24-8243_Exhibit_M_-_Naples_Depot_Museum_Plans_Structural.pdf
PDF 985 KB Posted
- Attached to
- Naples Depot Museum Hurricane Ian Repairs
- Solicitation number
- 24-8243
- Issued by
- Collier County, Florida
About this file
This document is a structural engineering plan sheet for the Naples Depot Museum Hurricane Ian Repairs project, prepared by American Structural Engineering for Collier County, Florida. The plan sheet, identified as sheet S-1, provides detailed repair specifications for wood and metal frame structures at 1051 5th Ave S, Naples, FL 34102. The structural notes and details outline specific repair requirements for damaged walls, including guidance on frame repairs, materials, and construction techniques. The document includes wind load criteria, structural notes, and precise architectural details for wood and metal frame repair with a scale of 1/2" = 1'-0".
The structural plan sheet indicates comprehensive repair strategies for addressing hurricane damage, with specific technical specifications for frame repairs and wall reconstruction. The document is sealed and authorized by a professional engineering certification (Certificate of Authorization Number: 31149), suggesting compliance with Florida's engineering and building standards. While the plan does not explicitly detail cost or funding sources, it represents a critical component of the broader Hurricane Ian repair project for the Naples Depot Museum, which is part of Collier County's reconstruction efforts following significant storm damage.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROPERTY DESCRIPTION
1051 5TH AVE S,
NAPLES, FL 34102
A m er ic an S tr u ct u ra l
C E
R T
IF
IC
A T
E O
F A
U T
H O
R
IZ
A T
IO
N
N U
M B
E R
: 3
E n gi n ee ri n g
AutoCAD SHX Text
STRUCTURAL NOTES:
AutoCAD SHX Text
%%UGENERAL NOTES:
AutoCAD SHX Text
COORDINATION OF CONSTRUCTION INCLUDING VERIFICATION OF DIMENSIONS,
AutoCAD SHX Text
ELEVATIONS, AND FIELD CONDITIONS IS THE RESPONSIBILITY OF THE
AutoCAD SHX Text
CONTRACTOR. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION
AutoCAD SHX Text
OF THE ENGINEER PRIOR TO CONSTRUCTION. SEE ARCHITECTURAL DRAWINGS
AutoCAD SHX Text
FOR DETAILS AND DIMENSIONS NOT SHOWN.
AutoCAD SHX Text
DRAWINGS SHALL NOT BE SCALED. CONTACT THE ENGINEER OR ARCHITECT
AutoCAD SHX Text
IF CLARIFICATION OF ANY DIMENSION IS REQUIRED.
AutoCAD SHX Text
IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE PROPER
AutoCAD SHX Text
ERECTION PROCEDURES TO ENSURE THE SAFETY OF THE BUILDING AND ITS
AutoCAD SHX Text
ALL SHORING, RE-SHORING, BRACING, TIE DOWNS, ETC.
AutoCAD SHX Text
COMPONENTS DURING CONSTRUCTION; THIS INCLUDES THE INSTALLATION OF
AutoCAD SHX Text
%%UDESIGN LOADS:
AutoCAD SHX Text
FLOOR (LIVE LOAD):
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
STAIRWAYS
AutoCAD SHX Text
DECKS AND BALCONIES
AutoCAD SHX Text
CORRIDORS (MULTI-FAMILY)
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
40 PSF
AutoCAD SHX Text
40 PSF
AutoCAD SHX Text
60 PSF
AutoCAD SHX Text
80 PSF
AutoCAD SHX Text
50 PSF
AutoCAD SHX Text
ROOF:
AutoCAD SHX Text
TOP CHORD LIVE LOAD
AutoCAD SHX Text
TOP CHORD DEAD LOAD
AutoCAD SHX Text
BOTTOM CHORD LIVE LOAD
AutoCAD SHX Text
BOTTOM CHORD DEAD LOAD
AutoCAD SHX Text
ATTIC LIVE LOAD
AutoCAD SHX Text
20 PSF
AutoCAD SHX Text
20 PSF
AutoCAD SHX Text
10 PSF
AutoCAD SHX Text
5 PSF
AutoCAD SHX Text
40 PSF
AutoCAD SHX Text
POLYCARBONATE PANELS
AutoCAD SHX Text
10 PSF
AutoCAD SHX Text
LATERAL EARTH PRESSURE
AutoCAD SHX Text
45 PSF/FT
AutoCAD SHX Text
INFORMATION PERTAINING TO THE EXISTING CONDITIONS GIVEN ON THESE
AutoCAD SHX Text
STRUCTURAL DRAWINGS REPRESENTS TO THE BEST OF OUR KNOWLEDGE THE
AutoCAD SHX Text
ACTUAL EXISTING FIELD CONDITIONS. AMERICAN STRUCTURAL ENGINEERING, INC.
AutoCAD SHX Text
MAKES NO WARRANTY AS TO THEIR ACCURACY. THE CONTRACTOR SHALL
AutoCAD SHX Text
FIELD VERIFY THE EXISTING CONDITIONS IMPERATIVE TO THE NEW WORK AND
AutoCAD SHX Text
REPORT DISCREPANCIES BETWEEN THE DRAWINGS AND THE FIELD CONDITIONS
AutoCAD SHX Text
TO THE ENGINEER FOR REVIEW.
AutoCAD SHX Text
IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY FOR THE SAFETY OF THE
AutoCAD SHX Text
WORKERS DURING ALL PHASES OF CONSTRUCTION AND FOR ADHERENCE TO
AutoCAD SHX Text
ALL APPLICABLE LAWS AND REGULATIONS GOVERNING ON-SITE SAFETY
AutoCAD SHX Text
PROCEDURES.
AutoCAD SHX Text
%%UCONCRETE:
AutoCAD SHX Text
ALL CONCRETE SHALL BE PLACED IN ACCORDANCE WITH THE AMERICAN
AutoCAD SHX Text
CONCRETE INSTITUTE "BUILDING CODE REQUIREMENTS FOR STRUCTURAL
AutoCAD SHX Text
CONCRETE" (ACI-318).
AutoCAD SHX Text
THE FOLLOWING MINIMUM DESIGN STRESSES SHALL BE MET:
AutoCAD SHX Text
CAST IN PLACE CONCRETE:
AutoCAD SHX Text
FOOTINGS
AutoCAD SHX Text
COLUMNS/PILASTERS
AutoCAD SHX Text
SLAB ON GRADE
AutoCAD SHX Text
BEAMS, ELEVATED SLABS
AutoCAD SHX Text
GROUTED MASONRY CELLS, OTHER
AutoCAD SHX Text f'c =
AutoCAD SHX Text
REINFORCEMENT:
AutoCAD SHX Text
TIES, STIRRUPS
AutoCAD SHX Text
WELDED WIRE FABRIC
AutoCAD SHX Text
ALL OTHER REINFORCEMENT
AutoCAD SHX Text
3000 PSI
AutoCAD SHX Text fy =
AutoCAD SHX Text
60,000 PSI
AutoCAD SHX Text fy =
AutoCAD SHX Text
60,000 PSI
AutoCAD SHX Text fy =
AutoCAD SHX Text
60,000 PSI
AutoCAD SHX Text
THE CONCRETE STRESSES LISTED ABOVE ARE BASED ON A 28 DAY
AutoCAD SHX Text
COMPRESSIVE STRENGTH AS DETERMINED BY LABORATORY TESTING OF
AutoCAD SHX Text
CONCRETE CYLINDERS.
AutoCAD SHX Text
REINFORCING STEEL SHALL BE ASTM A615, GRADE 60 DEFORMED BARS FREE
AutoCAD SHX Text
FROM OIL, SCALE AND RUST. WELDED WIRE FABRIC SHALL BE ASTM A185
AutoCAD SHX Text
IN FLAT MANUFACTURED SHEETS.
AutoCAD SHX Text
STRUCTURAL STEEL & EMBEDS:
AutoCAD SHX Text
BOLTS, ASTM A325
AutoCAD SHX Text
STEEL PLATES, ASTM A36
AutoCAD SHX Text Fy =
AutoCAD SHX Text
36,000 PSI
AutoCAD SHX Text Fy =
AutoCAD SHX Text
36,000 PSI
AutoCAD SHX Text
CONCRETE SHALL BE PLACED AND CURED TO ACI STANDARDS AND
AutoCAD SHX Text
SPECIFICATIONS.
AutoCAD SHX Text
PROPOSED DESIGN MIXES SHALL BE PROVIDED TO THE ENGINEER OF RECORD
AutoCAD SHX Text
FOR REVIEW AND APPROVAL. DESIGN MIXES SHALL INCLUDE RECENT FIELD
AutoCAD SHX Text
CYLINDERS OR LAB TESTS. THE MAXIMUM TIME ALLOWED FROM THE TIME
AutoCAD SHX Text
THE MIXING WATER IS ADDED TO THE TIME OF PLACEMENT IN ITS FINAL
AutoCAD SHX Text
POSITION SHALL NOT EXCEED %%U90 MINUTES.%%U IF FOR ANY REASON THERE IS
AutoCAD SHX Text
A LONGER DELAY, THE CONCRETE SHALL BE DISCARDED. NO WATER SHALL
AutoCAD SHX Text
BE ADDED ON SITE.
AutoCAD SHX Text
ALL SLABS SHALL BE CURED USING A DISSIPATING CURING COMPOUND
AutoCAD SHX Text
MEETING ASTM C309, TYPE 1-D. THE COMPOUND SHALL BE PLACED
AutoCAD SHX Text
IMMEDIATELY AFTER FINISHING. CALCIUM CHLORIDES SHALL NOT BE USED.
AutoCAD SHX Text
THE CONTRACTOR SHALL CONFIRM THE COMPATIBILITY OF THE CURING
AutoCAD SHX Text
COMPOUND WITH FLOOR FINISHES.
AutoCAD SHX Text
#14 AND #18 BARS
AutoCAD SHX Text
UP THRU #11 BARS
AutoCAD SHX Text
SLABS, WALL, JOISTS.
AutoCAD SHX Text
WEATHER OR IN CONTACT WITH GROUND:
AutoCAD SHX Text
CONCRETE NOT EXPOSED TO EARTH OR
AutoCAD SHX Text
#6 THRU #18 BARS
AutoCAD SHX Text
CONCRETE EXPOSED TO EARTH OR WEATHER:
AutoCAD SHX Text
UP THRU #5 BARS
AutoCAD SHX Text
PERMANENTLY EXPOSED TO EARTH
AutoCAD SHX Text
CONCRETE CAST AGAINST EARTH AND
AutoCAD SHX Text
COLUMNS
AutoCAD SHX Text
BEAMS
AutoCAD SHX Text 1 1/2"
AutoCAD SHX Text 1 1/2"
AutoCAD SHX Text 1 1/2"
AutoCAD SHX Text 3/4"
AutoCAD SHX Text 2"
AutoCAD SHX Text 1 1/2"
AutoCAD SHX Text 3"
AutoCAD SHX Text
REINFORCING STEEL CLEAR COVER REQUIREMENTS SHALL BE AS FOLLOWS:
AutoCAD SHX Text
ALL REINFORCING BARS SHALL BE LAPPED A MINIMUM OF 48 BAR DIAMETERS
AutoCAD SHX Text
IN CONCRETE UNLESS NOTED OTHERWISE.
AutoCAD SHX Text
ALL WELDED WIRE FABRIC SHALL BE LAPPED A MINIMUM OF ONE SPACE.
AutoCAD SHX Text
WELDED WIRE FABRIC SHALL BE SUPPORTED AT A MAXIMUM OF 3 FEET
AutoCAD SHX Text
BETWEEN SUPPORTS AND SHALL BE LOCATED IN THE BOTTOM HALF OF THE
AutoCAD SHX Text
SLAB, A MINIMUM OF 1 1/2" OFF THE BOTTOM. THE VAPOR BARRIER SHALL
AutoCAD SHX Text
BE MIN. 6 MIL AND SHALL BE LAPPED 6". ALL JOINTS MUST BE TAPED.
AutoCAD SHX Text
ALL FOOTING DOWELS SHALL MATCH THE SIZE AND SPACING OF THE VERTICAL
AutoCAD SHX Text
REINFORCEMENT. TYPICAL #5 DOWELS OR VERT. BARS EMBEDDED INTO THE
AutoCAD SHX Text
CONCRETE FOUNDATION SHALL HAVE A 10"-90%%D BEND UNLESS NOTED
AutoCAD SHX Text
OTHERWISE, AND SHALL BE EMBEDDED A MINIMUM OF 7".
AutoCAD SHX Text
ALL LONGITUDINAL BARS WITHIN FOOTINGS, WALLS, SLABS, BEAMS, ETC. SHALL
AutoCAD SHX Text
BE CONTINUOUS UNLESS NOTED OTHERWISE.
AutoCAD SHX Text
ALL REINFORCING BARS SHALL BE TIED IN PLACE WITH THE PROPER COVER
AutoCAD SHX Text
PRIOR TO ANY PLACEMENT OF CONCRETE PER ACI-318. "WET STICKING" OF
AutoCAD SHX Text
THE REINFORCEMENT AFTER PLACEMENT OF THE CONCRETE WILL NOT BE
AutoCAD SHX Text
ALLOWED.
AutoCAD SHX Text
ALL STRUCTURAL CONCRETE SHALL BE CONSOLIDATED BY INTERNAL VIBRATION.
AutoCAD SHX Text
CORNER REINFORCEMENT SHALL BE PROVIDED AT ALL INTERSECTIONS OF
AutoCAD SHX Text
CONCRETE BEAMS AND FOOTINGS. BARS SHALL BE PLACED AT TOP AND
AutoCAD SHX Text
BOTTOM AND SHALL MATCH THE LARGEST TERMINATING REINFORCING BAR.
AutoCAD SHX Text f'c =
AutoCAD SHX Text
3000 PSI
AutoCAD SHX Text f'c =
AutoCAD SHX Text
3000 PSI
AutoCAD SHX Text f'c =
AutoCAD SHX Text
3000 PSI
AutoCAD SHX Text f'c =
AutoCAD SHX Text
3000 PSI
AutoCAD SHX Text
%%UWOOD:
AutoCAD SHX Text
STRUCTURAL WOOD COMPONENTS SHALL HAVE THE FOLLOWING MINIMUM
AutoCAD SHX Text
PROPERTIES AT NORMAL LOAD DURATION UNDER DRY SERVICE OF CONDITION:
AutoCAD SHX Text
THE STRUCTURAL WOOD DESIGN SHOWN ON THE DRAWINGS HAS BEEN
AutoCAD SHX Text
PERFORMED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATION
AutoCAD SHX Text
FOR WOOD CONSTRUCTION" (NDS), 2015.
AutoCAD SHX Text Fb =
AutoCAD SHX Text Fv =
AutoCAD SHX Text Fc_=
AutoCAD SHX Text E =
AutoCAD SHX Text
BEAMS/HEADERS (#2 S.Y.P.):
AutoCAD SHX Text
1100 PSI
AutoCAD SHX Text
175 PSI
AutoCAD SHX Text
480 PSI
AutoCAD SHX Text
1,400,000 PSI
AutoCAD SHX Text Fb =
AutoCAD SHX Text Fv =
AutoCAD SHX Text Fc_=
AutoCAD SHX Text E =
AutoCAD SHX Text
LVL'S:
AutoCAD SHX Text
2850 PSI
AutoCAD SHX Text
285 PSI
AutoCAD SHX Text
750 PSI
AutoCAD SHX Text
2,000,000 PSI
AutoCAD SHX Text Fb =
AutoCAD SHX Text Fc =
AutoCAD SHX Text E =
AutoCAD SHX Text
2X4 & 2X6 STUDS (#2 S.Y.P.):
AutoCAD SHX Text
1150 PSI
AutoCAD SHX Text
1500 PSI
AutoCAD SHX Text
1,400,000 PSI
AutoCAD SHX Text Fb =
AutoCAD SHX Text E =
AutoCAD SHX Text
6X6 AND LARGER POST (#2 S.Y.P.):
AutoCAD SHX Text
850 PSI
AutoCAD SHX Text
1,200,000 PSI
AutoCAD SHX Text Fc =
AutoCAD SHX Text
525 PSI
AutoCAD SHX Text
ALL STRUCTURAL LUMBER SHALL BE #2 SOUTHERN YELLOW PINE (S.Y.P.)
AutoCAD SHX Text
OR BETTER UNLESS NOTED OTHERWISE
AutoCAD SHX Text
ALL WOOD IN CONTACT WITH CONCRETE OR EARTH, OR EXPOSED TO
AutoCAD SHX Text
WEATHER SHALL BE PRESSURE TREATED (P.T.) UNLESS AN APPROVED
AutoCAD SHX Text
MOISTURE BARRIER IS PROVIDED.
AutoCAD SHX Text
ALL WOOD FRAMING WITHIN 8" OF EXPOSED EARTH SHALL BE PRESSURE
AutoCAD SHX Text
TREATED (P.T.).
AutoCAD SHX Text
THERE SHALL BE A MINIMUM OF 6" BETWEEN ANY WOOD SIDING, WALL
AutoCAD SHX Text
SHEATHING OR FRAMING MEMBERS AND EXPOSED EARTH.
AutoCAD SHX Text
PLYWOOD ROOF AND FLOOR SHEATHING SHALL BE INSTALLED WITH THE
AutoCAD SHX Text
LONG DIMENSION PERPENDICULAR TO THE FRAMING MEMBERS. JOINTS
AutoCAD SHX Text
SHALL BE STAGGERED.
AutoCAD SHX Text
SEE STRUCTURAL DETAILS ELSEWHERE FOR THE SIZE AND SPACING OF THE
AutoCAD SHX Text
REQUIRED PLYWOOD FASTENERS. ROOF SHEATHING MUST BE FASTENED
AutoCAD SHX Text WITH MINIMUM 8d RING SHANK NAILS.
AutoCAD SHX Text
ALL SAWN LUMBER SIZES NOTED ON THE STRUCTURAL DRAWINGS ARE
AutoCAD SHX Text
NOMINAL SIZES. ALL LVL SIZES NOTED ON THE DRAWINGS ARE ACTUAL
AutoCAD SHX Text
DIMENSIONS.
AutoCAD SHX Text
SCREWS.
AutoCAD SHX Text
THE BUCKING ONLY SHALL BE ATTACHED WITH STAINLESS STEEL
AutoCAD SHX Text (e.g. "TAPCONS"). ALL WINDOW AND DOOR UNITS FASTENED INTO
AutoCAD SHX Text
STAINLESS STEEL (304 OR 316) OR CERAMIC COATED MASONRY SCREWS
AutoCAD SHX Text
P.T. BUCKING SHALL BE FASTENED TO MASONRY OR CONCRETE WITH
AutoCAD SHX Text 3.
AutoCAD SHX Text
ADEQUATE BARRIER.
AutoCAD SHX Text
COATING MUST BE CERTIFIED BY THE MANUFACTURER AS AN
AutoCAD SHX Text
EXPOSURE TO MOISTURE.
AutoCAD SHX Text
SUBJECT TO WEATHERING OR WHERE THERE IS A LIKELIHOOD OF PROLONGED
AutoCAD SHX Text
LUMBER SHALL BE PROVIDED AT ALL LOCATIONS WHERE LUMBER IS
AutoCAD SHX Text C.
AutoCAD SHX Text B.
AutoCAD SHX Text
PAINT ALUMINUM WITH ALKALI RESISTANT BITUMINOUS PAINT.
AutoCAD SHX Text
PAINT ALUMINUM WITH ASPHALT PAINT.
AutoCAD SHX Text ALUMINUM FROM THE P.T. (e.g. FELT PAPER). FACTORY POWDER
AutoCAD SHX Text
A PHYSICAL BARRIER MAY BE APPLIED TO SEPARATE THE
AutoCAD SHX Text A.
AutoCAD SHX Text
BE USED WHEN FASTENING ALUMINUM TO P.T. LUMBER:
AutoCAD SHX Text 1.
AutoCAD SHX Text
ALUMINUM:
AutoCAD SHX Text
ALUMINUM SHALL NOT COME INTO CONTACT WITH PRESSURE TREATED
AutoCAD SHX Text
LUMBER. THIS APPLIES FOR ANY GRADE OF ALUMINUM (STRUCTURAL
AutoCAD SHX Text
OR NON-STRUCTURAL). ONE OF THE FOLLOWING METHODS SHALL
AutoCAD SHX Text A.
AutoCAD SHX Text
HOT DIPPED GALVANIZED.
AutoCAD SHX Text
STAINLESS STEEL (304 OR 316).
AutoCAD SHX Text
PAINTED WITH A PROTECTIVE COATING TO PROVIDE A PHYSICAL
AutoCAD SHX Text
BARRIER BETWEEN STEEL AND P.T. LUMBER.
AutoCAD SHX Text B.
AutoCAD SHX Text C.
AutoCAD SHX Text
LUMBER. STEEL SHALL BE PROTECTED WITH ONE OF THE FOLLOWING:
AutoCAD SHX Text
UNPROTECTED STEEL SHALL NOT BE USED WITH PRESSURE TREATED
AutoCAD SHX Text
STEEL:
AutoCAD SHX Text 1.
AutoCAD SHX Text
PRESSURE TREATED LUMBER.
AutoCAD SHX Text
ALL FASTENERS MUST BE LABELED AS APPROVED FOR USE WITH ACQ
AutoCAD SHX Text 2.
AutoCAD SHX Text
FOOT OF SURFACE AREA TO THE FASTENER.
AutoCAD SHX Text
EQUIVALENT METHOD OF APPLYING 1.85 OZ. OF ZINC PER SQUARE
AutoCAD SHX Text D.
AutoCAD SHX Text C.
AutoCAD SHX Text B.
AutoCAD SHX Text
"Z-MAX" (G-185) BY "SIMPSON STRONG-TIE CO., INC." OR
AutoCAD SHX Text
LUMBER).
AutoCAD SHX Text
CERAMIC COATED (COATING APPROVED FOR USE WITH ACQ
AutoCAD SHX Text
STAINLESS STEEL (304 OR 316).
AutoCAD SHX Text
HOT DIPPED GALVANIZED.
AutoCAD SHX Text A.
AutoCAD SHX Text
FOLLOWING:
AutoCAD SHX Text
PLY BEAM) OR FASTEN INTO P.T. LUMBER SHALL BE ONE OF THE
AutoCAD SHX Text ALL FASTENERS USED TO JOIN P.T. LUMBER (e.g. BUILT-UP MULTI
AutoCAD SHX Text 1.
AutoCAD SHX Text
FASTENERS:
AutoCAD SHX Text
WHEREVER PRESSURE TREATED LUMBER IS REQUIRED. PRESSURE TREATED
AutoCAD SHX Text
QUATERNARY) TREATED LUMBER. THE STRUCTURAL PLANS INDICATE "P.T."
AutoCAD SHX Text
THE FOLLOWING REQUIREMENTS APPLY TO ACQ (ALKALINE COPPER
AutoCAD SHX Text
%%UP.T. LUMBER REQUIREMENTS:
AutoCAD SHX Text CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCING WITH CONSTRUCTION. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY FIELD CONDITION WHICH MAY NOT BE IN ACCORDANCE WITH DESIGN CONDITIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE JOB SITE CONSTRUCTION SAFETY. FOR FINISHED FLOOR ELEVATIONS, SLOPES, STEPS AND RECESSES, REFER TO ARCHITECTURAL PLANS. FOR SIZE AND LOCATION OF MECHANICAL SLEEVES AND OPENINGS, REFER TO MECHANICAL AND ARCHITECTURAL PLANS.
AutoCAD SHX Text THE STRUCTURAL SYSTEMS FOR THE ATTACHED DRAWINGS WERE DESIGNED PER THE WIND LOADING PRESENTED IN SECTION 1609 OF THE FLORIDA BUILDING CODE 7th EDITION (BUILDING) AND GRAVITY LOADING PRESENTED IN SECTION R301 OF THE FLORIDA BUILDING CODE 7th EDITION (RESIDENTIAL) USING THE FOLLOWING SUPERIMPOSED LOADS:
AutoCAD SHX Text PLYWOOD SPECIFIED ON THE STRUCTURAL DRAWINGS SHALL COMPLY WITH ALL PROVISIONS OF CHAPTER 23 OF THE FLORIDA BUILDING CODE, 7th EDITION (BUILDING).
AutoCAD SHX Text
%%UANCHORS:
AutoCAD SHX Text
CHEMICAL OR EPOXY ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH
AutoCAD SHX Text
THE MANUFACTURER'S INSTRUCTIONS. HOLES SHALL BE CLEANED AND
AutoCAD SHX Text
PREPARED TO ENSURE PROPER ADHESION OF THE EPOXY. ALL EPOXY
AutoCAD SHX Text
SHALL BE SIMPSON "SET" HIGH STRENGTH EPOXY OR APPROVED STRUCTURAL
AutoCAD SHX Text
EQUIVALENT.
AutoCAD SHX Text
CONCRETE OR MASONRY ANCHORS SHALL BE EITHER:
AutoCAD SHX Text
"TITEN HD" BY SIMPSON STRONG TIE.
AutoCAD SHX Text
NO SUBSTITUTIONS SHALL BE MADE WITHOUT THE APPROVAL OF THE ENGINEER
AutoCAD SHX Text
OF RECORD. EXPANSION TYPE ANCHORS SHALL NOT BE USED WITHOUT WRITTEN
AutoCAD SHX Text
SEE PLAN FOR THE LOCATION OF MASONRY SCREWS WHERE ALLOWED
AutoCAD SHX Text
"WEDGE-BOLT" SCREW ANCHORS BY POWERS FASTENERS.
AutoCAD SHX Text A.
AutoCAD SHX Text B.
AutoCAD SHX Text
REFER TO THE PLAN AND DETAILS FOR THE SPECIFIED SIZE AND EMBEDMENT
AutoCAD SHX Text
OF THE ANCHORS.
AutoCAD SHX Text
(E.G. "TAPCONS).
AutoCAD SHX Text
PERMISSION.
AutoCAD SHX Text NOTE: THESE DETAILS APPLY TO ALL INTERIOR NON-BEARING WALLS. CONTRACTOR SHALL REPORT ANY DISCREPANCIES TO ENGINEER FOR REVIEW.
AutoCAD SHX Text NOTE: THESE DETAILS APPLY TO ALL INTERIOR NON-BEARING WALLS. CONTRACTOR SHALL REPORT ANY DISCREPANCIES TO ENGINEER FOR REVIEW.
AutoCAD SHX Text
%%P0.18 (ENCLOSED)
AutoCAD SHX Text
132 MPH
AutoCAD SHX Text B
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text
30.0 FT.
AutoCAD SHX Text
170 MPH
AutoCAD SHX Text
%%UWIND LOAD CRITERIA
AutoCAD SHX Text
WIND EXPOSURE CATEGORY
AutoCAD SHX Text
NOMINAL WIND SPEED
AutoCAD SHX Text
INTERNAL PRESSURE COEFFICIENT
AutoCAD SHX Text
RISK CATEGORY
AutoCAD SHX Text
MEAN ROOF HEIGHT
AutoCAD SHX Text
ULTIMATE WIND SPEED
AutoCAD SHX Text
EXISTING WALL CLADDING CUT LINE
AutoCAD SHX Text
EXISTING CONCRETE SLAB
AutoCAD SHX Text
EXISTING 2"X4" STUDS
AutoCAD SHX Text
EXISTING DAMAGED 2"X4" STUDS (TYP.)
AutoCAD SHX Text 2"X4" NO.2 SYP SPLICE STUD WITH ROWS 10d NAILS @ 6" O.C STAGGERED OVER LENGTH OF SPLICE.(TYP.)
AutoCAD SHX Text
PROVIDE SIMPSON SPH4 @ EACH STUD (TYP.)
AutoCAD SHX Text
EXISTING 2"X4" BASE PLATE
AutoCAD SHX Text PROVIDE NEW 2"X4" PT NO.2 SYP BASE PLATE ALONG DAMAGED AREA WITH " X 5" 14" X 5" TAPCONS AT 32" O.C
AutoCAD SHX Text PROVIDE "X 3" TAPCON AT 14"X 3" TAPCON AT FREE ENDS OF EXISTING AND REPLACED BASE PLATES
AutoCAD SHX Text
EXISTING CONCRETE SLAB
AutoCAD SHX Text PROVIDE 2"X4"X 20 GA. METAL STUD FASTENED TO EXISTING STUD WITH (2) ROWS NO.8X " 34" LONG SELF TAPPING SCREWS AT 4" O.C OVER LENGTH OF SPLICE (TYP.)
AutoCAD SHX Text
EXISTING WALL CLADDING CUT LINE
AutoCAD SHX Text
EXISTING 2"X4" METAL STUDS
AutoCAD SHX Text
EXISTING DAMAGED 2"X4" METAL STUDS (TYP.)
AutoCAD SHX Text PROVIDE NEW 1-1/2"X4"X 20 GA. BOTTOM TRACK FASTENED TO EXISTING SLAB WITH "X 3" TAPCONS AT 14"X 3" TAPCONS AT 32" O.C ALONG LENGTH OF DAMAGED AREA
AutoCAD SHX Text
FAX: 239-649-7112
AutoCAD SHX Text
PH: 239-649-1551
AutoCAD SHX Text
NAPLES, FL.
AutoCAD SHX Text
791 10TH STREET S., SUITE 302
AutoCAD SHX Text
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
TOTAL SHEETS:
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
PROJECT:
AutoCAD SHX Text
CLIENT:
AutoCAD SHX Text
CIA
AutoCAD SHX Text
CIA
AutoCAD SHX Text 09/29/23
AutoCAD SHX Text
RDA230346
AutoCAD SHX Text
PK STUDIOS
AutoCAD SHX Text
NAPLES DEPOT MUSEUM HURRICANE IAN REAPAIRS
AutoCAD SHX Text TO THE BEST OF MY KNOWLEDGE AND BELIEF THESE PLANS AND SPECIFICATIONS CONFORM TO LOCAL BUILDING CODE REQUIREMENTS. C. JOE DECRISTOFARO FLORIDA P.E. # 90796
AutoCAD SHX Text S-1
AutoCAD SHX Text
STRUCTURAL NOTES & DETAILS DETAILS
AutoCAD SHX Text
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text
WOOD FRAME REPAIR DETAIL
AutoCAD SHX Text
SCALE 1-1/2" = 1'-0"
AutoCAD SHX Text
METAL FRAME REPAIR DETAIL
AutoCAD SHX Text
SCALE 1-1/2" = 1'-0"
| Sheets and Views |
| S-1 |
| 2023-12-08T15:21:17-0500 | |
| Clement J Decristofaro:A01410C00000177F07A661A000161C7 |