23 6313-RIB-Air Cooled Refrigerant Condensers-04-19-2024 (1)Project Manual.pdf
PDF 72 KB Posted
- Attached to
- Jefferson RCE HVAC System Replacements
- Solicitation number
- 645-DOTRFQ-3203-2027
- Issued by
- Jasper County, Iowa
About this file
This is a standard material specification document for air-cooled refrigerant condensers (Section 23 6313) issued as part of the Jefferson RCE HVAC System Replacements project in Iowa, with a bid submission deadline of November 18, 2026. The specification establishes requirements for packaged, factory-assembled, pre-wired condenser units suitable for outdoor use, including casing, condensing coils, fans, and controls. The units must comply with AHRI 210/240 and UL 207 standards, achieve a minimum SEER rating of 14, and utilize refrigerants with zero ozone depletion potential and global warming potential less than 50. The specification details requirements for aluminum-finned copper tubing coils with sub-cooling circuits, vertical discharge propeller-type fans with weatherproof motors, and factory-wired control panels with NEMA 250 enclosures. Installation must follow manufacturer instructions and comply with ASHRAE standards, with the contractor required to provide cooling season start-up and winter shutdown service for the first year of operation.
The specification requires manufacturer qualifications of minimum three years of documented experience in manufacturing such products and installer qualifications of minimum three years in performing related work. All products requiring electrical connections must be listed and classified by Underwriters Laboratories Inc. The document mandates submittal of product data, shop drawings, manufacturer's installation instructions, and operation and maintenance documentation, including one extra set of fan belts per unit. No pricing information, funding sources, set-asides, or contract award dates are specified in this technical specification document.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
0-Standard Material Specifications
- 1219 04-19-2024
Page
Air Cooled Refrigerant Condensers 23 6313
SECTION 23 6313
AIR COOLED REFRIGERANT CONDENSERS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Manufactured units.
B. Casing.
C. Condenser coils.
D. Fan requirements.
E. Controls.
1.02 RELATED REQUIREMENTS
A. Section 23 2300 - Refrigerant Piping.
B. Section 26 0583 - Wiring Connections: Electrical characteristics and wiring connections.
1.03 REFERENCE STANDARDS
A. AHRI 210/240 - Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment; 2023.
B. ASHRAE Std 15 - Safety Standard for Refrigeration Systems; 2022, with Addendum (2024).
C. ASHRAE Std 20 - Methods of Laboratory Testing Remote Mechanical-Draft Air-Cooled Refrigerant Condensers; 2019.
D. ASHRAE Std 90.1 I-P - Energy Standard for Buildings Except Low-Rise Residential Buildings;
Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
E. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum); 2020.
F. NEMA MG 1 - Motors and Generators; 2021.
G. UL 207 - Standard for Refrigerant-Containing Components and Accessories, Nonelectrical;
Current Edition, Including All Revisions.
1.04 SUBMITTALS
A. See Section 01 3000 - Administrative Requirements for submittal procedures.
B. Product Data: Provide rated capacities, weights, accessories, electrical requirements, and wiring diagrams.
C. Shop Drawings: Indicate components, assembly, dimensions, weights and loading, required clearances, and location and size of field connections. Include schematic layouts showing condenser, refrigeration compressors, cooling coils, refrigerant piping and accessories required for complete system.
D. Manufacturer's Instructions: Submit manufacturer's complete installation instructions.
E. Sustainable Design Documentation: Submit manufacturer's product data on refrigerant used, showing compliance with specified requirements.
F. Operation and Maintenance Data: Include start-up instructions, maintenance instructions, parts lists, controls, and accessories.
G. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.
1. See Section 01 6000 - Product Requirements, for additional provisions.
2. Extra Fan Belts: One set for each unit.
1.05 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacturing the type of products specified in this section, with minimum three years of documented experience.
B. Installer Qualifications: Company specializing in performing the work of this section with minimum 3 years of experience.
04-19-2024
Page
Air Cooled Refrigerant Condensers 23 6313
C. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories Inc. as suitable for the purpose specified and indicated.
1.06 DELIVERY, STORAGE, AND HANDLING
A. Comply with manufacturer's installation instruction for rigging, unloading and transporting units.
B. Protect units on site from physical damage. Protect coils.
PART 2 PRODUCTS
2.01 MANUFACTURED UNITS
A. Provide packaged, factory assembled, pre-wired unit, suitable for outdoor use consisting of casing, condensing coil and fans, integral sub-cooling coil liquid accumulator.
B. Construction and Ratings: In accordance with AHRI 210/240 and UL 207. Testing shall be in accordance with ASHRAE Std 20.
C. Performance Ratings: Energy Efficient Rating (EER)/Coefficient of Performance (COP) not less than prescribed by ASHRAE Std 90.1 I-P, in combination with compressor units.
D. Refrigerant: Use only refrigerants that have ozone depletion potential (ODP) of zero and global warming potential (GWP) of less than 50.
E. Minimum SEER ratingof 14.
2.02 CASING
A. House components in welded steel frame with steel panels with weather resistant, baked enamel finish.
B. Mount starters, disconnects, and controls in weatherproof panel provided with full opening access doors. Provide mechanical interlock to disconnect power when door is opened.
C. Provide removable access doors or panels with quick fasteners.
2.03 CONDENSER COILS
A. Coils: Aluminum fins mechanically bonded to seamless copper tubing. Provide sub-cooling circuits. Air test under water to 425 psig, and vacuum dehydrate. Seal with holding charge of nitrogen.
B. Coil Guard: Expanded metal with lint screens.
C. Configuration: Single refrigeration circuit with receiver.
2.04 FAN REQUIREMENTS
A. Vertical discharge direct driven propeller type condenser fans with fan guard on discharge, equipped with roller or ball bearings with grease fittings extended to outside of casing.
B. Weatherproof motors suitable for outdoor use, single phase permanent split capacitor or 3 phase, with permanent lubricated ball bearings and built-in current and thermal overload protection.
2.05 CONTROLS
A. Provide factory wired and mounted control panel, NEMA 250, containing fan motor starters, fan cycling thermostats, compressor interlock, and control transformer.
B. Provide controls to permit operation down to ____ degrees F ambient temperature.
C. Provide thermostat to cycle fan motors in response to outdoor ambient temperature.
D. Provide solid state control to vary speed of one condenser fan motor in response to refrigerant condensing pressure.
PART 3 EXECUTION
3.01 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Provide for connection to electrical service. See Section 26 0583.
04-19-2024
Page
Air Cooled Refrigerant Condensers 23 6313
C. Provide connection to refrigeration piping system. See Section 23 2300. Comply with ASHRAE Std 15.
D. Provide cooling season start-up, winter season shut-down service, for first year of operation.
E. Shut-down system if initial start-up and testing takes place in winter and machines are to remain inoperative. Repeat start-up and testing operation at beginning of first cooling season.
END OF SECTION