23214 - PCHS BP2 DISTRICT WIDE ACCESS CONTROL UPGRADES_CONSTRUCTION DOCUMENTS_2024 02 16.pdf
PDF 2 MB Posted
- Attached to
- District Wide Access Control BP#2
- Solicitation number
- RFP - PPS - 240000001311
- Issued by
- Kalamazoo County, Michigan
About this file
This document contains construction documents for Bid Package 2 of the District Wide Access Control upgrades project for Portage Public Schools in Portage, Michigan. The project involves renovations to the Central High School, including first floor demolition and new construction work. The scope includes adding access control devices and systems, upgrading the building's mechanical and electrical systems, and making interior finish upgrades. The construction documents provide details on the architectural, interior, mechanical, plumbing, and electrical work required. Bids for this project are due on February 16, 2024, and the work is expected to be completed under a single contract for the school district.
The construction documents do not provide specific pricing information, set-asides, or details on incumbents or funding sources. However, they do outline the technical requirements, construction phasing, and coordination needed between the various trades to complete the project successfully. Portage Public Schools is funding this project, but the exact budget amount is not disclosed in the documents provided.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT FOR CONSTRUCTION
PRELIM
IN
ARY
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
DESIGN TEAM
ARCHITECT/ENGINEER
CENTRAL HIGH SCHOOL - BID PACKAGE 2:
DISTRICT WIDE ACCESS CONTROL
PORTAGE PUBLIC SCHOOLS
Portage, Michigan
CONSTRUCTION DOCUMENTS
C O
V E
R S
H E
E T
-2
.1
G
F E
B R
U A
R Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P
A C
K A
G E
D
IS
T R
IC
T
W
ID
E A
C C
E S
S C
O N
T R
O L
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
PORTAGE CENTRAL HIGH SCHOOL
8135 SOUTH WESTNEDGE AVENUE
PORTAGE, MICHIGAN 49002
242 E. KALAMAZOO AVE, SUITE 100
KALAMAZOO, MICHIGAN 49007
PHONE: 269.343.6133
FAX: 269.343.6633
BUILDING: 2015 MICHIGAN BUILDING CODE AND 2012 NFPA 101 LIFE SAFETY CODE
ENERGY: 2015 MICHIGAN ENERGY CODE
PLUMBING: 2018 MICHIGAN PLUMBING CODE
MECHANICAL: 2015 MICHIGAN MECHANICAL CODE
FUEL GAS: (IFGC) 2015 INTERNATIONAL FUEL GAS CODE
ELECTRICAL: 2017 NATIONAL ELECTRICAL CODE WITH MICHIGAN AMENDMENTS
BARRIER-FREE: 2015 MICHIGAN BUILDING CODE AND 2009 ICC & C A117.1
USE GROUP: E
CONSTRUCTION TYPE: II-B
AUTOMATIC SPRINKLERS: YES
PROJECT AREA
TOTAL FINISHED PROJECT: 1,398 SQ. FT.
REFERENCED CODES
SITE ADDRESS
GENERAL
G 001 COVER SHEET
ARCHITECTURAL GENERAL
AG 001 GENERAL ARCHITECTURAL NOTES, INTERIOR PARTITION TYPES, DEVICE
ALIGNMENT GUIDELINES, & ABBREVIATIONS
ARCHITECTURAL DEMOLITION
AD 101 FIRST FLOOR DEMOLITION PLAN & REFLECTED CEILING DEMOLITION PLAN
ARCHITECTURAL
A 101 FIRST FLOOR PLAN & REFLECTED CEILING PLAN
INTERIORS GENERAL
IG 001 INTERIOR GENERAL NOTES
INTERIORS
I 101B FIRST FLOOR FINISH PLAN - UNIT B, ELEVATIONS, AND MATERIAL
SELECTION SCHEDULE
I 501 ENLARGED MILLWORK PLAN
MECHANICAL & PLUMBING GENERAL
MG 001 MECHANICAL & PLUMBING GENERAL NOTES, ABBREVIATIONS, AND
SYMBOLS
MECHANICAL
M 101 FIRST FLOOR SHEET METAL PLAN
ELECTRICAL - GENERAL
EG 001 ELECTRICAL SYMBOLS AND GENERAL NOTES
ELECTRICAL
E 101 FIRST FLOOR PLAN
DRAWING INDEX
ISSUED FOR DATE
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD BOTH SIDES;
(1 HOUR FIRE) U.L. ASSEMBLY U465
WHERE NOTED ON PLANS
METAL STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS (AT CHASE
WALLS ONLY) - UNLESS
NOTED OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD ON ROOM SIDE - BRACE
WALL @ 4'-0" O.C. MAXIMUM.
METAL STUD CHASE WALL
OR FURRING
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH
5/8" TYPE "X" GYPSUM BOARD BOTH
SIDES TO DECK
STRUCTURAL METAL STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
FLOOR CONSTRUCTION
METAL CH STUDS @ 16" O.C. WITH 5/8"
TYPE "X" GYPSUM BOARD ON ROOM
SIDE AND 1" TYPE "X" GYPSUM BOARD
PANEL ON CHASE SIDE
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH (2)
LAYERS 5/8" TYPE "X" GYPSUM
BOARD BOTH SIDES
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN ALL
WALLS - UNLESS
NOTED OTHERWISE -
WEAVE IN-BETWEEN
STUDS
FLOOR CONSTRUCTION
6" TOP AND BOTTOM TRACK WITH 3 5/8"
METAL STUD FRAMING @ 16" O.C.
(OFFSET) WITH 5/8" GYPSUM BOARD BOTH
SIDES
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
BOND BEAM
SEALANT
FLOOR CONSTRUCTION
4" CONCRETE MASONRY UNITS
CMU WALL (1 AND 2 HOUR FIRE)
U.L. ASSEMBLY - U905
HEAD
PLAN
SILL
CMU WALL WITH FURRING CMU WALL WITH FURRING BOTH SIDES
C H A S E S
ID
E
R O
O M
S
ID
E
METAL STUD CHASE WALL (1 HOUR FIRE)
U.L. ASSEMBLY U415
METAL STUD WALL (2 HOUR FIRE)
U.L. ASSEMBLY U425
METAL STUD SOUND WALL
6" CONCRETE MASONRY UNITS
8" CONCRETE MASONRY UNITS
10" CONCRETE MASONRY UNITS
STRUCTURE /
DECK ABOVE
BOND BEAM
FLOOR CONSTRUCTION
STRUCTURE /
DECK ABOVE
BOND BEAM
FLOOR CONSTRUCTION
HEAD
PLAN
SILL
4" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
6" CONCRETE MASONRY UNITS METAL FURRING
AND 5/8" GYPSUM BOARD
8" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
10" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
4" CONCRETE MASONRY UNITS WITH METAL FURRING
AND 5/8" GYPSUM BOARD - BOTH SIDES
12" CONCRETE MASONRY UNITS 12" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
1X 2X 4X 5X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
FLOOR CONSTRUCTION
METAL CH STUDS @ 16" O.C. WITH (2)
LAYERS 5/8" TYPE "X" GYPSUM BOARD
ON ROOM SIDE AND 1" TYPE "X"
GYPSUM BOARD PANEL ON CHASE SIDE
METAL STUD CHASE WALL (2 HOUR FIRE)
U.L. ASSEMBLY U438
6X 7X 8
6" CONCRETE MASONRY UNITS WITH METAL FURRING
AND 5/8" GYPSUM BOARD - BOTH SIDES
8" CONCRETE MASONRY UNITS WITH METAL FURRING
AND 5/8" GYPSUM BOARD - BOTH SIDES
10" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD - BOTH SIDES
12" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD - BOTH SIDES
9X
10X
11X
12X
13X
9XX
10XX
11XX
12XX
13XX
SEALANT SEALANT
METAL STUDS @ 16" O.C. WITH
1/2" RATED PLYWOOD ONE SIDE
AND 5/8" GYPSUM BOARD ON
BOTH SIDES.
3X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
1/2" RATED
PLYWOOD
FLOOR CONSTRUCTION
METAL STUD WALL
WITH PLYWOOD BACKING
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
WOOD STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD BOTH SIDES;
(1 HOUR FIRE) U.L. ASSEMBLY U305
WHERE NOTED ON PLANS
WOOD STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
SEALANT
SOUND BATTS IN ALL
WALLS - UNLESS
NOTED OTHERWISE
FLOOR CONSTRUCTION
WOOD STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD ON ROOM SIDE -
BRACE WALL @ 4'-0" O.C. MAXIMUM.
WOOD STUD CHASE WALL
C H A S E S
ID
E
R O
O M
S
ID
E
14X 15X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
WOOD STUDS @ 16" O.C. WITH (2)
LAYERS 5/8" TYPE "X" GYPSUM
BOARD BOTH SIDES
WOOD STUD WALL (2 HOUR FIRE)
U.L. ASSEMBLY U301
16X
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
INTERSECTION OF NON-RATED AT
1 HOUR RATED PARTITION
INTERSECTION OF NON-RATED AT 2 HOUR
RATED PARTITION - U.L. ASSEMBLY U425
1 HOUR RATED
PARTITION - REFER
TO PLAN
METAL STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
2 HOUR RATED
PARTITION -
REFER TO PLAN
METAL STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
INTERSECTION OF NON-RATED AT 2 HOUR
RATED PARTITION - U.L. ASSEMBLY U438
2 HOUR RATED
PARTITION -
REFER TO PLAN
CH STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
INTERSECTION OF
CONCRETE/MASONRY AT 1 HOUR
RATED PARTITION
CONCRETE OR MASONRY
WALL - REFER TO PLAN
1 HOUR RATED PARTITION -
REFER TO PLAN
METAL FURRING
GYPSUM BOARD CONTROL
JOINT NON-RATED PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
GYPSUM BOARD
METAL STUD FRAMING
BACKER
ROD AND
SEALANT
CONTROL JOINT
GYPSUM BOARD CONTROL
JOINT 1 HOUR RATED
PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
GYPSUM BOARD
METAL STUD FRAMING
(2) LAYERS TYPE
"X" GYPSUM
BOARD
CONTROL JOINT
GYPSUM BOARD CONTROL
JOINT 2 HOUR RATED
PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
METAL STUD FRAMING
(2) LAYERS TYPE "X"
GYPSUM BOARD
CONTROL JOINT
(2) LAYERS TYPE
"X" GYPSUM
BOARD
NOTE:
MOUNT EQUIPMENT AS SHOWN UNLESS SPECIFIED OTHERWISE.
MAX TWO DEVICES IN ONE HIGHER MOUNT
LOCATION AT LATCH SIDE OF DOOR, PROVIDE RFI
IF MORE DEVICES ARE NECESSARY. WHERE THERE
IS ONE DEVICE, CENTER OVER LOWER DEVICE. (TO
BE WITHIN ADA HEIGHT). (IF SWITCH CANNOT BE
LOCATED ON LATCH SIDE, LOCATE ONE DOOR
LEAF AWAY ON HINGE SIDE.)
DOOR
LOW DEVICES
RECEPTACLEVOICE/DATA
MASONRY COURSING
(WHERE APPLICABLE)
LIGHT SWITCH
F.A. AUDIO/VISUAL
ALIGNMENT NOTES
• ALIGN AND LOCATE CLOSE TOGETHER ANY DEVICES INSTALLED WITHIN 6' HORIZONTALLY.
• CENTER ALL DEVICES WHERE INDICATED ON COLUMN WRAP OR BUMP OUT; STACK AND ALIGN VERTICALLY.
• INSTALL DEVICES AT HEIGHTS INDICATED IN SYMBOL LEGEND UNLESS STACKING PER THIS DETAIL.
• WHERE HEIGHT IS SPECIFICALLY NOTED ON FLOOR PLANS, USE THAT MOUNTING HEIGHT
• CENTER ON DOORFRAME OR WHITEBOARDS ANY DEVICES INDICATED ABOVE.
O R L
A N D
IN
G
F R O
M F
LO
O
R
F R O
M F
LO
O
R O
R L
A N D
IN
G
6' - 0" MIN.
4" MAX
CAMERAS, CLOCKS, WALL
OCCUPANCY SENSORS
WHITE BOARD (WHERE APPLICABLE -
VERIFY WITH DETAILS/PLANS PROPER
INSTALL HEIGHT) CENTER ANY SINGLE
DEVICE WITH CENTER OF WHITE BOARD
ANY DEVICES
SHOWN OVER DOOR
TO BE CENTERED.
EQ EQ
EQ EQ
F R O
M F
LO
O
R O
R L
A N D
IN
G
SHORT THROW PROJECTOR
WHERE APPLICABLE
~12"
FA PULL STATION - HINGE SIDE
OF DOOR 1-LEAF AWAY WITHIN
5'-0" OF EXTERIOR OR STAIR
DOORS, WHEN WALL MOUNT
STROBES ARE ON PROJECT,
ALIGN ABOVE.
WHEN DEVICES ARE WITHIN DIMENSION, STACK
HIGH/LOW VERTICALLY AND GROUP DEVICES AT
SAME HEIGHT. UNLESS DEVICES IS PART OF
TECHNOLOGY DETAIL GROUPING OR SERVING A
FURNITURE GROUP.
CASEWORK, COORDINATE DEVICE BOTTOM
TO BE 2" OVER BACKSPLASH OR OVER
COUNTERTOP (IF NO BACKSPLASH). FOR
LARGE FORMAT TILE, ALIGN EDGE OF DEVICE
WITH HORIZONTAL GROUT LINE CLOSEST TO
COUNTERTOP.
COORDINATE OUTLET LOCATIONS WITH
GROUT LINES, EDGE OF DEVICE ON GROUT
LINE IF POSSIBLE. COORDINATE WITH
INTERIOR DESIGN DRAWINGS.
TYPICAL COLUMN
ENCLOSURE, CHASE OR
BUMP-OUT WITH DEVICES
INDICATED IN PLANS.
EQ EQ
EQEQEQEQ
THERMOSTAT,
SENSORS OR AV
CONTROLLER, CARD
READER, ETC.
DEVICES TO BE 4" MAX DISTANCE APART
NOT FOR CONSTRUCTION
PRELIM
IN
ARY
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
G E
N E
R A
L A
R C
H
IT
E C
T U
R A
L N
O T
E S
IN
T E
R
IO
R P
A R
T
IT
IO
N
T Y
P E
S
D E
V
IC
E A
L
IG
N M
E N
T G
U
ID
E L
IN
E S
A B
B R
E V
IA
T
IO
N
S
-2
.1
A G
F E
B R
U A
R Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P
A C
K A
G E
D
IS
T R
IC
T
W
ID
E A
C C
E S
S C
O N
T R
O L
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
GENERAL NOTES - ARCHITECTURAL - NEW CONSTRUCTION
1 THE OWNER RESERVES THE RIGHT TO REMOVE ANY ITEM FROM THE PROJECT PRIOR TO
COMMENCEMENT OF CONTRACTED DEMOLITION WORK.
2 ALL EXISTING CONDITIONS SHOULD BE FIELD VERIFIED BEFORE WORK BEGINS.
3 DIMENSIONS GIVEN ARE ACTUAL AND ARE TO THE FACE OF MASONRY UNITS OR TO THE
FACE OF STUD FRAMING, UNLESS NOTED OTHERWISE.
4 DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS. FOR
CONDITIONS NOT SHOWN, USE DETAILS CLOSEST TO CONDITION IN QUESTION.
5 EXTEND ALL INTERIOR WALL PARTITIONS FROM FLOOR TO STRUCTURE/DECK ABOVE
UNLESS NOTED OR DETAILED OTHERWISE.
6 WITHIN BUILDING INTERIOR PROVIDE BULLNOSE BLOCK IN CMU WALL ASSEMBLIES AT
ALL EXPOSED OUTSIDE CORNERS, INCLUDING WINDOW AND DOOR JAMBS, UNLESS
NOTES OR DETAILED OTHERWISE. PROVIDE SQUARE CORNERS AT ALL LOCATIONS
FINISHED WITH WALL TILE, REFER TO FINISH PLANS (I100 SHEETS) FOR LOCATIONS.
7 TOOTH-IN MASONRY AT NEW OPENINGS IN EXISTING WALLS.
8 TOOTH-IN NEW MASONRY INFILL INTO EXISTING OPENINGS AT ALL BULLNOSE BLOCK
LOCATIONS.
9 STUD WALLS SPANNING OVER 12'-0" IN HEIGHT SHALL BE A MINIMUM OF 20 GAGE.
10 STUD WALL SUPPORTING WALL CABINETS SHALL BE A MINIMUM OF 20 GAGE.
11 DOORS ARE TO BE 4" FROM CORNER OF ROOM, UNLESS NOTED OR DIMENSIONED
OTHERWISE.
12 FIRESTOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES AND
CONCEALED WALL SPACES AT CEILING, FLOOR AND ROOF LEVELS.
13 FIRESEAL ALL PENETRATIONS, SUCH AS, PIPES, DUCTS, CONDUITS, ETC. THROUGH FIRE
AND/OR SMOKE RATED ASSEMBLIES.
14 FOR CONTROL JOINT (C.J.) LOCATIONS REFER TO EXTERIOR ELEVATIONS AND/OR FLOOR
PLANS.
15 PAINT ALL ELECTRICAL PANEL COVERS AND ACCESS PANELS TO MATCH ADJACENT
FINISHES. USING OIL-BASED PAINT, NOT LATEX WALL PAINT.
16 PROVIDE WOOD BLOCKING IN WALLS THAT REQUIRE WALL MOUNTED EQUIPMENT OR
ACCESSORIES. COORDINATE WITH EQUIPMENT OR ACCESSORY MANUFACTURER.
17 ROVIDE ALL ASSOCIATED CURBS FOR ROOF TOP EQUIPMENT AND MECHANICAL ROOF
TOP UNITS. LARGE VOIDS BELOW THE AIR HANDLING UNITS SHALL BE FILLED WITH
INSULATION AS SPECIFIED FOR NOISE CONTROL.
18 ALL EXISTING ROOF TOP PENETRATIONS BEING REMOVED REQUIRE ROOF PATCHING TO
MATCH EXISTING ADJACENT.
GENERAL NOTES - ARCHITECTURAL - DEMOLITION
1 CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO
RELATED DEMOLITION WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL,
FLOOR OR CEILING INCLUDES ALL GENERAL MECHANICAL AND ELECTRICAL ITEMS WHICH
ARE A PART OF, OR ATTACHED TO IT.
2 CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS AND
BE RESPONSIBLE FOR THE SAME ADVISE CONSTRUCTION MANAGER OF ANY AND ALL
DISCREPANCIES.
3 PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND
DEMOLITION AS REQUIRED. FINISH TO MATCH EXISTING.
4 ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5 PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6 REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL
INFORMATION.
7 REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR
ADDITIONAL DEMOLITION NOTES.
8 SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF
REQUIRED.
9 AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL
ARE TO BE REMOVED. SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
SCALE: NONE
FIRE RATED WALL PLAN DETAILS
3/4" = 1'-0"
INTERIOR PARTITION TYPES
GENERAL NOTES - ARCHITECTURAL - PARTITIONS
1 NOT ALL WALL TYPES MAY BE USED ON PROJECT.
2 REFER TO CODE COMPLIANCE PLANS FOR LOCATIONS OF SMOKE AND FIRE-RATED
PARTITIONS.
3 ALL PARTITIONS EXTEND TO BOTTOM OF STRUCTURE, UNLESS NOTED OTHERWISE.
4 LINE OF STRUCTURE/DECK AS SHOWN AT THE HEAD CONDITION OF EACH PARTITION
TYPE IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION
CONDITIONS. TERMINATE RATED PARTITIONS AT UNDERSIDE OF STRUCTURAL DECK TO
MAINTAIN RATING. PROVIDE APPROPRIATE FRAMING AND GYPSUM BOARD TO OFFSET
AROUND STRUCTURE OR OTHER OBSTRUCTIONS, SUCH AS PIPING OR DUCTWORK.
5 PARTITIONS MAY TERMINATE AT STRUCTURAL MEMBERS WITH A RATING GREATER THAN
OR EQUAL THE PARTITION, PROVIDED THAT RATING IS CONTINUOUS TO STRUCTURAL
DECK ABOVE.
6 NON-RATED PARTITIONS THAT EXTEND TO STRUCTURE SHALL TERMINATE AT UNDERSIDE
OF STRUCTURAL DECK TO MAINTAIN A CONTINUOUS PLANE OF GYPSUM BOARD AS A
NOISE, SMOKE OR OTHER TYPE OF BARRIER.
7 ALL PARTITIONS EXTENDING TO STRUCTURE ABOVE SHALL TERMINATE WITH DEFLECTION
TRACK - REFER TO INTERIOR PARTITION TYPE DETAIL ON THIS SHEET.
8 ALL GYPSUM BOARD PARTITIONS NOT EXTENDING TO THE STRUCTURE MUST BE
BRACED.
9 UL DESIGN NUMBERS REFER TO THE FIRE RESISTANCE DIRECTORY; UNDERWRITERS
LABORATORY, LATEST EDITION.
10 MISCELLANEOUS NON-RATED CHASES TO BE 5/8" GYPSUM BOARD ON 3 5/8" METAL
STUD FRAMING AT 16" O.C., UNLESS NOTED OTHERWISE.
11 MISCELLANEOUS FURRING AROUND COLUMNS TO BE 5/8" GYPSUM BOARD ON 11/2"
STUDS, UNLESS NOTED OTHERWISE.
12 FIRE-RATED PARTITIONS TO HAVE FIRE-STOPPING SEALANTS AT HEAD, SILL JUNCTURE
WITH DISSIMILAR MATERIALS, ETC. AND AROUND ALL PENETRATIONS AND OPENINGS.
13 CONSTRUCT ALL PARTITIONS WITH SOUND ATTENUATION BATTS WITH THE FOLLOWING
SOUND BATT THICKNESS: 2 1/2" OR LESS METAL STUD - 1 1/2" THICKNESS, 3 5/8" OR
LARGER METAL STUD - 3" THICKNESS. UNLESS NOTED OTHERWISE.
PARTITION STUD KEY - METAL, CH, AND WOOD
A GYPSUM BOARD DIRECT APPLIED TO CMU
B 7/8"
C 1 1/2"
D 1 5/8"
E 2 1/2"
F 3 1/2"
G 3 5/8"
H 4
J 5 1/2"
K 6"
L 8"
M 10"
N 12"
P OPEN
Q OPEN
R 2 1/2"
S 4"
T 6"
U 2"x4"
V 2"x6"
W 2"x8"
METAL STUD/FURRING
DESIGNATION SIZE
METAL STUD/FURRING
DESIGNATION SIZE
METAL STUD/FURRING
DESIGNATION SIZE
PARTITION TYPE TAG (REFER TO FLOOR PLANS)
1X
PARTITION TYPE NUMBER STUD SIZE DESIGATION
FIRE RATING, IF REQUIRED
1X
LIST OF ABBREVIATIONS
ACP ACOUSTICAL PANEL CEILING
AFF ABOVE FINISH FLOOR
ALUM ALUMINUM
ANOD ANODIZED
CFMF COLD FORMED METAL FRAMING
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
DCMU DECOTATIVE CONCRETE MASONRY UNIT
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FRT FIRE RESISTANT TREATED
FV FIELD VERIFY
GYP BD GYPSUM BOARD
HM HOLLOW METAL
LVL LAMINATED VENEER LUMBER
MCM METAL COMPOSITE MATERIAL WALL PANEL
OC ON CENTER
PT PRESERVATIVE TREATED
PNT PAINT
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
TYP TYPICAL
VIF VERIFY IN FEILD
WD WOOD
12" = 1'-0"
DEVICE ALIGNMENT GUIDELINES
F
EQ
EQ
TS
T S
LOBBY
B1503
VESTIBULE
B1502
15' - 5 1/2"
/2
NOT FOR CONSTRUCTION
PRELIM
IN
ARY
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
F
IR
S T
F L
O O
R D
E M
O L
IT
IO
N
P L
A N
R
E F
L E
C T
E D
C E
IL
IN
G D
E M
O L
IT
IO
N P
L A
N
-2
.1
A D
F E
B R
U A
R Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P
A C
K A
G E
D
IS
T R
IC
T
W
ID
E A
C C
E S
S C
O N
T R
O L
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/4" = 1'-0"
FIRST FLOOR DEMOLITION PLAN - PARTIAL UNIT B
THIS DRAWING SHEET IS INTENDED TO BE PLOTTED IN
COLOR. IF THIS TEXT APPEARS IN BLACK AND WHITE,
IT IS PLOTTED INCORRECTLY. DISCARD AND OBTAIN
AN ACCURATE DRAWING
PORTAGE CENTRAL HIGHSCHOOL
AREA OF
WORK
B
KEY PLAN
SCALE: NO SCALE
A C
D E
G
F H
KEYED NOTES - ARCHITECTURAL - DEMOLITION
1 REMOVE AND DISCARD ALUMINUM ENTRANCE SYSTEM AND HARDWARE. PATCH WALL AS
REQUIRED.
2 REMOVE AND DISCARD FRAME AND BORROWED LITE. PREPARE OPENING FOR NEW
SYSTEM.
3 REMOVE AND DISCARD CEILING PANELS, GRID, AND SUSPENSION SYSTEM AS
REQUIRED FOR NEW CONSTRUCTION. PROTECT EXISTING TO REMAIN.
4 REMOVE AND DISCARD GYPSUM BOARD CEILING SYSTEM AS REQUIRED FOR NEW
CONSTRUCTION.
5 REMOVE AND DISCARD GYPSUM BOARD BULKHEAD.
1/4" = 1'-0"
FIRST FLOOR REFLECTED CEILING DEMOLITION PLAN -
PARTIAL UNIT B
ISSUED FOR DATE
INTERIOR VESTIBULE - NORTH ENTRANCE
FACULTY SPACE - BORROWED LITE
MAIN ENTRANCE - REFLECTED CEILING PLAN
F
EQ
EQ
TS
T S
B1502 B1502A B1502CB1502B
LOBBY
B1503
CHECK IN
B1504
A 101
F1
VESTIBULE
B1502
A 101BL1
A 101
BL2A
A 101 BL2B
14' - 10" +/- 3' - 2"
4' - 8"15' - 5 1/2" 5' - 5 1/2"
1K
1K
A 101
A 101
5' - 7" +/-
6" CFMS STUD
COLUMN FRAMING AS
REQ'D BY MANUF.
6" CFMS STUD
COLUMN FRAMING AS
REQ'D BY MANUF.
10" CFMS DOUBLE
HEADER AS REQ'D BY
MANUF., AT NEW WALLS
VESTIBULE
B1502
CHECK IN
B1504
LOBBY
B1503
2' - 8" 21' - 0"
/2
2' - 8"
' - 2
/2
6' - 1"
1K
1K
P-1 10' - 0"
ACP-1
10' - 4"A 101
A 101
GYPSUM BOARD
LAY-IN ACOUSTICAL TILE GRID
OR LIGHTING - REFER TO ELECTRICAL LIGHTING PLAN
MECHANICAL - REFER TO MECHANICAL SHEET METAL PLAN
KEY - REFLECTED CEILING
TECTUM CEILINGGENERAL NOTES - REFLECTED CEILINGS
1. WHERE CEILING TILE IS LESS THAN 3" AT PERIMETER OF ROOM PROVIDE A CUT 2x4
TILE IN LIEU OF FULL 2x2 TILE AND SMALL PIECE OF TILE OR DOUBLE GRID - MATCH
2x2 FOR STYLE AND COLOR.
2. AT AREAS OF EXPOSED CEILING PAINT ALL STRUCTURE, DUCTWORK, PIPING, CONDUIT,
HANGERS ETC., COORDINATE WITH MECHANICAL, ELECTRICAL AND PLUMBING
SPECIFICATIONS. REFER TO THE REFLECTED CEILING PLANS FOR PAINT COLORS.
FG2
R E F E R T
O S
C H E D
U
LE
8"8"
SCHED.
REFER TO
SEE PLAN
EQ. SEE SCHED. SEE SCHED. SEE SCHED. SEE SCHED. EQ.
S E E S
C H E D U
LE
T Y P
2" TYP.
SG-1
SG-1
SG-1
SG-1
A 101
H-1
3' - 7" 6" 3' - 7" 2" TYP.
SEE PLAN
T Y P
SG-1 SG-1
BL 1
A 101
H-2
A 101
S-2
A 101
S-2
T Y P
SEE PLAN
BL 2A
2' - 2"2" TYP.
SG-1 SG-1
A 101
H-1
A 101
S-1
A 101
S-1
T Y P
SG-1 SG-1
(2) EQ. SPACES 2" TYP.
BL 2B
SEE PLAN
A 101
H-1
A 101
S-1
A 101
S-1
FIRST FLOOR
100' - 0" (X' - X")
A 101
VESTIBULE
B1502
CHECK IN
B1504
FIRST FLOOR
100' - 0" (X' - X")
A 101
VESTIBULE
B1502
LOBBY
B1503
VESTIBULE
B1502
A 101
6" CFMS, FRAMING AS
REQ'D BY MANUF.
ACP CEILING, REFER
TO REFLECTED
CEILING PLANS
STUD WALL
PARTITION. REFER
TO FLOOR PLANS
FOR WALL TYPES
5/8 GYP. BOARD
ON 3 5/8" METAL
STUDS AT 16" O.C.
WITH BATT INSUL.
EXISTING ACP
CEILING, REFER TO
REFLECTED CEILING
PLANS
3 5/8" METAL STUD
KICKER AT 32" O.C.
OR AS REQ'D.
SEE PLAN
ALUMINUM FRAME -
REFER TO SCHEDULE
SEALANT AT PERIMETER,
BOTH SIDES
5/8" GYPSUM BOARD,
BOTH SIDES
METAL STUDS AT
16" O.C.
CFMS DOUBLE
HEADER
EXISTING CMU
EXISTING LINTEL
ALUMINUM FRAME - REFER
TO SCHEDULE
WINDOW - REFER TO PLAN
WALL BEYOND
EXISTING CMU
WINDOW - REFER TO
PLAN
SEALANT AT PERIMETER,
BOTH SIDES
ALUM. FRAME INFILL AT
CENTER MULLION
ALUMINUM FRAME
REFER TO SCHEDULE
ALUMINUM FRAME -
REFER TO SCHEDULE
SEALANT AT PERIMETER,
BOTH SIDES
5/8" GYPSUM BOARD,
BOTH SIDES
METAL STUDS AT
16" O.C.
NOT FOR CONSTRUCTION
PRELIM
IN
ARY
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
F
IR
S T
F L
O O
R P
L A
N
R E
F L E
C T
E D
C E
IL
IN
G P
L A
N
-2
.1
A
F E
B R
U A
R Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P
A C
K A
G E
D
IS
T R
IC
T
W
ID
E A
C C
E S
S C
O N
T R
O L
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
PORTAGE CENTRAL HIGHSCHOOL
AREA OF
WORK
B
KEY PLAN
SCALE: NO SCALE
A C
D E
G
F H
1/4" = 1'-0"
FIRST FLOOR PLAN - PARTIAL UNIT B
1/4" = 1'-0"
FIRST FLOOR REFLECTED CEILING PLAN - PARTIAL UNIT B
FIRST FLOOR DOOR SCHEDULE
NUMBER
ROOM NAME
FIRE RATING DOOR SIZE FRAME DETAILS
GLASS
ACCESS CONTROLS
HDWR. SET REMARKS
DOOR ROOM DOOR FRAME TYPE MAT FIN WIDTH HEIGHT ELEV MAT FIN HEAD JAMB SILL A-PHONE
BARRIER-F
REE
CARD
READER
ELEC. LOCK
HDWR. MAG HOLD
B1502 B1503 LOBBY - - FG2 FRP ANOD 3' - 0" 7' - 10" 1 AL ANOD H-1 - - SG-1 No Yes Yes Yes No - -
B1502A B1503 LOBBY - - FG2 FRP ANOD 3' - 0" 7' - 10" 1 AL ANOD H-1 - - SG-1 No No No Yes No - -
B1502B B1503 LOBBY - - FG2 FRP ANOD 3' - 0" 7' - 10" 1 AL ANOD H-1 - - SG-1 No No No Yes No - -
B1502C B1503 LOBBY - - FG2 FRP ANOD 3' - 0" 7' - 10" 1 AL ANOD H-1 - - SG-1 No No No Yes No - -
1/4" = 1'-0"
DOOR TYPES
1/4" = 1'-0"
FRAME ELEVATION
F1
1/4" = 1'-0"
BORROWED LITE ELVATIONS
METAL TRIM CORNER
TO MATCH ALUMINUM
STOREFRONT SYSTEM
1/4" = 1'-0"A 101
1 BUILDING SECTION
1/4" = 1'-0"A 101
2 BUILDING SECTION
NEW OPERABLE
WINDOW -
HORIZONTAL SLIDER
1 1/2" = 1'-0"A 101
3 BULKHEAD DETAIL
ISSUED FOR DATE
1 1/2" = 1'-0"A 101
H-1 HEAD DETAIL (DOOR)
1 1/2" = 1'-0"A 101
H-2 HEAD DETAIL (WINDOW)
1 1/2" = 1'-0"A 101
S-2 JAMB/SILL DETAIL (WINDOW)
1 1/2" = 1'-0"A 101
S-1 JAMB/SILL DETAIL (WINDOW)
NOT FOR CONSTRUCTION
PRELIM
IN
ARY
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L
L R
IG
H
T S
R E
S E
R V
E D
IN
T
E R
IO
R
G E
N E
R A
L N
O T
E S
-2
.1
IG
F E
B R
U A
R Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P
A C
K A
G E
D
IS
T R
IC
T
W
ID
E A
C C
E S
S C
O N
T R
O L
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
NOTES - INTERIORS
1 REFER TO MATERIAL SELECTION SCHEDULE FOR FINISH INFORMATION.
2 REFER TO ARCHITECTURAL FLOOR PLANS AND SPECIFICATION FOR ADDITIONAL
INFORMATION ON CONSTRUCTION MATERIALS.
3 REFER TO ARCHITECTURAL ENLARGED STAIR PLANS FOR RAILINGS, GUARD RAILS, FINISH
COLORS OF ANY PAINTED METALS. COORDINATE STAIR DETAILS WITH FLOORING TYPES
INDICATED ON FINISH PLANS.
4 REFER TO ARCHITECTURAL FLOOR PLANS FOR LOCKER LOCATIONS AND QUANTITIES.
5 REFER TO ARCHITECTURAL GENERAL SHEETS FOR BARRIER-FREE MOUNTING HEIGHT
REQUIREMNTS AND CODE-REQUIRED SIGNAGE.
6 REFER TO ARCHITECTURAL ENLARGED TOIELT ROOM PLANS FOR TOILET ACCESSORIES,
PARTITIONS, ETC.
7 REFER TO REFLECTED CEILING PLANS FOR CEILING FINISH AND HEIGHTS.
8 WALL MOUNTED DIFFUSERS, GRILLES, ACCESS PANELS, ELECTRICAL PANELS, ETC. ARE
TO BE PAINTED WITH AN OIL-BASED PAINT TO MATCH THE ADJACENT WALL FINISH.
9 AT AREAS OF EXPOSED CEILING WHERE DUCTWORK AND DIFFUSERS ARE TO BE
PAINTED, COORDINATE WITH MECHANICAL SPECIFICATIONS AND REFER TO THE
REFLECTED CEILING PLANS FOR PAINT COLORS.
10 CEILING ACCESS PANELS ARE TO BE PAINTED TO MATCH ADJACENT CEILING FINISH.
11 REFER TO DOOR SCHEDULE FOR FINISH ON DOORS AND FRAMES.
12 REFER TO FINISH PLANS FOR VISUAL DISPLAY BOARD LOCATIONS.
13 REFER TO INTERIOR ELEVATION SHEETS FOR REQUIREMENTS, GENERAL NOTES,
ABBREVIATIONS, AND HARDWARE/ACCESSORY SELECTIONS FOR CASEWORK.
14 REFER TO INTERIORS TYPICAL DETAIL SHEETS FOR TILE TRIM DETAILS, FLOORING
TRANSITIONS, WAINSCOT DETAILS, AND TYPICAL TILE PATTERN REQUIREMENTS.
15 ALL FLOOR SUPPORTED STORAGE RACKS, CABINETS, BOOKCASES, ETC. WHEN
ADJACENT TO THE WALL SHALL BE FASTENED TO BOTH THE FLOOR AND WALL.
16 PROVIDE BLOCKING AS REQUIRED FOR ATTACHMENT OF CASEWORK, MILLWORK,
SHELVING, EQUIPMENT, SPEACILITY FINISHES, ETC.
17 DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS. FOR
CONDITIONS NOT SHOWN USE DETAILS CLOSEST TO CONDITION IN QUESTION.
INDICATES WALL FINISH
INDICATES BASE FINISH
INDICATES FLOOR FINISH
INDICATES COUNTERTOP FINISH
INDICATES CABINET FINISH (BASE AND UPPER)
INDICATES EXTENT OF ATYPICAL FINISH (WALL, BASE, OR FLOOR)
INDICATES DISSIMILAR FLOOR MATERIAL FINISHES,
REFER TO TYPICAL FLOOR TRANSITION DETAILS
INDICATES MULTIPLE MATERIALS, REFER TO ENLARGED PLANS OR
ELEVATIONS
INDICATES PATTERNED INSTALLATION OF A SINGLE MATERIAL TYPE,
REFER TO DETAIL OR ELEVATION
INTERIOR - TYPICAL SYMBOLS AND REFERENCES
XX-#
X-# X-# X-#
X-# X-#
X-#
MULTI
X-P(A)
X X
X-#
INDICATES MATERIAL TYPE
INDICATES CORRESPONDING SELECTION IN MATERIAL SELECTION
SCHEDULE
INDICATES PATTERN INTENT, REFER TO DETAIL OR ELEVATION
INDICATES INSTALLATION OF GRAIN
XB-# INDICATES VISUAL DISPLAY BOARD, REFER TO VISUAL DISPLAY BOARD
SCHEDULES
CG-# INDICATES CORNER GUARD, REFER TO MATERIAL SELECTION SCHEDULE
INDICATES LOWER WALL FINISH
INDICATES BASE FINISH
INDICATES FLOOR FINISH
X-# X-# X-#
X-# INDICATES UPPER WALL FINISH- ABOVE 0' - 0" A.F.F.
- UP TO 0' - 0" A.F.F.
WHERE HEIGHTS ARE NOT INDICATED
REFER TO TYPICAL DETAIL OR ELEVATION
INDICATES WINDOW TREATMENT, REFER TO WINDOW TREATMENT
SCHEDULE
DEFINITIONS/ABBREVIATIONS - INTERIORS
A.F.F. ABOVE FINISHED FLOOR
BF BARRIER FREE
CL CENTER LINE
EX. EXISTING
HOLD HOLD DIMENSION
MIN. MINIMUM CODE ALLOWABLE DIMENSION
OC ON CENTER
OPP OPPOSITE
SIM SIMILAR
TYP. TYPICAL
V.I.F. VERIFY IN FIELD
THIS DRAWING SHEET IS INTENDED TO BE PLOTTED IN
COLOR. IF THIS TEXT APPEARS IN BLACK AND WHITE,
IT IS PLOTTED INCORRECTLY. DISCARD AND OBTAIN
AN ACCURATE DRAWING
LOBBY
B1503
VESTIBULE
B1502
EX
ECPTL-1
M U
LT
I
M U
LT
I
I 101B 3
I 501
1F
CHECK IN
B1504
EX
EX
EX
PL-1
PL-2
FRL-1
I 501
I 101B
EX
EC
PT
L
EX
EC
PT
L
EX
EC
PT
L
EX
EC
PT
L
FRL-1, CUT TO SIZE. GRAIN
TO RUN VERTICAL
7' - 11 1/2"
PAINT P-1 ABOVE WINDOW
FRAMES
RUBBER BASE, RB-1
ALIGN FRL SEAM LOCATIONS
WITH WINDOW MULLIONS
8" 3' - 7" 3' - 8 1/2"
PLASTIC LAMINATE COUNTER, PL-1
FRL-1, GRAIN TO RUN VERTICAL
RUBBER BASE, RB-1
5' - 3 1/4"
FRL-1 SEAM LOCATION TO BE CENTERED
EQEQ
LUXURY VINYL TILE TO CARPET TILE
LUXURY VINYL TILE
CARPET TILE
JOHNSONITE SLIMLINE TRANSITION, COLOR 40 BLACK
NOT FOR CONSTRUCTION
PRELIM
IN
ARY
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L
L R
IG
H
T S
R E
S E
R V
E D
F
IR
S T
F L
O O
R F
IN
IS
H P
L A
N
U N
IT
B
E
L E
V A
T
IO
N S
A
N D
M A
T E
R
IA
L S
E L E
C T
IO
N
S C
H E
D U
L E
-2
.1
I
B
F E
B R
U A
R Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P
A C
K A
G E
D
IS
T R
IC
T
W
ID
E A
C C
E S
S C
O N
T R
O L
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
THIS DRAWING SHEET IS INTENDED TO BE PLOTTED IN
COLOR. IF THIS TEXT APPEARS IN BLACK AND WHITE,
IT IS PLOTTED INCORRECTLY. DISCARD AND OBTAIN
AN ACCURATE DRAWING
PORTAGE CENTRAL HIGHSCHOOL
AREA OF
WORK
B
KEY PLAN
SCALE: NO SCALE
A C
D E
G
F H
MATERIAL SELECTION SCHEDULE
ABBREV ITEM MANUFACTURER PATTERN COLOR PRODUCT NO. SIZE
SINGLE SOURCE
BASIS OF
DESIGN
ADDITIONAL
MANUFACTURERS
REMARKS
ACP-1 ACOUSTIC CEILING PANEL USG ASTRO CLIMAPLUS WHITE 8221 24" X 24" X -- SQUARE EDGE | .55 NRC | 35 CAC
ECPTL-1 ENTRYWAY CARPET TILE MILLIKEN OBEX CUTX / GRAIN GREY GRX235-27 25 CM X 1M X ASHLAR INSTALLATION
FRL-1 FIBER REINFORCED LAMINATE PANELS PANOLAM / NEVAMAR -- GRAND ISLE MAPLE NW721 4' X 8' PANELS X GRAIN TO BE INSTALLED VERTICALLY | ALUMINUM TRIM | COLOR
MATCH CAULK JOINTS
P-1 PAINT SHERWIN WILLIAMS -- WOOL SKEIN SW6148 -- X -- --
PL-1 PLASTIC LAMINATE FORMICA -- NAVY GRAFIX - MATTE 7018-58 -- X -- --
PL-2 PLASTIC LAMINATE NEVAMAR -- GRAND ISLE MAPLE W-8371T -- X -- --
RB-1 RUBBER BASE TARKETT / JOHNSONITE DURACOVE - WITH TOE BLUE LAGOON 42 4" HIGH X -- --
1 NO COMPARABLE PRODUCTS OR PRODUCT SUBSTITUTIONS WILL BE REVIEWED FOR PRODUCTS DESIGNATED AS SINGLE SOURCE.
2 COMPARABLE PRODUCTS WILL BE REVIEWED FOR ITEMS LISTED AS BASIS OF DESIGN. COMPARABLE PRODUCTS ARE REQUIRED TO MEET ANY MINIMUM PERFORMANCE REQUIREMENTS LISTED IN REMARKS AND APPERANCE OF SPECIFIED PRODUCT.
3 REFER TO TYPICAL DETAILS AND PRODUCT SPECIFICATION FOR TRIMS AND ACCESSORIES ASSOCIATED WITH SPECIFIED PRODUCTS ABOVE.
GENERAL NOTES - MATERIAL SELECTION SCHEDULE
NOTES - FINISH PLANS
1 FINISH TAGS APPLY TO LIKE MATERIALS IN ENTIRE ROOM. I.E. CASEWORK TAG MAY
ONLY CALLOUT ONE RUN OF CASEWORK, BUT ALL CASEWORK IN ROOM RECEIVE THE
SAME FINISHES, UNLESS TAGGED DIFFERENTLY.
2 CASEWORK FINISH TAGS DO NOT APPLY TO CUSTOM MILLWORK PIECES. REFER TO
ENLARGED MILLWORK DETAILS FOR FINISH MATERIALS.
3 REFER TO ENLARGED FINISH PLANS AND PATTERN PLANS FOR ADDITIONAL FINISH
DETAILS.
4 DASHED LINE INDICATES LINE OF CEILING ABOVE, REFER TO REFLECTED CEILING PLANS.
5 WHERE NO FINISH TAG IS SHOWN ALL EXISTING FINISHES ARE TO REMAIN, UNLESS
OTHERWISE NOTED.
1/4" = 1'-0"
FIRST FLOOR FINISH PLAN - UNIT B
1/4" = 1'-0"I 101B
3 VESTIBULE B1502 - EAST
1/4" = 1'-0"I 101B
4 LOBBY B1503 - NORTH
3" = 1'-0"I 101B
1 TYPICAL FLOORING TRANSITIONS
21"
PLASTIC LAMINATE WORK
SURFACE, PL-1
PLASTIC LAMINATE
CASEWORK BASE, PL-2
RUBBER BASE, RB-1
FRL-1 BELOW DESK SURFACE,
GRAIN TO RUN VERTICAL
PLASTIC LAMINATE WORK
SURFACE, PL-1
PLASTIC LAMINATE CASEWORK
BASE, PL-2
PROVIDE CONCEALED
SUPPORT BRACKETS 36" O.C.
TYPICAL.
RUBBER BASE, RB-1
PAINT, P-1
FRL-1 BELOW DESK
SURFACE. GRAIN TO RUN
VERTICAL
EP
2' - 1 5/8" 5' - 10"
FRL-1 ATTACHED TO END PANEL
I 5011D
1C
I 501
1F
1E
I 501
1I
CHECK IN
B1504
4' - 8"
/2
2' - 1"
2' - 7"
I 501
1H
I 501
1G
33' - 2"
R 2"
ALIGN TOP OF BACKSPLASH
TO BOTTOM OF MULLION
PLASTIC LAMINATE WORK
SURFACE, PL-1
RUBBER BASE, RB-1
FRL-1 BELOW DESK
SURFACE. GRAIN TO RUN
VERTICAL
EXISTING WALL FINISH TO
REMAIN
NEW OPERABLE WINDOW.
REFER TO ARCH
TYPICAL 6" METAL STUD WITH
5/8" GYP WALL CONSTRUCTION.
REFER TO ARCH
PLASTIC LAMINATE COUNTER, PL-1
3/4" PLYWOOD SUBSTRATE
CONCEALED BRACKET WITHIN WALL
CONSTRUCTION. SIZED AND
SPACED AS REQUIRED
FRL-1 ON BOTH SIDES OF GYP WALL
CONTRUCTION, GRAIN TO RUN
VERTICAL
18" DEEP BASE CABINET, PL-2
18 3/4" 7 1/4"
RUBBER BASE, RB-1
2' - 2"
PLASTIC LAMINATE
BACKSPALSH, PL-1
PLASTIC LAMINATE
WORK SURFACE, PL-1
CONCEALED BRACKET WITHIN
WALL CONSTRUCTION.
SPACED 36" O.C.
FRL-1 ON BOTH SIDES OF
GYP WALL CONSTRUCTION,
GRAIN TO RUN VERTICAL
2' - 1"
PLASTIC LAMINATE
BACKSPALSH, PL-1
PLASTIC LAMINATE
WORK SURFACE, PL-1
CONCEALED BRACKET WITHIN
WALL CONSTRUCTION.
SPACED 36" O.C.
FRL-1 ON BOTH SIDES OF
GYP WALL CONSTRUCTION,
GRAIN TO RUN VERTICAL
8"
CAULK JOINTS WHERE FRAME
MEETS WALL
EXISTING DCMU WALL
FINISH TO REMAIN
FRL-1, CUT TO SIZE ON NEW
WALL CONSTRUCTION.
GRAIN TO RUN VERTICAL
RUBBER BASE, RB-1
NEW OPPERABLE WINDOW,
REFER TO ARCH.
3' - 2"4
/2
/2
PLASTIC LAMINATE
COUNTER, PL-1
NOT FOR CONSTRUCTION
PRELIM
IN
ARY
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L
L R
IG
H
T S
R E
S E
R V
E D
E N
L A
R G
E D
M
IL
L W
O R
K P
L A
N
-2
.1
I
F
E B
R U
A R
Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P
A C
K A
G E
D
IS
T R
IC
T
W
ID
E A
C C
E S
S C
O N
T R
O L
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
NOTES - MILLWORK
1 VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO FABRICATION.
2 ALL DIMENSIONS ARE FROM FINISH FACE UNLESS NOTED OTHERWISE.
3 CASEWORK FINISH TAGS DO NOT APPLY TO MILLWORK. REFER TO ELEVATIONS AND
DETAILS FOR MILLWORK FINISHES.
4 CABINETRY WITHIN MILLWORK SCOPE MUST BE FURNISHED FROM SAME VENDOR AND
MANUFACTURER AS ADJACENT MILLWORK DIEWALLS AND PANELS.
5 WIREWAYS AND ACCESS PANELS FOR MILLWORK MOUNTED DEVICES AND TECHNOLOGY
MUST BE COORDINATED WITH MECHANICAL, ELECTRICAL, TECHNOLOGY, AND SECURITY
CONTRACTORS.
6 FILLER PANELS SHALL BE NO LESS THAN 2" WIDE, UNLESS NOTED OTHERWISE.
7 FINISH ANY EXPOSED END PANELS, UNDERSIDE OF CABINETS OR OPEN CABINETS, WITH
MATERIAL SPECIFIED FOR FRONTS IN THAT ROOM.
8 ALL VERTICAL AND HORIZONTAL EXPOSED AND SEMI-EXPOSED SURFACES TO BE
FINISHED WITH BODY MATERIAL.
9 SUPPORT BRACKETS ARE REQUIRED EVERY 36" O.C. AT AREAS WHERE COUNTERTOP IS
OPEN UNDERNEATH. THE CONTRACTOR WILL BE RESPONSIBLE FOR PROVIDING
BRACKETS APPROPRIATELY SIZED BASED ON DEPTH OF COUNTER.
10 PATTERN OR GRAIN DIRECTION TO BE VERTICAL ON DOORS AND HORIZONTAL ON
DRAWERS - PER AWI STANDARDS, UNLESS NOTED OTHERWISE.
11 LOCKS: ALL CABINETS KEYED ALIKE, PER ROOM. SEE ELEVATIONS FOR LOCK
LOCATIONS.
12 GROMMET LOCATIONS SHALL BE VERIFIED IN THE FIELD WITH THE OWNER PRIOR TO
INSTALLATION - COORDINATE WITH POWER & DATA LOCATIONS FOR ANY ADDITIONAL
WIRE MANAGEMENT REQUIREMENTS.
13 SLABSMITHING' WILL BE REQUIRED IN INSTANCES WHERE A PATTERNED QUARTZ,
NATURAL STONE, OR SOLID SURFACE IS SPECIFIED.
14 WHERE MILLWORK IS INDICATED TO RECIEVE RESIDENTIAL APPLIANCES, FURNITURE, OR
OWNER-FURNISHED EQUIPMENT, COORDINATE WITH FINAL OWNER-PROVIDED
SELECTIONS.
MILLWORK HARWARE & ACCESSORY SELECTIONS
1 GROMMETS TYPE & FINISH: MOCKET BRAVA @BRV1, SATIN CHROME FINISH.
2 SUPPORT BRACKET TYPES & FINISH: A AND M HARDWARE HEAVY DUTY HYBRID
BRACKETS. SIZED AS REQUIRED. FINISH TO BE BLACK POWDERCOAT UNLESS
OTHERWISE NOTED.
3 PVC EDGEBANDING TO BE SELECTED
KEYED NOTES - ENLARGED MILLWORK PLANS
1 GROMMET LOCATIONS TO BE COORDINATED WITH ELECTRICAL
2 NEW CABINET HEATER, REFER TO MECHANICAL
3 CAULK JOINT
1/4" = 1'-0"I 501
1C CHECK IN DESK - INTERIOR RETURN
1/4" = 1'-0"I 501
1D CHECK IN DESK - INTERIOR FRONT
1/2" = 1'-0"I 501
1 CHECK IN B1504 I 501
1A CHECK IN B1504 - 3D VIEW
1/4" = 1'-0"I 501
1E CHECK IN DESK - INTERIOR TRANSACTION WINDOW
1 1/2" = 1'-0"I 501
1I CHECK IN B1504 - RETURN DETAIL
I 501
1B VESTIBULE - 3D VIEW
ADJ ADJUSTABLE
FP FILLER PANEL
RP REMOVABLE PANEL
P/O PULL-OUT DRAWER
BF BARRIER_FREE
CLR CLEAR OPENING
STANDARD ABBREVIATIONS - CASEWORK
1 1/2" = 1'-0"I 501
1H CHECK IN B1504 - COUNTER DETAIL
1 1/2" = 1'-0"I 501
1G CHECK IN B1504 - OPPERABLE WINDOW DETAIL
ISSUED FOR DATE
1/4" = 1'-0"I 501
1F VESTIBULE - TRANSACTION WINDOW
AUTOMATIC CONTROL DAMPER
BRITISH THERMAL UNIT PER HOUR
CALIBRATED BALANCING VALVE
CUBIC FEET PER MINUTE
ENTERING AIR TEMPERATURE
EXTERNAL STATIC PRESSURE
ELECTRIC WATER COOLER
ENTERING WATER TEMPERATURE
CONTROL VALVEC.V.
E.W.B.
E.W.C.
E.W.T.
EXIST.
E.A.
E.A.T.
E.D.B.
E.F.
E.S.P.
D.F.
D.S.
DN.
ENTERING WET BULB
EXISTING
DRINKING FOUNTAIN
DOWN SPOUT
EXHAUST AIR
ENTERING DRY BULB
EXHAUST FAN
DOWN
C.B.
C.H.
C.I.
C.M.
C.O.
C.B.V.
C.F.H.
C.F.M.
B.D.D.
B.F.
BTUH
B.V.
B.D.
A.F.F.
A.G.
A.P.D.
CATCH BASIN
CUBIC FEET PER HOUR
CABINET HEATER
CAST IRON
CEILING MOUNTED
CLEAN OUT
BALANCING DAMPER
ABOVE FINISHED FLOOR
ABOVE GRADE
AIR PRESSURE DROP
BACKDRAFT DAMPER
BARRIER FREE
BALANCING VALVE
A.C.D.
BRITISH THERMAL UNIT PER HOUR
LEAVING AIR TEMPERATURE
LEAVING WATER TEMPERATURE
MIXED AIR TEMPERATURE
FIELD INSTALLEDF.I.
MBH
M.B.
(THOUSANDS)
MOP BASIN
L.A.T.
L.W.B L.W.T.
M.A.
M.A.T.
MAX.
LAV.
L.D.B.
LOUV.
G.P.M.
H.B.
HP
I.E.
F.M.
F.P.M.
F.R.
LAVATORY
LEAVING DRY BULB
LEAVING WET BULB
MIXED AIR
MAXIMUM
LOUVER
FLOOR MOUNTED
FEET PER MINUTE
FIN RADIATION
GALLONS PER MINUTE
HOSE BIBB
HORSE POWER
INVERT ELEVATION
F.C.
F.D.
(FD)
F.H.C.
FLEXIBLE CONNECTION
FLOOR DRAIN
FIRE DAMPER
FIRE HOSE CABINET
TEMPERATURE RISET.R.
TOTAL STATIC PRESSURE
TERMINAL UNIT BOX
TEPID WATER CONNECTION
VIBRATION ISOLATORS
WATER PRESSURE DROP
W.SK. WASH SINK
V.
T.S.
T.S.P.
T.U.
T.W.C.
U.H.
URN.
VEL.
V.I.
V.I.F.
V.S.
V.T.R.
W.
W.C.
W.M.
W.P.D.
VELOCITY
VERIFY IN FIELD
VENT STACK
VENT THRU ROOF
WASTE
WATER CLOSET
WALL MOUNTED
TIP SPEED
UNIT HEATER
URINAL
VENT
MANUFACTURER(S)MFR.(S)
BACKFLOW PREVENTER
MANUAL AIR VENT
NORMALLY CLOSED
NON-FREEZE WALL HYDRANT
NOT IN CONTRACT
OUTSIDE AIR INTAKE
POST INDICATOR VALVE
PRESSURE REDUCING VALVE
PRESSURE / TEMPERATURE TAPPING
RELATIVE HUMIDITY
REVOLUTIONS PER MINUTE
REDUCED PRESSURE PRINCIPAL
STATIC PRESSURE
RETURN AIRR.A.
S.O.V.
R.D.
R.H.
R.I.O.
R.P.M.
RPPBP
R.V.
S.A.
SENS.
SHR.
SK.
S.P.
S.SK.
TEMP.
TOT.
SHUT-OFF VALVE
SENSIBLE
SHOWER
SERVICE SINK
TEMPERATURE
TOTAL
SINK
ROOF DRAIN
ROUGH IN ONLY
RELIEF VALVE
SUPPLY AIR
M.H.
MIN.
MTG.
M.V.
N.C.
N.F.W.H.
N.I.C.
N.O.
O.A.
O.A.I.
OCT.
P.A.
P.D.
P.I.V P.R.V.
P.T.
OUTSIDE AIR
OCTAVE
PIPE ANCHOR
PRESSURE DROP
MANHOLE
MINIMUM
MOUNTING
NORMALLY OPEN
E.T.R. EXISTING TO REMAIN
HUMIDITY SENSOR
THREE-WAY CONTROL VALVE
CONTROL VALVE
FLOW METER (PROBE TYPE)
TEMPERATURE SENSORTS
CARBON DIOXIDE SENSOR
DIFFERENTIAL PRESSURE SENSOR
AS
HS
CO2
DP
AIRFLOW SENSOR
F FREEZE STAT
MOTORIZED ACTUATORM
MS MOISTURE SENSOR
DS DUCT SMOKE SENSOR
TEPID WATER
TEPID WATER RETURNTWR
TW
HUMIDISTAT
PRESSURE GAUGE
OXYGEN
REDUCED PRESSURE PRINCIPLE BACKFLOW
PUMPED CONDENSATE
PRIMARY HEATING HOT WATER SUPPLY
PRIMARY HEATING HOT WATER RETURN
PRESSURE / TEMPERATURE TAPPING
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
OUTSIDE STEM AND YOKE VALVE
SMOKE DAMPER
SHUT-OFF VALVE
STEAM
SOFT HOT WATER
SPRING CHECK VALVE
SOFT HOT WATER RETURN
SOFT COLD WATER
SANITARY SEWER (BELOW FLOOR)
SANITARY SEWER (ABOVE FLOOR)
PREVENTER
O2
PHR
PC
PHS
SAN
SAN
SHW
SHWR
S
STM (#)
SCW
THERMOMETER
STRAINER
THROTTLING VALVE
THERMOSTAT
TRIPLE DUTY VALVE (STRAIGHT)
TRIPLE DUTY VALVE (ANGLE)
THREE-WAY CONTROL VALVE
STORM (BELOW FLOOR)
STORM SEWER (ABOVE FLOOR)
VENT
VACUUM BREAKER
VACUUM
UNION
ST
ST
VAC
V
STEAM TRAPT
AW
CAP
AWV
CR
CWR
CWS
CS
A
CD
COND
CTR
CTS
FP
FS
FD
GAS
FOR
FOS
HR
G
HS
HPR
HPS
CONTROL VALVE
HOT WATER SUPPLY (DOMESTIC)
HOT WATER RETURN (DOMESTIC)
HEAT PUMP SUPPLY
HEAT PUMP RETURN
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
GAS COCK
FUEL OIL SUPPLY
FUEL OIL RETURN
FOOTING DRAIN
FLOW SWITCH
FLOW METER (WAFER TYPE)
FLOW METER (PROBE TYPE)
FIRE PROTECTION
FIRE/SMOKE DAMPER
FIRE DAMPER (VERTICAL)
FIRE DAMPER (HORIZONTAL)
COOLING TOWER SUPPLY
COOLING TOWER RETURN
CONDENSATE DRAIN
CONDENSATE
COLD WATER (DOMESTIC)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CHECK VALVE
CALIBRATED BALANCING VALVE
BUTTERFLY VALVE
BALANCING VALVE
ACID WASTE VENT
ACID WASTE
COMPRESSED AIR
CHILLER RETURN
CHILLER SUPPLY
TEMPERATURE SENSOR
STORM SEWER (OVERFLOW SYSTEM)ST (OF)
MVAC MEDICAL VACUUM
MEDICAL AIRMA
S
S
T
H
TS
GLR
GLS GROUND LOOP WATER SUPPLY
GROUND LOOP WATER RETURN
REFRIGERANT LINE (SUCTION)
REFRIGERANT LINE (LIQUID)LIQUID
SUCTION
SNOWMELT SUPPLYSMS
SNOWMELT RETURNSMR
CO2 CARBON DIOXIDE
DI DEIONIZED WATER
N NITROGEN
N2O NITROUS OXIDE
NOT FOR CONSTRUCTION
PRELIM
IN
ARY
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L
L R
IG
H
T S
R E
S E
R V
E D
M E
C H
A N
IC
A
L
P L
U M
B
IN
G
G E
N E
R A
L N
O T
E S
A
B B
R E
V
IA
T
IO
N S
A
N D
S Y
M B
O L
S
-2
.1
M G
F E
B R
U A
R Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P
A C
K A
G E
P O
R T
A G
E D
IS
T
R
IC
T W
ID
E
A C
C E
S S
C O
N T
R O
L U
P G
R A
D E
S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
GENERAL NOTES - MECHANICAL - NEW CONSTRUCTION
1 DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS.
DRAWINGS ARE NOT TO BE CONSIDERED FABRICATION DRAWINGS.
2 IF THE CONTRACTOR ELECTS TO PROVIDE EQUIPMENT OTHER THAN BASIS OF DESIGN,
THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE THE LAYOUT AND
CLEARANCE REQUIREMENTS IN ALL SPACES CONTAINING EQUIPMENT AND PROVIDE
EQUIPMENT MEETING THE SPECIFICATIONS AND ACHIEVING CODE REQUIRED
CLEARANCES WITHIN THE SPACE PROVIDED. CONTRACTOR IS REQUIRED TO COVER ALL
ELECTRICAL COSTS FOR OTHER THAN BASIS OF DESIGN PRODUCTS SUCH AS
DIFFERENT VOLTAGE OR DIFFERENT SIZE MOTER.
3 COORDINATE ALL NEW CONSTRUCTION WORK OR ACTIVITY WITH THAT WHICH IS
REQUIRED BY OTHER TRADES OR INSTALLERS IN ORDER TO PROVIDE A COMPLETE
SYSTEM INCLUDING ALL NECESSARY COMPONENTS, FITTINGS, AND OFFSETS.
4 INSTALLER SHALL VERIFY ALL EXISTING JOBSITE CONDITIONS AND DIMENSIONS AND BE
RESPONSIBLE FOR THE SAME. NOTIFY THE ENGINEER OF DISCREPANCIES PRIOR TO
COMMENCING WORK.
5 FIRE SEAL ALL PENETRATIONS, SUCH AS PIPES, DUCTS, CONDUIT, ETC. THROUGH FIRE
AND/OR SMOKE RATED ASSEMBLIES.
6 MECHANICAL INSTALLER IS RESPONSIBLE FOR PATCHING OF WALLS, CEILINGS, AND
FLOORS WHERE FIXTURES, MECHANICAL EQUIPMENT, SHEET METAL, OR PIPING HAS
BEEN REMOVED, RELOCATED, OR INSTALLED.
7 ALL PIPING AND DUCTWORK SHALL AVOID LOCATIONS DIRECTLY ABOVE ALL ELECTRICAL
EQUIPMENT. COORDINATE WITH ELECTRICAL.
8 ALL LOW VOLTAGE CABLING SHALL BE RUN IN CONDUIT BETWEEN DEVICE AND CABLE
TRAY OR TECHNOLOGY RACK. NO CABLING SHALL BE VISIBLE IN EXPOSED CEILING
SPACES AND SHALL BE ROUTED IN CONDUIT THAT IS PAINTED TO MATCH SURFACE IT IS
SUPPORTED FROM. CABLING THAT IS ROUTED ABOVE AN ACCESSIBLE CEILING SPACE
CAN BE INDEPENDENTLY SUPPORTED WITH COMM HOOKS OR RINGS.
9 COORDINATE ALL TEMPERATURE SENSOR LOCATIONS WITH "ELECTRICAL DEVICES
ALIGNMENT GUIDELINES" DETAIL ON SHEET G 001.
10 WHERE SPACE PERMITS, ALL HYDRONIC BRANCH PIPING SHALL TAP OFF OF BOTTOM OR
SIDE OF PIPING MAINS PER BRANCH PIPING TAKE-OFF PIPING DETAIL THIS SHEET.
MANUAL AIR VENTS SHALL BE INSTALLED AT THE TOP OF ALL HYDRONIC SYSTEMS.
11 ALL EXISTING CLOSED SYSTEMS SHALL BE ISOLATED AND FLUSHED/CLEANED PRIOR TO
CONNECTION TO NEW SYSTEMS.
12 ALL BRANCH PIPING SHALL BE FURNISHED WITH SHUT-OFF VALVES IN AN ACCESSIBLE
LOCATION NEAR MAIN CONNECTION.
MECHANICAL SYMBOLSABBREVIATIONS
CONTROL SYMBOLS
GENERAL NOTES - MECHANICAL - DEMOLITION
1 ALL DUCTWORK, PIPING AND EQUIPMENT SHOWN DASHED SHALL BE REMOVED, EXCEPT
WHEN NOTED OTHERWISE. PROTECT EXISTING WORK WHICH IS TO REMAIN IN PLACE
FOR REUSE WITH TEMPORARY COVERS, SHORING, BRACING AND SUPPORTS. VERIFY
LOCATIONS OF AND PROTECT EXISTING INTERIOR ELECTRICAL AND MECHANICAL
UTILITIES AND SERVICES EXCEPT WHERE INDICATED OTHERWISE. ALL MATERIALS AND
EQUIPMENT REMOVED AND NOT REUSED SHALL BECOME PROPERTY OF THE
CONTRACTOR AND SHALL BE REMOVED FROM THE SITE. THE OWNER RESERVES THE
RIGHT TO KEEP, OR TO SALVAGE PARTS FROM, ANY EQUIPMENT PRIOR TO BEING
REMOVED FROM SITE. ALL MATERIALS AND EQUIPMENT REQUIRING REMOVAL AND
RELOCATION FOR REUSE SHALL BE CAREFULLY REMOVED AND STORED TO PREVENT
DAMAGE AND REINSTALLED AS THE WORK PROGRESSES.
2 CONTRACTOR SHALL PROTECT ALL WALLS, CEILINGS, FLOORS, LIGHTS AND OTHER
FINISHED SURFACES NOT BEING DEMOED. IF DAMAGED, THE CONTRACTOR SHALL
REPAIR TO MATCH EXISTING CONDITIONS.
5 PERFORM PRE-DEMOLITION TESTS. MEASURE AND RECORD VALUES INDICATED,
SUBMIT REPORT TO THE ENGINEER. ALL MEASUREMENTS SHALL BE TAKEN WITH THE
EQUIPMENT OPERATING AT FULL DESIGN CAPACITY. MEASURE AND RECORD GRILLE,
REGISTER, OR DIFFUSER AIRFLOW AND NECK SIZE. MEASURE AND RECORD AIRFLOW,
INLET STATIC PRESSURE, SUPPLY AIR TEMPERATURE, GPM, AND EWT/LWT OF
ASSOCIATED TERMINAL UNIT. MEASURE AND RECORD OA AND SA CFM OF THE
ASSOCIATED AIR HANDLING UNIT. MEASURE AND RECORD SPACE AND OUTDOOR
TEMPERATURE AND HUMIDITY.
TS
TS
TS
TS
Space
VESTIBULE
CUH-1
750 CFM
CUH-2
500 CFM
10"ø
"ø
SA-X
200 CFM
TYP. OF 2
SA-X
175 CFM
TYP. OF 4
EXIST.
14"x12"
E
XI
S T.
"ø
E
XI
S T.
"ø
E
XI
S T.
"ø
EXIST. 8"ø
EXIST. 8"ø
E
XI
S T.
"ø
Space
VESTIBULE
EXIST.
14"x12"
E
XI
S T.
"ø
E
XI
S T.
"ø
E
XI
S T.
"ø
SA-X
175 CFM
TYP. OF 4
E
XI
S T.
"ø
NOT FOR CONSTRUCTION
PRELIM
IN
ARY
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L
L R
IG
H
T S
R E
S E
R V
E D
F
IR
S T
F L
O O
R S
H E
E T
M E
T A
L P
L A
N
-2
.1
M
F E
B R
U A
R Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P
A C
K A
G E
P O
R T
A G
E D
IS
T
R
IC
T W
ID
E
A C
C E
S S
C O
N T
R O
L U
P G
R A
D E
S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
THIS DRAWING SHEET IS INTENDED TO BE PLOTTED IN
COLOR. IF THIS TEXT APPEARS IN BLACK AND WHITE,
IT IS PLOTTED INCORRECTLY. DISCARD AND OBTAIN
AN ACCURATE DRAWING
PORTAGE CENTRAL HIGHSCHOOL
AREA OF
WORK
B
KEY PLAN
SCALE: NO SCALE
A C
D E
G
F H
KEYED NOTES - MECHANICAL - NEW CONSTRUCTION
1 INSTALL NEW CABINET HEATER IN EXISTING OPENING. RECONNECT TO EXISTING
CONTROLS.
2 USE SALVAGED DUCTWORK TO CONNECT TO DIFFUSER.
ISSUED FOR DATE
1/4" = 1'-0"
FIRST FLOOR SHEET METAL PLAN - PARTIAL UNIT B
1/4" = 1'-0"
FIRST FLOOR MECHANICAL DEMOLITION PLAN
- PARTIAL UNIT B
CABINET HEATERS - ELECTRIC BASED ON MARKEL
MARK MODEL TYPE
AIRFLOW
(CFM)
COIL DATA MOTOR DATA
REMARKSCAPACITY
(MBH) KW
EAT
(°F)
LAT
(°F) AMPS
VOLTAGE
CUH-1 CUH945 SEMI-RECESSED 500 34.5 10.0 60 °F 123 °F 13 480/3/60 (1)
CUH-2 CUH945 SURFACE MOUNTED 500 34.5 10.0 60 °F 123 °F 13 480/3/60 (1)
NOTES:
1. FRONT TOP DISCHARGE, FRONT BOTTOM RETURN.
KEYED NOTES - MECHANICAL - DEMOLITION
1 EXISTING CABINET HEATER TO BE REPLACED. UNIT CONTROLS TO REMAIN. REUSE
EXISTING OPENING FOR NEW UNIT.
2 REMOVE AND SALVAGE EXISTING DIFFUSER. REMOVE EXISTING DUCTWORK AND
SALVAGE FOR CONNECTION TO DIFFUSER IN NEW LOCATION.
3 EXISTING THERMOSTAT TO REMAIN AND BE REUSED FOR NEW UNIT.
DO
FIRE ALARM SYMBOLS
RECEPTACLE SYMBOLS
F
V
V
F
F
S
FIRE ALARM MANUAL PULL STATION
FIRE ALARM - VISUAL ALARM
FIRE ALARM AUDIO/VISUAL ALARM, WALL MTD.
80"
80"
40"
PUSH-BUTTON STATION - 2 HOLE
PUSH-BUTTON STATION - 1 HOLE
40"
40"
DUPLEX RECEPTACLE - WITH GFI
DOUBLE DUPLEX RECEPTACLE
DUPLEX RECEPTACLE - WET LOCATION ENCLOSURE WITH GFI
DUPLEX RECEPTACLE - FOR ELECTRIC WATER COOLER, WITH GFI
WP
GFI
DUPLEX RECEPTACLE 16"
DUPLEX RECEPTACLE - EMERGENCY
SINGLE POLE SWITCH 40"
EXIT SIGN - CEILING MOUNTED
EMERGENCY BATTERY UNIT
EWC
OS
OS
OCCUPANCY SENSOR (SET TO VACANCY MODE) CEILING MOUNTED
OCCUPANCY SENSOR (SET TO VACANCY MODE) - WALL MOUNTED
FIRE ALARM - VISUAL ALARM, CEILING MTD.
FIRE ALARM AUDIO/VISUAL ALARM, CEILING MTD.
DUPLEX RECEPTACLE - 4" ABOVE COUNTER BACKSPLASH
DOOR OPERATOR
PUSH-BUTTON STATION - 3 HOLE 40"
EXIT SIGN - WALL MOUNTED
88"
88"
DUPLEX RECEPTACLE - SURFACE MOUNTED #WM500
DUPLEX RECEPTACLE - HORIZONTAL MOUNTING
DUPLEX RECEPTACLE - WITH (2) USB OUTLETS BETWEEN POWERUSB
RECEPTACLES VARIATIONS - HEIGHT PER ABOVE UNLESS INDICATED ON DRAWINGS:
RECTANGULAR LIGHT FIXTURE
RECTANGULAR EMERGENCY LIGHT FIXTURE ON EMERGENCY
POWER, SWITCHABLE
DOWNLIGHT WALL WASH FIXTURE
WALL MTD. LIGHT FIXTURE
DOWNLIGHT FIXTURE
DOWNLIGHT FIXTURE - EMERGENCY, SWITCHABLE
LIGHTING SYMBOLS MOUNTING HEIGHTS
POWER SYMBOLS MOUNTING HEIGHTS
DUPLEX RECEPTACLE - STACK ALIGNED BELOW DEVICE ABOVE
(DEVICE ALIGNMENT IS NOT LIMITED TO THOSE LABELED, REFER TO
ELECTRICAL DEVICE ALIGNMENT GUIDELINES)
H
ST
OSS
S 33S
SP
SD
3KS
S
SK
S3
SS
4KS
SWITCH AND PILOT LIGHT
DIMMER SWITCH (NON-SYSTEM TYPE) 0-10 ELV DIMMER
THREE-WAY SWITCH
FOUR-WAY SWITCH
KEY OPERATED, SINGLE POLE SWITCH
KEY OPERATED, THREE-WAY SWITCH
OCCUPANCY SENSOR (SET TO VACANCY MODE) - SWITCH MOUNTED
DUAL SINGLE POLE SWITCH
DUAL THREE-WAY SWITCH
KEY OPERATED, FOUR-WAY SWITCH
40"
40"
40"
40"
40"
40"
40"
40"
40"
40"
SLV-a LOW VOLTAGE CONTROL SWITCH, REFER TO DETAIL 40"
SECURITY SYMBOLS
RB
CR
KP
IC
SCP
MS
LD
DA
#n
CB
BT
ANT
SCR
S
VC
S
TS n
AV n
TV n
PRJ n
MIC
AUDIO/VISUAL
MCP
TC-#
GBB
STRUCTURED CABLING MOUNTING HEIGHTS
WAP
PAG
NOTES:
MOUNT DEVICES AT HEIGHTS INDICATED UNLESS INDICATED
OTHERWISE ON PLANS. HEIGHTS ARE TO BOTTOM OF DEVICE.
ACP #
CR
M
LS
RELEASE BUTTON
CARD READER
KEY PAD
INTERCOM
SECURITY CAMERA
SECURITY CAMERA
SECURITY CABLING PATHWAY
INTERCOM MASTER STATION
LOCKDOWN BUTTON
DURESS ALARM PUSH BUTTON
ACCESS CONTROL DETAIL INDICATOR: REFER TO ACCESS
CONTROL DETAILS AND SCHEDULE
MICROPHONE JACK
CEILING BOX
BLUETOOTH DEVICE
ANTENNA
PROJECTOR SCREEN
LOUDSPEAKER CEILING MOUNTED
VOLUME CONTROL
LOUDSPEAKER WALL MOUNTED
TECHNOLOGY OR TEACHER'S
STATION BOXES
A/V WALL STATION BOXES
TV WALL BACKBOX
PROJECTOR (OUTLET WITHIN 16"
OF PROJECTOR LOCATION)
MASTER CLOCK PANEL
CABLE TRAY
CLOCK
4'X8'X3/4" FIRE-RATED PLYWOOD
CONDUIT SLEEVE
DATA/VOICE OUTLET
DATA/VOICE OUTLET - ABOVE
BACKSPLASH
NETWORK COMMUNICATION RACK
DATA/VOICE OUTLET - SURFACE
GROUNDING BUS BAR
WIRELESS ACCESS POINT
PAGING SYSTEM HEAD END
ACCESS CONTROL PANEL
CARD READER, MULLION MOUNT
LOCKDOWN STROBE
SECURITY CONTROLS PATHWAY
REFER TO SECURITY DRAWINGS, DETAILS
AND PLANS FOR LOCATIONS AND
ROUGH-IN INFORMATION.
REFER TO TECHNOLOGY DRAWINGS,
DETAILS AND PLANS FOR LOCATIONS AND
ROUGH-IN DATA.
REFER TO TECHNOLOGY DRAWINGS,
DETAILS AND PLANS FOR LOCATIONS AND
ROUGH-IN DATA.
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E L E
C T
R
IC
A L S
Y M
B O
L S
A N
D G
E N
E R
A L
N O
T E
S
-2
.1
E G
F E
B R
U A
R Y
C E
N T
R A
L H
IG
H
S C
H O
O L
B
ID
P A
C K
A G
E
D
IS
T
R
IC
T W
ID
E
A C
C E
S S
C O
N T
R O
L
P o rt a g e M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L S
ELECTRICAL ABBREVIATIONS
(#) # INDICATES QUANTITIES (I.E. (4) 3" CONDUITS MEANS FOUR 3" DIAMETER
CONDUITS)
(E) EXISTING
AFC ABOVE FINISHED CEILING
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CT CURRENT TRANSFORMER
CU COPPER
DFA DROP FROM ABOVE
DW DISHWASHER
EM EMERGENCY
ET ELECTRONIC TRIP
EWC ELECTRIC WATER COOLER
FDS FUSIBLE DISCONNECT SWITCH
GAP GENERATOR ANNUNCIATOR PANEL
GD GARBAGE DISPOSAL
GEC GROUNDING ELECTRODE CONDUCTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER, 5mA
GFP GROUND FAULT PROTECTION OF EQUIPMENT, 30mA
GND GROUND
IAW IN ACCORDANCE WITH
IC INSULATION CONTACT
IDF INTERMEDIATE DISTRIBUTION FRAME
JB JUNCTION BOX
KCMIL THOUSANDS OF CIRCULAR MILS
LCP LIGHTING CONTROL PANEL
MDF MAIN DISTRIBUTION FRAME
NFDS NON-FUSIBLE DISCONNECT SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NTS NOT TO SCALE
OC ON CENTER
PB PULL BOX
REF REFRIGERATOR
RT RAINTIGHT
SPD SURGE PROTECTIVE DEVICE
TR TAMPER RESISTANT
TTB TELECOMMUNICATIONS TERMINAL BOARD
TX TRANSFORMER
TYP TYPICAL
ULSE UL SERVICE ENTRANCE RATED
UON UNLESS OTHERWISE NOTED
WP WEATHERPROOF
GENERAL NOTES - LIGHTING
1 ALL OCCUPANCY SENSORS AND PHOTOCELLS MOUNTED IN THE SAME ROOM SHALL BE
CONNECTED TOGETHER AND OPERATE AS ONE SYSTEM. DAYLIGHT HARVESTING SHALL
BE SELF CONTAINED WITHIN EACH ROOM AND SHALL BE FIELD ADJUSTED WITH
ENGINEER. MANUFACTURER SHALL PROVIDE FLOOR PLANS DURING SHOP DRAWING
PHASE SHOWING EXACT LOCATIONS AND QUANTITIES AS REQUIRED FOR A COMPLETE
SYSTEM.
2 ALL OCCUPANCY SENSOR WIRING SHALL BE CONCEALED WITHIN CONDUIT WHERE
EXPOSED. NO LOW VOLTAGE WIRING SHALL BE EXPOSED.
3 ALL CONDUITS SHALL RUN AS TIGHT TO DECK AS PERMITTED BY CODE. CONDUITS
SHALL BE RUN IN A NEAT MANNER. MAINTAIN THE SAME SPACING WHEN CONDUITS ARE
RUN TOGETHER. CONCEAL JUNCTION BOXES OVER LAY-IN CEILING AND USE EMT
DROPS DOWN TO CLOUDS. LOCATE CONDUIT DROPS TO CLOUDS AND CEILING
ELEMENTS IN LEAST VISIBLE LOCATION. NO MC-CABLE TO LIGHT FIXTURES SHALL BE
VISIBLE FROM ANY ANGLE.
4 RECESS NEW DEVICES AND ASSOCIATED CONDUIT AND BACKBOX IN EXISTING WALL.
CUT AND PATCH AS REQUIRED.
GENERAL NOTES - POWER
1 ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING
REQUIRED FOR NEW WORK OR WHERE DEVICES ARE REMOVED AND NOT REPLACED.
2 ELECTRICAL CONTRACTOR SHALL COORDINATE WITH G SERIES SHEETS DEVICE
COORDINATION DETAIL. DEVICES ARE TO ALIGN VERTICALLY AND HORIZONTALLY AND
FOLLOW THE RULES OF THIS DETAIL CONSISTENTLY. A PRE-INSTALL DEVICE
COORDINATION MEETING FOR DEVICE FINISHES AND LAYOUT MAY BE REQUIRED IN THE
SPECIFICATION FOR THIS PROJECT.
3 PATCH ALL PENETRATIONS AS REQUIRED TO MAINTAIN FIRE RATING.
4 REFER TO INTERIOR ELEVATIONS, SECTIONS, ARCHITECTURAL ELEVATIONS AND RELATED
DRAWINGS FOR EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS. WHERE DEVICES
ARE MOUNTED UNDER OR ABOVE TACK BOARDS, DOORS, WINDOWS, OR ANY PIECE OF
EQUIPMENT, THE ELECTRICAL DEVICE SHALL BE CENTERED AS SHOWN. COORDINATE
LOCATION OF FURNITURE CONNECTIONS AND/OR RECEPTACLES AND DATA RACEWAYS
WITH APPROVED FURNITURE SHOP DRAWINGS, FINAL CONNECTIONS TO FURNITURE BY
ELECTRICAL CONTRACTOR.
5 ALL CONDUITS SHALL RUN AS NEAR TO DECK AS PERMITTED BY CODE. SOME
CONDUITS WILL BE EXPOSED AND SHALL BE RUN IN A NEAT MANNER. MAINTAIN THE
SAME SPACING WHEN CONDUITS ARE RUN TOGETHER. CONCEAL JUNCTION BOXES
OVER LAY-IN CEILING AND USE EMT DROPS DOWN TO CLOUDS. LOCATE CONDUIT
DROPS TO CLOUDS AND CEILING ELEMENTS IN LEAST VISIBLE LOCATION.
6 WHEN CEILINGS ARE REMOVED ELECTRICAL CONTRACTOR SHALL PROPERLY SUPPORT
ALL CONDUIT AND LOW VOLTAGE WIRING AS REQUIRED PER NEC.
7 REMOVE CEILINGS AND GRID AS REQUIRED. REPLACE ANY DAMAGED CEILINGS.
8 ALL FIRE ALARM PULL STATIONS TO HAVE PLASTIC COVERS WITH ALARM.
9 ALL FIRE ALARM CABLING SHALL BE RUN IN CONDUIT. FIRE ALARM CABLING IS
PERMITTED TO BE IN CABLE TRAY WITH SEPARATION FROM BUILDING AND
COMMUNICATION CABLING.
10 THE FIRE ALARM CONTRACTOR SHALL SUBMIT FINAL FIRE ALARM SHOP DRAWINGS AS A
DELEGATED DESIGN SUBMITTAL TO THE AUTHORITY HAVING JURISDICTION
11 FIRE ALARM DEVICES SHOWN ON PLANS ARE INDICATED TO ILLUSTRATE GENERAL
DESIGN INTENT TO ASSIST THE CONTRACTOR IN SCOPING, PRICING, AND
COORDINATION WITH OTHER SYSTEMS
12 FIRE ALARM DEVICES SHOWN ARE NOT INTENDED TO REPRESENT A COMPLETE
ENGINEERED FIRE ALARM DESIGN
13…