LAUNDRY
COOLER
FREEZER
ELECT.
MECH.
GIRLS LOCKER
BOYS LOCKER
Room
STORAGE
COACH
COACH
TRAINING
FOOTBALL
STORAGE
99 9
EXISTING GYM SUPPLY AND RETURN GRILLES TO REMAIN.
C
D
E
B
A
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
MD102
MECHANICAL DEMOLITION
FLOOR PLAN - SECTOR B
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
1/8" = 1'-0"
DEMOLITION FLOOR PLAN - SECTOR B
. EXISTING KITCHEN EXHAUST FAND SUPPLY FAN TO BE REPLACED. EXISTING EQUIPMENT PLATFORM AND ROOF
CURB TO REMAIN FOR REUSE.
2 . REMOVE EXISTING EXHAUST FAN AND CAP THE EXISTING CURB. SEE CURB CAP DETAIL.
3 . REMOVE EXISTING GRAVITY INTAKE HOOD AND CAP THE EXISTING CURB. SEE CURB CAP DETAIL.
4 . EXISTING EXHAUST FAN TO REMAIN. DO NOT REMOVE.
5 . EXISTING DDC PANEL TO BE REMOVED. SEE NEW WORK DRAWINGS FOR NEW DDC PANEL
6 . EXISTING CEILING HEATER TO BE DEMOED. DEMO EXISTIN CIRCUIT BACK TO SOURCE.
7 . EXISTING ROOF MOUNTED EXHAUST FAN TO BE REMOVED AND REPLACED.
8 . EXISTING THROUGH WALL AIR CONDITIONER TO BE REPLACED.
9 . EXISTING HEAT PUMP TO BE DEMOLISHED.
10 . EXISTING HEAT PUMPS TO REMAIN.
11 . EXISTING CONCRETE EQUIPMENT PADS IN MECHANICAL EQUIPMENT YARD TO REMAIN FOR REUSE.
12 . REMOVED EXISTING ROOFTOP AIR CONDITIONER. EXISTING EQUIPMENT SUPPORT RAILS TO REMAIN FOR REUSE.
REMOVE ASSOCIATED CONDENSATE DRAIN PIPE. REMOVE EXISTING GAS PIPING AS NEEDED TO MAKE
CONNECTION TO NEW UNIT.
NOTES: (THIS SHEET ONLY)
No. Description Date
GENERAL NOTE: ALL EXISTING SUPPLY AND RETURN GRILLES AND ASSOCIATED FLEX
B
1 1 1 1 1
1 1 1 1 1 1 1
C
CORRIDOR
CORRIDOR
11111
1 1 1 1 1 1 1
2 2
C
D
E
B
A
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
MD103
MECHANICAL DEMOLITION
FLOOR PLAN - SECTOR C & D
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
1/8" = 1'-0"
DEMOLITION FLOOR PLAN - SECTOR C
1/8" = 1'-0"
DEMOLITION FLOOR PLAN - SECTOR D
NOTES: (THIS SHEET ONLY)
No. Description Date
GENERAL NOTE: ALL EXISTING SUPPLY AND RETURN GRILLES AND
ASSOCIATED FLEX DUCTS ARE TO BE DEMOLISHED AND REPLACED
WITH NEW UNDER THIS CONTRACTOR UNLESS NOTED OTHERWISE.
SEE DRAWINGS FOR EXCEPTIONS.
1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED
DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT
FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME
LOCATION.
2 . EXISTING CEILING HEATER TO BE DEMOED. DEMO EXISTIN
CIRCUIT BACK TO SOURCE.
3 . EXISTING INLINE EXHAUST FAN TO BE REMOVED. EXISTING
DUCTWORK TO REMAIN FOR REUSE.
4 . EXISTING THROUGH WALL AIR CONDITIONER TO BE REPLACED.
5 . EXISTING ROOF MOUNTED EXHAUST FAN TO BE REMOVED AND
REPLACED.
A
CORRIDOR
CORRIDOR
1111111
1 1 1 1 1 1
C
D
E
B
A
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
MD104
MECHANICAL DEMOLITION
FLOOR PLAN - SECTOR E
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
1/8" = 1'-0"
DEMOLITION FLOOR PLAN - SECTOR E
NOTES: (THIS SHEET ONLY)
No. Description Date
GENERAL NOTE: ALL EXISTING SUPPLY AND RETURN GRILLES AND ASSOCIATED FLEX
DUCTS ARE TO BE DEMOLISHED AND REPLACED WITH NEW UNDER THIS CONTRACTOR
UNLESS NOTED OTHERWISE. SEE DRAWINGS FOR EXCEPTIONS.
1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED
DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT
FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME
LOCATION.
2 . EXISTING CEILING HEATER TO BE DEMOED. DEMO EXISTIN
CIRCUIT BACK TO SOURCE.
3 . EXISTING INLINE EXHAUST FAN TO BE REMOVED. EXISTING
DUCTWORK TO REMAIN FOR REUSE.
4 . EXISTING ROOF MOUNTED EXHAUST FAN TO BE REMOVED AND
REPLACED.
M101
M102
M103
M103
M104
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M100
MECHANICAL NEW WORK
FLOOR PLAN - OVERALL
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
No. Description Date
1" = 20'-0"
MECHANICAL NEW WORK PLAN - OVERALL
C
D
E
B
A
CH-A1 CH-A2
CH-A3
CH-A4
WHHP-AD1
EX-GH-AD1
BOOK KEEPER
213 STORAGE
ASST. PRINCIPAL
PRINCIPAL
Room
SRO
203STORAGE
TEST
VAULT
CLINIC
WORK ROOM
CAREER CENTER
283.59 SF
STO.
COUNS.
COUNS.
STORAGE
STO.
STUDENT WAITING
ISS
TECH LAB
MAIN LOBBY
EXIT
OFFICE
PRACTICE
STORAGE
INSTR. REPAIR
MAT'L. PROC.
BAND
INST. STO.
CONTROL ROOM
VIDEO
LECTURE
OFFICE
183 STO.
STO.
TOILET
JAN.
CORRIDOR
RECEPTION
PARENT WAITING
ELECT.
Room
MEN
WOMEN
TOILET
TOILET
HALL
IU-1.1
IU-1.8 IU-1.7
IU-1.2
IU-1.6
IU-1.3 IU-1.4
IU-1.5
IU-1.12
IU-1.11
IU-1.10
IU-1.9
TT TT
TT
TT TT
TT
TT TT TT
TT
TT
TT
A1
A1
B1
20 B1
B1
B1
B1
B1
A1
B1
A3
A3
A3
A3
A3
A2
A2
A1
A2
A3
280A3
A3
A3
A2
A3
A3
A3
A3
A3
A3
A3
A3
A1
B1
MDC-1
WHHP-C3
A3
A3
A3
295A3
F-A2
F-A1
F-AD4
F-AD2
F-AD3
F-AD1
F-AD5
A3
A3
A3
A3
IHP-C1
D2
D2
D2
C2
A1
A1
A1
B1
F1
D6
IU-1.13
48"x12"
48"x12"
C2
C2
SS
C2
C2
C2
C2C2
C2
C2
C2
C2
C2
12"ø
10"ø
6"ø
6"ø
6"ø
6"ø
6"ø
6"ø
6"ø
6"ø
6"ø
6"ø
6"ø
8"ø 6"ø6"ø10"ø
C2
A1
IU
-1
.1
C1
10"ø
6"ø
6"ø 6"ø
8"ø
6"ø
6"ø
6"ø 8"ø
IU-1.14
IU-1.15
6"ø
C2
C2
C2
C2
C2
C2
D7
54' - 6"
IHP-B2
IHP-E1
IHP-C1 IHP-A1
IHP-A2
IHP-B1
F-B2
OAU-1
EXISTING GYMNASIUM EXHAUST FANS
(NOT SHOWN ON DRAWINGS) SHALL
REMAIN IN PLACE.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M101
MECHANICAL NEW WORK
FLOOR PLAN - SECTOR A
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
1 . NEW WALL HUNG HEAT PUMP MOUNTED IN SAME LOCATION AS REMOVED WHHP. PROVIDE TRANSITIONS AS REQUIRED TO
CONNECT NEW WHHP TO EXISTING DUCTWORK IN CHASE.
2 . VRF CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD STRUCTURE WITH
SUPPLEMENTAL 2"X2"X1/4" ANGLE IRON.
3 . MAIN/SUB VRF BRANCH CONTROLLER. BRANCH CONTROLLER SHALL BE MOUNTED ABOVE CEILING. SUSPEND FROM DROP RODS (MIN 3/8") AND CONNECTED TO OVERHEAD STRUCTURE WITH 2"X2"X1/4" ANGLE IRON. PROVIDE DRAIN PAN BELOW
MBC/SBC.SEE VRF DRAIN PAN DETAIL.
4 . NEW CENTRIFUGAL ROOF MOUNTED EXHAUST FAN. PROVIDE ROOF CURB ADAPTER AS NEEDED.
5 . NEW CEILING HEATER INSTALLED IN PLACE OF EXISTING.
6 . CONCEALED DUCT VRF FAN COIL UNIT. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD STRUCTURE
WITH SUPPLEMENTAL 2"X2"X1/4" ANGLE IRON.
7 . NEW FAN COIL UNIT MOUNTED ON EXISTING RETURN AIR PLENUM STAND. CONNECT EXISTING DUCTWORK TO NEW FAN COIL UNIT. PROVIDE DUCT FITTINGS AND TRANSITIONS AS REQUIRED. EXISTING OA DUCT CONNECTED TO RETURN DUCT TO REMAIN IN PLACE FOR REUSE. CONTRACTOR SHALL VERIFY OA DUCT DAMPER IS FUNCTIONAL AND BALANCE TO THE
SCHEDULED OUTSIDE AIR CFM.
8 . NEW INLINE EXHAUST FAN. PROVIDE DUCT TRANSITIONS AND FITTINGS TO CONNECT TO EXISTING DUCTWORK.
9 . EXISTING AIR HANDLER TO REMAIN. MECHANICAL CONTRACTOR SHALL SERVICE THE AIR HANDLER DURING
CONSTRUCTIORN.
10 . NEW 100% OUTSIDE AIR UNIT MOUNTED ON EXISTING CONCRETE EQUIPMENT PAD. ROUTE NEW DUCTOWRK AS SHOWN TO ADMIN AREA. CONNECT OA INTAKE TO EXISTING LOUVER DUCTWORK IN MECHANICAL MEZZANINE.
1/8" = 1'-0"
NEW WORK FLOOR PLAN - SECTOR A
NOTES: (THIS SHEET ONLY)
1/4" = 1'-0"
NEW WORK FLOOR PLAN - MECHANICAL MEZZANINE
No. Description Date
GENERAL NOTE: ALL EXISTING SUPPLY AND RETURN GRILLES AND ASSOCIATED FLEX
CH-B1
CH-B2
GYMNASIUM
CAFETORIUM
HEALTH/PLATFORM
MEDIA
VESTIBULE
VESTIBULE
STORAGE
TOILET
ELECT.
DATA
MEDIA PROD.
WORK ROOM
OFFICE
COMP.
AV STORAGE
DISPLAY
BOYS
MEZZ.
GIRLS
CONFERENCE
STORAGE
DISH WASH
KITCHEN
DRY STORAGE
OFFICE
TOILET
LAUNDRY
COOLER
FREEZER
ELECT.
MECH.
GIRLS LOCKER
BOYS LOCKER
857.55 SF
Room
STORAGE
COACH
COACH
TRAINING
FOOTBALL
STORAGE
A3
300A3
A3
A3
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A2
A2
A2
225A2
OHP-A2
OHP-A1
OHP-E1
OHP-B2
OHP-B1
OHP-C1
HRU-1
F-K3
F-B4
F-G2 F-G1
F-G4
TW-K1
OAU-CU-1
F-G3
C2
C2
F-K1
F-K6 C2
C2
C2
C2
E-KH-1
F-B1
TW-B1
TT
A2
A2
A2
A2
A2
A2
A2
A2
150C2
C2
TT
12"ø
8"ø 8"ø
8"ø 10"ø18"x20"
"x
16"x20"
"ø
8"ø 8"ø 8"ø
IHP-G1
C1
AVDMVD
KEF-1 KSF-1
A3
A3
A3
A2
A2
A3
A3
A3
A3
335A3
A3
A3
A3
A3
A3
A3
A3
A3
C2
C2 A3
A2
A2
D1
C2
C2
C2
C2
D4
C2
C2
C2 C2
C2
C2
C2
C2
D5
DOU-5
DOU-4
DCFU-4
DCFU-5
OHP-G1
TT
RTU-G2
RTU-G1
800 -
WH-G1
C2
C2
C2 C2
1 1
6 6
C2
C2
500C2
C2 ø10"
C2
C2
KILN
TT
TT
C
D
E
B
A
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M102
MECHANICAL NEW WORK
FLOOR PLAN - SECTOR B
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
1/8" = 1'-0"
NEW WORK FLOOR PLAN - SECTOR B
1 . CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO
OVERHEAD STRUCTURE WITH SUPPLEMENTAL 2"X2"X1/4" ANGLE IRON.
2 . NEW KITCHEN HOOD SUPPLY FAN MOUNTED ON ROOF CURB ADAPTER
3 . NEW KITCHEN HOOD EXHAUST FAN MOUNTED ON ROOF CURB ADAPTER
4 . NEW DOOR AIR CURTAIN MOUNTED IN PLACE OF EXISTING.
5 . NEW DDC PANEL IN DATA ROOM.
6 . <varies>
7 . EXISTING HEAT PUMP TO REMAIN. CONTRACTOR SHALL PERFORM ROUTINE
SERVICE ON THIS UNIT DURING CONSTRUCTION.
8 . NEW HEAT PUMP MOUNTED ON EXISTING CONCRETE EQUIPMENT PAD. VERIFY
EXISTING CONCRETE PAD SIZE.
9 . NEW 100% OUTSIDE AIR CONDENSING UNIT MOUNTED ON EXISITNG CONCRETE
EQUIPMENT PAD.
10 . NEW VRF HEAT RECOVERY UNIT MOUNTED ON EXISTING CONCRETE EQUIPMENT
PAD. VERIFY EXISTING CONCRETE EQUIPMENT PAD SIZE.
NOTES: (THIS SHEET ONLY)
No. Description Date
GENERAL NOTE: ALL EXISTING SUPPLY AND RETURN
GRILLES AND ASSOCIATED FLEX DUCTS ARE TO BE
DEMOLISHED AND REPLACED WITH NEW UNDER THIS
CONTRACTOR UNLESS NOTED OTHERWISE. SEE
DRAWINGS FOR EXCEPTIONS.
11 . NEW PACKAGED TERMINALAIR CONDITONER INSTALL IN EXISTING OPENING IN
WALL.
12 . EXISTING KITCHEN HOOD.
13 . NEW VERTICAL FAN COIL UNIT MOUNTED ON NEW RETURN AIR PLENUM STAND.
CONNECT NEW OUTISIDE AIR DUCT TO EXISTING ROOF INTAKE.
14 . NEW DUCTLESS HEAT PUMPS MOUNTED ON NEW CONCRETE EQUIPMENT PAD.
SEE CONCRETE EQUIPMENT PAD DETAIL. VERIFY LOCATION IN MECHANICAL
WITH OTHER EQUIPMENT.
15 . NEW WALL HEATER MOUNTED IN PLACE OF EXISTING.
16 . EXISTING GRAVITY VENTILATOR TO REMAIN.
17 . EXISTING DISHWASHER EXHAUST FAN TO REMAIN.
18 . NEW CEILING HEATER INSTALLED IN PLACE OF OLD.
19 . NEW EXHAUST GRILLE TO CONNECT TO EXISTING EXHAUST DUCT FROM
MECHANICAL MEZZANINE.
20 . EXISTING KILN EXHAUST FAN TO REMAIN.
21 . CONNECT NEW RETURN DUCTWORK TO EXISITNG DUCTWORK / PENETRATION.
PROVIDE FITTINGS AND TRANSITIONS NEEDED TO MAKE THE CONNECTION.
22 . ROUTE NEW SUPPLY DUCTWORK ON ROOF TO CONNECT TO EXISTING
DUCTWORK. PROVIDE DUCT SUPPORTS ON ROOF. PROVIDE FITTINGS AND
TRANSITITONS NEEDED FOR CONNECTION.
23 . PROVIDE NEW DDC THERMOSTAT FOR CONTROL OF PTHP. THERMOSTAT
MOUNTED ON WALL WITH B.E. AT 4'-6" A.F.F. PROVIDE SURFACE MOUNTED
RACEWAY AS REQUIRED TO CONCEAL ALL CONTROL WIRING BELOW CEILING
ROUTED FROM PTHP TO THERMOSTAT. COORDINATE NEW THERMOSTAT WITH
EXISTING LIGHT SWITCHES, WALL BOARDS, ETC.
WHHP-D7
WHHP-D9
WHHP-D8WHHP-D11 WHHP-D6 WHHP-D5 WHHP-D4
WHHP-D1WHHP-D12 WHHP-D10 WHHP-D2 WHHP-D3
F-D5
F-D4F-D3
WHHP-E12
CH-D1
CH-D2 CH-D3
WHHP-C14
F-D6
F-D1
TT
WHHP-D12
A3
A3
A3
A3
W H
H P
-E
CORRIDOR
CLASSROOM
CLASSROOM
WORK ROOM
STORAGE
CLASSROOM
CLASSROOM
LAUNDRY
HOME EC.
OFFICE
CLASSROOM
CLASSROOM
JAN.
BOYS
GIRLS
CLASSROOM
CLASSROOM
CLASSROOM
LAUNDRY
ELECT.
MEN
DISPLAY
WOMEN
TEACHER'S LOUNGE
DATA
ELECT.
CORRIDOR
TEAM PLANNING
1 1 1 1 1
1 1 1 1 1 1 1
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
TT
WHHP-D1
TT
WHHP-D2
TT
WHHP-D10
TT
WHHP-D3
A3
A3
A3
A3
TT
WHHP-D9
TT
WHHP-D11
TT
WHHP-D7
TT
WHHP-D8
TT
WHHP-D6
TT
WHHP-D5
TT
WHHP-D4
A2
A2
A3
A3
DFCU-D1.1
DOU-D1
DFCU-D1.2
F-D2
C2
C2
C1
C2
900C2
C2
C2
A2
F-C2
C2
C2
C2
F-C7 F-C3
C2
C2C2
TT
WHHP-C14
D3 D3 D3 D3 D3 D3
D3 D3 D3 D3 D3 D3
D
C2
C2
C2
C2
C2
F-E1
A2
A2
F-E2
F-E7 C2
C2
C2
C2
C2
TT
WHHP-C5
WHHP-C6 WHHP-C7
WHHP-C11 WHHP-C2 WHHP-C4 WHHP-C3
WHHP-C13
WHHP-C2
F-C6
F-C5 F-C4
WHHP-C8 WHHP-C9 WHHP-C10WHHP-C1
CH-C1
CH-C2
CH-C3
WHHP-C14
F-D6
F-D1
A3
A3
A3
A3
Room
LAUNDRY
ELECT.
MEN
DISPLAY
WOMEN
TEACHER'S LOUNGE
DATA
126ELECT.
CORRIDOR
TEAM PLANNING
RESOURCE
CLASSROOM
CLASSROOM
Room
BOYS
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
STORAGE
WORK ROOM
CLASSROOM
CLASSROOM
RESOURCE
CLASSROOM
COMPUTER LAB
OFFICE
PRACTICE
A2
A2
A3
A3
11111
1 1 1 1 1 1 1
TT
WHHP-C1
TT
WHHP-C8
TT
WHHP-C6
TT
WHHP-C10
TT
WHHP-C9
TT
WHHP-C7
TT
WHHP-C5
TT
WHHP-C11
TT
WHHP-C2
TT
WHHP-C2
TT
WHHP-C13
TT
WHHP-C4
TT
WHHP-C3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
DFCU-C1.1
DOU-C1
DFCU-C1.2
F-C1
C2
C2
C2
C2
C2
SS SS
C1
C2
B1
B1
A3
A2
F-C2
C2
C2
C2
F-C7
F-C3
C2
C2
TT
W H
H P
-C
D3 D3 D3 D3 D3 D3
D3D3D3D3 D3
D3
C2
C2
C2
TT
C
D
C
D
E
B
A
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M103
MECHANICAL NEW WORK
FLOOR PLAN - SECTOR C & D
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1/8" = 1'-0"
NEW WORK FLOOR PLAN - SECTOR C
1/8" = 1'-0"
NEW WORK FLOOR PLAN - SECTOR D
1 . NEW WALL HUNG HEAT PUMP MOUNTED IN SAME LOCATION AS
REMOVED WHHP. PROVIDE TRANSITIONS AS REQUIRED TO
CONNECT NEW WHHP TO EXISTING DUCTWORK IN CHASE.
2 . INSTALL NEW CEILING HEATER IN LOCATION OF EXISTING HEATER.
3 . NEW CENTRIFUGAL ROOF MOUNTED EXHAUST FAN. PROVIDE
ROOF CURB ADAPTER AS NEEDED.
4 . NEW PACKAGED TERMINALAIR CONDITONER INSTALL IN EXISTING
OPENING IN WALL.
5 . NEW INLINE EXHAUST FAN. PROVIDE DUCT TRANSITIONS AND
FITTINGS TO CONNECT TO EXISTING DUCTWORK.
6 . CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8")
CONNECTED TO OVERHEAD STRUCTURE WITH SUPPLEMENTAL
2"X2"X1/4" ANGLE IRON.
7 . PROVIDE NEW DDC THERMOSTAT FOR CONTROL OF PTHP.
THERMOSTAT MOUNTED ON WALL WITH B.E. AT 4'-6" A.F.F.
PROVIDE SURFACE MOUNTED RACEWAY AS REQUIRED TO
CONCEAL ALL CONTROL WIRING BELOW CEILING ROUTED FROM
PTHP TO THERMOSTAT. COORDINATE NEW THERMOSTAT WITH
EXISTING LIGHT SWITCHES, WALL BOARDS, ETC.
8 . NEW DUCTLESS HEAT PUMP MOUNTED ON EQUIPTMENT
PLATFORM ON ROOF. ROUT REFRIGERANT PIPING THROUGH PIPE
BOX AND TO DUCTLESS UNITS IN THE CORRIDORS. ROUTE
CONDENSATE PIPING FROM THE CEILING CASSETTES BACK
THROUGH THE PIPE BOX AND DISCHARGE ON THE ROOF.
No. Description Date
GENERAL NOTE: ALL EXISTING SUPPLY AND RETURN
GRILLES AND ASSOCIATED FLEX DUCTS ARE TO BE
DEMOLISHED AND REPLACED WITH NEW UNDER THIS
CONTRACTOR UNLESS NOTED OTHERWISE. SEE
DRAWINGS FOR EXCEPTIONS.
F-E10
F-E9
F-E8
WHHP-E12WHHP-E1WHHP-E2WHHP-E3WHHP-E11WHHP-E10WHHP-E4WHHP-E13
WHHP-E9WHHP-E8WHHP-E7WHHP-E6WHHP-E5WHHP-E14
CH-E1
CH-E2 CH-E3
A
TT
WHHP-E12
CORRIDOR
CORRIDOR
LAUNDRY
HOME EC.
OFFICE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
SPEC. ED.
SPEC. ED.
150CLASSROOM
CLASSROOM
WORK ROOM
STORAGE
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
BOYS
JAN.
GIRLS
161 CLASSROOM
CLASSROOM
BOOK ROOM
TEAM PLANNING
STORAGE
DARK ROOM
ART
ART
A3
A3
A3
A3
11111111
1 1 1 1 1 1
TT
WHHP-E3
TT
WHHP-E10
TT
WHHP-E4
TT
WHHP-E13
TT
WHHP-E11
TT
WHHP-E1
TT
WHHP-E2
TT
WHHP-E6
TT
WHHP-E5
TT
WHHP-E14
TT
WHHP-E7
TT
WHHP-E9
TT
WHHP-E8
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
DFCU-E1.1
DOU-E1
DFCU-E1.2
A3
A3
A3
A3
A3
A3
A3
F-E4
F -E
B1
F-E3
C2
C2
C1
C2
C2
C2
D3D3D3D3D3D3D3D3
D3 D3 D3 D3 D3 D3
C2
C2C2
C2
C2
F-E1 A2
A2
120F-E2
F-E7
C2
C2
C2
F-E11
TT
KILN
TT
C
D
E
B
A
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M104
MECHANICAL NEW WORK
FLOOR PLAN - SECTOR E
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1/8" = 1'-0"
NEW WORK FLOOR PLAN - SECTOR E
1 . NEW WALL HUNG HEAT PUMP MOUNTED IN SAME LOCATION AS
REMOVED WHHP. PROVIDE TRANSITIONS AS REQUIRED TO
CONNECT NEW WHHP TO EXISTING DUCTWORK IN CHASE.
2 . CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8")
CONNECTED TO OVERHEAD STRUCTURE WITH SUPPLEMENTAL
2"X2"X1/4" ANGLE IRON.
3 . NEW INLINE EXHAUST FAN. PROVIDE DUCT TRANSITIONS AND
FITTINGS TO CONNECT TO EXISTING DUCTWORK.
4 . NEW CEILING HEATER INSTALLED IN PLACE OF OLD.
No. Description Date
GENERAL NOTE: ALL EXISTING SUPPLY AND RETURN GRILLES AND
ASSOCIATED FLEX DUCTS ARE TO BE DEMOLISHED AND REPLACED
WITH NEW UNDER THIS CONTRACTOR UNLESS NOTED OTHERWISE.
SEE DRAWINGS FOR EXCEPTIONS.
CH-A1 CH-A2
CH-A3
CH-A4
BOOK KEEPER
213 STORAGE
ASST. PRINCIPAL
PRINCIPAL
Room
SRO
203STORAGE
TEST
VAULT
CLINIC
WORK ROOM
CAREER CENTER
STO.
195 COUNS.
COUNS.
STORAGE
STO.
STUDENT WAITING
ISS
TECH LAB
MAIN LOBBY
EXIT
OFFICE
PRACTICE
STORAGE
INSTR. REPAIR
MAT'L. PROC.
BAND
INST. STO.
CONTROL ROOM
VIDEO
LECTURE
OFFICE
STO.
STO.
TOILET
JAN.
CORRIDOR
CORRIDOR
RECEPTION
PARENT WAITING
ELECT.
Room
MEN
WOMEN
TOILET
TOILET
HALL
IU-1.1
IU-1.8 IU-1.7
IU-1.2
IU-1.6
IU-1.3
IU-1.4
IU-1.5
IU-1.12
IU-1.11
IU-1.10IU-1.9
TT TT
TT
TT TT
TT
TT TT TT
TT
TT
MDC-1
F-A2
F-A1
F-AD4
F-AD2
F-AD3
F-AD1
F-AD5
IHP-C1
IU-1.13
IU
-1
.1
IU-1.14
IU-1.15
IHP-B2
IHP-E1 IHP-C1 IHP-A1 IHP-A2
IHP-B1
F-B2
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M201
MECHANICAL NEW WORK
PIPING PLAN - SECTOR A
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
No. Description Date
1/8" = 1'-0"
NEW WORK PIPING PLAN - SECTOR A
1 . MAIN/SUB VRF BRANCH CONTROLLER. BRANCH CONTROLLER SHALL BE
MOUNTED ABOVE CEILING. SUSPEND FROM DROP RODS (MIN 3/8") AND
CONNECTED TO OVERHEAD STRUCTURE WITH 2"X2"X1/4" ANGLE IRON. PROVIDE
DRAIN PAN BELOW MBC/SBC.SEE VRF DRAIN PAN DETAIL.
2 . VRF CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED
TO OVERHEAD STRUCTURE WITH SUPPLEMENTAL 2"X2"X1/4" ANGLE IRON.
3 . CONCEALED DUCTED VRF UNIT SUSPENDED FROM STRUCTURE ABOVE CEILING.
4 . NEW FAN COIL UNIT MOUNTED ON EXISTING RETURN AIR PLENUM STAND. ROUTE
NEW REFRIGERANT LINE SET TO AIR HANDLER. ROUTE CONDENSATE AS SHOWN
TO EXISTING FLOOR DRAIN.
5 . EXISTING AIR HANDLER TO REMAIN. MECHANICAL CONTRACTOR SHALL SERVICE
THE AIR HANDLER DURING CONSTRUCTIORN.
6 . NEW 100% OUTSIDE AIR UNIT MOUNTED ON EXISTING CONCRETE EQUIPMENT
PAD. ROUTE NEW REFRIGERANT LINE SET TO AIR HANDLER. ROUTE
CONDENSATE AS SHOWN TO EXISTING FLOOR DRAIN.
7 . NEW AIR HANDLER. ROUTE NEW REFRIGERANT LINE SET TO AIR HANDLER.
ROUTE CONDENSATE AS SHOWN TO EXISTING FLOOR DRAIN.
NOTES: (THIS SHEET ONLY)
1/4" = 1'-0"
NEW WORK PIPING PLAN - MECHANICAL MEZZANINE
CH-B1
CH-B2
GYMNASIUM
CAFETORIUM
HEALTH/PLATFORM
MEDIA
CORRIDOR
VESTIBULE
VESTIBULE
STORAGE
TOILET
ELECT.
DATA
MEDIA PROD.
WORK ROOM
OFFICE
COMP.
AV STORAGE
DISPLAY
BOYS
MEZZ.
GIRLS
CONFERENCE
STORAGE
DISH WASH
241 KITCHEN
DRY STORAGE
OFFICE
TOILET
LAUNDRY
COOLER
FREEZER
ELECT.
MECH.
GIRLS LOCKER
BOYS LOCKER
857.55 SF
Room
STORAGE
COACH
COACH
TRAINING
FOOTBALL
STORAGE
OHP-A2
OHP-A1
OHP-E1 OHP-B2 OHP-B1
OHP-C1
HRU-1
F-K3
F-B4
F-G2 F-G1
F-G4
TW-K1
OAU-CU-1
F-G3
F-K1
F-K6
E-KH-1
F-B1
TW-B1
IHP-G1
KSF-1
KILN
DOU-5 DOU-4
DCFU-4 DCFU-5
OHP-G1
RTU-G2
RTU-G1
G
G
G
D D
R
R
D
D
D
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M202
MECHANICAL NEW WORK
PIPING PLAN - SECTOR B
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
No. Description Date 1/8" = 1'-0"
NEW WORK PIPING PLAN - SECTOR B
NOTES: (THIS SHEET ONLY)
1 . CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD STRUCTURE WITH SUPPLEMENTAL
2"X2"X1/4" ANGLE IRON.
2 . NEW DUCTLESS HEAT PUMPS MOUNTED ON NEW CONCRETE EQUIPMENT PAD. SEE CONCRETE EQUIPMENT PAD DETAIL. VERIFY
LOCATION IN MECHANICAL WITH OTHER EQUIPMENT.
3 . NEW VERTICAL FAN COIL UNIT MOUNTED ON NEW RETURN AIR PLENUM STAND. CONNECT NEW OUTISIDE AIR DUCT TO EXISTING
ROOF INTAKE.
4 . NEW VRF HEAT RECOVERY UNIT MOUNTED ON EXISTING CONCRETE EQUIPMENT PAD. VERIFY EXISTING CONCRETE EQUIPMENT
PAD SIZE.
5 . NEW 100% OUTSIDE AIR CONDENSING UNIT MOUNTED ON EXISITNG CONCRETE EQUIPMENT PAD. ROUTE NEW REFRIGERANT
LINE SET TO 100% OA UNIT IN EMCHANCAL MEZZANINE.
6 . NEW HEAT PUMP MOUNTED ON EXISTING CONCRETE EQUIPMENT PAD. ROUTE NEW REFRIGERANT LINE SET TO FAN COIL UNIT.
7 . EXISTING HEAT PUMP TO REMAIN. CONTRACTOR SHALL PERFORM ROUTINE SERVICE ON THIS UNIT DURING CONSTRUCTION.
8 . ROUTE CEILING CASSETTE CONDESATE TO FLOOR SINK IN DISH WASH ROOM. FEILD VERIFY EXACT LOCATION OF FLOOR SINK.
9 . ROUTE RTU CONDESATE PIPE TO GUTTER. PROVIDE CONDENSATE PIPE SUPPORTS ON ROOF.
10 . CONTRACTOR SHALL MODIFY EXISTING GAS PIPING AS REQUIRED FOR CONNECTION TO NEW UNIT AS SHOWN. VERIFY EXACT LOCATION OF GAS CONNECTION WITH APPROVED UNIT SUBMITTED. SEE TYPICAL RTU GAS CONNECTION DETAIL.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M401
MECHANICAL EQUIPMENT
PIPING DIAGRAMS
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
No. Description Date
NOT TO SCALE
VRF SYSTEM - PIPING DIAGRAM
NOT TO SCALE
OA SPLIT SYSTEM - PIPING DIAGRAM
GENERAL NOTE:
1. BASIS OF DESIGN IS AAON. IF CONTRACTOR SUBMITS MANUFACTURER OTHER THAN AAON, HE
SHALL SUBMIT MANUFACTURER'S REFRIGERANT PIPING SCHEMATIC. ALL REFRIGERATION
ACCESSORIES/COMPONENTS INCLUDING FIELD INSTALLED COMPONENTS SHALL BE PROVIDED BY
EQUPMENT MANUFACTURER, NO EXCEPTIONS.
2. CONTRACTOR SHALL SUBMIT EXACT REFRIGERANT PIPE LAYOUT/DISTANCE (EQUIVALENT
LENGTH) TO MANUFACTURER FOR EQUIPMENT MANUFACTURER TO SIZE REFRIGERANT PIPING.
THIS SHALL INCLUDE VERTICAL LIFT, NUMBER OF ELBOWS, ETC. DURING THE SUBMITTAL PROCESS, ENGINEER WILL REVIEW.
3. ONCE REFRIGERANT PIPING IS COMPLETE, IT SHALL BE INSPECTED BY A FACTORY TRAINED
REPRESENTATIVE.
GENERAL NOTES:
1. EQUIPMENT MODEL NUMBERS INDICATED ARE FOR BASIS-OF-DESIGN
MANUFACTURER, CARRIER, UNLESS NOTED OTHERWISE.
2. REFRIGERANT PIPING SIZES INDICATED ARE APPROXIMATE AND SHALL BE
VERIFIED / COORDINATED WITH EQUIPMENT SUPPLIER BASED ON REQUIRED
LENGTHS, SYSTEM LAYOUT / INSTALLATION, SYSTEM CAPACITY, ETC. AND OTHER
FACTORS AS REQUIRED BY MANUFACTURER.
MAIN ROUND TRUNK DUCT
2 3/16" DUCT WRAP INSULATION FOR
SUPPLY AND RETURN DUCT
OPENING IN SIDE OF RECTANGULAR SHEET METAL
DUCT SHALL BE CUT WITH DRILL-CUTTER OR TIN
SNIPS. DIAMETER OF OPENING SHALL MATCH INNER
DIAMETER OF FOAM GASKET OR DIAMETER
RECOMMENDED BY TAKEOFF MANUFACTURER
DUCT
DUCT MASTICSHEET METAL SCREWS ON 6" CENTERS
FOAM GASKET
EXTERIOR VAPOR BARRIER (ONLY) SECURED
TO FITTING WITH NYLON "ZIP STRIP" BAND
SECURE INNER DUCT TO FITTING WITH NYLON
ZIP STRIP BAND IN ADDITION TO NYLON
STRIPBAND. SEAL INNER CORE TO DUCT.
FLEXIBLE DUCTWORK
90° SADDLE TAKEOFF COLLAR DAMPER AND THERMA-SEAL
GASKET FLANGE AND DAMPER HANDLE STANDOFF, SIMILAR TO
CROWN PRODUCT MODEL #314-DSO
FOR SUPPLY/RETURN DUCTS, INSULATE ENTIRE FITTING (EXCEPT OPERATOR
HANDLE) WITH 2 3/16" DUCT WRAP SEALED WITH VAPOR PROOF MASTIC AND CLOTH
FABRIC TO FLEX DUCT VAPOR BARRIER (NOT SHOWN FOR CLARITY)
20 GAUGE GALVANIZED SHEET METAL COVER
SEAL AND CAULK ALL JOINTS WATERTIGHT
A S
R E
Q U
IR
E
D
AS REQUIRED
SHEET METAL COVER ATOP ANGLE IRON
CONTINUOUS INSULATION
LAG SCREWS TO CURB ON MAXIMUM 16" CENTERS
EXISTING ROOF CURB TO REMAIN FOR REUSE
EXISTING ROOF AND DECK
PLAN VIEW
ELEVATION VIEW
CONTRACTOR SHALL FIELD VERIFY
EXACT CURB DIMENSIONS PRIOR
TO FABRICATING CURB CAP.
3" X 3" X ¼" ANGLE IRON FULLY WELDED
(PROVIDE CENTER ANGLE AT MIDSPAN
FOR ALL CURBS LARGER THAN 8 SQ. FT.)
NOTE: ALL ITEMS IN THIS DETAIL ARE NEW UNLESS NOTED OTHERWISE.
CURB CAP IS TO BE CONSTRUCTED OF 3" X 3" X ¼" ANGLE IRON
MEMBERS, MITERED OR BUTTED AS SHOWN AND WELDED TOGETHER.
COVER ENTIRE FRAME WITH 20 GA. GALVANIZED SHEET METAL. SEAL
AND CAULK ALL SEAMS WATERTIGHT. LINE ENTIRE UNDERSIDE WITH 1 ½"
RIGID FIBERGLASS INSULATION. SECURE TO EXISTING CURB WITH
GALVANIZED LAG SCREWS ON 16" CENTERS.
PROVIDE 1" WIDE CLOSED CELL
ELASTOMERIC (ARMAFLEX) TAPE
AROUND FULL PERIMETER OF
CURB TO SEAL COVER TO CURB.
PROVIDE BACKERBOARD IN ANY GAPS
AND SEAL AIR TIGHT WITH SILICONE
CAULK AROUND FULL PERIMETER
AT POINT WHERE ANGLE IRON OVERLAPS
CURB.
CEILING, BY ARCHITECTURAL
SQUARE TO ROUND TRANSITION (WHERE ELBOW CONNECTS TO SQUARE
NECK DIFFUSERS). PROVIDE ROUND TO ROUND TRANSITION WHERE GRILLE
NECK SIZE DIFFERS FROM CONNECTING DUCT SIZE (EITHER LARGER OR
SMALLER). INSULATE ON SUPPLY DUCTS.
3 GORE ADJUSTABLE ELBOW. INSULATE
ON SUPPLY DUCTS.
NYLON ZIP STRIP ON OUTER VAPOR BARRIER.
ENSURE INSULATION IS PULLED DOWN WITH
VAPOR BARRIER SO NO DUCTWORK IS
UNINSULATED.
NOTE: DETAIL IS TYPICAL FOR ALL FLEX DUCT RUNOUTS TO DIFFUSERS
STAINLESS STEEL DRAWBAND
ON INNER DUCT
FLEX DUCT
INSULATION BLANKET ON TOP
OF SUPPLY DIFFUSERS
CEILING DIFFUSER
J
POWER WIRING AND CONDUIT BY ELECTRICAL
PROVIDE "KNOCK OUT" AND GROMMET
FOR POWER CABLE
ROOF CURB. SEE ROOF CURB DETAIL.
POWER CABLE BY ELECTRICAL
REMOVABLE ACCESS COVER FOR MOTOR
COMPARTMENT
INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT
SWITCH UNLESS SCHEDULED OTHERWISE
SEE SCHEDULE FOR DRIVE TYPE. (PROVIDE
ADJUSTABLE SHEAVE FOR ALL BELT DRIVE)
FACTORY WIRED FROM MOTOR TO
DISCONNECT SWITCH.
EXHAUST FAN
FACTORY FURNISHED DAMPER TRAY TO SUPPORT
BACK DRAFT DAMPER AND PROVIDE DUCT
ATTACHMENT.
FULL PERIMETER ANGLE IRON FRAMING BENEATH
CURB BY STRUCTURAL.
SECURE DUCT TO ROOF STRUCTURE WITH SHEET
METAL ON 4 SIDES. DUCT SHALL NOT BE
SUPPORTED BY DAMPER TRAY.
EXHAUST DUCT UP FROM BELOW
EXHAUST DUCT SHALL TRANSITION AS REQUIRED AT
UNDERSIDE OF ROOF DECK TO MATCH FANS DAMPER/
CURB SIZE.
MINIMUM 1 1/4" CLEARANCE FOR CONDUIT
FACTORY INSTALLED, MINIMUM 1/2"
DIA. CONDUIT CHASE
J
POWER WIRING AND CONDUIT BY ELECTRICAL
PROVIDE "KNOCK OUT" AND GROMMET
FOR POWER CABLE
ROOF CURB. SEE ROOF CURB DETAIL.
POWER CABLE BY ELECTRICAL
REMOVABLE ACCESS COVER FOR MOTOR
COMPARTMENT
INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT
SWITCH UNLESS SCHEDULED OTHERWISE
SEE SCHEDULE FOR DRIVE TYPE.
FACTORY WIRED FROM MOTOR TO
DISCONNECT SWITCH.
UPBLAST EXHAUST FAN
FACTORY FURNISHED DAMPER TRAY TO SUPPORT
BACK DRAFT DAMPER AND PROVIDE DUCT
ATTACHMENT.
FULL PERIMETER ANGLE IRON FRAMING BENEATH
CURB BY STRUCTURAL.
SECURE DUCT TO ROOF STRUCTURE WITH SHEET
METAL ON 4 SIDES. DUCT SHALL NOT BE
SUPPORTED BY DAMPER TRAY.
EXHAUST DUCT UP FROM BELOW
EXHAUST DUCT SHALL TRANSITION AS REQUIRED AT
UNDERSIDE OF ROOF DECK TO MATCH FANS DAMPER/
CURB SIZE.
MINIMUM 1 1/4" CLEARANCE FOR CONDUIT
FACTORY INSTALLED, MINIMUM 1/2"
DIA. CONDUIT CHASE GALVANIZED BIRD SCREEN
SECURE CURB CAP TO CURB WITH ANCHORS ON
MAXIMUM 12" CENTERS (MINIMUM 2 ANCHORS
EACH SIDE)
GRADE
WELDED WIRE MESH
AT MID DEPTH OF SLAB
6" X 6" 10/10 WWF
3000 PSI CONCRETE
1" CHAMFER
SEE SPECIFICATIONS FOR
PAD HEIGHT ABOVE
ADJACENT GRADE
2" MINIMUM
EXTERIOR CONCRETE PAD
FLOOR
1" CHAMFER
ANCHOR (TYPICAL OF 4)
INTERIOR CONCRETE PAD
WELDED WIRE MESH
AT MID DEPTH OF SLAB
6" X 6" 10/10 WWF
SEE SPECIFICATIONS FOR
PAD HEIGHT ABOVE
ADJACENT GRADE
2"
3000 PSI CONCRETE
1½"
3"
UNION
AC UNIT
DRAIN CONNECTION
DRAIN PIPE SHALL BE AT LEAST
THE SAME DIAMETER AS THE NIPPLE
ON THE DRAIN PAN CONNECTION
OPEN END NIPPLE
SEE DRAWINGS FOR
PIPE REQUIRED MATERIAL
SLOPE AS REQUIRED
IN SPECIFICATIONS
PIPE NIPPLE
6"
FRONT VIEW
4"
SIDE VIEW
V A
R
IE
S
CONDENSATE PIPE,
VERIFY SIZE (TYP)
UV - STABILIZED, EDPM ADJUSTABLE RUBBER PIPE
SUPPORT, VERIFY PIPE DIAMETER BEING SUPPORTED.
SPACED ON MAXIMUM 8 FT. CENTERS AND 24" OF
FITTINGS (ERICO CADDY PYRAMID RPSE - TYPICAL)
INSTALL CONDENSATE PIPE AT THE LOWEST
POSSIBLE ELEVATION TO REDUCE TOP
HEAVY PIPE AND TO REDUCE TIPPING OVER
BUT TO MAINTAIN SPECIFIED SLOPE.
GENERAL: THIS CONDENSATE SUPPORT SHALL BE USED WITH DRAIN ELEVATIONS ABOVE ROOF OF 7" OR LESS. CONDENSATE ELEVATIONS ABOVE 8" SHALL USE ERICO CADDY PYRAMID ST ADJUSTABLE
STRUT SUPPORT OR EQUAL BY MIRO.
OPENING IN SIDE OF RECTANGULAR
SHEET METAL DUCT SHALL BE CUT
WITH DRILL CUTTER (NOT TIN SNIPS).
DIAMETER OF OPENING SHALL MATCH
INNER DIAMTER OF FOAM GASKET.
DUCT
DUCT MASTIC
FOAM GASKET
SHEET METAL SCREWS
ON 4" CENTERSDUCT
2" DUCT WRAP INSULATION FOR SUPPLY DUCT
EXTERIOR VAPOR BARRIER (ONLY) SECURED TO
FITTING WITH NYLON "ZIP-STRIP" BAND
FLEXIBLE DUCTWORK
BELLMOUTH OR 45° FITTING WITH DAMPER
FOR SUPPLY DUCTS, INSULATE ENTIRE FITTING (EXCEPT OPERATOR HANDLE)
WITH 2" DUCTWRAP SEALED WITH VAPOR PROOF MASTIC AND CLOTH FABRIC
TO FLEX DUCT VAPOR BARRIER (NOT SHOWN FOR CLARITY)
PROVIDE OPTIONAL EXTENDED NECK SHAFT
FOR INSULATED DUCTS TO CLEAR INSULATION THICKNESS
SECURE INNER DUCT TO FITTING WITH 1/2" STAINLESS STEEL
DRAW BAND. CONTRACTOR SHALL NOT UTILIZE NYLON "ZIP-
STRIP" BAND TO SECURE INNER DUCT TO FITTING.
AIR
NOTE: SINGLE BI-POLAR IONIZATION UNIT SHOWN. INSTALLATION SIMILAR WHEN
MULTIPLE UNITS ARE INSTALLED IN ONE HVAC UNIT, EXCEPT 24V WIRING FROM
HVAC UNIT'S TERMINAL SIDE SHALL FEED CONTRACTOR FURNISHED TERMINAL
STRIP, WHICH SHALL THEN FEED POWER TO MULTIPLE UNITS. CONTRACTOR
FURNISHED TERMINAL STRIP SHALL BE ELECTRICALLY ISOLATED FROM THE HVAC
UNIT CASING AND ALL OTHER METAL COMPONENTS.
SECURE WITH SCREWS IN LOCATION THAT
WILL NOT DAMAGE HVAC EQUIPMENT OR
ASSOCIATED REFRIGERANT PIPE, WIRING
OR OTHER COMPONENTS
NEEDLEPOINT ELECTRODES. ENSURE UNIT IS
ORIENTED AND INSTALLED SO THAT AIR FLOW
PASSES BETWEEN ELECTRODES (INSTALL
PERPENDICULAR TO AIRFLOW). MAINTAIN
MANUFACTURER'S DISTANCE FROM NEEDLES
TO METAL SURFACE TO PREVENT ARCING.
FACTORY
FURNISHED
24VAC WIRING
BI-POLAR UNIT. SEE SCHEDULE FOR QUANTITY.
SEE ENLARGED DRAWING BELOW.
LED CONFIRMING IONIZATION OPERATION
B.A.S. CONTACTS TO ALLOW OWNER TO MONITOR STATUS.
MONITORING IS NOT INCLUDED IN THIS PROJECT.
BI-POLAR IONIZATION UNIT MOUNTED INSIDE UNIT DOWNSTREAM OF
FILTER IN SUPPLY AIRSTREAM IN LOCATION APPROVED BY HVAC
EQUIPMENT MANUFACTURER AND BI-POLAR MANUFACTURER
(FAN)
(24V POWER)
G
R
Y
W
C
O
CONNECT TO FAN AND 24V POWER TERMINALS ON 24 VAC
TERMINAL STRIP IN HVAC EQUIPMENT. ADDITIONAL GENERIC
TERMINALS ARE SHOWN FOR SYMBOLIC PURPOSES AND
ACTUAL TERMINALS WILL VARY BASED ON TYPE OF
EQUIPMENT.
PROVIDE ADDITIONAL WIRING (AS REQUIRED) IF FACTORY FURNISHED
WIRING WILL NOT REACH 24VAC TERMINAL STRIP. PROVIDE WIRE NUTS
AND ELECTRICAL TAPE AT JOINT. MATCH WIRE GAUGE OF
MANUFACTURER'S WIRING.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M501
MECHANICAL DETAILS
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
NOT TO SCALE
90° SADDLE TAP TAKEOFF FITTING DETAIL
NOT TO SCALE
CAP AT EXISTING CURB
NOT TO SCALE
CEILING GRILLE DUCT CONNECTION DETAIL
NOT TO SCALE
CENTRIFUGAL DOWN BLAST EXHAUST FAN DETAIL
NOT TO SCALE
CENTRIFUGAL UPBLAST EXHAUST FAN DETAIL (CHECK)
NOT TO SCALE
CONCRETE EQUIPMENT PAD DETAIL
NOT TO SCALE
CONDENSATE DRAIN TRAP DETAIL
NOT TO SCALE
CONDENSATE PIPE SUPPORT ON ROOF DETAIL
NOT TO SCALE
BELLMOUTH AND 45° TAKEOFF FITTING DETAIL
NOT TO SCALE
COMPACT BI-POLAR IONIZATION UNIT DETAIL
PROVIDE INSULATED HOUSING WHERE SCHEDULED
DUCT
AIRFLOW
PARALLEL BLADE BACKDRAFT DAMPER
SQUARE ACCESS PANEL FOR DAMPER ACTUATOR ACCESS
ACCESS PANEL (BOTH SIDES)
MOUNTING BRACKETS (TYP)
HANGING VIBRATION ISOLATORS. SEE SPECS FOR TYPE.
THREADED ROD
SUPPLEMENTAL ANGLE IRON FRAMING
DOUBLE NUTS
DOUBLE NUTS
DUCT
MOTOR. SEE SPECS FOR TYPE.
NOTE: BELT DRIVE FAN SIMILAR, EXCEPT MOTOR
OUTISDE OF FAN CASING, AND WITH INSULATED
MOTOR COVER WHERE SPECIFIED.
DUCT MOUNTING COLLAR (TYP INLET AND OUTLET). PROVIDE
1/2" X 1/2" WELDED WIRE GALVANIZED INLET GUARD FOR
NON-DUCTED INLET APPLICATIONS AS SCHEDULED.
MAINTAIN MINIMUM 2.5 TIMES WHERE DIAMETER STRAIGHT
DUCT LENGTH AT INLET AND OUTLET OF FAN BEFORE
ELBOW, TRANSITION, DAMPER, ETC.
PROVIDE MOTORIZED DAMPER WITH INTERNAL ACTUATOR WHERE
SCHEDULED. DAMPER VOLTAGE SHALL MATCH FAN VOLTAGE.
FLEXIBLE DUCT
CONNECTION (TYP)
GALVANIZED MOTOR COVER
WHERE SCHEDULED
BACKWARD
INCLINED WHEEL
MAINTAIN MINIMUM 2.5 TIMES
WHEEL DIAMETER STRAIGHT
DUCT LENGTH AT INLET AND
OUTLET OF FAN BEFORE ELBOW,
TRANSITION, DAMPER, ETC.
FACTORY INSTALLED NEMA-1
DISCONNECT SWITCH
FACTORY WIRED FROM MOTOR
TO DISCONNECT SWITCH
WELD SIDE ANGLE CLIP TO PAN (TYP OF 4)
TO CORNERS. SUSPEND WITH 3/8"
THREADED ROD. DO NOT BLOCK ACCESS
TO CONTROLLER.
PAN SHALL BE MIN. 18 GAUGE
GALVANIZED STEEL
2"
3/4" NIPPLE WELDED
TO PAN
PIPE 3/4" PAN DRAIN TO LOCATION
SHOWN ON DRAWINGS. SLOPE
PAN TO THIS SIDE.
FABRICATE DRAIN PAN MINIMUM
12" LONGER AND WIDER THAN
MAIN/SUB CONTROLLER
FABRICATE DRAIN PAN MINIMUM
12" LONGER AND WIDER THAN
MAIN/SUB CONTROLLER
18 GAUGE GALVANIZED SHEET METAL COVER FACTORY
FABRICATED BY EQUIPMENT SUPPORT MANUFACTURER
SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.AS REQUIRED
RAISED CHANNEL SUPPORT FOR
MOUNTING OF HEAT PUMPS (TYP).
CHANNELS TO BE FACTORY
FABRICATED INTO COVER.
COORDINATE SPACING OF SUPPORT CHANNELS
WITH DIMENSIONS OF HEAT PUMPS BEING
INSTALLED ATOP PLATFORM. SEE PLANS
FOR UNIT LAYOUT.
ROOF CURB. SEE ROOF CURB DETAIL.COORDINATE LENGTH OF PLATFORM
REQUIRED WITH UNIT LAYOUT INDICATED
ON PLANS
ISOMETRIC VIEW
HEAT PUMP UNIT. SEE PLANS FOR SIZING AND LAYOUT.
SECURE HEAT PUMP
TO SUPPORT CHANNEL.
LAG SCREWS TO CURB ON
MAXIMUM 16" CENTERS.
ROOF CURB. SEE
ROOF CURB DETAIL.
PROVIDE FACTORY FURNISHED
INTERNAL SUPPORT CHANNELS
AS REQUIRED TO SUPPORT
WEIGHT OF HEAT PUMP UNITS.
ROOF DECK SHALL BE
CONTINUOUS UNDER CURB.
6" (MIN.)
FRONT VIEW
PRESSURE TREATED WOOD NAILER
SHEET METAL SCREW IN SIDE OF
COUNTER FLASHING (TYP)
18 GAUGE GALVANIZED STEEL
COUNTER FLASHING
SHEET METAL SCREW (TYP)
18 GAUGE STEEL BASE SECTION
FIELD INSTALLED INSULATION
INTEGRAL 18 GAUGE
GALVANIZED
STEEL BASE PLATE
FIELD INSTALLED CANT
ROOF DECK CONTINUOUS
BENEATH SUPPORT RAIL
SEE ARCHITECTURAL DRAWINGS FOR SPECIFIC
DETAILS CONCERNING ROOF CONSTRUCTION,
FLASHING, ANCHORS, BLOCKING,
ROOF DECK TYPE, ETC.
C U
R B
H E
IG
H
T
S T
Y
LE
A
S T
Y
LE
B
S T
Y
LE
C
2" MAX.
1" 1"
FOLDING BLADE STATIC RATED FIRE DAMPER
IN TYPE 'B' FRAME (EXCEPT TYPE 'A' SHALL BE
USED AT SIDEWALL REGISTERS AND NON-DUCTED
TRANSFER OPENING). DYNAMIC RATED DAMPERS
SHALL BE USED WHERE SPECIFICALLY SHOWN
ON DRAWINGS
ATTACH FIRE DAMPER TO SLEEVE IN
ACCORDANCE WITH MANUFACTUER'S
UL INSTALLATION INSTRUCTIONS
FACTORY FURNISHED ROUND OR OVAL
TRANSITION WITH BLADE STACK OUT
OF AIR STREAM
ROUND AND OVAL FIRE DAMPER
INSTALLATION SIMILAR
DUCT (WHERE APPLICABLE)
SLEEVE LENGTH SHALL BE DETERMINED BY CONTRACTOR TO
BE WITHIN MINIMUM AND MAXIMUM DISTANCE FROM
WALL/FLOOR AS REQUIRED BY MANUFACTUER
NOTE: INSTALLATION SHALL CONFORM TO THE FIRE
DAMPERS MANUFACTURER'S "UL" INSTALLATION
INSTRUCTIONS
WALL OR FLOOR. CONTRACTOR SHALL VERIFY
THICKNESS RATING, AND MATERIAL OF
CONSTRUCTION FROM ARCHITECTURAL DRAWINGS,
AND USE THIS INFORMATION TO SELECT FIRE
DAMPER AND FIRE DAMPER ACCESSORIES.
PROVIDE MINIMUM OVERLAP ALL AROUND AS REQUIRED BY
MANUFACTURER'S UL INSTALLATION INSTRUCTIONS
CLEARANCE (TYPICAL) AS REQUIRED BY MANUFACTURER'S
UL INSTALLATION INSTRUCTIONS
165° FUSIBLE LINK
DUCT TO SLEEVE CONNECTION SHALL BE AN APPROVED
TYPE AS LISTED IN THE MANUFACTURER'S UL INSTALLATION
INSTRUCTIONS. PROVIDE DUCT SEALANT APPROVED BY
FIRE DAMPER MANUFACTURER.
PROVIDE ACCESS PANEL FOR RECTANGULAR DUCTS. FOR ROUND DUCTS,
DOOR SIZE SHALL BE AS NOTED IN SPECIFICATIONS. FOR FLOOR
PENETRATIONS ACCESS PANEL SHALL BE ABOVE FLOOR.
FACTORY PROVIDED SLEEVE. SLEEVE LENGTH AND GAUGE SHALL
BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH
MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.
FACTORY PROVIDED RETAINING ANGLES. ANGLE SIZE AND GAUGE
SHALL BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH
MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.
GROUT
1" ABOVE FLOOR; FLUSH FOR WALLS
SCHEDULE 10 (MINIMUM)
STEEL PIPE
CONDUIT OR PIPING
PIPING INSULATION AS SPECIFIED.
PIPE INSULATION SHALL BE CONTINUOUS
THRU PENETRATION.
SEAL BETWEEN SLEEVE AND PIPING WITH FIRE RESISTANT
SEALANT OF SUFFICIENT THICKNESS TO MAINTAIN WALL'S
OR FLOOR FIRE RATING (1" MINIMUM THICKNESS). IF WALL
IS NOT FIRE RATED, PROVIDE CAULKING IN LIEU OF FIRE
RESISTANT SEALANT. SEALANT IS ONLY REQUIRED ON
ONE SIDE OF WALL, UNLESS REQUIRED BY MANUFACTURER
ON BOTH SIDES.
FIBERGLASS BATTS PACKED BETWEEN SLEEVE
AND PIPE (OR PIPE INSULATION ON INSULATED PIPE)
WALL OR FLOOR. CONTRACTOR SHALL VERIFY
CONSTRUCTION TYPE (MASONRY, CONCRETE,
BRICK AND CMU, ETC.) AND THICKNESS.
INSIDE
UNINSULATED REFRIGERANT LIQUID PIPE
REFRIGERANT PIPE DROPS
IN WALL AS REQUIRED
INSULATED REFRIGERANT
SUCTION PIPE
20 GAUGE GALVANIZED
STEEL SHEET METAL SLEEVE
TERMINATE SLEEVE
FLUSH WITH WALL
OUTSIDE
PIPE PENETRATES WALL
NEAR GRADE LEVEL
EXTERIOR PAINTABLE SILICON CAULK.
PAINT TO MATCH EXTERIOR. EXTERIOR WALL. SEE ARCHITECTURAL PLANS
FOR CONSTRUCTION
FIRE RESISTANT FOAM OF APPROPRIATE
THICKNESS TO MAINTAIN WALL'S FIRE RATING
(1" MINIMUM THICKNESS)
DIA. -",
(SEE PLANS)
3"
DIM. + ?"
DIM. + ?"
3"
PAINT INTERIOR OF BOX MATTE BLACK.1
2 MINIMUM 26 GAUGE GALV. SHEET METAL.
4 ADAPTER MAY BE FABRICATED BY CONTRACTOR OR PROVIDED BY CROWN
PRODUCTS MODEL #666 ADAPTER OR EQUAL.
PROVIDE 1/2" DUCT LINER ON RETURN DUCT
APPLICATIONS AND NO LINER ON EXHAUST APPLICATION.
NOTES: (THIS DETAIL ONLY)
CAULK AROUND FULL PERIMETER OF ANGLE
EACH SIDE OF WALL.
3" X 3", 22 GAUGE SHEET METAL ANGLE
AROUND PERIMETER OF DUCT EACH SIDE
OF WALL. ANCHOR TO WALL WITH
EXPANSION ANCHOR.
DUCT WRAP INSULATION WITH FSK JACKET.
INSULATION IS CONTINUOUS THROUGH WALL
OPENING.
ELEVATION SECTION
NOTE: DETAIL IS SIMILAR FOR
UNINSULATED DUCTS. SEE
SPECIFICATION FOR REQUIRED
INSULATION THICKNESS.
SEAL WITH VAPOR PROOF MASTIC AND CLOTH FABRIC
OVERLAPPING ANGLE AND DUCT WRAP FSK JACKET TO
PREVENT PASSAGE OF SMOKE.
CAULK AROUND FULL PERIMETER OF ANGLE
EACH SIDE OF WALL.
3" X 3", 22 GAUGE SHEET METAL ANGLE AROUND
PERIMETER OF DUCT EACH SIDE OF WALL.
ANCHOR TO WALL WITH EXPANSION ANCHOR.
DUCT WRAP INSULATION WITH FSK
JACKET.INSULATION IS CONTINUOUS
THROUGH WALL OPENING.
SEAL WITH VAPOR PROOF MASTIC AND CLOTH
FABRIC OVERLAPPING ANGLE AND DUCT WRAP
FSK JACKET TO PREVENT PASSAGE OF SMOKE.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 0101
M502
MECHANICAL DETAILS
2023124
A L B
A N
Y M
ID
D
L E
S C
H O
O L
H
V A
C U
P G
R A
D E
S
09/22/2023
HHP
JA3
C
O R
D E
L L A
V E
A
L B
A N
Y G
A
NOT TO SCALE
CENTRIFUGAL INLINE FAN DETAIL
NOT TO SCALE
CONDENSATE AUXILIARY DRAIN PAN DETAIL
NOT TO SCALE
EQUIPMENT SUPPORT PLATFORM DETAIL (HP)
NOT TO SCALE
EQUIPMENT SUPPORT RAIL DETAIL
NOT TO SCALE
FIRE DAMPER DETAIL
NOT TO SCALE
PIPE SLEEVE DETAIL
NOT TO SCALE
PIPE SLEEVE DETAIL - REFRIGERANT PIPE THRU EXTERIOR WALL
NOT TO SCALE
RECTANGULAR TO ROUND FLAT ADAPTER
NOT TO SCALE
DUCT PENETRATION THRU WALL DETAIL
INSIDEOUTSIDE
GRADE
EXTERIOR 22 GAUGE HOOD SHALL BE PAINT GRIP SHEET
METAL. ALL JOINTS AND SEAMS SHALL BE STANDARD
SMACNA CONSTRUCTION, AND SEALED NEATLY AND
WATERTIGHT. PAINT EXTERIOR DUCTWORK WITH 2 COATS
OF ENAMEL PAINT. VERIFY COLOR WITH ENGINEER.
HVAC
UNIT CAULK FULL WIDTH.
SEAL WEATHERTIGHT.
TURN CONNECTING DUCT UPWARD WITH 2"
FLANGE ON RTAC CONNECTION. CAULK FULL
PERIMETER OF DUCT.
1 LAYER OF EXTERIOR 2" THICK ARMACELL CLOSED
CELL ELASTOMERIC INSULATION OVER SUPPLY AND
RETURN DUCTWORK. FIBERGLASS INTERNAL DUCT
LINER OR EXTERNAL DUCT WRAP/BOARD IS NOT
ALLOWED ON THE DUCT. FINISH INSULATION WITH 2
COATS OF ARMACELL ARMAFLEX FINISH AND
EMBOSSED ALUMINUM COVER.
SEE PLANS FOR DUCT CONTINUATION.
NOTE: THE DUCT ROUTING SHOWN BETWEEN THE HVAC UNIT AND THE EXTERIOR WALL IS
SYMBOLIC IN THIS DETAIL AND DOES NOT INTEND TO INDICATE ALL ELBOWS, TRANSITIONS,
OFFSETS, ETC. SEE FLOOR PLANS FOR ACTUAL ROUTING.
CONCRETE EQUIPMENT PAD. SEE
CONCRETE EQUIPMENT PAD DETAIL.
22 GAUGE 3 SIDED METAL DUCT HOOD BETWEEN HVAC UNIT AND
EXTERIOR WALL. EXTEND BOTH SIDES OF SHEET METAL COVER TO
CONCRETE PAD. FLANGE DUCT 2" AT CONCRETE PAD AND PROVIDE
WEATHERTIGHT SEALS AT CONNECTION POINTS.
22 GAUGE METAL COUNTER FLASHING FULL
WIDTH OF DUCT ANCHORED TO EXTERIOR
WALL AND OVERLAPPING FLANGE OF COVER
NOTE: BASIS OF DESIGN CONDENSATE DRAIN IS LOCATED BETWEEN SUPPLY AND RETURN
DUCT CONNECTIONS. ROUTE CONDENSATE TO EXTERIOR OF HOOD AND PROVIDE P-TRAP
AT EXTERIOR OF HOOD IN AN ACCESSIBLE LOCATION. SEE CONDENSATE DRAIN TRAP
DETAIL.
2" MIN. UPWARD TURNED FLANGE. CAULK
FULL WIDTH OF FLANGE.
DUCT
SEE PLANS FOR DUCT CONTINUATION.
DUCT
FIELD VERIFY EXISTING DUCT
OPENING DIMENSIONS.
INSIDEOUTSIDE
GRADE
EXTERIOR 22 GAUGE HOOD SHALL BE PAINT GRIP
SHEET METAL. ALL JOINTS AND SEAMS SHALL BE
STANDARD SMACNA CONSTRUCTION, AND SEALED
NEATLY AND WATERTIGHT. PAINT EXTERIOR
DUCTWORK WITH 2 COATS OF ENAMEL PAINT.
VERIFY COLOR WITH ENGINEER.
22 GAUGE METAL COUNTER FLASHING FULL
WIDTH OF DUCT ANCHORED TO RTAC AND
OVERLAPPING FLANGE OF COVER
HVAC
UNIT
CAULK FULL WIDTH
CAULK FULL WIDTH OF FLANGE
TURN CONNECTING DUCT UPWARD WITH 2"
FLANGE ON RTAC CONNECTION. CAULK FULL
PERIMETER OF DUCT.
1 LAYER OF EXTERIOR 2" THICK ARMACELL CLOSED
CELL ELASTOMERIC INSULATION. FIBERGLASS
INTERNAL DUCT LINER OR EXTERNAL DUCT
WRAP/BOARD IS NOT ALLOWED ON THE DUCT. FINISH
INSULATION WITH 2 COATS OF ARMACELL ARMAFLEX
FINISH AND EMBOSSED ALUMINUM COVER.
SEE PLANS FOR DUCT CONTINUATION.
NOTE: THE DUCT ROUTING SHOWN BETWEEN THE HVAC UNIT AND THE EXTERIOR WALL IS
SYMBOLIC IN THIS DETAIL AND DOES NOT INTEND TO INDICATE ALL ELBOWS, TRANSITIONS,
OFFSETS, ETC. SEE FLOOR PLANS FOR ACTUAL ROUTING.
CONCRETE EQUIPMENT PAD. SEE
CONCRETE EQUIPMENT PAD DETAIL.
22 GAUGE 3 SIDED METAL DUCT HOOD BETWEEN HVAC UNIT
AND EXTERIOR WALL. EXTEND BOTH SIDES OF SHEET METAL
COVER TO CONCRETE PAD. FLANGE DUCT 2" AT CONCRETE
PAD AND PROVIDE WEATHERTIGHT SEALS AT CONNECTION
POINTS. SLOPE HOOD TO PREVENT WATER POOLING ON
TOP OF HOOD.
22 GAUGE METAL COUNTER FLASHING FULL
WIDTH OF DUCT ANCHORED TO EXTERIOR
WALL AND OVERLAPPING FLANGE OF COVER
NOTE: DO NOT ENCLOSE CONDENSATE DRAIN CONNECTION IN SHEET METAL HOOD. SEE
DRAWINGS FOR CONDENSATE ROUTING.
2" MIN. UPWARD TURNED FLANGE. CAULK
FULL WIDTH OF FLANGE.
LIGHT
RETURN
DUCT
22 GAUGE PAINT GALV GRIP GALVANIZED FLASHING. PAINT
FLASHING TO MATCH WHAC COLOR. FLASHING SHALL EXTEND
UP 4". CAULK AND SEAL WATERTIGHT AT FLASHING OVERLAP
FLASHING OVER WHAC'S INTEGRAL VERTICAL FLASHING.
WALL HUNG HEAT PUMP (WHHP)
INTEGRAL SLOPED TOP
EXISTING EXTERIOR WALL. FIELD
VERIFY EXACT CONSTRUCTION.
INTEGRAL DISCONNECT SWITCH
INTEGRAL VINYL DRAIN TUBING BY EQUIPMENT
MANUFACTURER. PVC TUBING SHALL BE
INSERTED INTO VINYL TUBING
STAINLESS STEEL HOSE CLAMP
3/4" PAINTED SCHEDULE 80 PVC DRAIN PIPE
PIPE CLAMP SECURED TO WALL
ON MAX 18" CENTERS
HEAVY DUTY STEEL RETURN GRILLE.
CONDENSATE LINE DOWN WALL AT GRADE.
AT GRADE, ELBOW PIPE AWAY FROM
BUILDING.
ROUTE DUCT HARD AGAINST
WALL AS POSSIBLE.
PROVIDE 1" LINER FROM UNIT CONNECTION
THRU BOTH ELBOWS TO LOCATION SHOWN.
REMAINDER OF SUPPLY DUCT SHALL BE
EXTERNALLY INSULATED WITH 2 3/16" DUCT
WRAP.
EXACT MOUNTING HEIGHT OF WHAC UNIT ABOVE GRADE / FINISHED
FLOOR VARIES BASED ON EXISTING CONDITIONS. WHERE POSSIBLE,
MAINTAIN MINIMUM 12" FROM BOTTOM OF WHAC TO GRADE.
SEE
INSERT
ROUTE DUCT HARD AGAINST
WALL AS POSSIBLE.
NEW ARCHITECTURAL CHASE TO CONCEAL
DUCT. SEE ARCH DRAWINGS FOR DETAILS.
WALL CURB TO ALLOW INSTALLATION OF NEW
WHHP IN SAME LOCATION AS EXISTING WHHP.
CAULK FULL LENGTH, BOTH SIDES AND TOP OF
UNIT. COLOR SHALL MATCH EXTERIOR WALL.
1" DUCT LINER INSIDE ALL RETURN DUCT.
PROVIDE CLOSED CELL EPDM ADHESIVE BACKED WEATHER
STRIPPING AROUND FULL PERIMETER OF UNIT PRIOR TO
MOUNTING AGAINST WALL TO SERVE AS INSECT AND
INFILTRATION BARRIER.
FILTER ACCESS PANEL
INTERNALLY MOUNTED BI-POLAR
IONIZATION UNIT
8" A.F.F. TO B.E. GRILLE
SOUND TRAP ELBOW
BRICK AND BLOCK WALL
FILTER IN INTEGRAL FILTER RACK
3" X 3" X 1/4" STRUCTURAL ANGLE. PAINT EXPOSED ANGLE
WITH TWO COATS OF PANT TO MATCH BUILDING COLOR
SUPPLY DUCTWORK
EXISTING INSULATION ON
CHICKEN WIRE SUPPORT
SYSTEM.
CEILINGTRANSITION IN RISE FROM
UNIT CONNECTION SIZE TO
SIZE SHOWN ON PLAN
ELECTRIC HEAT
SPACE ABOVE CEILING IS EXTREMELY LIMITED.
OFFSET DUCTWORK HORIZONTALLY AS
REQUIRED TO AVOID CONFLICT WITH LIGHT
FIXTURES. ENSURE DUCT INSULATION IS NOT
COMPRESSED MORE THAN 25%.
NOTE: DETAIL IS SIMILAR FOR UNINSULATED DUCTS.
CAULK AROUND FULL PERIMETER OF ESCUTCHEON
EACH SIDE OF WALL.
3" WIDE (MINIMUM) GAUGE SHEET METAL ESCUTCHEON
AROUND PERIMETER OF DUCT EACH SIDE OF WALL.
ANCHOR TO WALL WITH EXPANSION ANCHOR.
DUCT
DUCT WRAP INSULATION WITH FSK JACKET.
INSULATION IS CONTINUOUS THROUGH WALL OPENING.SEAL WITH VAPOR PROOF MASTIC AND
CLOTH FABRIC OVERLAPPING
ESCUTCHEON AND DUCT
WRAP FSK JACKET TO PREVENT
PASSAGE OF SMOKE.
NOTE: THIS DETAIL IS APPLICABLE TO CONCEALED ROUND, FLAT OVAL,
AND SPIRAL DUCTWORK. THIS DETAIL IS NOT APPLICABLE TO THE
INSTALLATION OF EXPOSED NON-RECTANGULAR DUCTWORK. SEE
SPECIFICATIONS FOR REQUIRED INSULATION THICKNESS
ELEVATION
SECTION
MASONRY WALL SHOWN. INSTALLATION REQUIREMENTS
ARE THE SAME FOR GYP BOARD WALLS.
SEAL WITH FSK TAPE OVERLAPPING ESCUTCHEON AND DUCT
WRAP FSK JACKET TO PREVENT PASSAGE OF SMOKE.
DUCT WRAP INSULATION WITH FSK JACKET.
INSULATION IS CONTINUOUS THROUGH WALL
OPENING.
3" WIDE (MINIMUM) 22 GAUGE SHEET METAL
ESCUTCHEON AROUND PERIMETER OF DUCT EACH
SIDE OF WALL. ANCHOR TO WALL WITH EXPANSION
ANCHOR .ENSURE ESCUTCHEON WIDTH IS
SUFFICIENT TO CONCEAL EDGES OF WALL OPENING.
CAULK AROUND FULL PERIMETER OF ESCUTCHEON
EACH SIDE OF WALL.
PROCEDURE:
1. SAW CUT BED JOINT IN BRICK TO INSTALL ANGLE.
2. INSTALL ANGLE - BEAR 8" AT JAMB.
3. SAW CUT BED JOINT IN CMU TO INSTALL ANGLE.
4. GROUT JAMBS SOLID.
5. INSTALL ANGLE - BEAR 8" AT JAMB.
6. REMOVE MASONRY AS REQUIRED.
EXISTING BRICK
¼" THICK X 11" WIDE
STEEL PLATE SPANNING
FULL WIDTH OF OPENING.
4 x 4 x 3/8 ANGLE IRON
EXISTING CMU
4 x 4 x 3/8 ANGLE IRON
3/16
NOTE: EXISTING BRICK AND BLOCK WALL
CONSTRUCTION SHOWN. SIMILAR FOR OTHER WALL
CONSTRUCTIONS.
EXISTING ROOF
RE-WORK ROOFING FOR INSTALLATION
OF NEW ROOF CURB IN ACCORDANCE WITH
ROOF MANUFACTURER'S BOND REQUIREMENTS.
C U
R B
H E
IG
H
T
EQUIPMENT
GASKET SEALER
PRESSURE
TREATED
WOOD NAILER
RIGID INSULATION
METAL ROOF CURB
LAG BOLT
PRESSURE TREATED BLOCKING
AS REQUIRED TO MATCH
INSULATION THICKNESS.
DUCT
ANCHOR TO DECK
ROOF DECK TO EXTEND
BENEATH ENTIRE ROOF CURB,
COORDINATE DUCT OPENING
LOCATION WITH MECH. UNIT
FULL PERIMETER STRUCTURAL STEEL FRAMING
UNDER ROOF CURB.
EXISTING METAL DECK
5/16" X 1/2" (MINIMUM) HEX HEAD
SCREWS ON 18" CENTERS. PROVIDE
MINIMUM 2 SCREWS PER…
This is the start of the file's text. The full file is on GovTribe.