This is a technical specification document for air-cooled, scroll water chillers required for HVAC repair at the DOCJT Weber Building in Richmond, Kentucky, under project designation 525-C97T-CJ16-00/CKYJWC. The specification details the complete requirements for factory-assembled and run-tested water chiller units, including compressors, evaporators, condensers with fans, electrical power systems, and integrated controls. The basis of design is Daikin brand equipment, with acceptable equivalent products from Trane, Carrier, and York. The chillers must be capable of operating in ambient temperatures ranging from 32 degrees Fahrenheit to 105 degrees Fahrenheit and must comply with multiple industry standards including AHRI 590 certification, ASHRAE 15 safety codes, ASHRAE/IES 90.1 energy efficiency requirements, ASME Boiler and Pressure Vessel Code, and UL 1995 heating and cooling equipment standards. Installation must include proper seismic qualification, vibration isolation, and field assembly by factory-trained service personnel where applicable.
The specification establishes comprehensive performance and material requirements, including R-410A refrigerant classification as Safety Group A1, brazed plate or shell-and-tube evaporators, copper tube with aluminum fin or aluminum microchannel air-cooled condenser coils, and microprocessor-based standalone controls with BACnet communication interface capability. Manufacturers must provide five-year extended warranty coverage from the date of substantial completion, including complete chiller replacement, compressor and drive assembly, refrigerant and oil charges, and parts and labor. The specification mandates factory functional testing before shipment, AHRI 550/590 performance testing at design and part-load conditions, ASME inspection and stamping of evaporators, and sound power level rating for outdoor installations per AHRI 370 procedure. Startup service must be performed by factory-authorized representatives, including comprehensive system verification, performance testing, and operator training for facility maintenance personnel.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC Repair DOCJT Weber Building Richmond, Kentucky
525-C97T-CJ16-00/CKYJWC
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 1
SECTION 23 64 23.13 - AIR-COOLED, SCROLL WATER CHILLERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes packaged, air-cooled, electric-motor-driven, scroll water chillers.
1.2 DEFINITIONS
A. BAS: Building automation system.
B. COP: Coefficient of performance. The ratio of the rate of heat removal to the rate of energy input using consistent units for any given set of rating conditions.
C. DDC: Direct digital control.
D. EER: Energy-efficiency ratio. The ratio of the cooling capacity given in Btu/h to the total power input given in watts at any given set of rating conditions.
E. GFI: Ground fault interrupt.
F. IPLV: Integrated part-load value. A single-number part-load efficiency figure of merit for a single chiller calculated per the method defined by AHRI 550/590 and referenced to AHRI standard rating conditions.
G. I/O: Input/output.
H. kW/Ton: The ratio of total power input of the chiller in kilowatts to the net refrigerating capacity in tons at any given set of rating conditions.
I. NPLV: Nonstandard part-load value. A single number part-load efficiency figure of merit for a single chiller calculated per the method defined by AHRI 550/590 and intended for operating conditions other than the AHRI standard rating conditions.
J. SCCR: Short-circuit current rating.
K. TEAO: Totally enclosed air over.
L. TENV: Totally enclosed nonventilating.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: Complete set of manufacturer's prints of water chiller assemblies, control panels, sections and elevations, and unit isolation. Include the following:
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 2
1. Assembled unit dimensions.
2. Weight and load distribution.
3. Required clearances for maintenance and operation.
4. Size and location of piping and wiring connections.
5. Diagrams for power, signal, and control wiring.
1.4 INFORMATIONAL SUBMITTALS
A. Certificates: For certification required in "Quality Assurance" Article.
B. Seismic Qualification Data: Certificates, for water chillers, accessories, and components, from manufacturers.
C. Installation instructions.
D. Source quality-control reports.
E. Startup service reports.
F. Sample warranty.
1.5 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
1.6 QUALITY ASSURANCE
A. AHRI Certification: Certify chiller according to AHRI 590 certification program.
1.7 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of water chillers that fail in materials or workmanship within specified warranty period.
1. Extended warranties include, but are not limited to, the following:
a. Complete chiller including refrigerant and oil charge.
b. Complete compressor and drive assembly including refrigerant and oil charge.
c. Refrigerant and oil charge.
1) Loss of refrigerant charge for any reason due to manufacturer's product defect and product installation.
d. Parts and labor.
2. Warranty Period: Five years from date of Substantial Completion.
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 3
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Seismic Performance: Scroll water chillers shall withstand the effects of earthquake motions determined according to ASCE/SEI 7.
1. The term "withstand" means "the unit will remain in place without separation of any parts when subjected to the seismic forces specified and the unit will be fully operational after the seismic event."
2. Component Importance Factor: 1.0.
B. Site Altitude: Chiller shall be suitable for altitude at which installed without affecting performance indicated. Make adjustments to affected chiller components to account for site altitude.
C. Performance Tolerance: Comply with the following in lieu of AHRI 550/590:
1. Allowable Capacity Tolerance: Five percent.
2. Allowable Full-Load Energy Efficiency Tolerance: Five percent.
3. Allowable Part-Load Energy Efficiency Tolerance: Five percent.
D. AHRI Rating: Rate water chiller performance according to requirements in AHRI 550/590.
E. ASHRAE Compliance: ASHRAE 15 for safety code for mechanical refrigeration.
F. ASHRAE/IES 90.1 Compliance: Applicable requirements in ASHRAE/IES 90.1, Section 6 - "Heating, Ventilating, and Air-Conditioning."
G. ASME Compliance: Fabricate and stamp water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code.
H. Comply with NFPA 70.
I. Comply with requirements of UL 1995, "Heating and Cooling Equipment," and include label by a qualified testing agency showing compliance.
J. Outdoor Installations:
1. Chiller shall be suitable for outdoor installation indicated. Provide adequate weather protection to ensure reliable service life over a 25-year period with minimal degradation due to exposure to outdoor ambient conditions.
2.2 MANUFACTURERS
A. The basis of design is Daikin brand. Equivalent products manufactured by Trane, Carrier and York are acceptable.
http://www.specagent.com/LookUp/?ulid=12115&mf=04&src=wd
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 4
2.3 MANUFACTURED UNITS
A. Description: Factory-assembled and run-tested water chiller complete with compressor(s), compressor motors and motor controllers, evaporator, condenser with fans, electrical power, controls, and indicated accessories.
B. Fabricate water chiller mounting base with reinforcement strong enough to resist water chiller movement during a seismic event when water chiller is anchored to field support structure.
2.4 CABINET
A. Base: Galvanized-steel base extending the perimeter of water chiller. Secure frame, compressors, and evaporator to base to provide a single-piece unit.
B. Frame: Rigid galvanized-steel frame secured to base and designed to support cabinet, condenser, control panel, and other chiller components not directly supported from base.
C. Casing: Galvanized steel.
D. Finish: Coat base, frame, and casing with a corrosion-resistant coating capable of withstanding a 500-hour salt-spray test according to ASTM B117.
2.5 COMPRESSOR-DRIVE ASSEMBLIES
A. Compressors:
1. Description: Positive-displacement direct drive with hermetically sealed casing.
2. Operating Speed: Nominal 3600 rpm for 60-Hz applications.
3. Capacity Control: On-off compressor cycling, plus hot-gas bypass.
a. Digital compressor unloading is an acceptable alternative to achieve capacity control.
4. Oil Lubrication System: Automatic pump with strainer, sight glass, filling connection, filter with magnetic plug or removable magnet in sump, and initial oil charge.
a. Manufacturer's other standard methods of providing positive lubrication are acceptable in lieu of an automatic pump.
5. Vibration Isolation: Mount individual compressors on vibration isolators.
a. For multiple compressor assemblies, it is acceptable to isolate each compressor assembly in lieu of each compressor.
B. Compressor Motors:
1. Hermetically sealed and cooled by refrigerant suction gas.
2. High-torque, two-pole induction type with inherent thermal-overload protection on each phase.
C. Compressor Motor Controllers:
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 5
1. Across the Line: NEMA ICS 2, Class A, full voltage, nonreversing.
2.6 REFRIGERATION
A. Refrigerant: R-410A. Classified as Safety Group A1 according to ASHRAE 34.
B. Refrigerant Compatibility: Parts exposed to refrigerants shall be fully compatible with refrigerants, and pressure components shall be rated for refrigerant pressures.
C. Refrigerant Circuit: Each circuit shall include an electronic-expansion valve, refrigerant charging connections, a hot-gas muffler, compressor suction and discharge shutoff valves, a liquid-line shutoff valve, a replaceable-core filter-dryer, a sight glass with moisture indicator, a liquid-line solenoid valve, and an insulated suction line.
D. Pressure Relief Device:
1. Comply with requirements in ASHRAE 15, ASHRAE 147, and applicable portions of ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.
2. Select and configure pressure relief devices to protect against corrosion and inadvertent release of refrigerant.
3. ASME-rated, spring-loaded, pressure relief valve; single- or multiple-reseating type.
Pressure relief valve(s) shall be provided for each heat exchanger.
2.7 EVAPORATOR
A. Brazed Plate:
1. Direct-expansion, single-pass, brazed-plate design.
2. Type 304 or 316 stainless-steel construction.
3. Code Compliance: Tested according to ASME Boiler and Pressure Vessel Code.
4. Fluid Nozzles: Terminate with mechanical-coupling end connections for connection to field piping.
5. Inlet Strainer: Factory-furnished,-mesh strainer for field installation in supply piping to evaporator. Manufacturer has option to factory install strainer.
B. Flow Switch: Factory-furnished flow switch wired to chiller operating controls.
C. Heater: Factory-installed and -wired electric heater with integral controls designed to protect the evaporator to minus 20 deg F.
D. Remote-Mounting Kit: Designed for remote field mounting where indicated. Provide kit for field installation.
2.8 AIR-COOLED CONDENSER
A. Coil(s) with integral subcooling on each circuit.
B. Copper Tube with Plate Fin Coils:
1. Construct coils of copper tubes mechanically bonded to aluminum fins.
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 6
2. Coating: None.
C. Aluminum Microchannel Coils:
1. Series of flat tubes containing a series of multiple, parallel-flow microchannels layered between refrigerant header manifolds.
2. Single- or multiple-pass arrangement.
3. Construct fins, tubes, and header manifolds of aluminum alloy treated with a corrosion-resistant coating.
D. Hail Protection: Provide condenser coils with louvers, baffles, or hoods to protect against hail damage.
E. Fans: Direct-drive propeller type with statically and dynamically balanced fan blades, arranged for vertical air discharge.
F. Fan Motors: TENV or TEAO enclosure, with sealed and permanently lubricated bearings, and having built-in overcurrent- and thermal-overload protection.
1. Overcurrent- and thermal-overload protection not integral to motor is acceptable if provided with chiller electrical power package.
G. Fan Guards: Removable steel safety guards with corrosion-resistant coating.
2.9 INSULATION
A. Factory-applied insulation over all cold surfaces of chiller capable of forming condensation.
Components shall include, but not be limited to, evaporator, evaporator water boxes including nozzles, refrigerant suction pipe from evaporator to compressor, cold surfaces of compressor, refrigerant-cooled motor, and auxiliary piping.
2.10 ELECTRICAL
A. Factory installed and wired, and functionally tested at factory before shipment.
B. Factory-installed and -wired switches, motor controllers, transformers, and other electrical devices necessary shall provide a single-point field power connection to water chiller.
C. House in a unit-mounted, NEMA 250, Type 3R enclosure with hinged access door with lock and key or padlock and key.
D. Wiring shall be numbered and color-coded to match wiring diagram.
E. Factory wiring shall be located outside of an enclosure in a metal raceway. Terminal connections shall be made with not more than a 24-inch length of liquidtight conduit.
F. Field power interface shall be to NEMA KS 1, heavy-duty, nonfused disconnect switch.
Minimum SCCR according to UL 508 shall be as required by electrical power distribution system, but not less than 65,000 A.
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 7
G. Each motor shall have branch power circuit and controls with one of the following disconnecting means having SCCR to match main disconnecting means:
1. NEMA KS 1, heavy-duty, fusible switch with rejection-type fuse clips rated for fuses.
Select and size fuses to provide Type 2 protection according to IEC 60947-4-1.
2. NEMA KS 1, heavy-duty, nonfusible switch.
3. UL 489, motor-circuit protector (circuit breaker) with field-adjustable, short-circuit trip coordinated with motor locked-rotor amperes.
H. Each motor shall have overcurrent protection.
I. Overload relay sized according to UL 1995, or an integral component of water chiller control microprocessor.
J. Phase-Failure and Undervoltage: Solid-state sensing with adjustable settings.
K. Controls Transformer: Unit-mounted transformer with primary and secondary fuses and sized with enough capacity to operate electrical load plus spare capacity.
L. Control Relays: Auxiliary and adjustable time-delay relays, or an integral to water chiller microprocessor.
M. Service Receptacle:
1. Unit-mounted, 120-V GFI duplex receptacle.
2. Power receptacle from chiller internal electrical power wiring.
N. Indicate the following for water chiller electrical power supply:
1. Current, phase to phase, for all three phases.
2. Voltage, phase to phase and phase to neutral for all three phases.
3. Three-phase real power (kilowatts).
4. Three-phase reactive power (kilovolt amperes reactive).
5. Power factor.
6. Running log of total power versus time (kilowatt hours).
7. Fault log, with time and date of each.
2.11 CONTROLS
A. Factory installed and wired, and functionally tested at factory before shipment.
B. Standalone, microprocessor based, with all memory stored in nonvolatile memory so that reprogramming is not required on loss of electrical power.
C. Enclosure: Share enclosure with electrical power devices or provide a separate enclosure of matching construction.
D. Operator Interface: Keypad or pressure-sensitive touch screen. Multiple-character, digital display. Display the following:
1. Date and time.
2. Operating or alarm status.
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 8
3. Operating hours.
4. Outside-air temperature if required for chilled-water reset.
5. Temperature and pressure of operating set points.
6. Chilled-water entering and leaving temperatures.
7. Refrigerant pressures in evaporator and condenser.
8. Saturation temperature in evaporator and condenser.
9. No cooling load condition.
10. Elapsed time meter (compressor run status).
11. Pump status.
12. Antirecycling timer status.
13. Percent of maximum motor amperage.
14. Current-limit set point.
15. Number of compressor starts.
16. Alarm history with retention of operational data before unit shutdown.
17. Superheat.
E. Control Functions:
1. Manual or automatic startup and shutdown time schedule.
2. Capacity control based on evaporator leaving-fluid temperature.
3. Capacity control compensated by rate of change of evaporator entering-fluid temperature.
4. Chilled-water entering and leaving temperatures, control set points, and motor load limit.
5. Current limit and demand limit.
6. External water chiller emergency stop.
7. Antirecycling timer.
F. Manual-Reset Safety Controls: The following conditions shall shut down water chiller and require manual reset:
1. Low evaporator pressure or high condenser pressure.
2. Low chilled-water temperature.
3. Refrigerant high pressure.
4. High or low oil pressure.
5. High oil temperature.
6. Loss of chilled-water flow.
7. Control device failure.
G. BAS System Interface: Factory-install hardware and software to enable system to monitor, control, and display chiller status and alarms.
1. Hardwired I/O Points:
a. Monitoring: On/off status, common trouble alarm electrical power demand (kilowatts) electrical power consumption (kilowatt hours).
b. Control: On/off operation, chilled-water discharge temperature set-point adjustment electrical power demand limit.
2. Communication Interface: ASHRAE 135 (BACnet), communication interface shall enable control system operator to remotely control and monitor the water chiller from an operator workstation. Control features and monitoring points displayed locally at water chiller control panel shall be available through DDC system for HVAC.
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 9
H. Factory-installed wiring outside of enclosures shall be in NFPA 70-complaint raceway. Make terminal connections with liquidtight conduit.
2.12 ACCESSORIES
A. Factory-furnished spring isolators for field installation.
1. Spring Deflection: 1 inch.
2.13 CAPACITIES AND CHARACTERISTICS
A. Refer to Schedule on Drawings.
B. Low Ambient Operation: Chiller designed for operation to 32 deg F.
C. High Ambient Operation: Chiller designed for operation to 105 deg F.
D. Evaporator:
1. Type: Brazed plate or shell and tube.
2. Fouling Factor: 0.0005 sq. ft. x h x deg F/Btu.
E. Controls Power Connection: Fed through integral transformer.
2.14 MATERIALS
A. Steel:
1. ASTM A36/A36M for carbon structural steel.
2. ASTM A568/A568M for steel sheet.
B. Stainless Steel:
1. Manufacturer's standard grade for casing.
2. Manufacturer's standard type, ASTM A240/A240M for bare steel exposed to airstream or moisture.
C. Galvanized Steel: ASTM A653/A653M.
D. Aluminum: ASTM B209.
2.15 SOURCE QUALITY CONTROL
A. Perform functional test of water chillers before shipping.
B. Factory performance test water chillers, before shipping, according to AHRI 550/590.
1. Test the following conditions:
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 10
a. Design conditions indicated.
b. AHRI 550/590 part-load points.
C. Factory test and inspect evaporator according to ASME Boiler and Pressure Vessel Code:
Section VIII, Division 1. Stamp with ASME label.
D. For water chillers located outdoors, rate sound power level according to AHRI 370 procedure.
PART 3 - EXECUTION
3.1 WATER CHILLER INSTALLATION
A. Coordinate sizes and locations of bases with actual equipment provided. Cast anchor-bolt inserts into concrete bases.
B. Coordinate sizes, locations, and anchoring attachments of structural-steel support structures with actual equipment provided.
C. Install water chillers on support structure indicated.
D. Equipment Mounting:
1. Install water chillers on cast-in-place concrete equipment bases. Comply with requirements for equipment bases and foundations specified in Section 03 30 00 "Cast-in-Place Concrete."
2. Comply with requirements for vibration isolation and seismic-control devices specified in Section 23 05 48 "Vibration and Seismic Controls for HVAC."
3. Comply with requirements for vibration isolation devices specified in Section 23 05 48.13 "Vibration Controls for HVAC."
E. Maintain manufacturer's recommended clearances for service and maintenance.
F. Maintain clearances required by governing code.
G. Chiller manufacturer's factory-trained service personnel shall charge water chiller with refrigerant if not factory charged and fill with oil if not factory installed.
H. Install separate devices furnished by manufacturer and not factory installed.
1. Chillers shipped in multiple major assemblies shall be field assembled by chiller manufacturer's factory-trained service personnel.
3.2 PIPING CONNECTIONS
A. Comply with requirements in Section 23 21 13 "Hydronic Piping" and Section 23 21 16 "Hydronic Piping Specialties." Drawings indicate general arrangement of piping, fittings, and specialties.
B. Comply with requirements in Section 23 23 00 "Refrigerant Piping." Drawings indicate general arrangement of piping, fittings, and specialties.
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 11
C. Where installing piping adjacent to chillers, allow space for service and maintenance.
D. Connect each drain connection with a drain valve, full size of drain connection.
E. Connect each chiller vent connection with an automatic vent, full size of vent connection.
3.3 ELECTRICAL POWER CONNECTIONS
A. Connect wiring according to Section 26 05 19 "Low-Voltage Electrical Power Conductors and Cables."
B. Ground equipment according to Section 26 05 26 "Grounding and Bonding for Electrical Systems."
C. Provide nameplate for each electrical connection indicating electrical equipment designation and circuit number feeding connection. Nameplate shall be laminated phenolic layers of black with engraved white letters at least 1/2 inch high. Locate nameplate where easily visible.
3.4 CONTROLS CONNECTIONS
A. Install control and electrical power wiring to field-mounted control devices.
B. Connect control wiring between chillers and other equipment to interlock operation as required to provide a complete and functioning system.
C. Connect control wiring between chiller control interface and BAS system for remote monitoring and control of chillers. Comply with requirements in Section 23 09 23 "Direct Digital Control (DDC) System for HVAC."
D. Provide nameplate on face of chiller control panel indicating control equipment designation serving chiller and the I/O point designation for each control connection. Nameplate shall be laminated phenolic layers of black with engraved white letters at least 1/2 inch high.
3.5 STARTUP SERVICE
A. Engage a factory-authorized service representative to perform startup service.
B. Inspect field-assembled components, equipment installation, and piping and electrical connections for proper assemblies, installations, and connections.
C. Complete installation and startup checks according to manufacturer's written instructions and perform the following:
1. Verify that refrigerant charge is sufficient and water chiller has been leak tested.
2. Verify that pumps are installed and functional.
3. Verify that thermometers and gages are installed.
4. Operate water chiller for run-in period.
5. Check bearing lubrication and oil levels.
6. Verify proper motor rotation.
AIR-COOLED, SCROLL WATER CHILLERS 23 64 23.13 - 12
7. Verify static deflection of vibration isolators, including deflection during water chiller startup and shutdown.
8. Verify and record performance of chilled-water flow and low-temperature interlocks.
9. Verify and record performance of water chiller protection devices.
10. Test and adjust controls and safeties. Replace damaged or malfunctioning controls and equipment.
D. Visually inspect chiller for damage before starting. Repair or replace damaged components, including insulation. Do not start chiller until damage that is detrimental to operation has been corrected.
E. Prepare a written startup report that records results of tests and inspections.
3.6 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain water chillers.
1. Instructor shall be factory trained and certified.
2. Provide not less than four hours of training.
3. Train personnel in operation and maintenance and to obtain maximum efficiency in plant operation.
4. Provide instructional videos showing general operation and maintenance that are coordinated with operation and maintenance manuals.
5. Obtain Owner sign-off that training is complete.
6. Owner training shall be held at Project site.
END OF SECTION 23 64 23.13