24-8319_-_Exhibit_M_-_City_Gate_Blvd_N_Intersection-Signal_Plans_11-04-2024_S&S.pdf
PDF 3 MB Posted
- Solicitation number
- 24-8319
- Issued by
- Collier County, Florida
About this file
These are signalization plans prepared by Jacobs Engineering Group for the Collier County Transportation Management Services Department, specifically for the intersection improvement project at Collier Boulevard (County Road 951) and City Gate Boulevard North in Collier County, Florida. The plans, dated November 2024, detail a comprehensive traffic signal installation with multiple components including mast arm assemblies, signal heads, pedestrian signals, detection systems, fiber optic infrastructure, and associated electrical work. The project involves installing four mast arm assemblies ranging from 60' to 78' in length, vehicular and pedestrian traffic signals, microwave vehicle detection systems, signal priority and preemption systems, CCTV cameras, and associated electrical and communication infrastructure.
The plans specify detailed technical requirements including signal phasing, timing functions, and lighting design criteria for the signalized intersection. The lighting design calls for an average initial horizontal illumination of 3.0 foot candles with a uniformity ratio of 4:1 or less, and luminaires mounted at 35-foot heights with 158-watt fixtures. The project includes multiple conduit runs, signal cables, fiber optic connections, pull and splice boxes, electrical service installations, and pedestrian accessible signal components. The technical specifications reference the Florida Department of Transportation's Standard Plans and Specifications for Road and Bridge Construction, with specific technical special provisions from Collier County Traffic Operations, indicating a carefully planned and standardized approach to the intersection improvement project.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
11/1/2024 9:48:25 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\KEYSSG01.DGNAMANKWK
CONTRACT NO.
CONSTRUCTION
BEE LINE
EXPRESSWAY
T U
R N P
IK
E
PENSACOLA FORT WALTON
BEACH
PANAMA
CITY
CHIPLEY
TALLAHASSEE
JACKSONVILLE
ST AUGUSTINE
GAINESVILLE
OCALA DAYTONA BEACH
DELAND
NEW PORT RICHEY
TAMPA
LAKELAND
MELBOURNE -
COCOA
ORLANDO
BARTOWST PETERSBURG
SARASOTA -
BRADENTON
FT PIERCE
FT MYERS
WEST PALM
BEACH
FT LAUDERDALE
MIAMI
75NAPLES
KEY WEST
CITY
LAKE
F
LO
R
ID
A 'S
LOCATION OF PROJECT
T H
E
O F
F I
C I
A L
R
C O
D
T
I
S
E E
T
E C
T R
O N
C
G I
T A
L
Y
G N
N
A L
U
D
L E
G
A
C
T-1
SHEET DESCRIPTIONSHEET NO.
INDEX OF SIGNALIZATION PLANS
NO.
SHEET
YEAR
FISCAL
GOVERNING DESIGN STANDARDS:
GOVERNING STANDARD SPECIFICATIONS:
website: http://www.fdot.gov/design/standardplans
Standard Plans for Road Construction and associated IRs are available at the following
Constuction and applicable Interim Revisions (IRs).
Florida Department of Transportation, FY 2024-25 Standard Plans for Road and Bridge http://www.dot.state.fl.us/programmanagement/Implemented/SpecBooks for Road and Bridge Construction at the following website:
Florida Department of Transportation, FY 2024-25 Standard Specifications
GOVERNING SIGNALIZATION SPECIFICATIONS:
https://goo.gl/maps/iDgV4EFmU5a4C1s68
Updated August 2023
Dated February 2022
Signalization Technical Special Provisions (TSP)
Collier County Traffic Operations
TRANSPORTATION ENGINEERING DIVISION
COLLIER COUNTY (03000)
COLLIER COUNTY PROJECT ID: 68056
COLLIER COUNTY
TRANSPORTATION MANAGEMENT SERVICES DEPARTMENT
SIGNALIZATION PLANS
PROJECT MANAGER:
COLLIER COUNTY
BEE THAO, P.E.
ENGINEER OF RECORD:
SIGNALIZATION PLANS
ORLANDO, FL 32801
200 S. ORANGE AVENUE, SUITE 900
JACOBS ENGINEERING GROUP INC.
P.E. NO.: 90828
MD IMRAN SHAH, P.E.
PLANS
INTERSECTION IMPROVEMENT
CITY GATE BOULEVARD NORTH
COLLIER BOULEVARD (C.R. 951)
T-13 MAST ARM LIGHTING DATA TABLE
T-12 STANDARD MAST ARM DATA TABLE
T-11 MAST ARM TABULATION
T-10 SPLICE DIAGRAM
T-9 ACCESSIBLE PEDESTRIAN SIGNAL (APS) DETAILS
T-8 FO TRIVIEW MARKER DETAIL
T-7 GUIDE SIGN WORKSHEET
T-5 - T-6 SIGNALIZATION PLANS
T-4 GENERAL NOTES
T-3 TABULATION OF QUANTITIES
T-2 SIGNATURE SHEET
T-1 KEY SHEET
NOVEMBER 2024
BID PLANS
P.E. LICENSE NUMBER 90828
TEL. (407) 903-5295
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
11/1/2024 9:48:42 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\SIGNSG01.DGN
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
TRANSPORTATION MANAGEMENT SERVICES DEPARTMENT
TRANSPORTATION ENGINEERING DIVISION
NO.
SHEET
68056 COLLIER
CR 951
AMANKWK
SHEET DESCRIPTIONSHEET NO.
FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004, F.A.C.
THE ABOVE NAMED PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR THE
ON ANY ELECTRONIC COPIES.
AND THE SIGNATURE MUST BE VERIFIED
NOT CONSIDERED SIGNED AND SEALED
PRINTED COPIES OF THIS DOCUMENT ARE
ON THE DATE ADJACENT TO THE SEAL.
SIGNED AND SEALED BY
THIS ITEM HAS BEEN DIGITALLY
STATE OF
No 90828
R E
E
NI
G
NE LANOI
S S
E
F O
R P
ESNECI
L
A
DIROL
F
H
AHS
NARMI
D
M
MD IMRAN SHAH, P.E. NO. 90828
TEL. (407) 903-5295
ORLANDO, FL 32801
200 S. ORANGE AVENUE, SUITE 900
JACOBS ENGINEERING GROUP, INC.
T-2
SIGNATURE SHEET
SHEET DESCRIPTIONSHEET NO.
FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004, F.A.C.
THE ABOVE NAMED PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR THE
ON ANY ELECTRONIC COPIES.
AND THE SIGNATURE MUST BE VERIFIED
NOT CONSIDERED SIGNED AND SEALED
PRINTED COPIES OF THIS DOCUMENT ARE
ON THE DATE ADJACENT TO THE SEAL.
SIGNED AND SEALED BY
THIS ITEM HAS BEEN DIGITALLY
STATE OF
No 59474
R E
E
NI
G
NE LANOI
S S
E
F O
R P
ESNECI
L
A
DIROL
F
ATI
KAR .K TTE
B
T-11 MAST ARM TABULATION
T-10 SPLICE DIAGRAM
T-9 ACCESSIBLE PEDESTRIAN SIGNAL (APS) DETAILS
T-8 FO TRIVIEW MARKER DETAIL
T-7 GUIDE SIGN WORKSHEET
T-5 - T-6 SIGNALIZATION PLANS
T-4 GENERAL NOTES
T-3 TABULATION OF QUANTITIES
T-2 SIGNATURE SHEET
T-1 KEY SHEET
T-12 STANDARD MAST ARM DATA TABLE
T-2 SIGNATURE SHEET
BRETT K. RAKITA, P.E. NO. 59474
TEL. (813) 676-2296
NAPLES, FL 34108
5811 PELICAN BAY BLVD., SUITE 305
JACOBS ENGINEERING GROUP, INC.
SHEET DESCRIPTIONSHEET NO.
FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004, F.A.C.
THE ABOVE NAMED PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR THE
ON ANY ELECTRONIC COPIES.
AND THE SIGNATURE MUST BE VERIFIED
NOT CONSIDERED SIGNED AND SEALED
PRINTED COPIES OF THIS DOCUMENT ARE
ON THE DATE ADJACENT TO THE SEAL.
SIGNED AND SEALED BY
THIS ITEM HAS BEEN DIGITALLY
T-13 MAST ARM LIGHTING DATA TABLE
T-2 SIGNATURE SHEET
STATE OF
No 66457
R E
E
NI
G
NE LANOI
S S
E
F O
R P
ESNECI
L
A
DIROL
F
R E
S
AL
G ENNA A
R
U
A L
LAURA ANNE GLASER, P.E. NO. 66457
TEL. (239) 596-1715
NAPLES, FL 34108
5811 PELICAN BAY BLVD., SUITE 305
JACOBS ENGINEERING GROUP, INC.
T-3
TABULATION OF QUANTITIES
TABULATION OF QUANTITIES
NO.
ITEM
PAY
DESCRIPTION UNIT
SHEET NUMBERS
SHEET
TOTAL THIS
TOTAL
GRAND
T-5 T-6
PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL
630-2-11 CONDUIT, FURNISH & INSTALL, OPEN TRENCH LF 200 40 240 240
630-2-12 CONDUIT, FURNISH & INSTALL, DIRECTIONAL BORE LF 335 20 355 355
632-7-1 SIGNAL CABLE, NEW OR RECONSTRUCTED INTERSECTION, F&I PI 1 1 1
633-1-122 FIBER OPTIC CABLE, F&I, UNDERGROUND,13-148 FIBERS LF 120 120 120
633-2-31 FIBER OPTIC CONNECTION, INSTALL, SPLICE EA 4 4 4
633-3-11 FIBER OPTIC CONNECTION HARDWARE, F&I, SPLICE ENCLOSURE EA 1 1 1
633-3-12 FIBER OPTIC CONNECTION HARDWARE, F&I, SPLICE TRAY EA 1 1 1
633-3-15 FIBER OPTIC CONNECTION HARDWARE, F&I, PRETERMINATED PATCH PANEL EA 1 1 1
635-2-13 PULL & SPLICE BOX, F&I, 30" X 60" RECTANGULAR OR 36" ROUND COVER SIZE EA 1 1 1
635-2-14 PULL & SPLICE BOX, F&I, 17"x30" COVER SIZE (TYPE B) EA 13 13 13
639-1-122 ELECTRICAL POWER SERVICE, F&I, UNDERGROUND, METER PURCHASED BY CONTRACTOR AS 1 1 1
639-2-1 ELECTRICAL SERVICE WIRE, FURNISH & INSTALL LF 50 20 70 70
639-3-11 ELECTRICAL SERVICE DISCONNECT, F&I, POLE MOUNT EA 1 1 1
641-2-12 PRESTRESSED CONCRETE POLE, F&I, TYPE P-II SERVICE POLE EA 1 1 1
646-1-11 ALUMINUM SIGNALS POLE, F&I, PEDESTAL EA 4 4 4
649-21-10 STEEL MAST ARM ASSEMBLY, FURNISH AND INSTALL, SINGLE ARM 60' EA 2 2 2
649-21-15 STEEL MAST ARM ASSEMBLY, FURNISH AND INSTALL, SINGLE ARM 70' EA 1 1 1
649-21-21 STEEL MAST ARM ASSEMBLY, FURNISH AND INSTALL, SINGLE ARM 78' EA 1 1 1
650-1-14 VEHICULAR TRAFFIC SIGNAL, FURNISH & INSTALL ALUMINUM, 3 SECTION, 1 WAY AS 22 22 22
653-1-11 PEDESTRIAN SIGNAL, FURNISH & INSTALL LED COUNTDOWN, 1 WAY AS 4 4 4
660-3-11 VEHICLE DETECTION SYSTEM- MICROWAVE, FURNISH & INSTALL CABINET EQUIPMENT EA 1 1 1
660-3-12 VEHICLE DETECTION SYSTEM- MICROWAVE, FURNISH & INSTALL, ABOVE GROUND EQUIPMENT EA 4 4 4
663-1-111 SIGNAL PRIORITY AND PREEMPTION SYSTEM, F&I, OPTICAL, CABINET ELECTRONICS EA 1 1 1
663-1-112 SIGNAL PRIORITY AND PREEMPTION SYSTEM, F&I, OPTICAL, DETECTOR EA 4 4 4
665-1-12 PEDESTRIAN DETECTOR, FURNISH & INSTALL, ACCESSIBLE EA 4 4 4
670-5-111 TRAFFIC CONTROLLER ASSEMBLY, F&I, NEMA, 1 PREEMPTION AS 1 1 1
682-1-133 ITS CCTV CAMERA, F&I, DOME ENCLOSURE - NON-PRESSURIZED, IP, HIGH DEFINITION EA 2 2 2
684-1-1 MANAGED FIELD ETHERNET SWITCH, F&I EA 1 1 1
685-1-13 UNINTERRUPTIBLE POWER SUPPLY, FURNISH AND INSTALL, LINE INTERACTIVE WITH CABINET EA 1 1 1
685-2-1 REMOTE POWER MANAGEMENT UNIT-RPMU, F&I EA 1 1 1
700-3-201 SIGN PANEL, FURNISH & INSTALL OVERHEAD MOUNT, UP TO 12 SF EA 2 2 2
700-5-22 INTERNALLY ILLUMINATED SIGN, FURNISH & INSTALL OVERHEAD MOUNT, 12-18 SF EA 4 4 4
715-5-31 LUMINAIRE & BRACKET ARM- ALUMINUM, FURNISH & INSTALL NEW LUMINAIRE AND ARM ON NEW/EXISTING POLE EA 4 4 4
P.E. LICENSE NUMBER 90828
TEL. (407) 903-5295
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:49:00 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\TABQSG01.dgn
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
PROJECT NOTES SIGNAL LEGENDS
ABBREVIATIONS
T-4
GENERAL NOTES
R
C
(813) 275-3783
(239) 325-4105 x261
(239) 353-6047
(386) 586-6403
(561) 803-7942
(888) 632-0931 x2
(754) 221-1254
(239) 252-8260
(239) 252-5820
(239) 252-5835
(239) 252-5835
(239) 252-6134
(239) 252-6291
(239) 213-4712
(850) 599-1444
CONTACT PHONE
WB = WESTBOUND
VEH = VEHICLE
UPS = UNINTERRUPTIBLE POWER SUPPLY
TYP = TYPICAL
TMS = TRAFFIC MONITORING SITE
STA = STATION
SM = SINGLE MODE
SECT = SECTION
R/W = RIGHT OF WAY
RPMU = REMOTE POWER MANAGEMENT UNIT
RGS = RIGID GALVANISED STEEL
PED = PEDESTRIAN
MPH = MILE PER HOUR
MFES = MANAGED FIELD ETHERNET SWITCH
KVA = KILO VOLT AMPERE
HDPE = HIGH DENSITY POLY ETHYLENE
GND = GROUND
FPL = FLORIDA POWER & LIGHT
FO = FIBER OPTIC
EB = EASTBOUND
BFOC = BURIED FIBER OPTIC CABLE
BE = BURIED ELECTRIC
TECO PEOPLES GAS - FT MYERS
SUMMIT BROADBAND INC.
HOTWIRE COMMUNICATIONS
FLORIDA POWER & LIGHT - DISTRIBUTION
FLORIDA POWER & LIGHT - TRANSMISSION
CROWN CASTLE FIBER
COMCAST
COLLIER COUNTY TRAFFIC OPERATIONS (CCTO)
COLLIER COUNTY ROAD MAINTENANCE
COLLIER COUNTY PUBLIC UTILITIES (SEWER)
COLLIER COUNTY PUBLIC UTILITIES (WATER)
COLLIER COUNTY INFORMATION TECHNOLOGY (CCIT)
COLLIER COUNTY BCC ROAD MAINTENANCE (IRRIGATION)
CITY OF NAPLES- WATER
CENTURY LINK NAPLES
OWNER
JOAN DOMNING
MIKE REBER
WALTER DAVILA
MICHAEL MARTINEZ
CRAIG LEDBETTER
FIBERDIG TEAM
LEONARD MAXWELL-NEWBOLD
PAM WILSON
CHISTOPHER COVERT
ANTHONY STOLTS
ANTHONY STOLTS
MARK GILLIS
PAMELA LULICH
ALICIA ACEVEDO
BILL MCCLOUD
CONTACT PERSON
SIGNAL, MAINTENANCE, INSPECTION AND UTILITY CONTACTS:
APOLLO METRO SOLUTIONS #SL5-NW-150-L_T4
4000K, 17,900 LUMEN, 158W, TYPE 4,
STREET LIGHT MOUNTED ON SIGNAL POLE,
PROPOSED MAST ARM LUMINAIRE,
PROPOSED OVERHEAD SIGN
PROPOSED SIGNAL MAST ARM & POLE
PROPOSED SERVICE POLE
PROPOSED PEDESTRIAN POLE & DETECTOR
PROPOSED SPICE BOX
PROPOSED SIGNAL PULL BOX
PROPOSED PREEMPTION DETECTOR
PROPOSED CCTV CAMERA
PROPOSED MICROWAVE DETECTOR
PROPOSED SIGNAL HEAD (VERTICAL)
PROPOSED SIGNAL HEAD (HORIZONTAL)
PROPOSED SIGNAL CABINET
PROPOSED CONDUIT (DIRECTIONAL BORE)
PROPOSED CONDUIT (OPEN TRENCH)
COLLIER COUNTY TRAFFIC OPERATIONS FOR LATEST SPECIFICIATIONS OF HYBRID (VIDEO & RADAR) VEHICLE DETECTION SYSTEM.
RISER, CLAMP ETC.) AND POWER CABLES (14/3) FROM TRAFFIC SIGNAL CABINET TO INDIVIDUAL SENSOR UNIT. COORDINATE WITH THE PAY ITEMS FOR VEHICULAR DETECTION SYSTEM (660-3-11 & 660-3-12) INCLUDE SENSOR MOUNTING ASSEMBLIES (BRACKET,12.
USED FOR MOUNTING SIGNAL HEADS ON MAST ARMS.
THE PAY ITEM FOR VEHICULAR SIGNAL ASSEMBLIES (650-1-14) INCLUDES THE COST OF A HORIZONTAL ARTICULATING BRACKET 11.
IN CLOSE PROXIMITY TO THE UTILITY POLE. PAY ANY REQUIRED FEES TO THE POWER COMPANY FOR INSTALLATION.
COMPANY INVOLVES DESCENT OF THEIR POLE WITH CONDUIT AND SERVICE CONDUCTORS TO A PULL BOX SHOWN ON THE PLANS UTILITY ADJUSTMENT WORK THAT MAY BE ASSESSED BY THE POWER COMPANY. THE WORK TO BE ACCOMPLISHED BY THE POWER THE PAY ITEM FOR UNDERGROUND ELECTRICAL POWER SERVICE (639-1-122) INCLUDES ANY COST FOR THE OVERHEAD-TO-UNDERGROUND10.
POWER EACH VEHICLE DETECTION SENSOR UNIT FROM TRAFFIC SIGNAL CABINET.
PEDESTRIAN SIGNALS, ILLUMINATED SIGNS AND MAST ARM LUMINAIRES. IT ALSO INCLUDES CABLES (14/3) REQUIRED TO THE PAY ITEM FOR SIGNAL CABLE (632-7-1) INCLUDES ALL CABLES AND CONDUCTORS NEEDED FOR FULLY FUNCTIONAL 9.
SUBMIT FOR FINAL APPROVAL ALONG WITH OTHER EQUIPMENT SUBMITTALS REQUIRED FOR THIS PROJECT.
SECURELY ATTACHED TO EACH CABLE. ENSURE THE TAGGING SYSTEM IS IN ACCORDANCE WITH THE MAINTAINING AGENCY AND NEATLY BUNDLE AND CLEARLY IDENTIFY ALL FIELD WIRING WITH PERMANENT LEGIBLE, WEATHERPROOF TAGS THAT ARE8.
4 FEET WIDTH OF SIDEWALK IS ADJACENT TO ALL PED BUTTONS FOR PEDESTRIAN ACCESS.
PLACE SIGNAL CABLE, POWER AND DETECTOR WIRES IN SEPARATE PULL BOXES AND CONDUIT RUNS. ENSURE THAT MINIMUM 7.
THE REQUIREMENTS SPECIFIED IN THE CONTRACT, SPECIFICATIONS AND CONTRACT PLANS.
OF THE MAINTAINING AGENCY. THE CONTRACTOR IS RESPONSIBLE FOR INSURING THAT THE PROPOSED SIGNAL EQUIPEMENT MEETS APPROVAL OF SHOP DRAWINGS DOES NOT CONSTITUTE A WARRANTY THAT THE SIGNAL EQUIPMENT COMPILES WITH THE STANDARDS6.
ENSURE THE BOTTOM OF THE VERTICAL SIGNAL HEAD (ATTACHED TO MAST ARM POLE) IS 15 FEET ABOVE THE ROADWAY SURFACE.
MOUNT HORIZONTAL SIGNAL HEADS AT APPROXIMATELY THE SAME ELEVATION AS THE HORIZONTAL MAST ARM MEMBER.5.
MATERIALS WHEN THE INSTALLATION OF THE NEW SIGNAL EQUIPMENT IS COMPLETE.
INSPECTOR TWO COMPLETE SETS OF AS-BUILT PLANS. CONTACT THE MAINTAINING AGENCY TO ACCEPT DELIVERY OF AT THE TIME OF FINAL PROJECT INSPECTION, FURNISH COLLIER COUNTY ONE COMPLETE SET OF AS-BUILT PLANS AND THE4.
APOLLO METRO SOLUTIONS #SL5-NW-150-L_T4
DISTRIBUTION WITH 15' ARM AND 35’ MOUNTING HEIGHT,
a. LUMINAIRE, STREET LIGHT, 4000K, 17,900 LUMEN, 158W, TYPE 4, APPLIES TO ALL MATERIALS PROPOSED FOR THE PROJECT AND SPECIFICALLY INCLUDES:
PROJECT MANAGER, TRAFFIC OPERATIONS DEPARTMENT & TRANSPORTATION ENGINEERING DIVISION. THIS REQUIREMENT PRIOR TO ORDERING ANY EQUIPMENT, SUBMIT SPECIFICATIONS AND DESIGN DATA FOR APPROVAL BY COLLIER COUNTY 3.
THE MAINTAINING AGENCY FOR THE SIGNAL IS COLLIER COUNTY & RESPONSIBLE FOR POWER BILL.2.
provisions-and-supplemental-terms-and-conditions https://www.colliercountyfl.gov/government/growth-management/divisions/traffic-operations/traffic-technical-special- TRAFFIC OPERATIONS. THE TSP AND SUPPLEMENTAL TERMS & CONDITIONS CAN BE FOUND AT THE FOLLOWING LINK:
SIGNALIZATION TECHNICAL SPECIAL PROVISIONS (TSP-1 to TSP-48; UPDATED AUGUST 2023 VERSION) FROM COLLIER COUNTY RESPONSIBILITIES & DAMAGE ASSESSMENT FOR TRAFFIC SIGNAL CONSTRUCTION. REVIEW AND CONSTRUCT ACCORDING TO PROPERLY FOLLOW COLLIER COUNTY TRAFFIC OPERATIONS (CCTO) SUPPLEMENTAL TERMS AND CONDITIONS OF CONTRACTOR1.
P.E. LICENSE NUMBER 90828
TEL. (407) 903-5295
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:49:18 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\GNNTSG01.dgn
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
STOP
.8
.4
8 8 3 3
47 7
3 5 7
700-5-22
SIGN DETAILS
630-2-12
10 40
Feet
140 LF
175 LF
SIGNAL HEAD DETAILS
2 EA
2'X8'
CB-MA-01
2 EA
2'X9'
CB-MA-02
700-5-22
6 8 1
M P
G
V
B
A
B
CA
BA
CA
660-3-12 1 EA
1 EA
682-1-133
DZ-2A DZ-2B
DZ-6B DZ-6A
DETECTOR
PRE-EMPTION
663-1-112 4 EA (TOTAL)
COLLIER BLVD & CITY GATE BLVD N
PUSH BUTTON
FOR
D
FOR
PUSH BUTTON
C
2 EA
12"X9"
R10-03L
2 EA
12"X9"
R10-03R
PED. SIGNAL
COUNT-DOWN
1-SECT., 1-WAY
4 AS
653-1-11
P4 P6
P6
P6
C
D
198' 166'
P4
P4
D
C
7 AS
Y GR
3-SECT., 1-WAY
650-1-14
3-SECT., 1-WAY
11 AS
R Y G
650-1-14
3 5 71
3-SECT., 1-WAY
4 AS
R
Y
G
650-1-14
E *
630-2-11 150 LFCA
2 4
ONLY
F
F
1 EA
36"X24"
FTP-82-08
1 EA
36"X36" R03-01
(45 MPH)
COLLIER BLVD NB
(45 MPH)
COLLIER BLVD SB
PROP. R/W
PROP. R/W
CB
639-2-1
630-2-11 50 LF
50 LF
1-2" HDPE
2#6, 1#6 GND
700-3-201 700-3-201
FOC TO REMAIN
EXISTING 48 SM
SPECS 650-3.10.
ACCORDING TO FDOT STANDARDS
SIGNAL HEADS FOR FUTURE USE
CONCEAL ALL EB VEHICULAR
20 LF
C
O N
S
H E
R S
F U
T U
A H
W
Y
5' (TYP)
166' 198'
FOC TO REMAIN
EXISTING 48 SM
COUNTY ENGINEER
FIELD ADJUSTING AS DIRECTED BY THE
DELAY TIME IS INITIAL AND MAY REQUIRE
POLE ID. 2
POLE ID. 3
STA. 1449+19.52, 93.73' LT
EXISTING FP&L SERVICE POLE
PURPOSES AND NOT TO BE INSTALLED AT THIS TIME.
* FUTURE SIGNAL HEAD SHOWN SOLELY FOR STRUCTURAL ANALYSIS
NOTE:
POLE ID. 4
¡ CONST. COLLIER BLVD
HEAD FOR FUTURE USE.
CONCEAL WB THROUGH SIGNAL
POLE ID. 1
LUMINAIRE SL-1
LUMINAIRE SL-2
LUMINAIRE SL-3
LUMINAIRE SL-4
EXISTING LIGHT POLE TO REMAIN
CCTV 'A'
CCTV 'B'
682-1-133
FOR CCTV 'B'
CABINET ON MAST ARM POLE
INSTALL ETHERNET EXTENDER
DZ-1
DZ-5A
DZ-5B
Z
A
D Z
B
D Z
HYBRID DETECTOR (R2)
HYBRID DETECTOR (R8)
HYBRID DETECTOR (R4)
WITH ROADSIDE UNIT (RSU)
HYBRID DETECTOR (R6)
6'X40'(TYPICAL)
PRESENCE DETECTION
6'X6'(TYPICAL)
ADVANCE DETECTION
HV SPARE, LV SPARE.
VEH DETECTOR POWER/LIGHTING/ILLUMINATED SIGNS,
CB: 5 RUNS: VEH SIGNAL, VEH DETECTOR/PREEMPT/CCTV COMM,
LIGHTING/ILLUMINATED SIGNS, HV SPARE, LV SPARE.
DETECTOR/PREEMPT/CCTV COMM, VEH DETECTOR POWER/
CA: 7 RUNS: VEH SIGNAL, PED SIGNAL, PED DETECTOR, VEH
CONDUIT RUN LEGEND:
DETECTOR CHART
ID.
DETECTOR
ZONE
DETECTION
TYPE
& DET
ZONE SIZE
MOVEMENT
TO
CONNECTED
(SEC)
DELAY
R2
DZ-2A, DZ-2B
ADVANCE
6'x6'
(PHASE 2)
SB THROUGH
DZ-5A, DZ-5B
PRESENCE
6'x40'
(PHASE 5)
SB LEFT
R6
DZ-6A, DZ-6B
ADVANCE
6'x6'
(PHASE 6)
NB THROUGH
DZ-1
PRESENCE
6'x40'
(PHASE 1)
NB U TURN
R4
DZ-7A, DZ-7B
PRESENCE
6'x40'
(PHASE 7)
WB LEFT
DZ-4
PRESENCE
6'x40'
(PHASE 4)
WB RIGHT
R8 (FUTURE NOAH'S WAY)
R
R
C
R
R
C
P.E. LICENSE NUMBER 90828
TEL. (407) 903-5295
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:49:45 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\PLANSG01.dgn
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
SIGNALIZATION PLAN (1)
T-5
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:49:58 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\PLANSG01A.dgn
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
639-2-1
STOP
.8
.4
14501
8 8 3 3
47 7
P6
P6
198'
P4
P4
5' (TYP)
R
R
C
R
R
C
T-6
COLLIER BLVD @ CITY GATE BLVD N
4 3
SIGNALIZATION PLAN (2)
635-2-14
639-2-1
639-3-11
641-2-12
685-1-13
632-7-1
630-2-11
639-1-122
670-5-111
10 LF
1 PI
1 AS
1 EA
1 EA
1 AS
1 EA
635-2-14 3 EA
1 EA649-21-10
1 EA
630-2-11 10 LF
646-1-11
1 EA665-1-12
1 EA
630-2-12 20 LF
646-1-11
1 EA665-1-12
1 EA
630-2-11 10 LF
646-1-11
1 EA665-1-12
1 EA
630-2-11 10 LF
646-1-11
1 EA665-1-12
1 EA660-3-11
CONTROLLER TIMINGS
COORDINATE WITH COLLIER COUNTY TRAFFIC OPERATIONS FOR FINAL
CONTROLLER TIMINGS ARE INITIAL AND MAY REQUIRE FIELD ADJUSTMENT.
635-2-14 3 EA
1 EA649-21-15
STA. 1448+71.17, 94.94' LT
PROPOSED SIGNAL CABINET
4 EA
1 EA663-1-111
633-2-31 4 EA
633-1-122 100 LF
635-2-13 1 EA
633-3-11
633-3-12 1 EA
1 EA
48 SM FOC (SLACK)
SPLICE TRAY
SPLICE ENCLOSURE
SPLICES
633-3-15 1 EA
633-1-122 20 LF48 SM FOC (SLACK)
PRETERM PATCH PANEL
684-1-1 1 EAMFES
685-2-1 1 EA
RPMU
0 10
Feet
N
0 10
Feet
N
0 10
Feet
N
0 10
Feet
EL 14.98 3
EL 14.75 4
ARM LENGTH: 60'
STA. 1449+00.56, 72.30' RT
POLE LOCATION=
3. FLASHING OPERATIONS: RED FOR ALL MOVEMENTS.
CITY GATE BLVD N IS 30 MPH.
2. THE POSTED SPEED LIMITS ON COLLIER BLVD IS 45 MPH, ON
MINOR STREET: CITY GATE BLVD N (MOVEMENTS 4 AND 7).
1. MAJOR STREET: COLLIER BLVD (MOVEMENTS 1, 2, 5 AND 6)
NOTES:
ARM LENGTH: 70'
STA. 1450+40.95, 58.17' RT
POLE LOCATION=
635-2-14 3 EA
1 EA649-21-10
EL 15.25 2
ARM LENGTH: 60'
STA. 1450+25.40, 88.58' LT
POLE LOCATION=
EL 14.82 1
ARM LENGTH: 78'
STA. 1448+83.61, 84.38' LT
POLE LOCATION=
649-21-21
STA. 1449+05.00, 73.23' RT
PED POLE
STA. 1450+34.18, 88.34' LT
STA. 1450+36.95, 57.88' RT
STA. 1450+24.54, 68.41' RT
or
PHASE 1
PHASE 2
PHASE 3 PHASE 4
PHASE 2
7 4
SPECIAL S.O.P.
P6
P6
P4
20 LF
SPLICE BOX
1 EA715-5-31
1 EA715-5-31
1 EA715-5-31
1 EA715-5-31
CONTROLLER TIMINGS
TIMING FUNCTION
MOVEMENT NUMBER 1 2 3 4 5 6 7 8
T I
M I N
G
F
U N
C T I O
N
MINIMUM GREEN 7 15 7 7 15 7
EXTENSION 3.0 3.0 3.0 3.0 3.0 3.0
MAXIMUM GREEN 1 25 60 25 25 60 25
MAXIMUM GREEN 2
YELLOW CLEARANCE 4.8 4.8 3.7 4.8 4.8 3.7
ALL RED 5.5 2.6 6.0 5.5 2.6 6.0
PEDESTRAIN WALK 7 7
PED. CLEARANCE 36 32
RECALL Min. Min.
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:50:11 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\GSWKSG01.dgn
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
SYMBOL(S) X Y WID HTANGLE
SIGN NAME STATION(S)
WIDTH
HEIGHT
PANEL
LEGEND
COLOR
RADII
WIDTH
BORDER
COLOR
NUMBER
SIGN
QTY
CLEARANCE COLUMN SIZE AVERAGE
LENGTH
Edge Of Lane
OF POSTS
FIXTURE SPACINGNO. OF LIGHT FIXTURES
PHOTOMETRIC CURVE
WATT
VOLTAGE
SPACE
SPACE
COPY
SPACE
COPY
SPACE
COPY
COPY
SPACE
COPY
COPY
COPY
SPACE
SPACE
COPY
SPACE
COPY
SPACE
COPY
SPACE
COPY
COPY
SPACE
SPACE
COPY
SPACE
COPY
SPACE
COPY
SPACE
COPY
SPACE
SPACE
COPY
SPACE
COPY
SPACE
SPACE
COPY
SPACE
COPY
SPACE
COPY
COPY
SPACE
COPY
COPY
COPY
SPACE
SPACE
COPY
SPACE
COPY
SPACE
COPY
SPACE
COPY
COPY
SPACE
SPACE
COPY
SPACE
COPY
SPACE
COPY
SPACE
COPY
SPACE
SPACE
COPY
SPACE
COPY
SYMBOL(S) X Y WID HTANGLE
SIGN NAME STATION(S)
WIDTH
HEIGHT
PANEL
LEGEND
COLOR
RADII
WIDTH
BORDER
COLOR
QTY
CLEARANCE COLUMN SIZE AVERAGE
LENGTH
Edge Of Lane
OF POSTS
FIXTURE SPACINGNO. OF LIGHT FIXTURES
PHOTOMETRIC CURVE
WATT
VOLTAGE
9.65" 76.7" 9.65"
8'-0"
7"
10"EM
7"
6"
6"EM
12"2
BORDER
R=1.5"
TH=1"
5.95" 96.1" 5.95"
9'-0"
7"
10"E
7"
7"
10"E
7"
6" 6"E
12"
7"
10"E
7"2
BORDER
R=1.5"
TH=1"
CB-MA-01 2
8'-0" 1"
2'-0" 1.5"
White White
Green
67.1
B
6.5 l
2.9 v
5.8 d
4 9.6
L
19.3
9.6
C o
9.9 l l i
5.1 e
9.7 r
5 34.7
L
51.7
CB-MA-02 2
9'-0" 1"
2'-0" 1.5"
White White
Green
B
5.8 l
1.7 v
4.7 d
3.7 21
L
C i
2.8 t
4.9 y
7.7 6.3
G
9.6 a t
5.3 e
6.2 42.3
L
59.7
93.9
N
8.1 6
L
8.1
T-7
GUIDE SIGN WORKSHEET
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:50:32 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\SSDTSG01.DGN
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
FRONT VIEW
W A R N I N G
F
I
B
T
I
C
C A B L E
AND
1-800-432-2770
ONE CALL
SUNSHINE
239-252-2583
UTILITIES
COLLIER COUNTY
FIBER OPTIC ROUTE MARKER DETAIL
N.T.S.
TOP COVER DETAIL
IN THIS AREA CALL
BEFORE DIGGING
T-8
FO TRIVIEW MARKER DETAIL
R N I N G
F
I
B
T
I
C
C A B L E
AND
1-800-432-2770
ONE CALL
SUNSHINE
239-252-2583
UTILITIES
COLLIER COUNTY
IN THIS AREA CALL
BEFORE DIGGING
COLLIER COUNTY UTILITIES, 239-252-2583
INFORMATION SHALL BE SHOWN:
PROVIDED ON EACH ROUTE MARKER, THE FOLLOWING CONTACT
IN ADDITION TO THE SUNSHINE ONE CALL NUMBER (800-432-4770)3.
RECOMMENDATIONS.
ENSURE POST EMBEDMENT AND ANCHORING CONFORM TO MANUFACTURER'S
WITH LOCATE WIRE AND GROUND CONNECTORS (ELECTRONIC ROUTE MARKER).
INSTALL TRIVIEW MARKERS CONTAINING A TERMINAL BOARD EQUIPPED2.
SPECIAL PROVISIONS (TSP-40 TO TSP-47; DATED: AUGUST 2023)
LOCATIONS ACCORDING TO COLLIER COUNTY FIBER OPTIC TECHNICAL
INSTALL FIBER OPTIC TRIVIEW MARKERS ON ALL FIBER OPTIC PULL BOX1.
NOTES:
TEXT & WHITE BACKGROUND
THREE SIDES WITH BLACK
TRIVIEW MARKER PRINTED ON
WALL THICKNESS 0.125"
ORANGE TUBULAR POST WITH
FINISHED GRADE
WITH BLACK BACKGORUND
'WARNING' IN ORANGE TEXT
BLACK TOP COVER
2' MIN
6' MIN
MIN
"8
" MIN.
18"
SEE TOP COVER DETAIL
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:50:32 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\SSDTSG01.DGN
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
6. ALL CONDUIT TERMINATIONS SHALL HAVE BELL ENDS.
5. GROUND WIRE SHALL BE #6 STRANDED.
GROUNDING NETWORK.
SHALL BE BONDED TOGETHER TO FORM AN INTERSECTION
4. ALL SEPERATELY GROUNDED ELEMENTS AT AN INTERSECTION
COUNTDOWN, FULL HAND, AND FULL MAN TYPE.
3. PEDESTRIAN SIGNAL INDICATIONS SHALL BE L.E.D.,
FOR PEDESTRIAN DETECTION AS NEEDED.
2. PULL BOX NUMBER 2 (TYPE "B") SHALL CONTAIN CABLES
FOR PEDESTRIAN SIGNAL INDICATIONS.
1. PULL BOX NUMBER 1 (TYPE "B") SHALL CONTAIN CABLES
CONSTRUCTION NOTES:
(PELCO PRODUCTS, INC OR APPROVED EQUIVALENT)
SINGLE-STUD, IF REQUIRED.
ALUMINUM, 2-WAY,SIGNAL MOUNT, UPPER BRACKET
2-WAY AS REQUIRED.OR
COUNTDOWN, FULL HAND AND FULL MAN TYPE. 1-WAY
PEDESTRIAN, ALUMINUM SIGNAL INDICATION, L.E.D.
(PELCO PRODUCTS, INC. OR APPROVED EQUIVALENT)
TRI-STUD, IF REQUIRED.
ALUMINUM, 2-WAY,SIGNAL MOUNT, LOWER BRACKET
OR APPROVED EQUIVALENT)
(PELCO PRODUCTS, INC.SLIP FITTER, TRI-STUD
APPROVED EQUIVALENT)
.237 INCH WALL )PELCO PRODUCTS INC. PB-5100 OR
INCH O.D.X2
1POLE, SPUN ALUMINUM SCHEDULE 40, 4
SIGN
ACTUATED SIGNAL
R10-3 PEDESTRIAN
INC. PB-5325 OR APPROVED EQUIVALENT)
COLLAR, ALUMINUM (PELCO PRODUCTS,
PB-5335 OR APPROVED EQUIVALENT) PRODUCTS INC.
ALUMINUM DOOR AND GROUNDING LUG. (PELCO
ALUMINUM SQUARE BASE ASSEMBLY WITH
T O
FINAL GRADE
EQUIVALENT)
PB-5306 OR APPROVED
18 INCH LENGTH. (PELCO
INCH DIAMETER BY4
ANCHOR BOLT SET OF 4
NOT REQUIRED)
(FOUNDATION REINFORCING
(TYPE "1" CONCRETE)
36 INCH DEPTH.
24 INCH DIAMETER
(30" DEPTH).
40 CONDUIT
2" PVC SCHEDULE
CONTINUOUS OR ARRAY.
COPPER CLAD GROUND ROD
INCH DIAMETER8
520 LF
(30" DEPTH).
40 CONDUIT
3" PVC SCHEDULE
(TYPE "B")
PULL BOX NUMBER 2
12" APRON
(TYPE "B")
PULL BOX NUMBER 1
6" APRON 12" APRON
SIGNAL DETAIL
TYPICAL PEDESTRIAN
NOT TO SCALE
1"
FOR
PUSH BUTTON
SIGNAL (APS) PUSHBUTTON
ACCESSIBLE PEDESTRIAN
SIGNAL (APS) DETAILS
ACCESSIBLE PEDESTRIAN
MOUNTING HARDWARE.
THE THE FRAME, SIGN, ADA COMPLIANT PUSHBUTTON AND
THE PAYITEM FOR PEDESTRIAN DETECTOR SHALL INCLUDE2.
PUSHBUTTONS COMPLYING WITH CHAPTER 4K OF THE MUTCD.
ACCESSIBLE PEDESTRIAN SIGNALS AND PEDESTRIAN
PEDESTRIAN STREET CROSSINGS THEY SHALL INCLUDE
WHERE PEDESTRIAN SIGNAL HEADS ARE PROVIDED AT1.
ACCESIBLE PEDESTRIAN SIGNAL NOTES:
T-9
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:50:45 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\SPDTSG01.DGN
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
RX
TX
RX
TX
SM BLUE
AQUA
ROSE
VIOLET
YELLOW
BLACK
RED
WHITE
SLATE
BROWN
GREEN
ORANGE
BLUE
FUSION SPLICE (PROPOSED)
FUSION SPLICE (EXISTING)
CONNECTORIZED (PROPOSED)
CONNECTORIZED (EXISTING)
UNTERMINATED FIBER
SINGLE MODESM
EXISTING FIBER
PATCH PANEL
PRETERMINATED
LEGEND:
PROPOSED FIBER
SWITCH
ETHERNET
BUFFER TUBE
CCTV CCTV CAMERA
AQUA
ROSE
VIOLET
YELLOW
BLACK
RED
WHITE
SLATE
BROWN
GREEN
ORANGE
BLUE
SPLICE DIAGRAM
SM BLUE
SM GREEN
SM BROWN
SM ORANGE
SM GREEN
SM BROWN
SM ORANGE
AQUA
ROSE
VIOLET
YELLOW
BLACK
RED
WHITE
SLATE
BROWN
GREEN
ORANGE
BLUE
987654321
A Q
U A
R O
S E
V I O
L E
T Y
E L L
O W
B L
A C
K R
E D
W H I T
E S
L A
T E
B R
O W
N G
R E
E N
O R
A N
G E
B L
U E
CONTROLLER
SIGNAL
POE CABLE
CCTV
COLLIER BLVD
T-10
EXISTING 48 SM FOC
PROPOSED SPLICE ENCLOSUREFOC DROP
PROPOSED 48 SM
SM JUMPERS
FIBER PATCH PANEL
PROPOSED PRETERMINATED
SWITCH
PROPOSED ETHERNET
PROPOSED SPLICE BOX
CITY GATE BLVD N INTERSECTION
AT SW CORNER OF
SPLICE BOX & SIGNAL CABINET
CCTV
EXISTING 48 SM FOC
SM BLUE
MD IMRAN SHAH, PE
JACOBS ENGINEERING GROUP INC.
200 S. ORANGE AVENUE, SUITE. 900
ORLANDO, FLORIDA 32801
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:50:58 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\MSSGSG01.DGN
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
MAST ARM TABULATION
¡ LUMINAIRE ARM
POLE
LUMINAIRE ORIENTATION
T-11
¡ FIRST MAST ARM
ANALYSIS AND NOT TO BE INSTALLED AT THIS TIME.
1. ** ESTIMATED VALUE FOR FUTURE SIGNAL HEAD SHOWN SOLELY FOR STRUCTURAL
NOTE:
(MOUNTING HEIGHT, ANGLES ETC.)
SEE T-13 FOR LUMINARE DETAILS
SIGN ASIGN BSIGN CSIGN D
12345 W1
A
H1
B
H2
W2
C
H3
W3
D
H4
W4
TOTAL ARM LENGTH
(ARM M.H.)
HEIGHT
MOUNTING
ARM
TOP OF POLE FOUNDATION ELEVATION
CROWN ELEVATIONCROWN ELEVATION
R Y GR Y GR Y GR Y GR Y G V
¡ POLE
LUMINAIRE
(VARIES FOR EACH MAST ARM) (SEE TABLE)
L4 = LATERAL DISTANCE FROM THE POLE TO THE CCTV
DETECTOR (VARIES FOR EACH MAST ARM) (SEE TABLE)
L3 = LATERAL DISTANCE FROM THE POLE TO THE PREEMPTION
DETECTOR (VARIES FOR EACH MAST ARM) (SEE TABLE)
L1, L2 = LATERAL DISTANCE FROM THE POLE TO THE VEHICLE
R
Y
G
C L E
A R
A N
C E
L
IN
M
IN
IM
U M
.5
.0
PA
PA = POLE ATTACHED (VERTICAL HEAD)
* DENOTES NUMBER OF SECTIONS IN SIGNAL HEAD ASSEMBLY
SIGNAL DATA SIGN & DEVICE DATA
NO.
ID
NO.
SHT
BY STA.
LOCATION
ELEVATION
FOUND
TOP OF
NO.
M
AR
WY
RD
ELEV.
CROWN
Y/N
NAIRE
LUMI-
Y/N
COMP.
TERM.
V/H
SIGNAL
Y/N
PLATES
BACK
Y/N
SIGNAL
PED.
DISTANCE FROM POLE (FT)
LENGTH
ARM
TOTAL
M.H.
ARM
90/270
DUAL ARMS
BETWEEN
ANGLE DISTANCE FROM POLE / HEIGHT AND WIDTH OF SIGN (FT)
COLOR
PAINT
1 * 2 * 3 * 4 * 5 * 6 * 7 * A H1 W1 B H2 W2 C H3 W3 L1 L2 L3 L4
1 T-5, 6 1448+83.61, 84.38' LT 14.82 1 16.45 Y Y V/H Y N 13.8 3 26.8 3 38.2 3 49.7 3 64.5 3 75.0 3 PA 3 78 21.0 6.0 2 9 18.5 3 3 44 32.5 57.2 ENG IVY
2 T-5, 6 1450+25.40, 88.58' LT 15.25 1 16.50 Y Y V/H Y N 19.4 3 31.4. 3 43.4 3 56.2 3 PA 3 60 21.0 11.5 2 8 37.3 49.8 ENG IVY
3 T-5, 6 1450+40.95, 58.17' RT 14.98 1 16.18 Y Y V/H Y N 19.7 3 32.7 3 44.6 3 55.85 3 66.7 3 PA 3 70 21.0 11.5 2 9 62 3 2 38.6 26.0 50.0 ENG IVY
4 T-5, 6 1449+00.56, 72.30' RT 14.75 1 16.61 Y Y V/H Y N 17.2 3 22.2 3 33.2 3 44.2 3 55.2 3 PA 3 60 21.0 9.5 2 8 38.7 49.8 ENG IVY
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:51:11 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\MSSGSG02.DGN
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
STANDARD MAST ARM
DATA TABLE T-12
1448+83.61, 84.38' LT
1450+29.39, 88.45' LT
1450+40.95, 58.17' LT
1499+00.56, 72.30' LT
A78/S/H
A60/S
A70/S/H
A60/S
DS/16/5.0
DS/14/5.0
DS/16/5.0
DS/14/5.0
(ft.)
UB
(ft.)
UAA
POLE
STANDARD MAST ARM ASSEMBLIES DATA TABLE
(deg)
LL
(deg)
UF
SECOND ARM
(ft.)
FAA
FIRST ARM
NUMBERS
ID
STRUCTURE
Table Date 11-01-16
ID
SHAFT
DRILLED
ID
ARM
ID
ARM
DESIGNATION
ID
POLE
(ft.)
SAA
P.E. LICENSE NUMBER 59474
TEL. (813) 676-2296
BRETT K. RAKITA, P.E.
JACOBS ENGINEERING GROUP INC.
5811 PELICAN BAY BLVD., SUITE 305
NAPLES, FL 34108
section 455-15 for Structure ID number 4.
Install temporary surface casing prior to drilled shaft installation in accordance with FDOT Standard Specifications 5.
Work with Index 649-030 and 649-031.4.
that include non-standard Handhole location, paint color, terminal compartment requirement, and pedestrian features.
Work this sheet with the Signal Designer’s “Mast Arm Tabulation”. See “Mast Arm Tabulation” for special instructions 3.
and the pole height shortened from UA to UAA.
If an entry appears in column UAA, a shorter pole is required. This is obtained by removing length from the pole tip 2.
and the arm length shortened from FA to FAA. SAA Similar.
If an entry appears in column FAA, a shorter arm is required. This is obtained by removing length from the arm tip 1.
NOTES [Notes Date 11-01-18]:
P6/S/L
P4/S/L
P5/S/L
P4/S/L
UG = 35 FT.
LK = 5/16 IN.
LJ = 3/8 IN.
LB = 15 FT.
differences from Index 649-030:
All luminaires contain the following Note:
P.E. LICENSE NUMBER 66457
TEL. (239) 596-1715
LAURA A. GLASER
JACOBS ENGINEERING GROUP INC.
5811 PELICAN BAY BLVD, SUITE. 305
NAPLES, FLORIDA 34108
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
11/1/2024 9:51:24 AM c:\pw_workdir\den003\kwadwo.amankwahnkyi@jacobs.com\d1625959\PLDTLT01.dgn
ROAD NO. COUNTY
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
COUNTY PROJECT NO.
(5 FEET ABOVE THE PAVEMENT)
VERTICAL ILLUMINATION:
HORIZONTAL ILLUMINATION:
AVERAGE INITIAL INTENSITY
3.0 FOOT CANDLES (1.5 MIN.)
1.5 FOOT CANDLES (1.2 MIN.)
SIGNALIZED INTERSECTIONS
LIGHTING DESIGN CRITERIA
UNIFORMITY RATIO AVG./MIN. 4:1 OR LESS
MAX./MIN. 10:1 OR LESS
(LUMINAIRES MOUNTED ON MAST ARMS)
SIGNAL LUMINAIRE DATA
NO.
LUMINAIRE
POLE ID. STATION CENTERLINE SIDE
ARM
OR
DIST.
(DEGREES)
ARM ANGLE
LUMINAIRE
WATTAGE
LUMINAIRE
VOLTAGE
LUMINAIRE
HEIGHT
MOUNTING
INTERSECTION
SL-1 1 1448+83.61 COLLIER BLVD LT 15' 0 158 120 35 COLLIER BLVD / CITY GATE BLVD N
SL-2 2 1450+25.40 COLLIER BLVD LT 15' 0 158 120 35 COLLIER BLVD / CITY GATE BLVD N
SL-3 3 1450+40.95 COLLIER BLVD RT 15' 0 158 120 35 COLLIER BLVD / CITY GATE BLVD N
SL-4 4 1449+00.56 COLLIER BLVD RT 15' 0 158 120 35 COLLIER BLVD / CITY GATE BLVD N
T-13
MAST ARM LIGHTING
DATA TABLE