This is a Standard Material Specifications document (Section 23 5400) for forced air furnaces and thermostats related to the Jefferson RCE HVAC System Replacements project in Iowa. The specification details the required furnace systems, including gas-fired forced air units with an Annual Fuel Utilization Efficiency (AFUE) rating of 0.95 (condensing), self-contained packaged units with sealed combustion and direct venting configured for upflow operation. Key components specified include hot-rolled steel primary heat exchangers, aluminized steel secondary heat exchangers, atmospheric gas burners with electronic pilot ignition, centrifugal supply fans with variable pitch motor pulleys, and 1-inch thick washable urethane air filters. The specification mandates that bidders verify compatibility with existing furnace and motor specifications, matching capacity and motor configurations (single, two-speed, or multiple-speed) to current installations. Thermostats must be low-voltage, microcomputer-based units with remote sensors, programmable scheduling for weekdays and weekends, and continuous low-speed fan operation capability.
Installation must comply with manufacturer instructions and multiple national codes including NFPA 54 (National Fuel Gas Code), NFPA 90A and 90B (heating and air-conditioning installation standards), NFPA 211 (chimneys and vents), NFPA 70 (National Electrical Code), and ANSI Z21.47 (gas-fired central furnaces). Manufacturers must have a minimum of three years documented experience, and installers must be manufacturer-approved with specified years of experience to be determined. Warranty requirements include three years for solid-state ignition modules, five years for heat exchangers, and one year for installer work. All products must be listed and classified by UL and CSA in accordance with applicable standards and regulations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
0-Standard Material Specifications
- 1219 04-19-2024
Page
Furnaces 23 5400
SECTION 23 5400
FURNACES
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Forced air furnaces.
B. Thermostats.
1.02 REFERENCE STANDARDS
A. ANSI Z21.47 - American National Standard for Gas-Fired Central Furnaces; 2021.
B. ASHRAE Std 52.2 - Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size; 2017, with Addendum (2022).
C. ASHRAE Std 103 - Method of Testing for Annual Fuel Utilization Efficiency of Residential Central Furnaces and Boilers; 2022.
D. NEMA MG 1 - Motors and Generators; 2021.
E. NFPA 54 - National Fuel Gas Code; 2024.
F. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
G. NFPA 90A - Standard for the Installation of Air-Conditioning and Ventilating Systems; 2021.
H. NFPA 90B - Standard for the Installation of Warm Air Heating and Air-Conditioning Systems;
2018.
I. NFPA 211 - Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances;
2024.
J. UL (DIR) - Online Certifications Directory; Current Edition.
1.03 SUBMITTALS
A. See Section 01 3000 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide rated capacities, weights, accessories, electrical nameplate data, and wiring diagrams.
C. Operation and Maintenance Data: Include manufacturer's descriptive literature, operating instructions, installation instructions, maintenance and repair data, and parts listing.
D. Warranty: Submit manufacturers warranty and ensure forms have been filled out in Owner's name and registered with manufacturer.
1.04 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacturing the type of products specified in this section, with minimum three years of documented experience.
B. Installer Qualifications: Company specializing in performing the work of this section with minimum ___ years of experience and approved by manufacturer .
1.05 WARRANTY
A. Provide three year manufacturers warranty for solid state ignition modules.
B. Provide five year manufacturers warranty for heat exchangers.
C. Provide one year installers' warranty.
PART 2 PRODUCTS
2.01 REGULATORY REQUIREMENTS
A. Comply with NFPA 70.
B. Products Requiring Electrical Connection: Listed and classified by UL (DIR) as suitable for the purpose specified and indicated.
04-19-2024
Page
Furnaces 23 5400
2.02 GAS FIRED FURNACES
A. Annual Fuel Utilization Efficiency (AFUE): 0.95 ("condensing") in accordance with ASHRAE Std 103.
B. Units: Self-contained, packaged, factory assembled, pre-wired unit consisting of cabinet, supply fan, heating element, controls, air filter, humidifier, and accessories; wired for single power connection with control transformer.
1. Safety certified by CSA in accordance with ANSI Z21.47.
2. Venting System: Direct.
3. Combustion: Sealed.
4. Air Flow Configuration: Upflow.
5. Heating: Natural gas fired.
6. Accessories:
a. Condensate drain.
C. Performance:
1. Heating Capacity:
a. Bidder to check existing furnace capacity an match existing.
b. Gas heating capacities are sea level ratings.
2. Air Handling:
a. Bidder to check existing furnace capacity an match existing.
D. Cabinet: Steel with baked enamel finish, easily removed and secured access doors with safety interlock switches, glass fiber insulation with reflective liner. If not certified for combustible flooring, please provide additional steel base.
E. Primary Heat Exchanger:
1. Material: Hot-rolled steel.
2. Shape: Tubular type.
F. Secondary Heat Exchanger:
1. Material: Aluminized steel.
G. Gas Burner:
1. Atmospheric type with adjustable combustion air supply.
2. Gas valve, two stage provides 100 percent safety gas shut-off; 24 volt combining pressure regulation, safety pilot, manual set (On-Off), pilot filtration, automatic electric valve.
3. Electronic pilot ignition, with electric spark igniter.
4. Combustion air damper with synchronous spring return damper motor.
5. Non-corrosive combustion air blower with permanently lubricated motor.
H. Gas Burner Safety Controls:
1. Thermocouple sensor: Prevents opening of gas valve until pilot flame is proven and stops gas flow on ignition failure.
2. Flame rollout switch: Installed on burner box and prevents operation.
3. Vent safety shutoff sensor: Temperature sensor installed on draft hood and prevents operation, manual reset.
4. Limit Control: Fixed stop at maximum permissible setting, de-energizes burner on excessive bonnet temperature, automatic resets.
I. Supply Fan: Centrifugal type rubber mounted with direct drive with adjustable variable pitch motor pulley.
J. Motor:
1. 1750 rpm single-speed, permanently lubricated, hinge mounted.
2. Motor: Bidder to check existing motor and verify RPM and whether it is single, two speed, or multiple speed and match existing.
3. Comply with NEMA MG 1.
K. Air Filters: 1 inch thick urethane, washable type arranged for easy replacement.
L. Operating Controls:
04-19-2024
Page
Furnaces 23 5400
1. Room Thermostat: Cycles burner to maintain room temperature setting.
2. Supply Fan Control: Energize from bonnet temperature independent of burner controls, with adjustable timed off delay and fixed timed on delay, with manual switch for continuous fan operation. Provide continuous low speed fan operation.
2.03 THERMOSTATS
A. Bidder to evaluate existing thermostat to determine compatibility with new furnace.
B. Room Thermostat: Low voltage, electric solid state microcomputer based room thermostat with remote sensor:
1. Preferential rate control to minimize overshoot and deviation from setpoint.
2. Programming based on weekdays, Saturday and Sunday.
3. Thermostat Display:
a. Time of day.
b. Actual room temperature.
c. Programmed temperature.
d. Programmed time.
e. Duration of timed override.
f. Day of week.
g. System Mode Indication: Heating, cooling, fan auto, off, and on, auto or on, off.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that substrates are ready for installation of units and openings are as indicated on shop drawings.
B. Verify that proper power supply is available and located correctly.
C. Verify that proper fuel supply is available for connection.
3.02 INSTALLATION
A. Install in accordance with manufacturer's instructions and requirements of authorities having jurisdiction.
B. Install in accordance with NFPA 90A.
C. Install gas fired furnaces in accordance with NFPA 54.
D. Provide vent connections in accordance with NFPA 211.
END OF SECTION